181109_-_Electrical_B3_Set.pdf
PDF 2 MB Posted
- Attached to
- Corrosion Control Equipment Federal contract opportunity
- Solicitation number
- W912JV-19-Q-7011
About this file
Electrical Drawings
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Orientation.pdf | ||
| SOW_Corrosion_Control_Equipment_2019_rev4.docx | DOCX document | |
| Q&A__2.docx | DOCX document | |
| Questions_and_answers.docx | DOCX document | |
| Kingsley_B3_Architectural_2_of_2.pdf | ||
| 181109_-_Mechanical_B3_Set.pdf | ||
| Kingsley_B3_Plumbing_-_Stamped.pdf | ||
| SOW_Corrosion_Control_Equipment_2019_rev4.docx | DOCX document | |
| Kingsley_B3_Architectural_1_of_2.pdf | ||
| SOW_Corrosion_Control_Equipment_2019_rev3.docx | DOCX document |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
VFD
MS
MX
RECEPTACLE SYMBOLS
DUPLEX RECEPTACLE TEXT INDICATES MOUNTING HEIGHT
SIMPLEX RECEPTACLE
DOUBLE DUPLEX RECEPTACLE
ABOVE COUNTER DUPLEX RECEPTACLE
60"
RECEPTACLE NOTATIONS:
DENOTES DEDICATED OUTLETSD
DENOTES WEATHER PROOF OUTLETSWP
DENOTES EXPLOSION PROOF CLASS 1 DIVISION 2 OUTLETSX2
DENOTES EXPLOSION PROOF CLASS 1 DIVISION 1 OUTLETSX1
DENOTES GROUND FAULT INTERRUPTER OUTLETSGFCI
DENOTES ELECTRIC WATER COOLER OUTLETSEWC
SERVICE & DISTRIBUTION SYMBOLS
GROUND ACCESS WELL
GROUND ROD
GROUNDING CONDUCTORG
PANELBOARD
LIGHTNING AIR TERMINAL
STATIC GROUND RECEPTACLE
GR
MOTOR & EQUIPMENT CONNECTION
SYMBOLS
ELECTRICAL CONNECTION TO EQUIPMENT AND MOTORS, SIZED
PER NEC. COORDINATE REQUIREMENTS WITH CONTRACTOR
FURNISHING MOTOR OR EQUIPMENT. REFER TO
SPECIFICATIONS AND EQUIPMENT WIRING SCHEDULE FOR
ADDITIONAL WORK ASSOCIATED WITH MOTOR OR EQUIPMENT.
VARIABLE FREQUENCY MOTOR CONTROLLER
NON-FUSIBLE DISCONNECT SWITCH
FUSIBLE DISCONNECT SWITCH
MTS
MOTOR STARTING SWITCH WITH OVERLOADS
MOTOR STARTING SWITCH WITHOUT OVERLOADS
MANUAL TRANSFER SWITCH
ENCLOSED CIRCUIT BREAKER
GENERAL SYMBOLS
KEYED NOTE, USED TO DESCRIBE ADDITIONAL
INFORMATION OF WORK REQUIRED, SPECIFIC TO
THE SHEET AND/OR DETAIL IT IS SHOWN WITH.
DETAIL NUMBER / SHEET NUMBER#/E-###
9.###
LINE TYPE KEY
EXISTING TO BE REMOVED BY THIS
CONTRACTOR (DARK DASHED LINE)
NEW WORK BY THIS CONTRACTOR
(DARK SOLID LINE)
ONE-LINE EQUIPMENT ENCLOSURE
PANEL DIVISION LINES
SITE UNDERGROUND ELECTRICE
SINGLE POLE SWITCH
LUMINAIRE CONTROL SYMBOLS
PHOTO ELECTRIC CONTROL (X REPRESENTS
OCCUPANCY/PHOTO SENSOR SCHEDULE DESIGNATION)
OCCUPANCY SENSOR CEILING MOUNT (X REPRESENTS
OCCUPANCY/PHOTO SENSOR SCHEDULE DESIGNATION)
ELECTRONIC TIME CLOCK
LUMINAIRE SYMBOLS
RECESSED LUMINAIRE
RECESSED TROFFER
RECESSED LINEAR
SURFACE ROUND LUMINAIRE
WALL MOUNTED EXIT SIGN
CEILING MOUNTED EXIT SIGN
OS X
TC
PE
ARROW DENOTES EXIT SIGN CHEVRON
EMERGENCY BATTERY UNIT
LOW VOLTAGE SWITCH
* DENOTES SWITCH NAME, SEE LIGHTING
CONTROL PANEL & SWITCH SCHEDULE.
L
SWITCH NOTATIONS:
3 DENOTES 3-WAY SWITCH
4 DENOTES 4-WAY SWITCH
D DENOTES WALL BOX DIMMER SWITCH
WSX DENOTES OCCUPANCY SENSOR
(X REPRESENTS SCHEDULE DESIGNATION)
P DENOTES PILOT SWITCH
T DENOTES TIMER SWITCH
EMERGENCY SHADING MODIFIER
PENDANT INDUSTRIAL
WALL BRACKET
A1
1Ra
LUMINAIRE TYPE
LUMINAIRE CIRCUITRY & CONTROL KEY:
LOWER CASE LETTER INDICATES SWITCHLEG CONTROL
"R" INDICATES LIGHTING CONTROL PANEL
REFER TO LIGHTING CONTROL PANEL SCHEDULE
NUMBER INDICATES BRANCH PANEL CIRCUIT NUMBER
SURFACE INDUSTRIAL
GENERAL NOTES:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
20.
REFER TO THE G SERIES DRAWINGS FOR CODE ANALYSIS
PLANS, INFORMATION AND NOTES.
THE CONTRACTOR SHALL BECOME FAMILIAR WITH THE
DETAILS OF WORK, VERIFY DIMENSIONS IN THE FIELD,
AND ADVISE THE ARCHITECT/ENGINEER OF ANY
DISCREPANCY BEFORE PERFORMING ANY WORK.
THE COMPLETE INSTALLATION SHALL BE IN ACCORDANCE
WITH THE ABA (AMERICANS WITH BARRIERS ACT).
REFER TO ARCHITECTURAL DRAWINGS FOR FIRE RATED
WALLS AND FLOORS. MAKE RATED PENETRATIONS AS
REQUIRED. SEAL ALL RATED PENETRATIONS AS
IDENTIFIED IN DIVISION 1 REQUIREMENTS.
FLUSH MOUNT ALL TOGGLE SWITCHES AND
RECEPTACLES AT HEIGHTS ABOVE FINISHED FLOOR AS
SHOWN IN THE DEVICE MOUNTING HEIGHT DETAIL,
EXCEPT WHERE OTHERWISE NOTED. DEVICES MAY BE
SURFACE MOUNTED WHEN CONDUIT IS SPECIFIED
EXPOSED.
CIRCUIT NUMBERS ARE SHOWN FOR CIRCUIT
IDENTIFICATION. CIRCUITING SHALL AGREE WITH
NUMBERING ON THE PANEL SCHEDULES PROVIDED.
BALANCE THE LOAD ON PANELS AS EVENLY AS POSSIBLE
BETWEEN EACH PHASE. COMMON NEUTRALS MAY NOT BE
USED FOR BRANCH CIRCUITS. BALANCE THE LOAD ON
PANEL AS EVENLY AS POSSIBLE BETWEEN EACH PHASE.
CIRCUITS SERVING EMERGENCY AND EXIT LUMINAIRES
WILL BE RUN IN SEPARATE RACEWAY FROM ALL OTHER
CIRCUITS.
A #12 GREEN INSULATED GROUND CONDUCTOR SHALL BE
INSTALLED WITH CIRCUIT CONDUCTORS TO ALL
RECEPTACLES.
CONCEAL ALL CONDUIT IN WALLS, PARTITIONS, ABOVE
CEILING, ETC. UNLESS OTHERWISE INDICATED ON THE
PLANS OR IN THE SPECIFICATIONS. CONDUIT IN
MECHANICAL ROOMS, AND STORAGE ROOMS WITHOUT
CEILINGS MAY BE EXPOSED ON BUILDING STRUCTURE.
BOXES LOCATED ON OPPOSITE SIDES OF NON-RATED
WALLS SHALL BE OFFSET A MINIMUM OF 6"
HORIZONTALLY. "THRU-THE-WALL" BOXES SHALL NOT BE
ALLOWED.
COORDINATE AND CO-LOCATE WALL MOUNTED
RECEPTACLE LOCATIONS WITH TECHNOLOGY
(VOICE/DATA, ETC) OUTLETS SHOWN ON THE T-SERIES
DRAWINGS UNLESS OTHERWISE NOTED, EACH
TECHNOLOGY OUTLET SHALL BE LOCATED WITHIN 24"OF
ITS ASSOCIATED RECEPTACLE. ASSOCIATED RECEPTACLE
SHALL BE DEFINED AS THE RECEPTACLE NEAREST THE
LOCATION OF, AND AT THE SAME HEIGHT AS,THE
TECHNOLOGY OUTLET WHEN MULTIPLE RECEPTACLES
ARE SHOWN ON A WALL.
DUPLEX RECEPTACLES FOR ELECTRIC WATER COOLERS
(EWC) SHALL BE CONCEALED BEHIND WATER COOLER
ACCESS PLATE OR BE DIRECTLY BELOW AND CENTERED
ON EWC. CONTRACTOR SHALL VERIFY TYPE OF EWC TO
BE INSTALLED.
CONTRACTOR SHALL VERIFY ALL FURNITURE, MODULAR
FURNITURE AND EQUIPMENT LOCATIONS WITH
ARCHITECTURAL PLANS, ELEVATIONS AND REVIEWED
SHOP DRAWINGS. PRIOR TO MAKING THE ACTUAL
ELECTRICAL INSTALLATION THIS CONTRACTOR SHALL
ADJUST RECEPTACLES, OUTLETS OR CONNECTION
LOCATIONS TO ACCOMMODATE FURNITURE AND/OR
EQUIPMENT.
ELECTRICAL AND TELECOMMUNICATIONS EQUIPMENT
SHALL BE MOUNTED TO AVOID IMPEDANCE OF,
OPERATION OF, AND/OR ACCESS TO ELECTRICAL AND
MECHANICAL EQUIPMENT. ALL MOUNTING OF
ELECTRICAL AND TELECOMMUNICATIONS EQUIPMENT, ON
EQUIPMENT SUPPLIED BY ANOTHER CONTRACTOR, SHALL
BE APPROVED IN ADVANCE BY THE OTHER CONTRACTOR.
CONTRACTOR TO PROVIDE SUITABLE MECHANICAL
PROTECTION AROUND ALL CONDUITS STUBBED OUT
FROM FLOORS, WALLS OR CEILINGS DURING
CONSTRUCTION TO PREVENT BENDING OR DAMAGING OF
STUB OUTS DUE TO CARELESSNESS WITH
CONSTRUCTION EQUIPMENT.
CONTRACTOR SHALL BE RESPONSIBLE FOR ALL
OPENINGS REQUIRED IN WALLS. ALL OPENINGS SHALL BE
REPAIRED TO MATCH EXISTING BY A QUALIFIED
CONTRACTOR AT THE EXPENSE OF THIS CONTRACTOR.
ALL CONDUITS THROUGH WALLS SHALL BE GROUTED OR
SEALED INTO OPENINGS.
