C1 POL EFSO LOCATION & ELECTRICAL DISTRIBUTION SITE PLAN.pdf
PDF 2 MB Posted
- Attached to
- Consolidated Construction Project Federal contract opportunity
- Solicitation number
- W912LN-18-B-5002
About this file
EFSO
View the file
Other files for this federal contract opportunity
Show all 50
Consolidated Construction Project has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
100-200'
100-200'
REMOVE EXISTING EFSO
FIBERGLASS STAIR PROJECT TO BE
COMPLETED BY OTHERS
EFSO TO BE MOUNTED ADJACENT
TO FIBERGLASS STAIRS.
REMOVE EXISTING EFSO.
SEE NOTE 3.
UPPER POL
APPROXIMATE LOCATION OF
EXISTING COMMUNICATIONS LINES
GUARDRAIL
EFSO TO BE MOUNTED ON BOLLARD.
SEE DETAIL 2 THIS PAGE.
EXISTING EFSO
ADJACENT TO MASTER
ALARM PANEL TO REMAIN
EXISTING UNISTRUT
SUPPORTS IN THESE
AREAS
EMERGENCY FUEL SHUTOFF
PUSHBUTTON
FINISH GRADE
6"Ø HEAVY DUTY, H.D. GALVANIZED
STEEL PIPE BOLLARD CONC. FILLED
6"
FILL W/ 3500 PSI
CONCRETE
6" 6"
CONC. ROUNDED SMOOTH
PAINTED GREEN (EXACT COLOR
AS DIRECTED BY COR)
TAPERED AWAY FROM PIPE
S
L
O
P
E
GALVANIZED METAL BANDING
STRIPS TO SECURELY ATTACH
SIGN TO BOLLARD
EMERGENCY FUEL SHUTOFF
SIGNAGE. SEE NOTE 4.
GENERAL NOTES: POSTS MAY BE DRIVEN OR SET
IN A DUG HOLE AND BACKFILLED. IF DRIVEN, A DRIVING CAP
SHALL BE USED. THE DUG HOLE INSTALLATION SHALL BE
USED IN AREAS OF POOR SOIL CONDITIONS OR AS
DIRECTED BY THE C.O.R. BACKFILL SHALL BE COMPACTED
AS DIRECTED BY THE C.O.R.
NOTE: ON STEEP SLOPES (1 ON 2 OR STEEPER) ADD ONE
FOOT EMBEDMENT FOR GREATER STABILITY
5'-0" TYP.
4'-6"
4'-0" MIN
G
R
O
U
N
D
S
L
O
P
E
EMERGENCY
FUEL
SHUTOFF
PUSH
GRAPHIC SCALE (IN FEET)
LEGEND
EXISTING CHAIN LINK FENCE
NOTES
1. THE PURPOSE OF THIS PLAN IS TO PROVIDE THE CONTRACTOR WITH GENERAL
SITE INFORMATION REGARDING THE CONSTRUCTION/REPAIR OF EMERGENCY
FUEL SHUTOFF (EFSO) STATIONS.
2. EMERGENCY FUEL SHUTOFFS (EFSO'S) SHALL BE WIRED IN TWO SERIES
CIRCUITS. UPPER POL SHALL CONTAIN 4 EFSO'S WIRED IN SERIES, LOWER POL
SHALL CONTAIN 5 EFSO'S WIRED IN SERIES. SHUTOFFS ARE REQUIRED TO BE
LOCATED ADJACENT TO AND BETWEEN 100FT-200FT FROM EXISTING FUELING
STANDS AND PUMPS OR AS DIRECTED BY THE COR.
3. REMOVE EXISTING EFSO. CUT AND CAP BELOW GRADE. USE EXISTING
CONDUCTORS TO TRACE PATH AND CONDUITS BACK TO B215. REUSE EXISTING
CONDUITS TO FULLEST EXTENT PRACTICAL.
4. CONTRACTOR TO PROVIDE NEW SIGNAGE AT ALL EFSO LOCATIONS. SIGNS
SHALL BE WEATHER, CHEMICAL, UV, AND MOISTURE RESISTANT SUITABLE FOR
EXTERIOR INSTALLATION. SIGNS SHALL READ "EMERGENCY FUEL SHUTOFF
PUSH" WITH RED BACKGROUND AND WHITE LETTERING. SIGN DIMENSIONS
SHALL BE 10INX14IN. SIGNS SHALL BE SECURELY ATTACHED TO UNISTRUTS
ABOVE EACH EFSO. COORDINATE WITH COR FOR LOCATIONS WHERE NO
UNISTRUT IS REQUIRED FOR SIGN PLACEMENT.
5. NEW EFSO'S TO BE EXPLOSION PROOF, CLASS I, DIVISION 2, GROUP C
ELECTRICAL FIXTURES, WEATHER RATED. ALL EQUIPMENT/MATERIALS SHALL
BE CONSTRUCTED OF RUST-FREE, CORROSION RESISTANT MATERIALS.
6. CONTRACTOR TO RETURN DISTURBED AREAS TO EXISTING CONDITIONS. SEE
DETAILS THIS SHEET FOR TRENCHING/EXCAVATION REQUIREMENTS.
7. INFORMATION ON THIS PLAN IS NOT GUARANTEED BY VTANG TO BE
COMPREHENSIVE NOR COMPLETE. THE CONTRACTOR SHALL LOCATE ALL
EXISTING UTILITIES WHERE EARTH DISTURBANCE IS ANTICIPATED.
8. INFORMATION ON THIS PLAN IS COMPILED FROM EXISTING VTANG CAD FILES,
VT STATE ORTHOGRAPHIC IMAGING AND FIELD SURVEYING.
9. CONTRACTOR SHALL CALL "DIGSAFE" AT 811 AND BOB LETOURNEAU AT
660-5401 PRIOR TO ANY EARTH DISTURBANCE.
EXISTING EFSO LOCATION
INSTALL NEW EFSO
EXISTING/PROPOSED
MASTER ALARM PANEL
EXISTING MAIN FIRE
COMMUNICATIONS PANEL
EXISTING EFSO CIRCUIT
EXISTING LIGHT POLES
EXISTING EMERGENCY
SHUTOFF
EXISTING HAND HOLES
EXISTING HAND HOLES
DDB/CED DDB/CED MWL
JAN 2018
AS NOTED
POL EFSO LOCATION &
ELECTRICAL DISTRIBUTION
SITE PLAN
C1
CURZ172301
C O
N T
R A
C T
P
L A
N S
M A
Y
EXISTING COMM
PROPOSED EFSO CIRCUIT
EFSO BOLLARD DETAIL
NTS
C1
D+2
18"
12''
UNPAVED
* SUITABLE MATERIAL SHALL CONTAIN NO STONES GREATER THAN 4'' IN
DIAMETER, NO FROZEN LUMPS, AND ONLY MINOR AMOUNTS OF CLAY OR
LIFTS AND COMPACTED BEFORE PLACING NEXT LIFT.
TYPICAL TRENCH DETAIL
NTS
C1
MOUND SLIGHTLY
THE CONTRACTOR SHALL BE
RESPONSIBLE FOR COMPLYING WITH
OSHA - VOSHA REGULATIONS
SAND FILL. ON SITE MATERIAL MAY
BE USED.
WARNING TAPE: TAPE SHALL BE 6-INCHES
IN WIDTH, RED IN COLOR AND MESSAGE
SHALL READ "ELECTRICAL LINE BELOW"
EFSO POST DETAIL
NTS
C1
Z:\CAD\In-House Projects\2018 Projects\2018 EFSO Installation\C1 EFSO Locations.dwg