07 60 00
View the file
Other files
| File | Type | Posted |
|---|---|---|
| W912JF-17-R-0002-0003_Solicitation_Amendment_Conforming_Copy.pdf | ||
| W912JF-17-R-0002-0003_Solicitation_Amendment.pdf | ||
| Addendum_2_-_08_41_13.pdf | ||
| Addendum_2_MILCON_SCIF.docx | DOCX document | |
| Addendum_2_-_12_22_00.pdf | ||
| Addendum_2_-_10_22_19.pdf | ||
| Questions_and_Answers_May_4_2017.xlsx | XLSX spreadsheet | |
| Addendum_2_-_08_33_23.pdf | ||
| Addendum_2_-_14_24_00.pdf | ||
| Addendum__MILCON_SCIF.docx | DOCX document | |
| Amendment_2_-_May_4_2017.pdf | ||
| Addendum_2_-_32_31_13.pdf | ||
| Addendum_2_-_10_51_55.pdf | ||
| Addendum_2_Electrical_Lighting_Plan_EL101.pdf | ||
| Addendum_2_Structural_Sheet_S102.pdf | ||
| W912JF-17-R-0002-0001_Solicitation_Amendment.pdf | ||
| Addendum_1_MILCON_SCIF.docx | DOCX document | |
| SCIF_Site_visit_sign_in_sheet.pdf | ||
| EXHIBIT_A_-_Past_Performance_Relevancy_Questionnaire.doc | DOC document | |
| EXHIBIT_C_Past_Performance.doc | DOC document | |
| W912JF-17-R-0002_Solicitation.pdf | ||
| EXHIBIT_B_Subcontractor_Consent_Form.doc | DOC document |
Show all 22
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
UNCLASSIFIED/FOR OFFICIAL USE ONLY
Air National Guard NDDA Construct DGS RPA IS 60330398
SECTION 07 60 00
FLASHING AND SHEET METAL
08/08
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
AMERICAN ARCHITECTURAL MANUFACTURERS ASSOCIATION (AAMA)
AAMA 2605 (2011) Voluntary Specification, Performance Requirements and Test Procedures for Superior Performing Organic Coatings on Aluminum Extrusions and Panels
ASTM INTERNATIONAL (ASTM)
ASTM A480/A480M (2014b) Standard Specification for General Requirements for Flat-Rolled Stainless and Heat-Resisting Steel Plate, Sheet, and Strip
ASTM A653/A653M (2015) Standard Specification for Steel Sheet, Zinc-Coated (Galvanized) or Zinc-Iron Alloy-Coated (Galvannealed) by the Hot-Dip Process
ASTM A755/A755M (2011) Standard Specification for Steel Sheet, Metallic Coated by the Hot-Dip Process and Prepainted by the Coil-Coating Process for Exterior Exposed Building Products
ASTM B209 (2014) Standard Specification for Aluminum and Aluminum-Alloy Sheet and Plate (2010) Standard Specification for Aluminum and Aluminum-Alloy Sheet and Plate
ASTM B221 (2014) Standard Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Profiles, and Tubes
ASTM B69 (2013) Standard Specification for Rolled Zinc
ASTM D4586/D4586M (2007; E 2012; R 2012) Asphalt Roof Cement, Asbestos-Free
SHEET METAL AND AIR CONDITIONING CONTRACTORS' NATIONAL ASSOCIATION
(SMACNA)
SMACNA 1793 (2012) Architectural Sheet Metal Manual, 7th Edition
SECTION 07 60 00 Page 1
Addendum 2
SINGLE PLY ROOFING INDUSTRY (SPRI)
ANSI/SPRI RD-1 (2009) Performance Standard for Retrofit Drains
1.2 GENERAL REQUIREMENTS
Finished sheet metalwork will form a weathertight construction without waves, warps, buckles, fastening stresses or distortion, which allows for expansion and contraction. Sheet metal mechanic is responsible for cutting, fitting, drilling, and other operations in connection with sheet metal required to accommodate the work of other trades. Coordinate installation of sheet metal items used in conjunction with roofing with roofing work to permit continuous roofing operations.
1.3 SUBMITTALS
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are for Contractor Quality Control approval. Submittals with an "S" are for inclusion in the Sustainability Notebook, in conformance to Section 01 33 29 SUSTAINABILITY REPORTING.
