LAN HVAC Replacement

Closed Solicitation Posted

Solicitation number
FY261222006
Agency
Responses due
Set-aside
Total Small Business

Opportunity facts

Place of performance
El Paso, Texas 79902, United States

Notice details come from SAM.gov. Updated .

About this opportunity

The International Boundary and Water Commission, U.S. Section seeks removal and replacement of an existing HVAC system at its El Paso headquarters, with quotes due May 6, 2026 at 3:00 p.m. MST. This is a 100% Small Business Set Aside; only small businesses may compete.

Place of performance is El Paso, Texas, 4191 N. Mesa Street. The work requires removal of an air-cooled Liebert HVAC system using R-22 refrigerant and installation of a replacement Liebert PDX Air-Cooled System (model PX023UA1A809KM or equivalent) with a remote condensing unit. The new system shall use R-410A refrigerant or an alternative compliant with current regulations, deliver 23 kW cooling capacity with minimum Energy Efficiency Ratio of 10.0, operate at 460V three-phase 60Hz, and maintain an ambient operating range of 65°F to 95°F. The scope includes crane service for removal and installation, refrigeration piping installation, electrical reconnection, system startup and commissioning with operating data documentation, and complete Operation & Maintenance manuals in hard copy and digital format. A motorized damper system must enable switching between the new Liebert unit and the existing Carrier HVAC system. All work shall comply with ASHRAE standards, EPA regulations, and federal energy efficiency requirements.

Minimum warranty is one year parts and labor with a five-year compressor warranty; extended warranty options are encouraged. The NAICS code is 238220 (Plumbing, Heating, and Air-Conditioning Contractors) with SBA size standard of $19 million. PSC code is N041 (Installation of Equipment—Refrigeration, Air Conditioning, and Air Circulating Equipment). Quotes must be submitted as all-or-none for the complete CLIN structure and remain valid for 90 days. Questions are due by 3:00 p.m. MST on May 1. Evaluation uses Lowest Price Technically Acceptable methodology. Award will be made to the responsible small business offeror whose conforming offer provides best value. Offerors must include an active UEI and submit quotes via email to angelica.baca@ibwc.gov.

Notice text

9 versions

Update #9 · Latest ·

This is a combined synopsis/solicitation for commercial items in accordance with the format in FAR Subpart 12.6, as supplemented with additional information included in this notice. This announcement constitutes the only solicitation; quotes are being requested, and a written solicitation will not be issued separately.

The solicitation number is FY261222006. This solicitation is issued as a request for quote (RFQ) for LAN HVAC Replacement at El Paso, HQ, 4191 N. Mesa, El Paso, TX 79902.

This is a 100% Small Business Set Aside. Only offers from Small Businesses will be considered for this solicitation.

The associated North American Industry Classification System (NAICS) code is 238220 – Plumbing, Heating, and Air-Conditioning Contractors. Product of Service Code for this requirement is N041–Installation of Equipment-Refrigeration, Air Conditioning, and Air Circulating Equipment. The Small Business Administration (SBA) size standard for this sector is $19.0 Million.

Services shall be quoted ALL or NONE as per CLIN structure and SOW attached. CLIN structure needs to be returned with your quote via e-mail directly to my attention at angelica.baca@ibwc.gov.

Quotes shall be good for 90 Days.

Offer due date/local time: May 6, 2026; 3:00 pm MST.

Only questions submitted by email to angelica.baca@ibwc.gov will be considered. Questions received from Offerors after 3p on May 1, 2026, may not be responded to.

Active UEI (Unique Entity Identifier) must be included in your offer.

Description: The International Boundary and Water Commission, United States Section (IBWC) requires LAN HVAC Replacement for El Paso HQ, 4191 N. Mesa, El Paso, TX 79902.

COR for this request: Antonio Almaguer (please do not contact him directly if you have any questions). All questions need to be directed to my attention.

Evaluation of Offer – The Government will award a contract resulting from this solicitation to the responsible offeror whose offer conforming to the solicitation will be most advantageous to the Government, price and other factors considered. The following factors shall be used to evaluate Offers: Technical acceptability to meet IBWC requirements; Technical Approach and Past Performance.

The Government will award a contract resulting from this combined synopsis/solicitation to the lowest price technically acceptable (LPTA), responsible offeror.

Technical Approach - Quote must demonstrate the technical approach by providing a narrative addressing all the items in the scope. The narrative shall at a minimum include your plan of action, equipment, key team members, and schedule.

Past Performance – Quotes shall demonstrate successful past performance of at least 3 three (3) references for similar projects. The information shall include name of person, company, phone number, email address, and brief description of the project.

Offerors shall meet or exceed and specifications and scope of work of items being quoted.

Offerors shall include a completed copy of the provision at 52.212-3, Offeror Representations and Certifications-Commercial Items, with its offer. NOTE: The offeror shall complete only paragraph (b) of this provision if the Offeror has completed the annual representations and certification electronically via the System for Award Management (SAM) website accessed at https://www.sam.gov.

END of combined synopsis/solicitation

Attachments:

CLIN Structure

Clauses and Provisions

Scope of Work

Modification 001 - 4/20/26 -  My client will be conducting a single site visit for all interested vendors, which is scheduled for April 24th from 9:00 to 10:00 a.m. Please note that this will be the only site visit available, so I encourage your team to attend during this time. Direct POC: Sebastian Calderon sebastian.calderon@ibwc.gov

Modification 002 - Q&A 4/21/26 -

Is the outdoor condensing unit on top of the roof? Yes

How many stories? 3 stories high and is the model corresponding to the Evaporative unit that we have in the Server room.

Are you using a third party such as Automated Logic for the  BMS Controls integration? The unit is controlled from the built-in console on the evaporative unit in the server room (servicing area) not part of the Building Automation System (BMS). 

Modification 003 - Q&A 4/22/26 - To include Technical Approach and Past Performance on solicitation description.

Modification 004 - Site Visit information 4/26/26:

-The server room is on the second floor accessible by elevator or stairs.

-Elevator capacity is 4000 lbs.; 4X7 ft door, Dimensions: 4ft W, 6.5ft L, 7.3ft H.

