Amendment_0001_Projnet_7080294_Response_Detail_4-way_Switch.pdf

PDF 1021 KB Posted

Attached to
Electrical project entitled, Repair/Replace Electrical Distribution Line, Main-Gingko, McChord Field, Joint Base-Lewis-McChord, Washington.
Solicitation number
W912DW17B0005
Issued by

About this file

Amendment 0001 Projnet responses

View the file

Other files

File Type Posted
W912DW17B0005_BIDABSTRACTMAINGINGKO23AUG17.pdf PDF
W912DW-17-B-0005_AMENDMENT_0005.pdf PDF
W912DW-17-B-0005_Amendment_0005_Gingko_As-Built_Dwgs_(1997).pdf PDF
amendment4IFB0005.pdf PDF
26_11_14.00_10_-_Main_Elec_Supply_Station_&_Substation_-_10Aug2017.pdf PDF
E-502_Elec_Details_Rev-1_10Aug2017.pdf PDF
E-505_Elec_Manhole_Details_Rev-1_10Aug2017_-_Copy.pdf PDF
amendment4IFB0005.pdf PDF
26_11_14.00_10_-_Main_Elec_Supply_Station_&_Substation_-_10Aug2017.pdf PDF
E-505_Elec_Manhole_Details_Rev-1_10Aug2017_-_Copy.7z 7Z file
E-502_Elec_Details_Rev-1_10Aug2017.pdf PDF
33_71_02_-_UG_Elec_Distribution_-_08Aug2017.pdf PDF
W912DW-17-B-0005_Rev_Dwgs_Amend-0003.pdf PDF
W912DW17B0005_Amd_0003.pdf PDF
AMD_0002_Combined_Rev_Dwgs_-_04Aug2017.pdf PDF
W912DW17B0005_Amd_0002.pdf PDF
amendment1IFB17B0005.pdf PDF
Site_Visit_Attendance_Roster___17-B-0005.pdf PDF
Amendment_0001_33_71_02_-_UG_Elec_Distribution_-_31Jul2017.pdf PDF
Amendment_0001_CE0435_Sect_01_11_00_-_Summary_of_Work_31Jul2017.pdf PDF
CE0435_Atch-4_McChord_Pipeline_Manual_-_Utility_Crossings_F-7.pdf PDF
CE0435_Atch-3_BNSF_2017_Temp_Occupancy_App_and_Instructions.pdf PDF
CE0435_Complete_Specs_-_19Jun2017_FINAL.pdf PDF
CE0435_Main-Gingko_IFB_Dwgs_Rev-1_29Jun2017xx.pdf PDF
CE0435_Atch-2_BNSF_2017_Pipeline,_Wire_Line_App_and_Instructions.pdf PDF
W912DW-17-B-0005_R&R_Electrical_Distro_Line_Main_Gingko.pdf PDF
CE0435_Atch-1_BNSF_Utility_Accommodation_Policy.pdf PDF
Show all 27

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

UGP

UGP

U G

P

U G

P

U G

P

U G

P

GRAVEL

30 kVA TRANSFORMER

GAS SWITCH

A

SEE NOTE

4 & 5 (TYP)A

E

F

VR104

E-505

D

INTERNAL

TO VAULT

MH 04

4 3 2 1

OPERATING SIDE

N

THREE-PHASE UNITS—Continued

Model1 One-Line Diagram2

Ratings3 Catalog Number

Net Wt., Lbs. (Kg)4kV Short-Circuit

Amperes, RMS, Sym.Max BIL

15.5 95 12 500 25 000

944222 864222

1100 (495) 1100 (495)

29 125 12 500 25 000

944223 864223

1100 (495) 1100 (495)

38 150 12 500 25 000

944224 864224

1350 (607.5) 1350 (607.5)

Provide 4-way Padmounted Switch, S&C Electric Model 422, Base Catalog # 864222 (or approved equal) as follows:

Provide the following:

2 each, 900 amp load interrupters (Ways 1 & 2).

2 each, 600-amp fault interrupters (Ways 3 & 4).

25 kA short circuit rating ("8" in base catalog #) 1200 amp copper main bus (-Z5) 4-way steel enclosure with olive green finish (-P4) No potential indications or test features (-L1) (test points will be provided on the cable terminators)

900-amp load interrupters on Ways 1 & 2 (-K1-K2) 900-amp bushings without studs on Ways 1 & 2

600-amp fault interrupters on Ways 3 & 4 (no suffix)** 600-amp bushings without studs on Ways 3 & 4 (-M1)**

**Note: 900A fault interrupters and bushings should be used if 600A fault interrupters are not available for this configuration.