Submit the following in accordance with Section 01 33 00 SUBMITTAL
PROCEDURES:
SD-02 Shop Drawings
Covering on flat, sloped, or curved surfaces; G
Gutters; G
Downspouts; G
Metal Plate Panels; G
Metal Fascia Panels ; G
Metal Soffit Panels ; G
Flashing for roof drains; G
Base flashing; G
Counterflashing; G
Flashing at roof penetrations; G
Reglets; G
Copings; G
Drip edge; G
Open valley flashing; G
Eave flashing; G
SECTION 07 60 00 Page 2
Amendment 2
Indicate thicknesses, dimensions, fastenings and anchoring methods, expansion joints, and other provisions necessary for thermal expansion and contraction. Scaled manufacturer's catalog data may be submitted for factory fabricated items.
SD-11 Closeout Submittals
Quality Control Plan
Submit for sheet metal work in accordance with paragraph entitled "Field Quality Control."
1.4 DELIVERY, HANDLING, AND STORAGE
Package and protect materials during shipment. Uncrate and inspect materials for damage, dampness, and wet-storage stains upon delivery to the job site. Remove from the site and replace damaged materials that cannot be restored to like-new condition. Handle sheet metal items to avoid damage to surfaces, edges, and ends. Store materials in dry, weather-tight, ventilated areas until immediately before installation.
PART 2 PRODUCTS
2.1 MATERIALS
Do not use lead, lead-coated metal, or galvanized steel. Use any stainless steel products unless other products listed by SMACNA Arch.
Manual are indicated for a particular item. Conform to the requirements specified and to the thicknesses and configurations established in SMACNA Arch. Manual for the materials. Different items need not be of the same metal, except that if copper is selected for any exposed item, all exposed items must be copper.
Furnish sheet metal items in 8 to 10 foot lengths. Single pieces less than 8 feet long may be used to connect to factory-fabricated inside and outside corners, and at ends of runs. Factory fabricate corner pieces with minimum 12 inch legs. Provide accessories and other items essential to complete the sheet metal installation. Provide accessories made of the same or compatible materials as the items to which they are applied.
Fabricate sheet metal items of the materials specified below and to the gage, thickness, or weight shown in Table I at the end of this section.
Provide sheet metal items with mill finish unless specified otherwise.
Where more than one material is listed for a particular item in Table I, each is acceptable and may be used except as follows:
2.1.1 Exposed Sheet Metal Items
Must be of the same material. Consider the following as exposed sheet metal: gutters, including hangers; downspouts; gravel stops Metal Soffit Panels and Metal Fascia Panels fascias ; cap, valley, steeped, base, and eave flashings and related accessories.
2.1.2 Drainage
Do not use copper for an exposed item if drainage from that item will pass over exposed masonry, stonework or other metal surfaces. In addition to the metals listed in Table I, lead-coated copper may be used for such items.
SECTION 07 60 00 Page 3
2.1.3 Steel Sheet, Zinc-Coated (Galvanized)
ASTM A653/A653M with G90 coating, prepainted by coil-coating process .
2.1.3.1 Finish
Exposed exterior items of zinc-coated steel sheet must have a baked-on, factory-applied 2-coat color coating of polyvinylidene fluoride or other equivalent fluorocarbon coating complying with ASTM A755/A755M applied after metal substrates have been cleaned and pretreated. Provide finish coating dry-film thickness of 0.8 to 1.3 mils and color as selected by Contracting Officer.
2.1.4 Zinc Sheet and Strip
ASTM B69, Type I, a minimum of 0.024 inch thick.
2.1.5 Stainless Steel
ASTM A480/A480M , Type 302 or 304, 2D Finish, fully annealed, dead-soft temper.
2.1.6 Aluminum Alloy Sheet and Plate
ASTM B209 0.125 inch thick; AAMA 2605 PVDF finish or equivalent to match storefront. Use to wrap corners adjacent to storefront, as infill at storefront glazing pockets, and where otherwise shown, of anodized clear form alloy , and temper appropriate for use.
2.1.6.1 Finish
Exposed exterior sheet metal items of aluminum must have a baked-on, factory-applied color coating of polyvinylidene fluoride (PVF2) or other equivalent fluorocarbon coating applied after metal substrates have been cleaned and pretreated. Provide finish coating dry-film thickness of 0.8 to 1.3 mils and color as selected by Contracting Officer.
2.1.7 Aluminum Alloy, Extruded Bars, Rods, Shapes, and Tubes
ASTM B221.
