Amendment A00003 Sheet C-11-Revised 04MAR21.pdf

PDF 1 MB Posted

Attached to
W912DR21B0007 | Third High Reservoir Federal contract opportunity
Solicitation number
W912DR21B0007
Issued by
Department of the Army Corps of Engineers Engineering District Baltimore

About this file

This document is an amendment to construction drawings for improvements to the Third High Reservoir. Key details include specifications for reinforced concrete structures like outlet pipes, manholes, and foundations with a minimum compressive strength of 4,000 psi. Reinforcing steel is required to meet ASTM A615 Grade 60. Concrete cover depths and placement procedures are defined. The related federal contract opportunity is solicitation number W912DR21B0007 for maintenance and improvements to the Third High Reservoir issued by the Department of the Army Corps of Engineers Baltimore District. The drawings provide construction requirements for reinforced concrete elements of the reservoir improvements.

View the file

Other files for this federal contract opportunity

Show all 17

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SECTION A

60''

RUNGS (BEYOND)

OUTLET

CONC. f'c=4000 psi

C

L R

C

L R

30'' DIA

10"

16''

#6 @6'' O.C. EACH

WAY TOP & BOTTOM

PROVIDE A 12'' LAYER OF

LIMEROCK WITH 3/4'' MAX. SIZE

COMPACTED TO 95% MODIFIED

PROCTOR TEST (TYP)

C L A

S S

B

L A

P

S P

L I C

E

T

Y P

#6 @6'' O.C. VERT.

EACH FACE

O

C

H

O R

I Z

O N

T A

L

E

F

O

C

H

O R

O

C

H

O R

C

L R

#5 @6'' O.C.

EACH WAY

TOP & BOTTOM

MJ LONG SLEEVE

CONNECTION

MJ LONG SLEEVE

CONNECTION

AUTOMATIC

COMBINATION AIR

VALVE

STANDARD 30" DIA

WATERTIGHT MANHOLE

FRAME AND COVER

WWF 4x4 - W1.4 x W1.4

16''

#5 @6'' O.C.

EACH WAY &

EACH FACE

SEE DETAIL A

ON SHEET

C

L R

'' DEEP

SHEAR KEY (TYP)

3" CLR

(TYP)

2" CLR

(TYP)

3" CLR

(TYP)

EL. 401.0

EL. 406.0

EL. 386.0

EL. 387.0

C

L R

C

L R

10"

'' X 6'' X L RUBBER

WATERSTOP (TYP)

RUBBER

GASKET

2" CORPORATION

STOP SIDE

12'' 12''

EXISTING 24"

BLOW-OFF

DRAIN

PROJECTED

BACK

4"

D

I

A

2"

TYP

7 8

2"

4"

PLAN

PRESSURE PLATE RING

PLAN

PRESSURE PLATE

8''

4''

PL

8''

4''

2''

2''

2''

B B

SECTION B-B

DETAIL A

DRILL 8 -9/16"

HOLES

CHISELED

ARROW

DRILL AND TAP STD

1/2" THREAD - 8 HOLES

CHISELED ARROW

8 - 1/2" ANCHORS

8 - #4 ANCHORS OR 1/2'' x 8'' (LENGTH

AFTER WELD) ELECTRICALLY WELDED

STUDS, NELSON H4L OR EQUAL

DRILL AND TAP

1/2''- NC THREAD

8 - 1/2'' X 1 1/2'' STAINLESS

STEEL Hex HEAD BOLTS

GASKET SEE NOTE 3

1/2" BAR HANDLE

PLAN VIEW (EL. 386.0)

I N

T L

E T

OUTLET

A

C-11

1'-4" 5'-0" 1'-4"

D

I

A

#6 @6 T&b EW t=20''

PROVIDE STD. HOOK AT

ENDS OF ALL

REINFORCEMENT

3'-6'' X 3'-6'' CORNER

BARS OF THE SAME

SIZE AND SPACING

SHOWN ON SECTION

DETAIL 1/C-09 (TYP)

1'-0" 1'-0"

MIDDLE STRIP

#3 THRU

#11 BARS

#14 THRU

#18 BARS

Lcd = COMPRESSION DEVELOPMENT LENGTH

Ltd = TENSION DEVELOPMENT LENGTH (WITHOUT HOOKS)

LAP SPLICE NOT PERMITTED; USE MECH.

SPLICES PER ACI 318, SECTION 12.14.3

USE 30 BAR DIAMETER FOR ALL CONC.

STRENGTHS.

COMPRESSION SPLICE

LENGTH SCHEDULE (Lc)

NOTE:

1- TOP BARS MUST BE CONCENTRATED WITHIN WIDTH OF THE COLUMN PLUS

1.5 ON EACH SIDE OF THE COLUMN (ACI 13.5.3.2 AND 13.5.3.4).

2- INTEGRITY REINFORCEMENT IS REQUIRED (ACI 13.3.8.5). ALL BOTTOM BARS

IN THE COLUMN STRIP MUST BE CONTINUOUS OR SPLICED OVER THE

SUPPORT WITH CLASS "B" TENSION LAP SPLICES. AT LEAST TWO OF THE

COLUMN STRIP BOTTOM BARS IN EACH DIRECTION MUST PASS WITHIN THE

COLUMN CORE AND BE ANCHORED AT EXTERIOR SUPPORTS.

