R0008.pdf
PDF 2 MB Posted
- Attached to
- Tactical Response Force Alert Facility at Malmstrom AFB, MT Federal contract opportunity
- Solicitation number
- W912DW18R0002
About this file
Amendment R0008. The purpose of this amendment is to revise 5 drawings, Attachment 00 73 00-A and 4 sections.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Attachment_1_for_Section_00_22_16_Revised.docx | DOCX document | |
| R0007.pdf | ||
| R0006.pdf | ||
| R0005.pdf | ||
| R0004.pdf | ||
| R0003.pdf | ||
| R0002.pdf | ||
| R0001.pdf | ||
| Attachment_1_for_Section_00_22_16.docx | DOCX document | |
| Part_3_of_3_Drawings.pdf | ||
| Part_2_of_3_Specifications.pdf | ||
| Part_1_of_3_Request_for_Proposal.PDF |
Show all 12
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
W68MD970805559
AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT
Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.
15A. NAME AND TITLE OF SIGNER (Type or print)
30-105-04EXCEPTION TO SF 30
APPROVED BY OIRM 11-84
STANDARD FORM 30 (Rev. 10-83) Prescribed by GSA
FAR (48 CFR) 53.243
Request for Proposal (RFP) W912DW18R0002 Amendment R0008
(Please see continuation page for details)
1. CONTRACT ID CODE PAGE OF PAGES
J 1 2
16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)
16C. DATE SIGNED
BY 26-Apr-2018
16B. UNITED STATES OF AMERICA15C. DATE SIGNED15B. CONTRACTOR/OFFEROR
(Signature of Contracting Officer)(Signature of person authorized to sign)
8. NAME AND ADDRESS OF CONTRACTOR (No., Street, County, State and Zip Code) X W912DW18R0002
X 9B. DATED (SEE ITEM 11)
23-Mar-2018
10B. DATED (SEE ITEM 13)
9A. AMENDMENT OF SOLICITATION NO.
11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS
X The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offer is extended, X is not extended.
Offer must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended by one of the following methods:
(a) By completing Items 8 and 15, and returning copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted;
or (c) By separate letter or telegram which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN
REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by telegram or letter, provided each telegram or letter makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.
12. ACCOUNTING AND APPROPRIATION DATA (If required)
13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS.
IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.
A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE
CONTRACT ORDER NO. IN ITEM 10A.
B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, appropriation date, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(B).
C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:
D. OTHER (Specify type of modification and authority)
E. IMPORTANT: Contractor is not, is required to sign this document and return copies to the issuing office.
14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)
10A. MOD. OF CONTRACT/ORDER NO.
2. AMENDMENT/MODIFICATION NO. 5. PROJECT NO.(If applicable)
6. ISSUED BY
3. EFFECTIVE DATE
26-Apr-2018
CODE
USA ENGINEER DISTRICT, SEATTLE
ATTN: CENWS-CT
4735 EAST MARGINAL WAY SOUTH, BLDG. 1202
SEATTLE WA 98134-2388
W912DW 7. ADMINISTERED BY (If other than item 6)
4. REQUISITION/PURCHASE REQ. NO.
CODE
See Item 6
FACILITY CODECODE
EMAIL:TEL:
W912DW18R0002
SECTION SF 30 BLOCK 14 CONTINUATION PAGE
SUMMARY OF CHANGES
The following have been added by full text: R0008
1. This amendment eight (0008) provides for the following:
Section 08 33 23, Overhead Coiling Doors (Revised) Section 26 20 00, Interior Distribution System (Revised) Section 28 31 76, Interior Fire Alarm and Mass Notification System (Revised) Section 31 63 29, Drilled Concrete Piers and Shafts (Revised) Attachment 00 73 00-A, Index of Drawings (Revised) Drawing A-400, Enlarged Plans and Sections (Revised) Drawing A-411, Interior Elevations (Revised) Drawing A-601, Colors and Materials Schedule (Revised) Drawing A-605, Room Finish Schedules (Revised) Drawing G-004, Life Safety Plan – First Floor (Revised)
2. The bid submittal time and date of 1:00:00 PM LOCAL TIME, 30 April 2018 remains the same.
3. The attached revised sections are to be replaced in their entirety. Specifications changes are generally identified, for convenience, either by strikeout for deletions, and double underlining of text for additions or a single dark line in the margin. All portions of the revised sections shall apply whether or not changes have been indicated.
4. NOTICE TO OFFERORS: Offerors must acknowledge receipt of all amendments including this amendment by number and date on SF1442.
Encl:
Section 08 33 23 (Revised) Section 26 20 00 (Revised) Section 28 31 76 (Revised) Section 31 63 29 (Revised) Attachment 00 73 00-A (Revised) Drawing A-400 (Revised) Drawing A-411 (Revised) Drawing A-601 (Revised) Drawing A-605 (Revised) Drawing G-004 (Revised)
(End of Summary of Changes)
MAFB Tactical Response Force Alert Facility 16031 Malmstrom AFB, Great Falls, MT W912DW18R0002
SECTION TABLE OF CONTENTS
DIVISION 08 - OPENINGS
SECTION 08 33 23
OVERHEAD COILING DOORS
08/15
PART 1 GENERAL
1.1 REFERENCES
1.2 SUBMITTALS
1.3 DELIVERY, STORAGE, AND HANDLING
PART 2 PRODUCTS
2.1 SYSTEM DESCRIPTION
2.1.1 Design Requirements
2.1.1.1 Overhead Coiling Door Detail Shop Drawings
2.1.2 Performance Requirements
2.1.2.1 Wind Loading
2.1.2.2 Air Infiltration
2.1.2.3 Operational Cycle Life
2.2 COMPONENTS
2.2.1 Overhead Coiling Doors
2.2.1.1 Curtain Materials and Construction
2.2.1.2 Insulated Curtains
2.2.1.3 Curtain Bottom Bar
2.2.1.4 Locks
2.2.1.5 Weather Stripping
2.2.1.6 Locking Devices
2.2.1.7 Safety Interlock
2.2.1.8 Overhead Drum
2.2.1.9 Slats
2.2.2 Hardware
2.2.2.1 Guides
2.2.2.2 Equipment Supports
2.2.2.3 Hood
2.2.3 Counterbalancing Mechanism
2.2.3.1 Brackets
2.2.3.2 Counterbalance Barrels
2.2.4 Manual Door Operators
2.2.4.1 Manual Chain-Hoist Door Operators
2.2.5 Electric Door Operators
2.2.5.1 Door-Operator Types
2.2.5.2 Electric Motors
2.2.5.3 Motor Bearings
2.2.5.4 Motor Starters, Controls, and Enclosures
2.2.5.5 Control Enclosures
2.2.5.6 Transformer
2.2.5.7 Remote-Control Stations
2.2.5.8 Speed-Reduction Units
2.2.5.9 Chain Drives
2.2.5.10 Brakes
SECTION 08 33 23 Page 1 R0008
2.2.5.11 Clutches
