WVARNG Patriot Guardens Electrical Service Project Drawings.pdf

PDF 2 MB Posted

Attached to
Patriot Guardens Electrical Service Installation Constructio
Solicitation number
CRFQ 0603 ADJ2600000012 2
Issued by
Monongalia County, West Virginia

About this file

This file consists of electrical service project drawings and specifications for the West Virginia Army National Guard's Patriot Guardians facility. The project, numbered 25015, involves the design and installation of a complete electrical service infrastructure system serving multiple buildings and areas within the facility. The scope includes underground 480/277-volt and 120/208-volt electrical distribution systems, with multiple feeder routes, transformer installations, disconnect switches, grounding systems, and associated conduit work. The project includes a base bid with multiple alternates, specifically Alternate #1 which addresses termination at the jobsite trailer's panel and future cooling building provisions. The drawings indicate seven primary feeder circuits (tagged A through G) with varying conductor sizes in both copper and aluminum options, ranging from 2-inch to 5-inch conduit sizes. The electrical infrastructure must comply with the 2020 National Electrical Code and American Electric Power (AEP) utility requirements, with all work subject to required inspections and utility coordination.

The project design was completed by Miller Engineering Inc., with drawings dated September 12, 2025, indicating this is construction documentation. The electrical system serves multiple switching and distribution points (SW-1 through SW-6) and three transformers (TX-1, TX-2, TX-3) with ratings of 37.5 KVA, 45 KVA, and 75 KVA respectively. The electrical specifications require specific materials including Schedule 40 PVC for underground raceways, THHN/THWN wiring in PVC conduit for exterior installations, and NEMA 3R rated enclosures for all outdoor equipment. Contractor responsibilities include utility location verification prior to earthwork, coordination with other trades, and compliance with all specified electrical codes and AEP requirements. The drawings detail underground burial specifications with magnetic tape identification, gravel backfill requirements, and various in-ground junction box details with specific depth and installation parameters.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

UNDERGROUND480/277

UNDERGROUND

480/277

A

B

B

C

D

SW

-1

SW

-2

DPHN-1

D

PH

N -2

S W

-3

T X

-3

D P

L N

-1

S W

-4 T

X -2

SW-5

FEED FROM OWNER PROVIDED PANEL

240V

#10 CONDUCTOR

#12 GRN

1" CND

FOR OWNER EXISTING

METER BOXES, REMOVE

METER BASE AND BLANK

OFF HOLE. (TYP)

E

E

QUAZITE PG1118BA12 OR APPROVED EQUAL

ELECTRICAL SERVICE DISCONNECT

ROAD CROSSING

ROAD CROSSING

ROAD CROSSING

ROAD CROSSING

ROAD CROSSING

ROAD CROSSING

(1) CONDUIT TO BE SPARE

S W

-6 T

X -1

ROAD CROSSING

ROAD CROSSING

BASE BID

ALTERNATE #1

ALTERNATE #1

ALTERNATE #1

ALTERNATE #1

ROAD CROSSING

FUTURE COOLING BUILDING

ALTERNATE #1: TERMINATE AT JOBSITE TRAILER'S PANEL (TYP-3)

1. WIRING IS SHOWN ON DRAWINGS ONLY FOR SPECIFIC ROUTES OR

SPECIAL CONDITIONS.

2. WIRING AND CONDUIT OR SHALL BE REQUIRED FOR ALL OUTLETS

AND DEVICES. FOLLOW INDICATED CIRCUITS NUMBERS AND PANEL

DESIGNATION. OBTAIN PRIOR APPROVAL OF ENGINEER FOR

DEVIATIONS.

3. ALTHOUGH ALL BRANCH CIRCUIT WIRING IS NOT SHOWN, IT IS THE

INTENT OF THESE DOCUMENTS THAT A COMPLETE BRANCH CIRCUIT

WIRING SYSTEM BE INSTALLED. ALL NEUTRALS SHALL BE FULL

CAPACITY. THE USE OF SHARED OR COMMON NEUTRALS IS

PROHIBITED ON ALL ELECTRIC WIRING.

