1/4" JOINT FILLER
S.O.G. SEE PLAN
ROUGHENED SURFACE WITH
1/4" AMPLITUDE
(3)-#5 LONG. DIRECTION
& #5 @ 12" O.C.
TRANSV. DIRECTION
METAL STUDS BY
METAL STUD MANUF.
BRICK, SEE ARCH.
FULLY GROUT BEHIND
BRICK BELOW GRADE
TO 3" ABOVE GRADE
T/ SLAB
SEE PLAN
FINISH GRADE
SEE CIVIL
#5 @ 12" O.C. HORIZ. & VERTI.
DIRECTION AT EACH FACE
DOWELS WITH STD. 90 DEG.
HOOKS, MATCH AND LAP VERT.
WALL REINF.
1-#5 CONT. @ TOP
#3 @ 12" O.C.
4" MIN 4" MIN
2'-0"
B2
8" B1
E.O.S.
B1 = 8" AT 8" WIDE METAL STUDS
= 6" AT 6" WIDE METAL STUDS
B2 = 1'-4" AT 8" WIDE METAL STUDS
= 1'-2" AT 6" WIDE METAL STUDS
3" SLAB INSULATION PER ARCH.
ISOLATION JOINT
S.O.G. SEE PLAN
3-#5 @ TOP AND
BOTTOM AT EACH WAY
3'-0"
EXISTING
STRUCTURE
T/ SLAB
SEE PLAN
SEE DETAIL C3/S-302 FOR
TYP. PIER REINF.
ROUGHENED SURFACE
WITH 1/4" AMPLITUDE
8"
#5 X 1'-6" LONG @ 12"O.C.
SET IN EPOXY EACH WAY
WITH 6" MIN. EPOXY
EMBEDMENT INTO
EXISTING WALL
#5 X 1'-6" LONG @ 12"O.C.
SET IN EPOXY WITH 6"
MIN. EMBEDMENT INTO
EXISTING FOOTING
SEPARATE POUR
AROUND COLUMN
CONTRACTOR TO FIELD VERIFY EXISTING TOP OF FOOTING LOCATION TO
MATCH NEW FOOTING ELEVATIONS WITH EXISTING FOOTING ELEVATIONS
(3) TIES WITHIN TOP 5"
ISOLATION JOINT
S.O.G. SEE PLAN
SEE PLAN FOR FOOTING
SIZE AND REINF. INFO
T/ SLAB
SEE PLAN
ROUGHENED SURFACE
WITH 1/4" AMPLITUDE
CL
SEPARATE POUR
AROUND COLUMN
BRICK, SEE
ARCH.
FINISH GRADE
SEE CIVIL
EQ EQ
STL COLUMN, SEE PLAN FOR
SIZE AND ORIENTATION
DETAIL A-A
#4 TIES @ 12" O.C.
14 #7 DOWELS
CONTINUE WALL
REINFORCEMENT
THROUGH PIER
1'-2" 1'-2"
2'-4"
E.O.S.
CONTINUE WALL
REINFORCEMENT
THROUGH PIER
VARIES
VARIES
3" SLAB
INSULATION
PER ARCH.
(3) TIES WITHIN TOP 5"
SEE SCHEDULE
FLOOR SLAB
C L
R
1/2" PJF
COLUMN, SEE PLAN
3" CLR. (TYP.)
SEE SCHEDULE FOR
FOOTING REINFORCEMENT
SPREAD
FOOTING,
SEE PLAN
SEPARATE POUR
AROUND COLUMN
GRANULAR FILL
COMPACTED SUBGRADE
±1 1/2" NON-SHRINK GROUT
T/ SLAB
SEE PLAN
T/ FOOTING
SEE PLAN
DETAIL A-A
2'-4"
1'-2" 1'-2"
#4 TIES @ 12" O.C.
14 #7 DOWELS
ROUGHENED SURFACE
WITH 1/4" AMPLITUDE
(3) TIES WITHIN TOP 5"
FOR ISOLATION JOINT
SEE DETAIL C1/S-501
BRACE AND BEAM CONNECTIONS ARE
PART OF THE DELEGATED CONNECTION
DESIGN.
NOTE:
P
ANCHOR RODS
T/ PIER
WP
HSS OR W-SECTION
COLUMN, SEE PLAN
3/8" GUSSET PL.
(TYP.)
5/16
PIER
5/16
C L B
R A C E
HSS BRACE, SEE ELEVATIONS
FOR SIZE AND CONNECTION
DESIGN FORCES (TYP.)