2.2.5.12 Weather/Smoke Seal Sensing Edge
2.2.6 Surface Finishing
PART 3 EXECUTION
3.1 INSTALLATION
3.1.1 Field Painted Finish
3.2 ADJUSTING AND CLEANING
3.2.1 Acceptance Provisions
3.2.1.1 Maintenance and Adjustment
3.3 CLOSEOUT ACTIVITIES
3.3.1 Warranty
3.3.2 Operation And Maintenance
-- End of Section Table of Contents --
SECTION 08 33 23 Page 2
SECTION 08 33 23
OVERHEAD COILING DOORS
08/15
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
AMERICAN SOCIETY OF CIVIL ENGINEERS (ASCE)
ASCE 7 (2010; Errata 2011; Supp 1 2013) Minimum Design Loads for Buildings and Other Structures
AMERICAN SOCIETY OF HEATING, REFRIGERATING AND AIR-CONDITIONING
ENGINEERS (ASHRAE)
ASHRAE FUN IP (2013; Addenda and Corrigendum 2013) Fundamentals Handbook, I-P Edition
ASME INTERNATIONAL (ASME)
ASME B29.400 (2001; R 2013) Combination, "H" Type Mill Chains, and Sprockets
ASTM INTERNATIONAL (ASTM)
ASTM A153/A153M (2016) Standard Specification for Zinc Coating (Hot-Dip) on Iron and Steel Hardware
ASTM A27/A27M (2013) Standard Specification for Steel Castings, Carbon, for General Application
ASTM A307 (2014) Standard Specification for Carbon Steel Bolts and Studs, 60 000 PSI Tensile Strength
ASTM A36/A36M (2014) Standard Specification for Carbon Structural Steel
ASTM A48/A48M (2003; R 2012) Standard Specification for Gray Iron Castings
ASTM A53/A53M (2012) Standard Specification for Pipe, Steel, Black and Hot-Dipped, Zinc-Coated, Welded and Seamless
ASTM A653/A653M (2015; E 2016) Standard Specification for Steel Sheet, Zinc-Coated (Galvanized) or Zinc-Iron Alloy-Coated (Galvannealed) by the Hot-Dip Process
SECTION 08 33 23 Page 3
ASTM A666 (2015) Standard Specification for Annealed or Cold-Worked Austenitic Stainless Steel Sheet, Strip, Plate and Flat Bar
ASTM A780/A780M (2009; R 2015) Standard Practice for Repair of Damaged and Uncoated Areas of Hot-Dip Galvanized Coatings
ASTM A924/A924M (2016) Standard Specification for General Requirements for Steel Sheet, Metallic-Coated by the Hot-Dip Process
ASTM B221 (2014) Standard Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Profiles, and Tubes
ASTM D2000 (2012) Standard Classification System for Rubber Products in Automotive Applications
ASTM E283 (2004; R 2012) Determining the Rate of Air Leakage Through Exterior Windows, Curtain Walls, and Doors Under Specified Pressure Differences Across the Specimen
ASTM E330/E330M (2014) Structural Performance of Exterior Windows, Doors, Skylights and Curtain Walls by Uniform Static Air Pressure Difference
ASTM E84 (2016) Standard Test Method for Surface Burning Characteristics of Building Materials
ASTM F568M (2007) Standard Specification for Carbon and Alloy Steel Externally Threaded Metric Fasteners
NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA)
NEMA ICS 2 (2000; R 2005; Errata 2008) Standard for Controllers, Contactors, and Overload Relays Rated 600 V
NEMA ICS 6 (1993; R 2011) Enclosures
NEMA MG 1 (2016) Motors and Generators
NEMA ST 1 (1988; R 1994; R 1997) Specialty Transformers (Except General Purpose Type)
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA 70 (2014) National Electrical Code
1.2 SUBMITTALS
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are for information only. When
SECTION 08 33 23 Page 4 used, a designation following the "G" designation identifies the office that will review the submittal for the Government. Submittals with an "S" are for inclusion in the Sustainability Notebook, in conformance to Section 01 33 29 SUSTAINABILITY REPORTING. Submit the following in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:
SD-02 Shop Drawings
Overhead Coiling Doors; G Electric Door Operators; G Hood; G Installation Drawings; G
SD-03 Product Data
Overhead Coiling Doors; G Hardware; G Electric Door Operators; G
SD-05 Design Data
Overhead Coiling Doors; G Hardware; G Electric Door Operators; G
SD-10 Operation and Maintenance Data
Operation and Maintenance Manuals Manufacture's Brochures
SD-11 Closeout Submittals
Warranty; G
1.3 DELIVERY, STORAGE, AND HANDLING
Deliver doors to the jobsite wrapped in a protective covering with the brands and names clearly marked thereon. Store doors in an adequately ventilated dry location that is free from dirt and dust, water, or other contaminants. Store in a manner that permits easy access for inspection and handling.
PART 2 PRODUCTS
2.1 SYSTEM DESCRIPTION
Doors to be coiling type, with interlocking slats, complete with anchoring and door hardware, guides, hood, and operating mechanisms, and designed for use on openings as indicated. Use grease-sealed or self-lubricating bearings for rotating members.
2.1.1 Design Requirements
2.1.1.1 Overhead Coiling Door Detail Shop Drawings
Provide installation drawings for overhead coiling door assemblies which show: elevations of each door type, shape and thickness of materials, finishes, details of joints and connections, details of guides and fittings, rough opening dimensions, location and description of hardware, SECTION 08 33 23 Page 5 anchorage locations, and counterbalancing mechanism and door operator details. Show locations of replaceable fusible links on wiring diagrams for power, signal and controls. Include a schedule showing the location of each door with the drawings.
2.1.2 Performance Requirements
2.1.2.1 Wind Loading
Design and fabricate door assembly to withstand the wind loading pressure of at least 45 pounds per square foot with a maximum deflection of 1/120 of the opening width. Provide test data showing compliance with ASTM E330/E330M. Sound engineering principles may be used to interpolate or extrapolate test results to door sizes not specifically tested. Ensure complete assembly meets or exceeds the requirements of ASCE 7.
2.1.2.2 Air Infiltration
Provide a maximum air leakage rating of 1.0 cfm/sf when tested in accordance with ASTM E283 at a pressure of 1.57 psf.
2.1.2.3 Operational Cycle Life
Design all portions of the door, hardware and operating mechanism that are subject to movement, wear, or stress fatigue to operate through a minimum number of 10 cycles per day. One complete cycle of door operation is defined as when the door is in the closed position, moves to the fully open position, and returns to the closed position.