DRAWINGS INDICATE THE EXTENT OF HAZARDOUS
LOCATIONS. INSTALLATION MEANS AND METHODS SHALL
BE SUITABLY RATED FOR THE ENVIRONMENT INDICATED
ON THE DRAWINGS.
ALL INTERLOCKING REQUIRED BY THE DRIVE
MANUFACTURER BETWEEN THE VARIABLE FREQUENCY
DRIVE AND THE DISCONNECT SWITCHES SHALL BE THE
RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR.
SCCR RATINGS LISTED FOR EQUIPMENT ARE MINIMUM
REQUIREMENTS FOR BUS BRACING AND DEVICE RATING.
ALL EQUIPMENT SHALL BE FULLY RATED UNLESS
SPECIFICALLY NOTED AS SERIES RATED.
EC SHALL REFER TO T-SERIES AND FA-SERIES SET OF
DOCUMENTS INCLUDED IN THIS BID PACKAGE FOR ALL
TELECOMMUNICATION AND FIRE ALARM WORK
ASSOCIATED WITH THIS PROJECT. EC SHALL INCLUDE IN
THIS BID ALL LABOR AND MATERIALS REQUIRED FOR THE
COMPLETE BOXES AND RACEWAY SYSTEMS FOR BOTH
TELECOMMUNICATION AND FIRE ALARM SYSTEMS (BOTH
NEW AND FUTURE). ALL CABLE TRAY, CONDUITS, BOXES
AND OUTLETS REQUIRED FOR TELECOMMUNICATION AND
FIRE ALARM SYSTEM INSTALLATION SHALL BE
COORDINATED WITH THE ASSOCIATED DRAWING SET AND
VERIFIED IN FIELD WITH TELECOMMUNICATION AND FIRE
ALARM CONTRACTORS PRIOR TO ROUGH-IN.
COORDINATE CONDUIT BETWEEN ALL SYSTEMS FOR A
CLEAN INSTALLATION.
SHEET NO.:
SHEET CONTENTS
DO NOT SCALE DRAWINGS
ISSUED
M&H NO.:
DATE:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
© Copyright This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.
Mead & Hunt, Inc.
9600 NE Cascades Parkway, Suite 100 Portland, OR 97220 phone: 503-548-1494 meadhunt.com www.tetratech.com
711 TANK FARM ROAD, SUITE 110
SAN LUIS OBISPO, CA 93401
PHONE: (805) 542-9052 FAX: (805) 542-9254
/7 /2
:4 :2
P
M C
R e v it L o c a l\
-1
.0 -E
-C E
N T
R A
L -2 jr h .r v t
E-001
NOTES, SYMBOLS &
ABBREVIATIONS
O R
A N
G
K in g s le y F ie ld
K la m a th
F a lls
O
R
C O
N S
T R
U C
T C
O R
R O
S
IO
N C
O N
T R
O L H
A N
G A
R
3142200-121252.01
KAS
IMR
11/09/18
JRH
ELECTRICAL ABBREVIATIONS
3R NEMA 3R RATING
4X NEMA 4X RATING
A AMPERES
A/E ARCHITECT / ENGINEER
AAC ABOVE ACCESSIBLE CEILING
ACCU AIR COOLED CONDENSING UNIT
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AHU AIR HANDLING UNIT
ALT ALTERNATE
APE AIRCRAFT PROCESS EQUIPMENT
ATS AUTOMATIC TRANSFER SWITCH
BLDG BUILDING
BRKR BREAKER
C CONDUIT
CB CIRCUIT BREAKER
CF CIRCULATION FAN
CH CHILLER
CHWP CHILLED WATER PUMP
CKT CIRCUIT
CP CIRCULATION PUMP
CRAC COMPUTER ROOM AIR CONDITIONER
CRP CONDENSATION RETURN
CUH CABINET UNIT HEATER
DC DROP CORD
DDC DIGITAL CONTROL PANEL
DH DUCT HEATER
DISC DISCONNECT
DO DOOR OPERATOR
DWG DRAWING
E/O ELECTRICAL-TO-OPTICAL CONVERTER
EC ELECTRICAL CONTRACTOR
ECB ENCLOSED CIRCUIT BREAKER
EF EXHAUST FAN
EM EMERGENCY
EMT ELECTRICAL METALLIC TUBING
ES EQUIPMENT SUPPLIER
ETR EXISTING TO REMAIN
EWC ELECTRICAL WATER COOLER
EWH ELECTRICAL WATER HEATER
F FUSED
FA FIRE ALARM
FCU FAN COIL UNIT
GC GENERAL CONTRACTOR
GD GARBAGE DISPOSAL
GFI GROUND FAULT INTERRUPTER
GND GROUND
GWH GAS WATER HEATER
HD HAND DRYER
HP HORSEPOWER
HVAC HEATING, VENTILATION, AIR CONDITIONING
HWB HOT WATER BOILER
HWP HOT WATER PUMP
IEWH INSTANTANEOUS ELECTRIC WATER HEATER
IH INFRARED HEATER
IMC INTERMEDIATE METALLIC CONDUIT
IWH INSTANTANEOUS WATER HEATER
J-BOX JUNCTION BOX
MAU MAKE-UP AIR UNIT
MAX MAXIMUM
MC MECHANICAL CONTRACTOR
MCC MOTOR CONTROL CENTER
MDF MAIN DISTRIBUTION FRAME
MDP MAIN DISTRIBUTION PANEL
MIN. MINIMUM
MNS MASS NOTIFICATION SYSTEM
MTD MOUNTED
MTG MOUNTING
MTS MANUAL TRANSFER SWITCH
NIC NOT IN CONTRACT
NL NIGHT LIGHT
NL/EL NIGHT LIGHT AND EMERGENCY LIGHT
NTS NOT TO SCALE
OC ON CENTER
OFCI OWNER FURNISHED, CONTRACTOR INSTALLED
OFOI OWNER FURNISHED, OWNER INSTALLED
PH PHASE
PNL PANEL
PVC POLYVINYL CHLORIDE
RCP RADIANT CEILING PANEL
RECPT RECEPTACLE
REF REFRIGERATOR
REQ'D REQUIRED
RF RETURN FAN
RGS RIGID GALVANIZED STEEL CONDUIT
MAY ALSO BE REFERENCED AS RMC OR GRC
RMC RIGID METAL CONDUIT
RTU ROOF TOP UNIT
S/N SOLID NEUTRAL
SE SERVICE ENTRANCE
SEC-P SECURITY PANEL
SF SUPPLY FAN
SP SUMP PUMP
SS STAINLESS STEEL
SW SWITCH
TBR TO BE REMOVED
TCP TEMPERATURE CONTROL PANEL
TFA TO FLOOR ABOVE
TFB TO FLOOR BELOW
TYP TYPICAL
UC UNIT COOLER
UG UNDERGROUND
UH UNIT HEATER
UNO UNLESS NOTED OTHERWISE
UV UNIT VENTILATER
V VOLTS
VFD VARIABLE FREQUENCY DRIVE
VS VERSUS
W WATTS
WCC WATER COOLED CONDENSER
WH WATER HEATER
WL WET LOCATION LISTED
WP WEATHERPROOF
XFMR TRANSFORMER
XP EXPLOSION PROOF
11/09/18 B-3 FINAL
3. FEEDER SIZES SHOWN ON THE RISER DIAGRAM INDICATE FEEDER AMPACITIES
AND DO NOT NECESSARILY CORRESPOND TO THE CIRCUIT BREAKER AMPACITIES.
CERTAIN FEEDERS MAY BE SIZED FOR DERATION FACTORS AND/OR OVERSIZED
FOR VOLTAGE DROP PER NEC REQUIREMENTS.
2. ALL THE CONDUCTOR AMPACITIES ARE BASED ON TABLE 310.15(B)(16) OF THE
2017 NEC FOR COPPER CONDUCTOR TYPE THHN/THWN-2
1. THE SCHEDULE IS A SCHEDULE OF TYPICAL FEEDERS AND SOME OF THE SIZES
MAY NOT APPLY TO THIS PROJECT.
FEEDER SCHEDULE NOTES:
2500Y 2500 7 3 - 500 1 - 500 1 - 350 - 4"
2500 2500 7 3 - 500 - 1 - 350 - 3 - 1/2"
1200Y 1200 4 3 - 350 1 - 350 1 - # 3/0 - 3"
1200 1200 4 3 - 350 - 1 - # 3/0 - 3"
1000Y 1000 3 3 - 400 1 - 400 1 - # 2/0 - 3-1/2"
1000 1000 3 3 - 400 - 1 - # 2/0 - 3"
800Y 800 2 3 - 500 1 - 500 1 - # 1/0 - 3 - 1/2"
800 800 2 3 - 500 - 1 - # 1/0 - 3"
700Y 700 2 3 - 500 1 - 500 1 - # 1/0 - 3-1/2"
700 700 2 3 - 500 - 1 - # 1/0 - 3"
600Y 600 2 3 - 350 1 - 350 1 - # 1 - 3"
600 600 2 3 - 350 - 1 - # 1 - 3"
500Y 500 2 3 - 250 1 - 250 1 - # 2 - 3"
500 500 2 3 - 250 - 1 - # 2 - 2-1/2"
450Y 450 2 3 - # 4/0 1 - # 4/0 1 - # 2 - 2-1/2"
450 450 2 3 - # 4/0 - 1 - # 2 - 2"
400Y 400 1 3 - 500 1 - 500 1 - # 3 - 3-1/2"
400 400 1 3 - 500 - 1 - # 3 - 3"
380Y 380 1 3 - 500 1 - 500 1 - # 3 - 3-1/2"
380 380 1 3 - 500 - 1 - # 3 - 3"
350Y 350 1 3 - 500 1 - 500 1 - # 3 - 3-1/2"
350 350 1 3 - 500 - 1 - # 3 - 3"
300Y 300 1 3 - 350 1 - 350 1 - # 4 - 3-1/2"
300 300 1 3 - 350 - 1 - # 4 - 3"
250Y 250 1 3 - 250 1 - 250 1 - #4 - 3"
250 250 1 3 - 250 - 1 - #4 - 2-1/2"
225Y 225 1 3 - # 4/0 1 - # 4/0 1 - # 4 - 2-1/2"
225 225 1 3 - # 4/0 - 1 - # 4 - 2"
200Y 200 1 3 - # 3/0 1 - # 3/0 1 - # 6 - 2-1/2"
200 200 1 3 - # 3/0 - 1 - # 6 - 2"
175Y 175 1 3 - # 2/0 1 - # 2/0 1 - # 6 - 2"
175 175 1 3 - # 2/0 - 1 - # 6 - 2"
150Y 150 1 3 - # 1/0 1 - # 1/0 1 - # 6 - 2"
150 150 1 3 - # 1/0 - 1 - # 6 - 1-1/2"
125Y 125 1 3 - # 1/0 1 - # 1/0 1 - # 6 - 2"
125 125 1 3 - # 1/0 - 1 - # 6 - 1-1/2"
110Y 110 1 3 - # 1 1 - # 1 1 - # 6 - 2"
110 110 1 3 - # 1 - 1 - # 6 - 1-1/2"
100Y 100 1 3 - # 1 1 - # 1 1 - # 8 - 1-1/2"
100 100 1 3 - # 1 - 1 - # 8 - 1-1/2"
80Y 80 1 3 - # 3 1 - # 3 1 - # 8 - 1-1/4"
80 80 1 3 - # 3 - 1 - # 8 - 1-1/4"
70Y 70 1 3 - # 4 1 - # 4 1 - # 8 - 1-1/4"
70 70 1 3 - # 4 - 1 - # 8 - 1-1/4"
60Y 60 1 3 - # 4 1 - # 4 1 - # 10 - 1-1/4"
60 60 1 3 - # 4 - 1 - # 10 - 1"
50Y 50 1 3 - # 6 1 - # 6 1 - # 10 - 1-1/4"
50 50 1 3 - # 6 - 1 - # 10 - 1"
45Y 45 1 3 - # 6 1 - # 6 1 - # 10 - 1"
45 45 1 3 - # 6 - 1 - # 10 - 3/4"
40Y 40 1 3 - # 8 1 - # 8 1 - # 10 - 1"
40 40 1 3 - # 8 - 1 - # 10 - 3/4"
35Y 35 1 3 - # 8 1 - # 8 1 - # 10 - 3/4"
35 35 1 3 - # 8 - 1 - # 10 - 3/4"
30Y 30 1 3 - # 10 1 - # 10 1 - # 10 - 3/4"
30 30 1 3 - # 10 - 1 - # 10 - 3/4"
25Y 25 1 3 - # 10 1 - # 10 1 - # 10 - 1/2"
25 25 1 3 - # 10 - 1 - # 10 - 1/2"
20Y 20 1 3 - # 12 1 - # 12 1 - # 12 - 1/2"
20 20 1 3 - # 12 - 1 - # 12 - 1/2"
PHASE NEUTRAL EQ GND ISO GND
MARK AMPACITY
NO. OF
SETS
CONDUCTOR SIZES (AWG or KCMIL) CONDUIT
SIZE
COPPER FEEDER SCHEDULE
B
B
BB
B
B B
B B
BB
B
B
B
B B
B
B
B
B
B B
B
B
B
B
B
B
B
B B
B
B
B B
B
B
B
BBBB
B
B
BB
B
B
B
B B B B B B
B
B
B
B
BB
T
CB
EXISTING COMMUNICATIONS MANHOLE
ELECTRICAL TRANSFORMER VAULT AND UTILITY
TRANSFORMER. INSTALL TRANSFORMER VAULT PER
UTILITY REQUIREMENTS. TRANSFORMER VAULT
SHALL BE ORIENTATED TO ALLOW TRANSFORMER
ACCESS FROM THE NORTH.
