H01_Lighting_Plan.pdf

PDF 580 KB Posted

Attached to
Underground Utilities Federal contract opportunity
Solicitation number
W912SV-18-B-6002
Issued by
Department of the Army Massachusetts Army National Guard

View the file

Other files for this federal contract opportunity

Other files attached to Underground Utilities, newest first.
File Type Posted
B01_Abstract_18B6002.pdf PDF
B01_Bid_Opening_Sign-in_W912SV-18-B-6002.pdf PDF
A07_W912SV-18-B-6002_RFIs_28_Aug_2018.pdf PDF
H01_B165_IZZEA_AREA_OSP_Drawing.pdf PDF
A07_W912SV-18-B-6002-0002_(SF30_copy).pdf PDF
H01_Plan_of_Location_of_Existing_COMM_Underground_Structures.pdf PDF
H01_SECTION_265700.pdf PDF
A07_W912SV-18-B-6002-0002_(conform_copy).pdf PDF
H01_B170_AREA_OSP_Drawing.pdf PDF
H01_B155_AREA_OSP_Drawing.pdf PDF
A07_W912SV-18-B-6002_RFIs_22_Aug_2018.pdf PDF
A01_SOW_Underground_Utilities_REVISED_22AUG18.pdf PDF
H01_B169_MILCON_AREA_OSP_Drawing.pdf PDF
A07_W912SV-18-B-6002-0001_(SF30_copy).pdf PDF
A07_JBCC_NCIC_Access_Form_W912SV-18-B-6002_BID_OPENING.pdf PDF
A07_W912SV-18-B-6002_RFIs_15_Aug_2018.pdf PDF
A07_W912SV-18-B-6002-0001_(conform_copy).pdf PDF
A07_Pre-Bid_Slides_18B6002_Underground_Utilities.pdf PDF
A07_Pre-Bid_Conference_&_Site_Visit_Minutes_18B6002_Underground_Utilties.pdf PDF
A07_Pre-Bid_Conference_Site_Visit_Sign-in_18B6002_Underground_Utilties.pdf PDF
A07_JBCC_NCIC_Access_Form_W912SV-18-B-6002_BID_OPENING.pdf PDF
A07_W912SV-18-B-6002.pdf PDF
A07_JBCC_NCIC_Access_Form_W912SV-18-B-6002.pdf PDF
Show all 23

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

P a g e | 1 of 11

SECTION 265600

LIGHTING REQUIREMENTS

1. GENERAL

1.1 RELATED DOCUMENTS

1.1.1 Drawings, general and technical provisions of the Contract, including General and

Supplementary Conditions and other Division 01 Specifications Sections, apply to this Section.

This specification section supercedes lighting references indicated on various notes on the drawings.

1.1.2 REFERENCES

The publications listed below form a part of this specification to the extent referenced.

Publications are referenced within the text by their basic designation only.

AMERICAN NATIONAL STANDARDS INSTITUTE

(ANSI)

ANSI C62.41.1-2002 IEEE Guide on the Surge Environment in Low-Voltage

(1000 V and less) AC Power Circuits

ANSI C62.41.2-2002 IEEE Recommended Practice on Characterization of

Surges in Low-Voltage (1000 V and less) AC Power

Circuits

ANSI C78.377-2008 Specifications for the Chromaticity of Solid State Lighting

Products for Electric Lamps

ANSI C136.31-2010 Roadway and Area Lighting Equipment – Luminaire

Vibration

ANSI C136.3-2005 (R2009) Roadway and Area Lighting Equipment – Luminaire

Attachments

ILLUMINATING ENGINEERING SOCIETY OF NORTH AMERICA (IESNA)

HB-10-11 IES Lighting Handbook

LM-79-08 Electrical and Photometric Measurements of Solid-Sate

Lighting Products

LM-80-08 Measuring Lumen Maintenance of LED Light Sources

RP-8 Roadway Lighting ANSI Approved

INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE)

IEEE STDSPCD1155 IEEE Standards Dictionary: Glossary of Terms &

Definitions

INTERNATIONAL ELECTROTECHNICAL COMMISSION (IEC)

P a g e | 2 of 11

IEC 60529-2004 Degrees of Protection Provided by Enclosures (IP Code)

IEC 60068-2-30 Environmental Testing - Part 2–30: Tests - Test Db:

Damp heat, cyclic (12 h + 12 h cycle)

IEC 60068-2-14 Environmental Testing. Tests. Test N. Change of temperature

NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA)

NEMA C78.377-2008 American National Standard for Electric

Lighting (SSL) Products NEMA C136.10 American National Standard for Roadway and Area king-Type Photocontrol Devices

Interchangeability and Testing

NEMA IC S6 Industrial Control and Systems: Enclosures

WD 7-2000 NEMA Guide Publication: Occupancy Motion Sensors

NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)

NFPA 70 National Electrical Code (NEC)

UNDERWRITERS LABORATORIES

(UL)

UL 773 Standard for Plug-In, Locking Type Photocontrols for Use with Area Lighting

UL 773A Standard for Nonindustrial Photoelectric Switches for

Lighting Control

UL 1310 Standard for Class 2 Power Units

1.2 SUMMARY

1.2.1 The exterior lighting plan(s) for this project shall be generated by the general contractor.

The general contractor shall provide the services of a professional lighting designer who shall use the parameters and requirements as described within this section for the overall lighting layout of the project. The lighting plans shall be completed, and ready for approval within two

(2) months of the start of the project.

