SANG_Bldg_1414-Upgrade_HVAC_&_Fire_Alarm_-_Drawings_Pt2.pdf

PDF 1 MB Posted

Attached to
Bldg 1414 HVAC and Fire Alarm Repair
Solicitation number
W912JB-19-B-5006
Issued by

About this file

Drawings - Pt.2

View the file

Other files

File Type Posted
Bid_Opening_Abstract_1414.pdf PDF
Bid_Opening_Sign_In_Sheet.pdf PDF
RFI_DOCUMENT_8-20-19.pdf PDF
W912JB-19-B-5006_Solicitation_Amendment_0004.pdf PDF
W912JB-19-B-5006_Solicitation_Amendment_0003.pdf PDF
RFI's_From_15_August_Site_Visit.pdf PDF
Site_Visit_Minutes_1414_2nd.pdf PDF
Sign_In_Sheet_2nd.pdf PDF
Superintendent_RFI.pdf PDF
RFI_Clarification_on_ACM_and_Lead_Paint.pdf PDF
1414_TEOC_Sept_2012.pdf PDF
Appendix_D._SANG_Bldg_1414_ACM_Survey.pdf PDF
RFI_Clarification_on_4_subjects.pdf PDF
W912JB-19-B-5006_Solicitation_Amendment_0002.pdf PDF
Site_Visit_Minutes_1414.pdf PDF
Sign_In_Sheet.pdf PDF
W912JB-19-B-5006_Solicitation_Amendment_0001.pdf PDF
SANG_Bldg_1414-Upgrade_HVAC_&_Fire_Alarm_-_Drawings_Pt1.pdf PDF
Bldg_1414_HVAC_DDC_-_Brand_Name_Justification.pdf PDF
W912JB19B5006.pdf PDF
Building_1414_SIMPLEX_-_Brand_Name_Justification.pdf PDF
SANGB_Vetting_Access_Request.pdf PDF
Building_1414_-_AF_Form_66_Rev_00.xls XLS spreadsheet
SANG_Bldg_1414-Upgrade_HVAC_&_Fire_Alarm_-_Drawings_Pt4.pdf PDF
SANG_Bldg_1414-Upgrade_HVAC_&_Fire_Alarm_-_Drawings_Pt3.pdf PDF
SANG_Bldg_1414-Upgrade_HVAC_&_Fire_Alarm_-_Specifications_-_Rev_01.pdf PDF
UPDATED___Presolicitation_Notice_1414_HVAC.PDF PDF
UPDATED___Presolicitation_Notice_1414_HVAC.PDF PDF
Presolicitation_Notice_1414_HVAC.pdf PDF
Show all 29

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

B1

B

A1

A

Aa

Ab

Ac

Ad

B2

2a33a44a55a66a7 3a1

11a2

MATCHLINE - SEE SHEET M101

EX.SA DUCT

EX.32x20EX.36x20

EX.SUPPLY DUCT

TO REMAIN

EX.28x20

EX. RELIEF AIR DUCT

EX. RELIEF AIR DUCT

EX. RELIEF AIR DUCT

EX. RELIEF AIR DUCT

EX.36x20

EX.RTU-2

(ON ROOF)

EX.WALL

LOUVER

EX.18"Ø

EX.12"Ø

EX

.12

"Ø

EX

.10 "Ø

EX

.18

"Ø

EX

.8"

Ø

EX

.8" Ø

EX.8x8

UP

EX

.10

"Ø

EX

.10 "Ø

EX

.8"

Ø

EX.8"Ø

EX.14x6

EX.10"Ø

EX.EG

225 CFM

EX.28x16EX.34x22EX.40x26EX.60x30

EX

.28 x1

EX

.28 x1

EX

.28 x1

EX

.28 x1

EX

.28 x1

EX

.36 x2

EX.28x28 EX.28x16

EX

.24 x1

EX

.24 x1

EX

.24 x1

EX. EG

100 CFM

EX. EG

75 CFM

EX. 64x32

EX.24x20

EX

.18 x1

EX.10"Ø

EX.CUH TO

REMAIN

HV-1

(ON ROOF)

RTU-4

(ON ROOF)

VAV-34

VAV-35

VAV-37

VAV-38

VAV-41

VAV-40

VAV-43

VAV-42

VAV-39

VAV-44

VAV-36 EX.SD

90 CFM

22x36 RA OPENING

ON TOP OF DUCT

WITH BIRDSCREEN

EX.SD

CFM

EX.SD

125 CFM

EX.SD

400 CFM

EX.SD

230 CFM

EX.SD

50 CFM

EX.SD

400 CFM

EX.SD

400 CFM

EX.SD

CFM

EX.SD

400 CFM

EX.SD

250 CFM

EX.SD

250 CFM

EX.SD

250 CFM

SD-1

CFM

SD-1

240 CFM

EX.SD

235 CFM

HP-3

(WALL UNIT) HP-4

(WALL UNIT)

ACU-3

ACU-4

EX.RD

600 CFM

RD-1

600 CFM

14x14

12"Ø

EX.RD

800 CFM

EX.RD

840 CFM

x1 x1

EX.RD

840 CFM

24x18

"Ø

"Ø

EX.RD

600 CFM

EX.RD

440 CFM

10x18

EX.RD

450 CFM

RD-1

CFM

"Ø

16x18

"Ø

8" Ø

EX.RD

400 CFM

EX. RD

125 CFMEX.RD

125 CFM

36x20

NEW EF-3

(ON ROOF)

6" Ø

6" Ø

8x8

40x20

PATCH EX. 26" DIA.

WALL OPENINGS

EX.RD

CFM

EX. RD

350 CFM

EX.RD

350 CFM

EX.RD

600 CFM

EX.RD

150 CFM

EX.RD

50 CFM

MODIFY EXISTING

WALL OPENING TO

ROUTE NEW DUCT

18x18 x1

NEW EF-2

280 CFM

EX.EG

115 CFM

EX. EG

165 CFM

8" Ø

8" Ø

8" Ø

8" Ø

EX.SD

175 CFM

EX.SD

175 CFM

EX.SD

175 CFM

EX.SD

175 CFM

12x8 12x12

6"Ø

EX.SD

300 CFM

EX.SD

300 CFM

SD-1

300 CFM

SD-1

300 CFM

PATCH EX. 22"x14"

WALL OPENINGS

"Ø

"Ø

"Ø

"Ø

12x10

"Ø x1

EX. SD

150 CFM

EX.SD

150 CFM

EX.SD

40 CFM

EX.SD

140 CFM

14x10

PATCH EX. 16" DIA.

WALL OPENINGS

12"Ø

8"Ø

8"Ø

6"Ø

8"Ø x1

8x

EX. SD

125 CFM

EX.SD

400 CFM

SD-1

300 CFM

EX.SD

CFM

EX.SD

200 CFM

EX.SD

200 CFM

SD-1

CFM

24x14 x1

EX.SD

1000 CFM

EX.SD

1000 CFM

EX.SD

1000 CFM

EX.SD

1000 CFM

EX.SD

1000 CFM

EX.SD

1000 CFM

HV-2

(ON ROOF)

28x1824x1424 x8 x8

30x24 RETURN

AIR DUCT MAIN

DN FROM HV-2

40x20

36x20

RTU-5

(ON ROOF)

30x24 SUPPLY

AIR DUCT MAIN

DN FROM HV-2

CAP

CAP CAP

CAPEX.SD

1500 CFM

EX.SD

1500 CFM

EX.SD

1500 CFM

EX.SD

1500 CFM

EX.SD

1500 CFM

EX.SD

1500 CFM

EX.SG

500 CFM

EX.SG

500 CFM

30x24 SUPPLY AIR DUCT

MAIN DN FROM HV-2

EX.SD

50 CFM

32x32

30x24 SUPPLY AIR DUCT

MAIN DN FROM HV-2

24x32 24x32

EX

.10

"Ø

EX

.10 "Ø

SD-1

240 CFM

EX.SD

CFM PROVIDE 16x16 GRAVITY TYPE

RELIEF AIR DAMPER AND ROOF

HOOD. REUSE AND MODIFY

EXISTING ROOF OPENING TO

INSTALL NEW HOOD (RH-1)

MODIFY EX. ROOF

OPENING FOR HV-1

RETURN AIR

24x22 24x22

22x24 RA OPENING

ON TOP OF DUCT

WITH BIRDSCREEN

22x24 RA OPENING

ON TOP OF DUCT

WITH BIRDSCREEN

EX.RD

400 CFM

EX.SD

CFM

x1

FDFD

FD

FD

FD

FD10"Ø

10"Ø

12"Ø

"Ø

6" Ø

10"Ø

8"Ø10"Ø 12x12

10"Ø

10"Ø

10"Ø x6 x1

14x12

12x6 12x10

10"Ø

10"Ø 12x812x12

18x12 x1 x1 x1 x1

30x16 x1 x2 x1

10"Ø

10"Ø 10"Ø

10"Ø

14x8 14x8

14x8 14x12 6x8

14x14

NEW 6" CONCRETE

HOUSEKEEPING PAD

FIRST FLOOR

PLAN - EAST

M102

HVAC NEW

WORK

127th WING

BUILDING 1414

RENOVATION

http://www.AECOM.com

27777 Franklin Road, Suite 2000 Southfield, MI 48034 United States P: 248 204 5900 F: 248 204 5901

SCALE: 3 32" = 1'-0"

2a33a44a55a66a7

G F1

F E1

E D

C

C B1

B A1

A

Aa Ab

Ac Ad

D

11a2

NEW WORK KEYED NOTES:

ROUTE NEW MAIN SUPPLY AND RETURN DUCTWORK UP THROUGH ROOF AND

CONNECT TO NEW HV UNIT.

REUSE EXISTING SUPPLY DUCTWORK TO EXTENT SHOWN AND RECONNECT TO NEW

DUCTWORK SYSTEM. FIELD VERIFY EXISTING CONDITIONS.

PROVIDE NEW GRAVITY TYPE RELIEF AIR DAMPER AND ASSOCIATED ROOF HOOD

(RH-1). MODIFY AND REUSE EXISTING ROOF OPENING TO INSTALL NEW DAMPER AND

ROOF HOOD. INSTALL PER MANUFACTURER'S RECOMMENDATIONS.

PROVIDE NEW FIRE DAMPER AT NEW DUCT WALL PENETRATION. VERIFY REQUIRED

FIRE DAMPER SIZE PER INSTALLED DUCT.

REUSE EXISTING SUPPLY AND/OR RETURN AIR CEILING DIFFUSER. CONNECT TO NEW

DUCTWORK SYSTEM AND RE-BALANCE TO NEW DESIGN CFM AS SHOWN ON DRAWING.

CLEAN EXISTING REUSED DIFFUSER THROUGHOUT. THIS WORK IS TYPICAL FOR ALL

EXISTING DIFFUSERS TAGGED WITH EX.SD AND EX.RD.

PROVIDE NEW SUPPLY (SD-1) AND/OR RETURN DIFFUSER (RD-1), AND CONNECT TO

NEW DUCTWORK SYSTEM. BALANCE TO DESIGN CFM AS SHOWN ON DRAWING.

PATCH EXISTING DEMOLISHED DUCT WALL PENETRATION NOT IN USE TO MATCH

EXISTING CONSTRUCTION. REFER TO ARCHITECTURAL NOTES ON THIS DRAWING.

PROVIDE NEW VAV BOX WITH ASSOCIATED REHEAT COIL, ALC COMPATIBLE CONTROLS,

SUPPORTS AND ACCESSORIES. CONNECT TO NEW DUCTWORK SYSTEM AND CEILING

DIFFUSERS AS SHOWN ON DRAWINGS. REFER TO VAV TERMINAL UNIT SCHEDULE ON

M600 FOR SIZE AND CAPACITY. INSTALL AND PROVIDE REQUIRED CLEARANCES PER

MANUFACTURER'S RECOMMENDATIONS.

CONNECT EXISTING EXHAUST DUCT TO NEW EXHAUST FAN ON ROOF.