2.1.8 Fasteners
Use the same metal or a metal compatible with the item fastened. Use stainless steel fasteners to fasten dissimilar materials.
PART 3 EXECUTION
3.1 INSTALLATION
3.1.1 Workmanship
Make lines and angles sharp and true. Free exposed surfaces from visible wave, warp, buckle, and tool marks. Fold back exposed edges neatly to form a 1/2 inch hem on the concealed side. Make sheet metal exposed to the weather watertight with provisions for expansion and contraction.
Make surfaces to receive sheet metal plumb and true, clean, even, smooth, SECTION 07 60 00 Page 4 dry, and free of defects and projections. For installation of items not shown in detail or not covered by specifications conform to the applicable requirements of SMACNA 1793, Architectural Sheet Metal Manual. Provide sheet metal flashing in the angles formed where roof decks abut walls, curbs, ventilators, pipes, or other vertical surfaces and wherever indicated and necessary to make the work watertight. Join sheet metal items together as shown in Table II.
3.1.2 Mechanical Fastening
3.1.2.1 Mechanical Fastening of Aluminum
Use No. 12, aluminum alloy, sheet metal screws or other suitable aluminum alloy or stainless steel fasteners. Drive fasteners in holes made with a No. 26 drill in securing side laps, end laps, and flashings. Space fasteners 12 inch maximum on center. Where end lap fasteners are required to improve closure, locate the end lap fasteners not more than 2 inch from the end of the overlapping sheet.
3.1.3 Protection from Contact with Dissimilar Materials
3.1.3.1 Aluminum
Do not allow aluminum surfaces in direct contact with other metals except stainless steel, zinc, or zinc coating. Where aluminum contacts another metal, paint the dissimilar metal with a primer followed by two coats of aluminum paint. Where drainage from a dissimilar metal passes over aluminum, paint the dissimilar metal with a non-lead pigmented paint.
3.1.3.2 Metal Surfaces
Paint surfaces in contact with mortar, concrete, or other masonry materials with alkali-resistant coatings such as heavy-bodied bituminous paint.
3.1.3.3 Wood or Other Absorptive Materials
Paint surfaces that may become repeatedly wet and in contact with metal with two coats of aluminum paint or a coat of heavy-bodied bituminous paint.
3.1.4 Expansion and Contraction
Provide expansion and contraction joints at not more than 32 foot intervals for aluminum and at not more than 40 foot intervals for other metals. Provide an additional joint where the distance between the last expansion joint and the end of the continuous run is more than half the required interval. Space joints evenly. Join extruded aluminum gravel stops and fascias by expansion and contraction joints spaced not more than 12 feet apart.
3.1.5 Base Flashing
Extend up vertical surfaces of the flashing not less than 8 inch and not less than 4 inch under the roof covering. Where finish wall coverings form a counterflashing, extend the vertical leg of the flashing up behind the applied wall covering not less than 6 inch. Overlap the flashing strips with the previously laid flashing not less than 3 inch. Fasten the strips at their upper edge to the deck. Horizontal flashing at vertical surfaces must extend vertically above the roof surface and fastened at
SECTION 07 60 00 Page 5 their upper edge to the deck a minimum of 6 inch on center with hex headed, galvanized shielded screws a minimum of 2-inch lap of any surface. Solder end laps and provide for expansion and contraction.
Extend the metal flashing over crickets at the up-slope side of curbs, and similar vertical surfaces extending through sloping roofs, the metal flashings. Extend the metal flashings onto the roof covering not less than
4.5 inch at the lower side of vertical surfaces extending through the roof decks. Install and fit the flashings so as to be completely weathertight. Provide factory-fabricated base flashing for interior and exterior corners. Do not use metal base flashing on built-up roofing.
3.1.6 Counterflashing
Except where indicated or specified otherwise, insert counterflashing in reglets located from 9 to 10 inch above roof decks, extend down vertical surfaces over upturned vertical leg of base flashings not less than 3 inch.
Fold the exposed edges of counterflashings 1/2 inch. Provide end laps in counterflashings not less than 3 inch and make it weathertight with plastic cement. Do not make lengths of metal counterflashings exceed 10 feet. Form the flashings to the required shapes before installation.
Factory-form the corners not less than 12 inch from the angle. Secure the flashings in the reglets with lead wedges and space not more than 18 inch apart; on stair/elevator towers short runs, place wedges closer together.
