YTPM 22-0004 REFERENCE Fall Protection Reference Drawings_2025.05.15.pdf
PDF 3 MB Posted
- Attached to
- Repair Barrel Roof, Hangar 3
- Solicitation number
- FA660625R0002
About this file
These are detailed technical drawings for a Guardian Fall Protection System designed for a roof, specifically for the Department of Air Force Reserve Command project FA6606-25-R-0002. The drawings provide comprehensive installation specifications for a horizontal lifeline system with multiple anchor points, including CB-18 Hybrid Anchors, Single Point Anchors, and associated components like eye bolts, in-line dampers, load cells, and removable trolleys. The system is engineered for two users in fall arrest or four users in fall restraint, with specific requirements for anchor placement, including minimum distances from roof edges, maximum span lengths, and critical installation notes about decking reinforcement, structural mounting, and mandatory bi-annual and annual inspections by competent and qualified personnel.
The technical drawings detail precise installation methods, including the use of #14-10x3" wood screws for mounting, minimum 1.75" thick tongue and groove decking, and specific structural components like Schedule 80 pipe and galvanized steel plates. The system includes multiple safety features such as slip swage indicators, checkline in-line dampers, and intermediate brackets. The drawings emphasize compliance with OSHA and ANSI regulatory requirements for fall protection, with explicit instructions for anchor placement, environmental condition considerations, and worker equipment specifications. The recommended system spans range from 20' to 40' depending on the anchor type, with specific configurations for different roof and structural mounting scenarios.
View the file
Other files
Show all 13
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
CB-HYBRID HLL SYSTEM GENERAL NOTES:
1. EACH HORIZONTAL LIFELINE IS DESIGNED FOR UP TO TWO USERS IN FALL ARREST OR FOUR
USERS IN FALL RESTRAINT; 25' OF VERTICAL CLEARANCE IS REQUIRED TO USE SYSTEM IN
ARREST.
2. THE FALL PROTECTION SYSTEMS SHALL NOT BE USED TO HOIST MATERIALS OR EQUIPMENT.
3. THESE SYSTEMS HAVE BEEN DESIGNED TO MEET OSHA AND ANSI REGULATORY REQUIREMENTS
FOR FALL PROTECTION.
4. THE SYSTEM SHALL BE USED IN FALL RESTRAINT IF MINIMUM VERTICAL CLEARANCE IS NOT MET.
5. "COMPETENT PERSON" MEANS A PERSON WHO IS CAPABLE OF IDENTIFYING HAZARDOUS OR
DANGEROUS CONDITIONS IN PERSONAL FALL ARREST SYSTEM OR ANY COMPONENT THEREOF,
AS WELL AS IN THEIR APPLICATION AND USE OF RELATED EQUIPMENT.
6. "QUALIFIED PERSON" MEANS ONE WITH A RECOGNIZED DEGREE OR PROFESSIONAL CERTIFICATE
AND EXTENSIVE KNOWLEDGE AND EXPERIENCE IN FALL PROTECTION WHO IS CAPABLE OF
DESIGN, ANALYSIS, EVALUATION, AND SPECIFICATIONS IN THE SUBJECT WORK, PROJECT, OR
PRODUCT.
7. SAFE ACCESS TO, EGRESS FROM, AND USE OF THE SYSTEM SHALL BE DETERMINED BY THE
COMPETENT PERSON OF RECORD FOR THE BUILDING AND DESCRIBED IN THE WRITTEN FALL
PROTECTION PLAN.
8. RESCUE PLAN SHALL BE DETERMINED BY THE COMPETENT PERSON OF RECORD FOR THE
BUILDING AND DESCRIBED IN THE WRITTEN FALL PROTECTION PLAN; IF THE SYSTEM IS TO BE
USED IN FALL ARREST.
9. TEMPORARY FALL PROTECTION MEASURES SHALL BE UTILIZED DURING ERECTION AND
DISMANTLING OF PERMANENT SYSTEM, AS DETERMINED BY THE COMPETENT PERSON OF
RECORD FOR THE BUILDING.