ROUTE NEW MAIN SUPPLY AND/OR RETURN AIR DUCTWORK UP THROUGH ROOF

OPENING AND CONNECT TO NEW RTU OR HV UNIT ON ROOF.

PROVIDE NEW SPLIT TYPE HEAT PUMP UNIT WITH ASSOCIATED SUPPORTS AND

CONTROLS. ROUTE NEW REFRIGERANT LINES CONCEALED THROUGH CEILING SPACE

OR WALL-MOUNTED AS POSSIBLE. ROUTE CONDENSATE LINE INDOOR AND DRAIN

OUTDOOR ON GRADE (SEE DETAIL ON M501). PROVIDE NEW 6" CONCRETE

HOUSEKEEPING PAD ON GRADE TO INSTALL OUTDOOR CONDENSING UNIT. INSTALL

INDOOR AND OUTDOOR UNITS PER MANUFACTURER'S INSTRUCTIONS.

CAP, SEAL AND INSULATE EXISTING WALL LOUVER.

GENERAL ARCHITECTURAL NOTES:

1. SAWCUT AND REMOVE PORTION OF WALL AS REQUIRED FOR NEW WORK. TEMPORARILY SHORE OPENING AS

REQUIRED FOR INSTALLATION OF NEW WORK. PATCH EXISTING WALL IF DAMAGED BY NEW WORK, FIRE STOP AND SEAL TO MAINTAIN EXISTING FIRE RATING. PROVIDE LINTELS AT NEW WALL OPENINGS AS REQUIRED.

2. PATCH AND FILL IN WALL PENETRATIONS IN KIND AS A RESULT OF DEMOLITION AND NEW WORK SCOPE.

MAINTAIN EXISTING FIRE RATING.

3. REMOVE, SALVAGE AND RE-INSTALL ALL CEILING TILES AS REQUIRED FOR DEMOLITION AND NEW WORK

SCOPE. REPLACE ANY DAMAGED AND/OR MISSING TILES IN KIND.

4. REMOVE PORTION OF ROOF AS REQUIRED FOR NEW WORK. COORDINATE LOCATION OF OPENINGS AND CURB SUPPORTS WITH STRUCTURE BELOW. PATCH EXISTING ROOFING IF DAMAGED BY NEW WORK IN KIND.

OVERLAP NEW AND EXISTING ROOFING MINIMUM 6" ON ALL SIDES.

5. ALL ROOFING WORK, INCLUDING EQUIPMENT CURBS, FLASHING, PATCHING, PENETRATIONS, REPAIRS, ETC.

SHALL BE PERFORMED IN ACCORDANCE WITH THE LATEST NRCA, NATIONAL ROOFING CONTRACTORS ASSOCIATION, ROOFING MANUALS AND DETAILS FOR LOW OR STEEP SLOPE SYSTEMS AND PER ROOFING

MANUFACTURER TO MAINTAIN EXISTING WARRANTIES.

1. CONTRACTOR SHALL INCLUDE THE ABATEMENT OF ALL ASBESTOS CONTAINING BUILDING

MATERIALS (ACBM) IN THEIR BID, THAT IS REQUIRED TO COMPLETE THE SCOPE OF WORK

INDICATED ON CONTRACT DOCUMENTS.

2. ASBESTOS ABATED IN THE COURSE OF THIS PROJECT MUST BE PROPERLY COLLECTED,

CONTAINERIZED AND DISPOSED OF IN A LANDFILL LICENSED TO ACCEPT ASBESTOS WASTE.

ALL ASBESTOS DISPOSAL MANIFESTS MUST BE COORDINATED WITH, AND SIGNED BY, 127TH

WING ENVIRONMENTAL MANAGEMENT OFFICE PERSONNEL.

3. CONTRACTOR SHALL UTILIZE SELFRIDGE ANG BASE (SANGB) FORM 23 FOR TRACKING

HAZARDOUS MATERIALS AND SANGB FORM 72 FOR SOLID WASTE TRACKING AND

DIVERSION.

4. CONTRACTOR SHALL ASSUME THE PRESENCE OF ASBESTOS CONTAINING DRY WALL JOINT

COMPOUND IN EXISTING WALLS ABOVE CEILING NOTED FOR PENETRATION BY NEW SUPPLY

AIR DUCTS.

1. IF SUSPECTED ASBESTOS CONTAINING BUILDING MATERIAL (ACBM) IS ENCOUNTERED, WORK IN

THE IMMEDIATE VICINITY MUST STOP AND THE OWNERS CONTRACTING OFFICER SHALL BE

NOTIFIED. AFTER CONSULTATION WITH BASE PERSONNEL, THE OWNERS CONTRACTING OFFICER

WILL DIRECT FURTHER ACTION TO BE TAKEN. WORK SHOULD PROCEED UNINTERRUPTED IN

UNAFFECTED AREAS OF THE PROJECT.

2. BASED ON THE AGE OF THE BUILDINGS AT SELFRIDGE ANG BASE, THERE IS THE POTENTIAL FOR

THE PRESENCE OF LEAD ON PAINTED SURFACES. BEST MANAGEMENT PRACTICES MUST BE

EMPLOYED TO MINIMIZE DUST AND ADEQUATELY PROTECT WORKERS FROM LEAD BASED PAINT

(LBP) EXPOSURE IN ACCORDANCE WITH OSHA AND MIOSHA STANDARDS.

3. IF ASBESTOS AND/OR LEAD IS SUSPECTED IT SHOULD BE TESTED FOR. IF EITHER ASBESTOS

AND/OR LEAD IS FOUND, FOLLOW APPLICABLE OSHA GUIDELINES FOR REMEDIATION.

4. FOR ADDITIONAL INFORMATION, CONTRACTOR TO REQUEST ASBESTOS INSPECTION REPORT

FROM SELFRIDGE AIR NATIONAL GUARD BASE.

GENERAL NOTES:

1. DO NOT SCALE DRAWINGS.

ALL DIMENSIONS ARE IN NOMINAL BRITISH IMPERIAL UNITS.

2. SEE ADDITIONAL GENERAL NOTES ON SHEET M000.

3. DRAWINGS ARE BASED UPON GOVERNMENT'S RECORD DRAWINGS AND FIELD

VERIFICATION. NOTIFY GOVERNMENT OF DISCREPANCIES OR CONDITIONS REQUIRING

SUPPLEMENTAL INSTRUCTIONS PRIOR TO CONTINUATION OF WORK.

4. VERIFY ALL DIMENSIONS, CONDITIONS AND LOCATION OF EXISTING EQUIPMENT,

CONTROLS, PUMPS, PIPING, DUCTWORK, DIFFUSERS, ETC. IN FIELD, AND NOTIFY THE

RESPECTIVE DISCIPLINE OF ANY DISCREPANCIES BEFORE COMMENCEMENT OF WORK.

5. REFER TO ELEC. DRAWINGS FOR ADDITIONAL INFORMATION OF ELECTRICAL

REQUIREMENTS.

6. ALL WORK SHALL COMPLY WITH LOCAL AND NATIONAL CODES, UFC STANDARDS,

MANUFACTURERS RECOMMENDATIONS, SANG AND ANG DESIGN POLICIES,

ANGTEL-15-01, ANGTEL-15-01-04, ANGTEL-15-01-05, ETC.

7. INSTALL NEW HVAC EQUIPMENT AND COMPONENTS WITH ADEQUATE CLEARANCE SPACE,

FOR ACCESS AND MAINTENANCE, AS REQUIRED PER LOCAL CODE, ANG-ETL POLICIES,

UFC STANDARDS AND MANUFACTURERS REQUIREMENTS.

8. THE CONTRACTOR SHALL REPLACE/RESTORE ANY ITEM OR EQUIPMENT REQUIRED TO

REMAIN OPERATIONAL OR TEMPORARILY BEING RELOCATED/OFFSETED, OR THAT IS

DAMAGED DURING CONSTRUCTION. EXISTING PIPING, CONDUIT, WIRES, SUPPORT, ETC.

THAT IS REQUIRED TO BE OFFSET TO FACILITATE THE INSTALLATION OF NEW WORK

SHALL BE REINSTALLED AND RESTORED TO ITS ORIGINAL CONDITION. CONTRACTOR IS

REQUIRED TO FIELD VERIFY AREA OF WORK WHERE NEW EQUIPMENT ARE INSTALLED

BEFORE START OF WORK. THIS WORK IS PART OF THE CONTRACTOR'S CONTRACT

RESPONSIBILITIES.

9. MECHANICAL DEMOLITION WORK SHALL INCLUDE, BUT NOT BE LIMITED TO, THE REMOVAL

OF EXISTING AIR CONDITIONING EQUIPMENT, BOILERS, PUMPS, PIPING, SHEET METAL

DUCTWORK, HEATING COILS, AIR-COOLED CHILLER, ETC. AS INDICATED AND/OR

DESCRIBED ON DEMOLITION DRAWINGS. COMPLETELY REMOVE ALONG WITH CONTROLS,

PNEUMATIC TUBING, HANGERS, SUPPORTS AND ALL RELATED ACCESSORIES.

10. FIELD VERIFY EXACT SIZE AND LOCATION OF EXISTING MECHANICAL SERVICES AND

UTILITIES BEING REUSED.

11. PATCH ALL OPENINGS IN FLOOR, CEILINGS AND WALLS CREATED BY DEMOLITION OR

NEW WORK AS REQUIRED TO MATCH EXISTING CONSTRUCTION.

12. ALL EQUIPMENT BEING REUSED AND/OR RELOCATED SHALL BE THOROUGHLY CLEANED

AND RECONDITIONED PRIOR TO START-UP.

13. CAP ALL BRANCH DUCTS FROM GRILLES, REGISTERS, DIFFUSERS, AND PIPING BEING

REMOVED, WHETHER INDICATED ON PLAN OR NOT.

14. PROVIDE TEMPORARY CAP ON ALL OPEN ENDED ACTIVE SUPPLY, RETURN AIR, EXHAUST

AIR DUCTWORK, REGISTERS AND GRILLES TO BE REUSED.

15. TEST AND BALANCE AIR & WATER VOLUMES TO FINAL DESIGN VALUES.

16. THE CONTRACTOR SHALL VERIFY WITH STRUCTURAL REQUIREMENT TO INSTALL NEW

EQUIPMENT ON ROOF, OR SUSPEND FROM EXISTING STRUCTURE.