EXISTING UTILITY VAULT 227480.
REFER TO SHEET E-701 FOR
WORK ASSOCIATED WITH
EXISTING UTILITY VAULT.
INSTALL (1) -4" CONDUIT
PER PACIFIC POWER
UTILITY REQUIREMENTS.
EXISTING UTILITY HV DUCT BANK.
MUST MAINTAIN CONTINUITY
THROUGHOUT DURATION OF
PROJECT
COORDINATE ENTRY WITH
ELECTRICAL ROOM AND CHASE.
FOR POWER CONTINUATION, SEE E-SERIES DRAWINGS.
FOR TECHNOLOGY SYSTEMS, SEE T-SERIES DRAWINGS.
SWITCHBOARD 'MSB/MTR'.
BOND EQUIPMENT TO GROUND GRID PER CODE.
G G
G
GG
G
#4/0AWG
BOND ALL METAL BOLLARDS WITHIN
10'-0" OF UTILITY TRANSFORMER AND
SWITCHBOARD INDIVIDUALLY TO
GROUND RING.
E
E
EEEEEEE
E
E
E
CONCRETE ENCASE
CONDUIT BELOW DRIVEWAY.
SEE DETAIL 2/E-503
REFER TO SHEET C-081 AND
ASSOCIATED DETAILS FOR
DIVISION 26 WORK ASSOCIATED WITH
NEW AIRFIELD / TAXIWAY LIGHTING.
E
GP
1/LB-9 (PUMP POWER)
1/LB-11 (PUMP ALARM)
1/LB-13 (GFCI/WP RECEPTACLE)
E E
SHEET NO.:
SHEET CONTENTS
DO NOT SCALE DRAWINGS
ISSUED
M&H NO.:
DATE:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
© Copyright This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.
Mead & Hunt, Inc.
9600 NE Cascades Parkway, Suite 100 Portland, OR 97220 phone: 503-548-1494 meadhunt.com www.tetratech.com
711 TANK FARM ROAD, SUITE 110
SAN LUIS OBISPO, CA 93401
PHONE: (805) 542-9052 FAX: (805) 542-9254
/7 /2
:4 :2
P
M C
R e v it L o c a l\
-1
.0 -E
-C E
N T
R A
L -2 jr h .r v t
E-010
ELECTRICAL SITE
PLAN
O R
A N
G
K in g s le y F ie ld
K la m a th
F a lls
O
R
C O
N S
T R
U C
T C
O R
R O
S
IO
N C
O N
T R
O L H
A N
G A
R
3142200-121252.01
KAS
IMR
11/09/18
JRH
PLAN
NORTH
TRUE
NORTH
1" = 20'-0"1
ELECTRICAL SITE PLAN
11/09/18 B-3 FINAL
UP
J
POWER GENERAL NOTES:
1.
2.
3.
4.
ALL DEVICES AND EQUIPMENT IN CORROSION CONTROL HANGAR 123 SHALL BE
SURFACE MOUNTED. ALL CONDUIT SHALL BE RUN OVERHEAD AND OUTSIDE OF
THE HAZARDOUS CLASSIFICATION ZONE. NO CONDUIT SHALL BE ROUTED
BELOW HANGAR SLAB, UNLESS NOTED OTHERWISE. CONDUIT SHALL NOT BE
ATTACHED TO LEAD-LINED HANGAR WALLS. CONDUIT SHALL BE ATTACHED TO
HORIZONTAL STRUCTURAL GIRDERS. PROVIDE ADDITIONAL SUPPORTS AS
REQUIRED. ALL SUPPORTS, HANGARS AND STRUT UTILIZED IN HANGAR 123
SHALL BE NEMA 4X. COORDINATE ROUTING WITH OTHER TRADES. ALL
CONDUIT IN HANGAR 123 SHALL BE RMC.
SEE DRAWINGS E-151 AND E-152 FOR AREA CLASSIFICATION ZONES.
REFER TO DETAIL 3/E-503 FOR CONDUIT REQUIREMENTS FOR PASSING THRU
LEAD-LINED WALLS.
REFER TO E-603 FOR ELECTRICAL EQUIPMENT WIRING SCHEDULE.
X-RAY VAULT
ROOM
X-RAY CR
FILM VIEWING
ROOM
OIL ANALYSIS
ROOM
OFFICE
EQUIPMENT
ROOM
INSPECTION
BAY
VEST.
STENCIL
ROOM
FIRE
PROTECTION
ROOM124
AIR LOCK
PPE CLEAN
ROOM/
CIRCULAT.
WOMEN'S
LOCKER
ROOM
WOMEN'S
JAN
MEN'S
LAUNDRY
ROOM
MEN'S
LOCKER
ROOM
HALLWAY
VEST.
OFFICE
TRAINING /
BREAK ROOM
PAINT BOOTH
BEAD BOOTH
ROOM
PAINT MIXING
ROOM/STOR
GFCI/WP
GFCI/WP GFCI/WP
GFCI/WP
GFCI/WP
GFCI/WP
GFCI/WP
GFCI/WP
GFCI/WP
GFCI/WP
GFCI
GFCI GFCI
GFCI
GFCI
GFCI
GFCI
GFCI
GFCI
GFCI
GFCI/WPGFCI/WP
GFCI/WP
GFCI/WP
GFCI/WP
M T
S
GENERATOR
PLUG
PANEL 1/LC
PANEL 1/LD
PANEL 1/LF
46"
46"
46"
9.304
115A
STORAGE
9.3079.307
PANEL 1/LB
PANEL 1/LA
PANEL 1/HA
PANEL 1/LA
UNLESS NOTED OTHERWISE
PANEL 1/LF
UNLESS NOTED OTHERWISE
PANEL 1/LF
UNLESS NOTED OTHERWISE
PANEL 1/LD
UNLESS NOTED OTHERWISE
PANEL 1/LD
UNLESS NOTED OTHERWISE
PANEL 1/LC
UNLESS NOTED OTHERWISE
PANEL 1/LB
UNLESS NOTED OTHERWISE
PANEL 1/LB
UNLESS NOTED OTHERWISE
PANEL 1/LA
UNLESS NOTED OTHERWISE
EEWS-1
9.312
SW
SW
SW
46"
E-101
19 19
HD
46"
PFT
PFT
1/LD-33
1/LD-39
1/LD-39
HD
1/LD-41
GFCI
EWC
E-101
GFCI/WP
GFCI/WP
E-102
1/LD-26
EEWS-1
9.312
SW
SW
SW
46"46"
EEWS-1EEWS-1
EEWS-1
PL-1
PL-2
MPM
PL-1
PL-2
1/LF-8
1/LF-2,4,6
46"
CR
CR
1/LF-10
1/LF-12
9 11
46"
GFCI GFCI
15 15
21 21
L6-30R
1/LF-14,16
(3#10, 3/4"C.)
XRAY
1/LF-18
1/LF-28
46"
46"
GFCI
PAINTBLAST
BEAD
1/LB-1,3,5
1/LB-24
GFCI/WP
OHD OHD
46"
1/LB-8
46"
46"
46"
46"
1/LC-5
1/LC-7
1/LC-9
GFCI
HANGAR
OHD OHD
46"
GFCI/WP
GFCI/WP
GFCI/WP
GFCI/WP
GFCI/WP
46"
46" 46" 46"
46"
46"
GFCI/WP
46"
PANEL 1/LE
DOOR-1
DOOR-2
DOOR-2
DOOR-1
1/LE-1,3,5
1/LE-2,4,6
OHD
9 9 11
151515
1/LA-17
1/LA-19 1/LA-211/LA-23
BAP-1
1/LA-25
REM-1
1/LA-27
REM-1
1/LA-29
EEWS-1
1/LA-31
DC/1LE
MTS/1LE
RSF
2/LE-9
X1
EPO
LCP
BEACON LIGHT
@ 7'-6"
BEACON LIGHT
@ 7'-6"
9.320 9.320
9.320
GR GR GR GR
GR GR GR GR
9.321
9.321
G G G G G G G G G G
G G G G G G G G G G
G
G
G
G
G
G
CU-2CU-1
HP-3
HP-1
CU-1
CU-2
IR-1
1/LA-2
G
TO ELEC ROOM
GROUND BUS
IR-2
1/LA-2
IR-3
1/LA-4
IR-4
1/LA-4
DF-4
1/LA-35
DF-6
1/LA-35
DF-1
1/LA-35
DF-3
1/LA-35
DF-5
1/LA-35
DF-2
1/LA-35
EF-1
9.332
9.332
EF-3
1/LC-15
(ON ROOF)
1/HA-1,3,5
HP-2
1/LF-23,25
2/LB-16,18
1/LD-38,40
CUH
CUH
SMS
1/LA-39
SMS
1/LA-37
DETAIL 4/E-501, TYPICAL
9.337
P-3
1/LA-33
9.316
9.316
9.316
9.301 TYP OF 4
72"
9.302
GFCI
GFCI
21 5
64" 64"
46"
9.313
GFCI
MOUNT UNDER SINK FOR
FUTURE GARBAGE DISPOSAL
GFCIGFCI
LAUNDRY
ROOM
42"
DRY
1/LD-14,16
42"
GFCI
SHEET NO.:
SHEET CONTENTS
DO NOT SCALE DRAWINGS
ISSUED
M&H NO.:
DATE:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
© Copyright This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.