2.2 COMPONENTS
2.2.1 Overhead Coiling Doors
2.2.1.1 Curtain Materials and Construction
Provide curtain slats fabricated from Grade A steel sheets conforming to ASTM A653/A653M, with the additional requirement of a minimum yield point of 33,000 psi. Provide sheets, galvanized in accordance with ASTM A653/A653M and ASTM A924/A924M.
Fabricate doors from interlocking cold-rolled slats, with section profiles as specified, designed to withstand the specified wind loading. Ensure the provided slats are continuous without splices for the width of the door.
Provide slats filled with manufacturer's standard thermal insulation complying with maximum flame-spread and smoke-developed indexes of 75 and 450, respectively, according to ASTM E84. Enclose insulation completely within slat faces on interior surface of slats.
2.2.1.2 Insulated Curtains
Form Curtains from manufacturer's standard shapes of interlocking slats.
Maximum assembly U-value shall be 0.84. Supply slat system with a minimum R-value of 8 when calculated in accordance with ASHRAE FUN IP. Slats to consist of a urethane core not less than 7/8-inch thick, completely enclosed within metal facings. Ensure the exterior face of slats are the same gauge as specified for curtains. Select an interior face not lighter than 0.0276-inches. The insulated slat assembly requires a flame spread rating of not more than 25 and a smoke development factor of not more than
SECTION 08 33 23 Page 6
50 when tested in accordance with ASTM E84.
2.2.1.3 Curtain Bottom Bar
Install curtain bottom bars as pairs of angles from the manufacturer's standard steel, stainless and aluminum extrusions not less than 2.0 by 2.0-inches by 0.188-inch. Ensure steel extrusions conform to ASTM A36/A36M.
Stainless steel extrusions conforming to ASTM A666, Type 304. Aluminum extrusions conforming to ASTM B221. Galvanize angles and fasteners in accordance with ASTM A653/A653M and ASTM A924/A924M. Coat welds and abrasions with paint conforming to ASTM A780/A780M.
2.2.1.4 Locks
Provide end and/or wind locks of Grade B cast steel conforming to ASTM A27/A27M, galvanized in accordance with ASTM A653/A653M, ASTM A153/A153M and ASTM A924/A924M. Secure locks at every other curtain slat.
2.2.1.5 Weather Stripping
Ensure weather-stripping at the door-head and jamb is 1/8-inch thick sheet of natural or neoprene rubber with air baffles. Secure weather stripping to the insides of hoods with galvanized-steel fasteners through continuous galvanized-steel pressure bars at least 5/8-inch wide and 1/8-inch thick.
Ensure threshold weather-stripping is 1/8-inch thick sheet natural or neoprene rubber secured to the bottom bars.
Provide weather-stripping of natural or neoprene rubber conforming to
ASTM D2000.
2.2.1.6 Locking Devices
Ensure slide bolt engages through slots in tracks for locking by padlock, located on both left and right jamb sides, operable from coil side.
2.2.1.7 Safety Interlock
Equip power-operated doors with safety interlock switch to disengage power supply when door is locked.
2.2.1.8 Overhead Drum
Fabricate drums from nominal 0.028-inch thick, hot-dip galvanized steel sheet with G90 (Z275) zinc coating, complying with ASTM A653/A653M.
2.2.1.9 Slats
No. 5F, 18 gauge, Grade 40 steel, ASTM A653/A653M galvanized steel zinc coating.
2.2.2 Hardware
Ensure all hardware conforms to ASTM A153/A153M, ASTM A307, ASTM F568M, and
ASTM A27/A27M.
SECTION 08 33 23 Page 7
2.2.2.1 Guides
Fabricate curtain jamb guides from the manufacturer's standard angles or channels of same material and finish as curtain slats unless otherwise indicated. Provide guides with sufficient depth and strength to retain curtain, and to withstand loading. Ensure curtain operates smoothly. Slot bolt holes for track adjustment.
2.2.2.2 Equipment Supports
Fabricate door-operating equipment supports from the manufacturer's standard steel shapes and plates conforming to ASTM A36/A36M, galvanized in accordance with ASTM A653/A653M and ASTM A924/A924M. Size the shapes and plates in accordance with the industry standards for the size, weight, and type of door installation.
2.2.2.3 Hood
Provide a hood with a minimum 24-gauge galvanized sheet metal, flanged at top for attachment to header and flanged at bottom to provide longitudinal stiffness. The hood encloses the curtain coil and counterbalance mechanism.
Provide a 24-gauge galvanized steel hood with reinforced top and bottom edges. Provide minimum 1/4-inch steel intermediate support brackets as required to prevent excessive sag.
2.2.3 Counterbalancing Mechanism
Counterbalance doors by means of manufacturer's standard mechanism with an adjustable-tension, steel helical torsion spring mounted, around a steel shaft and contained in a spring barrel connected to top of curtain with barrel rings. Use grease-sealed or self-lubricating bearings for rotating members.
2.2.3.1 Brackets
Provide the manufacturer's standard mounting brackets with one located at each end of the counterbalance barrel conforming to ASTM A48/A48M. Provide brackets of either cast iron or cold-rolled steel.
2.2.3.2 Counterbalance Barrels
Fabricate spring barrel of manufacturer's standard hot-formed, structural-quality, welded or seamless carbon-steel pipe, conforming to ASTM A53/A53M. Ensure the barrel is of sufficient diameter and wall thickness to support rolled-up curtain without distortion of slats. Limit barrel deflection to not more than 0.03 inch per foot of span under full load.
a. Barrel: Provide steel pipe capable of supporting curtain load with maximum deflection of 0.03 inches per foot of width.
b. Spring Balance: Provide an oil-tempered, heat-treated steel helical torsion spring assembly designed for proper balance of door. Ensure that effort to operate manually operated units does not exceed 25 lbs.
Provide wheel for applying and adjusting spring torque.
SECTION 08 33 23 Page 8
2.2.4 Manual Door Operators
2.2.4.1 Manual Chain-Hoist Door Operators
Provide door operators which consist of an endless steel hand chain, chain-pocket wheel, guard, and a geared reduction unit of at least a 3 to 1 ratio with a maximum lifting force of 30 lbf. Required pull for operation cannot exceed 35 pounds. Provide for doors indicated.
Provide chain hoists with a self-locking mechanism allowing the curtain to be stopped at any point in its upward or downward travel and to remain in that position until moved to the fully open or closed position. Provide hand chains of cadmium-plated alloy steel conforming to ASME B29.400.
Ensure yield point of the chain is at least three times the required hand-chain pull.
Provide chain sprocket wheels of cast iron conforming to ASTM A48/A48M.
2.2.5 Electric Door Operators
Provide for doors indicated. Provide electrical wiring and door operating controls conforming to the applicable requirements of NFPA 70.