-Evaporator Unit in Server room with 3ft door access to hallway.

-Condenser on 3rd Floor Roof with Crane access only from SW corner of Bldg.

Modification 005 - Add Q&As below and attached Site visit sign in sheet - 4/28/26

  1. The Performance Specification lists the Liebert PX023UA1A809KM PDX Air-Cooled System as a 23-ton machine. However, according to the manufacturer, this model is a 23kW unit, which is approximately 6.5 tons. Could you please confirm if the requirement is for a 23-ton or a 6.5-ton machine?                                                                                    The reference to a “23‑ton” system in the Statement of Work was a clerical error. The correct requirement is 23 kW. All proposed equipment must meet the performance, environmental, and operational criteria associated with a 23 kW cooling system. This correction supersedes any earlier references in the SOW.                                                                                                                                                                                                                                                           2.    Does the client require the Liebert brand specifically, or may we propose an equivalent alternative?                   The agency does not require the Liebert brand specifically. Equivalent alternatives are acceptable; however, all proposed substitutes must:
    1. Meet or exceed all technical specifications outlined in the SOW,
    2. Demonstrate full compatibility with existing infrastructure,
    3. Include supporting documentation verifying equivalency, and
    4. Be submitted for agency technical review.                                                                                                  Please ensure that any proposed equipment aligns with the agency’s operational needs and long‑term support considerations.                                                                                                                                                                                                                                                                                                        3. The SOW in section 4. Performance Specification a “23 tons” HVAC unit but the Liebert PX023uA1A809KM model is rated at 23 kW (~6.5 tons). Please clarify are you expecting a 23 ton unit?   The reference to a “23‑ton” system in the Statement of Work was a clerical error. The correct requirement is 23 kW. All proposed equipment must meet the performance, environmental, and operational criteria associated with a 23 kW cooling system. This correction supersedes any earlier references in the SOW.                                                                                                                                4. Could you confirm the location of the electrical panel that feeds the indoor and outdoor Liebert units? The bid documents note reconnecting the new equipment to the existing electrical infrastructure, but I do not recall seeing the associated panel during the walk.                                                                            The 4x4 junction box next to the Liebert unit is labeled with “Panel H1, Circuit 20,22,24 480volts” the Breaker panel H1 is in 1st floor supply room, close to West exit door.  I do not have information on brakers to Condenser unit on the roof.
    5. The line sets specified for the new unit are the same size as the existing ones. Can you confirm whether the current lines can be reused? We understand they would still need to be properly flushed and cleaned. If replacement is required, could you provide approximate lengths from the indoor unit to the outdoor unit?                                                                                                                                                                Line sets are currently operational and in use                                                                                                                                                                                                                                                        Modification 006 - Update SOW attachment - 4/29/26                                                                                                                                                                                                                                    Modification 007 - 5/1/26 - Q&As below:                                                                                                  
    6. -Line set is currently operational and in use. Line set is currently operational and in use.

      -The server room is on the second floor accessible by elevator or stairs. The server room is on the second floor accessible by elevator or stairs.

      -Elevator capacity is 4000 lbs.; 4X7 ft door, Dimensions: 4ft W, 6.5ft L, 7.3ft H. Elevator capacity is 4000 lbs.; 4X7 ft door, Dimensions: 4ft W, 6.5ft L, 7.3ft H.

      -Evaporator Unit in Server room with 3ft door access to hallway. Evaporator Unit in Server room with 3ft door access to hallway.

      -Condenser on 3rd Floor Roof with Crane access only from SW corner of Bldg. Condenser on 3rd Floor Roof with Crane access only from SW corner of Bldg                                                                              The line sets specified for the new unit are the same size as the existing ones. Can you confirm whether the current lines can be reused? We understand they would still need to be properly flushed and cleaned. If replacement is required, could you provide approximate lengths from the indoor unit to the outdoor unit?                                                                                                                                                                Line sets are currently operational and in use                                                                                                                                                                                                                                                          Modification 008 - 5/2/26 - Q&As below:                                                                                                  

    7. Please confirm the required electrical capacity for the new Liebert unit (MCA and MOCP).
    8. Based on site observations, the existing wiring appears to be sized for approximately 60 amps (#6 conductors with 3/4" conduit).
    9. Please confirm if the existing electrical infrastructure is adequate, or if new feeders, conduit, or breaker upgrades will be required.                                                                                                                              The Unit is connected to a Triple 50A Breaker and is supplying 480 volts.  Wires and ¾ inch conduit were installed when we moved into this building somewhere around 2018/9.                                                                                                                                                                                                                                                                                                                                                                                                                                                                            
Update #8 ·

This is a combined synopsis/solicitation for commercial items in accordance with the format in FAR Subpart 12.6, as supplemented with additional information included in this notice. This announcement constitutes the only solicitation; quotes are being requested, and a written solicitation will not be issued separately.

The solicitation number is FY261222006. This solicitation is issued as a request for quote (RFQ) for LAN HVAC Replacement at El Paso, HQ, 4191 N. Mesa, El Paso, TX 79902.

This is a 100% Small Business Set Aside. Only offers from Small Businesses will be considered for this solicitation.

The associated North American Industry Classification System (NAICS) code is 238220 – Plumbing, Heating, and Air-Conditioning Contractors. Product of Service Code for this requirement is N041–Installation of Equipment-Refrigeration, Air Conditioning, and Air Circulating Equipment. The Small Business Administration (SBA) size standard for this sector is $19.0 Million.

Services shall be quoted ALL or NONE as per CLIN structure and SOW attached. CLIN structure needs to be returned with your quote via e-mail directly to my attention at angelica.baca@ibwc.gov.

Quotes shall be good for 90 Days.

Offer due date/local time: May 6, 2026; 3:00 pm MST.

Only questions submitted by email to angelica.baca@ibwc.gov will be considered. Questions received from Offerors after 3p on May 1, 2026, may not be responded to.

Active UEI (Unique Entity Identifier) must be included in your offer.

Description: The International Boundary and Water Commission, United States Section (IBWC) requires LAN HVAC Replacement for El Paso HQ, 4191 N. Mesa, El Paso, TX 79902.

