Mansfield RFI Answers 4.doc

DOC document 31 KB Posted

Attached to
MANSFIELD AFRC AND FMS Federal contract opportunity
Solicitation number
W91364-09-B-0001
Issued by
Department of the Army Ohio Army National Guard

About this file

Amendment 4 Answers to Mansfield RFI's 4 RFI's that were missed.

View the file

Other files for this federal contract opportunity

Other files attached to MANSFIELD AFRC AND FMS, newest first.
File Type Posted
Bid Abstract MANGB AFRC.xls XLS spreadsheet
Mansfield RFI Answers 3.doc DOC document
Mansfield RFI Answers 2.doc DOC document
Mansfield RFI Answers 1.doc DOC document
Mansfield Pre-bid Mtg Attendees.xls XLS spreadsheet
SF 24.pdf PDF
MNSF_06_Arch_FMS_v1.pdf PDF
MNSF_16_Elec_FMS.pdf PDF
MNSF_12_FirePro.pdf PDF
4. Mansfield Specs V3 —
3. Mansfield Specs V2 —
MNSF_07_Arch_FMS_v2.pdf PDF
MNSF_13_Elec_General.pdf PDF
MNSF_04_Arch_AFRC_v1.pdf PDF
MNSF_14_Elec_AFRC_v1.pdf PDF
MNSF_15_Elec_AFRC_v2.pdf PDF
MNSF_03_Civil_v2.pdf PDF
MNSF_01_Cover_and_Index.pdf PDF
MNSF_11_Plumb.pdf PDF
MNSF_09_Mech_AFRC.pdf PDF
MNSF_02_Civil_v1.pdf PDF
MNSF_08_Struct.pdf PDF
MNSF_05_Arch_AFRC_v2.pdf PDF
2. Mansfield Specs V1 —
bidding instruction.pdf PDF
09-B-0001.doc DOC document
Show all 26

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

PAGE

Mansfield RFI Answers #4

THIS ANSWERS SEVERAL RFI’S THAT WERE PREVIOUSLY OVERLOOKED.

THERE ARE NOW FOUR (4) AMENDMENTS; ALL FOUR (4) MUST BE ACKNOWLEDGED ON YOUR PROPOSAL.

1. Question:- Specification 331216 Utility Valves and Accessories specifies the use of double disc gate valves for the water system. I have spoken with both American Flow Control as well as Mueller regarding this specification. Neither of those manufacturers make a double disc gate valve in 3”-10”. Is the use of a resilient wedge gate valve acceptable?

Response: This would be acceptable.

2. Question:- Specification 331216 Utility Valves and Accessories as well as detail 8 on C502 call for the valve boxes to consist of a cast iron cover, lid and base casting with a 6” ductile iron shaft. The outside diameter of 6” DIP is 6.90 inches. The standard #6 cast valve box base has a clear opening of 7 inches. Is it the intent to have the 6 inch shaft slip through the valve box base? Would the use of a 3pc valve box, manufactured by one of the approved manufacturers be acceptable?

Response: The 3pc valve box would be acceptable. Verification with the Government would be required.

3. Question: Specification 331100 Pressure Pipe indicates that pressure class 250 is to be used for the 6 inch fire water and AWWA C900 PVC is to be used for the water in sizes 2 inch trough 10 inches with a minimum pressure class of 250 psi. The thickest wall AWWA C900 PVC pipe that is currently manufactured is DR 14 which is currently classified as a 200 psi pressure class. Is AWWA 900 DR 14 acceptable?

Response: Approved.

4. Question: Plan sheet C300 and sheet C303 show four roof drain connections to the proposed 12 inch and 18 inch RCP. I have not been able to determine what size pipe is required at these locations.

Response: Pipe shall be size sufficiently to handle the downspouts as shown on the architectural plan F-A102.