1.2.2 The design shall include provisions for Light-Emitting Diode (LED) lighting applications for roadway lighting and sidewalk illumination where the construction work is taking place. That includes: Izzea Street, Granville Avenue, Corn Street, Chavez Street, Reichart Street, Generous

P a g e | 3 of 11

Street, Easton Street and Reilly Street. Some areas will require primarily street lighting and other areas shall require sidewalk illumination. Also, provide for exterior lighting for new “Perimeter

Loop” layout per attached plan. Provide for approximately forty-five (45) exterior street lights where designated by lighting professional design. Provide for an additional eighty-five (85) exterior sidewalk illumination pole mounted fixtures. Using the quantity of lighting fixtures indicated or as required by the lighting design, provide professionally designed lighting plans.

Lighting plans shall include all required hand-holes, properly sized conduit, wiring, lighting panels, etc. Utilize the new underground primary lighting feeds to power up the new lighting.

There is one lighting panel shown on the one-line diagram plan, however an additional (or more)

15kV lighting panel (s) may be necessary. Lighting plans for construction must be approved by

Civil Engineering and the Base Commander.

1.2.3 Contractor shall procure the services of a qualified lighting designer with proven skills and knowledge related to the calculation, design, construction, installation, and operation of lighting systems; and has received training concerning types and application of light sources, field measurement equipment, luminaries, and their placement, to comply with applicable standards and criteria.

1.2.4 Contractor’s LED fixture manufacturers shall submit written certification that their luminaires comply with Part 2, PRODUCTS of this section. The certification shall be included in the first submittal from the contractor. Incomplete and/or incorrect information is unacceptable and will result in the light fixture failing to meet Air Force requirements.

1.3 WARRANTIES

1.3.1 LED luminaire warranties shall begin on the date of final acceptance of the installation by the contracting officer or designated representative, as executed by DD Form 1354, Transfer and

Acceptance of DOD Real Property.

1.3.2 Provide a five (5) year finish warranty on all paint finishes. Finish warranty shall include warranty against failure or substantial deterioration such as blistering, cracking, peeling, chalking, or fading. Provide a five (5) year warranty on all lighting poles. On-site replacement includes transportation, removal, and installation of new products.

1.3.3 The LED manufacturer shall provide a written five-year on-site replacement warranty for defective or non-starting power supply units and LED source assemblies, which include, but are not limited to, LED packages, LED arrays, LED modules, LED dies, encapsulates, and phosphors.

1.3.4 The LED manufacturer shall provide a written five-year on-site replacement warranty for any LED source assembly, package, array, or module, which does not include the power supply, against 10% or more of the individual LEDs in that assembly, package, array, or module failing to illuminate.

1.3.5 The LED manufacturer warranty period shall begin on the date of final acceptance, as executed by a DD Form 1354. The contractor will provide the contracting officer with the signed warranty certificates prior to final payment.

P a g e | 4 of 11

1.4 SUBMITTALS Government approval is required for items (a) through (c).

1.4.1 Shop drawings.

a. Certified lighting design incorporating requirements outlined in this section. Consider possible snow and ice buildup. The luminaire fixture weight and effective projected area shall not exceed the pole’s requirements for all dynamic loading; e.g. wind, snow, ice.

b. IESNA LM-79 report on manufacturer’s standard production model luminaire to include:

Testing agency, report number, date, manufacturer’s name, catalog number, LED driver, drive current, ambient temperature

Luminaire efficacy (lumens/watt), minimum light output, zonal lumen density

Color qualities (CCT, CRI, chromaticity)

ANSI C78.377 Duv

Electrical measurements (input voltage, input current, input power [watts])

Spectral distribution over visible wavelengths (mW/nm)

Absolute intensity candlepower (cd) summary table

Isocandela plot

Luminance summary table

Illuminance – point to point

Illuminance – cone of light plot

Illuminance – isofootcandle plot

Illuminance – roadway isofootcandle plot (if streetlight)

Picture of sample

Photometric file, including BUG rating

IESNA LM-80 report on LED package, array, or module, to include:

Testing agency, report number, date, type of equipment, and LED lightsource being tested.