10. RETIREMENT OF THESE SYSTEMS SHALL RESULT IN TERMINATION OF ALL COMPONENTS
RENDERING THEM USELESS FOR ANY OTHER FALL PROTECTION SYSTEM.
11. NO SUBSTITUTIONS TO MATERIALS OR MANUFACTURER'S EQUIPMENT IS PERMITTED.
12. REFER TO SYSTEM'S USER GUIDE FOR INITIAL CABLE SAGS AND ADDITIONAL INFORMATION.
WORKER EQUIPMENT NOTES:
8. ANCHOR LAYOUT DOES NOT PROVIDE FULL ROOF FALL PROTECTION COVERAGE.
9. ANCHORS SHALL BE RIGGED SUCH THAT THE USER CAN NEITHER FREE FALL MORE THAN 6 FEET, NOR CONTACT ANY LOWER LEVEL. (OSHA 1926.502(D)(16)).
10. USE OF ANSI Z359 APPROVED PERSONAL FALL PROTECTION EQUIPMENT THAT IS RATED TO 1,350
LBS. AVERAGE ARREST FORCE AND 1,800 LBS. MAXIMUM ARREST FORCE IS REQUIRED.
11. WORKER WEIGHT RANGE (INCLUDING EQUIPMENT) IS 130-310 LBS.
12. FOR LIFELINES PLACED WITHIN SIX FEET FROM A FALL HAZARD, EQUIPMENT MUST BE ADJUSTED
AND VERIFIED BY A COMPETENT PERSON TO MEET THE FOLLOWING:
12.1. EFFECTIVE LANYARD LENGTH MUST BE SHORTER THAN THE MINIMUM DISTANCE FROM THE
HORIZONTAL LIFELINE TO A FALL HAZARD, IF THE SYSTEM IS TO BE USED IN FALL RESTRAINT.
12.2. EFFECTIVE LANYARD LENGTH MUST BE ADJUSTED SUCH THAT THE USER CAN NEITHER FREE
FALL MORE THAN 6 FEET, NOR CONTACT ANY LOWER LEVEL, IF THE SYSTEM IS TO BE USED IN
FALL ARREST.
STRUCTURAL NOTES:
1. ATTENTION: THE ENGINEER'S SEAL INDICATES ONLY THAT THE ANCHORS DETAILED ON THESE
PLANS ARE DESIGNED TO WITHSTAND THE INDICATED LOADS, OR HAVE BEEN LAB TESTED FOR
THE INDICATED LOADS. THE ABILITY OF THE BUILDING STRUCTURE TO SUPPORT THE LOADS
TRANSFERRED FROM THE ANCHOR ATTACHMENT SURFACE HAS NOT BEEN VERIFIED BY GFP'S
SPECIALTY ENGINEER . THIS SHALL BE VERIFIED SEPARATELY BY THE ENGINEER OF RECORD FOR THE BUILDING STRUCTURE, BY A LICENSED PROFESSIONAL ENGINEER HIRED BY THE BUILDING OWNER, OR IF HIRED, BY GFP's SPECIALTY ENGINEER.
2. HORIZONTAL LIFELINE ANCHOR LOADS ARE LIMITED TO A MAXIMUM FORCE OF 2,500 LBS WITH
THE SYSTEM CONFIGURATION(S) SHOWN WHEN INSTALLED AND USED IN ACCORDANCE WITH
GUARDIAN INSTRUCTIONS.
3. ANCHORS ARE DESIGNED FOR AN ULTIMATE LOAD OF 5,000 LBS.
4. ALL EXISTING STRUCTURES TO WHICH THE FALL PROTECTION SYSTEM IS ATTACHED FOR
PRIMARY SUPPORT ARE ASSUMED TO BE OF ORIGINAL INTEGRITY.
5. BUILDING OWNER SHALL VERIFY THAT THE EXISTING CONDITIONS AT ANCHOR LOCATIONS MEET
THE REQUIREMENTS OF THE CONDITIONS SHOWN IN THESE DRAWINGS. GUARDIAN FALL
PROTECTION SHALL BE CONTACTED IN CASE OF DISCREPANCY BETWEEN THESE DRAWINGS AND
EXISTING CONDITION.