4. EXTERIOR WIRING IS TO BE THHN/THWN IN PVC CONDUIT. MAX. OF

3'-0" OF FLEXIBLE METALLIC SEALTILE CONDUIT MAY BE USED TO

EXTERIOR EQUIPMENT.

5. ALL UNDERGROUND RACEWAY TO BE SCH 40 PVC. BURIAL DEPTH

FOR SERVICE CONDUITS TO BE PER AEP REQUIREMENTS. ALL

OTHER CONDUIT BURIAL DEPTHS PER 2020 NEC.

6. VERIFY ALL FIELD CONDITIONS AND MEASUREMENTS PRIOR TO

CONSTRUCTION. COORDINATE ALL WORK WITH OTHER TRADES.

7. PERFORM ALL WORK IN ACCORDANCE WITH 2020 NEC.

8. INSTALL NEW SERVICES IN ACCORDANCE WITH AEP REQUIREMENTS.

OBTAIN ALL INSPECTIONS REQUIRED.

9. CONTRACTOR IS RESPONSIBLE FOR HAVING ALL UNDERGROUND

UTILITIES LOCATED PRIOR TO BEGINNING OF ANY EARTHWORK.

ELECTRICAL NOTES

1. ELECTRIC SERVICE BACKBOARD THIS LOCATION. SEE

SHEET E502.

2. ELECTRIC BACKBOARD - MOBILE HOME AREA THIS

LOCATION. SEE SHEET E502.

3. INSTALL PANEL/SWITCH ON TREATED WOOD

BACKBOARD MOUNTED ON 6X6 POSTS ANCHORED IN 10'

SONOTUBE FILLED W/ 3,500 PSI CONCRETE.

SHEET NOTES

PA OFFICE:

429 LAUREL RUN ROAD

CARMICHAELS, PA 15320

PH: (724) 966-5655

WV OFFICE:

54 WEST RUN RD.

MORGANTOWN, WV 26508

PH: (304) 291-2234

SHEET NAME:

MILLER ENGINEERING INC.

COPY RIGHT:

CHECKED BY:

DRAWN BY:

DESIGNED BY:

BCM

SEAL:

CONSULTANT:

PROJECT NAME:

PROJECT OWNER:

PROJECT STATUS:

PROJECT NUMBER:

ORIGINAL PAGE SIZE: 22x34

E101

ELECTRICAL SITE

PLAN

12 SEPT 2025

TRT

BCM

25015

CONSTRUCTION

DOCUMENTS

WEST VIRGINIA ARMY

NATIONAL GUARD

PATRIOT GUARDANS

ELECTRICAL

SERVICE

N O

D

E S

C R

IP

T

IO

N

D A

T E

1" = 60'-0"

ELECTRICAL SITE PLAN

FEEDER SCHEDULE

TAG # SETS

CONDUCTOR SIZE(COPPER) CONDUCTOR SIZE(ALUMINUM)

CONDUIT SIZE

POWER & NEUTRAL GROUND POWER & NEUTRAL GROUND

A 1 4 - 400KCMIL #1/0 4 - 500KCMIL #3/0 5"

B 1 3 - #1/0 #6 3 - #4/0 #2 3"

C 1 3 - #6 #8 3 - #4 #6 2"

D 1 2 - #1 #6 2 - #2/0 #4 2"

E 1 4 - #2 #8 4 - #1/0 #6 2"

F 1 4 - #2/0 #4 4 - #4/0 #2 2-1/2"

G 1 3 - #2 #8 3 - #1/0 #6 2"

1. WIRING IS SHOWN ON DRAWINGS ONLY FOR SPECIFIC ROUTES OR

SPECIAL CONDITIONS.

2. WIRING AND CONDUIT OR SHALL BE REQUIRED FOR ALL OUTLETS

AND DEVICES. FOLLOW INDICATED CIRCUITS NUMBERS AND PANEL

DESIGNATION. OBTAIN PRIOR APPROVAL OF ENGINEER FOR

DEVIATIONS.