All data required by IESNA LM-80.

Note: Test laboratories for the IESNA LM-79 and IESNA LM-80 reports shall be one of the following:

National Voluntary Laboratory Accreditation Program (NVLAP) - accredited for solid-state lighting testing as part of the Energy-Efficient Lighting Products laboratory accreditation program.

One of the qualified labs listed on the Department of Energy (DOE) SSL web site (http://www1.eere.energy.gov/buildings/ssl/test_labs.html).

A manufacturer’s in-house lab that meets the following criteria:

(1) Manufacturer has been regularly engaged in the design and production of http://www1.eere.energy.gov/buildings/ssl/test_labs.html

P a g e | 5 of 11

HID roadway and area luminaires and the manufacturer’s lab has been successfully certifying these fixtures for a minimum of 15 years,

(2) Annual equipment calibration, including photometer calibration, in accordance with the NIST.

c. Product Certificates:

Submitted by the installing contractor, certification from the manufacturer indicating the expected useful life of the provided luminaires. The useful life shall be directly correlated to the IESNA LM-80 test data, interpreted for IESNA TM-21.

Minimum LED life shall be 50,000 hours.

Manufacturer certification that fixture meets recyclability requirements.

Manufacturer certification that the luminaires satisfy ―Part 1-4 General

Requirements‖ and ―Part 2 Products‖ portions of this specification.

2 PRODUCTS

2.1 Provide Exterior LED Luminaires. Suggested manufacturers are:

Hubbell Outdoor Lighting

Spaulding Lighting

Devine Lighting

Whiteway Lighting

Beacon

2.1.1 Prohibited Applications.

2.1.2 Solar-powered or combination solar- and utility-powered LED luminaires are prohibited because of associated battery installation, performance, and maintenance problems.

2.1.3 LED luminaires that require remote mounting of any component needed for operation — such as ballasts, drivers, light engine electronics, or other controls — are not allowed.

Components needed to make the fixture operational shall be integral to the fixture housing.

2.1.4 Metal halide, mercury vapor, or fluorescent fixture enclosures — are prohibited. Only new, complete-assembly LED luminaires shall be used.

2.2 Technical Specifications. LED fixture design, component specifications, submittals, and installation criteria shall comply with UFC 3-530-01, IESNA standards, and the requirements in

Paragraph 3.

2.3 Surge Protection. Surge protection internal to the luminaire shall comply with Paragraph

2.4 LUMINAIRES

P a g e | 6 of 11

2.4.1 Provide luminaires complete with LED light source and power supply unit. Details, shapes, and dimensions are indicative of the general type desired but are not intended to restrict selection to luminaires of a particular manufacturer. Luminaires of similar design, light distribution and brightness characteristics, and of equal finish and quality will be acceptable.

2.4.2 GENERAL PRODUCT REQUIREMENTS

2.4.2.1 Luminaires shall be UL-listed for wet locations and wiring cavities shall be field-accessible for service or repair needs.

2.4.2.2 Luminaires must be rated for operation in ambient temperatures from -30 °C to

+50 °C.

2.4.2.3 Luminaires shall be full cutoff or fully-shielded as defined by IESNA RP-8.

Alternatively, the full cutoff can be validated by meeting the following IESNA TM-15 B-U-G ratings (backlight, uplight, and glare):

Maximum uplight (U) rating of U1.

Maximum glare (G) rating equal to G2.

Optical systems for roadway and area luminaires, including the driver, shall be sealed and rated for IP 66 as defined in IEC 60529.

Luminaires shall be fully assembled and electrically tested prior to shipment from factory.

2.4.2.4 Mounted luminaires, a wildlife shield shall be included on the fixture to prevent wildlife access.

The color of the luminaires shall be bronze, unless specified otherwise.

Coatings shall be capable of surviving ASTM B117 salt fog environment for 1000 hours minimum without blistering or peeling.

Coatings shall demonstrate gloss retention greater than or equal to 90% for 1000 hours’ exposure QUV test per ASTM G154 UVB313, 4-hour UV-B 60

°C/4-hour condensation 50 °C.

Luminaires shall be fully functional after testing for thermal shock according to IEC

60068-2-14 and be fully functional after testing.

Luminaires shall be tested according to IEC 60068-2-30, damp heat, steady state, for high humidity and high temperatures and be fully functional after testing.

Luminaire arm bolts shall be 304 stainless steel or zinc-plated steel.

P a g e | 7 of 11

If a lens not integral to the luminaire is used, the optical enclosure (lens/window) shall be constructed from clear and UV-resistant acrylic or UV- treated tempered glass.

If the lens is integral to the luminaire, the lens shall be UV treated tempered glass.

At least 80% of the luminaire material by weight shall be recyclable at the manufacturer’s stated end of life.