2a33a44a55a66a7

G

F1

F

E1

E

D1

C1

C

B1

B

A1

A

Aa

Ab

Ac

Ad

D

11a2

C2

C3

B2

3a1

2a33a44a55a66a7 3a1

11a2

2a33a44a55a66a7

G

F1

F

E1

E

D1

C1

C

B1

B

A1

A

Aa

Ab

Ac

Ad

D

11a2

C2

C3

B2

3a1

2a33a44a55a66a7 3a1

11a2

G G

G G

G G

G G

G G

G G

G G

G G

G

G

EX. RTU-2

TO REMAIN

EX. CAPPED

ROOF VENT

EX. HW BOILERS FLUE

STACK ROOF OPENING

(E) PLUMBING

VENT PIPE

(TYP FOR ALL)

(TYP)

(TYP)

EX.CU

(TO REMAIN)

EX.PLBG VENT

(TYP FOR ALL)

(TYP)

(TYP)

(TYP)

(TYP)

(TYP) (TYP)

(TYP)(TYP)

(TYP)

(TYP)

EX.2" GAS

LINE TO

EX.RTU-S

EX. RTU-1

TO REMAIN

EX.2" GAS LINE

DOWN TO 4"

EX. GAS MAIN

EX.1"GAS

EX. CU

GGGG

GGGGG

RTU-3

(220 CFH)

(2532 LBS)

GGGGG

G G

G G

G G

G G

G G

G G

G G

G G

G G

G G

G G

G G

G G

G G

G

EX. GAS

METER

CAPPED

EX.FAN

(TYP)

EX. ROOF DRAIN

(TYP FOR ALL)

(TYP)

(TYP)

EX.CAPPED

ROOF VENT

3" GAS LINE DN

TO MECH. ROOM

G

G

4" NG

4" NG

RTU-4

(220 CFH)

(2532 LBS)

4" NG

RTU-5

(220 CFH)

(2532 LBS)

1" NG

4" NG

HV-2

(300 CFH)

(2532 LBS)

HV-1

(600 CFH)

(2532 LBS)

4" NG

2" NG

3" NG

3" NG

3" NG

EF-3

(400 CFM)

EF-2

(280 CFM)

EX.EF-1

(TO REMAIN)

RHB-2 CONCENTRIC

VERTICAL FLUE VENT

CAP

CAP

CAP

CAP

CAP

CAP

CAP

CAP

CAP

CAP

CAP

EX.CAPPED

ROOF VENT

CAP

CAP

CAP

CAP

CAP

CAP

CAPCAPCAP

EX. ROOF

VENT

CAP

RH-1

(RELIEF AIR HOOD)

ROOF PLAN -

HVAC NEW

M103

WORK

127th WING

BUILDING 1414

RENOVATION

http://www.AECOM.com

27777 Franklin Road, Suite 2000 Southfield, MI 48034 United States P: 248 204 5900 F: 248 204 5901

SCALE: 116"= 1'-0"

2a33a44a55a66a7

G F1

F E1

E D

C

C B1

B A1

A

Aa Ab

Ac Ad

D

11a2

2a33a44a55a66a7

G F1

F E1

E D

C

C B1

B A1

A

Aa Ab

Ac Ad

D

11a2

NEW WORK KEYED NOTES:

PROVIDE NEW 15-TON ROOFTOP UNIT (RTU) WITH ASSOCIATED PREFABRICATED

ROOF CURB, ECONOMIZER, GAS LINE CONNECTION, ACCESSORIES AND ALC

COMPATIBLE PACKAGED CONTROLS. INSTALL UNIT CURB ON EXISTING ROOF PER

MANUFACTURER'S RECOMMENDATIONS AND ARCHITECTURAL NOTES. COORDINATE

WITH EXISTING ROOF CONDITIONS. ROUTE NEW SUPPLY AND RETURN DUCTS DOWN

TO CEILING SPACE BELOW ROOF LINE. COORDINATE WITH STRUCTURAL AND

ELECTRICAL TRADES.

PROVIDE NEW HEATING AND VENTILATION UNIT (HV) WITH ASSOCIATED

PREFABRICATED ROOF CURB, FRESH AIR HOOD, GAS LINE CONNECTION,

ACCESSORIES AND ALC COMPATIBLE PACKAGED CONTROLS. INSTALL UNIT CURB ON

EXISTING ROOF PER MANUFACTURER'S RECOMMENDATIONS AND ARCHITECTURAL

NOTES. COORDINATE WITH EXISTING ROOF CONDITIONS. ROUTE NEW SUPPLY AND

RETURN DUCTS DOWN TO CEILING SPACE BELOW ROOF LINE. COORDINATE WITH

STRUCTURAL AND ELECTRICAL TRADES.

PROVIDE NEW TOILET EXHAUST FAN EF-3 WITH ASSOCIATED PREFABRICATED ROOF

CURB, BACK DRAFT DAMPER AND ACCESSORIES. INSTALL ON EXISTING ROOF AND

COORDINATE WITH EXISTING CONDITIONS. CONNECT NEW FAN WITH EXISTING

TOILET EXHAUST DUCT BELOW ROOF LINE. INTERLOCK NEW EF-3 WITH RTU-5

OPERATION.

PROVIDE NEW TOILET EXHAUST FAN EF-2 WITH ASSOCIATED PREFABRICATED ROOF

CURB, BACK DRAFT DAMPER AND ACCESSORIES. INSTALL ON EXISTING ROOF AND

COORDINATE WITH EXISTING CONDITIONS. CONNECT NEW FAN WITH EXISTING

TOILET EXHAUST DUCT BELOW ROOF LINE. INTERLOCK NEW EF-2 WITH RTU-4

OPERATION.

REUSE AND MODIFY EXISTING ROOF OPENING (DEMOLISHED BOILERS EXHAUST

STACK) TO ACCOMMODATE NEW 3" GAS LINE AND NEW 6" CONCENTRIC FLUE VENT

SERVING NEW RHB-2. PATCH ROOF OPENING AROUND NEW PENETRATIONS AS

REQUIRED.

ROUTE NEW 3" GAS LINE FROM MAIN MECHANICAL ROOM UP TO ROOF THROUGH

EXISTING ROOF OPENING. ROUTE NEW GAS LINE ON ROOF AND CONNECT TO NEW

RTU-3,4,5 AND HV-1,2 UNITS.

ROUTE NEW 6" CONCENTRIC VENT PIPE SERVING NEW RHB-2 THROUGH EXISTING

ROOF OPENING. INSTALL PER MANUFACTURER'S REQUIREMENTS. PATCH EXISTING

ROOF OPENING AROUND NEW PENETRATION AS REQUIRED.

CAP AND SEAL EXISTING ROOF VENT CURB WITH INSULATED TYPE SHEET METAL

ROOF CAP. REFER TO ARCHITECTURAL NOTES.

CAP AND SEAL EXISTING ROOF CURB FOR DEMOLISHED ROOF FAN WITH INSULATED

TYPE SHEET METAL ROOF CAP. REFER TO ARCHITECTURAL NOTES.

MODIFY EXISTING ROOF OPENING TO INSTALL NEW RELIEF AIR HOOD.

GENERAL ARCHITECTURAL NOTES:

1. SAWCUT AND REMOVE PORTION OF WALL AS REQUIRED FOR NEW WORK. TEMPORARILY SHORE OPENING AS REQUIRED FOR INSTALLATION OF NEW WORK. PATCH EXISTING WALL IF DAMAGED BY NEW WORK, FIRE STOP

AND SEAL TO MAINTAIN EXISTING FIRE RATING.

2. PATCH AND FILL IN ROOF PENETRATIONS IN KIND AS A RESULT OF DEMOLITION AND NEW WORK SCOPE.

3. REMOVE PORTION OF ROOF AS REQUIRED FOR NEW WORK. COORDINATE LOCATION OF OPENINGS AND CURB SUPPORTS WITH STRUCTURE BELOW. PATCH EXISTING ROOFING IF DAMAGED BY NEW WORK IN KIND.

OVERLAP NEW AND EXISTING ROOFING MINIMUM 6" ON ALL SIDES.

4. ALL ROOFING WORK, INCLUDING EQUIPMENT CURBS, FLASHING, PATCHING, PENETRATIONS, REPAIRS, ETC.

SHALL BE PERFORMED IN ACCORDANCE WITH THE LATEST NRCA, NATIONAL ROOFING CONTRACTORS ASSOCIATION, ROOFING MANUALS AND DETAILS FOR LOW OR STEEP SLOPE SYSTEMS AND PER ROOFING

MANUFACTURER TO MAINTAIN EXISTING WARRANTIES.

GENERAL NOTES:

1. DO NOT SCALE DRAWINGS.

ALL DIMENSIONS ARE IN NOMINAL BRITISH IMPERIAL UNITS.

2. SEE ADDITIONAL GENERAL NOTES ON SHEET M000.

3. DRAWINGS ARE BASED UPON GOVERNMENT'S RECORD DRAWINGS AND FIELD

VERIFICATION. NOTIFY GOVERNMENT OF DISCREPANCIES OR CONDITIONS REQUIRING

SUPPLEMENTAL INSTRUCTIONS PRIOR TO CONTINUATION OF WORK.

4. VERIFY ALL DIMENSIONS, CONDITIONS AND LOCATION OF EXISTING EQUIPMENT,

CONTROLS, PUMPS, PIPING, DUCTWORK, DIFFUSERS, ETC. IN FIELD, AND NOTIFY THE

RESPECTIVE DISCIPLINE OF ANY DISCREPANCIES BEFORE COMMENCEMENT OF WORK.

5. REFER TO ELEC. DRAWINGS FOR ADDITIONAL INFORMATION OF ELECTRICAL

REQUIREMENTS.

6. ALL WORK SHALL COMPLY WITH LOCAL AND NATIONAL CODES, UFC STANDARDS,

MANUFACTURERS RECOMMENDATIONS, SANG AND ANG DESIGN POLICIES,

ANGTEL-15-01, ANGTEL-15-01-04, ANGTEL-15-01-05, ETC.

7. INSTALL NEW HVAC EQUIPMENT AND COMPONENTS WITH ADEQUATE CLEARANCE SPACE,

FOR ACCESS AND MAINTENANCE, AS REQUIRED PER LOCAL CODE, ANG-ETL POLICIES,

UFC STANDARDS AND MANUFACTURERS REQUIREMENTS.

8. THE CONTRACTOR SHALL REPLACE/RESTORE ANY ITEM OR EQUIPMENT REQUIRED TO

REMAIN OPERATIONAL OR TEMPORARILY BEING RELOCATED/OFFSETED, OR THAT IS

DAMAGED DURING CONSTRUCTION. EXISTING PIPING, CONDUIT, WIRES, SUPPORT, ETC.

THAT IS REQUIRED TO BE OFFSET TO FACILITATE THE INSTALLATION OF NEW WORK

SHALL BE REINSTALLED AND RESTORED TO ITS ORIGINAL CONDITION. CONTRACTOR IS

REQUIRED TO FIELD VERIFY AREA OF WORK WHERE NEW EQUIPMENT ARE INSTALLED

BEFORE START OF WORK. THIS WORK IS PART OF THE CONTRACTOR'S CONTRACT

RESPONSIBILITIES.

9. PAINT ALL NEW GAS PIPING ON ROOF PER SANGB STANDARDS AND REQUIREMENT.

10. FIELD VERIFY EXACT SIZE AND LOCATION OF EXISTING MECHANICAL SERVICES AND

UTILITIES BEING REUSED.

11. PATCH ALL OPENINGS IN ROOF, FLOOR, CEILINGS AND WALLS CREATED BY DEMOLITION

OR NEW WORK AS REQUIRED TO MATCH EXISTING CONSTRUCTION.

12. ALL EQUIPMENT BEING REUSED AND/OR RELOCATED SHALL BE THOROUGHLY CLEANED

AND RECONDITIONED PRIOR TO START-UP.

13. CAP ALL BRANCH DUCTS FROM GRILLES, REGISTERS, DIFFUSERS, AND PIPING BEING

REMOVED, WHETHER INDICATED ON PLAN OR NOT.

14. PROVIDE TEMPORARY CAP ON ALL OPEN ENDED ACTIVE SUPPLY, RETURN AIR, EXHAUST

AIR DUCTWORK, REGISTERS AND GRILLES TO BE REUSED.

15. TEST AND BALANCE AIR & WATER VOLUMES TO FINAL DESIGN VALUES.

EX.RHB-1

EX.UH-1

EX.DWHEX. AHU

(ABANDON IN PLACE)

EX. ABANDONED HW SUPPLY

& RETURN PIPING LOOP

(OUT OF PROJECT AREA)

EX. ABANDONED HW SUPPLY

& RETURN PIPING LOOP

(OUT OF PROJECT AREA)

(OUT OF PROJECT AREA)

EX. 2" HW REHEAT

RETURN PIPING LOOP

EX. 2" HW REHEAT

SUPPLY PIPING LOOP

EX. HW SUPPLY & RETURN

REHEAT PIPING TO EX. VAV BOXES

(OUT OF PROJECT AREA)

EX. HWS&R REHEAT

PIPING LOOP

(OUT OF PROJECT AREA)

EX.