Electric door-operator assemblies needs to be the sizes and capacities recommended and provided by the door manufacturer for specified doors.
Furnish complete assemblies with electric motors and factory-prewired motor controls, starter, gear reduction units, solenoid-operated brakes, clutch, remote-control stations, manual or automatic control devices, and accessories as required for proper operation of the doors.
Design the operators so that motors may be removed without disturbing the limit-switch adjustment and affecting the emergency auxiliary operators.
Provide a manual operator of chain-gear mechanism with a release clutch to permit manual operation of doors in case of power failure. Arrange the emergency manual operator so that it may be put into and out of operation from floor level, and its use does not affect the adjustment of the limit switches. Provide an electrical or mechanical device that automatically disconnects the motor from the operating mechanism when the emergency manual operating mechanism is engaged.
2.2.5.1 Door-Operator Types
Provide an operator mounted to the right or left door head plate with the operator on coil side of the door-hood assembly and connected to the door drive shaft with drive chain and sprockets. Front clearance is required for this type of mounting.
2.2.5.2 Electric Motors
Provide motors which are the high-starting-torque, reversible, constant-duty electrical type with overload protection of sufficient torque and horsepower to move the door in either direction from any position.
Ensure they produce a door-travel speed of not less than 8 nor more than 12 inches per second without exceeding the horsepower rating.
Provide motors which conform to NEMA MG 1 designation, temperature rating, service factor, enclosure type, and efficiency to the requirements specified.
SECTION 08 33 23 Page 9
2.2.5.3 Motor Bearings
Select bearings with bronze-sleeve or heavy-duty ball or roller antifriction type with full provisions for the type of thrust imposed by the specific duty load.
Pre-lubricate and factory seal bearings in motors less than 1/2 horsepower.
Equip motors coupled to worm-gear reduction units with either ball or roller bearings.
Equip bearings in motors 1/2 horsepower or larger with lubrication service fittings. Fit lubrication fittings with color-coded plastic or metal dust caps.
In any motor, bearings that are lubricated at the factory for extended duty periods do not need to be lubricated for a given number of operating hours. Display this information on an appropriate tag or label on the motor with instructions for lubrication cycle maintenance.
2.2.5.4 Motor Starters, Controls, and Enclosures
Provide each door motor with: a factory-wired, unfused, disconnect switch;
a reversing, across-the-line magnetic starter with thermal overload protection; 120-volt operating coils with a control transformer limit switch; and a safety interlock assembled in a NEMA ICS 6 type enclosure as specified herein. Ensure control equipment conforms to NEMA ICS 2.
Provide adjustable switches, electrically interlocked with the motor controls and set to stop the door automatically at the fully open and fully closed position.
2.2.5.5 Control Enclosures
Provide control enclosures that conform to NEMA ICS 6 for general purpose NEMA Type 1.
2.2.5.6 Transformer
Provide starters with 230/460 to 115 volt control transformers with one secondary fuse when required to reduce the voltage on control circuits to 120 volts or less. Provide a transformer conforming to NEMA ST 1.
2.2.5.7 Safety-Edge Device
Provide each door with a pneumatic safety device extending the full width of the door and located within a U-section neoprene or rubber astragal, mounted on the bottom rail of the bottom door section. Device needs to immediately stop and reverse the door upon contact with an obstruction in the door opening during downward travel and cause the door to return to full-open position. A safety device is not a substitute for a limit switch.
Connect safety device to the control circuit through a retracting safety cord and reel.
2.2.5.7 Remote-Control Stations
Provide interior remote control stations which are full-guarded, SECTION 08 33 23 Page 10 R0008
G3ENDRDN
Rectangle momentary-contact three-button, heavy-duty, surface-mounted NEMA ICS 6 type enclosures as specified. Mark buttons "OPEN," "CLOSE," and "STOP." Ensure the "CLOSE" button requires a constant pressure to maintain the closing motion of the door. When the door is in motion and the "STOP" button is pressed, ensure the door stops instantly and remains in the stopped position. From the stopped position, the door may then be operated in either direction. Provide control stations at the doors and at a remote location within the building as indicated. The controls shall have a timer capability to allow automatic closing of the doors after a set interval.
2.2.5.8 Speed-Reduction Units
Provide speed-reduction units consisting of hardened-steel worm and bronze worm gear assemblies running in oil or grease and inside a sealed casing, coupled to the motor through a flexible coupling. Drive shafts need to rotate on ball- or roller-bearing assemblies that are integral with the unit.
Provide minimum ratings of speed reduction units in accordance with AGMA provisions for class of service.
Ground worm gears to provide accurate thread form; machine teeth for all other types of gearing. Surface harden all gears.
Provide antifriction type bearings equipped with oil seals.
2.2.5.9 Chain Drives
Provide roller chains that are a power-transmission series steel roller type conforming to ASME B29.400, with a minimum safety factor of 10 times the design load.
Heat-treat or otherwise harden roller-chain side bars, rollers, pins, and bushings.
Provide high-carbon steel chain sprockets with machine-cut hardened teeth, finished bore and keyseat, and hollow-head setscrews.
2.2.5.10 Brakes
Provide 360-degree shoe brakes or shoe and drum brakes. Ensure the brakes are solenoid-operated and electrically interlocked to the control circuit to set automatically when power is interrupted.
2.2.5.11 Clutches
Ensure clutches are either the 4-inch diameter, multiple face, externally adjustable friction type or adjustable centrifugal type.
2.2.5.12 Weather/Smoke Seal Sensing Edge
Provide automatic stop control by an automatic sensing switch within neoprene astragal extending the full width of door bottom bar.
Provide an electric sensing edge device. Ensure the door immediately stops downward travel when contact occurs before door fully closes. Provide a self-monitoring wireless sensing edge connection to the motor operator;
eliminating the need for a physical traveling electric cord connection between bottom bar sensing edge device and motor operator. Supervised
SECTION 08 33 23 Page 11 system alters normal door operation; preventing damage, injury or death due to an inoperable sensing edge system.
2.2.6 Surface Finishing
Comply with NAAMM's "Metal Finishes Manual for Architectural and Metal Products" for recommendations for applying and designating finishes.
Noticeable variations in the same metal component are not acceptable.
Variations in appearance of adjoining components are acceptable if they are within the range of approved samples and are assembled or installed to minimize contrast.
PART 3 EXECUTION
3.1 INSTALLATION
Install overhead coiling door assembly, anchors and inserts for guides, brackets, motors, switches, hardware, and other accessories in accordance with approved detail drawings and manufacturer's written instructions.
Upon completion of installation, ensure doors are free from all distortion.
Install overhead coiling doors, motors, hoods, and operators at the mounting locations as indicated for each door in the contract documents and as required by the manufacturer.