Fill caulked-type reglets or raked joints which receive counterflashing with caulking compound. Turn up the concealed edge of counterflashings built into masonry or concrete walls not less than 1/4 inch and extend not less than 2 inch into the walls. Install counterflashing to provide a spring action against base flashing.
3.1.7 Metal Reglets
Provide factory fabricated caulked type or friction type reglets with a minimum opening of 1/4 inch and a depth of 1 1/4 inch, as approved.
3.1.7.1 Caulked Reglets
Provide with rounded edges and metal strap brackets or other anchors for securing to the concrete forms. Provide reglets with a core to protect them from injury during the installation. Provide built-up mitered corner pieces for internal and external angles. Wedge the flashing in the reglets with lead wedges every 18 inch, caulked full and solid with an approved compound.
3.1.7.2 Friction Reglets
Provide with flashing receiving slots not less than 5/8 inch deep, one inch jointing tongues, and upper and lower anchoring flanges installed at 24 inch maximum snaplock receiver. Insert the flashing the full depth of the slot and lock by indentations made with a dull-pointed tool, wedges, and filled with a sealant. For friction reglets, install flashing snaplock receivers at 24 inch on center maximum. When the flashing has been inserted the full depth, caulk the slot and lock with wedges and fill with sealant.
3.1.8 Gravel Stops Metal Soffit Panels and Metal Fascia Panel s
Prefabricate in the shapes and sizes indicated and in lengths not less that 8 feet. Extend flange at least 4 inch onto roofing. Provide prefabricated, mitered corners internal and external corners. Ensure that
SECTION 07 60 00 Page 6 vertical wall air barrier and roof air or vapor barrier form continuous envelope prior to attaching metal fascia and soffit panels. Install gravel stops and fascias after all plies of the roofing membrane have been applied, but before the flood coat of bitumen is applied. Prime roof flange of gravel stops and fascias on both sides with an asphalt primer.
After primer has dried, set flange on roofing membrane and strip-in.Nail flange securely to wood nailer with large-head, barbed-shank roofing nails
1.5 inch long spaced not more than 3 inch on center, in two staggered rows.
3.1.8.1 Edge Strip
Hook the lower edge of fascias at least 3/4 inch over a continuous strip of the same material bent outward at an angle not more than 45 degrees to form a drip. Nail hook strip to a wood nailer at 6 inchmaximum on center. Where fastening is made to concrete or masonry, use screws spaced 12 inch on center driven in expansion shields set in the concrete or masonry. Where horizontal wood nailers are slotted to provide for insulation venting, install strips to prevent obstruction of vent slots.
Where necessary, install strips over 1/16 inch thick compatible spacer or washers.
3.1.8.2 Joints
Leave open the section ends of gravel stops and fascias 1/4 inch and backed with a formed flashing plate, mechanically fastened in place and lapping each section end a minimum of 4 inch set laps in plastic cement.
Face nailing will not be permitted. Install prefabricated aluminum gravel stops and fascias in accordance with the manufacturer's printed instructions and details.
3.1.9 Metal Drip Edge
Provide a metal drip edge, designed to allow water run-off to drip free of underlying construction, at eaves and rakes prior to the application of roofing shingles. Apply directly on the wood deck at the eaves and over the underlay along the rakes. Extend back from the edge of the deck not more than 3 inch and secure with compatible nails spaced not more than 10 inch on center along upper edge.
3.1.10 Gutters
The hung type of shape indicated and supported on underside by brackets that permit free thermal movement of the gutter. Provide gutters in sizes indicated complete with mitered corners, end caps, outlets, brackets, and other accessories necessary for installation. Bead with hemmed edge or reinforce the outer edge of gutter with a stiffening bar not less than 3/4 by 3/16 inch of material compatible with gutter. Fabricate gutters in sections not less than 8 feet. Lap the sections a minimum of one inch in the direction of flow or provide with concealed splice plate 6 inch minimum. Join the gutters, other than aluminum, by riveted and soldered joints. Join aluminum gutters with riveted sealed joints. Provide expansion-type slip joints midway between outlets. Install gutters below slope line of the roof so that snow and ice can slide clear. Support gutters on as indicated . Adjust gutters to slope uniformly to outlets, with high points occurring midway between outlets. Fabricate hangers and fastenings from metals.
SECTION 07 60 00 Page 7
3.1.11 Downspouts
Space supports for downspouts according to the manufacturer's recommendation for the substrate. Types, shapes and sizes are indicated.
