About this file

This document is a detailed mechanical engineering drawing (Sheet MH-101) for HVAC ductwork in the First Floor Plan - East section of Building 606 at the United States Military Academy, West Point, NY. The drawing is part of a renovation project (Project Number 94078) for the General Instruction Building, with the solicitation number W912DS19C0034 issued by the US Army Corps of Engineers New York District. The drawing comprehensively maps out complex ductwork routing, including various air handling units (AVB), exhaust and return air systems (ER-1, RR-1, LSR-1), and supply and return air ducts with specific cubic feet per minute (CFM) measurements for multiple rooms. The document includes technical specifications such as duct sizes, airflow volumes, fire damper locations, and a note requiring specific government approval for any ductwork substitutions.

View the file

Other files

File Type Posted
MSEC- Building 606 - Amendment 9 - RFIs - 5 Nov 25.pdf PDF
A-601_AM 9.pdf PDF
08 71 00_AM 9.pdf PDF
MP-101_AM 7.pdf PDF
E-611_AM 7.pdf PDF
08 71 00_AM 7.pdf PDF
MSEC- Building 606 - Amendment 7 - RFIs - 21 Oct 25.pdf PDF
I-130_AM 6.pdf PDF
I-100.1_AM 6.pdf PDF
AD-301_AM 6.pdf PDF
A-305_AM 6.pdf PDF
A-102_AM 6.pdf PDF
A-413_AM 6.pdf PDF
A-502_AM 6.pdf PDF
A-504_AM 6.pdf PDF
MP-107_AM 6.pdf PDF
MP-105_AM 6.pdf PDF
MP-101_AM 6.pdf PDF
S-322_AM 6.pdf PDF
S-315_AM 6.pdf PDF
S-107_AM 6.pdf PDF
07 52 00_AM 6.pdf PDF
08 60 45_AM 6.pdf PDF
08 81 00_AM 6.pdf PDF
A-551_AM 5.pdf PDF
MSEC- Building 606 - Amendment 5 - RFIs - 8 Oct 25 rev JF.pdf PDF
A-601_AM 4.pdf PDF
Solicitation Amendment W912DS25RA0020004 SF 30.pdf PDF
MS-100_AM3.pdf PDF
01 91 19_AM3.pdf PDF
01 30 00_AM3.pdf PDF
HP802 - HVAC_PLUMBING_AND ELECTRICAL COORDINATION SCHEDULE_AM3.pdf PDF
E-618 - Panelboard Schedules_AM3.pdf PDF
E-513.pdf PDF
A-121.pdf PDF
07 60 00.pdf PDF
C-101.pdf PDF
RFIs_MSEC_Amendment 2 _ 2 Sep 25.pdf PDF
Criteria and Factors for Evaluation_Basis of Award_Evaluation Criteria_Rating System_AM 2 revised.pdf PDF
MSEC- Building 606 - Amendment 1 - RFIs - 20 Aug 25.pdf PDF
W912DS19C0034 PN 94078 Repair Building 606 Revised RTA Drawings - Volume 4.pdf PDF
W912DS19C0034 PN 94078 Repair building 606 REV.RTA Specification Manual Volume 3.pdf PDF
W912DS19C0034 PN 94078 Repair building 606 REV.RTA Specification Manual Volume 1.pdf PDF
JA-002-25 Lutron Lighting Controls MSEC - 31 Jan 25 signedJF sDL rev. 1 -_Redacted.pdf PDF
JA-009-25 Semco Pinnacle DOAS MSEC - 31 Jan 25 signedJF sDL rev. 1_Redacted.pdf PDF
JA-005-25 DAS MSEC - 31 Jan 25 signedJF sDL -_Redacted.pdf PDF
JA-003-25 Shark Meter MSEC - 31 Jan 25 signedJF sDL -_Redacted.pdf PDF
Criteria and Factors for Evaluation_Basis of Award_Evaluation Criteria_Rating System.pdf PDF
W912DS19C0034 PN 94078 Repair Building 606 Revised RTA Drawings - Volume 2.pdf PDF
W912DS19C0034 PN 94078 Repair Building 606 Revised RTA Drawings - Volume 1.pdf PDF
Show 40 more