BASE PLATE
FC1
COMBINED FOOTING SCHEDULE
2'-0"20'-0" x 6'-0"
FOOTING
TYPE
THICKNESSLENGTH x WIDTH
TOP BOTTOM
LONGITUDINAL BARS
(LONG BARS)
TOP BOTTOM
TRANSVERSE BARS
(SHORT BARS)
2'-0"26'-0" x 6'-0" (23) #7 (8) #7
2'-0"32'-0" x 6'-0" (30) #7 (8) #7
2'-0"36'-0" x 6'-0" (32) #7 (8) #7
(18) #6 (8) #6
FC2
FC4
FC6
(23) #6
(30) #6
(32) #6
(8) #6
(8) #6
(8) #6
2'-0"45'-0" x 6'-0" (39) #7 (8) #7FC7 (39) #6 (8) #6
(18) #7 (8) #7
BRACE AND BEAM CONNECTIONS ARE
PART OF THE DELEGATED CONNECTION
DESIGN.
NOTE:
P
ANCHOR RODS
T/ PIER
WP
3/8" GUSSET PL.
(TYP.)
5/16
PIER
5/16
C L B
R A C E
HSS BRACE, SEE ELEVATIONS
FOR SIZE AND CONNECTION
DESIGN FORCES (TYP.)
STEEL BASE PLATE
3/4"x1'-4"x3'-0"
P
S.O.G. SEE PLANEXISTING
STRUCTURE
T/ SLAB
SEE PLAN
#5 X 1'-6" LONG SMOOTH
DOWELS @ 12"O.C. SET
IN EPOXY WITH 6" MIN.
EPOXY EMBEDMENT INTO
EXISTING WALL
S.O.G. SEE PLAN
T/ SLAB
SEE PLAN
FINISH GRADE
SEE CIVIL
NO PIPES SHALL PASS
THRU FOOTINGS
SLEEVE
PIPE TO CLEAR SLEEVE
BY 1/2" ALL AROUND
P O
N D
-F S
B J oi nt
V en tu re
P ar kw ay
L an e, S ui te
P ea ch tr ee C or ne rs , G
A
P ho ne : 6
.3
.7 w w w .p on dc o.
co m
A D
A L
B
R E
G
IO
N A
L M
X T
R A
IN
IN
G F
A C
IL
IT
Y
P R
O J E
C T
N U
M B
E R
P
T F
L
J o in t B a s e
M c G u ir e
-D ix
-L a k e h u rs t, N e w
J e rs e y
M A
Y
N
Y D
A /E
B O
R D
E R
F
IL
E N
A M
E
S u b m it te d b y
P lo t D a te
F
S B
A N
S I D
U S
A
R M
Y E
N G
IN
E
E R
D
IS
T R
IC
T
N E
W Y
O R
K h tt p /w w w
.n a n .u s a c e .a rm y .m il
F S
B
- -S O
L
IC
IT
A
T
IO
N N
O
F
IL
E N
A M
E
D W
N B
Y
C K
D B
Y
D E
S
IG
N E
D B
Y
D A
T E
S
IZ
E
S U
B M
IT
T
E D
B Y
P L O
T D
A T
E
C O
N T
R A
C T
N O
P L O
T T
E D
B Y
US Army Corps of Engineers
New York District
D E
S C
R
IP
T
IO
N M
A R
K A
P P
R
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E A
P P
R
D
2 3
C
4 5
A
B
SHEET
REFERENCE
NUMBER
0 1"
THIS BAR IS ONE INCH ON
ORIGINAL DRAWING
IF NOT ONE INCH ON THIS
SHEET, ADJUST SCALES
ACCORDINGLY
xx xx c -x xx .d w g
C U s e rs
\c re lli n b \D o c u m e n ts
\1 -R
M T
F v S tr u c tu ra l_ c re lli n b .r v t
/6
/2
:3 :1
P
M
/6
/2
:3
:1
P
M
S-301
F O
U N
D A
T
IO
N S
E C
T
IO
N S
A N
D D
E T
A I L
S
B J C
S A
C M
W H
S A
C
SCALE: N.T.S.
C1
FOUNDATION WALL SECTION
SCALE: N.T.S.
C2
PIER AND EXISTING WALL SECTION
SCALE: N.T.S.B1
FOUNDATION WALL AT PIER SECTION
SPREAD FOOTING SCHEDULE
FOOTING TYPE WIDTH LENGTH THICKNESS REINFORCEMENT
F1 3'-0" 3'-0" 1'-0" (3) - #5 BARS E.W. BOT
F2 3'-6" 3'-6" 1'-0" (4) - #5 BARS E.W. BOT
F3 4'-0" 4'-0" 1'-6" (5) - #5 BARS E.W. BOT
F4 6'-0" 6'-0" 1'-6" (5) - #5 BARS E.W., T&B
F6 9'-0" 9'-0" 2'-0" (11) - #6 BARS E.W., T&B
SCALE: N.T.S.