Provide complete including elbows and offsets. Provide downspouts in approximately 10 foot lengths. Provide end joints to telescope not less than 1/2 inch and lock longitudinal joints. Provide gutter outlets with wire ball strainers for each outlet. Provide strainers to fit tightly into outlets and be of the same material used for gutters. Keep downspouts not less than one inch away from walls. Fasten to the walls at top, bottom, and at an intermediate point not to exceed 5 feet on center with leader straps or concealed rack-and-pin type fasteners. Form straps and fasteners of metal compatible with the downspouts.
3.1.11.1 Terminations
Neatly fit into the drainage connection the downspouts terminating in drainage lines and fill the joints with a portland cement mortar cap sloped away from the downspout. Provide downspouts terminating in splash blocks with elbow-type fittings. Provide splash pans as specified.
3.1.12 Flashing for Roof Drains
Provide a 30 inch square sheet indicated. Taper insulation to drain from 24 inch out. Set flashing on finished felts in a full bed of asphalt roof cement, ASTM D4586/D4586M . Heavily coat the drain flashing ring with asphalt roof cement. Clamp the roof membrane, flashing sheet, and stripping felt in the drain clamping ring. Secure clamps so that felts and drain flashing are free of wrinkles and folds. Retrofit roof drains must conform to ANSI/SPRI RD-1 .
3.1.13 Open Valley Flashing
Provide valley flashing free of longitudinal seams, of width sufficient to extend not less than 6 inch under the roof covering on each side. Provide a 1/2 inch fold on each side of the valley flashing. Lap the sheets not less than 6 inch in the direction of flow and secure to roofing construction with cleats attached to the fold on each side. Nail the tops of sheets to roof sheathing. Space the cleats not more than 12 inch on center. Provide exposed flashing not less than 4 inch in width at the top and increase one inch in width for each additional 8 feet in length.
Where the slope of the valley is 4.5 inch or less per foot, or the intersecting roofs are on different slopes, provide an inverted V-joint, one inch high, along the centerline of the valley; and extend the edge of the valley sheets 8 inch under the roof covering on each side.
3.1.14 Eave Flashing
One piece in width, applied in 8 to 10 foot lengths with expansion joints spaced as specified in paragraph entitled "Expansion and Contraction."
Provide a 3/4 inch continuous fold in the upper edge of the sheet to engage cleats spaced not more than 10 inch on center. Locate the upper edge of flashing not less than 18 inch from the outside face of the building, measured along the roof slope. Fold lower edge of the flashing over and loose-lock into a continuous edge strip on the fascia. Where eave flashing intersects metal valley flashing, secure with one inch flat locked joints with cleats that are 10 inch on center.
SECTION 07 60 00 Page 8
3.1.15 Sheet Metal Covering on Flat, Sloped, or Curved Surfaces
Except as specified or indicated otherwise, cover and flash all minor flat, sloped, or curved surfaces such as crickets, bulkheads, dormers and small decks with metal sheets of the material used for flashing; maximum size of sheets, 16 by 18 inch. Fasten sheets to sheathing with metal cleats. Lock seams and solder. Lock aluminum seams as recommended by aluminum manufacturer. Provide an underlayment of roofing felt for all sheet metal covering.
3.1.16 Flashing at Roof Penetrations and Equipment Supports
Provide preformed EPDM flashing for all pipes, ducts, and conduits projecting through the roof surface and for equipment supports, guy wire anchors, and similar items supported by or attached to the roof deck.
3.1.17 Copings
Provide coping using prefinished aluminum sheets 8 or 10 feet long joined by a 3/4 inch locked and soldered or sealed seams. Terminate outer edges in edge strips. Install with sealed cover plate joints as indicated.
3.2 PAINTING
Field-paint sheet metal for separation of dissimilar materials.
3.3 CLEANING
Clean exposed sheet metal work at completion of installation. Remove grease and oil films, handling marks, contamination from steel wool, fittings and drilling debris, and scrub-clean. Free the exposed metal surfaces of dents, creases, waves, scratch marks, and solder or weld marks.
3.4 REPAIRS TO FINISH
Scratches, abrasions, and minor surface defects of finish may be repaired in accordance with the manufacturer's printed instructions and as approved. Repair damaged surfaces caused by scratches, blemishes, and variations of color and surface texture. Replace items which cannot be repaired.
