36C25526Q0584.docx
DOCX document 29 KB Posted
- Solicitation number
- 36C25526Q0584
About this file
This is a Sources Sought Notice for Automatic Transfer Switch (ATS) and Isolation Panel services at Dwight D. Eisenhower VA Medical Center in Leavenworth, Kansas. The Department of Veterans Affairs is conducting market research to identify qualified contractors capable of providing inspection, preventive maintenance, repair, and emergency response services for ATS units and isolation electrical power panels. Responses are due by August 11, 2026, at 1:00 pm CST to Contract Specialist Maria Riza R. Owen at maria.owen2@va.gov. This is a pre-solicitation notice that does not obligate the government to award a contract; phone calls will not be accepted. The NAICS code is 238210 with a small business size standard of $19 million. SDVOSB and VOSB vendors must be registered in the SBA VetCert database.
Responding companies must submit written documentation including company name, address, point of contact, phone, email, UEI number, CAGE code, small business designation, and a detailed capability statement demonstrating technical expertise. The anticipated period of performance is October 1, 2026, through September 30, 2031. The contractor must maintain valid Kansas electrical licensing, possess documented experience with ATS and healthcare isolation power systems, perform annual VA privacy and security training, pass VA background checks, use calibrated testing instruments, and comply with NFPA standards, OSHA regulations, and VA safety requirements. Key deliverables include routine service reports (within 48 hours), emergency repair reports (within 24 hours), and annual executive summaries. The facility includes 17 ATS units from manufacturers including ASCO, Zenith, and Cummins, plus four Square D isolation panels requiring ongoing maintenance and monitoring.
View the file
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Sources Sought Notice Sources Sought Notice
| SUBJECT* |
| Automatic Transfer Switch and Isolation Panel Service | Leavenworth VAMC | |
GENERAL INFORMATION
| CONTRACTING OFFICE’S ZIP CODE* |
| 66048 |
| SOLICITATION NUMBER* |
| 36C25526Q0584 |
| RESPONSE DATE/TIME/ZONE |
| 08-11-2026 1pm CENTRAL TIME, CHICAGO, USA |
| ARCHIVE |
| 30 DAYS AFTER THE RESPONSE DATE |
| RECOVERY ACT FUNDS |
| N |
SET-ASIDE
| PRODUCT SERVICE CODE* |
| J059 |
| NAICS CODE* |
| 238210 |
| CONTRACTING OFFICE ADDRESS |
| Department of Veterans Affairs |
Network Contracting Office (NCO) 15 3450 S 4th Street Trafficway
Leavenworth KS 66048
POINT OF CONTACT*
Contract Specialist Maria Riza R. Owen maria.owen2@va.gov 913-946-1965
PLACE OF PERFORMANCE
| ADDRESS |
| Dwight D. Eisenhower VA Medical Center |
4101 S. 4th St.
Leavenworth KS
| POSTAL CODE |
| 66048 |
COUNTRY
ADDITIONAL INFORMATION
AGENCY’S URL
URL DESCRIPTION
AGENCY CONTACT’S EMAIL ADDRESS
EMAIL DESCRIPTION
DESCRIPTION
Sources Sought Notice:
This is not a request for formal proposals or quotes, it does not obligate the Government to award a contract. Requests for a solicitation will not receive a response. Responses to this Sources Sought must be in writing.
The purpose of this Sources Sought announcement is for market research to make appropriate acquisition decisions and to gain knowledge of potentially qualified businesses interested in and capable of providing the required services.
Documentation of technical expertise must be presented in sufficient detail for the government to determine that your company possesses the necessary functional area expertise and experience to compete for this acquisition.
Responses to this notice shall include the following:
(a) company name
(b) address
(c) point of contact
(d) phone and email
(e) UEI number
(f) Cage Code
(g) Type of small business, e.g., Services Disabled Veteran Owned Small Business, Veteran-Owned Small Business, 8(a), HUBZone, Women Owned Small Business, Small Disadvantaged Business, Small Business, or Large Business; and
(h) Capability statement that addresses the organization’s qualifications and ability to perform as a contractor for the work described below.