COR for this request: Antonio Almaguer (please do not contact him directly if you have any questions). All questions need to be directed to my attention.

Evaluation of Offer – The Government will award a contract resulting from this solicitation to the responsible offeror whose offer conforming to the solicitation will be most advantageous to the Government, price and other factors considered. The following factors shall be used to evaluate Offers: Technical acceptability to meet IBWC requirements; Technical Approach and Past Performance.

The Government will award a contract resulting from this combined synopsis/solicitation to the lowest price technically acceptable (LPTA), responsible offeror.

Technical Approach - Quote must demonstrate the technical approach by providing a narrative addressing all the items in the scope. The narrative shall at a minimum include your plan of action, equipment, key team members, and schedule.

Past Performance – Quotes shall demonstrate successful past performance of at least 3 three (3) references for similar projects. The information shall include name of person, company, phone number, email address, and brief description of the project.

Offerors shall meet or exceed and specifications and scope of work of items being quoted.

Offerors shall include a completed copy of the provision at 52.212-3, Offeror Representations and Certifications-Commercial Items, with its offer. NOTE: The offeror shall complete only paragraph (b) of this provision if the Offeror has completed the annual representations and certification electronically via the System for Award Management (SAM) website accessed at https://www.sam.gov.

END of combined synopsis/solicitation

Attachments:

CLIN Structure

Clauses and Provisions

Scope of Work

Modification 001 - 4/20/26 -  My client will be conducting a single site visit for all interested vendors, which is scheduled for April 24th from 9:00 to 10:00 a.m. Please note that this will be the only site visit available, so I encourage your team to attend during this time. Direct POC: Sebastian Calderon sebastian.calderon@ibwc.gov

Modification 002 - Q&A 4/21/26 -

Is the outdoor condensing unit on top of the roof? Yes

How many stories? 3 stories high and is the model corresponding to the Evaporative unit that we have in the Server room.

Are you using a third party such as Automated Logic for the  BMS Controls integration? The unit is controlled from the built-in console on the evaporative unit in the server room (servicing area) not part of the Building Automation System (BMS). 

Modification 003 - Q&A 4/22/26 - To include Technical Approach and Past Performance on solicitation description.

Modification 004 - Site Visit information 4/26/26:

-The server room is on the second floor accessible by elevator or stairs.

-Elevator capacity is 4000 lbs.; 4X7 ft door, Dimensions: 4ft W, 6.5ft L, 7.3ft H.

-Evaporator Unit in Server room with 3ft door access to hallway.

-Condenser on 3rd Floor Roof with Crane access only from SW corner of Bldg.

Modification 005 - Add Q&As below and attached Site visit sign in sheet - 4/28/26

  1. The Performance Specification lists the Liebert PX023UA1A809KM PDX Air-Cooled System as a 23-ton machine. However, according to the manufacturer, this model is a 23kW unit, which is approximately 6.5 tons. Could you please confirm if the requirement is for a 23-ton or a 6.5-ton machine?                                                                                    The reference to a “23‑ton” system in the Statement of Work was a clerical error. The correct requirement is 23 kW. All proposed equipment must meet the performance, environmental, and operational criteria associated with a 23 kW cooling system. This correction supersedes any earlier references in the SOW.                                                                                                                                                                                                                                                           2.    Does the client require the Liebert brand specifically, or may we propose an equivalent alternative?                   The agency does not require the Liebert brand specifically. Equivalent alternatives are acceptable; however, all proposed substitutes must:
    1. Meet or exceed all technical specifications outlined in the SOW,
    2. Demonstrate full compatibility with existing infrastructure,
    3. Include supporting documentation verifying equivalency, and
    4. Be submitted for agency technical review.                                                                                                  Please ensure that any proposed equipment aligns with the agency’s operational needs and long‑term support considerations.                                                                                                                                                                                                                                                                                                        3. The SOW in section 4. Performance Specification a “23 tons” HVAC unit but the Liebert PX023uA1A809KM model is rated at 23 kW (~6.5 tons). Please clarify are you expecting a 23 ton unit?   The reference to a “23‑ton” system in the Statement of Work was a clerical error. The correct requirement is 23 kW. All proposed equipment must meet the performance, environmental, and operational criteria associated with a 23 kW cooling system. This correction supersedes any earlier references in the SOW.                                                                                                                                4. Could you confirm the location of the electrical panel that feeds the indoor and outdoor Liebert units? The bid documents note reconnecting the new equipment to the existing electrical infrastructure, but I do not recall seeing the associated panel during the walk.                                                                            The 4x4 junction box next to the Liebert unit is labeled with “Panel H1, Circuit 20,22,24 480volts” the Breaker panel H1 is in 1st floor supply room, close to West exit door.  I do not have information on brakers to Condenser unit on the roof.
    5. The line sets specified for the new unit are the same size as the existing ones. Can you confirm whether the current lines can be reused? We understand they would still need to be properly flushed and cleaned. If replacement is required, could you provide approximate lengths from the indoor unit to the outdoor unit?                                                                                                                                                                Line sets are currently operational and in use                                                                                                                                                                                                                                                        Modification 006 - Update SOW attachment - 4/29/26                                                                              Modification 007 - 5/1/26 - Q&As below:                                                                                                  

      -Line set is currently operational and in use. Line set is currently operational and in use.

      -The server room is on the second floor accessible by elevator or stairs. The server room is on the second floor accessible by elevator or stairs.

      -Elevator capacity is 4000 lbs.; 4X7 ft door, Dimensions: 4ft W, 6.5ft L, 7.3ft H. Elevator capacity is 4000 lbs.; 4X7 ft door, Dimensions: 4ft W, 6.5ft L, 7.3ft H.

      -Evaporator Unit in Server room with 3ft door access to hallway. Evaporator Unit in Server room with 3ft door access to hallway.

      -Condenser on 3rd Floor Roof with Crane access only from SW corner of Bldg. Condenser on 3rd Floor Roof with Crane access only from SW corner of Bldg.