ANCHOR PLACEMENT GENERAL NOTES:
1. ANCHORS MAY BE MOVED FROM LOCATIONS SHOWN ON PLAN LAYOUTS BY UP TO 2'-0" TOWARD
OR AWAY FROM THE EDGE OF THE ROOF, OR BY 5'-0" PARALLEL TO THE EDGE OF THE ROOF AS
LONG AS THE CONDITIONS SHOWN FOR THE ANCHORAGE REMAIN THE SAME AND AS LONG AS
THE NEW LOCATIONS ARE APPROVED BY A QUALIFIED PERSON.
2. THE ENGINEER THAT DESIGNED THE SYSTEM OR AN ENGINEER WITH SIMILAR EXPERIENCE AND
QUALIFICATIONS SHALL BE CONSULTED BEFORE MODIFYING THE DESIGN.
3. THIS SYSTEM IS DESIGNED TO BE PERMANENT AND SHALL NOT BE RELOCATED.
4. ANCHORS SHALL NOT BE PLACED CLOSER THAN 6 FEET TO THE LEADING EDGE OF A FALL
HAZARD UNLESS FALL PROTECTION TO ACCESS THOSE ANCHORS IS PROVIDED.
5. CONTRACTOR SHALL ENSURE NO OBSTRUCTIONS EXIST BETWEEN ANCHOR POINTS THAT MAY
INTERFERE WITH THE INSTALLATION OF HORIZONTAL LIFE LINE.
INSPECTION NOTES:
1. A COMPETENT PERSON INDEPENDENT OF THE USER SHALL INSPECT THESE SYSTEMS ON A
BI-ANNUAL BASIS.
2. A QUALIFIED PERSON TRAINED IN THE OPERATION OF HORIZONTAL LIFELINES SHALL INSPECT
THESE SYSTEMS ON AN ANNUAL BASIS.
3. ALL WORKERS USING THESE SYSTEMS SHALL BE TRAINED ON THE PROPER USE AND INSPECTION
OF ANCHORS AND FALL PROTECTION EQUIPMENT.
4. PROOF LOAD ANCHOR TESTING IS RECOMMENDED ON 100% OF ANCHORS INSTALLED.
ENVIRONMENTAL CONDITION NOTES:
1. EXTREME ENVIRONMENTAL CONDITIONS SHALL INCREASE THE FREQUENCY OF INSPECTIONS
REQUIRED.
2. HIGH WIND LOADS AND PRECAUTIONS SHALL BE ACCOUNTED FOR IN THE WRITTEN FALL
PROTECTION PLAN, AS DETERMINED BY THE COMPETENT PERSON OF RECORD FOR THE
BUILDING.
TABLE 1 RECOMMENDATIONS FOR SYSTEM SPANS
ANCHOR TYPE SPAN WITH CORNERS STRAIGHT RUN
TOPFIX POSTS 20' (6m) 30' (9m)
CB HYBRID POSTS 20' (6m) 30' (9m)
BOLT TO STRUCTURAL
STEEL (WALL
MOUNT/OVERHEAD)
30' (9m) 40' (12m)
FOR R
EFERENCE O
NLY
10'
10'
20'
20'
30'
60'
30'
20'
20'
12'
10'
20'
20'
30'
60'
30'
20'
20'
12'
27' 27' 27' 27' 27' 27' 27' 21'21'
1'
10'
HLL 2
APP 186 LF
GUARDIAN HYBRID SYSTEM LEGEND
CB-18 HYBRID ANCHOR + EYE BOLT + ** DAMPER
CB-18 SINGLE POINT ANCHOR
CABLE
CB-18 HYBRID ANCHOR + EYE BOLT + ** LOADCELL
CB-18 HYBRID ANCHOR + ** INTERMEDIATE BRACKET ROOF PLAN VIEW
SCALE: 1/32" = 1'-0" GUARDIAN SYSTEM GENERAL NOTES:
1. SEE SHEET 1 FOR GENERAL NOTES, WORKER
EQUIPMENT NOTES, AND STRUCTURAL NOTES.