3. ALTHOUGH ALL BRANCH CIRCUIT WIRING IS NOT SHOWN, IT IS THE

INTENT OF THESE DOCUMENTS THAT A COMPLETE BRANCH CIRCUIT

WIRING SYSTEM BE INSTALLED. ALL NEUTRALS SHALL BE FULL

CAPACITY. THE USE OF SHARED OR COMMON NEUTRALS IS

PROHIBITED ON ALL ELECTRIC WIRING.

4. EXTERIOR WIRING IS TO BE THHN/THWN IN PVC CONDUIT. MAX. OF

3'-0" OF FLEXIBLE METALLIC SEALTILE CONDUIT MAY BE USED TO

EXTERIOR EQUIPMENT.

5. ALL UNDERGROUND RACEWAY TO BE SCH 40 PVC. BURIAL DEPTH

FOR SERVICE CONDUITS TO BE PER AEP REQUIREMENTS. ALL

OTHER CONDUIT BURIAL DEPTHS PER 2020 NEC.

6. VERIFY ALL FIELD CONDITIONS AND MEASUREMENTS PRIOR TO

CONSTRUCTION. COORDINATE ALL WORK WITH OTHER TRADES.

7. PERFORM ALL WORK IN ACCORDANCE WITH 2020 NEC.

8. INSTALL NEW SERVICES IN ACCORDANCE WITH AEP REQUIREMENTS.

OBTAIN ALL INSPECTIONS REQUIRED.

9. CONTRACTOR IS RESPONSIBLE FOR HAVING ALL UNDERGROUND

UTILITIES LOCATED PRIOR TO BEGINNING OF ANY EARTHWORK.

ELECTRICAL NOTES

UNDERGROUND480/277

UNDERGROUND

480/277

A

B

B

C

D

ROAD CROSSING

T X

-1

S W

-6

BASE BID

ALTERNATE #1

ALTERNATE #1

ALTERNATE #1

ALTERNATE #1

DPHN-1

D

PH

N -2

S W

-3

T X

-3

D P

L N

-1

T X

-2

S W

-4

SW

-1

SW

-2

SW-5

ROAD CROSSING

ROAD CROSSING

ROAD CROSSING

ROAD CROSSING

FUTURE COOLING BUILDING

PA OFFICE:

429 LAUREL RUN ROAD

CARMICHAELS, PA 15320

PH: (724) 966-5655

WV OFFICE:

54 WEST RUN RD.

MORGANTOWN, WV 26508

PH: (304) 291-2234

SHEET NAME:

MILLER ENGINEERING INC.

COPY RIGHT:

CHECKED BY:

DRAWN BY:

DESIGNED BY:

BCM

SEAL:

CONSULTANT:

PROJECT NAME:

PROJECT OWNER:

PROJECT STATUS:

PROJECT NUMBER:

ORIGINAL PAGE SIZE: 22x34

E102

ELECTRICAL SITE

PLAN

12 SEPT 2025

TRT

BCM

25015

CONSTRUCTION

DOCUMENTS

WEST VIRGINIA ARMY

NATIONAL GUARD

PATRIOT GUARDANS

ELECTRICAL

SERVICE

FEEDER SCHEDULE

TAG # SETS

CONDUCTOR SIZE(COPPER) CONDUCTOR SIZE(ALUMINUM)

CONDUIT SIZE

POWER & NEUTRAL GROUND POWER & NEUTRAL GROUND

A 1 4 - 400KCMIL #1/0 4 - 500KCMIL #3/0 5"

B 1 3 - #1/0 #6 3 - #4/0 #2 3"

C 1 3 - #6 #8 3 - #4 #6 2"

D 1 2 - #1 #6 2 - #2/0 #4 2"

E 1 4 - #2 #8 4 - #1/0 #6 2"

F 1 4 - #2/0 #4 4 - #4/0 #2 2-1/2"

G 1 3 - #2 #8 3 - #1/0 #6 2"