Mead & Hunt, Inc.
9600 NE Cascades Parkway, Suite 100 Portland, OR 97220 phone: 503-548-1494 meadhunt.com www.tetratech.com
711 TANK FARM ROAD, SUITE 110
SAN LUIS OBISPO, CA 93401
PHONE: (805) 542-9052 FAX: (805) 542-9254
/7 /2
:4 :3
P
M C
R e v it L o c a l\
-1
.0 -E
-C E
N T
R A
L -2 jr h .r v t
E-101
FIRST FLOOR
POWER PLAN
O R
A N
G
K in g s le y F ie ld
K la m a th
F a lls
O
R
C O
N S
T R
U C
T C
O R
R O
S
IO
N C
O N
T R
O L H
A N
G A
R
3142200-121252.01
KAS
IMR
11/09/18
JRH
KEYED NOTES
9.301 ROUTE MECHANICAL EQUIPMENT BRANCH CIRCUITS UNDERGROUND
BETWEEN EQUIPMENT AND DISCONNECTS.
9.302 PROVIDE 200A, 3-POLE, 4-WIRE GENERATOR RECEPTACLE. COORDINATE
EXACT NEMA REQUIREMENTS WITH BASE PRIOR TO ORDERING.
9.304 ELECTRICAL MAIN SERVICE CHASE. ELECTRICAL CHASE CONTINUES UP TO
BOTTOM OF ELECTRICAL ROOM ON THE EQUIPMENT FLOOR. CONDUITS TO
ENTER THE BOTTOM OF SERVICE SWITCHBOARD. COORDINATE
INSTALLATION WITH TELECOM SERVICE CONDUITS AND FOUNDATION WALL
OPENING.
9.307 XRAY VAULT ROOM RECESSED BACKBOXES TO BE LINED WITH EQUAL
THICKNESS SHEET LEAD. REFER TO SHEET A-142 FOR ADDITIONAL
INFORMATION. CONDUITS PENETRATING LEAD LINING SHOULD BE DONE SO
WITH A LEAD WRAPPED ELBOW TO PREVENT PASSAGE OF X-RAY THROUGH
THE OPENING. PROVIDE EXTENSIONS RINGS AS REQUIRED FOR BACKBOX
IN CMU WALL.
9.312 RECEPTACLES DESIGNATED WITH 'SW' ARE CONTROLLED VIA OCCUPANCY
SENSOR. PROVIDE PLUG LOAD POWER PACK(S) ASSOCIATED WITH CEILING
MOUNTED OCCUPANCY SENSOR(S). REFER TO ASSOCIATED LIGHTING
PLANS FOR OCCUPANCY SENSOR TYPE AND LOCATION.
9.313 PROVIDE 4" SQUARE BOX WITH 1" CONDUIT INSTALLED BETWEEN JUNCTION
BOX AND PANEL 1/LD FOR FUTURE. PROVIDE PULL STRING. JUNCTION BOX
INSTALLED AT 18"AFF. COORDINATE WITH MILLWORK CONTRACTOR.
9.316 PROVIDE NEMA 4X STRUT RACK FROM FLOOR TO STRUCTURAL GIRDER
FOR INSTALLATION OF EQUIPMENT. PROVIDE STRUT CROSS MEMBERS AS
REQUIRED. EQUIPMENT SHALL NOT BE MOUNTED TO LEAD LINED HANGAR
WALL. COORDINATE DEVICE REQUIREMENTS OF OTHER TRADES (FIRE
ALARM, CONTROLS, ETC.) INSTALLED IN THIS LOCATION FOR RACK SIZE.
9.320 REFER TO DETAIL 2/E-501 FOR SCHEMATIC DIAGRAM OF X-RAY INTERLOCK
SYSTEM.
9.321 PROVIDE FEDERAL SIGNAL 121S-120R, RED, ROTATING LIGHT (MODIFIED
WITH SEPARATE CONDUCTORS FOR MOTOR NEUTRAL AND LAMP NEUTRAL).
PROVIDE WALL MOUNT BRACKET LWMB2.
9.332 ALL DISCONNECT SWITCHES IN HANGAR 123 SHALL BE NEMA 4X.
9.337 PROVIDE A TOTAL OF TEN (10) - 1" SPARE CONDUITS WITH PULL STRING
FROM PANEL 1/LD (SECOND TUB) TO ABOVE ACCESSIBLE CEILING AND CAP
FOR FUTURE USE.
1/8" = 1'-0"1
FIRST FLOOR POWER PLAN
11/09/18 B-3 FINAL
1/4" = 1'-0"2
ENLARGED KITCHEN AREA - ROOM 113
1/4" = 1'-0"3
ENLARGED LAUNDRY - ROOM 111
NOTE: ALL 120V NORMAL POWER RECEPTACLES FED FROM PANEL 1/LD UNLESS OTHERWISE NOTED. NOTE: ALL 120V NORMAL POWER RECEPTACLES FED FROM PANEL 1/LD UNLESS
OTHERWISE NOTED.
DN
EQUIPMENT
ROOM
ELEC.
E-102
IT
GFCI/WP46"
46"
46"
46" 46"
46"
46"
46"46"
11 11
CP-1
CP-2
CP-3
2/LA-19
2/LA-19
2/LA-19
WH-1
2/LA-21
SAC-1
SAC-1
BAC-1
BAC-1
AD-1
2/LA-23
HPW-1HPW-2
HPW-1
HPW-2SPM-1
2/LA-25
BP-1
AHU-1
AHU-2
B-1
B-2
2/LA-27,29
2/LA-31,33
EF-2
2/LA-35
ERU-1
MAU-1
VFD
VFD
P-1
P-2
P-1
P-2
UH-2
UH-1
TCP
2/LA-37
EF-4
2/LA-39
46"
EQUIPMENT
ROOM
IT
X1N
2/LA-2
NE
2/LA-2
N
2/LA-2
N
2/LA-2
N
2/LA-2
NE
2/LA-2
N
2/LA-2
N
2/LA-2
NE
2/LA-2
N
2/LA-2
N
2/LA-2
N
2/LA-2
N
2/LA-2
N
2/LA-2
NE
2/LA-2
N
2/LA-2
N
2/LA-2
NE
2/LA-2
N
2/LA-2
N
2/LA-2
N
2/LA-2
NE
2/LA-2
N
2/LA-2
9.202
9.202 (TYP.)
(TYP.)
ELEC.
2/LA-2
NE
9.203
2/LA-2
2/LA-2
N
N
9.204(TYP.)
2/LA-2
N1E
2/LA-2
N1
2/LA-2
N1
9.205
VIA LCP FOR PE ON /
TIMECLOCK OFF
PANEL 2/LA
1/LD-36
1/HA-12Ra
OCE
9.2129.212
MSB/HA PANEL MDP/LAXFMR T-1 PANEL 2/LE
PANEL 2/LA
46"
46"
46"
46"
46" 46"
ELEC.
IT
2/LA-12/LA-1
9.3179.317
9.330
9.331
PANEL MP/HA
GND GND
2/LB-11
AP
7 9
PANEL 2/LB
JP
FP
FMCP NAC
2/LE-2,4,6
9.314
9.315
46"
46"
GFCI
GFCI
2/LE-1 2/LE-3
FIRE
PROTECTION
ROOM
1/LD-28
1/LD-28
ANT
2/LE-5
BC
2/LE-7
SHEET NO.:
SHEET CONTENTS
DO NOT SCALE DRAWINGS
ISSUED
M&H NO.:
DATE:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
© Copyright This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.
Mead & Hunt, Inc.
9600 NE Cascades Parkway, Suite 100 Portland, OR 97220 phone: 503-548-1494 meadhunt.com www.tetratech.com
711 TANK FARM ROAD, SUITE 110
SAN LUIS OBISPO, CA 93401
PHONE: (805) 542-9052 FAX: (805) 542-9254
/7 /2
:4 :3
P
M C
R e v it L o c a l\
-1
.0 -E
-C E
N T
R A
L -2 jr h .r v t
E-102
EQUIPMENT FLOOR
ELECTRICAL PLANS
O R
A N
G
K in g s le y F ie ld
K la m a th
F a lls
O
R
C O
N S
T R
U C
T C
O R
R O
S
IO
N C
O N
T R
O L H
A N
G A
R
3142200-121252.01
KAS
IMR
11/09/18
JRH
1/8" = 1'-0"1
EQUIPMENT FLOOR POWER PLAN
1/8" = 1'-0"2
EQUIPMENT FLOOR LIGHTING REFLECTED CEILING PLAN
1/4" = 1'-0"3
ENLARGED PLAN - ELEC 203
11/09/18 B-3 FINAL
1/4" = 1'-0"4
ENLARGED FIRE PROTECTION ROOM 122
KEYED NOTES
9.202 MOUNT FIXTURE AT 9'-0" AFF MEASURED FROM BOTTOM OF FIXTURE.
9.203 MOUNT FIXTURE AT 8'-0" AFF MEASURED FROM BOTTOM OF FIXTURE.
9.204 MOUNT FIXTURE AT 8'-6" AFF MEASURED FROM BOTTOM OF FIXTURE.
9.205 MOUNT FIXTURE AT 7'-6" AFF MEASURED FROM BOTTOM OF FIXTURE.
9.212 MOUNT FIXTURE AT 7'-0" ABOVE STAIR/LANDING MEASURED FROM BOTTOM
OF FIXTURE.
9.314 FIRE PUMP CONTROLLER
9.315 JOCKEY PUMP CONTROLLER
9.317 INSTALL L5-20 SIMPLEX RECEPTACLE TO SIDE OF CABLE TRAY (TYPICAL OF
4). REFER TO DETAIL 8/E-501.
9.330 PROVIDE SURGE PROTECTIVE DEVICES (SPD) ON ALL 120VAC CIRCUITS
ASSOCIATED WITH EQUIPMENT FED FROM PANEL 2/LE. PROVIDE HINGED
TERMINAL BOX ADJACENT TO PANEL 2/LE FOR ALL SPD(S). SPD MUST HAVE
BOTH UL 1449 AND UL 1283 LISTING.
9.331 HOUSEKEEPING PAD BY OTHERS. COORDINATE SIZE AND LOCATION WITH
GENERAL CONTRACTOR PRIOR TO INSTALLATION.
NOTE: ALL 120V NORMAL POWER RECEPTACLES SHALL BE FED FROM PANEL 2/LB, UNLESS NOTED OTHERWISE.
NOTE: ALL 120V NORMAL POWER RECEPTACLES SHALL BE FED FROM PANEL 2/LA, UNLESS NOTED OTHERWISE.
9.322 9.322
9.322 9.322
9.322
9.322
9.322
9.322
9.322
9.322
9.322
9.322
9.322
9.322
9.323 9.323
9.323 9.323
9.3239.323
9.323 9.323
9.323 9.323
9.323 9.323 9.323
9.3239.323
9.324
9.324
9.325
9.326
9.327
(TYP)
G
G
G
G
G
G
G
G
G
G
G
G G
GGGGGGGGGGGGGGGGGG
G
G
G
GGG
G G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G G
G G G G G G
G
G
G
G
G
G
G
G
G
G
G
G G
G G G G G G G G G G
G
G
G
G G
G
G
G G G G G G G G G G G G G G
G G
G
G
G
G G G G G G G G G
G G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
GGGGGGGGGGGG
G
GGGGGGG
G
G
9.328 9.329
9.323
9.323
9.323
LIGHTNING PROTECTION AND
GROUNDING GENERAL NOTES:
1.