Install overhead coiling doors, switches, and controls along accessible routes in compliance with regulatory requirements for accessibility and as required by the manufacturer.
3.1.1 Field Painted Finish
Ensure field painted steel doors and frames are in accordance with Section 09 90 00 PAINTS AND COATINGS and manufacturer's written instructions.
Protect weather stripping from paint. Ensure finishes are free of scratches or other blemishes.
3.2 ADJUSTING AND CLEANING
3.2.1 Acceptance Provisions
After installation, adjust hardware and moving parts. Lubricate bearings and sliding parts as recommended by manufacturer to provide smooth operating functions for ease movement, free of warping, twisting, or distortion of the door assembly.
Adjust seals to provide weather-tight fit around entire perimeter.
Engage a factory-authorized service representative to perform startup service and checks according to manufacturer's written instructions.
Test the door opening and closing operation when activated by controls or alarm-connected fire-release system. Adjust controls and safeties. Replace damaged and malfunctioning controls and equipment. Reset door-closing mechanism after successful test.
Test and make final adjustment of new doors at no additional cost to the Government.
SECTION 08 33 23 Page 12
3.2.1.1 Maintenance and Adjustment
Not more than 90 calendar days after completion and acceptance of the project, examine, lubricate, test, and re-adjust doors as required for proper operation.
3.3 CLOSEOUT ACTIVITIES
3.3.1 Warranty
Furnish a written guarantee that the helical spring and counterbalance mechanism are free from defects in material and workmanship for not less than two years after completion and acceptance of the project.
Warrant that upon notification by the Government, any defects in material, workmanship, and door operation are immediately correct within the same time period covered by the guarantee, at no cost to the Government.
3.3.2 Operation And Maintenance
Submit 2 copies of the Operation and Maintenance Manuals 30 calendar days prior to testing the Overhead Coiling Door Assemblies. Update and resubmit data for final approval no later than 30 calendar days prior to contract completion.
Submit Operation and Maintenance Manuals for Overhead Coiling Door Assemblies, including the following items:
1. Materials
2. Devices
3. Electric Door Operators
4. Hood
5. Counterbalancing Mechanism
6. Painting
7. Procedures
8. Manufacture's Brochures
9. Parts Lists
Provide operation and maintenance manuals which are consistent with manufacturer's standard brochures, schematics, printed instructions, operating procedures, and safety precautions. Provide test data that is legible and of good quality.
-- End of Section --
SECTION 08 33 23 Page 13
SECTION TABLE OF CONTENTS
DIVISION 26 - ELECTRICAL
SECTION 26 20 00
INTERIOR DISTRIBUTION SYSTEM
08/08
PART 1 GENERAL
1.1 REFERENCES
1.2 DEFINITIONS
1.3 SUBMITTALS
1.4 QUALITY ASSURANCE
1.4.1 Fuses
1.4.2 Regulatory Requirements
1.4.3 Standard Products
1.4.3.1 Alternative Qualifications
1.4.3.2 Material and Equipment Manufacturing Date
1.5 MAINTENANCE
1.5.1 Electrical Systems
1.6 WARRANTY
PART 2 PRODUCTS
2.1 MATERIALS AND EQUIPMENT
2.2 CONDUIT AND FITTINGS
2.2.1 Rigid Metallic Conduit
2.2.1.1 Rigid, Threaded Zinc-Coated Steel Conduit
2.2.2 Rigid Nonmetallic Conduit
2.2.3 Intermediate Metal Conduit (IMC)
2.2.4 Electrical, Zinc-Coated Steel Metallic Tubing (EMT)
2.2.5 Plastic-Coated Rigid Steel and IMC Conduit
2.2.6 Flexible Metal Conduit
2.2.6.1 Liquid-Tight Flexible Metal Conduit, Steel
2.2.7 Fittings for Metal Conduit, EMT, and Flexible Metal Conduit
2.2.7.1 Fittings for Rigid Metal Conduit and IMC
2.2.7.2 Fittings for EMT
2.2.8 Fittings for Rigid Nonmetallic Conduit
2.3 SURFACE RACEWAY
2.3.1 Surface Metal Raceway
2.4 CABLE TRAYS
2.4.1 Cable Runways
2.4.2 Basket-Type Cable Trays
2.5 OUTLET BOXES AND COVERS
2.5.1 Floor Outlet Boxes
2.5.2 Outlet Boxes for Telecommunications System
2.6 CABINETS, JUNCTION BOXES, AND PULL BOXES
2.7 WIRES AND CABLES
2.7.1 Conductors
2.7.2 Color Coding
2.7.3 Insulation
2.7.4 Bonding Conductors
2.7.4.1 Telecommunications Bonding Backbone (TBB)
SECTION 26 20 00 Page 1
2.7.4.2 Bonding Conductor for Telecommunications
2.8 SPLICES AND TERMINATION COMPONENTS
2.9 DEVICE PLATES
2.10 SWITCHES
2.10.1 Toggle Switches
2.10.2 Switch with Red Pilot Handle
2.10.3 Breakers Used as Switches
2.10.4 Disconnect Switches
2.11 FUSES
2.11.1 Fuseholders
2.11.2 Cartridge Fuses, Current Limiting Type (Class R)
2.11.3 Cartridge Fuses, High-Interrupting Capacity, Current Limiting
Type (Classes J, L, and CC)
2.11.4 Cartridge Fuses, Current Limiting Type (Class T)
2.12 RECEPTACLES
2.12.1 Switched Duplex Receptacles
2.12.2 Plug Load Switched Duplex Receptacles
2.12.3 Weatherproof Receptacles
2.12.4 Ground-Fault Circuit Interrupter Receptacles
2.12.5 Special Purpose Receptacles
2.12.6 Range Receptacles
2.12.7 Dryer Receptacles
2.13 PANELBOARDS
2.13.1 Enclosure
2.13.2 Panelboard Buses
2.13.2.1 Panelboard Neutrals for Non-Linear Loads
2.13.2.2 Mini-Power Center
2.13.3 Circuit Breakers
2.13.3.1 Multipole Breakers
2.13.3.2 Circuit Breaker With GFI
2.13.3.3 Circuit Breakers for HVAC Equipment
2.13.4 Fusible Switches for Panelboards
2.14 ENCLOSED CIRCUIT BREAKERS
2.15 MOTOR SHORT-CIRCUIT PROTECTOR (MSCP)
2.16 TRANSFORMERS
2.16.1 Specified Transformer Efficiency
2.16.2 Transformers With Non-Linear Loads
2.17 MOTORS
2.17.1 High Efficiency Single-Phase Motors
2.17.2 Premium Efficiency Polyphase Motors