                                                                                                                                                                          
Update #7 ·

This is a combined synopsis/solicitation for commercial items in accordance with the format in FAR Subpart 12.6, as supplemented with additional information included in this notice. This announcement constitutes the only solicitation; quotes are being requested, and a written solicitation will not be issued separately.

The solicitation number is FY261222006. This solicitation is issued as a request for quote (RFQ) for LAN HVAC Replacement at El Paso, HQ, 4191 N. Mesa, El Paso, TX 79902.

This is a 100% Small Business Set Aside. Only offers from Small Businesses will be considered for this solicitation.

The associated North American Industry Classification System (NAICS) code is 238220 – Plumbing, Heating, and Air-Conditioning Contractors. Product of Service Code for this requirement is N041–Installation of Equipment-Refrigeration, Air Conditioning, and Air Circulating Equipment. The Small Business Administration (SBA) size standard for this sector is $19.0 Million.

Services shall be quoted ALL or NONE as per CLIN structure and SOW attached. CLIN structure needs to be returned with your quote via e-mail directly to my attention at angelica.baca@ibwc.gov.

Quotes shall be good for 90 Days.

Offer due date/local time: May 6, 2026; 3:00 pm MST.

Only questions submitted by email to angelica.baca@ibwc.gov will be considered. Questions received from Offerors after 3p on May 1, 2026, may not be responded to.

Active UEI (Unique Entity Identifier) must be included in your offer.

Description: The International Boundary and Water Commission, United States Section (IBWC) requires LAN HVAC Replacement for El Paso HQ, 4191 N. Mesa, El Paso, TX 79902.

COR for this request: Antonio Almaguer (please do not contact him directly if you have any questions). All questions need to be directed to my attention.

Evaluation of Offer – The Government will award a contract resulting from this solicitation to the responsible offeror whose offer conforming to the solicitation will be most advantageous to the Government, price and other factors considered. The following factors shall be used to evaluate Offers: Technical acceptability to meet IBWC requirements; Technical Approach and Past Performance.

The Government will award a contract resulting from this combined synopsis/solicitation to the lowest price technically acceptable (LPTA), responsible offeror.

Technical Approach - Quote must demonstrate the technical approach by providing a narrative addressing all the items in the scope. The narrative shall at a minimum include your plan of action, equipment, key team members, and schedule.

Past Performance – Quotes shall demonstrate successful past performance of at least 3 three (3) references for similar projects. The information shall include name of person, company, phone number, email address, and brief description of the project.

Offerors shall meet or exceed and specifications and scope of work of items being quoted.

Offerors shall include a completed copy of the provision at 52.212-3, Offeror Representations and Certifications-Commercial Items, with its offer. NOTE: The offeror shall complete only paragraph (b) of this provision if the Offeror has completed the annual representations and certification electronically via the System for Award Management (SAM) website accessed at https://www.sam.gov.

END of combined synopsis/solicitation

Attachments:

CLIN Structure

Clauses and Provisions

Scope of Work

Modification 001 - 4/20/26 -  My client will be conducting a single site visit for all interested vendors, which is scheduled for April 24th from 9:00 to 10:00 a.m. Please note that this will be the only site visit available, so I encourage your team to attend during this time. Direct POC: Sebastian Calderon sebastian.calderon@ibwc.gov

Modification 002 - Q&A 4/21/26 -

Is the outdoor condensing unit on top of the roof? Yes

How many stories? 3 stories high and is the model corresponding to the Evaporative unit that we have in the Server room.

Are you using a third party such as Automated Logic for the  BMS Controls integration? The unit is controlled from the built-in console on the evaporative unit in the server room (servicing area) not part of the Building Automation System (BMS). 

Modification 003 - Q&A 4/22/26 - To include Technical Approach and Past Performance on solicitation description.

Modification 004 - Site Visit information 4/26/26:

-The server room is on the second floor accessible by elevator or stairs.

-Elevator capacity is 4000 lbs.; 4X7 ft door, Dimensions: 4ft W, 6.5ft L, 7.3ft H.

-Evaporator Unit in Server room with 3ft door access to hallway.

-Condenser on 3rd Floor Roof with Crane access only from SW corner of Bldg.

Modification 005 - Add Q&As below and attached Site visit sign in sheet - 4/28/26

  1. The Performance Specification lists the Liebert PX023UA1A809KM PDX Air-Cooled System as a 23-ton machine. However, according to the manufacturer, this model is a 23kW unit, which is approximately 6.5 tons. Could you please confirm if the requirement is for a 23-ton or a 6.5-ton machine?                                                                                    The reference to a “23‑ton” system in the Statement of Work was a clerical error. The correct requirement is 23 kW. All proposed equipment must meet the performance, environmental, and operational criteria associated with a 23 kW cooling system. This correction supersedes any earlier references in the SOW.                                                                                                                                                                                                                                                           2.    Does the client require the Liebert brand specifically, or may we propose an equivalent alternative?                   The agency does not require the Liebert brand specifically. Equivalent alternatives are acceptable; however, all proposed substitutes must:
    1. Meet or exceed all technical specifications outlined in the SOW,
    2. Demonstrate full compatibility with existing infrastructure,
    3. Include supporting documentation verifying equivalency, and
    4. Be submitted for agency technical review.                                                                                                  Please ensure that any proposed equipment aligns with the agency’s operational needs and long‑term support considerations.                                                                                                                                                                                                                                                                                                        3. The SOW in section 4. Performance Specification a “23 tons” HVAC unit but the Liebert PX023uA1A809KM model is rated at 23 kW (~6.5 tons). Please clarify are you expecting a 23 ton unit?   The reference to a “23‑ton” system in the Statement of Work was a clerical error. The correct requirement is 23 kW. All proposed equipment must meet the performance, environmental, and operational criteria associated with a 23 kW cooling system. This correction supersedes any earlier references in the SOW.                                                                                                                                4. Could you confirm the location of the electrical panel that feeds the indoor and outdoor Liebert units? The bid documents note reconnecting the new equipment to the existing electrical infrastructure, but I do not recall seeing the associated panel during the walk.                                                                            The 4x4 junction box next to the Liebert unit is labeled with “Panel H1, Circuit 20,22,24 480volts” the Breaker panel H1 is in 1st floor supply room, close to West exit door.  I do not have information on brakers to Condenser unit on the roof.
    5. The line sets specified for the new unit are the same size as the existing ones. Can you confirm whether the current lines can be reused? We understand they would still need to be properly flushed and cleaned. If replacement is required, could you provide approximate lengths from the indoor unit to the outdoor unit?                                                                                                                                                                Line sets are currently operational and in use                                                                                                                                                                                                                                                        Modification 006 - Update SOW attachment - 4/29/26                                                                                                                                                                              
Update #6 ·

This is a combined synopsis/solicitation for commercial items in accordance with the format in FAR Subpart 12.6, as supplemented with additional information included in this notice. This announcement constitutes the only solicitation; quotes are being requested, and a written solicitation will not be issued separately.