50 files listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

D5W29D4D3D2 D1

AE

AD

CL1

AC

AB

AA

A6A5.1A5A4.6A4.4A4.2A4A3.7A3.2A3A2.7A2A1.9A1.5A1.3A1

CLASSROOM

HC TLT

CLASSROOM

CLASSROOM

CORR

119CORR

STOR

STOR

CORRIDOR

VEST

CLASSROOM

COLLAB

ELECT

CORR

STAIR 1

ST1

48"x18" S/A

26"x14" R/A

WATER SERVICE & BACKFLOW

PREVENTER

20"x36" OA UP

& DN

44"x38" SA DN & 36"x26" UP

HC TLT

ELEV LOBBY

CLASSROOM

124CLASSROOM

CLASSROOM

CLASSROOM

HC TLT

COLLAB

STOR

CLASSROOM

VEST

CORR

CORR

119CORR

STOR

CORRIDOR

VEST

CLASSROOM

CLASSROOM

118CLASSROOM

CLASSROOM

CORRIDOR

CORRIDOR

COLLAB

COLLAB

COLLAB

COLLAB

CONF

ELECT

CORR

STAIR 1

ST1

FIRE PUMP

WATER SERVICE & BACKFLOW

PREVENTER

WELLNESS RM

HC TLT

VEST

CLASSROOM

105 CFM

CB

(TYP. 3)

110 CFM

CB

115 CFM

CB

(TYP. 4)

95 CFM

CB

85 CFM

CB

70 CFM

CB

1130 CFM

CB

70 CFM

CB

80 CFM

CB

(TYP. 4)

80 CFM

CB

(TYP. 4)

80 CFM

CB

(TYP. 4)

70 CFM

CB

80 CFM

CB

(TYP. 4)

80 CFM

CB

85 CFM

CB

80 CFM

CB

85 CFM

CB

80 CFM

CB

(TYP. 3)

85 CFM

CB

80 CFM

CB

(TYP. 4)

85 CFM

CB

80 CFM

CB

(TYP. 3)

85 CFM

CB

90 CFM

CB

(TYP. 4)

CUH

1-1

AVB

R2-110

AVB

R2-109

AVB

R2-107

AVB

R2-106

AVB

R2-103

AVB

R2-101

AVB

R2-102

AVB

R2-115

AVB

R2-116

AVB

R2-117

AVB

R2-118

AVB

R2-119

AVB

R2-114

AVB

R2-112

AVB

R2-113

AVB

B1-103

6"x4"

6"x8" S/A

6" ø

8"ø

8"ø S/A

12"x12"

"x

8" x8

"x

8"

6"ø

6"ø

6" x8

"6" x8

36"x16" CB E/A

6" x8

16"x18" CB S/A

"x

34"x24" S/A

8" x6

8"x6"

10"x10"

6"ø

8" x8

10"ø R/A

10"ø S/A

10"x8"

6" x8

6" x8

14"x14" S/A

10"ø S/A

10"x10"

12"x12" S/A

10"ø

12"x12" R/A14"x14" R/A

COLLAB

102AVB

B1-101

AVB

B1-102

A6

M-301

A8

M-301

S E

E M

H -1

LSD-1

135 CFM

LSD-1

135 CFM

LSD-1

135 CFM

LSD-1

130 CFM

LSD-1

135 CFM

(3)LSD-1

350 CFM

8" x1

0" S

/A

(3)LSR-1

350 CFM

CD-1

30 CFM

ER-1

425 CFM

ER-1

460 CFM

ER-1

320 CFM

ER-1

320 CFM

ER-1

320 CFM

ER-1

330 CFM

ER-1

320 CFM

ER-1

325 CFM

ER-1

320 CFM

ER-1

325 CFM

ER-1

320 CFM

ER-1

355 CFM

ER-1

130 CFM

ER-1

150 CFM

ER-1

75 CFM

RR-1

100 CFM

LSR-1

100 CFM

LSR-1

210 CFMRR-1

50 CFM

RR-1

50 CFM

(2)RR-1

285 CFM

RR-1

285 CFM

RR-1

285 CFM

LSR-1

200 CFM

80 CFM

CB

(TYP. 4)

BE.3

BF.7

BB.1

BB.9

A1.1B12B11.1

AVB

R2-105

AVB

R2-108

AVB

R2-104

10"x8" EA DN WITH

FD AT FLOOR

12"x10" E/A

6" x4

8" x1 0"

"x

8"

16"x14" 18"x16"

"ø

CD-1

75 CFM

LSD-1

105 CFM

8"ø

8" x6

LSD-1

80 CFM

"x

6"

LSD-1

80 CFM

LSD-1

105 CFM

CD-1

75 CFM

8" ø

6" x8

LSD-1

110 CFM

8"x10"

10"x10"

12"x10"

12"x10" S/A

26"x14"

LSD-1

100 CFM

8" ø LSD-1

170 CFM

8"x10"

8"x8"

LSD-1

130 CFM

12"x8"

LSD-1

125 CFM

12"x10" S/A

LSD-1

125 CFM

14"x10"