C4
SPREAD FOOTING AT PIER SECTION
SCALE: N.T.S.
B2
SCHEMATIC BRACE CONNECTION
SCALE: N.T.S.
B4
FOOTING SCHEDULE
SCALE: N.T.S.A1
SCHEMATIC BRACE CONNECTION
SCALE: N.T.S.A2
EXISTING PIER SECTION BTWN COLUMNS
SCALE: N.T.S.A4
PIPE PASSING THRU FDN STEM WALL
A
M E
N D
M E
N T
/0
/1
EXISTING SWITCHBOARD 'MSS', 480/277V, 3PH, 4W;
A
/3 P
R T
D L S
IG
FEEDER SCHEDULE:
SIX 4-INCH CONDUITS, EACH WITH FOUR 500 KCMIL.
PROVIDE TWO 4-INCH SPARE CONDUITS WITH PULL
STRING.
3-1/0&1#6G.-2"C.
TWO 3 1/2-INCH CONDUITS, EACH WITH FOUR 600
KCMIL AND ONE 1/0 GND.
4-1/0&1#6G.-2"C.
4#4&1#10G-1-1/4"C.
4-500KCMIL&1#2G-3-1/2"C.
FIVE 3 1/2-INCH CONDUITS, EACH WITH FOUR 500
KCMIL AND ONE 4/0 GND.
4-3/0&1#6G-2-1/2"C.
2#12&1#12G.-3/4"C.
NEW 'T2324'
1500KVA
12,470V: 480/277V
3PH, 4W PMT
A
/3 P
PNL
'H1M1'
'T-DPL1'
NEW 225KVA
480: 208/120V
N
G
M
A
/3 P
EXISTING MGB
A
/3 P
A
/3 P
A
/3 P
PNL
'TP-5'
150A
MCB
PNL
'TP-1'
150A
MCB
A
/3 P
PNL
'TP-2'
150A
MCB
A
/3 P
PNL
'TP-3'
150A
MCB
A
/3 P
PNL
'TP-4'
150A
MCB
PNL
'H1S'
A
/3 P
PNL
'H11'
PANEL 'DPL1' 800A, 120/208V, 3PH, 4W
A
/3 P
PNL
'L12'
A
/3 P
PNL
'H1-2'
PNL
'H21'
A
/3 P
A
/3 P
3#2&1#2G-5"C., 15KV RATED, 1 SPARE 5"C.
A
/3 P
A
/3 P
SPARE
#3/0G.
PNL
'H2M1'
A
/3 P
CHILLER
'CH-1'
M
A
/3 P
PNL
'IT-1'
150A
MCB
1 1
T2216 T2309A T2323
SC2200-1
A
/3 P
PNL
'L13' 150A
MCB
A
/3 P
SPD
SPARE
EXISTING
PAD MOUNTED
SWITCH
NEW SWITCHBOARD 'SWBD1', 2000A, 480/277V, 3PH, 4W;
A
/3 P
L S
IG
A
/3 P
R T
D L S
IG
A
/3 P
L S
IG
A
/3 P
L S
IG
PNL
'KC-1'
A
/3 P
L S
IG
PNL
'KC-2'
A
/3 P
L S
IG
A
/3 P
8 3 9
A
/3 P
SPARE
A
/3 P
SPARE
A
/3 P
A
/3 P
A
/2 P
L S
IG
FACP
SPARE
LSIG
SPARE
LSIG
SPARE
LSIG
G
A
/2 P
MINI POWER-
ZONE PANEL
UL 1449
A
/3 P
SPD
UL 1449
# 4/0G-1"C
SCCR: 42,000
SCCR: 22,000
EXISTING
T2216
EXISTING
MH-2309B
MH-2309A
MH-2302
3#350MCM, 15KV RATED, IN 5"C.
AND ONE 5"C. SPARE WITH PULL-
STRING.
3#2AWG, 15KV RATED, IN 2"C. AND
ONE 2"C. SPARE WITH PULL-
STRING.