The solicitation number is FY261222006. This solicitation is issued as a request for quote (RFQ) for LAN HVAC Replacement at El Paso, HQ, 4191 N. Mesa, El Paso, TX 79902.

This is a 100% Small Business Set Aside. Only offers from Small Businesses will be considered for this solicitation.

The associated North American Industry Classification System (NAICS) code is 238220 – Plumbing, Heating, and Air-Conditioning Contractors. Product of Service Code for this requirement is N041–Installation of Equipment-Refrigeration, Air Conditioning, and Air Circulating Equipment. The Small Business Administration (SBA) size standard for this sector is $19.0 Million.

Services shall be quoted ALL or NONE as per CLIN structure and SOW attached. CLIN structure needs to be returned with your quote via e-mail directly to my attention at angelica.baca@ibwc.gov.

Quotes shall be good for 90 Days.

Offer due date/local time: May 6, 2026; 3:00 pm MST.

Only questions submitted by email to angelica.baca@ibwc.gov will be considered. Questions received from Offerors after 3p on May 1, 2026, may not be responded to.

Active UEI (Unique Entity Identifier) must be included in your offer.

Description: The International Boundary and Water Commission, United States Section (IBWC) requires LAN HVAC Replacement for El Paso HQ, 4191 N. Mesa, El Paso, TX 79902.

COR for this request: Antonio Almaguer (please do not contact him directly if you have any questions). All questions need to be directed to my attention.

Evaluation of Offer – The Government will award a contract resulting from this solicitation to the responsible offeror whose offer conforming to the solicitation will be most advantageous to the Government, price and other factors considered. The following factors shall be used to evaluate Offers: Technical acceptability to meet IBWC requirements; Technical Approach and Past Performance.

The Government will award a contract resulting from this combined synopsis/solicitation to the lowest price technically acceptable (LPTA), responsible offeror.

Technical Approach - Quote must demonstrate the technical approach by providing a narrative addressing all the items in the scope. The narrative shall at a minimum include your plan of action, equipment, key team members, and schedule.

Past Performance – Quotes shall demonstrate successful past performance of at least 3 three (3) references for similar projects. The information shall include name of person, company, phone number, email address, and brief description of the project.

Offerors shall meet or exceed and specifications and scope of work of items being quoted.

Offerors shall include a completed copy of the provision at 52.212-3, Offeror Representations and Certifications-Commercial Items, with its offer. NOTE: The offeror shall complete only paragraph (b) of this provision if the Offeror has completed the annual representations and certification electronically via the System for Award Management (SAM) website accessed at https://www.sam.gov.

END of combined synopsis/solicitation

Attachments:

CLIN Structure

Clauses and Provisions

Scope of Work

Modification 001 - 4/20/26 -  My client will be conducting a single site visit for all interested vendors, which is scheduled for April 24th from 9:00 to 10:00 a.m. Please note that this will be the only site visit available, so I encourage your team to attend during this time. Direct POC: Sebastian Calderon sebastian.calderon@ibwc.gov

Modification 002 - Q&A 4/21/26 -

Is the outdoor condensing unit on top of the roof? Yes

How many stories? 3 stories high and is the model corresponding to the Evaporative unit that we have in the Server room.

Are you using a third party such as Automated Logic for the  BMS Controls integration? The unit is controlled from the built-in console on the evaporative unit in the server room (servicing area) not part of the Building Automation System (BMS). 

Modification 003 - Q&A 4/22/26 - To include Technical Approach and Past Performance on solicitation description.

Modification 004 - Site Visit information 4/26/26:

-The server room is on the second floor accessible by elevator or stairs.

-Elevator capacity is 4000 lbs.; 4X7 ft door, Dimensions: 4ft W, 6.5ft L, 7.3ft H.

-Evaporator Unit in Server room with 3ft door access to hallway.

-Condenser on 3rd Floor Roof with Crane access only from SW corner of Bldg.

Modification 005 - Add Q&As below and attached Site visit sign in sheet - 4/28/26

  1. The Performance Specification lists the Liebert PX023UA1A809KM PDX Air-Cooled System as a 23-ton machine. However, according to the manufacturer, this model is a 23kW unit, which is approximately 6.5 tons. Could you please confirm if the requirement is for a 23-ton or a 6.5-ton machine?                                                                                    The reference to a “23‑ton” system in the Statement of Work was a clerical error. The correct requirement is 23 kW. All proposed equipment must meet the performance, environmental, and operational criteria associated with a 23 kW cooling system. This correction supersedes any earlier references in the SOW.                                                                                                                                                                                                                                                           2.    Does the client require the Liebert brand specifically, or may we propose an equivalent alternative?                   The agency does not require the Liebert brand specifically. Equivalent alternatives are acceptable; however, all proposed substitutes must:
    1. Meet or exceed all technical specifications outlined in the SOW,
    2. Demonstrate full compatibility with existing infrastructure,
    3. Include supporting documentation verifying equivalency, and
    4. Be submitted for agency technical review.                                                                                                  Please ensure that any proposed equipment aligns with the agency’s operational needs and long‑term support considerations.                                                                                                                                                                                                                                                                                                        3. The SOW in section 4. Performance Specification a “23 tons” HVAC unit but the Liebert PX023uA1A809KM model is rated at 23 kW (~6.5 tons). Please clarify are you expecting a 23 ton unit?   The reference to a “23‑ton” system in the Statement of Work was a clerical error. The correct requirement is 23 kW. All proposed equipment must meet the performance, environmental, and operational criteria associated with a 23 kW cooling system. This correction supersedes any earlier references in the SOW.                                                                                                                                4. Could you confirm the location of the electrical panel that feeds the indoor and outdoor Liebert units? The bid documents note reconnecting the new equipment to the existing electrical infrastructure, but I do not recall seeing the associated panel during the walk.                                                                            The 4x4 junction box next to the Liebert unit is labeled with “Panel H1, Circuit 20,22,24 480volts” the Breaker panel H1 is in 1st floor supply room, close to West exit door.  I do not have information on brakers to Condenser unit on the roof.
    5. The line sets specified for the new unit are the same size as the existing ones. Can you confirm whether the current lines can be reused? We understand they would still need to be properly flushed and cleaned. If replacement is required, could you provide approximate lengths from the indoor unit to the outdoor unit?                                                                                                                                                                Line sets are currently operational and in use                                                                                                                                                                                      
Update #5 ·

