UNCLASSIFIED/FOR OFFICIAL USE ONLY

Air National Guard NDDA Construct DGS RPA IS 60330398

SECTION 12 22 00

CURTAINS AND DRAPES

08/16

PART 1 GENERAL

1.1 REFERENCES

The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.

ASTM INTERNATIONAL (ASTM)

ASTM D3691/D3691M (2009) Woven, Lace, and Knit Household Curtain and Drapery Fabrics

ASTM E84 (2014) Standard Test Method for Surface Burning Characteristics of Building Materials

CALIFORNIA DEPARTMENT OF PUBLIC HEALTH (CDPH)

CDPH SECTION 01350 (2004; Add 2004-01) Standard Practice for the Testing Of Volatile Organic Emissions from Various Sources Using Small-Scale Environmental Chambers

NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)

NFPA 76 (2016) Standard for the Fire Protection of Telecommunications Facilities

NFPA 701 (2015) Standard Methods of Fire Tests for Flame Propagation of Textiles and Films

SCIENTIFIC CERTIFICATION SYSTEMS (SCS)

SCS SCS Global Services (SCS)Indoor Advantage

UNDERWRITERS LABORATORIES (UL)

UL 2818 (2013) GREENGUARD Certification Program For Chemical Emissions For Building Materials, Finishes And Furnishings

1.2 SUBMITTALS

Government approval is required for submittals with a "G" designation;

submittals not having a "G" designation are for Contractor Quality Control approval.. When used, a designation following the "G" designation identifies the office that will review the submittal for the Government.

Submittals with an "S" are for inclusion in the Sustainability Notebook, in conformance with Section 01 33 29 SUSTAINABILITY REPORTING. Submit the following in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:

SD-02 Shop Drawings

SECTION 12 22 00 Page 1

Addendum 2

Drawings; G

SD-04 Samples

Drapery Fabric; G

Submit a range of three samples, 36 by 36 inches or larger, to match the fabric quality, weight, pattern, and color shown or specified. Once selected, label approved samples to identify locations for their use in the project. Maintain identification and approval markings until final acceptance of the work.

Finished Drapery

Provide one full size sample installation including hardware.

Install the finished drapery on a track at the location indicated.

SD-06 Test Reports

Flame Resistance

SD-07 Certificates

Indoor Air Quality

SD-08 Manufacturer's Instructions

Drapery Hardware

Special Fabrication

Before fabrication, submit the manufacturer's printed instructions for fabrics requiring special fabrication methods.

SD-10 Operation and Maintenance Data

Drapery System, Data Package 1; G

SD-11 Closeout Submittals

Indoor Air Quality for Fabrics; S

1.3 CERTIFICATIONS

1.3.1 Indoor Air Quality Certifications

1.3.1.1 Fabrics and Wallcoverings

Provide products certified to meet indoor air quality requirements by UL 2818 (Greenguard) Gold, SCS Global Services Indoor Advantage Gold or provide validation by other third-party program that products meet the requirements of this paragraph. Provide current product certification documentation from certification body. Fabrics and wallcoverings must meet emissions requirements of CDPH SECTION 01350 (limit requirements for either office or classroom spaces regardless of space type).

SECTION 12 22 00 Page 2

Amendment 2

1.4 Drawings

Submit drawings indicating the following:

Windows and other locations requiring drapery extent of drapery, to ceiling or to specific height above windows; location of each different drapery fabric when more than one type, pattern or color is to be provided; width of window and width of drapery extension if bay window.

1.5 SYSTEM REQUIREMENTS

Submit data for completed drapery system in accordance with Section 01 78 23 OPERATION AND MAINTENANCE DATA. Include laundering and dry cleaning instructions for fabrics requiring special care. Furnish separate instruction sheet for each material (one for fiberglass, one for Verel). For fabrics which are not permanently or inherently flame resistant, furnish instruction to include frequency and process required for retreating the fabric to renew the effectiveness of the flame resistant treatment. Head each sheet with name and number of room or rooms in which each material is hung. In lieu of instruction sheets, provide instructions on small, permanent labels (either iron-on type or sewn-on) affixed to back of the heading of each panel.

1.6 DELIVERY, STORAGE, AND HANDLING

Deliver draperies and hardware to the site in sealed containers clearly labeled with manufacturer's name and contents. Store in a safe, dry, clean, and well ventilated area. Do not open containers until needed for installation, unless verification inspection is required.