Luminaires shall produce a minimum efficacy of 70 lumens per watt.

Luminaires shall incorporate modular electrical connections and be constructed to allow replacement of all or part of the optics, heat sinks, power supply units, and electrical components using only a simple tool, such as a screwdriver.

Luminaires shall bear a nameplate inscribed with the manufacturer's name, address, model number, date of manufacture, and serial number, securely affixed in a conspicuous place. The nameplate of the distributing agent will not be acceptable.

Roadway and area mast-arm-mounted luminaires shall have an integral tilt adjustment of ±5°, in accordance with ANSI C136.3.

Luminaires must pass 3G vibration testing in accordance with ANSI C136.31.

Luminaires shall have surge protection to meet ―C Low‖ waveforms as defined in

ANSI/IEEE C62.41.2, Scenario 1 Location Category C.

Luminaires shall incorporate provisions to attach a twist-lock style photocell.

2.5 WIRING

2.5.1 Twist-style wire nuts and tap-style stripless connectors are not acceptable for factory electrical connections.

2.6 POWER SUPPLY UNITS

a. The maximum drive current to each individual LED shall not exceed 525 mA.

b. Rated to operate between -30 °C to [+40 °C] [+50 °C].

c. Designed to operate on voltage system 277V or 480V nominal based on lighting design supplied by general contractor. Fluctuations in line voltage up to 15% shall have no visible effect on the luminous output.

d. Operating frequency: 60 Hz.

P a g e | 8 of 11

e. Power factor (PF): ≥ 0.90.

f. Total current harmonic distortion (THD) for current: ≤ 20%.

g. Comply with FCC 47 CFR Section 15, Class B, non-consumer RFI/EMI standards.

h. Reduction of hazardous substances- (RoHS-) compliant.

i. Luminaires under a covered structure shall be UL-listed Class P with a sound rating Driver shall be dimmable and compatible with a standard dimming control circuits.

j. Driver shall be protected against damage due to either an open-circuit or short-circuit fault condition on the driver output. The driver shall resume normal operation when the fault is removed.

k. Over-temperature protection shall be provided to cut off output power if temperature limit is exceeded. The driver shall resume normal operation when within normal operating temperature.

2.7 LED LIGHT SOURCE

a. Correlated color temperature (CCT) shall be in accordance with ANSI C78.377.

[Nominal CCT: 3000 K: 3045 ± 175 K or

Nominal CCT 3500 K: 3465 ± 245 K]

[Nominal CCT: 4000 K: 3985 ± 275 K or

Nominal CCT 4500 K: 4503 ± 243 K]

[Nominal CCT 5000 K: 5028 ± 283 K or

Nominal CCT 5700 K: 5665 ± 355 K]

[Nominal CCT: 6500 K: 6530 ± 510 K]

b. Color Rendering Index (CRI) shall be:

[≥ 80 for 3000 K – 3500 K]

[≥ 70 for 4000 K – 6500 K]

c. Thermal management shall be passive by design and shall consist of heat sinks with no fans, pumps, or liquids.

2.8 ELECTRICAL SYSTEM

P a g e | 9 of 11

2.8.1 Provide appropriately sized lighting panels tied into the underground primary work with controls to accommodate general contractor furnished lighting design.

2.9 DAYLIGHTING CONTROLS

All street, exterior parking lot, drive, and front aisle areas shall be controlled such that exterior luminaires shall not operate during hours of daylight.

Controls may include a combination photocell plus time switch or an energy management system.

Controls shall allow automatic on and off settings based on daylighting, plus timed off settings after expected activity ends.

The energy management system shall employ predetermined control strategies to include automatic dimming for adaptive standards.

2.10 POLE Details below are SUGGESTED anchoring methods for sidewalk illumination lighting. Only general contractor lighting design documents shall be used for construction.

2.11 Street light posts/Sidewalk light posts-

Contractor to provide 3 options for design of lights for sidewalks and for street lighting.

Option 1 shall be of Modern style lighting

Option 2 shall be of Traditional style lighting

Option 3 shall be of Decorative (wrought iron style- can be faux)

Examples of Images below- these are NOT indicative of the exact type but use as a guideline for the lighting designer. Both the street light and sidewalk light shall be of the same style and match each other respectively.

Example of Decorative

Example of Traditional (no solar panels)

Example of Modern

CONCRETE BASE REQUIREMENT

Concrete support base shall be designed by lighting designer. Minimum base height for street lighting shall be to (2) feet high (above grade) reinforced concrete and shall be dependent on location of the lighting pole, traffic, appearance, etc. Concrete base shall have aesthetically pleasing and minimal. Sidewalk lights shall be located adjacent to the sidewalks with bases buried in the ground so that only a minimal section of the base is visible.