NFOR R
EFERENCE O
NLY
**CHECKLINE LOAD
CELL (ITEM #4)
**8MM WIRE ROPE
(ITEM #9)
**SLIP SWAGE INDICATOR, TYP.
(ITEM #10)
**CHECKLINE IN-LINE DAMPER
(ITEM #3)
EYE BOLT, TYP.
(ITEM #5)
**CHECKBALL TROLLEY
REMOVABLE (ITEM #7) **INTERMEDIATE BRACKET
(ITEM #6)
CB-18 HYBRID ANCHOR, TYP.
(ITEM #2)
CB-18 SINGLE POINT ANCHOR
(ITEM #1)
(60) #14-10x3" WOOD SCREWS
(ITEM #8)
*REINFORCE DECKING
AS RECOMMENDED BY
THE LICENSED BUILDING
ENGINEER
*MIN. 1.75" THICK T&G
DECKING
1'-6"
1'-4"
1'-4"
CB-18 HYBRID ANCHOR
(ITEM #2)
(60) #14-10x3" SCREWS
FOR WOOD DECK DIRECTLY INTO PLYWOOD
AND BLOCKING
(ITEM #8)
1'-4"
1'-4"
1'-6"
*REINFORCE DECKING
AS RECOMMENDED BY
THE LICENSED BUILDING
ENGINEER
*MIN. 1.75" THICK T&G
DECKING
DETAIL 1: GUARDIAN HYBRID LIFELINE INSTALLATION
SCALE: 1" = 1'-0"
INSTALLATION NOTES:
1. THE INSTALLATION SPECIFICATIONS
SHOWN HAVE BEEN DESIGNED TO MEET
OSHA AND ANSI REGULATORY
REQUIREMENTS FOR FALL PROTECTION.
2. CONTRACTOR SHALL VERIFY ANCHOR
HEIGHT ALLOWS ADEQUATE CLEARANCE
FOR WATERPROOFING.
3. WATERPROOFING AND ASSOCIATED
ROOFING WORK SHALL BE PERFORMED BY
OTHERS.
4. INSTALLATION DETAILS AND INSTRUCTIONS
ON THESE SHOP DRAWINGS SUPERSEDE
ANY GENERIC INSTALLATION NOTES
INCLUDED ON PRODUCT DATA FOR SIMILAR
PROJECTS.
DETAIL 2: CB-18 SINGLE POINT ANCHOR INSTALLATION
SCALE: 3/4" = 1'-0"
DETAIL 3: CB-18 HYBRID ANCHOR INSTALLATION
SCALE: 3/4" = 1'-0"
FOR R
1'-4"
1'-4" 2"
1'-6"
Ø3/8"
5/16"
2.5" SCH. 80 PIPE
ASTM A 53 GRADE B
(2.875" O.D./2.323" I.D.)
3/8" S.S. 304 CAP PLATE
WITH M16 NUT WELDED
UNDERNEATH
16x16x3/8".
ASTM A36 PLATE
3/16"
1/2"
16"
16"
3/8"
5/16"
2.5" SCHEDULE 80 PIPE
ASTM A53 GRADE B
(2.875" O.D./2.323" I.D.)
2" TYP.
2" TYP.
1"
1"
5/8" DIA. GALVANIZED
STEEL U-BAR
3/16" THICK x 2-1/2" DIA.
ASTM A36 CAP PLATE
16x16x3/8".
ASTM A36 PLATE
Ø3/8"
2-1/4"
18"
3/16"TYP
3 PLCS.
5 EYE BOLT
SCALE: 3" = 1'-0"
2 CB-18 HYBRID ANCHOR
SCALE: 3/4" = 1'-0"
3 ** INLINE DAMPER
SCALE: 1" = 1'-0" 4 ** LOAD CELL
SCALE: 1" = 1'-0"
6 ** INTERMEDIATE BRACKET
SCALE: 1-1/2" = 1'-0" 7 ** REMOVABLE TROLLEY
SCALE: 1-1/2" = 1'-0"
1 CB-18 SINGLE POINT ANCHOR
SCALE: 3/4" = 1'-0"
FOR R