J046--Water Treatment and Chemistry Services for Cooling Towers and Chillers Base plus 4 Year

Closed Special Notice Posted

Solicitation number
36C24725Q0830
Agency
Responses due
Set-aside
Service-Disabled Veteran-Owned Small Business

Opportunity facts

Place of performance
Department of Veterans Affairs Ralph H. Johnson VA Medical Center Charleston, South Carolina 29401, United States

Notice details come from SAM.gov. Updated .

About this opportunity

The Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 7 has issued a Special Notice for water treatment and chemistry services for cooling towers and chillers at the Ralph H. Johnson VA Medical Center in Charleston, SC and Tuscaloosa VA Medical Center. This is a Service-Disabled Veteran-Owned Small Business set-aside opportunity under solicitation number 36C24725Q0830, covering a base contract period plus four additional years. The contract involves maintenance and chemical treatment services for TRANE chillers and EVASCO cooling towers, with the system processing approximately 1.4 million gallons of annual makeup water. The solicitation has been extended with responses now due August 25, 2025 at 10:00 AM CST, and questions must be submitted by August 20, 2025 at 1:00 PM CST. The notice includes detailed technical specifications and answers to contractor questions about system operations and requirements.

The primary objective is to secure comprehensive water treatment services including monthly on-site service, chemical delivery and storage, corrosion coupon analysis, and emergency response capabilities for the VA's cooling systems. Contractors must be located within 100 miles of the facility to provide reasonable emergency response times and must follow manufacturer instructions and industry best practices for water treatment. The contract covers three 1000-ton chillers that typically operate 1-2 units simultaneously for approximately 1,467 hours monthly, along with multiple cooling towers requiring chemical treatment and monitoring. Key requirements include digital service reporting via email/PDF, accommodation of both dry and liquid chemical treatment options pending contractor verification, and capability to respond to water quality emergencies including potential Legionella events. Only Service-Disabled Veteran-Owned Small Businesses are eligible to compete for this opportunity, which falls under NAICS code 325998 for miscellaneous chemical product manufacturing.

Notice text

3 versions

Update #3 · Latest ·

Clarification Questions:

System Scope & Access

Could you kindly confirm the approximate number and type of cooling towers, chillers, and any closed-loop systems (e.g., hot water, glycol) that will be covered under this contract?

Information is in Introduction to PWS. Chiller type-TRANE; Cooling Tower type EVASCO.

Chemical Delivery & Storage

Will the VA accept routine chemical deliveries (e.g., in totes or drums) to a designated mechanical area on site, or are there restrictions on storage location, access hours, or container size?

Information is in PWS. Chemical and testing Supplies. See item 9, 10. Vendor must consult with Boiler/Chiller plant manager on details.

Service Schedule Expectations

Is monthly on-site service expected for all systems? Would any systems require seasonal startup/shutdown support, or is year-round service anticipated?

Follow PWS, manufactures instructions and best practices. (See performance requirements.)

Corrosion Coupon Program

Will the contractor be expected to provide corrosion coupons and holders, or are those already installed on site? If so, are we responsible for full analysis and reporting?

Follow PWS, manufactures instructions and best practices.

Reporting Requirements

Would you prefer digital service reports to be submitted via email/PDF, or is there a VA platform (such as TMS or SharePoint) required for uploads?

Digital service reports via email/PDF is acceptable. If this changes we will advise.

Emergency Support

Are vendors expected to offer 24 48 hour emergency response for water quality or biological issues (e.g., suspected Legionella events)? If so, please confirm expected response time and point of contact protocol. Information in PWS under Chemical water Treatment Contractor Qualifications Item 3. (Must be within a 100 miles of the site to provide a reasonable response time.)

Evaluation Factors

Will the evaluation be conducted strictly under a Lowest Price Technically Acceptable (LPTA) approach, or will the government consider past performance or technical narrative as part of a broader assessment? Defer to CO

Labor vs. Materials Breakdown

Should chemicals, corrosion analysis, and testing be priced as separate line items, or should these be bundled into a flat monthly rate?

Defer to CO

Annual Estimate (for Planning)

While we understand that previous vendor data isn t provided, would you be able to share a rough estimate of expected annual service frequency or volume of chemical usage to help us appropriately size our proposal?