2.
3.
4.
THE LIGHTNING PROTECTION SHALL REQUIRE AN INSPECTION PRIOR TO
ACCEPTANCE PER UFC 3-575-01. THE SYSTEM SHALL BE INSPECTED BY A
COMMERCIAL, 3RD PARTY INSPECTOR WHOSE SOLE WORK IS LIGHTNING
PROTECTION AND SHALL BE CERTIFIED BY THIS 3RD PARTY INSPECTOR AS
COMPLIANT WITH AFI 32-1065 AND NFPA 780.
THE USE OF BUILDING STEEL AS DOWN CONDUCTORS IS NOT PERMITTED.
INSTALLATION OF THE LIGHTNING PROTECTION SYSTEM SHALL NOT VOID
THE WARRANTY OF THE ROOF.
ANY EXHAUST AND VENTS SHALL BE PROTECTED BY ADDITIONAL AIR
TERMINALS. REFER TO MECHANICAL AND PLUMBING PLANS.
LIGHTNING PROTECTION
AND GROUNDING SYMBOLS
GROUND ROD
GROUND ACCESS WELL
LIGHTNING AIR TERMINAL
STATIC GROUND RECEPTACLE
GR
GROUNDING CONDUCTORG
SHEET NO.:
SHEET CONTENTS
DO NOT SCALE DRAWINGS
ISSUED
M&H NO.:
DATE:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
© Copyright This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.
Mead & Hunt, Inc.
9600 NE Cascades Parkway, Suite 100 Portland, OR 97220 phone: 503-548-1494 meadhunt.com www.tetratech.com
711 TANK FARM ROAD, SUITE 110
SAN LUIS OBISPO, CA 93401
PHONE: (805) 542-9052 FAX: (805) 542-9254
/7 /2
:4 :3
P
M C
R e v it L o c a l\
-1
.0 -E
-C E
N T
R A
L -2 jr h .r v t
E-103
LIGHTNING
PROTECTION AND
GROUNDING PLAN
O R
A N
G
K in g s le y F ie ld
K la m a th
F a lls
O
R
C O
N S
T R
U C
T C
O R
R O
S
IO
N C
O N
T R
O L H
A N
G A
R
3142200-121252.01
KAS
IMR
11/09/18
JRH
1/8" = 1'-0"1
LIGHTNING PROTECTION AND GROUNDING PLAN
11/09/18 B-3 FINAL
KEYED NOTES
9.322 PROVIDE BIMETALLIC CONNECTOR BETWEEN #1/0 AL AND #2 AWG CU DOWN
CONDUCTOR. PROVIDE #2 AWG CU "DOWN CONDUCTOR" FROM ROOF TO
GROUND TERMINAL AS INDICATED. "DOWN CONDUCTOR" SHALL BE
ROUTED IN CONDUIT INTERIOR TO THE BUILDING AND WITHIN CMU/STUD
CAVITY WHEREVER POSSIBLE.
9.323 LIGHTNING PROTECTION SYSTEM GROUND TERMINALS SHALL BE MINIMUM
3/4" X 10'-0" COPPER-CLAD STEEL GROUND ROD BURIED INTO EARTH 1'-6"
TO TOP OF GROUND ROD. CONDUCTORS SHALL BE PERMANENTLY
CONNECTED TO GROUND TERMINAL WITH EXOTHERMIC WELD. PROVIDE
MINIMUM ONE (1) GROUND TERMINAL IN A GROUND ACCESS WELL FOR
TESTING REQUIREMENTS. REFER TO PLANS FOR EXACT QUANTITY OF
ACCESS WELLS.
9.324 PROVIDE #1/0 AL "MAIN-SIZE LIGHTNING CONDUCTOR" FOR INTERCONNECT
OF ALL AIR TERMINALS ON ROOF.
9.325 CONNECT LIGHTNING PROTECTION SYSTEM / GROUND RING TO BUILDING
GROUND VIA MAIN GROUND BAR IN ELECTRICAL ROOM. REFER TO DETAIL
1/E-503 FOR ADDITIONAL REQUIREMENTS.
9.326 PROVIDE #1/0 BARE COPPER COUNTERPOISE GROUND RING SYSTEM
INSTALLED A MINIMUM OF 3'-8" AWAY FROM STRUCTURE. GROUND RING
SHALL BE BURIED AT LEAST 30" BELOW GRADE.
9.327 20'-0" MAXIMUM SEPARATION BETWEEN AIR TERMINALS ALONG ROOF
PERIMETER AND AS INDICATED (TYPICAL).
9.328 BOND STRIKE TERMINATION DEVICE DIRECTLY TO TOP OF MECHANICAL
UNIT.
9.329 BOND TO BOTTOM OF MECHANICAL UNIT METALLIC ENCLOSURE.
OS1
OS1
OS1
OS3
OS3
OS2
OS2
OS1
OS3
OS3
OS1
OS1OS1
OS1
OS1
OS1
OS1
OS2
OS1
OS1
OS1 OS1
OS1
OS1
OS2
OS2
L
L
L
L
L
L
OS2
OS2
OS1
LIGHTING GENERAL NOTES:
1.
2.
3.
4.
5.
6.
7.
8.
REFER TO SHEET E-001 FOR NOTES, SYMBOLS AND ABBREVIATIONS.
REFER TO SHEET E-601 FOR LUMINAIRE SCHEDULE.
REFER TO SHEET E-602 FOR OCCUPANCY SENSOR, LIGHTING CONTROL
PANEL AND SWITCH STATION SCHEDULES.
EC SHALL ALLOW TIME AND EFFORT FOR ALL OCCUPANCY SENSOR AND
PHOTO SENSOR CALIBRATION.
LOCATION OF CEILING OCCUPANCY SENSORS ON THIS PLAN ARE SHOWN
DIAGRAMMATICALLY AND DOESN'T SUGGEST ACUTAL LOCATIONS. EC SHALL
COORDINATE EXACT PLACEMENT IN FIELD BASED ON THIE INSTALLED
DUCTWORK, PIPING AND DIFFUSERS TO PREVENT OCCUPANCY SENSOR
NUISANCE TRIPPING. DO NOT INSTALL SENSORS WITHIN 3'-0" OF DIFFUSERS.
ALL EMERGENCY BATTERY OPERATED EXIT LIGHTS AND EBU'S SHALL BE
WIRED FROM SAME LIGHTING BRANCH CIRCUIT AS ROOM BEING SERVED.
ALL DEVICES AND EQUIPMENT IN CORROSION CONTROL HANGAR 123 SHALL
BE SURFACE MOUNTED. ALL CONDUIT SHALL BE RUN OVERHEAD AND
OUTSIDE OF THE HAZARDOUS CLASSIFICATION ZONE. NO CONDUIT SHALL BE
ROUTED BELOW HANGAR SLAB, UNLESS NOTED OTHERWISE. CONDUIT
SHALL NOT BE ATTACHED TO LEAD-LINED HANGAR WALLS. CONDUIT SHALL
BE ATTACHED TO HORIZONTAL STRUCTURAL GIRDERS. PROVIDE ADDITIONAL
SUPPORTS AS REQUIRED. ALL SUPPORTS, HANGARS AND STRUT UTILIZED IN
HANGAR 123 SHALL BE NEMA 4X. COORDINATE ROUTING WITH OTHER
TRADES. ALL CONDUIT IN HANGAR 123 SHALL BE RMC.
REFER TO DETAIL 3/E-503 FOR CONDUIT REQUIREMENTS FOR PASSING THRU
LEAD-LINED WALLS.
X-RAY CR
OIL ANALYSIS
ROOM
OFFICE
EQUIPMENT
ROOM
INSPECTION
BAY
VEST.
STENCIL
ROOM
FIRE
PROTECTION
ROOM
AIR LOCK
PPE CLEAN ROOM/
CIRCULAT.
WOMEN'S
LOCKER
ROOM
WOMEN'S
JAN
MEN'S
LAUNDRY
ROOM
MEN'S
LOCKER
ROOM
HALLWAY
VEST.
OFFICE
TRAINING /
BREAK ROOM
PAINT BOOTH
PAINT MIXING
ROOM/STOR
BEAD BOOTH
ROOM
AEA
B1E
B1E
D
A3
A
N1
N3
N3
OAE
OAE
OAE OCE
OC
OCE
OC1
OC2
OC2
OC2
N1
N1
OCE
OCE
D
3bPANEL 1/LC
PANEL 1/LF
PANEL 1/LD
OCE
X1
X1
X1
X1
X1
X1
X1
X1
X3
X3
HANGAR
9.207 L 8Rd
L 8Rd
L 8Rd
L 8Rd
L 6Rc
L 6Rc
L 6Rc
L 6Rc
L 4Rb
L 4Rb
L 4Rb
L 4Rb
L 2Ra
L 2Ra
L 2Ra
L 2Ra
9.208 (TYP.)
F 10Rg
F 10Rg
F 10Rg
F 10Re
F 10Re
F 10Re
F 10Rf
F 10Rf
EBU1 EBU1
EBU1
EBU1
EBU1
EBU1 EBU1
EBU1
EBU1
EBU1
EBU1
9.220 (TYP.)
1/HA-12Ra
1/HA-12Ra
1/HA-12Ra
VIA LCP FOR PE ON /
TIMECLOCK OFF
VIA LCP FOR PE ON /
TIMECLOCK OFF
VIA LCP FOR PE ON /
TIMECLOCK OFF
9.208
9.208
9.208
1/HA-12Ra
VIA LCP FOR PE ON /
TIMECLOCK OFF
9.209
9.210(TYP.)
VIA LCP FOR PE ON /
TIMECLOCK OFF
1/LA-12Ra
9.211
1/HA-12Ra
VIA LCP FOR PE ON /
TIMECLOCK OFF
9.209 1/HA-12Ra
VIA LCP FOR PE ON /
TIMECLOCK OFF
9.209
1/HA-12Ra
VIA LCP FOR PE ON /
TIMECLOCK OFF
OC
1/HA-12Ra
VIA LCP FOR PE ON /
TIMECLOCK OFF
9.209
1/HA-12Ra
VIA LCP FOR PE ON /
TIMECLOCK OFF
9.209
1/HA-12Ra
VIA LCP FOR PE ON /
TIMECLOCK OFF
1/HA-12Ra
VIA LCP FOR PE ON /
TIMECLOCK OFF
9.212
1/HA-12Ra
VIA LCP FOR PE ON /
TIMECLOCK OFF
OCE
1/HA-12Ra
VIA LCP FOR PE ON /
TIMECLOCK OFF
9.209
OC1 OC1
1/LA-12Ra 1/LA-12Ra
VIA LCP FOR PE ON /
TIMECLOCK OFF
VIA LCP FOR PE ON /
TIMECLOCK OFF
9.211
9.211
OCE
1/HA-12Ra
VIA LCP FOR PE ON /
TIMECLOCK OFF
9.209
1/HA-12Ra
VIA LCP FOR PE ON /
TIMECLOCK OFF
9.209
QE
P
9.206
9.206
N1
N1
N1
N1
A2E A2
A2
B
BE
BE
BE
BE
B
B
BE
BE
WS
WS
WS
C
C
32b
32a
C 30a
C 30b C 30a
C
30b
C
30b
C
30b
CE
30b
32b D1
32b D1E
32b D1
32a D1E
32a D1
32a D1E
32a D1 a ab
3b
D2
T 32 D2
30b
D1
30b D1
30b D1E
30b D1E
30b D1 b b b
3b
3b
D2
D2
D2
D2
T T
30a D1
30a D1E
30a D1E a
D1 30a
D4 30c
D3 30b
Da
Db a,b,c,d
X1
D
WS
D
19 19
A3
D A
AE
A
3D
D A
A
FILM VIEWING
ROOM
AE
WS
X-RAY VAULT
ROOM
3D
21a
N2
21a
N2
21b
N2
21b
N2
21b
N2E
21b
N2
21a
N2
21a
N2E
21b
N2
21b
N2
21a
N2
21a
N2
21b
N2E
21a
N2E
9.214 (TYP.)