3.5 FIELD QUALITY CONTROL
Establish and maintain a Quality Control Plan for sheet metal used in conjunction with roofing to assure compliance of the installed sheet metalwork with the contract requirements. Remove work that is not in compliance with the contract and replace or correct. Include quality control, but not be limited to, the following:
a. Observation of environmental conditions; number and skill level of sheet metal workers; condition of substrate.
b. Verification that specified material is provided and installed.
c. Inspection of sheet metalwork, for proper size(s) and thickness(es), fastening and joining, and proper installation.
SECTION 07 60 00 Page 9
3.5.1 Procedure
Submit for approval prior to start of roofing work. Include a checklist of points to be observed. Document the actual quality control observations and inspections. Furnish a copy of the documentation to the Contracting Officer at the end of each day.
TABLE I. SHEET METAL WEIGHTS, THICKNESSES, AND GAGES
Sheet Metal Items Aluminum, inch
Plate .125
Downspouts and leaders
.032
Downspout clips and anchors
.040 clip
.125 anchor
Downspout straps, 2-inch
.060
Strainers, wire diameter or gage
.144 diameter
Flashings:
Base .040
Cap (Counter-flashing)
.032
SECTION 07 60 00 Page 10
TABLE I. SHEET METAL WEIGHTS, THICKNESSES, AND GAGES
Sheet Metal Items Aluminum, inch
Eave -
Bond barrier -
Stepped .032
Valley .0
Pipe vent sleave (d)
Gravel stops Soffit and fascias:
Extrusions .075
Sheets, corrugated .032
Sheets, smooth .050
Edge strip .050
Gutters:
Gutter section .032
Continuous cleat .032
Hangers, dimensions 1 inch by .080 inch (c)
Joint Cover plates (See Table II)
.032
Reglets (c) -
SECTION 07 60 00 Page 11
TABLE I. SHEET METAL WEIGHTS, THICKNESSES, AND GAGES
Sheet Metal Items Aluminum, inch
(b) May be lead weighing 4 pounds per square foot.
(c) May be polyvinyl chloride.
(d) 2.5 pound minimum lead sleeve with 4 inch flange. Where lead sleeve is impractical, refer to paragraph entitled "Single Pipe Vents" for optional material.
TABLE II. SHEET METAL JOINTS
TYPE OF JOINT
Item Designation Copper, Terne-Coated Stainless Steel, Zinc-Coated Steel and Stainless Steel
Aluminum Remarks
Joint cap for building expansion seam, cleated joint at roof
1.25 inch single lock, standing seam, cleated
1.25 inch single lock, standing
Flashings
Base One inch 3 inch lap for expansion joint
One inch flat locked, soldered;
sealed; 3 inch lap for expansion joint
Aluminum producer's recommended hard setting sealant for locked aluminum joints. Fill each metal expansion joint with a joint sealing compound compound.
SECTION 07 60 00 Page 12
TABLE II. SHEET METAL JOINTS
TYPE OF JOINT
Item Designation Copper, Terne-Coated Stainless Steel, Zinc-Coated Steel and Stainless Steel
Aluminum Remarks
Cap-in reglet 3 inch lap 3 inch lap Seal groove with joint sealing compound.
Reglets Butt joint -- Seal reglet groove with joint sealing compound.
Eave One inch flat locked, cleated. One inch loose locked, sealed expansion joint, cleated.
One inch flat locked, locked, cleated one inch loose locked, sealed expansion joints, cleated
Same as base flashing.
Stepped 3 inch lap 3 inch lap --
Valley 6 inch lap cleated 6 inch lap cleated --
Edge strip Butt Butt --
Gravel stops: Soffit and Fascia:
Extrusions -- Butt with 1/2 inch space
Use sheet flashing beneath and a cover plate
Sheet, smooth Butt with 1/4 inch space
Butt with 1/4 inch space
Use sheet flashing backup plate.
Sheet, corrugated Butt with 1/4 inch space
Butt with 1/4 inch space
Use sheet flashing beneath and a cover plate or a combination unit
Gutters 1.5 inch lap, riveted and soldered
One inch flat locked riveted and sealed
Aluminum producers recommended hard setting sealant for locked aluminum joints.
(a) Provide a 3 inch lap elastomeric flashing with manufacturer's recommended sealant.
SECTION 07 60 00 Page 13
TABLE II. SHEET METAL JOINTS
TYPE OF JOINT
Item Designation Copper, Terne-Coated Stainless Steel, Zinc-Coated Steel and Stainless Steel
Aluminum Remarks
-- End of Section --