400 HZ
CONVERTER
A
/3 P
(3)2000:5
#4/0 TO BUILDING
STEEL
#6 TO FACP
#3/0 TO TMGB
#4/0 TO EXISTING
COUNTERPOISE
#4/0 TO DOMESTIC
WATER PIPE
NEW MGB TO BE MOUNTED IN
ELECTRICAL ROOM 172
# 4/0G-1"C
P O
N D
-F S
B J oi nt
V en tu re
P ar kw ay
L an e, S ui te
P ea ch tr ee C or ne rs , G
A
P ho ne : 6
.3
.7 w w w .p on dc o.
co m
A D
A L
B
R E
G
IO
N A
L M
X T
R A
IN
IN
G F
A C
IL
IT
Y
P R
O J E
C T
N U
M B
E R
P
T F
L
J o in t B a s e
M c G u ir e
-D ix
-L a k e h u rs t, N e w
J e rs e y
M A
Y
N
Y D
A /E
B O
R D
E R
F
IL
E N
A M
E
S u b m it te d b y
P lo t D a te
F
S B
A N
S I D
U S
A
R M
Y E
N G
IN
E
E R
D
IS
T R
IC
T
N E
W Y
O R
K h tt p /w w w
.n a n .u s a c e .a rm y .m il
F S
B
- -S O
L
IC
IT
A
T
IO
N N
O
F
IL
E N
A M
E
D W
N B
Y
C K
D B
Y
D E
S
IG
N E
D B
Y
D A
T E
S
IZ
E
S U
B M
IT
T
E D
B Y
P L O
T D
A T
E
C O
N T
R A
C T
N O
P L O
T T
E D
B Y
US Army Corps of Engineers
New York District
D E
S C
R
IP
T
IO
N M
A R
K A
P P
R
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E A
P P
R
D
2 3
C
4 5
A
B
SHEET
REFERENCE
NUMBER
0 1"
THIS BAR IS ONE INCH ON
ORIGINAL DRAWING
IF NOT ONE INCH ON THIS
SHEET, ADJUST SCALES
ACCORDINGLY
xx xx c -x xx .d w g
C U s e rs
\w o rt h in g to n j\ D o c u m e n ts
\1 -R
M T
F v M
E P
W o rt h in g to n J p o n d c o .c o m
.r v t
/6
/2
:5
:5
A
M
/6
/2
:5
:5
A
M
E-602
E L E
C T
R
IC
A L O
N E
-L
IN
E D
IA
G
R A
M
T H
J W
J S
J W
SCALE: N.T.S.
A2
ELECTRICAL ONE-LINE DIAGRAM
GENERAL NOTES:
1. SEE E-001 AND E-002 FOR GENERAL ELECTRICAL
NOTES, ABBREVIATIONS, AND SYMBOLS.
KEYNOTES:
CONTRACTOR SHALL PROVIDE BASE STANDARD NEW SMART
METER. BASE STANDARD METER SHALL BE EIG NEXUS #
1262/1272 METER PRODUCT SERIES OR EQUAL. METER SHALL BE
SOCKET MOUNTED AS A SEPERATE ENCLOSURE ON THE SIDE OF
THE SWBD. TO BE COMPLETED WITH NECESSARY INSTRUMENT
TRANSFORMERS, SENSORS, AND TRANSDUCERS. PROVIDE ALL
WIRING AND CONDUITS AS NECESSARY.
NEW BREAKER SHALL MATCH EXISTING PANELS SCCR RATING.
REFER TO E-606 FOR CONDUCTOR AND CONDUIT SIZE.
SPLICE NEW PRIMARY FEEDER IN EXISTING MANHOLE.
CIRCUIT BREAKER SHALL BE LOCKABLE IN THE "ON" POSITION
WITH HANDLE PAINTED RED. PROVIDE NAMEPLATE TO READ
"FIRE PROTECTION SAFETY EQUIPMENT" (RED WITH WHITE
LETTERS).
PROVIDE MINI POWER ZONE WITH A 20A/2P PRIMARY CIRCUIT
BREAKER, 7.5VA, 480-240/120V, 1-PHASE TRANSFORMER, 40A, 2-
POLE SECONDARY MAIN, AND SIX 20A 1-POLE BRANCH CIRCUIT
BREAKERS. REFEED EXISTING FACP.
COORDINATE BACKFEED OF EXISTING SWITCHBOARD "MSS'
WITH ALL TRADES PRIOR TO INSTALLATION. BACKFEED
INSTALLATION MUST BE COMPLETE PRIOR TO DISTURBING
EXISTING UNDERGROUND UTILITIES UNDER NEW AREA 'A'.
LSIG BREAKERS TO BE PROVIDED WITH MAINTENANCE SWITCH
WITH LOCAL STATUS INDICATOR FOR ARC FLASH MITIGATION.