9.214 (TYP.)
a,b a,b
3b
3a
D
3a 3b
PANEL 1/HA
UNLESS NOTED OTHERWISE
PANEL 1/LF
UNLESS NOTED OTHERWISE
PANEL 1/LF
UNLESS NOTED OTHERWISE
PANEL 1/LD
UNLESS NOTED OTHERWISE
PANEL 1/LD
UNLESS NOTED OTHERWISE
PANEL 1/LC
UNLESS NOTED OTHERWISE
PANEL 1/LB
UNLESS NOTED OTHERWISE
PANEL 1/LB
UNLESS NOTED OTHERWISE
PANEL 1/HA
UNLESS NOTED OTHERWISE
PANEL 1/LB
9.206(TYP.)
A
A2
A1
B2
B1
B
LCP 9.215
WP
WP
WP
WP
WP
WP
PE
MOUNT ON ROOF.
AIM NORTH.
OB
1/HA-14Rb
VIA LCP FOR
PE ON / OFF
(MTD ON ROOF)
OB
1/HA-14Rb
VIA LCP FOR
PE ON / OFF
(MTD ON ROOF)
OB
1/HA-14Rb
VIA LCP FOR
PE ON / OFF
(MTD ON PARAPET)
OB
1/HA-14Rb
VIA LCP FOR
PE ON / OFF
(MTD ON PARAPET)
A
EBU
9.209
PANEL 1/HA
B
A2
B
BE
B
BE
B
C 32a
C 30a
C
C
C
C
C
C
OC
1/HA-12Ra
9.216
VIA LCP FOR PE ON /
TIMECLOCK OFF
A4E
Q
Q
Q
(TYP.)
Q
Q
Q
Q
QE
QE
D3 30b
D3 30b
D3 30b
30a D1
30a D1E
30a D1
30a D1E
30a D1
30a D1E
30a D1
30a D1E
30a D1
UU
9.210
9.210
9.210
9.217
(TYP.) d
30d 30d
Dc
9.210 (TYP.)
9.217
(TYP.)
a,b,c,d
9.3079.307
EBU1
9.221
9.222
9.222
9.316
9.316 a
A
A
9.223
9.223
9.223
9.224
KEYED NOTES
9.206 OCCUPANCY SENSORS SHALL BE PENDANT MOUNTED BELOW ALL
STRUCTURAL BEAMS, PLUMBING AND MECHANICAL PIPING AND DUCTWORK
TO ALLOW FOR CLEAN VIEWING ANGLE.
9.207 REFER TO DETAIL 1/E-501. TYPICAL FOR ALL WALL MOUNTED EXIT SIGNS
SHOWN ON THIS PLAN.
9.208 MOUNT FIXTURE AT 32'-0" AFF MEASURED FROM BOTTOM OF FIXTURE.
9.209 MOUNT FIXTURE AT 10'-0" AFF MEASURED FROM BOTTOM OF FIXTURE.
9.210 MOUNT FIXTURE AT 13'-0" AFF MEASURED FROM BOTTOM OF FIXTURE OR
ON NEAREST HORIZONTAL STRUCTURAL GIRDER. ALL TYPE F FIXTURES
SHALL BE MOUNTED AT SAME HEIGHT.
9.211 MOUNT FIXTURE AT 13'-6" AFF MEASURED FROM BOTTOM OF FIXTURE.
9.212 MOUNT FIXTURE AT 7'-0" ABOVE STAIR/LANDING MEASURED FROM BOTTOM
OF FIXTURE.
9.214 MOUNT FIXTURE AT 12'-0" AFF MEASURED FROM BOTTOM OF FIXTURE.
9.215 PROVIDE WITH NEMA 4X ENCLOSURE.
9.216 MOUNT FIXTURE BELOW MEZZANINE STAIR LANDING AT 9'-6" AFG
MEASURED FROM BOTTOM OF FIXTURE.
9.217 FIXTURE SHALL BE TRAPEZE MOUNTED BELOW MECHANICAL DUCTWORK
AT 12'-0" AFF MEASURED FROM BOTTOM OF FIXTURE.
9.220 MOUNT FIXTURE AT ROUGHLY 8'-6" AFF TO BOTTOM OF FIXTURE OR ON
NEAREST HORIZONTAL STRUCTURAL GIRDER. ALL EBUS SHALL BE
MOUNTED AROUND HANGAR AT SAME HEIGHT.
9.221 PROVIDE ADDITIONAL NEMA 4X STRUT SUPPORTS OFF OF STRUCTURAL
GIRDER TO ALLOW FOR EXIT SIGN MOUNTING. TYPICAL OF EXIT SIGNS IN
HANGAR 123.
9.222 MOUNT TO COLUMN.
9.223 PROVIDE FEDERAL SIGNAL 121S-120R, RED, ROTATING LIGHT (MODIFIED
WITH SEPARATE CONDUCTORS FOR MOTOR NEUTRAL AND LAMP NEUTRAL).
PROVIDE WALL MOUNT BRACKET LWMB2. MOUNT BEACON LIGHT AT 7'-6".
BEACON LIGHTS (TYPICAL OF 3 WITH THIS NOTE) CONTROLLED BY SWITCH
IN AIR LOCK 124. BEACON LIGHTS SHALL BE CIRCUITED TO PANEL 1/LA-41.
9.224 PROVIDE SWITCH WITH ENGRAVED NAMEPLATE "XRAY BEACON LIGHTS".
9.307 XRAY VAULT ROOM RECESSED BACKBOXES TO BE LINED WITH EQUAL
THICKNESS SHEET LEAD. REFER TO SHEET A-142 FOR ADDITIONAL
INFORMATION. CONDUITS PENETRATING LEAD LINING SHOULD BE DONE SO
WITH A LEAD WRAPPED ELBOW TO PREVENT PASSAGE OF X-RAY THROUGH
THE OPENING. PROVIDE EXTENSIONS RINGS AS REQUIRED FOR BACKBOX
IN CMU WALL.
9.316 PROVIDE NEMA 4X STRUT RACK FROM FLOOR TO STRUCTURAL GIRDER
FOR INSTALLATION OF EQUIPMENT. PROVIDE STRUT CROSS MEMBERS AS
REQUIRED. EQUIPMENT SHALL NOT BE MOUNTED TO LEAD LINED HANGAR
WALL. COORDINATE DEVICE REQUIREMENTS OF OTHER TRADES (FIRE
ALARM, CONTROLS, ETC.) INSTALLED IN THIS LOCATION FOR RACK SIZE.
SHEET NO.:
SHEET CONTENTS
DO NOT SCALE DRAWINGS
ISSUED
M&H NO.:
DATE:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
© Copyright This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.
Mead & Hunt, Inc.
9600 NE Cascades Parkway, Suite 100 Portland, OR 97220 phone: 503-548-1494 meadhunt.com www.tetratech.com
711 TANK FARM ROAD, SUITE 110
SAN LUIS OBISPO, CA 93401
PHONE: (805) 542-9052 FAX: (805) 542-9254
/7 /2
:4 :4
P
M C
R e v it L o c a l\
-1
.0 -E
-C E
N T
R A
L -2 jr h .r v t
E-121
FIRST FLOOR
LIGHTING PLAN
O R
A N
G
K in g s le y F ie ld
K la m a th
F a lls
O
R
C O
N S
T R
U C
T C
O R
R O
S
IO
N C
O N
T R
O L H
A N
G A
R
3142200-121252.01
KAS
IMR
11/09/18
JRH
1/8" = 1'-0"1
FIRST FLOOR LIGHTING PLAN
UP
X-RAY VAULT
ROOM
X-RAY CR
FILM VIEWING
ROOM
OIL ANALYSIS
ROOM
OFFICE
EQUIPMENT
ROOM
INSPECTION
BAY
VEST.
STENCIL
ROOM
FIRE
PROTECTION
ROOM
AIR LOCK
PPE CLEAN
ROOM/
CIRCULAT.
WOMEN'S
LOCKER
ROOM
WOMEN'S
JAN
MEN'S
LAUNDRY
ROOM
MEN'S
LOCKER
ROOM
HALLWAY
VEST.
OFFICE
TRAINING /
BREAK ROOM
PAINT BOOTH
BEAD BOOTH
ROOM
PAINT MIXING
ROOM/STOR
9.1019.102
5'-0"
E-152
E-152
CLASS 1, DIVISION 1 AREA IN TRENCH
HAZARDOUS CLASSIFICATION NOTES:
1.
2.
3.
4.
5.
ALL ELECTRICAL WORK IN HAZARDOUS AREAS SHALL BE IN ACCORDANCE
WITH NATIONAL ELECTRICAL CODE ARTICLE 501 CLASSIFICATION INDICATED.
CLASSIFICATION APPLIES TO ENTIRE VOLUME OF ROOM, PAINT BOOTH, OR
BEAD BLAST BOOTH. DIVISION 2 AREA EXTENDS OUTSIDE ROOM TO A THREE
FOOT RADIUS FROM CENTERLINE OF OUTSIDE DOOR FACE FROM FLOOR TO
TOP OF DOOR.
BELOW FLOOR LEVEL: ANY PIT OR DEPRESSION BELOW THE LEVEL OF THE
HANGAR FLOOR SHALL BE CLASSIFIED AS A CLASS 1 DIVISION 1 LOCATION
THAT SHALL EXTEND UP TO SAID FLOOR LEVEL.
AREAS NOT CUT OFF OR VENTILATED FROM HANGAR: THE ENTIRE AREA OF
THE HANGAR INCLUDING ANY ADJACENT AND COMMUNICATION AREAS NOT
SUITABLY CUT OFF FROM THE HANGAR SHALL BE CLASSIFIED AS CLASS 1
DIVISION 2 LOCATION UP TO 18" AFF.
VICINITY OF AIRCRAFT: THE AREA WITHIN 5 FEET HORIZONTALLY FROM
AIRCRAFT POWER PLANTS OR FUEL TANK SHALL BE CLASSIFIED AS A CLASS
1 DIVISION 2 LOCATION THAT SHALL EXTEND UPWARD FROM FLOOR TO A
LEVEL 5 FEET ABOVE THE UPPER SURFACE OF THE WINGS AND OF ENGINE
ENCLOSURES.
HAZARDOUS CLASSIFICATION
HATCHING KEY:
CLASS 1, DIVISION 1
CLASS 1, DIVISION 2
SHEET NO.:
SHEET CONTENTS
DO NOT SCALE DRAWINGS
ISSUED
M&H NO.:
DATE:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
© Copyright This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.