This Sources Sought is for Dwight D. Eisenhower VA Medical Center, Leavenworth, Kansas who have a requirement for Automatic Transfer Switch (ATS) Inspection, Preventive Maintenance, Repair Services, and Isolation Power Panel Inspection.
The NAICS Code is 238210 with a Small Business size standard of $19 million. SDVOSB/VOSB vendors must be registered in the SBA VetCert database.
Offerors capable of providing this service shall notify the Contract Specialist no later than (NLT) August 11, 2026, 1:00 pm CST via email at maria.owen2@va.gov All information is to be submitted via email to: maria.owen2@va.gov. Phone calls will not be accepted.
Performance Work Statement Automatic Transfer Switch (ATS) Inspection, Preventive Maintenance, Repair Services, and Isolation Power Panel Inspection
1. Scope The Department of Veterans Affairs requires a qualified contractor to provide all labor, materials, equipment, tools, supervision, transportation, and technical expertise necessary to perform inspections, testing, preventive maintenance, repairs, and emergency response services for Automatic Transfer Switches (ATS) and Isolation Electrical Power Panels throughout the Dwight D. Eisenhower VA Medical Center, 4101 S 4th Street, Leavenworth, KS 66048. All work shall ensure safe, reliable, and code‑compliant operation of all systems.
2. Period of Performance October 1, 2026 – September 30, 2031
3. Performance Objectives The contractor shall deliver the following outcomes:
3.1 ATS Systems
· Ensure all ATS units operate safely, reliably, and in accordance with NFPA standards and manufacturer specifications.
· Maintain full functionality of transfer and retransfer operations, voltage sensing, phase rotation, time‑delay functions, and ATS battery systems.
3.2 Isolation Power Panels
· Ensure proper operation of Line Isolation Monitors (LIMs) and electrical isolation systems per NFPA 99.
· Maintain accurate, clearly labeled circuits consistent with facility electrical drawings.
3.3 Emergency Repairs
· Restore system functionality rapidly for critical outages with minimal disruption to clinical operations.
3.4 Compliance & Safety
· Ensure all work complies with NFPA 70, NFPA 70B, NFPA 99, OSHA, VA standards, and manufacturer guidelines.
4. Performance Requirements
4.1 ATS Inspection and Maintenance Tasks
The contractor shall perform and document the following measurable tasks:
· Visual inspection with photographic evidence.
· Cleaning of enclosures using manufacturer‑approved methods.
· Infrared thermal scanning with image attachments.
· Measurement and recording of temperature and torque values using calibrated instruments.
· Operational testing, documenting pass/fail for:
· transfer
· retransfer
· voltage sensing
· time‑delay functions
· phase rotation
· ATS battery testing where applicable (voltage, load test, specific gravity).
· Lubrication of components using manufacturer‑specified lubricants.
· Coordinated generator functional testing, including recorded transfer and retransfer times.
4.2 Isolation Panel Inspection and Testing Requirements
The contractor shall:
· Provide photographic documentation of panel inspections.
· Test LIMs, verify alarm set points, simulate faults, and document response times.
· Perform NFPA 99‑compliant ground‑fault testing.
· Measure voltage, current, and insulation resistance values.
· Verify labeling accuracy against electrical drawings.
· Clean interiors with nonconductive tools and record methods.
· Verify torque values using calibrated instruments.
5. Performance Standards
6. Performance Monitoring (Government Surveillance) The COR will evaluate contractor performance using the following methods:
· Inspection of reports (routine & emergency) for accuracy and completeness.
· Random onsite inspections of ATS and isolation panel systems.
· Verification of corrective action timelines.
· Review of emergency response logs.