CHEMICAL

FEEDER

EX. HOUSEKEEPING

PAD TO REMAIN

EX. CW

MAKEUP LINE

EX. ABANDONED HW SUPPLY

& RETURN PIPING LOOP

(OUT OF PROJECT AREA)

EX.HWS

EX

.H

W S

EX

.H

W R

EX.HWR

EX.HWS

EX.HWR

EX

.H

W S

EX

.H

W R

EX.HWR

EX. ABANDONED HW SUPPLY

& RETURN PIPING LOOP

(OUT OF PROJECT AREA)

2"

EX. HWS&R REHEAT

PIPING TO EX.VAV BOXES

(OUT OF PROJECT AREA)

EX. 2" HWR

EX. HWS&R REHEAT

PIPING TO EX.VAV BOXES

(OUT OF PROJECT AREA)

4" HWS&R

4" HWS&R

1-14" HWS&R

1-12" HWS&R

1-12" HWS&R

1-14" HWS&R

2" HWS&R

EX.1" HWS&R

1-12" HWS&R

RHB-2

CP-1

CP-2

S

S

S

S

S

S

S

VAV-26

VAV-25

VAV-28VAV-27

VAV-29

VAV-30

VAV-31

VAV-32

VAV-33

1" HWS&R

S

S

ET-1

1"HWS

1"HWR

HW

S

HW

R

S

2a33a44a55a66a7

G

F1

F

E1

E

D1

C1

C

D

11a2

C2

C3

3a1

MATCHLINE - SEE SHEET M105

FIRST FLOOR

PLAN - WEST

M104

HVAC PIPING

NEW WORK

127th WING

BUILDING 1414

RENOVATION

http://www.AECOM.com

27777 Franklin Road, Suite 2000 Southfield, MI 48034 United States P: 248 204 5900 F: 248 204 5901

SCALE: 3 32" = 1'-0"

2a33a44a55a66a7

G F1

F E1

E D

C

C B1

B A1

A

Aa Ab

Ac Ad

D

11a2

NEW WORK KEYED NOTES:

PROVIDE A NEW CONDENSING TYPE BOILER (RHB-2) AND INSTALL ON EXISTING

HOUSEKEEPING PAD. CONNECT NEW BOILER TO EXISTING HOT WATER REHEAT

PIPING LOOP. MODIFY EXISTING PIPING LOOP AS REQUIRED TO INSTALL NEW BOILER

(SEE DRAWING M502). PROVIDE MAKE UP WATER, GAS AND VENTING CONNECTIONS

PER MANUFACTURER'S RECOMMENDATIONS. PROVIDE ALC COMPATIBLE DDC

CONTROLS AND REPROGRAM BOILER SEQUENCE FOR LEAD-LAG TYPE OPERATION.

PROVIDE TWO HOT WATER RE-CIRCULATION PUMPS (CP-1 & CP-2), AND CONNECT TO

EXISTING HOT WATER REHEAT PIPING LOOP. MODIFY EXISTING PIPING AS REQUIRED

TO INSTALL NEW PUMPS IN A PARALLEL CONFIGURATION. PROVIDE VARIABLE

FREQUENCY DRIVE FOR EACH PUMP WITH COMPATIBLE ALC DDC CONTROLS.

REPROGRAM NEW PUMPS CONTROL SEQUENCE TO OPERATE WITH MODIFIED BOILER

SYSTEM IN LEAD-LAG TYPE OPERATION.

PROVIDE A NEW EXPANSION TANK ET-1 AND RECONNECT TO EXISTING HOT WATER

REHEAT PIPING LOOP.

RECONNECT EXISTING UNIT HEATER (1414 UH-1) TO EXISTING HOT WATER REHEAT

PIPING LOOP AS SHOWN.

REUSE EXISTING 1-1/2" HWS & R REHEAT PIPING LOOP TO SUPPLY NEW VAV HOT

WATER REHEAT COILS.

CONNECT NEW VAV BOX HOT WATER REHEAT COIL TO NEW HOT WATER REHEAT

PIPING LOOP.

PROVIDE NEW SPACE TEMPERATURE SENSOR AND CONNECT TO ASSOCIATED VAV

BOX AS SHOWN.

REFER TO ASBESTOS ABATEMENT NOTES ON THIS DRAWING.

GENERAL ARCHITECTURAL NOTES:

1. SAWCUT AND REMOVE PORTION OF WALL AS REQUIRED FOR NEW WORK. TEMPORARILY SHORE OPENING AS

REQUIRED FOR INSTALLATION OF NEW WORK. PATCH EXISTING WALL IF DAMAGED BY NEW WORK, FIRE STOP AND SEAL TO MAINTAIN EXISTING FIRE RATING. PROVIDE LINTELS AT NEW WALL OPENINGS AS REQUIRED.

2. PATCH AND FILL IN WALL PENETRATIONS IN KIND AS A RESULT OF DEMOLITION AND NEW WORK SCOPE.

MAINTAIN EXISTING FIRE RATING.

3. REMOVE, SALVAGE AND RE-INSTALL ALL CEILING TILES AS REQUIRED FOR DEMOLITION AND NEW WORK

SCOPE. REPLACE ANY DAMAGED AND/OR MISSING TILES IN KIND.

4. REMOVE PORTION OF ROOF AS REQUIRED FOR NEW WORK. COORDINATE LOCATION OF OPENINGS AND CURB SUPPORTS WITH STRUCTURE BELOW. PATCH EXISTING ROOFING IF DAMAGED BY NEW WORK IN KIND.

OVERLAP NEW AND EXISTING ROOFING MINIMUM 6" ON ALL SIDES.

5. ALL ROOFING WORK, INCLUDING EQUIPMENT CURBS, FLASHING, PATCHING, PENETRATIONS, REPAIRS, ETC.

SHALL BE PERFORMED IN ACCORDANCE WITH THE LATEST NRCA, NATIONAL ROOFING CONTRACTORS ASSOCIATION, ROOFING MANUALS AND DETAILS FOR LOW OR STEEP SLOPE SYSTEMS AND PER ROOFING

MANUFACTURER TO MAINTAIN EXISTING WARRANTIES.

1. CONTRACTOR SHALL INCLUDE THE ABATEMENT OF ALL ASBESTOS CONTAINING BUILDING

MATERIALS (ACBM) IN THEIR BID, THAT IS REQUIRED TO COMPLETE THE SCOPE OF WORK

INDICATED ON CONTRACT DOCUMENTS.

2. ASBESTOS ABATED IN THE COURSE OF THIS PROJECT MUST BE PROPERLY COLLECTED,

CONTAINERIZED AND DISPOSED OF IN A LANDFILL LICENSED TO ACCEPT ASBESTOS WASTE.

ALL ASBESTOS DISPOSAL MANIFESTS MUST BE COORDINATED WITH, AND SIGNED BY, 127TH

WING ENVIRONMENTAL MANAGEMENT OFFICE PERSONNEL.

3. CONTRACTOR SHALL UTILIZE SELFRIDGE ANG BASE (SANGB) FORM 23 FOR TRACKING

HAZARDOUS MATERIALS AND SANGB FORM 72 FOR SOLID WASTE TRACKING AND

DIVERSION.

4. CONTRACTOR SHALL ASSUME THE PRESENCE OF ASBESTOS CONTAINING DRY WALL JOINT

COMPOUND IN EXISTING WALLS ABOVE CEILING NOTED FOR PENETRATION BY NEW SUPPLY

AIR DUCTS.

1. IF SUSPECTED ASBESTOS CONTAINING BUILDING MATERIAL (ACBM) IS ENCOUNTERED, WORK IN

THE IMMEDIATE VICINITY MUST STOP AND THE OWNERS CONTRACTING OFFICER SHALL BE

NOTIFIED. AFTER CONSULTATION WITH BASE PERSONNEL, THE OWNERS CONTRACTING OFFICER

WILL DIRECT FURTHER ACTION TO BE TAKEN. WORK SHOULD PROCEED UNINTERRUPTED IN

UNAFFECTED AREAS OF THE PROJECT.

2. BASED ON THE AGE OF THE BUILDINGS AT SELFRIDGE ANG BASE, THERE IS THE POTENTIAL FOR

THE PRESENCE OF LEAD ON PAINTED SURFACES. BEST MANAGEMENT PRACTICES MUST BE

EMPLOYED TO MINIMIZE DUST AND ADEQUATELY PROTECT WORKERS FROM LEAD BASED PAINT

(LBP) EXPOSURE IN ACCORDANCE WITH OSHA AND MIOSHA STANDARDS.

3. IF ASBESTOS AND/OR LEAD IS SUSPECTED IT SHOULD BE TESTED FOR. IF EITHER ASBESTOS

AND/OR LEAD IS FOUND, FOLLOW APPLICABLE OSHA GUIDELINES FOR REMEDIATION.

4. FOR ADDITIONAL INFORMATION, CONTRACTOR TO REQUEST ASBESTOS INSPECTION REPORT

FROM SELFRIDGE AIR NATIONAL GUARD BASE.

GENERAL NOTES:

1. DO NOT SCALE DRAWINGS.

ALL DIMENSIONS ARE IN NOMINAL BRITISH IMPERIAL UNITS.

2. SEE ADDITIONAL GENERAL NOTES ON SHEET M000.

3. DRAWINGS ARE BASED UPON GOVERNMENT'S RECORD DRAWINGS AND FIELD

VERIFICATION. NOTIFY GOVERNMENT OF DISCREPANCIES OR CONDITIONS REQUIRING

SUPPLEMENTAL INSTRUCTIONS PRIOR TO CONTINUATION OF WORK.

4. VERIFY ALL DIMENSIONS, CONDITIONS AND LOCATION OF EXISTING EQUIPMENT,

CONTROLS, PUMPS, PIPING, DUCTWORK, DIFFUSERS, ETC. IN FIELD, AND NOTIFY THE

RESPECTIVE DISCIPLINE OF ANY DISCREPANCIES BEFORE COMMENCEMENT OF WORK.

5. REFER TO ELEC. DRAWINGS FOR ADDITIONAL INFORMATION OF ELECTRICAL

REQUIREMENTS.

6. ALL WORK SHALL COMPLY WITH LOCAL AND NATIONAL CODES, UFC STANDARDS,

MANUFACTURERS RECOMMENDATIONS, SANG AND ANG DESIGN POLICIES,

ANGTEL-15-01, ANGTEL-15-01-04, ANGTEL-15-01-05, ETC.

7. INSTALL NEW HVAC EQUIPMENT AND COMPONENTS WITH ADEQUATE CLEARANCE SPACE,

FOR ACCESS AND MAINTENANCE, AS REQUIRED PER LOCAL CODE, ANG-ETL POLICIES,

UFC STANDARDS AND MANUFACTURERS REQUIREMENTS.

8. THE CONTRACTOR SHALL REPLACE/RESTORE ANY ITEM OR EQUIPMENT REQUIRED TO

REMAIN OPERATIONAL OR TEMPORARILY BEING RELOCATED/OFFSETED, OR THAT IS

DAMAGED DURING CONSTRUCTION. EXISTING PIPING, CONDUIT, WIRES, SUPPORT, ETC.

THAT IS REQUIRED TO BE OFFSET TO FACILITATE THE INSTALLATION OF NEW WORK

SHALL BE REINSTALLED AND RESTORED TO ITS ORIGINAL CONDITION. CONTRACTOR IS

REQUIRED TO FIELD VERIFY AREA OF WORK WHERE NEW EQUIPMENT ARE INSTALLED

BEFORE START OF WORK. THIS WORK IS PART OF THE CONTRACTOR'S CONTRACT

RESPONSIBILITIES.

9. MECHANICAL DEMOLITION WORK SHALL INCLUDE, BUT NOT BE LIMITED TO, THE REMOVAL

OF EXISTING AIR CONDITIONING EQUIPMENT, BOILERS, PUMPS, PIPING, SHEET METAL

DUCTWORK, HEATING COILS, AIR-COOLED CHILLER, ETC. AS INDICATED AND/OR

DESCRIBED ON DEMOLITION DRAWINGS. COMPLETELY REMOVE ALONG WITH CONTROLS,

PNEUMATIC TUBING, HANGERS, SUPPORTS AND ALL RELATED ACCESSORIES.

10. FIELD VERIFY EXACT SIZE AND LOCATION OF EXISTING MECHANICAL SERVICES AND

UTILITIES BEING REUSED.