N O

D

E S

C R

IP

T

IO

N

D A

T E

1" = 60'-0"

ELECTRICAL SITE PLAN - PHOTO

OVERLAY

POWER CO. POLE

DPHN1

3Ø, 4W

277/480V

400A MCB

30 CKT

NEMA3R

SW-1

3P

480V

400A NF

NEMA 3R

S.E. RATED

5" CND W/ PULL STRING

A

TX-3

3Ø

480-208/120

75KVA

NEMA 3R

DPLN1

3Ø, 4W

120/208V

200A MCB

30 CKT

NEMA 3R

SW-3

3P

480V 100/90A F

NEMA 3R

TX-2

3Ø

480-208/120

45KVA

NEMA 3R

SW-4

3P

480V 60/60A F

NEMA 3R

DPHN2

3Ø, 4W

277/480V

150A MCB

30 CKT

NEMA 3R

#1/0 BARE CU

CAD WELD (TYP)

3/4" X 10' CU GRN ROD (TYP)

B

C

B

B

C

400A

METER

SOCKET

NEMA 3R

M

SW-2

3P 480V

400/300A F

NEMA 3R

AA

1Ø,240V 200A

METER

SOCKET

NEMA 3R

M

1Ø,240V 200A

METER

SOCKET

NEMA 3R

M

TX-1

1Ø

480-240/120

37.5KVA

NEMA 3R

D

#6 BARE CU

#6 BARE CU

#8 BARE CU

F

E

E

1Ø,240V 200A

METER

SOCKET

NEMA 3R

M

(2) 3" STUB UPS FOR FUTURE EXPANSION OF COOLING BUILDING

CONDUCTOR BY UTILITY

5/8" X 8' CU GRN ROD

3/4" X 10' CU GRN ROD

3/4" X 10' CU GRN ROD

SW-6

2P

480V 100/100A F

NEMA 3R

D

BASE BID ALTERNATE #1

G

NUMBER & SIZE OF

CONDUITS PER PLAN VIEWS

SATISFACTORY SOIL MATERIAL:

MATERIAL EXCAVATED FROM TRENCH

FREE OF STONES LARGER THAN 3" IN

SIZE AND FREE OF WET, FROZEN OR

ORGANIC MATERIALS.

TOPSOIL

RESTORE TO GRADE

6" WIDE MAGNETIC TAPE (RED)

LABELLED "ELECTRIC"

_3"

'36"

-12"

6" -6"

NUMBER & SIZE OF

CONDUITS PER PLANS

SATISFACTORY SOIL MATERIAL: MATERIAL

EXCAVATED FROM TRENCH FREE OF

STONES LARGER THAN 3" IN SIZE AND FREE

OF WET, FROZEN OR ORGANIC MATERIALS,

TAMPED ON 6" LIFTS TO A SUITABLE FILL.

3" GRAVEL

6" WIDE MAGNETIC TAPE

(RED) LABELED "ELECTRIC"

2"

4"

- 3

- 1

2" P40 PVC PIPE TO

DAYLIGHT w/ SCREEN

COVER FOR

DRAINAGE

#57 STONE BACKFILL CONDUIT NUMBER

AND SIZE PER

PLANS

PENTAGON BOLT

PENTAGON BOLT

TAPER SOIL OR

CONCRETE OVER 4"

LID, MIN.

ANSI TIER

LOOP CONDUCTORS IN

HANDHOLE, SIZE AND

NUMBER PER PLANS

QUAZITE BOX

M

IN

' D E

P T

H

GRADE1" MIN.

PA OFFICE:

429 LAUREL RUN ROAD

CARMICHAELS, PA 15320

PH: (724) 966-5655

WV OFFICE:

54 WEST RUN RD.

MORGANTOWN, WV 26508

PH: (304) 291-2234

SHEET NAME:

MILLER ENGINEERING INC.