This is a combined synopsis/solicitation for commercial items in accordance with the format in FAR Subpart 12.6, as supplemented with additional information included in this notice. This announcement constitutes the only solicitation; quotes are being requested, and a written solicitation will not be issued separately.

The solicitation number is FY261222006. This solicitation is issued as a request for quote (RFQ) for LAN HVAC Replacement at El Paso, HQ, 4191 N. Mesa, El Paso, TX 79902.

This is a 100% Small Business Set Aside. Only offers from Small Businesses will be considered for this solicitation.

The associated North American Industry Classification System (NAICS) code is 238220 – Plumbing, Heating, and Air-Conditioning Contractors. Product of Service Code for this requirement is N041–Installation of Equipment-Refrigeration, Air Conditioning, and Air Circulating Equipment. The Small Business Administration (SBA) size standard for this sector is $19.0 Million.

Services shall be quoted ALL or NONE as per CLIN structure and SOW attached. CLIN structure needs to be returned with your quote via e-mail directly to my attention at angelica.baca@ibwc.gov.

Quotes shall be good for 90 Days.

Offer due date/local time: May 6, 2026; 3:00 pm MST.

Only questions submitted by email to angelica.baca@ibwc.gov will be considered. Questions received from Offerors after 3p on May 1, 2026, may not be responded to.

Active UEI (Unique Entity Identifier) must be included in your offer.

Description: The International Boundary and Water Commission, United States Section (IBWC) requires LAN HVAC Replacement for El Paso HQ, 4191 N. Mesa, El Paso, TX 79902.

COR for this request: Antonio Almaguer (please do not contact him directly if you have any questions). All questions need to be directed to my attention.

Evaluation of Offer – The Government will award a contract resulting from this solicitation to the responsible offeror whose offer conforming to the solicitation will be most advantageous to the Government, price and other factors considered. The following factors shall be used to evaluate Offers: Technical acceptability to meet IBWC requirements; Technical Approach and Past Performance.

The Government will award a contract resulting from this combined synopsis/solicitation to the lowest price technically acceptable (LPTA), responsible offeror.

Technical Approach - Quote must demonstrate the technical approach by providing a narrative addressing all the items in the scope. The narrative shall at a minimum include your plan of action, equipment, key team members, and schedule.

Past Performance – Quotes shall demonstrate successful past performance of at least 3 three (3) references for similar projects. The information shall include name of person, company, phone number, email address, and brief description of the project.

Offerors shall meet or exceed and specifications and scope of work of items being quoted.

Offerors shall include a completed copy of the provision at 52.212-3, Offeror Representations and Certifications-Commercial Items, with its offer. NOTE: The offeror shall complete only paragraph (b) of this provision if the Offeror has completed the annual representations and certification electronically via the System for Award Management (SAM) website accessed at https://www.sam.gov.

END of combined synopsis/solicitation

Attachments:

CLIN Structure

Clauses and Provisions

Scope of Work

Modification 001 - 4/20/26 -  My client will be conducting a single site visit for all interested vendors, which is scheduled for April 24th from 9:00 to 10:00 a.m. Please note that this will be the only site visit available, so I encourage your team to attend during this time. Direct POC: Sebastian Calderon sebastian.calderon@ibwc.gov

Modification 002 - Q&A 4/21/26 -

Is the outdoor condensing unit on top of the roof? Yes

How many stories? 3 stories high and is the model corresponding to the Evaporative unit that we have in the Server room.

Are you using a third party such as Automated Logic for the  BMS Controls integration? The unit is controlled from the built-in console on the evaporative unit in the server room (servicing area) not part of the Building Automation System (BMS). 

Modification 003 - Q&A 4/22/26 - To include Technical Approach and Past Performance on solicitation description.

Modification 004 - Site Visit information 4/26/26:

-The server room is on the second floor accessible by elevator or stairs.

-Elevator capacity is 4000 lbs.; 4X7 ft door, Dimensions: 4ft W, 6.5ft L, 7.3ft H.

-Evaporator Unit in Server room with 3ft door access to hallway.

-Condenser on 3rd Floor Roof with Crane access only from SW corner of Bldg.

Update #4 ·

This is a combined synopsis/solicitation for commercial items in accordance with the format in FAR Subpart 12.6, as supplemented with additional information included in this notice. This announcement constitutes the only solicitation; quotes are being requested, and a written solicitation will not be issued separately.

The solicitation number is FY261222006. This solicitation is issued as a request for quote (RFQ) for LAN HVAC Replacement at El Paso, HQ, 4191 N. Mesa, El Paso, TX 79902.

This is a 100% Small Business Set Aside. Only offers from Small Businesses will be considered for this solicitation.

The associated North American Industry Classification System (NAICS) code is 238220 – Plumbing, Heating, and Air-Conditioning Contractors. Product of Service Code for this requirement is N041–Installation of Equipment-Refrigeration, Air Conditioning, and Air Circulating Equipment. The Small Business Administration (SBA) size standard for this sector is $19.0 Million.

