J059--Automatic Transfer Switch and Isolation Panel Service | Leavenworth VAMC |

Closed Pre-Solicitation Posted

Not the latest version. See the latest solicitation from .

Solicitation number
36C25526Q0584
Agency
Responses due
Set-aside
No set-aside

Opportunity facts

Place of performance
Dwight D. Eisenhower VA Medical Center 4101 S. 4th St. Leavenworth KS 66048

Notice details come from SAM.gov. Updated .

About this opportunity

The Department of Veterans Affairs Veterans Integrated Service Network 15 is conducting market research to identify qualified contractors capable of providing Automatic Transfer Switch inspection, preventive maintenance, repair, and isolation power panel services at Dwight D. Eisenhower VA Medical Center in Leavenworth, Kansas, with responses due August 11, 2026, at 1:00 pm CST. This is a sources sought notice that does not obligate the government to award a contract.

Place of performance is Leavenworth, Kansas. The contractor must maintain valid Kansas electrical licensing, possess documented experience with ATS and healthcare isolation power systems, perform annual VA privacy and security training, pass VA background checks, use calibrated testing instruments, and comply with NFPA standards, OSHA regulations, and VA safety requirements. The facility includes 17 ATS units from ASCO, Zenith, and Cummins manufacturers, plus four Square D isolation panels.

Anticipated period of performance is October 1, 2026, through September 30, 2031. NAICS 238210 applies, with a $19 million small business size standard. SDVOSB and VOSB vendors must be registered in the SBA VetCert database. Key deliverables include routine service reports within 48 hours, emergency repair reports within 24 hours, and annual executive summaries.

Respondents must submit written documentation via email to maria.owen2@va.gov including company name, address, point of contact, phone, email, UEI number, CAGE code, small business designation, and a detailed capability statement demonstrating technical expertise and experience. Phone calls will not be accepted.

Notice text

Sources Sought Notice:

This is not a request for formal proposals or quotes, it does not obligate the Government to award a contract. Requests for a solicitation will not receive a response. Responses to this Sources Sought must be in writing.

The purpose of this Sources Sought announcement is for market research to make appropriate acquisition decisions and to gain knowledge of potentially qualified businesses interested in and capable of providing the required services.

Documentation of technical expertise must be presented in sufficient detail for the government to determine that your company possesses the necessary functional area expertise and experience to compete for this acquisition.

Responses to this notice shall include the following:

(a) company name

(b) address

(c) point of contact

(d) phone and email

(e) UEI number

(f) Cage Code

(g) Type of small business, e.g., Services Disabled Veteran Owned Small Business, Veteran-Owned Small Business, 8(a), HUBZone, Women Owned Small Business, Small Disadvantaged Business, Small Business, or Large Business; and

(h) Capability statement that addresses the organization s qualifications and ability to perform as a contractor for the work described below.

This Sources Sought is for Dwight D. Eisenhower VA Medical Center, Leavenworth, Kansas who have a requirement for Automatic Transfer Switch (ATS) Inspection, Preventive Maintenance, Repair Services, and Isolation Power Panel Inspection.

The NAICS Code is 238210 with a Small Business size standard of $19 million. SDVOSB/VOSB vendors must be registered in the SBA VetCert database.

Offerors capable of providing this service shall notify the Contract Specialist no later than (NLT) August 11, 2026, 1:00 pm CST via email at maria.owen2@va.gov

All information is to be submitted via email to: maria.owen2@va.gov. Phone calls will not be accepted.

Performance Work Statement

Automatic Transfer Switch (ATS) Inspection, Preventive Maintenance, Repair Services, and Isolation Power Panel Inspection

1. Scope

The Department of Veterans Affairs requires a qualified contractor to provide all labor, materials, equipment, tools, supervision, transportation, and technical expertise necessary to perform inspections, testing, preventive maintenance, repairs, and emergency response services for Automatic Transfer Switches (ATS) and Isolation Electrical Power Panels throughout the Dwight D. Eisenhower VA Medical Center, 4101 S 4th Street, Leavenworth, KS 66048. All work shall ensure safe, reliable, and code compliant operation of all systems.

2. Period of Performance

October 1, 2026 September 30, 2031

3. Performance Objectives

The contractor shall deliver the following outcomes:

3.1 ATS Systems

Ensure all ATS units operate safely, reliably, and in accordance with NFPA standards and manufacturer specifications.

Maintain full functionality of transfer and retransfer operations, voltage sensing, phase rotation, time delay functions, and ATS battery systems.

3.2 Isolation Power Panels

Ensure proper operation of Line Isolation Monitors (LIMs) and electrical isolation systems per NFPA 99.

Maintain accurate, clearly labeled circuits consistent with facility electrical drawings.

3.3 Emergency Repairs

Restore system functionality rapidly for critical outages with minimal disruption to clinical operations.

3.4 Compliance & Safety

Ensure all work complies with NFPA 70, NFPA 70B, NFPA 99, OSHA, VA standards, and manufacturer guidelines.

4. Performance Requirements

4.1 ATS Inspection and Maintenance Tasks

The contractor shall perform and document the following measurable tasks:

Visual inspection with photographic evidence.

Cleaning of enclosures using manufacturer approved methods.

Infrared thermal scanning with image attachments.

Measurement and recording of temperature and torque values using calibrated instruments.

Operational testing, documenting pass/fail for:

transfer

retransfer

voltage sensing

time delay functions

phase rotation

ATS battery testing where applicable (voltage, load test, specific gravity).

Lubrication of components using manufacturer specified lubricants.

Coordinated generator functional testing, including recorded transfer and retransfer times.

4.2 Isolation Panel Inspection and Testing Requirements

The contractor shall:

Provide photographic documentation of panel inspections.