No information.

Update #2 ·

ADDITIONAL QUESTIONS AND ANSWERS FOR SOLICITATION 36C24725Q0830

Number of Towers:

Total Annual Makeup gallons to tower systems:

Cooling Tower makeup = 1,396,878

Total Tonnage of Chillers while in operation:

3 chillers. 1000 tons each. Usually 1 or 2 on-line.

Total water volume in Cooling tower sumps:

Check in manufactures instruction.

Tower run time (Hours/Months) 24/7/365? Less?Â

Chiller 5= 27/hrs; Chiller 6= 706 hrs; Chiller 8= 734/hrs. Monthly total= 1467/hrs/Mo.

Question Given the extension till Monday, 8/25/25, could you please schedule another site visit for this week, or perhaps give us the opportunity to have one of our technicians visit the facility for a brief visit? I will accommodate a quick visit today at 1:00 pm

Â

One of the questions recently submitted mentioned that dry chemistry is currently is use and if this is a requirement, but I am not sure if it was clearly answered. I believe it is dry chemical. contractor will have to verify when awarded.

Â

Question Is Dry Chemistry for the cooling tower treatment a strict requirement, or are we able to propose Liquid Chemistry as well? Need to verify this with the boiler/chiller plant operators after award.

Update #1 ·

Presolicitation Notice

Presolicitation Notice

Page 3 of 3

Page 1 of 3

Questions Answered for RFI: 36C24725Q0843

Solicitation 36C24725Q0830 has been extended until 10:00am CST, Monday, August 25, 2025. Any questions must be submitted by 1:00pm CST, Thursday, August 20, 2025.

Water Treatment and Water Chemistry Services for Cooling Towers and Chillers Base plus 4 Year

1. Are the Steam Boilers included? No

2. Do you know if you are feeding a Nitrite in the chiller loops? I do not think so but I m unsure.

3. Do you feed the secondary chillers separate or are they on the same loop? Not to my knowledge.

4. I noticed that you are feeding a dry chemical for your towers, are you opposed to feeding a liquid chemical instead? No dry chemicals are fed into the towers. It is mixed at the mixing station upstairs by the bathroom.

Â

Files

File Type Posted
36C24725Q0830_4.docx DOCX document
36C24725Q0830_3.docx DOCX document
Cooling Tower Testing Results 072025.pdf PDF
36C24725Q0830_2.docx DOCX document
0722025 BW Charleston Cooling Towers HPC.pdf PDF

Notice history

Notice Type Posted
This notice Latest special notice Special Notice
J046--Water Treatment and Chemistry Services for Cooling Towers and Chillers Base plus 4 Year Solicitation
J046--FY25: Water Treatment and Chemistry Services for Cooling Towers and Chillers Base plus 4 Year Original Pre-Solicitation

Similar open opportunities

Opportunity Agency Set-aside Responses due
J041--RFQ SDVOSB Set-Aside CHILLER TUBE CLEANING SERVICES WJB Dorn VA Medical Center 6439 Garners Ferry Road Columbia, South Carolina 29209, United States · NAICS 561210 Veterans Integrated Service Network 7 Service-Disabled Veteran-Owned Small Business
H246--Reverse Osmosis, Deionization Equipment and PE Water Softene 2026-2027 Department of Veterans Affairs Long Beach CA 90822, United States · NAICS 221310 Veterans Integrated Service Network 22 No set-aside
Rental of two chillers for one year Asheville, North Carolina 28805, United States · NAICS 238220 Veterans Integrated Service Network 6 Service-Disabled Veteran-Owned Small Business
Z2NZ--Turn Key Chiller Equipment (Purchase and Install) Pineville, Louisiana 71360, United States · NAICS 238220 Veterans Integrated Service Network 16 Service-Disabled Veteran-Owned Small Business
Z2DA--cooling tower 2 and 3 repair Department of Veterans Affairs Vamc Baltimore MD 21201 · NAICS 236220 Veterans Integrated Service Network 5 Total Small Business

On GovTribe

Work this opportunity

  • Track it in your pipeline
  • Find teaming partners
  • Similar opportunities
  • Ask GovTribe AI about this opportunity

GovTribe for Federal Contractors