11. PATCH ALL OPENINGS IN FLOOR, CEILINGS AND WALLS CREATED BY DEMOLITION OR

NEW WORK AS REQUIRED TO MATCH EXISTING CONSTRUCTION.

12. ALL EQUIPMENT BEING REUSED AND/OR RELOCATED SHALL BE THOROUGHLY CLEANED

AND RECONDITIONED PRIOR TO START-UP.

13. CAP AND TERMINATE ALL EXISTING PIPING NOT IN USE AND EXTEND OUT OF PROJECT

AREA. DRAIN ALL EXISTING PIPING, CAP AND SEAL.

14. PROVIDE TEMPORARY CAP ON ALL OPEN ENDED ACTIVE SUPPLY AND RETURN HOT

WATER PIPING TO BE REUSED.

15. TEST AND BALANCE AIR & WATER VOLUMES TO FINAL DESIGN VALUES.

EX. ABANDONED HW SUPPLY

& RETURN PIPING LOOP

(OUT OF PROJECT AREA)

EX.CUH TO

REMAIN

1-14" HWS&R

1-14" HWS&R

3/4" HWS&R

1" HWS&R

1" HWS&R

1-14" HWS&R

VAV-33

VAV-34

VAV-35

VAV-36

VAV-37

VAV-38VAV-39

VAV-41

VAV-40

VAV-42

VAV-43

VAV-44

HV-2

(ON ROOF)

HV-1

(ON ROOF)

ACU-3

ACU-4

HP-3

HP-4

S S

S

S

S

S

S

S

SS

S

S

HW

S

HW

R

SC

B1

B

A1

A

Aa

Ab

Ac

Ad

B2

2a33a44a55a66a7 3a1

11a2

MATCHLINE - SEE SHEET M104

FIRST FLOOR

PLAN - EAST

M105

HVAC PIPING

NEW WORK

127th WING

BUILDING 1414

RENOVATION

http://www.AECOM.com

27777 Franklin Road, Suite 2000 Southfield, MI 48034 United States P: 248 204 5900 F: 248 204 5901

SCALE: 3 32" = 1'-0"

2a33a44a55a66a7

G F1

F E1

E D

C

C B1

B A1

A

Aa Ab

Ac Ad

D

11a2

NEW WORK KEYED NOTES:

CONNECT NEW VAV BOX HOT WATER REHEAT COIL TO NEW HOT WATER REHEAT

PIPING LOOP.

PROVIDE NEW SPACE TEMPERATURE SENSOR AND CONNECT TO ASSOCIATED VAV

BOX AS SHOWN.

PROVIDE NEW SPACE TEMPERATURE SENSOR AND CONNECT TO ASSOCIATED HV

UNIT ON ROOF AS SHOWN.

ROUTE NEW LIQUID AND GAS REFRIGERANT LINES TO NEW SPLIT TYPE HEAT PUMP

UNIT. INSTALL PIPING CONCEALED IN CEILING SPACE OR WALL-MOUNTED AS

POSSIBLE. INSTALL PER MANUFACTURER'S RECOMMENDATIONS. SEE DETAIL ON M501.

RECONNECT EXISTING HOT WATER PIPING TO NEW HOT WATER REHEAT PIPING LOOP.

FIELD VERIFY EXISTING PIPING ABOVE CEILING.

GENERAL ARCHITECTURAL NOTES:

1. SAWCUT AND REMOVE PORTION OF WALL AS REQUIRED FOR NEW WORK. TEMPORARILY SHORE OPENING AS

REQUIRED FOR INSTALLATION OF NEW WORK. PATCH EXISTING WALL IF DAMAGED BY NEW WORK, FIRE STOP AND SEAL TO MAINTAIN EXISTING FIRE RATING. PROVIDE LINTELS AT NEW WALL OPENINGS AS REQUIRED.

2. PATCH AND FILL IN WALL PENETRATIONS IN KIND AS A RESULT OF DEMOLITION AND NEW WORK SCOPE.

MAINTAIN EXISTING FIRE RATING.

3. REMOVE, SALVAGE AND RE-INSTALL ALL CEILING TILES AS REQUIRED FOR DEMOLITION AND NEW WORK

SCOPE. REPLACE ANY DAMAGED AND/OR MISSING TILES IN KIND.

4. REMOVE PORTION OF ROOF AS REQUIRED FOR NEW WORK. COORDINATE LOCATION OF OPENINGS AND CURB SUPPORTS WITH STRUCTURE BELOW. PATCH EXISTING ROOFING IF DAMAGED BY NEW WORK IN KIND.

OVERLAP NEW AND EXISTING ROOFING MINIMUM 6" ON ALL SIDES.

5. ALL ROOFING WORK, INCLUDING EQUIPMENT CURBS, FLASHING, PATCHING, PENETRATIONS, REPAIRS, ETC.

SHALL BE PERFORMED IN ACCORDANCE WITH THE LATEST NRCA, NATIONAL ROOFING CONTRACTORS ASSOCIATION, ROOFING MANUALS AND DETAILS FOR LOW OR STEEP SLOPE SYSTEMS AND PER ROOFING

MANUFACTURER TO MAINTAIN EXISTING WARRANTIES.

1. CONTRACTOR SHALL INCLUDE THE ABATEMENT OF ALL ASBESTOS CONTAINING BUILDING

MATERIALS (ACBM) IN THEIR BID, THAT IS REQUIRED TO COMPLETE THE SCOPE OF WORK

INDICATED ON CONTRACT DOCUMENTS.

2. ASBESTOS ABATED IN THE COURSE OF THIS PROJECT MUST BE PROPERLY COLLECTED,

CONTAINERIZED AND DISPOSED OF IN A LANDFILL LICENSED TO ACCEPT ASBESTOS WASTE.

ALL ASBESTOS DISPOSAL MANIFESTS MUST BE COORDINATED WITH, AND SIGNED BY, 127TH

WING ENVIRONMENTAL MANAGEMENT OFFICE PERSONNEL.

3. CONTRACTOR SHALL UTILIZE SELFRIDGE ANG BASE (SANGB) FORM 23 FOR TRACKING

HAZARDOUS MATERIALS AND SANGB FORM 72 FOR SOLID WASTE TRACKING AND

DIVERSION.

4. CONTRACTOR SHALL ASSUME THE PRESENCE OF ASBESTOS CONTAINING DRY WALL JOINT

COMPOUND IN EXISTING WALLS ABOVE CEILING NOTED FOR PENETRATION BY NEW SUPPLY

AIR DUCTS.

1. IF SUSPECTED ASBESTOS CONTAINING BUILDING MATERIAL (ACBM) IS ENCOUNTERED, WORK IN

THE IMMEDIATE VICINITY MUST STOP AND THE OWNERS CONTRACTING OFFICER SHALL BE

NOTIFIED. AFTER CONSULTATION WITH BASE PERSONNEL, THE OWNERS CONTRACTING OFFICER

WILL DIRECT FURTHER ACTION TO BE TAKEN. WORK SHOULD PROCEED UNINTERRUPTED IN

UNAFFECTED AREAS OF THE PROJECT.

2. BASED ON THE AGE OF THE BUILDINGS AT SELFRIDGE ANG BASE, THERE IS THE POTENTIAL FOR

THE PRESENCE OF LEAD ON PAINTED SURFACES. BEST MANAGEMENT PRACTICES MUST BE

EMPLOYED TO MINIMIZE DUST AND ADEQUATELY PROTECT WORKERS FROM LEAD BASED PAINT

(LBP) EXPOSURE IN ACCORDANCE WITH OSHA AND MIOSHA STANDARDS.

3. IF ASBESTOS AND/OR LEAD IS SUSPECTED IT SHOULD BE TESTED FOR. IF EITHER ASBESTOS

AND/OR LEAD IS FOUND, FOLLOW APPLICABLE OSHA GUIDELINES FOR REMEDIATION.

4. FOR ADDITIONAL INFORMATION, CONTRACTOR TO REQUEST ASBESTOS INSPECTION REPORT

FROM SELFRIDGE AIR NATIONAL GUARD BASE.

GENERAL NOTES:

1. DO NOT SCALE DRAWINGS.

ALL DIMENSIONS ARE IN NOMINAL BRITISH IMPERIAL UNITS.

2. SEE ADDITIONAL GENERAL NOTES ON SHEET M000.

3. DRAWINGS ARE BASED UPON GOVERNMENT'S RECORD DRAWINGS AND FIELD

VERIFICATION. NOTIFY GOVERNMENT OF DISCREPANCIES OR CONDITIONS REQUIRING

SUPPLEMENTAL INSTRUCTIONS PRIOR TO CONTINUATION OF WORK.

4. VERIFY ALL DIMENSIONS, CONDITIONS AND LOCATION OF EXISTING EQUIPMENT,

CONTROLS, PUMPS, PIPING, DUCTWORK, DIFFUSERS, ETC. IN FIELD, AND NOTIFY THE

RESPECTIVE DISCIPLINE OF ANY DISCREPANCIES BEFORE COMMENCEMENT OF WORK.

5. REFER TO ELEC. DRAWINGS FOR ADDITIONAL INFORMATION OF ELECTRICAL

REQUIREMENTS.

6. ALL WORK SHALL COMPLY WITH LOCAL AND NATIONAL CODES, UFC STANDARDS,

MANUFACTURERS RECOMMENDATIONS, SANG AND ANG DESIGN POLICIES,

ANGTEL-15-01, ANGTEL-15-01-04, ANGTEL-15-01-05, ETC.

7. INSTALL NEW HVAC EQUIPMENT AND COMPONENTS WITH ADEQUATE CLEARANCE SPACE,

FOR ACCESS AND MAINTENANCE, AS REQUIRED PER LOCAL CODE, ANG-ETL POLICIES,

UFC STANDARDS AND MANUFACTURERS REQUIREMENTS.

8. THE CONTRACTOR SHALL REPLACE/RESTORE ANY ITEM OR EQUIPMENT REQUIRED TO

REMAIN OPERATIONAL OR TEMPORARILY BEING RELOCATED/OFFSETED, OR THAT IS

DAMAGED DURING CONSTRUCTION. EXISTING PIPING, CONDUIT, WIRES, SUPPORT, ETC.

THAT IS REQUIRED TO BE OFFSET TO FACILITATE THE INSTALLATION OF NEW WORK

SHALL BE REINSTALLED AND RESTORED TO ITS ORIGINAL CONDITION. CONTRACTOR IS

REQUIRED TO FIELD VERIFY AREA OF WORK WHERE NEW EQUIPMENT ARE INSTALLED

BEFORE START OF WORK. THIS WORK IS PART OF THE CONTRACTOR'S CONTRACT

RESPONSIBILITIES.

9. MECHANICAL DEMOLITION WORK SHALL INCLUDE, BUT NOT BE LIMITED TO, THE REMOVAL

OF EXISTING AIR CONDITIONING EQUIPMENT, BOILERS, PUMPS, PIPING, SHEET METAL

DUCTWORK, HEATING COILS, AIR-COOLED CHILLER, ETC. AS INDICATED AND/OR

DESCRIBED ON DEMOLITION DRAWINGS. COMPLETELY REMOVE ALONG WITH CONTROLS,

PNEUMATIC TUBING, HANGERS, SUPPORTS AND ALL RELATED ACCESSORIES.

10. FIELD VERIFY EXACT SIZE AND LOCATION OF EXISTING MECHANICAL SERVICES AND

UTILITIES BEING REUSED.

11. PATCH ALL OPENINGS IN FLOOR, CEILINGS AND WALLS CREATED BY DEMOLITION OR

NEW WORK AS REQUIRED TO MATCH EXISTING CONSTRUCTION.

12. ALL EQUIPMENT BEING REUSED AND/OR RELOCATED SHALL BE THOROUGHLY CLEANED

AND RECONDITIONED PRIOR TO START-UP.

13. CAP AND TERMINATE ALL EXISTING PIPING NOT IN USE AND EXTEND OUT OF PROJECT

AREA. DRAIN ALL EXISTING PIPING, CAP AND SEAL.