LSD-1

130 CFM

LSD-1

120 CFM 6"x6" S/A LSD-1

50 CFM6"ø

LSD-1

45 CFM

6"x8"

LSD-1

50 CFM

8"x8"

LSD-1

45 CFM

8" x1

0"

14"x12" 12"ø24

"x

34"x20"

6"x6"

8"x8"

"x

8"

14"x8" 20"x10"

"x

12"x10"

8" ø

6" x1

0"

12"x14"

22"x6"

"x

10"x8"

8"x6"

8" x6

10"x8" 12"x12"

10"x8"

14"x10"

14"x6"

18"x12"

"x

16"x16"22"x12"

"x

8" 8" x8

8" x8

10"x8" CB S/A

36"x10"

"x

22"x16"

"x

14"x26"

16"x16" 14"x16"

10"x22"

16"x10"

"x

8" x1

0"

6" x8

8" x1 0"

8"x8" CB S/A

8" x1

0"

"x 8"

LOBBY

10"x10"

VD (TYP.)

"x

8"

"x

14"x12"16"x14"

12"x6" 12"x6"

10"x10"

6"ø 6"ø 6"ø

6"ø 6"ø

6"ø

VD (TYP.)

10"x10"

6"ø 6"ø

6"ø6"ø

6" ø

6" ø

6" ø

6" ø10"x10"

8"x8"

8" x8

6"ø 6"ø

6"ø6"ø6"ø 6"ø

6"ø6"ø

ER-1

150 CFM

CD-1

190 CFM

6"ø 6"ø

6"ø6"ø

6" ø

6" ø

6"ø 6"ø 6"ø 6"ø 6"ø

6"ø

6"ø

6"ø 6"ø 6"ø

6"ø6"ø

6"ø

6"ø6"ø 6"ø

6"ø6"ø

8"x10" 8"x10"

12"x6"

10"ø 22"x10"

"x

6"x10"

"x

6"

"x

6"

14"x6"

8" x8

22"x10"

14"x6"

8"x10"

12"x6"

8"x10"

VD (TYP.)

18"x6"

"x

36"x10"

8" x1

0"

6" ø

6" ø

VD (TYP.)

8"x4"

8"x4"

6" ø

8"x4"

8"x4"

AVB

R2-1111

04 8 16268

SCALE: 1/8" = 1'-0"

NORTH

US Army Corps of Engineers ®

SHEET ID

U S

A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

S U

B M

IT

T

E D

B Y

S

IZ

E

C H

E C

K E

D B

Y

A N

S I D

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

S O

L

IC

IT

A

T

IO

N N

O

G

2 3 4 5 6 7 8 9 10

F

E

D

C

B

A

D A

T E

File Path:

Plot Date:

M A

R K

D E

S C

R

IP

T

IO

N

P R

O J E

C T

N O

Autodesk Docs://West Point Bldg 606/219208-WP606-M20.rvt

10/3/2025 2:08:52 PM

MH-101

F

IR

S T

F L O

O R

P L A

N E

A S

T

D U

C T

W O

R K

U N

IT

E

D S

T A

T E

S M

IL

IT

A R

Y A

C A

D E

M Y

W

E S

T P

O

IN

T N

Y P

N

F

Y

N E

W Y

O R

K D

IS

T

R

IC

T A

K

A K

J F

M

A Y

W D

S C

E C

REV RTA SUBMISSION

R E

P A

IR

B

L D

G

G

E N

E R

A L I N

S T

R U

C T

IO

N

B L D

G

SCALE: 1/8" = 1'-0"A1

FIRST FLOOR PLAN DUCTWORK - EAST

KEYNOTE - MH-101

1 36"x26" R/A UP & 28"x58" DOWN

2 28"x20" CB E/A UP

3 30"x20" CB S/A UP

4 FIRE DAMPER AT HVAC CHASE WALL. PROVIDE FOR ALL DUCTWORK THAT PENETRATES FIRE RATED PARTITION.

5 10"x4" E/A UP. ALL EXHAUST DUCTWORK SERVICING ELECTRICAL ROOMS SHALL BE ALUMINUM AND PROTECTED WITH 2 HOUR RATED FIRE BARRIER DUCT WRAP. NO FIRES DAMPERS SHALL BE USED IN THIS SYSTEM.

GENERAL NEW WORK NOTES:

1. SUBSTITUTION FOR ROUND OR RECTANGULAR DUCTWORK

FROM WHAT IS SHOWN ON PLAN MUST RECEIVE SPECIFIC

GOVERNMENT APPROVAL.

A

D D

E N

D U

M

/0

/2