2.17.3 Motor Sizes
2.17.4 Wiring and Conduit
2.18 MOTOR CONTROLLERS
2.18.1 Control Wiring
2.18.2 Control Circuit Terminal Blocks
2.18.2.1 Types of Terminal Blocks
2.18.3 Control Circuits
2.18.4 Enclosures for Motor Controllers
2.18.5 Multiple-Speed Motor Controllers and Reversible Motor
Controllers
2.18.6 Pushbutton Stations
2.18.7 Pilot and Indicating Lights
2.19 MANUAL MOTOR STARTERS (MOTOR RATED SWITCHES)
2.19.1 Pilot Lights
2.20 LOCKOUT REQUIREMENTS
2.21 TELECOMMUNICATIONS SYSTEM
2.22 COMMUNITY ANTENNA TELEVISION (CATV) SYSTEM
2.22.1 Backboards
2.23 GROUNDING AND BONDING EQUIPMENT
SECTION 26 20 00 Page 2
2.23.1 Ground Rods
2.23.2 Ground Bus
2.23.3 Telecommunications and CATV Grounding Busbar
2.24 HAZARDOUS LOCATIONS
2.25 MANUFACTURER'S NAMEPLATE
2.26 FIELD FABRICATED NAMEPLATES
2.27 WARNING SIGNS
2.28 FIRESTOPPING MATERIALS
2.29 WIREWAYS
2.30 METERING
2.31 SURGE PROTECTIVE DEVICES
2.32 FACTORY APPLIED FINISH
2.33 SOURCE QUALITY CONTROL
2.33.1 Transformer Factory Tests
2.34 COORDINATED POWER SYSTEM PROTECTION
PART 3 EXECUTION
3.1 INSTALLATION
3.1.1 Underground Service
3.1.2 Hazardous Locations
3.1.3 Service Entrance Identification
3.1.3.1 Labels
3.1.4 Wiring Methods
3.1.4.1 Pull Wire
3.1.5 Conduit Installation
3.1.5.1 Restrictions Applicable to EMT
3.1.5.2 Restrictions Applicable to Flexible Conduit
3.1.5.3 Service Entrance Conduit, Underground
3.1.5.4 Underground Conduit Other Than Service Entrance
3.1.5.5 Conduit Installed Under Floor Slabs
3.1.5.6 Conduit Through Floor Slabs
3.1.5.7 Stub-Ups
3.1.5.8 Conduit Support
3.1.5.9 Directional Changes in Conduit Runs
3.1.5.10 Locknuts and Bushings
3.1.5.11 Flexible Connections
3.1.5.12 Telecommunications and Signal System Pathway
3.1.6 Cable Tray Installation
3.1.7 Boxes, Outlets, and Supports
3.1.7.1 Boxes
3.1.7.2 Pull Boxes
3.1.7.3 Extension Rings
3.1.8 Mounting Heights
3.1.9 Conductor Identification
3.1.9.1 Marking Strips
3.1.10 Splices
3.1.11 Covers and Device Plates
3.1.12 Electrical Penetrations
3.1.13 Grounding and Bonding
3.1.13.1 Ground Rods
3.1.13.2 Grounding Connections
3.1.13.3 Ground Bus
3.1.13.4 Telecommunications System
3.1.14 Equipment Connections
3.1.15 Elevator
3.1.16 Government-Furnished Equipment
3.1.17 Watthour Meters
3.1.18 Surge Protective Devices
SECTION 26 20 00 Page 3
3.2 FIELD FABRICATED NAMEPLATE MOUNTING
3.3 WARNING SIGN MOUNTING
3.4 FIELD APPLIED PAINTING
3.5 FIELD QUALITY CONTROL
3.5.1 Devices Subject to Manual Operation
3.5.2 600-Volt Wiring Test
3.5.3 Transformer Tests
3.5.4 Ground-Fault Receptacle Test
3.5.5 Grounding System Test
3.5.6 Watthour Meter
-- End of Section Table of Contents --
SECTION 26 20 00 Page 4
SECTION 26 20 00
INTERIOR DISTRIBUTION SYSTEM
08/08
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to in the text by the basic designation only.
AMERICAN SOCIETY OF HEATING, REFRIGERATING AND AIR-CONDITIONING
ENGINEERS (ASHRAE)
ASHRAE 90.1 (2010) Energy Standard for Buildings Except Low-Rise Residential Buildings
ASME INTERNATIONAL (ASME)
ASME A17.1 (2007) Safety Code for Elevators and Escalators
ASTM INTERNATIONAL (ASTM)
ASTM B1 (2013) Standard Specification for Hard-Drawn Copper Wire
ASTM B8 (2011) Standard Specification for Concentric-Lay-Stranded Copper Conductors, Hard, Medium-Hard, or Soft
ASTM D709 (2013) Laminated Thermosetting Materials
INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE)
IEEE 100 (2000; Archived) The Authoritative Dictionary of IEEE Standards Terms
IEEE 81 (2012) Guide for Measuring Earth Resistivity, Ground Impedance, and Earth Surface Potentials of a Ground System
IEEE C2 (2017) National Electrical Safety Code
INTERNATIONAL ELECTRICAL TESTING ASSOCIATION (NETA)
NETA ATS (2013) Standard for Acceptance Testing Specifications for Electrical Power Equipment and Systems
NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA)
ANSI C12.1 (2008) Electric Meters Code for Electricity Metering
SECTION 26 20 00 Page 5
ANSI C12.7 (2014) Requirements for Watthour Meter Sockets
ANSI C80.1 (2005) American National Standard for Electrical Rigid Steel Conduit (ERSC)
ANSI C80.3 (2005) American National Standard for Electrical Metallic Tubing (EMT)
NEMA 250 (2014) Enclosures for Electrical Equipment (1000 Volts Maximum)
NEMA FU 1 (2012) Low Voltage Cartridge Fuses
NEMA ICS 1 (2000; R 2015) Standard for Industrial Control and Systems: General Requirements
NEMA ICS 2 (2000; R 2005; Errata 2008) Standard for Controllers, Contactors, and Overload Relays Rated 600 V
NEMA ICS 4 (2015) Terminal Blocks
NEMA ICS 6 (1993; R 2011) Enclosures
NEMA KS 1 (2013) Enclosed and Miscellaneous Distribution Equipment Switches (600 V Maximum)
NEMA MG 1 (2016) Motors and Generators
NEMA MG 10 (2013) Energy Management Guide for Selection and Use of Fixed Frequency Medium AC Squirrel-Cage Polyphase Induction Motors
NEMA MG 11 (1977; R 2012) Energy Management Guide for Selection and Use of Single Phase Motors
NEMA RN 1 (2005; R 2013) Polyvinyl-Chloride (PVC) Externally Coated Galvanized Rigid Steel Conduit and Intermediate Metal Conduit
NEMA ST 20 (1992; R 1997) Standard for Dry-Type Transformers for General Applications
NEMA TC 2 (2013) Standard for Electrical Polyvinyl Chloride (PVC) Conduit
NEMA TC 3 (2015) Standard for Polyvinyl Chloride (PVC) Fittings for Use With Rigid PVC Conduit and Tubing
NEMA TP 1 (2002) Guide for Determining Energy Efficiency for Distribution Transformers
NEMA VE 1 (2009) Standard for Metal Cable Tray Systems
SECTION 26 20 00 Page 6