PART 2 PRODUCTS

2.1 PRODUCT SUSTAINABILITY CRITERIA

For products in this section, where applicable and to extent allowed by performance criteria, provide and document the following:

2.1.1 Reduce Volatile Organic Compounds (VOC) (LOW-EMITTING MATERIALS) for Products

Reduced VOC content is identified for some products in this section;

provide documentation in accordance with Section 01 33 29 SUSTAINABILITY REPORTING paragraph REDUCE VOLATILE ORGANIC COMPOUNDS (VOC) (LOW-EMITTING MATERIALS). Other products listed in this section may be available with reduced VOC content; identify those products that meet project requirements for reduced VOC content, and provide documentation in accordance with Section 01 33 29 SUSTAINABILITY REPORTING paragraph REDUCE

VOLATILE ORGANIC COMPOUNDS (VOC) (LOW-EMITTING MATERIALS).

2.2 MATERIALS

2.2.1 Fabrics

Provide certification of indoor air quality for fabrics.

2.2.1.1 Drapery Fabric

ASTM D3691/D3691M . Provide privacy curtain fabric manufactured from man-made fibers. Fabric physical characteristics must be as follows:

SECTION 12 22 00 Page 3

a. Finished fabric weight: Minimum 8 ounces per linear yard

b. Pattern: As selected by Project Engineer from manufacturer's full available range of opaque fabrics

c. Weave: Closed (0 to 7 percent)

d. Texture: As selected by Project Engineer

e. Color: As selected by Project Engineer

Provide thermal curtains at server rooms to separate hot and cold aisles at locations shown and as follows:

Fabric: Clear polyurethane plastic sheet, PVC-free, complying with NFPA 76 data center standard, including static-dissipation requirements, and ASTM E84 for Class 1 fire resistance and smoke developed requirements.

2.2.1.2 Drapery Lining

None; At privacy curtains, mount two drapes back-to-back for finished appearance on both sides at each location to receive privacy drapes.

2.2.1.3 Flame Resistance

NFPA 701 . Drapery fabric and lining must pass the small and large scale test. Treatment to enhance flame resistance must be permanent type. If treated, fabric must pass the small and large scale test after being subjected to the accelerated dry cleaning or laundering cycles specified in NFPA 701 .

2.2.2 Sewing Thread

Pre-shrunk mercerized cotton (50/3) or monofilament in equivalent size, except do not use monofilament in the heading.

2.2.3 Heading

2.2.3.1 Heading Hooks

Slip-in-type, nickel-plated steel, and of a size adequate to hold the heading upright. Provide one hook for each pleat. Provide 10 percent surplus hooks for possible lost or damaged hooks.

2.2.3.2 Snap-Tape System (Ripplefold)

Heavy vinyl or nylon tape with locking fasteners attached to tape to form desired pleat spaces and fullness. Cut tapes to size and sew to drapery fabric to form the heading.

2.2.4 Drapery Hardware

At Privacy Curtains provide ceiling mounted tracks of heavy-duty type.

Traverse rods or tracks must be manually operated, one-way draw . Rods and tracks must be cold-rolled, commercial quality steel minimum 0.030 inch thick or extruded aluminum minimum 0.050 inch thick. Rod and track cross section width and depth must be sufficient to carry the drapery without

SECTION 12 22 00 Page 4 sagging. Track configuration (number of channels) must be such so as to permit drapery operation as specified or indicated. Finish steel components with a white baked enamel, vinyl, or epoxy coating as standard with the manufacturer. Finish aluminum components with an anodic clear (natural) coating as standard with the manufacturer. Provide smooth and non-sticking sliding surfaces. Provide one-piece rod and track up to 16 feet long. Provide steel brackets and intermediate supports. Provide one manufacturer's design throughout.

At Thermal Curtains in Datacenter/Server Rooms provide aluminum tracks designed to receive clear urethane curtains, attached to acoustical ceiling grid, including pre-fabricated corners and shapes required for continuously sealed installation.

2.2.4.1 Hand Traverse Cordless Track System

At Privacy Curtains provide extra heavy duty track assembly with baton on both sides of draperies where it is readily visible and easily used.

