Mansfield RFI Answers 4.doc
DOC document 31 KB Posted
- Attached to
- MANSFIELD AFRC AND FMS Federal contract opportunity
- Solicitation number
- W91364-09-B-0001
About this file
Amendment 4 Answers to Mansfield RFI's 4 RFI's that were missed.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Bid Abstract MANGB AFRC.xls | XLS spreadsheet | |
| Mansfield RFI Answers 3.doc | DOC document | |
| Mansfield RFI Answers 2.doc | DOC document | |
| Mansfield RFI Answers 1.doc | DOC document | |
| Mansfield Pre-bid Mtg Attendees.xls | XLS spreadsheet | |
| SF 24.pdf | ||
| MNSF_06_Arch_FMS_v1.pdf | ||
| MNSF_16_Elec_FMS.pdf | ||
| MNSF_12_FirePro.pdf | ||
| 4. Mansfield Specs V3 | — | |
| 3. Mansfield Specs V2 | — | |
| MNSF_07_Arch_FMS_v2.pdf | ||
| MNSF_13_Elec_General.pdf | ||
| MNSF_04_Arch_AFRC_v1.pdf | ||
| MNSF_14_Elec_AFRC_v1.pdf | ||
| MNSF_15_Elec_AFRC_v2.pdf | ||
| MNSF_03_Civil_v2.pdf | ||
| MNSF_01_Cover_and_Index.pdf | ||
| MNSF_11_Plumb.pdf | ||
| MNSF_09_Mech_AFRC.pdf | ||
| MNSF_02_Civil_v1.pdf | ||
| MNSF_08_Struct.pdf | ||
| MNSF_05_Arch_AFRC_v2.pdf | ||
| 2. Mansfield Specs V1 | — | |
| bidding instruction.pdf | ||
| 09-B-0001.doc | DOC document |
Show all 26
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PAGE
Mansfield RFI Answers #4
THIS ANSWERS SEVERAL RFI’S THAT WERE PREVIOUSLY OVERLOOKED.
THERE ARE NOW FOUR (4) AMENDMENTS; ALL FOUR (4) MUST BE ACKNOWLEDGED ON YOUR PROPOSAL.
1. Question:- Specification 331216 Utility Valves and Accessories specifies the use of double disc gate valves for the water system. I have spoken with both American Flow Control as well as Mueller regarding this specification. Neither of those manufacturers make a double disc gate valve in 3”-10”. Is the use of a resilient wedge gate valve acceptable?
Response: This would be acceptable.
2. Question:- Specification 331216 Utility Valves and Accessories as well as detail 8 on C502 call for the valve boxes to consist of a cast iron cover, lid and base casting with a 6” ductile iron shaft. The outside diameter of 6” DIP is 6.90 inches. The standard #6 cast valve box base has a clear opening of 7 inches. Is it the intent to have the 6 inch shaft slip through the valve box base? Would the use of a 3pc valve box, manufactured by one of the approved manufacturers be acceptable?
Response: The 3pc valve box would be acceptable. Verification with the Government would be required.
3. Question: Specification 331100 Pressure Pipe indicates that pressure class 250 is to be used for the 6 inch fire water and AWWA C900 PVC is to be used for the water in sizes 2 inch trough 10 inches with a minimum pressure class of 250 psi. The thickest wall AWWA C900 PVC pipe that is currently manufactured is DR 14 which is currently classified as a 200 psi pressure class. Is AWWA 900 DR 14 acceptable?
Response: Approved.
4. Question: Plan sheet C300 and sheet C303 show four roof drain connections to the proposed 12 inch and 18 inch RCP. I have not been able to determine what size pipe is required at these locations.
Response: Pipe shall be size sufficiently to handle the downspouts as shown on the architectural plan F-A102.