NEMA WD 1 (1999; R 2005; R 2010) Standard for General Color Requirements for Wiring Devices
NEMA WD 6 (2012) Wiring Devices Dimensions Specifications
NEMA Z535.4 (2011) American National Standard for Product Safety Signs and Labels
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA 70 (2014) National Electrical Code
NFPA 70E (2015; ERTA 1 2015) Standard for Electrical Safety in the Workplace
NFPA 780 (2014) Standard for the Installation of Lightning Protection Systems
TELECOMMUNICATIONS INDUSTRY ASSOCIATION (TIA)
TIA-568-C.1 (2016) Commercial Building Telecommunications Cabling Standard, Part 1: General Requirements
TIA-569 (2015d) Commercial Building Standard for Telecommunications Pathways and Spaces
TIA-607 (2011b) Generic Telecommunications Bonding and Grounding (Earthing) for Customer Premises
U.S. NATIONAL ARCHIVES AND RECORDS ADMINISTRATION (NARA)
29 CFR 1910.147 Control of Hazardous Energy (Lock Out/Tag Out)
UNDERWRITERS LABORATORIES (UL)
UL 1 (2005; Reprint Jul 2012) Standard for Flexible Metal Conduit
UL 1010 (2006) Receptacle-Plug Combinations for Use in Hazardous (Classified) Locations
UL 1063 (2006; Reprint Jul 2012) Machine-Tool Wires and Cables
UL 1242 (2006; Reprint Mar 2014) Standard for Electrical Intermediate Metal Conduit -- Steel
UL 1449 (2014; Reprint Mar 2016) Surge Protective Devices
UL 1561 (2011; Reprint Jun 2015) Dry-Type General Purpose and Power Transformers
SECTION 26 20 00 Page 7
UL 198M (2003; Reprint Feb 2013) Standard for Mine-Duty Fuses
UL 20 (2010; Reprint Feb 2012) General-Use Snap Switches
UL 360 (2013; Reprint Jan 2015) Liquid-Tight Flexible Steel Conduit
UL 4248 (2007) UL Standard for Safety Fuseholders
UL 44 (2014; Reprint Feb 2015) Thermoset-Insulated Wires and Cables
UL 467 (2007) Grounding and Bonding Equipment
UL 486A-486B (2013; Reprint Jan 2016) Wire Connectors
UL 486C (2013; Reprint Feb 2014) Splicing Wire Connectors
UL 489 (2016) Molded-Case Circuit Breakers, Molded-Case Switches, and Circuit-Breaker Enclosures
UL 498 (2012; R 2016) Attachment Plugs and Receptacles
UL 5 (2011) Surface Metal Raceways and Fittings
UL 50 (2007; Reprint Apr 2012) Enclosures for Electrical Equipment, Non-environmental Considerations
UL 506 (2008; Reprint Oct 2013) Specialty Transformers
UL 508 (1999; Reprint Oct 2013) Industrial Control Equipment
UL 510 (2005; Reprint Jul 2013) Polyvinyl Chloride, Polyethylene and Rubber Insulating Tape
UL 514A (2013) Metallic Outlet Boxes
UL 514B (2012; Reprint Nov 2014) Conduit, Tubing and Cable Fittings
UL 514C (2014; Reprint Dec 2014) Nonmetallic Outlet Boxes, Flush-Device Boxes, and Covers
UL 6 (2007; Reprint Nov 2014) Electrical Rigid Metal Conduit-Steel
UL 651 (2011; Reprint May 2014) Standard for Schedule 40 and 80 Rigid PVC Conduit and Fittings
SECTION 26 20 00 Page 8
UL 67 (2009; Reprint Apr 2015) Standard for Panelboards
UL 674 (2011; Reprint Jul 2013) Electric Motors and Generators for Use in Division 1 Hazardous (Classified) Locations
UL 698 (2006) Industrial Control Equipment for use in Hazardous (Classified) Locations
UL 797 (2007; Reprint Dec 2012) Electrical Metallic Tubing -- Steel
UL 83 (2014) Thermoplastic-Insulated Wires and Cables
UL 869A (2006) Reference Standard for Service Equipment
UL 870 (2008; Reprint Feb 2013) Standard for Wireways, Auxiliary Gutters, and Associated Fittings
UL 877 (1993; Reprint Dec 2009) Standard for Circuit Breakers and Circuit-Breaker Enclosures for Use in Hazardous (Classified) Locations
UL 886 (1994; Reprint Nov 2005) Standard for Outlet Boxes and Fittings for Use in Hazardous (Classified) Locations
UL 943 (2006; Reprint Jun 2012) Ground-Fault Circuit-Interrupters
UL 984 (1996; Reprint Sep 2005) Hermetic Refrigerant Motor-Compressors
1.2 DEFINITIONS
Unless otherwise specified or indicated, electrical and electronics terms used in these specifications, and on the drawings, shall be as defined in
IEEE 100.
1.3 SUBMITTALS
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are for information only. When used, a designation following the "G" designation identifies the office that will review the submittal for the Government. The following shall be submitted in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:
SD-02 Shop Drawings
Panelboards; G Transformers; G Cable trays
SECTION 26 20 00 Page 9
Include wiring diagrams and installation details of equipment indicating proposed location, layout and arrangement, control panels, accessories, piping, ductwork, and other items that must be shown to ensure a coordinated installation. Wiring diagrams shall identify circuit terminals and indicate the internal wiring for each item of equipment and the interconnection between each item of equipment. Drawings shall indicate adequate clearance for operation, maintenance, and replacement of operating equipment devices.
Wireways Marking strips
SD-03 Product Data
Receptacles Circuit breakers; G Switches Transformers; G Enclosed circuit breakers Motor controllers Manual motor starters Metering; G Telecommunications Grounding Busbar Surge protective devices
Submittals shall include performance and characteristic curves.
SD-06 Test Reports
600-volt wiring test; G Grounding system test; G Transformer tests; G Ground-fault receptacle test; G
SD-07 Certificates
Fuses
SD-09 Manufacturer's Field Reports
Transformer factory tests
SD-10 Operation and Maintenance Data
Electrical Systems, Data Package 5
Metering, Data Package 5
Submit operation and maintenance data in accordance with Section 01 78 23, OPERATION AND MAINTENANCE DATA and as specified herein.
