This document is a facility management and safety instruction guide for the Fire Suppression System (FSS) in Building 55350, EMETF Data Center Room 163, transmitter #1175 at Fort Huachuca.

The FSS utilizes model FST-951 detectors, with seven units mounted beneath the raised floor and nine in the ceiling throughout the data center. Floor tiles marked with "SD" labels and additional tape labeled "Suppression System Det." indicate detector locations. Before conducting cleaning or maintenance activities that may disturb the system, personnel must contact the Fort Huachuca Fire Alarm station at 533-5059 and allow five minutes or the time allotted by the dispatcher. To prevent accidental discharge, the suppression alarm must be disabled by turning the key on the suppression disconnect switch near the tanks to "Disarmed." All detectors exposed to dust or environmental elements must be covered during cleaning, then uncovered after completion and dust clearance. The alarm must clear before the switch is returned to "Armed" position. After re-arming, personnel must contact the Fire Alarm Department at 533-5059 to restore the system to normal operations. The alarm system may require reset through the EMETF system in room 108 office before resetting the Data Center FSS alarm. Special Systems contact Scott Pearce (378-3154 ext 4) is available for local Sierra Vista support. FSS inspections are required every six months.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Fire Suppression System (FSS)

Bldg 55350 EMETF Data Center Rm 163, transmitter #1175.

Cleaning under floor may set off sensors or detectors (model FST-951) for FSS.

There are seven under the raised floor and nine in the ceiling for the Data Center.

Floor tiles are labeled (SD) where detectors are mounted and located below ceiling detectors. Additional tape identifies floor sensors labeled “Suppression System Det. “

There are building sensors, however not identified or labeled by red tape and conduit markings.

If planning to clean or disturb FSS, contact Ft. Huachuca Fire Alarm station/host, 533-5059.

Notify them this building and transmitter #1175, allow 5 minutes or time allotted from dispatcher.

Disable FSS suppression alarm, turn key on suppression disconnect switch near tanks to “Disarmed”.

Alarm will sound on panel, but system will not discharge while in disarmed position.

Cover all detectors that will be exposed to dust or elements that may be affected.

After cleaning complete and dust has cleared, remove covered detectors.

Ensure alarm has cleared, DO NOT TURN TANKS or DISARMED switch back to normal unless cleared.

Return key position back to ARMED location and contact Fire Alarm Department, 533-5059 and notify alarm is to be set back to normal.

Alarm system may require reset to EMETF system in room 108 office then to Data Center FSS alarm.

Local Sierra Vista possible contact w/Special Systems Scott Pearce. (378-3154 ext 4)

FSS inspections due every 6 months.