Services shall be quoted ALL or NONE as per CLIN structure and SOW attached. CLIN structure needs to be returned with your quote via e-mail directly to my attention at angelica.baca@ibwc.gov.

Quotes shall be good for 90 Days.

Offer due date/local time: May 6, 2026; 3:00 pm MST.

Only questions submitted by email to angelica.baca@ibwc.gov will be considered. Questions received from Offerors after 3p on May 1, 2026, may not be responded to.

Active UEI (Unique Entity Identifier) must be included in your offer.

Description: The International Boundary and Water Commission, United States Section (IBWC) requires LAN HVAC Replacement for El Paso HQ, 4191 N. Mesa, El Paso, TX 79902.

COR for this request: Antonio Almaguer (please do not contact him directly if you have any questions). All questions need to be directed to my attention.

Evaluation of Offer – The Government will award a contract resulting from this solicitation to the responsible offeror whose offer conforming to the solicitation will be most advantageous to the Government, price and other factors considered. The following factors shall be used to evaluate Offers: Technical acceptability to meet IBWC requirements; Technical Approach and Past Performance.

The Government will award a contract resulting from this combined synopsis/solicitation to the lowest price technically acceptable (LPTA), responsible offeror.

Technical Approach - Quote must demonstrate the technical approach by providing a narrative addressing all the items in the scope. The narrative shall at a minimum include your plan of action, equipment, key team members, and schedule.

Past Performance – Quotes shall demonstrate successful past performance of at least 3 three (3) references for similar projects. The information shall include name of person, company, phone number, email address, and brief description of the project.

Offerors shall meet or exceed and specifications and scope of work of items being quoted.

Offerors shall include a completed copy of the provision at 52.212-3, Offeror Representations and Certifications-Commercial Items, with its offer. NOTE: The offeror shall complete only paragraph (b) of this provision if the Offeror has completed the annual representations and certification electronically via the System for Award Management (SAM) website accessed at https://www.sam.gov.

END of combined synopsis/solicitation

Attachments:

CLIN Structure

Clauses and Provisions

Scope of Work

Modification 4/20/26 -  My client will be conducting a single site visit for all interested vendors, which is scheduled for April 24th from 9:00 to 10:00 a.m. Please note that this will be the only site visit available, so I encourage your team to attend during this time. Direct POC: Sebastian Calderon sebastian.calderon@ibwc.gov

Modification Q&A 4/21/26 -

Is the outdoor condensing unit on top of the roof? Yes

How many stories? 3 stories high and is the model corresponding to the Evaporative unit that we have in the Server room.

Are you using a third party such as Automated Logic for the  BMS Controls integration? The unit is controlled from the built-in console on the evaporative unit in the server room (servicing area) not part of the Building Automation System (BMS). 

Modification Q&A 4/22/26 - To include Technical Approach and Past Performance on solicitation description.

Update #3 ·

This is a combined synopsis/solicitation for commercial items in accordance with the format in FAR Subpart 12.6, as supplemented with additional information included in this notice. This announcement constitutes the only solicitation; quotes are being requested, and a written solicitation will not be issued separately.

The solicitation number is FY261222006. This solicitation is issued as a request for quote (RFQ) for LAN HVAC Replacement at El Paso, HQ, 4191 N. Mesa, El Paso, TX 79902.

This is a 100% Small Business Set Aside. Only offers from Small Businesses will be considered for this solicitation.

The associated North American Industry Classification System (NAICS) code is 238220 – Plumbing, Heating, and Air-Conditioning Contractors. Product of Service Code for this requirement is N041–Installation of Equipment-Refrigeration, Air Conditioning, and Air Circulating Equipment. The Small Business Administration (SBA) size standard for this sector is $19.0 Million.

Services shall be quoted ALL or NONE as per CLIN structure and SOW attached. CLIN structure needs to be returned with your quote via e-mail directly to my attention at angelica.baca@ibwc.gov.

Quotes shall be good for 90 Days.

Offer due date/local time: May 6, 2026; 3:00 pm MST.

Only questions submitted by email to angelica.baca@ibwc.gov will be considered. Questions received from Offerors after 3p on May 1, 2026, may not be responded to.

Active UEI (Unique Entity Identifier) must be included in your offer.

Description: The International Boundary and Water Commission, United States Section (IBWC) requires LAN HVAC Replacement for El Paso HQ, 4191 N. Mesa, El Paso, TX 79902.

COR for this request: Antonio Almaguer (please do not contact him directly if you have any questions). All questions need to be directed to my attention.

Evaluation of Offer – The Government will award a contract resulting from this solicitation to the responsible offeror whose offer conforming to the solicitation will be most advantageous to the Government, price and other factors considered. The following factors shall be used to evaluate Offers: Technical acceptability to meet IBWC requirements; Technical Approach and Past Performance.

The Government will award a contract resulting from this combined synopsis/solicitation to the lowest price technically acceptable (LPTA), responsible offeror.

Offerors shall include a completed copy of the provision at 52.212-3, Offeror Representations and Certifications-Commercial Items, with its offer. NOTE: The offeror shall complete only paragraph (b) of this provision if the Offeror has completed the annual representations and certification electronically via the System for Award Management (SAM) website accessed at https://www.sam.gov.

END of combined synopsis/solicitation

Attachments:

CLIN Structure

Clauses and Provisions

Scope of Work

Modification 4/20/26 -  My client will be conducting a single site visit for all interested vendors, which is scheduled for April 24th from 9:00 to 10:00 a.m. Please note that this will be the only site visit available, so I encourage your team to attend during this time. Direct POC: Sebastian Calderon sebastian.calderon@ibwc.gov

Modification Q&A 4/21/26 -

Is the outdoor condensing unit on top of the roof? Yes

How many stories? 3 stories high and is the model corresponding to the Evaporative unit that we have in the Server room.

Are you using a third party such as Automated Logic for the  BMS Controls integration? The unit is controlled from the built-in console on the evaporative unit in the server room (servicing area) not part of the Building Automation System (BMS). 