7. Deliverables
7.1 Routine Service Reports – Due within 48 hours
Reports shall include:
· date/time of service
· personnel names
· equipment inspected
· all measured values
· photos and thermal images
· pass/fail results
· deficiencies and recommended corrective actions
· references to NFPA/manufacturer standards
7.2 Emergency Repair Reports – Due within 24 hours
Include issue description, corrective actions, parts replaced, test results, and verification of restored operation.
7.3 Annual Executive Summary – Due within 30 days
Provide an overview of:
· system condition
· recurring deficiencies
· reliability trends
· recommended upgrades or corrective projects
8. Contractor Qualifications Contractor personnel shall:
· Maintain valid Kansas electrical licensing.
· Have documented experience with ATS and healthcare isolation power systems.
· Complete annual VA privacy, security, and safety training.
· Pass VA background checks (VAAR 852.237‑70).
· Use calibrated testing instruments.
· Wear VA‑issued identification badges.
9. Security & Safety Requirements Contractor shall comply with:
· VA safety regulations
· OSHA regulations
· NFPA standards
· VA infection‑control procedures
10. Non‑Conforming Performance Failure to perform may result in:
· Notice of Concern
· Corrective Action Request
· Cure Notice in accordance with FAR 49.607
11. List of Equipment
Automatic Transfer Switch List
| Type |
| CAT # |
| SER # |
| CUST DESIG |
| ASCO |
| H07ATBB31200N5XM |
| 1329719-WE |
| ATS-4 122 Generator Shelter |
| ASCO |
| J07ATS30600C5XC |
| 2688889-001RE |
| Elevator ATS 88/89 SW GEAR |
| ZENITH |
| ZTS2L15FC-7 |
| 1402776-1 |
| ATS-4-EHC1A 91 North |
| ASCO |
| J07ATBB30400N5XC |
| 2564471-001WE |
| ATS-B91 01 91 North |
| ZENITH |
| ZTS000B00060E |
| 151048000-10-1 |
| ATS-5-EHM1A 91 North |
| ZENITH |
| ZTS2L15FC-7 |
| 1402776-2 |
| ATS-3-GE-X-RAY 91 North |
| ZENITH |
| ZTS2L15EC-7 |
| 1402847-2 |
| ATS-1-EC1A 91 North |
| ZENITH |
| ZTS2L15EC-7 |
| 1402847-1 |
| ATS-2-EC21 91 North |
| CUMMINS |
| BTPCB-1500816 |
| B15M800254 |
| Lift Station ATS Cemetery |
| ASCO |
| G7AUBB31600C5XM |
| 1457708 WE |
| ATS 3 122 Platform |
| ASCO |
| J07ATBB30150C5XC |
| 1329727 WE |
| ATS-2 122 Sub-basement |
| ASCO |
| J07ATBB30600C5XC |
| 1329726 WE |
| ATS-1 122 Sub-basement |
| ASCO |
| H07ATBB31200C5XC |
| 581676 WE |
| BLD89_ATS-1 88/89 |
| ZENITH |
| ZBTS00B10260F |
| 150163519-10-1 |
| Chiller ATS-1 Bldg 161 |
| CUMMINS |
| BTPCC-A073V586 |
| E23M241483 |
| POWER HOUSE ATS |
| ASCO |
| G07ATBB31600C5XC |
| 2731373-001WE |
| BLD89 ATS-2 88/89 |
| ASCO |
| E0094003100095XC |
| 2443570-001WE |
| DOM BLD 160 |
| ASCO |
| H07ATBA30800C5XC |
| 581679-FP |
| 91 ATS 1 91 South |
Isolation Panel Equipment
| Item # |
| Manufacturer |
| Panel Type |
| Serial Model |
| 1 |
| Square D |
| ISO |
| 220525257 |
| 2 |
| Square D |
| ISO |
| 2201511637 |
| 3 |
| Square D |
| ISO |
| 2201524814 |
| 4 |
| Square D |
| ISO |
| *= Required Field |
| Sources Sought Notice |