S&C Catalog 864222-Z5-P4-L1-K1-K2-M1 ***

One Line Diagram (from Sh. E-601)

Layout (from Sheet E-401)

***Note: Contractor shall verify catalog number and all suffixes with the manufacturer prior to ordering.

4-WAY PADMOUNTED SWITCH DETAILS

SWITCH CATALOG NUMBER AND ACCESSORIES

Black & Veatch Special Projects Corp.

31 July 2017

SKETCH SK-PAS-20170731-01 (Sheet 1 of 2)

600AF

600AT

TO

EXIST

KVA

XFMR

NEW

O/H

TIE

INC.

FROM

(TERMINATOR SIDE)

600AF

50AT

(OPERATING SIDE)

4 3 2 1

SWGRSWITCH

G3ECNMJK

Text Box Amend-0001 Sketch associated with Dwg Sht E-401 and E-601; Note: these Details and Notes will supersede and/or supplement current Notes and Details shown on Dwgs E-401 and E-601 as applicable.

R-Stack (without Test Point), Standard Elbow (with Test Point), Hex Tool, 2 Insulating Plugs and Caps and 1 Stud 62BJT2 — 15/25kV

92BJT2 = 900A (copper components) (qty 3) Insulating Plug with Cap

Apparatus Bushing

R-Stack Elbow

Stud

Standard Elbow

R-Stack

Components

4 Total ComponentsR-

St ac k

Provide cable adapters (qty 6) for 500 kcmil copper MV-105 cables.

Provide #4 tinned copper braid shield adapter (qty 2).

Provide cold shrinkable sleeves (qty 6) for cable adapters.

Way #1: Provide Richards Manufacturing Co. (or approved equal) 900 amp deadbreak elbows and accessories as follows:

Way #2: Provide same as Way #1:

Way #4 Provide same as Way #1, except cables shall be 350 kcmil copper MV-105, two per phase.

Way #3 Provide Richards Manufacturing Co. (or approved equal) 600 amp deadbreak elbows and accessories as follows:

600A Elbow (with Test Point), Stud, Insulating Plug and Cap, Lug and Cable Adapter 62LCT2WX — 15/25kV Use Table W1 to select “W”.

63LCT2WX — 35kV

Provide cable adapters (qty 3) for 350 kcmil copper MV-105 cables.

Provide #4 tinned copper braid shield adapter (qty 1).

Provide cold shrinkable sleeves (qty 3) for cable adapters.

***Note: Contractor shall verify catalog number and all suffixes with the manufacturer prior to ordering.

4-WAY PADMOUNTED SWITCH DETAILS

CABLE TERMINATIONS AND ACCESSORIES

Black & Veatch Special Projects Corp.

31 July 2017

SKETCH SK-PAS-20170731-01 (Sheet 2 of 2)

G3ECNMJK

Text Box Amend-0001 Sketch associated with Dwg Sht E-401 and E-601; Note: these Details and Notes will supersede and/or supplement current Notes and Details shown on Dwgs E-401 and E-601 as applicable.

200A LoadBreak Elbow Overview
600/900A Deadbreak Overview
R-Stack Overview
R-800 Overview
High-Fault Current Elbow Overview
600/900A 35kv JUNCTIONS Overview
Table 1 - W Cable Adapter Sizes
200A Loadbreak Elbow
Overview
Kits, Parts & Accessories
Ordering Information
600/900A Deadbreak
Overview
Elbow Kits
Accessories
Ordering Information
R-Stack
Overview
Installation Configurations
Elbow Kits
Parts & Accessories
Ordering Information
R-800
Overview
Installation
Selection Guide & Product Ratings
Kit Options
Accessories
Ordering Information
Bushing Extender R-800
Overview
Kit Options & Product Ratings
SSC Series - Cold Shrink Splice
Overview
Ordering Information
Disconnectable Joints
Overview
Innovations
Kits
Joint Accessories
600/900A Deadbreak Junctions
Overview
Ordering Information
Junction Dimensions
Apparatus Bushings
Overview
600A 35kV R-Stack Arrester
Overview
Kit Options
Reference
Selection Guide — W — Size-Sensitive Components
Selection Guide — X — Lug Connectors
Selection Guide — Suffix — Shield Adapter & Jacket Seal Options
Table W1-W3 — Cable Adapter Sizes
Table Z1-Z2 — Cold Shrink Sizes
Table X — Cable Sizes
Table 1 — Shield Adapter Kits
Table 2a — AEIC/ICEA Cable Specifications Calculated Dimensions — Stranded Conductor
Table 2b — AEIC/ICEA Cable Specifications Calculated Dimensions — Compressed Conductor
Table 2c — AEIC/ICEA Cable Specifications Calculated Dimensions — Compact Conductor
Index