Update #2 ·

This is a combined synopsis/solicitation for commercial items in accordance with the format in FAR Subpart 12.6, as supplemented with additional information included in this notice. This announcement constitutes the only solicitation; quotes are being requested, and a written solicitation will not be issued separately.

The solicitation number is FY261222006. This solicitation is issued as a request for quote (RFQ) for LAN HVAC Replacement at El Paso, HQ, 4191 N. Mesa, El Paso, TX 79902.

This is a 100% Small Business Set Aside. Only offers from Small Businesses will be considered for this solicitation.

The associated North American Industry Classification System (NAICS) code is 238220 – Plumbing, Heating, and Air-Conditioning Contractors. Product of Service Code for this requirement is N041–Installation of Equipment-Refrigeration, Air Conditioning, and Air Circulating Equipment. The Small Business Administration (SBA) size standard for this sector is $19.0 Million.

Services shall be quoted ALL or NONE as per CLIN structure and SOW attached. CLIN structure needs to be returned with your quote via e-mail directly to my attention at angelica.baca@ibwc.gov.

Quotes shall be good for 90 Days.

Offer due date/local time: May 6, 2026; 3:00 pm MST.

Only questions submitted by email to angelica.baca@ibwc.gov will be considered. Questions received from Offerors after 3p on May 1, 2026, may not be responded to.

Active UEI (Unique Entity Identifier) must be included in your offer.

Description: The International Boundary and Water Commission, United States Section (IBWC) requires LAN HVAC Replacement for El Paso HQ, 4191 N. Mesa, El Paso, TX 79902.

COR for this request: Antonio Almaguer (please do not contact him directly if you have any questions). All questions need to be directed to my attention.

Evaluation of Offer – The Government will award a contract resulting from this solicitation to the responsible offeror whose offer conforming to the solicitation will be most advantageous to the Government, price and other factors considered. The following factors shall be used to evaluate Offers: Technical acceptability to meet IBWC requirements; Technical Approach and Past Performance.

The Government will award a contract resulting from this combined synopsis/solicitation to the lowest price technically acceptable (LPTA), responsible offeror.

Offerors shall include a completed copy of the provision at 52.212-3, Offeror Representations and Certifications-Commercial Items, with its offer. NOTE: The offeror shall complete only paragraph (b) of this provision if the Offeror has completed the annual representations and certification electronically via the System for Award Management (SAM) website accessed at https://www.sam.gov.

END of combined synopsis/solicitation

Attachments:

CLIN Structure

Clauses and Provisions

Scope of Work

Modification 4/20/26 -  My client will be conducting a single site visit for all interested vendors, which is scheduled for April 24th from 9:00 to 10:00 a.m. Please note that this will be the only site visit available, so I encourage your team to attend during this time. Direct POC: Sebastian Calderon sebastian.calderon@ibwc.gov

Update #1 ·

This is a combined synopsis/solicitation for commercial items in accordance with the format in FAR Subpart 12.6, as supplemented with additional information included in this notice. This announcement constitutes the only solicitation; quotes are being requested, and a written solicitation will not be issued separately.

The solicitation number is FY261222006. This solicitation is issued as a request for quote (RFQ) for LAN HVAC Replacement at El Paso, HQ, 4191 N. Mesa, El Paso, TX 79902.

This is a 100% Small Business Set Aside. Only offers from Small Businesses will be considered for this solicitation.

The associated North American Industry Classification System (NAICS) code is 238220 – Plumbing, Heating, and Air-Conditioning Contractors. Product of Service Code for this requirement is N041–Installation of Equipment-Refrigeration, Air Conditioning, and Air Circulating Equipment. The Small Business Administration (SBA) size standard for this sector is $19.0 Million.

Services shall be quoted ALL or NONE as per CLIN structure and SOW attached. CLIN structure needs to be returned with your quote via e-mail directly to my attention at angelica.baca@ibwc.gov.

Quotes shall be good for 90 Days.

Offer due date/local time: May 6, 2026; 3:00 pm MST.

Only questions submitted by email to angelica.baca@ibwc.gov will be considered. Questions received from Offerors after 3p on May 1, 2026, may not be responded to.

Active UEI (Unique Entity Identifier) must be included in your offer.

Description: The International Boundary and Water Commission, United States Section (IBWC) requires LAN HVAC Replacement for El Paso HQ, 4191 N. Mesa, El Paso, TX 79902.

COR for this request: Antonio Almaguer (please do not contact him directly if you have any questions). All questions need to be directed to my attention.

Evaluation of Offer – The Government will award a contract resulting from this solicitation to the responsible offeror whose offer conforming to the solicitation will be most advantageous to the Government, price and other factors considered. The following factors shall be used to evaluate Offers: Technical acceptability to meet IBWC requirements; Technical Approach and Past Performance.

The Government will award a contract resulting from this combined synopsis/solicitation to the lowest price technically acceptable (LPTA), responsible offeror.

Offerors shall include a completed copy of the provision at 52.212-3, Offeror Representations and Certifications-Commercial Items, with its offer. NOTE: The offeror shall complete only paragraph (b) of this provision if the Offeror has completed the annual representations and certification electronically via the System for Award Management (SAM) website accessed at https://www.sam.gov.

END of combined synopsis/solicitation

Attachments:

CLIN Structure

Clauses and Provisions

Scope of Work

Files

Similar open opportunities

Opportunity Agency Set-aside Responses due
E21 prca HVAC replacement NAICS 238220 Bureau of Reclamation Total Small Business
Gwmp - arho bunker HVAC NAICS 238220 Intermountain Region Service-Disabled Veteran-Owned Small Business
Forest-Wide HVAC Repairs\Upgrades McCall, Idaho, United States · NAICS 238220 Forest Service Total Small Business
Troubleshoot & Repair of Portable Chillers Service Requirement Jbsa Lackland, Texas 78236, United States · NAICS 238220 Air Education and Training Command Total Small Business
HVAC repair JV resource_jordan valley NAICS 238220 Oregon-Washington Region Total Small Business

On GovTribe

Work this opportunity

  • Track it in your pipeline
  • Find teaming partners
  • Similar opportunities
  • Ask GovTribe AI about this opportunity