1.4 QUALITY ASSURANCE
1.4.1 Fuses
Submit coordination data as specified in paragraph, FUSES of this section.
SECTION 26 20 00 Page 10
1.4.2 Regulatory Requirements
In each of the publications referred to herein, consider the advisory provisions to be mandatory, as though the word, "shall" had been substituted for "should" wherever it appears. Interpret references in these publications to the "authority having jurisdiction," or words of similar meaning, to mean the Contracting Officer. Equipment, materials, installation, and workmanship shall be in accordance with the mandatory and advisory provisions of NFPA 70 unless more stringent requirements are specified or indicated.
1.4.3 Standard Products
Provide materials and equipment that are products of manufacturers regularly engaged in the production of such products which are of equal material, design and workmanship. Products shall have been in satisfactory commercial or industrial use for 2 years prior to bid opening. The 2-year period shall include applications of equipment and materials under similar circumstances and of similar size. The product shall have been on sale on the commercial market through advertisements, manufacturers' catalogs, or brochures during the 2-year period. Where two or more items of the same class of equipment are required, these items shall be products of a single manufacturer; however, the component parts of the item need not be the products of the same manufacturer unless stated in this section.
1.4.3.1 Alternative Qualifications
Products having less than a 2-year field service record will be acceptable if a certified record of satisfactory field operation for not less than 6000 hours, exclusive of the manufacturers' factory or laboratory tests, is furnished.
1.4.3.2 Material and Equipment Manufacturing Date
Products manufactured more than 3 years prior to date of delivery to site shall not be used, unless specified otherwise.
1.5 MAINTENANCE
1.5.1 Electrical Systems
Submit operation and maintenance manuals for electrical systems that provide basic data relating to the design, operation, and maintenance of the electrical distribution system for the building. This shall include:
a. Single line diagram of the "as-built" building electrical system.
b. Schematic diagram of electrical control system (other than HVAC, covered elsewhere).
c. Manufacturers' operating and maintenance manuals on active electrical equipment.
1.6 WARRANTY
The equipment items shall be supported by service organizations which are reasonably convenient to the equipment installation in order to render satisfactory service to the equipment on a regular and emergency basis during the warranty period of the contract.
SECTION 26 20 00 Page 11
PART 2 PRODUCTS
2.1 MATERIALS AND EQUIPMENT
Materials, equipment, and devices shall, as a minimum, meet requirements of UL, where UL standards are established for those items, and requirements of
NFPA 70.
2.2 CONDUIT AND FITTINGS
Shall conform to the following.
2.2.1 Rigid Metallic Conduit
2.2.1.1 Rigid, Threaded Zinc-Coated Steel Conduit
ANSI C80.1, UL 6.
2.2.2 Rigid Nonmetallic Conduit
PVC Type EPC-40, and EPC-80 in accordance with NEMA TC 2, UL 651.
2.2.3 Intermediate Metal Conduit (IMC)
UL 1242, zinc-coated steel only.
2.2.4 Electrical, Zinc-Coated Steel Metallic Tubing (EMT)
UL 797, ANSI C80.3.
2.2.5 Plastic-Coated Rigid Steel and IMC Conduit
NEMA RN 1, Type 40 (40 mils thick).
2.2.6 Flexible Metal Conduit
UL 1.
2.2.6.1 Liquid-Tight Flexible Metal Conduit, Steel
UL 360.
2.2.7 Fittings for Metal Conduit, EMT, and Flexible Metal Conduit
UL 514B. Ferrous fittings shall be cadmium- or zinc-coated in accordance with UL 514B.
2.2.7.1 Fittings for Rigid Metal Conduit and IMC
Threaded-type. Split couplings unacceptable.
2.2.7.2 Fittings for EMT
Die cast compression type for exterior. Steel set screw type fitting for interior.
SECTION 26 20 00 Page 12 R0008
G3ENDRDN
Rectangle
2.2.8 Fittings for Rigid Nonmetallic Conduit
NEMA TC 3 for PVC, and UL 514B.
2.3 SURFACE RACEWAY
2.3.1 Surface Metal Raceway
UL 5, two-piece painted steel, totally enclosed, snap-cover type. Provide multiple outlet-type raceway with grounding-type receptacle where indicated. Receptacles shall be as specified herein and shall be spaced minimum of one every 18 inches.
2.4 CABLE TRAYS
NEMA VE 1. Cable trays and runways shall form a wireway system, and shall be of nominal depth as indicated. Trays shall include splice and end plates, dropouts, and miscellaneous hardware. Edges, fittings, and hardware shall be finished free from burrs and sharp edges. Fittings shall have not less than load-carrying ability of straight tray sections and shall have manufacturer's minimum standard radius. Radius of bends shall be 12 inches minimum.
2.4.1 Cable Runways
Provide cable runways with 1-1/2 inch rungs on 12-inch centers, steel construction with flat black powder coat paint, UL classified as an equipment grounding conductor. Include runway support clamps and brackets, seismic bracing, splice kits, dropouts, and accessories.
2.4.2 Basket-Type Cable Trays
Provide stainless steel basket tray with straight section and fitting side rails and rungs made of AISI Type 304 or Type 316. Weld transverse members (rungs) or corrugated bottoms to the side rails with Type 316 stainless steel welding wire. Provide size as indicated and 4 inch depth with maximum wire mesh spacing of 2 by 4 inch.
2.5 OUTLET BOXES AND COVERS
UL 514A, cadmium- or zinc-coated, if ferrous metal. UL 514C, if nonmetallic.
2.5.1 Floor Outlet Boxes
Boxes shall be adjustable and concrete tight. Each outlet shall consist of cast-metal body with threaded openings, or sheet-steel body with knockouts for conduits, adjustable, brass flange ring, and cover plate as indicated.
2.5.2 Outlet Boxes for Telecommunications System
Provide standard type 4 11/16 inches square by 2-1/8 inches deep. Outlet boxes for wall-mounted telecommunications outlets shall be 4 by 2-1/8 by 2 1/8 inches deep as indicated. Depth of boxes shall be large enough to allow manufacturers' recommended conductor bend radii.
2.6 CABINETS, JUNCTION BOXES, AND PULL BOXES
Volume greater than 100 cubic inches, UL 50, hot-dip, zinc-coated, if sheet
SECTION 26 20 00 Page 13 steel.
2.7 WIRES AND CABLES
Wires and cables shall meet applicable requirements of NFPA 70 and UL for type of insulation, jacket, and conductor specified or indicated. Wires and cables manufactured more than 12 months prior to date of delivery to site shall not be used.
2.7.1 Conductors
Conductors No. 8 AWG and larger diameter shall be stranded. Conductors No.
10 AWG and smaller diameter shall be solid, except that…
This is the start of the file's text. The full file is on GovTribe.