Mead & Hunt, Inc.
9600 NE Cascades Parkway, Suite 100 Portland, OR 97220 phone: 503-548-1494 meadhunt.com www.tetratech.com
711 TANK FARM ROAD, SUITE 110
SAN LUIS OBISPO, CA 93401
PHONE: (805) 542-9052 FAX: (805) 542-9254
/7 /2
:4 :4
P
M C
R e v it L o c a l\
-1
.0 -E
-C E
N T
R A
L -2 jr h .r v t
E-151
FIRST FLOOR
HAZARDOUS
CLASSIFICATION
AREAS
O R
A N
G
K in g s le y F ie ld
K la m a th
F a lls
O
R
C O
N S
T R
U C
T C
O R
R O
S
IO
N C
O N
T R
O L H
A N
G A
R
3142200-121252.01
KAS
IMR
11/09/18
JRH
1/8" = 1'-0"1
FIRST FLOOR HAZARDOUS CLASSIFICATION AREAS PLAN
KEYED NOTES
9.101 PAINT BOOTH TO BE SELECTED BY GOVERNMENT. DIMENSIONS AND
CLASSIFICATION AREAS TO BE FINALIZED AFTER GOVERNMENT SELECTION.
CLASSIFICATION AREA EXTENDS 3'-0" BEYOND ANY OPENING IN BOOTH.
9.102 BEAD BLAST BOOTH TO BE BY GOVERNMENT. DIMENSIONS AND
CLASSIFICATION AREAS TO BE FINALIZED AFTER GOVERNMENT SELECTION.
CLASSIFICATION AREA EXTENDS 3'-0" BEYOND ANY OPENING IN BOOTH.
TOP OF WING AND/OR ENGINE ENCLOSURE
CLASS 1, DIVISION 1 AREA (IN PIT)
HAZARDOUS CLASSIFICATION NOTES:
1.
2.
3.
4.
5.
ALL ELECTRICAL WORK IN HAZARDOUS AREAS SHALL BE IN ACCORDANCE
WITH NATIONAL ELECTRICAL CODE ARTICLE 501 CLASSIFICATION INDICATED.
CLASSIFICATION APPLIES TO ENTIRE VOLUME OF ROOM, PAINT BOOTH, OR
BEAD BLAST BOOTH. DIVISION 2 AREA EXTENDS OUTSIDE ROOM TO A THREE
FOOT RADIUS FROM CENTERLINE OF OUTSIDE DOOR FACE FROM FLOOR TO
TOP OF DOOR.
BELOW FLOOR LEVEL: ANY PIT OR DEPRESSION BELOW THE LEVEL OF THE
HANGAR FLOOR SHALL BE CLASSIFIED AS A CLASS 1 DIVISION 1 LOCATION
THAT SHALL EXTEND UP TO SAID FLOOR LEVEL.
AREAS NOT CUT OFF OR VENTILATED FROM HANGAR: THE ENTIRE AREA OF
THE HANGAR INCLUDING ANY ADJACENT AND COMMUNICATION AREAS NOT
SUITABLY CUT OFF FROM THE HANGAR SHALL BE CLASSIFIED AS CLASS 1
DIVISION 2 LOCATION UP TO 18" AFF.
VICINITY OF AIRCRAFT: THE AREA WITHIN 5 FEET HORIZONTALLY FROM
AIRCRAFT POWER PLANTS OR FUEL TANK SHALL BE CLASSIFIED AS A CLASS
1 DIVISION 2 LOCATION THAT SHALL EXTEND UPWARD FROM FLOOR TO A
LEVEL 5 FEET ABOVE THE UPPER SURFACE OF THE WINGS AND OF ENGINE
ENCLOSURES.
9.1019.102
HAZARDOUS CLASSIFICATION
HATCHING KEY:
CLASS 1, DIVISION 1
CLASS 1, DIVISION 2
SHEET NO.:
SHEET CONTENTS
DO NOT SCALE DRAWINGS
ISSUED
M&H NO.:
DATE:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
© Copyright This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.
Mead & Hunt, Inc.
9600 NE Cascades Parkway, Suite 100 Portland, OR 97220 phone: 503-548-1494 meadhunt.com www.tetratech.com
711 TANK FARM ROAD, SUITE 110
SAN LUIS OBISPO, CA 93401
PHONE: (805) 542-9052 FAX: (805) 542-9254
/7 /2
:4 :4
P
M C
R e v it L o c a l\
-1
.0 -E
-C E
N T
R A
L -2 jr h .r v t
E-152
HAZARDOUS
CLASSIFICATION
AREAS -
ELEVATIONS
O R
A N
G
K in g s le y F ie ld
K la m a th
F a lls
O
R
C O
N S
T R
U C
T C
O R
R O
S
IO
N C
O N
T R
O L H
A N
G A
R
3142200-121252.01
KAS
IMR
11/09/18
JRH
1/8" = 1'-0"1
HAZARDOUS CLASSIFICATION ELEVATION - HANGAR BAY
KEYED NOTES
9.101 PAINT BOOTH TO BE SELECTED BY GOVERNMENT. DIMENSIONS AND
CLASSIFICATION AREAS TO BE FINALIZED AFTER GOVERNMENT SELECTION.
CLASSIFICATION AREA EXTENDS 3'-0" BEYOND ANY OPENING IN BOOTH.
9.102 BEAD BLAST BOOTH TO BE BY GOVERNMENT. DIMENSIONS AND
CLASSIFICATION AREAS TO BE FINALIZED AFTER GOVERNMENT SELECTION.
CLASSIFICATION AREA EXTENDS 3'-0" BEYOND ANY OPENING IN BOOTH.
1/8" = 1'-0"2
HAZARDOUS CLASSIFICATION ELEVATION - PAINT AND BEAD BOOTHS
3'-0"
F R
A M
E H
E
IG
H T
0'-4"
LOCATE 3" ABOVE DOOR FRAME
WHEN DIM ABOVE IS 12" OR
GREATER.
ALIGN WITH TOP OF DOOR
FRAME WHEN DIM. ABOVE
DOOR HEAD <12" MOUNT
ON STRIKE SIDE
FUSED DISC.
SW. BY C.
4#12, 3/4"C.
CONTROL PANEL
BY EQUIPMENT
SUPPLIER
5#16, 3/4"C.
OPEN/CLOSE
PUSH BUTTON
ONE EACH SIDE
TO PANEL
INTERLOCK
PANEL
BEACON
TERMINAL
BOX
TO FIELD INTERLOCK DEVICES (DOOR SWITCHES)
KEYED NOTES:
1. MOUNT INTERLOCK PANEL TO WALL OF ROOM 105.
2. MOUNT BEACON TERMINAL BOX WITHIN 8'-0" OF INTERLOCK PANEL IN ROOM 105.
3. MOUNT JUNCTION BOX WITHIN 8'-0" OF INTERLOCK PANEL FOR JOINING INTERLOCK
CIRCUITS.
4. MOUNT JUNCTION BOX WITHIN 8'-0" OF INTERLOCK PANEL FOR PROVIDING 120V
A.C. POWER TO PANEL.
5. REFER TO SHEET E-101 FOR BEACON LIGHT LOCATIONS.
6. REFER TO SHEET E-101 FOR EPO LOCATION.
GENERAL NOTES:
1. X-RAY INTERLOCK SYSTEM EQUIPMENT AND DEVICES PROVIDED BY
GOVERNMENT, INSTALLED AND WIRED BY ELECTRICAL CONTRACTOR. X-RAY
INTERLOCK SYSTEM IS TSG CAT. TSGDD1423.
2. ELECTRICAL CONTRACTOR RESPONSIBLE FOR ALL CONDUIT, BACKBOXES AND
WIRING.
3. COORDINATE INSTALLATION OF SYSTEM WITH C.O.R.
1 2
120V
3#12, 3/4"C.
3#12, 3/4"C.
TO EPO
FOR BIDDING PURPOSES ASSUME 4#12, 3/4"C. (TYPICAL OF ALL)
6#12, 3/4"C.
1" CONDUIT WITH MFR CABLE
12#12, 1"C.
2" 2"18" DIA.
GROUND
PAINT THE WORD "GROUND" IN 1"
BLACK LETTERS AND THE DATE
TESTED IN 1/2" BLACK LETTERS
PAINT RED
PAINT YELLOW
GROUND
RECEPTACLE SET IN
FLOOR
PLAN
3/4"
2-3/4" DIA.
-7
/8
M
IN
F
O R
H A
N G
A R
S
M
IN
F
O R
H Y
D R
A N
T
R E
F U
E L
IN
G S
Y S
T E
M
CAST BRONZE COVER,
FRICTION FIT BRASS PIN
CAST BRONZE HOUSING.
#4 FOR WATER SERVICE
MAIN CONNECTION IN
HANGARS.
IN HANGARS, MAX.
RESISTANCE TO GROUND
SHALL BE 25 OHMS FROM
ANY GROUND ROD.
INSTALL BELOW CONCRETE
SLAB. EXOTHERMIC
BONDING. GROUNDING
CABLE: #4 FOR HANGARS. #
1/0 FOR HYDRANT
REFUELING.
3/4" N.C. THREAD.
3/4" PIPE OR ROD FOR
HANGARS. 3/4" COPPER-
WELD GROUND ROD FOR
HYDRANT REFUELING.
#10 BRASS BALL CHAIN.
FINISHED HANGAR FLOOR
OR APRON PAVEMENT.
ELEVATION
2'-0" MIN. BELOW FINAL GRADE
CONDUITS-TYPE, QUANTITY AND SIZE AS
SHOWN ON DRAWINGS
4" SAND FILL ABOVE AND BELOW CONDUITS
COMPACTED BACKFILL W/ 2" OR SMALLER
AGGREGATE
METALLIC WARNING TAPE 6" BELOW FINAL GRADE
PAVEMENT
MULTIPLE CONDUITS UNDER PAVEMENT
2'-0" MIN. BELOW FINAL GRADE
CONDUITS-TYPE, QUANTITY AND SIZE AS
SHOWN ON DRAWINGS
4" SAND FILL ABOVE AND BELOW CONDUITS
COMPACTED BACKFILL W/ 2" OR
SMALLER AGGREGATE
METALLIC WARNING TAPE 12" BELOW FINAL
GRADE
ORGANIC TOP SOIL (GRASS AREA)MULTIPLE CONDUITS UNDER GRASS
CONTINUOUS (360 DEGREE) SWIVEL
GROUNDED RETRACTABLE POWER
CORD W/ DUAL RECEPTACLE ON END.
FURNISHED W/ 12 FT OF 12-3 SJO CORD
(2 CONDUCTORS PLUS GROUND)
ENCLOSED STEEL CONSTRUCTION,
UL LISTED, LOCKING RATCHET TO
HOLD CORD AT DESIRED LENGTH.
MOUNTS ON 4" OCTAGONAL OUTLET
BOX.
PORTABLE OUTLET BOX FOR (2) STANDARD DUPLEX
RECEPTACLES. DANIEL WOODHEAD #3000 WITH TWO
(2) 20A, 120V DUPLEX RECEPTACLES IN BOX.
BALL
STOP
NEMA L5-20R
RECEPTACLE
U-CHANNEL STRUT
1/2" ALL-THREAD
SUPPORT
EMT CONDUIT
SUPPORTED TO
CEILING
FINISHED FLOOR
46"
18"
POWER RECEPTACLES
LOCATED IN OFFICES AND
OTHER FINISHED AREAS
UNLESS NOTED OTHERWISE.