14. PROVIDE TEMPORARY CAP ON ALL OPEN ENDED ACTIVE SUPPLY AND RETURN HOT

WATER PIPING TO BE REUSED.

15. TEST AND BALANCE AIR & WATER VOLUMES TO FINAL DESIGN VALUES.

NOTES:

1. INSULATE ALL NEW SUPPLY AND FRESH AIR DUCTWORK PER DUCTWORK.

2. ALL FLEXIBLE LOW-PRESSURE DUCTWORK SHALL BE INSULATED AND NOT EXCEED 5'-0" IN LENGTH.

MAIN SUPPLY DUCT

VOLUME DAMPER

ROUND BRANCH

DUCT

DIFFUSER

RIGID DUCT (MIN 12")

LAY-IN CEILING

MAIN SUPPLY DUCT

VOLUME DAMPER

DUCT

45° SMACNA

TAKE-OFF FITTING

(TYP)

5'-0" (MAX) FLEXIBLE

DUCT

DIFFUSER

CEILING

TYPICAL BRANCH DUCTWORK DETAIL

N.T.S.

45° SMACNA TAKE-OFF

FITTING TO AIR TERMINAL

UNIT

MAIN

SUPPLY

PLAN VIEW

FLOW

FL

OW

TYPICAL SUPPLY DUCT TAKEOFF DETAIL

N.T.S.PROVIDE MAX 5'-0"

FLEXIBLE DUCT

DUCT COLLAR

(TYP)

RIGID DUCT

(MIN 12")

DUCT COLLAR

(TYP)

VOLUME DAMPER

(TYP AT EACH

BRANCH DUCT)

VD

FLEX DUCT SUPPORTED

WITHOUT SAGS OR KINKS SAME

SIZE AS DIFFUSER THROAT

SEE DUCT

TAKEOFF DETAIL

45° SMACNA

TAKE-OFF FITTING

(TYP)

RECTANGULAR MED.

VELOCITY SUPPLY DUCT

CONICAL SPIN-IN FITTINGS WITH

DAMPERS. LOW VELOCITY FLEX DUCT

FLEX DUCT SIZE EQUAL TO THE DUCT

DIMENSIONS SHOWN ON THE DRAWING

LOW VELOCITY FLEX. DUCT MAX.

5'- 0" LENGTH

FLEXIBLE DUCT CONNECTION

TO AIR DISTRIBUTION DEVICE

SEE SCHEDULE FOR SIZE

SQUARE TO

ROUND

TRANSITION

VOLUME

DAMPER

LOW VELOCITY

DUCT

REHEAT COIL

TERMINAL BOX

MED. VELOCITY

FLEX. DUCT. 1'- 0"

MAX. LENGTH

TYPICAL VAV TERMINAL BOX DETAIL WITH REHEAT COIL

N.T.S.

ROOF EXHAUST FAN DETAIL

N.T.S.

W/ROD TO STRUCTURE

PIPE HANGER

ENDS

LONG) W/FLARED

SHIELD (MIN 12"

18 GAUGE PIPE

PIPE

1"

PITCH DOWN

OPEN DRAIN

DRAIN PAN

WHERE X = CASING STATIC PRESSURE IN INCHES WC.

B (1" + X)/2

AHU TYPE

DRAW THRU 1" + X

A

B

A

SIZE AS THE NIPPLE ON THE DRAIN PAN

DRAIN LINE SHALL BE AT LEAST THE SAME

TOWARD DRAIN

OR ROOF

BLOW THRU 1" 1" + X

CLEAN OUT

6" MIN.

EXISTING ROOF

BACKDRAFT

DRIP PAN - ALL JOINTS

SOLDERED WATERTIGHT

PAN MINIMUM DEPTH OF 2"

MINIMUM 1/4 THROAT

ROOF MOUNTED HOOD

ACOUSTICALLY LINED WITH 1"

LINING IN HOOD AND THROAT

ALL SIDES

WASHERS, MAX. 12"O.C.

BRASS SCREWS WITH 3/4"DIA.

MUST BE LEVEL

TOP OF CURB

" M

IN

MAXIMUM DIMENSION

CONSTRUCTION

DAMPER

TYPICAL PIPE HANGER DETAIL

N.T.S.

NOTE:

USE FOR COLD PIPING ONLY. FOR HOT PIPING AND STEAM

PIPING OMIT SHIELD AND USE CLEVIS SIZE SAME AS PIPE SIZE.

AIR HANDLING UNIT CONDENSATE DRAIN TRAP DETAIL

N.T.S.

NOTE:

VERIFY TRAP DEPTH & THE DISTANCE BETWEEN THE TRAP OUTLET & DRAIN PAN

OUTLET WITH AHU MANUFACTURER'S INSTALLATION INSTRUCTIONS.

PIPE TO DRAIN

WHEN SHOWN ON

FLOOR PLANS.

TYPICAL ROOF RELIEF HOOD DETAIL

N.T.S.

TYPICAL ROOFTOP UNIT DETAIL

N.T.S.

SPUN ALUMINUM OR

FIBERGLASS HOUSING

ROOF OPENING PER

SELECTED FAN

MANUFACTURER'S

INSULATED

PRE-FABROOF

SOUND CURB

TYPICAL GAS PIPING CONNECTION

GAS-FIRED

EQUIPMENT

UNION (SHOWN)

OR FLANGED

CONNECTION

6'-0" MAXIMUM

PLUG

COCKS

N.T.S

ROOFTOP UNIT

SUPPLY

AIR

RETURN

AIR

VARIES - FIELD VERIFY

NOTE:

EXISTING ROOF CURB CONDITIONS TO BE

VERIFIED IN FIELD PRIOR TO CONSTRUCTION

4-1 4"

8" MIN.

NOTE: SWEEP BACK EXISTING GRAVEL.

CLEAN AND PREPARE ROOF FOR NEW WORK.

TYPICAL ROOF CURB CAP DETAIL

N.T.S

FAN MOTOR DRIVE AND

BEARING OUT OF AIR STREAM

GRAVITY

DAMPER

PROVIDE COUNTER

FLASHING

PREFABRICATED

SOUND CURB

ALUMINUM MESH

BIRD SCREEN

DISCONNECT SWITCH

FACTORY WIRED TO MOTOR

PIPE

INSULATION

12" SECTION

OF HEAVY

DENSITY

COVERING

EXISTING ROOF

CONSTRUCTION

EXISTING ROOF

STRUCTURE

CLEAN

OUT

INSULATED PRE-FAB

ROOF CURB WITH

WOOD NAILER

EXISTING ROOF

STRUCTURE

VENT

ROOF

BOOT/FLASHING

(FIELD SUPPLIED)

12" MINIMUM

CLEARANCE ABOVE

HEIGHT ANTICIPATED

SNOW LEVEL. MAXIMUM

OF 24" ABOVE ROOF.

ROOF

COMBUSTION

AIR

VENT

CAP

STRAP SUPPORT

(FIELD SUPPLIED)

EXHAUST

VENT

COMBUSTION

AIR

TYPICAL VENT TERMINATION DETAIL

N.T.S.

NOTE:

1. REFER TO MANUFACTURER'S MANUAL FOR

INSTALLATION INSTRUCTIONS.

MECHANICAL

DETAILS

M501

127th WING

BUILDING 1414

RENOVATION

http://www.AECOM.com

27777 Franklin Road, Suite 2000 Southfield, MI 48034 United States P: 248 204 5900 F: 248 204 5901

SPLIT HEAT PUMP - SCHEMATIC DETAIL

FINISHED FLOOR

NEW 6" CONCRETE

HOUSEKEEPING PAD

OUTDOOR UNIT

ACU-3,4

ROOF

CEILING

INTEGRATED SUPPLY

AND RETURN CEILING

GRILLES

NOTE:

1. PROVIDE AND INSTALL REFRIGERANT

PIPING AND ACCESSORIES PER THE

MANUFACTURER'S RECOMMENDATIONS.

FLEXIBLE

CONNECTION (TYP)

GRADE

INSTALL AS REQUIRED

PER MANUFACTURER'S

REQUIREMENTS

INDOOR UNIT

HP-3,4

ROUTE REFRIGERANT PIPING

INSIDE ROOM CONCEALED AS

POSSIBLE. FIELD VERIFY

STRUCTURAL STEEL

SEAL ALL PIPING

PENETRATIONS

RUN CONDENSATE LINE INSIDE ROOM

AND DRAIN OUTDOOR ON GRADE

HWHR

HOSE END DRAIN CONNECTION

AIRFLOW

HOT WATER

TEMPERING COIL

AUTOMATIC BALANCING

VALVE

HWHS

BALL VALVE

P/T

P/T NO

CNC

HOT WATER REHEAT COIL WITH THREE WAY CONTROL VALVE PIPING DETAIL

N.T.S.

MV

DRAIN

MAX. SPACING 4

PIPE DIA.

EX. AIR

SEPARATOR

EX.CHEMICAL

FEEDER

EX.3 4" BYPASS

3/4 " B

YP

AS

S

EX

.3 4"

BY

PA

SS

HIGH CAPACITY

AIR VENT

HIGH CAPACITY

AIR VENT

EX.3/4" CW

MAKEUP

EXPANSION

TANK

DRAIN

VALVE

NEW

ET-1

CP

EX.VAV

VAV

BP

1/2"

HWS

1/2"

HWR

2"

HWS

2"

HWR

EX.2" HWREX.2" HWS

EX.2" HWS

EX.2" HWS

2" HWS

EX. 2" HWS

FS

EX.1" HWREX.1" HWREX.3 4" HWR EX.3 4" HWR

EX. 1" HWS EX. 1" HWS EX.3 4" HWS EX.3 4" HWS

RHB

HEATING HOT WATER VAV REHEAT BOILER - PIPING SCHEMATIC

N.T.S.

EX. 2" HWS

EX.2" HWR

BACKFLOW

PREVENTER

S

BOILER SENSOR

PARALLEL HW INLINE CIRCULATING PUMPS DETAIL

N.T.S.

DRAIN

RHB

EX.

EX.

BP

CP

2" HWS & R

1/2" DRAIN VALVE

UNIONS

CALIBRATED

2-WAY CONTROL VALVE

HEATING RETURN

HEATING SUPPLY

MANUAL

AIR VENT

BALANCING VALVE

PETE'S PLUGS

(TYPICAL)

WITH HOSE CONNECTION

COIL AT VARIABLE

VOLUME BOX

(SEE PLANS)

SHUTOFF VALVE

(LINE SIZE)

NOTES:

1. ALL VALVES AND FITTINGS (EXCEPT CONTROL VALVES) SHALL BE

THE SAME SIZE AS PIPE UNLESS NOTED OTHERWISE.

2. CONTROL VALVE SHALL BE SIZED AND PROVIDED BY TEMPERATURE

CONTROL CONTRACTOR. FOR LINE SIZE, REFERENCE GPM, AS

PROVIDED BY THE SCHEDULE ON M600 DRAWING.

3. SHUTOFF VALVE TYPE PER SPECIFICATION.

4. COORDINATE BOX LOCATION WITH LIGHTING, SPRINKLER SYSTEMS,

DUCTS, PIPING, ETC, SO THAT SYSTEM IS COMPLETELY ACCESSIBLE

FOR SERVICE.

VARIABLE VOLUME BOX W/ HOT WATER REHEAT COIL PIPING DETAIL

N.T.S.

REDUCER (AS

NEEDLE VALVE

P

P

PRESSURE GAUGE

PUMP

SIDE VIEW

PUMP

REDUCER

PLAN VIEW

PUMP

REQ'D)

SUPPLY

RETURN

IF OPENING IN STRUCTURE IS

IRREGULAR AND GREATER THAN

1", WRAP DUCT WITH 1" THICK

FIBROUS MATERIAL AND FILL

REMAINING OPENING WITH GROUT.

IF OPENING LIMITED TO DESIRED

3/4" SPACE, PACK WITH FIBROUS

MATERIAL AND SEAL BOTH SIDES

WITH RESILIENT NON-HARDENING

SEALER.

