TABLE 1

Insulation Material for Piping

Service

Material Specification Type Class VR/VB Req'd

Perlite ASTM C610 No

Flexible Elastomeric Cellular ASTM C534/C534M I 2 No

Cold Domestic Water Piping, Makeup Water & Drinking Fountain Drain Piping

Cellular Glass ASTM C552 II 2 No

Flexible Elastomeric Cellular ASTM C534/C534M I No

Hot Domestic Water Supply & Recirculating Piping (Max 93 C 200 F )

Mineral Fiber ASTM C547 I 1 No

Cellular Glass ASTM C552 II 2 No

Flexible Elastomeric Cellular ASTM C534/C534M I No

Faced Phenolic Foam ASTM C1126 III Yes

Refrigerant Suction Piping ( 1.67 degrees C 35 degrees F nominal)

Flexible Elastomeric Cellular ASTM C534/C534M I No

Cellular Glass ASTM C552 II 1 Yes

Compressed Air Discharge, Steam and Condensate Return ( 94 to 121 Degrees C 201 to 250 Degrees F

Cellular Glass ASTM C552 II No

Mineral Fiber ASTM C547 I 1 No

Calcium Silicate ASTM C533 I No

Faced Phenolic Foam ASTM C1126 III Yes

Perlite ASTM C610 No

Flexible Elastomeric Cellular ASTM C534/C534M I 2 No

Exposed Lavatory Drains, Exposed Domestic Water Piping & Drains to Areas for Handicapped Personnel

Flexible Elastomeric Cellular ASTM C534/C534M I No

Horizontal Roof Drain Leaders (Including Underside of Roof Drain Fittings)

Flexible Elastomeric Cellular ASTM C534/C534M I No

Faced Phenolic Foam ASTM C1126 III Yes

Cellular Glass ASTM C552 III Yes

SECTION 23 07 00 Page 34 spatrick Cloud

TABLE 2

Piping Insulation Thickness ( mminch ) For flexible cellular foam the thickness should be 13mm instead of 15mm. Economic thickness or prevention of condensation is the basis of these tables. If prevention of condensation is the criterion, the ambient temperature and relative humidity must be stated. Do not use integral wicking material in Chilled water applications exposed to outdoor ambient conditions in climatic zones 1 through 4.

Service

Material Tube And Pipe Size (mm) (inch)

<25<1 25-<40 1-<1.5

40-<100 1.5-<4

100-<200 4-<8

> or = 200 >8

Flexible Elastomeric Cellular 251 251 251 N/A N/A

Mineral Fiber with Wicking Material

251 401.5 401.5 502 502

Heating Hot Water Supply & Return, Heated Oil (Max 121 C 250 F )

Mineral Fiber 401.5 401.5 502 502 502

Calcium Silicate 652.5 652.5 803 803 803

Cellular Glass 502 652.5 753 803 803

Perlite 652.5 652.5 803 803 803

Flexible Elastomeric Cellular 251 251 251 N/A N/A

Cold Domestic Water Piping, Makeup Water & Drinking Fountain Drain Piping

Cellular Glass 401.5 401.5 401.5 401.5 401.5

Flexible Elastomeric Cellular 251 251 251 N/A N/A

Hot Domestic Water Supply & Recirculating Piping (Max 93 C 200 F )

Mineral Fiber 251 251 251 401.5 401.5

Cellular Glass 401.5 401.5 401.5 502 502

Flexible Elastomeric Cellular 251 251 251 N/A N/A

Refrigerant Suction Piping ( 1.67 degrees C 35 degrees F nominal)

Flexible Elastomeric Cellular 251 251 251 N/A N/A

Cellular Glass 401.5 401.5 401.5 401.5 401.5

Compressed Air Discharge, Steam and Condensate Return ( 94 to 121 Degrees C 201 to 250 Degrees F