This is a Questions & Answers document for the CCAP-DDH Clean Agent Inspection Services solicitation, dated 22 June 2026, for a base year plus two option years contract.
The document clarifies key requirements for inspecting one existing Clean Agent Fire Suppression System serving a data center/server room. The system comprises nine FM-200 (PROINERT2) tanks, 16 smoke detectors (nine ceiling-mounted, seven sub-floor), two pull stations, two abort stations, four agent strobes, two fire strobes, one control panel, and two batteries. Pre-action sprinkler testing is not applicable as no sprinkler system is present. The document confirms that digital as-built drawings will not be provided in the solicitation due to proprietary information restrictions, though such documents were located on-site during a visit. One question regarding Monaco MAAP+ Fire Alarm Control Panel testing requirements—specifically whether a Monaco-certified technician or qualified fire protection technician is acceptable—received no answer from the government. The RFQ response due date has been extended to Thursday, 25 June 2026.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
CCAP-DDH 22 June 2026
Clean Agent Inspection Services Base plus 2 Option Year
Question & Answer
Questions:
1. Could you please confirm whether the requirement is for one existing Clean Agent Fire Suppression System serving the data center/server room?
Answer: Yes, “one existing Clean Agent Fire Suppression System serving the data center/server room”
2. For pricing purposes, are system/device quantities available? Specifically, the number of clean agent cylinders/tanks, agent type/quantity, smoke detectors, pull stations, abort stations, horns/strobes/notification devices, and control panels included in the inspection.
Answer: 9 Tanks FM-200 (PROINERT2), 9 Smoke detectors in the celling/7 in the sub floor, 2 pull stations, 2 abort stations, 4 Agent strobes, 2 Fire Strobes, 1 control panel, 2 batteries.
3. The Statement of Work mentions pre-action sprinkler testing “if applicable.” Could you please confirm whether the pre-action sprinkler riser inspection and flow test should be included in the fixed-price quote?
Answer: No sprinkler system.
4. Could you please confirm whether the Monaco MAAP+ Fire Alarm Control Panel testing requires a Monaco-certified or manufacturer-authorized technician, or if a qualified fire protection/fire alarm technician may perform this work in coordination with the Fort Huachuca Fire Department?
Answer: Unable to get an answer to this question.
5. During our site visit, we located as-built drawings in the room and discussed obtaining digital copies of those documents, as well as the inspection documentation from the previous inspection completed in February 2026. As these documents are important for accurately evaluating the system and developing a comprehensive proposal, we wanted to follow up on their availability.
Answer: Digital drawings will not be included in the solicitation as it is proprietary information.
6. During our discussion, it was also mentioned that the site would work on providing the digital as-built drawings and that consideration was being given to extending the RFP due date until next week, contingent upon receipt of the Inergen system documentation.
Answer: Digital drawings will not be included in the solicitation as it is proprietary information.
7. Could you please confirm the revised expectations and timeline for the RFP, including whether the due date will be extended and when we can expect to receive the requested documentation?
Answer: The RFQ has been Extended until Thursday 25 June 2026.