PIPE SLEEVE OR

SHEET METAL SLEEVE.

3/4" SPACE, PACK WITH

FIBROUS MATERIAL ALL AROUND

BUILDING WALL

NON-HARDENING

RESILIENT SEALANT

BOTH SIDES.

DUCT (OR SILENCER)AS REQUIRED.

DUCT LINING

PIPE

IN ALL FINISHED AREAS.

CHROME PLATED ESCUTCHEON

LET THEM LOAD ONTO

SIDE OF WALL. DO NOT

AND DUCTS ON EITHER

NOTE: SUPPORT PIPES

THE WALL.

NOTE: FOR FIRE RATED WALLS

RATING, PROVIDE APPROVED SEALANT

SYSTEM EQUAL TO 3M OR FLAMESTOP.

REQUIRING ONE HOUR OR GREATER

TYPICAL WALL PENETRATIONS DETAIL (NON-FIRE-RATED WALLS)

N.T.S.

(MIN.) (MIN.)(TYP.)

AS REQUIRED (TYP.)

FIRE-PROOF WALL

"FIRESTOP" MATERIAL

CARRIER PIPE 6"

INSULATION SHALL

BE PROVIDED WITH

THE SAME PERFORMANCE

AS THE FIRESTOPPING

METALLIC PIPE

MATERIAL

6"

PIPE INSULATION

REQUIRED (TYP.)

COUPLING AS

METAL JACKET

TYPICAL FIRE-PROOF FRAMED WALL PENETRATION DETAIL

N.T.S.

FITTING

"S" TYPE SLIP

FIRE DAMPER

WALL SLEEVE

DUCTWORK

ANGLE

SLEEVE RETAINING

FIRE PARTITION

BOTTOM OF DUCT.

ACCESS DOOR IN

DAMPER.

FOR SERVICING

TYPICAL FIRE DAMPER DETAIL

N.T.S.

BUILDING WALL

EX.VAV

TO VAV

TO

MECHANICAL

DETAILS

M502

127th WING

BUILDING 1414

RENOVATION

http://www.AECOM.com

27777 Franklin Road, Suite 2000 Southfield, MI 48034 United States P: 248 204 5900 F: 248 204 5901

MECHANICAL

SCHEDULES

M600

127th WING

BUILDING 1414

RENOVATION

http://www.AECOM.com

27777 Franklin Road, Suite 2000 Southfield, MI 48034 United States P: 248 204 5900 F: 248 204 5901

ROOFTOP UNIT (RTU) SCHEDULE

MARK MODEL FAN & MOTOR COOLING HEATING PHYSICAL DATA ELECTRICAL REMARKS

SUPPLY AIR

(CFM)

OUTSIDE AIR

(CFM)

HEATING AIR

(CFM)

FAN

TYPE

NO.

FANS

ESP

(IN WC)

FAN SPEED

(RPM)

POWER

(BHP)

TYPE STAGES REFRIGERANT CAPACITY

(TOTAL/SENS. MBH)

MAT

(DB/WB °F)

LAT

(DB/WB °F)

EER/IEER TYPE SIZE STAGES EFF

INPUT

(MBH)

OUTPUT

(MBH)

MAT

(DB°F)

LAT

(DB °F)

LENGTH

(IN)

WIDTH

(IN)

HEIGHT

(IN)

WEIGHT

(LBS)

VOLT PHASE MCA MOP FLA

RTU-3

48LCS017B3M6-1E1

C0 4875 1650 3900 CENTR. 1 1.4 947 3.17 DX 3 R-410A 179.73/123.05 79.5/67.2 56.1/55.4 12.5/18.4 N. GAS LOW 2 81 220.0/176.0 178.0/142.0 35.0 68.8 141 86.4 58.5 2,562 460 3 44.9 50 48 1, 2, 3, 4

RTU-4

48LCS017B3M6-1E1

C0 4500 1300 3000 CENTR. 1 1.4 931 2.88 DX 3 R-410A 173.41/118.93 78.8/66.2 54.3/53.5 12.5/18.4 N. GAS LOW 2 81 220.0/176.0 178.0/142.0 34.2 70.8 141 86.4 58.5 2,562 460 3 44.9 50 48 1, 2, 3, 4

RTU-5

48LCS017B3M6-1E1

C0 5200 1300 3000 CENTR. 1 1.4 962 3.45 DX 3 R-410A 175.17/132.39 78.5/65.2 54.9/54.0 12.5/18.4 N. GAS LOW 2 81 220.0/176.0 178.0/142.0 34.2 65.9 141 86.4 58.5 2,562 460 3 44.9 50 48 1, 2, 3, 4

HEATING & VENTILATION UNIT (HV) SCHEDULE

MARK MODEL FAN & MOTOR HEATING PHYSICAL DATA ELECTRICAL REMARKS

SUPPLY AIR

(CFM)

OUTSIDE AIR

(CFM)

FAN

TYPE

NO.

FANS

ESP

(IN WC)

FAN SPEED

(RPM)

POWER

(BHP)

TYPE NO.

BURNERS

STAGES EFF

INPUT

(MBH)

OUTPUT

(MBH)

MAT

(DB°F)

LAT

(DB °F)

LENGTH

(IN)

WIDTH

(IN)

HEIGHT

(IN)

WEIGHT

(LBS)

VOLT PHASE MCA MOP FLA

HV-1 HDG600TMRLN71F3JY2AGA00 10000 1800 CENTR. 2 0.8 1118 12.05 N. GAS 2 2 80 600 480 54 89.8 182 44 43 1,861 460 3 18.9 25 19.1 1, 2, 3

HV-2 HDG300TMRLN71F2HT2AGA00 6000 600 CENTR. 2 0.8 984 4.24 N. GAS 1 2 80 300 240 60.2 90 114 44 43 1,264 460 3 6.8 15 7.1 1, 2, 3

NOTES:

1. MODEL NUMBERS: BASIS OF DESIGN CARRIER, OR APPROVED EQUAL.

2. PROVIDE WITH 16" INSULATED ROOF CURB, SINGLE POINT CONNECTION W/ NON-FUSED DISCONNECT, MERV 8 CARTRIDGE FILTERS, OUTSIDE AIR INTAKE HOOD, SINGLE ENTHALPY ECONOMIZER W/ BAROMETRIC RELIEF, UNPOWERED CONVENIENCE OUTLET, STAINLESS STEEL HEAT EXCHANGER, RETURN AIR SMOKE DETECTOR AND HAIL GUARD.

3. FACTORY PROVIDED CONTROLS SHALL BE DDC READY FOR USE ON EXISTING DISTRICT CONTROLS SYSTEM.X

4. HEATING CAPACITY CALCULATED AT -10°F OUTSIDE AIR TEMPERATURE.

NOTES:

1. MODEL NUMBERS ARE MODINE. ACCEPTABLE ALTERNATE: REZNOR.

2. PROVIDE WITH 16" INSULATED ROOF CURB, SINGLE POINT CONNECTION W/ NON-FUSED DISCONNECT, MERV 8 CARTRIDGE FILTERS, OUTSIDE AIR INTAKE HOOD, UNPOWERED CONVENIENCE OUTLET, STAINLESS STEEL HEAT EXCHANGER AND RETURN AIR SMOKE DETECTOR.

3. FACTORY PROVIDED CONTROLS SHALL BE DDC READY FOR USE ON EXISTING DISTRICT CONTROLS SYSTEM.

4. HEATING CAPACITY CALCULATED AT -10°F OUTSIDE AIR TEMPERATURE.

VARIABLE AIR VOLUME TERMINAL UNIT W/ REHEAT COIL SCHEDULE

MARK INLET SIZE

(IN DIA)

BASIS OF DESIGN COOLING AIRFLOW DATA HEATING DATA REMARKS

MANUFACTURER MODEL MAX AIRFLOW

(CFM)

MAX APD

(IN WC)

AIRFLOW

(CFM)

CAPACITY

(MBH)

FLOW

(GPM)

EWT

(°F)

LWT

(°F)

MAX WPD

(FT HD)

ROWS

VAV-25 12 PRICE SDV 1200 0.5 485 15.8 1.1 160 130 0.09 2 1,2

VAV-26 14 PRICE SDV 1600 0.41 800 26.0 1.7 160 130 0.1 2 1,2

VAV-27 10 PRICE SDV 750 0.58 290 9.4 0.6 160 130 0.06 2 1,2

VAV-28 12 PRICE SDV 1300 0.5 700 22.8 1.5 160 130 0.15 2 1

VAV-29 7 PRICE SDV 400 0.75 400 13.0 0.9 160 130 0.18 2 1

VAV-30 14 PRICE SDV 1600 0.41 800 26.0 1.7 160 130 0.1 2 1

VAV-31 10 PRICE SDV 800 0.58 400 13.0 0.9 160 130 0.1 2 1

VAV-32 14 PRICE SDV 1600 0.41 600 19.5 1.3 160 130 0.07 2 1

VAV-33 10 PRICE SDV 750 0.58 665 21.6 1.4 160 130 0.19 2 1

VAV-34 8 PRICE SDV 600 0.69 190 6.2 0.5 160 135 0.06 2 1,2

VAV-35 7 PRICE SDV 400 0.75 310 10.1 0.7 160 130 0.11 2 1

VAV-36 12 PRICE SDV 1200 0.5 375 12.2 0.8 160 130 0.06 2 1

VAV-37 10 PRICE SDV 750 0.58 400 13.0 0.9 160 130 0.1 2 1

VAV-38 6 PRICE SDV 195 0.32 80 2.6 0.5 160 150 0.04 2 1,2

VAV-39 12 PRICE SDV 950 0.5 285 9.3 0.6 160 130 0.06 2 1,2

VAV-40 12 PRICE SDV 1000 0.5 600 19.5 1.3 160 130 0.12 2 1

VAV-41 10 PRICE SDV 775 0.58 480 15.6 1.0 160 130 0.14 2 1

VAV-42 12 PRICE SDV 1080 0.5 1080 35.2 2.3 160 130 0.27 2 1,2

VAV-43 8 PRICE SDV 600 0.69 315 10.3 0.7 160 130 0.11 2 1,2

VAV-44 12 PRICE SDV 1200 0.5 730 23.8 1.6 160 130 0.15 2 1

NOTES:

1. MODEL NUMBERS ARE PRICE. ACCEPTABLE ALTERNATE: TITUS.

2. PROVIDE WITH 3-WAY CONTROL VALVE.

PUMP SCHEDULE

MARK LOCATION MODEL SERVICE FLOW

(GPM)

PRESSURE

(FT HD)

SPEED

(RPM)

IMPELLER DIA

(IN)

ELECTRICAL REMARKS

VOLT/

PHASE

MOTOR

(HP)

BRAKE

(HP)

CP-1 MECH RM E-80 1.5x1.5x9.5B VAV REHEAT 40 85 1800 9 480/3 5 1.85 1, 2, 3

CP-2 MECH RM E-80 1.5x1.5x9.5B VAV REHEAT 40 85 1800 9 480/3 5 1.85 1, 2, 3

NOTES:

1. MODEL NUMBERS ARE BELL & GOSSETT. ACCEPTABLE ALTERNATE: TACO, ARMSTRONG.

2. SEE HVAC PIPING DETAILS FOR INSTALLATION REQUIREMENTS.

3. PROVIDE WITH VARIABLE SPEED MOTOR AND DRIVE.

BOILER SCHEDULE

MARK LOCATION MODEL INPUT

(MBH)

OUTPUT

(MBH)

GPM MAX. PD

(FT)

VENT

(IN DIA)

INTAKE

(IN DIA)

HOT WATER

SUPPLY TEMP

(°F)

HOT WATER

RETURN TEMP

(°F)

REMARKS

RHB-2

MAIN MECH

RM KBN400 400 376 25 20 4 4 160 130 1, 2,3,4,5

NOTES:

1. MODEL NUMBERS: BASIS OF DESIGN LOCHINVAR KNIGHT SERIES, OR APPROVED EQUAL.

2. PROVIDE W/ BOILER CIRCULATION PUMP INTEGRAL TO BOILER (BP-2: GRUNDFOS 40-80 ECM, OR EQUAL), 120V/1PH, 2.5 AMPS, 0.37 HP. THREE WIRES TO PUMP: 120V, 0-10v FROM

BOILER TO PUMP AND ENABLE CONTACTS FROM BOILER TO PUMP.