Ceiling mounted in extruded aluminum track anodized in clear (natural) finish.

2.2.5 Fasteners

Provide zinc plated.

2.3 FABRICATION

Prior to cutting and fabrication, field measure each drapery location paying particular attention to field conditions affecting the work.

2.3.1 Drapery Fabrication

2.3.1.1 Panels

Privacy Curtains: Make from full or half widths of fabric to give a minimum of 120 percent fullness. 120 percent fullness is defined as 1.2 times the rod width plus overlaps and returns. Provide ripplefold.

Draperies must be floor length. Floor length draperies must hang 1 inch above finish floors. Provide table-sized drapery panels with a plus or minus tolerance of 1/4 inch accurately laid-out before cutting. Cut fabric to allow for pleats and for outside ends to return to the walls.

For traverse draperies, allow for a minimum overlap of 3 inches at the center. Accurately match patterned fabrics to provide identical designs horizontally and vertically on each window within each room. Where variations in length or placement of windows occur in a room, match patterns horizontally. When fabricating panels from fabrics which require special methods or instructions, conform to the workroom instructions provided by the fabric manufacturer. Sew seams and hems using a firm interlocking stitch at a stitch rate per inch appropriate to fabric being sewn. Sew with enough slack present so that thread shrinkage due to laundering and dry cleaning will not pucker seams and hems. Do not expose seam and hem raw edges.

2.3.1.2 Headings

Pleat evenly to required widths. Make headings 4 inches high with triple french pleats, and double fold. Include permanent finish stiffener of buckram, crinoline, or pellon across entire heading. Paper stiffening is not acceptable. Machine stitch pleats for a depth of at least 3-3/4 inches.

Do not use horizontal stitching across the width of the heading.

SECTION 12 22 00 Page 5

2.3.1.3 Seams

Join widths by serging, overlock, and safety stitch. Retain selvage when practical.

2.3.1.4 Hems

Double fold hems (top and bottom) and blind stitch so as not to show on the panel face. Make side seams 1-1/2 inches wide and bottom seams 4 inches deep with weights sewn 1/2 inch above hem bottom. Provide weights at corners and each vertical seam. When lining is attached to the drapery fabric, single fold heading is acceptable, however, double fold the bottom hem.

2.3.2 Thermal Curtains

Fabric to ensure continuous seal at top and bottom of curtains. Ensure that curtains are of sufficient length to achieve seal at raised access floor surfaces.

PART 3 EXECUTION

3.1 EXAMINATION

Ensure that work of other trades and cleaning operations are completed.

Test completed installation to ensure smooth and continuous operation of all draperies, hardware and accessories.

3.2 INSTALLATION

Install draperies in rooms and areas indicated . Include all material indicated, specified, or necessary for a complete finished drapery installation. Contractor is responsible for the required quantities of draperies and hardware.

Do not install building construction materials that show visual evidence of biological growth.

3.2.1 Hardware

Install in accordance with the manufacturer's printed instructions and as specified herein. Install ceiling tracks parallel to walls and windows, fasten at each end, at 16 inches from each end and with additional intermediate fasteners spaced not more than 48 inches apart. Install wall rods with end brackets and provide intermediate support brackets 24 inches from each end with additional intermediate support brackets spaced not more than 48 inches apart. Provide fasteners for installation as follows:

Fastener Structural Material

Wood or sheet metal screw Wood

Self tapping screw Metal

Case hardened, self-tapping sheet metal screw Sheet metal

SECTION 12 22 00 Page 6

Fastener Structural Material

Screw or bolt in expansion shield Solid masonry

Toggle or molly bolt Hollow masonry, wallboard, plaster

3.2.2 Draperies

Install with a minimum clearance of 1/4 inch between the ceiling and top of drapery heading. Floor length draperies must hang 1 inch above finished floors; sill length, 1/2 inch above window sills and heating-air conditioning units; and apron length, 1 inch below bottom of window aprons. Insert heading hooks at rear of each pleat, placed to obtain the clearance specified. Press well before hanging, except fiberglass.

Dress-down and adjust hung draperies to provide best form and appearance.

Traverse draperies must operate smoothly and easily over the full range of travel. Remove incorrectly sized drapery and remake to correct size.

Remove damaged, spotted, or otherwise defective fabric and repair to original state or replace with new material.

-- End of Section --