COPY RIGHT:

CHECKED BY:

DRAWN BY:

DESIGNED BY:

BCM

SEAL:

CONSULTANT:

PROJECT NAME:

PROJECT OWNER:

PROJECT STATUS:

PROJECT NUMBER:

ORIGINAL PAGE SIZE: 22x34

E501

ELECTRICAL DETAILS

12 SEPT 2025

TRT

BCM

25015

CONSTRUCTION

DOCUMENTS

WEST VIRGINIA ARMY

NATIONAL GUARD

PATRIOT GUARDANS

ELECTRICAL

SERVICE

N O

D

E S

C R

IP

T

IO

N

D A

T E

DRAWING NOT SCALABLE

SERVICE ONE-LINE

FEEDER SCHEDULE

TAG # SETS

CONDUCTOR SIZE(COPPER) CONDUCTOR SIZE(ALUMINUM)

CONDUIT SIZE

POWER & NEUTRAL GROUND POWER & NEUTRAL GROUND

A 1 4 - 400KCMIL #1/0 4 - 500KCMIL #3/0 5"

B 1 3 - #1/0 #6 3 - #4/0 #2 3"

C 1 3 - #6 #8 3 - #4 #6 2"

D 1 2 - #1 #6 2 - #2/0 #4 2"

E 1 4 - #2 #8 4 - #1/0 #6 2"

F 1 4 - #2/0 #4 4 - #4/0 #2 2-1/2"

G 1 3 - #2 #8 3 - #1/0 #6 2"

DRAWING NOT SCALABLE

BURIED CONDUIT DETAIL

DRAWING NOT SCALABLE

ROAD CROSSING DETAIL

DRAWING NOT SCALABLE

IN GROUND BOX DETAIL

PANEL

SWITCH

8' - 0"

2"X12" TREATED BOARD (TYP)

6"X6" TREATED POST (TYP)

INSTALL POST IN 10"

SONOTUBE & FILL WITH 3,500

PSI CONCRETE.

ARRANGE ELECTRICAL EQUIPMENT AS NEEDED IN FIELD.

NOTE: ONE POST WILL BE

REPLACED W/ 30' UTILITY POLE

AT SERVICE #4

TRANSFORMER

3,500 PSI CONCRETE PAD

CONSTRUCT GALVANIZED UNI-STRUT RACK.

COORDINATE SPACING PER MFR'S INSTRUCTIONS

& MOUNTING CONNECTION LOCATIONS OF

ELECTRICAL EQUIPMENT.

METER

NON-FUSED

DISCONNECT

13' - 0"

6"Ø GALVANIZED POST (TYP)

INSTALL POST IN 10"

SONOTUBE & FILL WITH 3,500

PSI CONCRETE.

FUSED

DISCONNECT

TO UTILITY POLE

VERIFY TERMINATION LOCATION WITH UTILITY REQUIREMENTS

PA OFFICE:

429 LAUREL RUN ROAD

CARMICHAELS, PA 15320

PH: (724) 966-5655

WV OFFICE:

54 WEST RUN RD.

MORGANTOWN, WV 26508

PH: (304) 291-2234

SHEET NAME:

MILLER ENGINEERING INC.

COPY RIGHT:

CHECKED BY:

DRAWN BY:

DESIGNED BY:

BCM

SEAL:

CONSULTANT:

PROJECT NAME:

PROJECT OWNER:

PROJECT STATUS:

PROJECT NUMBER:

ORIGINAL PAGE SIZE: 22x34

E502

ELECTRICAL DETAILS

12 SEPT 2025

TRT

BCM

25015

CONSTRUCTION

DOCUMENTS

WEST VIRGINIA ARMY

NATIONAL GUARD

PATRIOT GUARDANS

ELECTRICAL

SERVICE

N O

D

E S

C R

IP

T

IO

N

D A

T E

DRAWING NOT SCALABLE

ELECTRIC POWER BACKBOARD - MOBILE HOME AREA

DRAWING NOT SCALABLE

ELECTRIC SERVICE BACKBOARD - METERING POINT

(2) 5" CND

PA OFFICE:

429 LAUREL RUN ROAD

CARMICHAELS, PA 15320

PH: (724) 966-5655

WV OFFICE:

54 WEST RUN RD.

MORGANTOWN, WV 26508

PH: (304) 291-2234

SHEET NAME:

MILLER ENGINEERING INC.