3. PROVIDE CONDENSATE NEUTRALIZER.

4. PROVIDE WITH BOILER FLOW SWITCH.

5. PROVIDE WITH BACNET GATEAWAY FOR COMMUNICATION WITH BASE ALC NETWORK AND 3-WIRE CASCADE CONTROLLER.

6. NEW BOILER SHALL BE PROGRAMMED TO OPERATE IN LEAD-LAG OPERATION WITH EX. RHB-1.

SPLIT SYSTEM HEAT PUMP SCHEDULE

SERVICE OUTDOOR CONDENSING UNIT INDOOR UNIT REMARKS

MARK MODEL COOLING HEATING SOUND POWER

(DB)

WEIGHT

(LBS)

ELECTRICAL MARK MODEL TYPE AIRFLOW

(CFM)

WEIGHT

(LBS)

SOUND POWER

(DB)

DIMENSIONS

CAPACITY

(MBH)

AMBIENT

(°F)

SEER CAPACITY

(MBH)

HSPF COP VOLT PHASE MCA MOP LENGTH

(IN)

WIDTH

(IN)

HEIGHT

(IN)

OFFICE HP-3 38MHRQ12A 12 95 17 10.1 9 3.2 64 58 208 1 7 15 ACU-3 40MHHQ12 WALL 324 22 41 32 8 12 1, 2, 3 OFFICE HP-4 38MHRQ12A 12 95 17 10.1 9 3.2 64 58 208 1 7 15 ACU-4 40MHHQ12 WALL 324 22 41 32 8 12 1, 2, 3

NOTES:

1. MODEL NUMBERS: BASIS OF DESIGN CARRIER, OR APPROVED EQUAL.

2. PROVIDE WITH LOW AMBIENT KIT, CONDENSATE PUMP, THERMOSTAT, AND MANUFACTURER'S REFRIGERATION LINESET.

3. NOISE LEVELS AND AIRFLOW EXPRESSED AT "HIGH" FAN SETTING

4. PUMPED CONDENSATE OUTSIDE ON GRADE THOUGH OUTSIDE WALL. FIELD VERIFY FOR LOCATION.

EXPANSION TANK SCHEDULE

MARK LOCATION MODEL SERVICE TANK VOLUME

(GAL)

INITIAL FILL PRESSURE

(PSI)

TANK DIAMETER

(IN)

TANK HEIGHT

(IN)

REMARKS

ET-1 MAIN MECH

ROOM

85LBC HOT WATER REHEAT 22 12 16 35 1,2

NOTES:

1. MODEL NUMBER: BASIS OF DESIGN AMTROL. ACCEPTABLE ALTERNATE: WESSLES, ARMSTRONG, FLEXCON, BELL & GOSSETT.

ROOF EXHAUST FAN SCHEDULE

UNIT DATA PERFORMANC DATA MOTOR DATA

MARK LOCATION MODEL FAN TYPE FLOW (CFM) ESP (IN. WG) DRIVE TYPE SOUND RATING

(SONES)

HP BHP VOLTS PHASE WEIGHT (LBS) REMARKS

EF-2 ROOF G-098 CENTRIFUGAL 280 0.5 DIRECT 5.5 1/6 0.05 115 1 54 1,2,3,4

EF-3 ROOF G-098 CENTRIFUGAL 400 0.5 DIRECT 7 1/6 0.12 115 1 54 1,2,3,5

DIFFUSER, REGISTER, GRILLE SCHEDULE

MARK TYPE MODEL CFM RANGE NECK SIZE FACE SIZE CEILING

MODULE SIZE

VOLUME CONTROL

DAMPER

FINISH REMARKS

SD-1 SUPPLY

CEILING

SCD 201 - 250 8" RD 22x22 24x24 NO WHITE 1

SD-1 SUPPLY

CEILING

SCD 251 - 400 10" RD 22x22 24x24 NO WHITE 1

SD-1 SUPPLY

CEILING

SCD 401 - 550 12" RD 22x22 24x24 NO WHITE 1

RD-1 RETURN

CEILING

80SR 150 - 800 6" RD-16" RD 23-¾ x 23-¾ 24x24 NO WHITE 1,2

SG-1 SUPPLY WALL 510/L 250 12x6 12x6 NO WHITE 1

REMARKS:

1. MODEL NUMBER: BASIS OF DESIGN GREENHECK. ACCEPTABLE ALTERNATE: LOREN COOK, , PENN BERRY, OR EQUAL.

2. PROVIDE WITH MATCHING ROOF CURB, BACKDRAFT DAMPER AND BIRD SCREEN.

3. PROVIDE WITH UNIT -MOUNTED DISCONNECT.

4. INTERLOCK WITH RTU-4 OPERATION.

5. INTERLOCK WITH RTU-5 OPERATION.

REMARKS:

1. MODEL NUMBER: BASED ON PRICE. ACCEPTABLE ALTERNATE: TITUS, KRUEGER, OR EQUAL.

2. PROVIDE WITH INTEGRATED PLENUM TO ROUND NECK CONNECTION.

HOOD DIMENSIONS

RELIEF AIR HOOD

MARK LOCATION SERVICE CFM

WIDTH HEIGHTLENGTH

THROAT

DIMENSIONS

REMARKS

RH-1 WAREHOUSE HV-2 993 30" 39" 16" 16"x16" 1, 2

NOTES:

1. MODEL NUMBERS ARE GREENHECK, OR ACCEPTABLE EQUAL.

2. PROVIDE WITH 22"x22" PREFABRICATED ROOF CURB.

MECHANICAL

CONTROLS -

M701

SCHEMATIC

DIAGRAMS

127th WING

BUILDING 1414

RENOVATION

http://www.AECOM.com

27777 Franklin Road, Suite 2000 Southfield, MI 48034 United States P: 248 204 5900 F: 248 204 5901

AO - OUTSIDE AIR

DAMPER AT FURNACE

AI - DISCHARGE AIR TEMP

RA

N.C.

OA

BI - FAN STATUS

BO - FAN START/STOP

BO - COOLING STAGES

DX

GAS

BO - HEATING STAGES

DA

BI - ZONE OVERRIDE

AI - ZONE TEMP

AI - ZONE SETPOINT ADJUST

RTU-3, 4 & 5 - SEQUENCE OF OPERATION:

RUN CONDITIONS - OCCUPANCY SCHEDULE:

THE UNIT SHALL RUN ACCORDING TO A USER DEFINABLE OCCUPANCY SCHEDULE IN THE FOLLOWING MODES:

OCCUPIED MODE:

THE UNIT SHALL MAINTAIN:

• A 76°F (ADJ.) COOLING SETPOINT

• A 68°F (ADJ.) HEATING SETPOINT.

UNOCCUPIED MODE (NIGHT SETBACK):

THE UNIT SHALL MAINTAIN:

• A 85°F (ADJ.) COOLING SETPOINT.

• A 55°F (ADJ.) HEATING SETPOINT.

OCCUPANCY SCHEDULE FOR DAILY WORKING HOURS, WEEKENDS AND HOLIDAYS SHALL BE CLOSELY COORDINATED WITH BUILDING OWNER TO DEFINE AND PROGRAM DDC CONTROLS AND HVAC SYSTEMS OPERATION ACCORDINGLY.

ZONE TEMPERATURE ALARMS:

ALARMS SHALL BE PROVIDED AS FOLLOWS:

• HIGH ZONE TEMP: IF THE ZONE TEMPERATURE IS GREATER THAN THE COOLING SETPOINT BY A USER DEFINABLE

AMOUNT (ADJ.).

• LOW ZONE TEMP: IF THE ZONE TEMPERATURE IS LESS THAN THE HEATING SETPOINT BY A USER DEFINABLE

AMOUNT (ADJ.).

ZONE SETPOINT ADJUST:

THE OCCUPANT SHALL BE ABLE TO ADJUST THE ZONE TEMPERATURE HEATING AND COOLING SETPOINTS AT THE

ZONE SENSOR.

ZONE OPTIMAL START:

THE UNIT SHALL USE AN OPTIMAL START ALGORITHM FOR MORNING START-UP. THIS ALGORITHM SHALL MINIMIZE THE UNOCCUPIED WARM-UP OR COOL-DOWN PERIOD WHILE STILL ACHIEVING COMFORT CONDITIONS BY THE START OF

SCHEDULED OCCUPIED PERIOD.

ZONE UNOCCUPIED OVERRIDE:

A TIMED LOCAL OVERRIDE CONTROL SHALL ALLOW AN OCCUPANT TO OVERRIDE THE SCHEDULE AND PLACE THE UNIT INTO AN OCCUPIED MODE FOR AN ADJUSTABLE PERIOD OF TIME. AT THE EXPIRATION OF THIS TIME, CONTROL

OF THE UNIT SHALL AUTOMATICALLY RETURN TO THE SCHEDULE.

FAN:

THE FAN SHALL RUN ANYTIME THE FURNACE IS COMMANDED TO RUN, UNLESS SHUTDOWN ON SAFETIES. THE FAN SHALL RUN CONTINUOUSLY DURING OCCUPIED MODE OF OPERATION. DURING UNOCCUPIED MODE OF OPERATION, THE FAN SHALL CYCLE AUTOMATICALLY WITH THE FURNACE TO MAINTAIN THE NIGHT SETBACK TEMPERATURE

SETPOINTS DURING UNOCCUPIED MODE OF OPERATION.

COOLING STAGE:

THE CONTROLLER SHALL MEASURE THE ZONE TEMPERATURE AND STAGE THE COOLING TO MAINTAIN ITS COOLING SETPOINT. TO PREVENT SHORT CYCLING, THE STAGE SHALL HAVE A USER DEFINABLE (ADJ.) MINIMUM RUNTIME.

THE COOLING SHALL BE ENABLED WHENEVER:

• OUTSIDE AIR TEMPERATURE IS GREATER THAN 60°F (ADJ.).

• AND THE ZONE TEMPERATURE IS ABOVE COOLING SETPOINT.

• AND THE FAN IS ON.

GAS HEATING STAGE:

THE CONTROLLER SHALL MEASURE THE ZONE TEMPERATURE AND STAGE THE HEATING TO MAINTAIN ITS HEATING SETPOINT. TO PREVENT SHORT CYCLING, THE STAGE SHALL HAVE A USER DEFINABLE (ADJ.) MINIMUM RUNTIME.

THE HEATING SHALL BE ENABLED WHENEVER:

• OUTSIDE AIR TEMPERATURE IS LESS THAN 65°F (ADJ.).

• AND THE ZONE TEMPERATURE IS BELOW HEATING SETPOINT.

• AND THE FAN IS ON.

MINIMUM OUTSIDE AIR VENTILATION - FIXED PERCENTAGE:

THE MAIN AND FURNACE OUTSIDE AIR DAMPERS SHALL BE OPEN DURING BUILDING OCCUPIED HOURS AND CLOSED

DURING UNOCCUPIED HOURS OR EMERGENCY SHUTDOWN.

DISCHARGE AIR TEMPERATURE:

THE CONTROLLER SHALL MONITOR THE DISCHARGE AIR TEMPERATURE.

ALARMS SHALL BE PROVIDED AS FOLLOWS:

• HIGH DISCHARGE AIR TEMP: IF THE DISCHARGE AIR TEMPERATURE IS GREATER THAN 120°F (ADJ.).

• LOW DISCHARGE AIR TEMP: IF THE DISCHARGE AIR TEMPERATURE IS LESS THAN 40°F (ADJ.).

FAN STATUS:

THE CONTROLLER…