TABLE 1

Insulation Material for Piping

Service

Material Specification Type Class VR/VB Req'd

Condensate Drain Located Inside Building

Cellular Glass ASTM C552 II 2 No

Flexible Elastomeric Cellular ASTM C534/C534M I No

Medium Temperature Hot Water, Steam and Condensate ( 122 to 176 Degrees C 251 to 350 Degrees F )

Mineral Fiber ASTM C547 I 1 No

Calcium Silicate ASTM C533 I No

Cellular Glass ASTM C552 I or II No

Perlite ASTM C610 No

Flexible Elastomeric Cellular ASTM C534/C534M I 2 No

High Temperature Hot Water & Steam ( 177 to 371 Degrees C 351 to 700 Degrees F )

Mineral Fiber ASTM C547 I 2 No

Calcium Silicate ASTM C533 I No

Perlite ASTM C610 No

Cellular Glass ASTM C552 No

Brine Systems Cryogenics ( -34 to -18 Degrees C -30 to 0 Degrees F )

Cellular Glass ASTM C552 II 2 No

Flexible Elastomeric Cellular ASTM C534/C534M I No

Brine Systems Cryogenics ( -18 to 1.11 Degrees C 0 to 34 Degrees F )

Cellular Glass ASTM C552 II 2 No

Flexible Elastomeric Cellular ASTM C534/C534M I No

Note: VR/VB = Vapor Retarder/Vapor Barrier

NOTE: Tabl e 2 i s not i ncl usi ve of al l syst ems r equi r i ng i nsul at i on. Pi pe i nsul at i on t hi cknesses must meet or exceed t he r equi r ement s of ASHRAE 90. 2 f or l ow- r i se r esi dent i al bui l di ngs, and ASHRAE 90. 1 f or al l ot her bui l di ngs except l ow- r i se r esi dent i al . Edi t , modi f y, and add t o t he i nf or mat i on cont ai ned i n Tabl es 1 and 2 as r equi r ed f or t he pr oj ect . Use Tabl e 6. 8. 3A and Tabl e 6. 8. 3B i n ASHRAE 90. 1 f or mi ni mum t hi ckness i n bui l di ngs

SECTION 23 07 00 Page 35 spatrick Cloud

TABLE 2

Piping Insulation Thickness ( mminch ) For flexible cellular foam the thickness should be 13mm instead of 15mm. Economic thickness or prevention of condensation is the basis of these tables. If prevention of condensation is the criterion, the ambient temperature and relative humidity must be stated. Do not use integral wicking material in Chilled water applications exposed to outdoor ambient conditions in climatic zones 1 through 4.

Service

Material Tube And Pipe Size (mm) (inch)

<25<1 25-<40 1-<1.5

40-<100 1.5-<4

100-<200 4-<8

> or = 200 >8

Mineral Fiber 401.5 401.5 502 502 502

401.5 * 502* 652.5 * 803* 903.5 *

Calcium Silicate 652.5 803 100 4 100 4 115 4.5

Cellular Glass 502 652.5 803 803 803

Perlite 652.5 803 100 4 100 4 115 4.5

Flexible Elastomeric Cellular 251 251 251 N/A N/A

Exposed Lavatory Drains, Exposed Domestic Water Piping & Drains to Areas for Handicapped Personnel

Flexible Elastomeric Cellular 130.5 130.5 130.5 130.5 130.5

Horizontal Roof Drain Leaders (Including Underside of Roof Drain Fittings)

Cellular Glass 401.5 401.5 401.5 401.5 401.5

Flexible Elastomeric Cellular 251 251 251 N/A N/A

Faced Phenolic Foam 251 251 251 251 251

Condensate Drain Located Inside Building

Cellular Glass 401.5 401.5 401.5 401.5 401.5

Flexible Elastomeric Cellular 251 251 251 N/A N/A

Medium Temperature Hot Water, Steam and Condensate ( 122 to 176 Degrees C 251 to 350 Degrees F )

Mineral Fiber 401.5 803 803 100 4 100 4

652.5 * 80* 903.5 *

Calcium Silicate 652.5 903.5 115 4.5 115 4.5 125 5

SECTION 23 07 00 Page 39

TABLE 2

Piping Insulation Thickness ( mminch ) For flexible cellular foam the thickness should be 13mm instead of 15mm. Economic thickness or prevention of condensation is the basis of these tables. If prevention of condensation is the criterion, the ambient temperature and relative humidity must be stated. Do not use integral wicking material in Chilled water applications exposed to outdoor ambient conditions in climatic zones 1 through 4.

Service

Material Tube And Pipe Size (mm) (inch)

<25<1 25-<40 1-<1.5

40-<100 1.5-<4

100-<200 4-<8

> or = 200 >8

Perlite 652.5 903.5 115 4.5 115 4.5 125 5

Flexible Elastomeric Cellular 251 251 251 N/A N/A

High Temperature Hot Water & Steam ( 177 to 371 Degrees C 351 to 700 Degrees F )

Mineral Fiber 652.5 803 803 100 4 100 4

Calcium Silicate 100 4 115 4.5 150 6 150 6 150 6

Perlite 100 4 115 4.5 150 6 150 6 150 6

Brine Systems Cryogenics ( -34 to -18 Degrees C -30 to 0 Degrees F )

Cellular Glass 652.5 652.5 803 803 903.5

Flexible Elastomeric Cellular 251 251 N/A N/A N/A

Brine Systems Cryogenics ( -18 to 1.11 Degrees C 0 to 34 Degrees F )

Cellular Glass 502 502 502 652.5 803

Flexible Elastomeric Cellular 251 251 251 N/A N/A

3.2.2 Aboveground Cold Pipelines

NOTE: I nsul at i on may be omi t t ed on domest i c col d- wat er pi pi ng and i nt er i or r oof dr ai ns wher e condensat i on and f r eezi ng ar e not pr obl ems.

However , t he desi gner must mai nt ai n condi t i oned space cont r ol under cool i ng condi t i ons - meet t he ener gy budget , not al l ow condensat i on f or mat i on and not al l ow f r eezi ng.

The following cold pipelines for minus 34 to plus 16 degrees C minus 30 to plus 60 degrees F , shall be insulated in accordance with Table 2 except those piping listed in subparagraph Pipe Insulation in PART 3 as to be

SECTION 23 07 00 Page 40