COPY RIGHT:

CHECKED BY:

DRAWN BY:

DESIGNED BY:

BCM

SEAL:

CONSULTANT:

PROJECT NAME:

PROJECT OWNER:

PROJECT STATUS:

PROJECT NUMBER:

ORIGINAL PAGE SIZE: 22x34

E601

ELECTRICAL

SCHEDULES

12 SEPT 2025

TRT

BCM

25015

CONSTRUCTION

DOCUMENTS

WEST VIRGINIA ARMY

NATIONAL GUARD

PATRIOT GUARDANS

ELECTRICAL

SERVICE

N O

D

E S

C R

IP

T

IO

N

D A

T E

DISCONNECT SWITCH SCHEDULE

TAG SERVES POLES VOLTS SIZE/FUSE NEMA ENCLOSURE TYPE

SW-1 POWER CO METER 3 480 V 400A/NF TYPE 3R NON-FUSED, SERVICE RATED

SW-2 SERVICE DISCONNECT 3 480 V 400A/300A TYPE 3R FUSED, SERVICE RATED

SW-3 T-4 3 480 V 100A/90A TYPE 3R FUSED

SW-4 T-3 3 480 V 60A/60A TYPE 3R FUSED

SW-5 GREENHOUSE 2 240 V 30A/20A TYPE 3R FUSED

SW-6 TX-1 1 480 V 100A/100A TYPE 3R FUSED

TRANSFORMER SCHEDULE

TAG PHASE PRIMARY SECONDARY RATING ENCLOSURE

TX-1 1 480 V 120/240 V 37.5 KVA TYPE 3R

TX-2 3 480 V 120/208 V 45 KVA TYPE 3R

TX-3 3 480 V 120/208 V 75 KVA TYPE 3R

100% RATED MAIN BREAKER

Notes:

29 30 27 28 25 26 23 24 21 22 19 20 17 18 15 16 13 14 11 12 9 10 7 8 5 ... 1 -- Space 6 3 ... 4

DPHN-2 120 A 3

2 90 A TX-1

CKT Circuit Description Trip Poles Poles Trip Circuit Description CKT

ENCLOSURE: NEMA 3R MAIN TYPE: MCB

WIRES: 4 MAIN: 300 A

VOLTS: 480/277 Wye PHASES: 3

Branch Panel: DPHN-1

Notes:

29 30 27 28 25 26 23 24 21 22 19 20 17 18 15 16 13 14 11 12 9 10 7 8 5 ... 6 3 ... 4

TX-2 60 A 3

3 90 A TX-3

CKT Circuit Description Trip Poles Poles Trip Circuit Description CKT

ENCLOSURE: NEMA 3R MAIN TYPE: MCB

WIRES: 4 MAIN: 120 A

VOLTS: 480/277 Wye PHASES: 3

Branch Panel: DPHN-2

(1) VERIFY TRIP RATING W/ OWNER EQUIPMENT

Notes:

29 30 27 28 25 26 23 24 21 22 19 20 17 18 15 16 13 14 11 12 9 10 7 ... 8

MOBILE HOME 3 (1) 200 A 2

... 6

3 ... 4

MOBILE HOME 1 (1) 200 A 2

2 200 A MOBILE HOME 2 (1)

CKT Circuit Description Trip Poles Poles Trip Circuit Description CKT

ENCLOSURE: NEMA 3R MAIN TYPE: MCB

WIRES: 4 MAIN: 200 A

VOLTS: 120/208 Wye PHASES: 3

Branch Panel: DPLN-1

Sheets
E101 - ELECTRICAL SITE PLAN
E501 - ELECTRICAL DETAILS
E502 - ELECTRICAL DETAILS
E601 - ELECTRICAL SCHEDULES

File details come from the government source that posted it. Updated .