Test LIMs, verify alarm set points, simulate faults, and document response times.

Perform NFPA 99 compliant ground fault testing.

Measure voltage, current, and insulation resistance values.

Verify labeling accuracy against electrical drawings.

Clean interiors with nonconductive tools and record methods.

Verify torque values using calibrated instruments.

5. Performance Standards

6. Performance Monitoring (Government Surveillance)

The COR will evaluate contractor performance using the following methods:

Inspection of reports (routine & emergency) for accuracy and completeness.

Random onsite inspections of ATS and isolation panel systems.

Verification of corrective action timelines.

Review of emergency response logs.

7. Deliverables

7.1 Routine Service Reports Due within 48 hours

Reports shall include:

date/time of service

personnel names

equipment inspected

all measured values

photos and thermal images

pass/fail results

deficiencies and recommended corrective actions

references to NFPA/manufacturer standards

7.2 Emergency Repair Reports Due within 24 hours

Include issue description, corrective actions, parts replaced, test results, and verification of restored operation.

7.3 Annual Executive Summary Due within 30 days

Provide an overview of:

system condition

recurring deficiencies

reliability trends

recommended upgrades or corrective projects

8. Contractor Qualifications

Contractor personnel shall:

Maintain valid Kansas electrical licensing.

Have documented experience with ATS and healthcare isolation power systems.

Complete annual VA privacy, security, and safety training.

Pass VA background checks (VAAR 852.237 70).

Use calibrated testing instruments.

Wear VA issued identification badges.

9. Security & Safety Requirements

Contractor shall comply with:

VA safety regulations

OSHA regulations

NFPA standards

VA infection control procedures

10. Non Conforming Performance

Failure to perform may result in:

Notice of Concern

Corrective Action Request

Cure Notice in accordance with FAR 49.607

11. List of Equipment

Automatic Transfer Switch List

Type

CAT #

SER #

CUST DESIG

ASCO

H07ATBB31200N5XM

1329719-WE

ATS-4 122 Generator Shelter

ASCO

J07ATS30600C5XC

2688889-001RE

Elevator ATS 88/89 SW GEAR

ZENITH

ZTS2L15FC-7

1402776-1

ATS-4-EHC1A 91 North

ASCO

J07ATBB30400N5XC

2564471-001WE

ATS-B91 01 91 North

ZENITH

ZTS000B00060E

151048000-10-1

ATS-5-EHM1A 91 North

ZENITH

ZTS2L15FC-7

1402776-2

ATS-3-GE-X-RAY 91 North

ZENITH

ZTS2L15EC-7

1402847-2

ATS-1-EC1A 91 North

ZENITH

ZTS2L15EC-7

1402847-1

ATS-2-EC21 91 North

CUMMINS

BTPCB-1500816

B15M800254

Lift Station ATS Cemetery

ASCO

G7AUBB31600C5XM

1457708 WE

ATS 3 122 Platform

ASCO

J07ATBB30150C5XC

1329727 WE

ATS-2 122 Sub-basement

ASCO

J07ATBB30600C5XC

1329726 WE

ATS-1 122 Sub-basement

ASCO

H07ATBB31200C5XC

581676 WE

BLD89_ATS-1 88/89

ZENITH

ZBTS00B10260F

150163519-10-1

Chiller ATS-1 Bldg 161

CUMMINS

BTPCC-A073V586

E23M241483

POWER HOUSE ATS

ASCO

G07ATBB31600C5XC

2731373-001WE

BLD89 ATS-2 88/89

ASCO

E0094003100095XC

2443570-001WE

DOM BLD 160

ASCO

H07ATBA30800C5XC

581679-FP

91 ATS 1 91 South

Isolation Panel Equipment

Item #

Manufacturer

Panel Type

Serial Model

1

Square D

ISO

220525257

2

Square D

ISO

2201511637

3

Square D

ISO

2201524814

4

Square D

ISO

Files

File Type Posted
36C25526Q0584.docx DOCX document

Notice history

Notice Type Posted
J059--Automatic Transfer Switch and Isolation Panel Service | Leavenworth VAMC | Latest solicitation Solicitation
J059--Automatic Transfer Switch and Isolation Panel Service | Leavenworth VAMC | Solicitation
This notice Pre-Solicitation
J059--Automatic Transfer Switch and Isolation Panel Service | Leavenworth VAMC | Original Pre-Solicitation

Similar open opportunities

Opportunity Agency Set-aside Responses due
H112--Annual/Sem-i annual fire smoke inspections and auto door services l EKH Kansas 66048, United States · NAICS 541350 Veterans Integrated Service Network 15 Total Small Business
J061--SOURCES SOUGHT NOTICE - Triennial Electrical Inspection Testing and Maintenance Services Requirement - Louis A Johnson VA Medical Center 36C24527Q0039 Department of Veterans Affairs Louis A Johnson VA Medical Center Clarksburg, West Virginia 26301, United States · NAICS 238210 Veterans Integrated Service Network 5 No set-aside
J061--Uninterruptible Power Supply St. Louis VA Medical Center NAICS 811210 Veterans Integrated Service Network 15 No set-aside
657A5-26-111, Triennial Electrical Testing Marion, Illinois 62959, United States · NAICS 238210 Veterans Integrated Service Network 15 Service-Disabled Veteran-Owned Small Business Sole Source
J061--541 Electrical Power Distribution Equipment Testing, Inspection, and Maintenance - VAMC Cleveland Department of Veterans Affairs Louis Stokes Cleveland VA Medical Center Cleveland, Ohio 44106, United States · NAICS 238210 Veterans Integrated Service Network 10 Total Small Business

On GovTribe

Work this opportunity

  • Track it in your pipeline
  • Find teaming partners
  • Similar opportunities
  • Ask GovTribe AI about this opportunity