ALL SWITCHES, FA PULL STATIONS
AND POWER RECEPTACLES LOCATED
IN UNFINISHED AREAS UNLESS NOTED
OTHERWISE.
NOTE:
MOUNTING HEIGHT DIMENSION FOR POWER RECEPTACLES ABOVE
COUNTER SHALL BE 6" ABOVE TOP OF COUNTER OR COUNTER
BACKSPLASH MEASURED TO THE CENTER OF THE OUTLET BOX.
CENTER OF
OUTLET BOX
SHEET NO.:
SHEET CONTENTS
DO NOT SCALE DRAWINGS
ISSUED
M&H NO.:
DATE:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
© Copyright This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.
Mead & Hunt, Inc.
9600 NE Cascades Parkway, Suite 100 Portland, OR 97220 phone: 503-548-1494 meadhunt.com www.tetratech.com
711 TANK FARM ROAD, SUITE 110
SAN LUIS OBISPO, CA 93401
PHONE: (805) 542-9052 FAX: (805) 542-9254
/7 /2
:4 :4
P
M C
R e v it L o c a l\
-1
.0 -E
-C E
N T
R A
L -2 jr h .r v t
E-501
DETAILS
O R
A N
G
K in g s le y F ie ld
K la m a th
F a lls
O
R
C O
N S
T R
U C
T C
O R
R O
S
IO
N C
O N
T R
O L H
A N
G A
R
3142200-121252.01
KAS
IMR
11/09/18
JRH
NO SCALE1
EXIT SIGN WALL MOUNTING AT DOOR
NO SCALE3
MOTORIZED ROLL-UP DOOR WITH
PUSH BUTTON CONTROL
11/09/18 B-3 FINAL
NO SCALE2
INTERLOCK PANEL WIRING DIAGRAM
NO SCALE4
STATIC GROUNDING RECEPTACLE
NO SCALE5
UNDERGROUND CONDUIT DETAIL-PAVEMENT
NO SCALE6
UNDERGROUND CONDUIT DETAIL-GRASS
NO SCALE7
RETRACTABLE RECEPTACLE DETAIL
NO SCALE8
RACK RECEPTACLE DETAIL
NO SCALE9
DEVICE MOUNTING HEIGHTS DETAIL
UNIVERSAL FLAT SURFACE AIR
TERMINAL BASE MOUNTED
VERTICALLY
CUAT / ALAT - STYLE GENTLY
TAPERED AIR TERMINAL
CABLE FASTENER
COPPER OR ALUMINUM
CLASS I OR CLASS II
LIGHTNING PROTECTION
CONDUCTOR
TOP VIEW (COVER REMOVED)
GROUND ROD
GROUND CLAMP
GRAVEL OR CRUSHED
STONE
GROUNDING CONDUCTOR
COVER REFERENCED ABOVE
(TOP VIEW)
POLYMER CONCRETE
FIBERGLASS REINFORCED BOX
SECTION A-A
A-A A-A
WELD CONDUCTOR TO
GROUND ROD OR USE
HIGH COMPRESSION
FITTING
3/4" X 10' COPPERCLAD
GROUND ROD
#4/0 CU. GROUND
CONDUCTOR
NATIVE BACKFILL
GENERAL NOTES:
1. NEUTRAL SYSTEM TO TEST AT LESS THAN 10 OHMS. IF THIS CAN'T BE MET, INFORM
CONTRACTING OFFICER FOR DIRECTIONS.
4"
CUAT / ALAT - STYLE GENTLY
TAPERED AIR TERMINAL
UNIVERSAL SWIVEL AIR
TERMINAL BASE
COPPER OR ALUMINUM,
CLASS I
OR CLASS II LIGHTNING
PROTECTION CONDUCTOR
NPL LIGHTNING PROTECTION
CONDUCTORS
FASTEN COPPER CONDUCTORS
WITH COPPER STANDING SEAM
METAL ROOM FASTER. FASTEN
ALUMINUM CONDUCTORS WITH
ALUMINUM STANDING SEAM
METAL ROOF FASTENER.
LIGHTNING PROTECTION
CONDUCTORS SHALL BE
FASTENED AT INTERVALS NOT
MORE THAN 36" ON CENTER
EXTRUDED COPPER STANDING
SEAM METAL ROOF AIR TERMINAL
BASE. FOR SURFACES NOT
COMPATIBLE WITH COPPER USE
EXTRUDED ALUMINUM STANDING
SEAM METAL ROOF AIR TERMINAL
BASE. PENETRATING SCREW
HARDWARE NOT ALLOWED.
NOTES:
AIR TERMINAL SPACING SHALL CONFORM TO NFPA 780 & UL 96A REQUIREMENTS.
MATERIAL COMPATIBILITY SHALL CONFORM TO NFPA 780 & 96A REQUIREMENTS.
MATERIAL CLASS SHALL CONFORM TO NFPA 780 & UL 96A REQUIREMENTS.
AIR TERMINALS SHALL BE UL LISTED.
SHEET NO.:
SHEET CONTENTS
DO NOT SCALE DRAWINGS
ISSUED
M&H NO.:
DATE:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
© Copyright This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.
Mead & Hunt, Inc.
9600 NE Cascades Parkway, Suite 100 Portland, OR 97220 phone: 503-548-1494 meadhunt.com www.tetratech.com
711 TANK FARM ROAD, SUITE 110
SAN LUIS OBISPO, CA 93401
PHONE: (805) 542-9052 FAX: (805) 542-9254
/7 /2
:4 :4
P
M C
R e v it L o c a l\
-1
.0 -E
-C E
N T
R A
L -2 jr h .r v t
E-502
DETAILS
O R
A N
G
K in g s le y F ie ld
K la m a th
F a lls
O
R
C O
N S
T R
U C
T C
O R
R O
S
IO
N C
O N
T R
O L H
A N
G A
R
3142200-121252.01
KAS
IMR
11/09/18
JRH
11/09/18 B-3 FINAL
NO SCALE2
AIR TERMINAL BASE
NO SCALE3
CABLE FASTENER
NO SCALE4
BI-METAL CONNECTOR
NO SCALE5
BONDING CONNECTOR
NO SCALE6
CROSS RUN CONNECTOR
NO SCALE7
PARALLEL CONNECTOR
NO SCALE8
PARALLEL CONNECTOR
NO SCALE10
GROUND ACCESS WELL
NO SCALE9
GROUND CONDUCTOR SECTION DETAIL
NO SCALE1
AIR TERMINAL - METAL SEAM ROOF
#2 GRD
#6 GRD#3/0 GRD
#3/0 GRD
#3/0 GRD
CABLE TRAY
TELECOM EQUIPMENT RACK(S)
MAIN TELECOM ROOM
MAIN GROUNDING BUSBAR (TMGB)
STREET SIDE OF BUILDING
WATER METER. CONNECT TO
METALLIC WATER MAIN
WITHIN 5'-0" OF WATER
SERVICE ENTRANCE. PROVIDE
JUMPER ACROSS WATER METER.
CONCRETE FOOTING
GROUND BUS LOCATED IN
ELECTRICAL ROOM.
SWITCHBOARD
NEUTRAL BUS
PANELBOARD(S) GROUND BUS
NOTES:
1. ALL GROUND CONDUCTORS TO BE ROUTED IN PVC CONDUIT.
2. ALL GROUND CONDUCTORS ON THIS DIAGRAM SHALL BE COPPER.
3. REFER TO SHEET E-103 FOR CONNECTIONS OF LIGHTNING PROTECTION SYSTEM TO GROUND RING.
EQUIPMENT GROUNDING
CONDUCTOR
PER NEC 250.122. SEE
FEEDER SCHEDULE
GROUNDING ELECTRODE CONDUCTOR
SIZED PER NEC 250.66.
15KVA-#8 AWG
30KVA-#6 AWG
45KVA-#4 AWG
75KVA-#3 AWG
112.5KVA-#2 AWG
150KVA - #1/0 AWG
225KVA - #3/0 AWG
300KVA-#4/0 AWG
REMOVABLE LINK
TYPICAL: DRY-TYPE TRANSFORMER IN ELECTRICAL ROOMS.
SEE PLANS FOR EXACT LOCATIONS AND ROOM NUMBERS.
GROUND RING
FOUNDATION REBAR
UL LISTED FITTINGS FOR THE
PURPOSE (TYP)
REBAR STUBBED THROUGH FLOOR BY FOUNDATION
CONTRACTOR.
GROUND BUS
SWITCHBOARD
MAIN BONDING JUMPER
SIZED PER NEC 250.28(D).
GR GR GR
LEAD-LINED SIDE OF HANGAR
123 OR XRAY ROOM 104.
LEAD WRAP CONDUIT
ELBOW. PROVIDE ELBOW
ADJACENT TO WALL
CONDUIT PENETRATING LEAD WALL
LEAD LINING. SEE ARCHITECTURAL PLANS.
3"3"
3"
UNDISTURBED EARTH
1" ABOVE SIDES OF DUCT.
CROWN DUCT TO A PEAK
CAST-IN PLACE CONCRETE
ENCASEMENT.
SECURE TOP SPACER TO PREVENT
CONDUITS FROM FLOATING DURING
CONCRETE POUR.
DUCTBANKS CONDUITS. SEE DIV.
26 SECTIONS FOR SIZES AND
QUANTITIES.
EPOXY COATED #4 REBAR;
CONTINUOUS ALONG
DUCTBANK (TYP)
CONCRETE PAVERS FOR
LEVELING
PLASTIC CONDUIT
SPACERS/SUPPORTS
DETAIL NOTES:
CONCRETE COVER DIMENSIONS SHOWN ARE MINIMUM.
DUCT BANK SHALL BE A MINIMUM OF 36" BELOW GRADE.
RED PLASTIC WARNING TAPE;
12" BELOW GRADE
3"
3"
1 POWER
2 POWER SPARE
3"
3"
SHEET NO.:
SHEET CONTENTS
DO NOT SCALE DRAWINGS
ISSUED
M&H NO.:
DATE:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
© Copyright This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.
Mead & Hunt, Inc.
9600 NE Cascades Parkway, Suite 100 Portland, OR 97220 phone: 503-548-1494 meadhunt.com www.tetratech.com
711 TANK FARM ROAD, SUITE 110
SAN LUIS OBISPO, CA 93401
PHONE: (805) 542-9052 FAX: (805) 542-9254
/7 /2
:4 :4
P
M C
R e v it L o c a l\
-1
.0 -E
-C E
N T
R A
L -2 jr h .r v t
E-503
DETAILS
O R
A N
G
K in g s le y F ie ld
K la m a th
F a lls
O
R
C O
N S
T R
U C
T C
O R
R O
S
IO
N C
O N
T R
O L H
A N
G A
R
3142200-121252.01
KAS
IMR
11/09/18
JRH
11/09/18 B-3 FINAL
NO SCALE1
GROUNDING SYSTEM DETAIL (TYP)
NO SCALE3
CONDUIT THRU LEAD-LINED WALL DETAIL
NO SCALE2
ELECTRICAL DUCTBANK TYPICAL SECTION - 2 X 4
SHEET NO.:
SHEET CONTENTS
DO NOT SCALE DRAWINGS
ISSUED
M&H NO.:
DATE:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
© Copyright This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.
Mead &…