NOTE:

1. TABULATED VALUES ARE BASED ON A MINIMUM YIELD STRENGTH OF 60,000 PSI AND

NORMAL-WEIGHT CONCRETE. LENGTHS ARE IN INCHES. ALL LAP SPLICE ARE CLASS "B"

SPLICES.

2. TENSION DEVELOPMENT LENGTHS AND TENSION LAP SPLICE LENGTHS ARE CALCULATED

PER ACI 318-11, SECTIONS 12.2.3 AND 12.15, RESPECTIVELY, WITH BAR SIZES LIMITED TO #3

THROUGH #11.

3. SPLICE LENGTHS FOR TOP BARS OF BEAMS & SLABS THICKER THAN 12" HAVE BEEN

MULTIPLIED BY A FACTOR OF 1.3 Ld PER ACI 350-06 & 318-11

B

A R

D I A

TENSION

EMBEDMENT

COMPRESSION AND TENSION DEVELOPMENT LENGTH SCHEDULE

3000 P.S.I. 4000 P.S.I. 5000 P.S.I. 6000 P.S.I. 8000 P.S.I. 10000 P.S.I.

BAR

SIZE

Lcd Ltd Lcd Ltd Lcd Ltd Lcd Ltd Lcd Ltd Lcd Ltd

#4

#5

#6

#7

#8

#9

#10

#11

#14

#18

TENSION SPLICE LENGTH SCHEDULE

3000 P.S.I. 4000 P.S.I. 5000 P.S.I. 6000 P.S.I. 8000 P.S.I. 10000 P.S.I.

BAR

SIZE

TOP

BARS

#4

#5

#6

#7

#8

#9

#10

#11

#14

#18

LAP SPLICE, NOT PERMITTED; USE MECH. SPLICES PER ACI 318, SECTION 12.14.3

OTHER

BARS

TOP

BARS

OTHER

BARS

TOP

BARS

OTHER

BARS

TOP

BARS

OTHER

BARS

TOP

BARS

OTHER

BARS

TOP

BARS

OTHER

BARS

DRAWING NUMBER PLATE

SCALE:

DATE: SHEET:

WASHINGTON AQUEDUCT

THIRD HIGH RESERVOIR, WASHINGTON, DC

MAINTENANCE AND IMPROVEMENTS

NOVEMBER 2019

THIRD HIGH RESERVOIR

Nova Consulting

U.S. ARMY ENGINEER DISTRICT, BALTIMORE

CORPS OF ENGINEERS

BALTIMORE, MARYLAND

HAROLD V. AIKEN, PE

AS SHOWN

80.3-5.14 14

C-11

PRESSURIZED MANHOLE DETAIL

PRESSURIZED PLATE DETAIL

GENERAL SHEET NOTES

GENERAL:

1. MANHOLE IS DESIGNED FOR A MAXIMUM PRESSURE OF 20 PSI.

CONCRETE:

1. CONCRETE DESIGN AND REINFORCEMENT SHALL BE IN ACCORDANCE WITH "CODE

REQUIREMENTS FOR ENVIRONMENTAL ENGINEERING CONCRETE STRUCTURES"

(ACI 350-06) AND "SPECIFICATIONS FOR STRUCTURAL ENVIRONMENTAL CONCRETE

STRUCTURES" (ACI 350.5).

2. ALL CONCRETE SHALL BE FROST RESISTANT NORMAL WEIGHT CONCRETE (145

PCF) WITH 5% TOTAL AIR CONTENT & SHALL ACHIEVE A 28-DAY COMPRESSIVE

STRENGTH (F'c) OF 4000 PSI. THE DESIGN MIX SHALL HAVE A MAXIMUM

WATER-CEMENT RATIO OF 0.42 BY WEIGHT, & A MAXIMUM OF 5 BAGS OF CEMENT IN

EA. CUBIC YARD OF CONCRETE. SUBMIT PROPOSED MIX DESIGN FOR REVIEW

PRIOR TO FIELD POURING. MIX SHALL BE IDENTIFIED BY MIX NUMBER OR OTHER

POSITIVE IDENTIFICATION.

3. ALL CEMENT SHALL CONFORM TO ASTM C150, TYPE 1 & CONCRETE MAXIMUM

AGGREGATE SIZE SHALL BE 3/4" FOR FOOTINGS, WALLS, BEAM & SLABS

CONFORMING TO ASTM C33.

4. FOR ALL CONCRETE TO BE PLACED IN SLABS (INCLUDING SLABS ON GRADE) AND

WALL PANELS, THE SLUMP SHALL NOT EXCEED 4" (±1"). NO WAIVERS OF THIS

REQUIREMENT SHALL BE CONSIDERED. SLUMP FOR PUMPED CONCRETE SHALL

NOT EXCEED 7(±1")".

5. PLACING OF CONCRETE IN ALL REINFORCED COLUMNS AND WALLS SHALL BE IN

EQUAL LIFTS NOT EXCEEDING 7'-6" IN HEIGHT. ALL DOWELS FOR COLUMNS AND

WALLS SHALL BE SECURED IN POSITION PRIOR TO CONCRETING.

6. ALL CONCRETE STRUCTURAL COMPONENTS SHALL HAVE ITS STRENGTH TESTED IN

ACCORDANCE WITH ASTM STANDARDS & ACI 350-06. A MINIMUM OF FOUR TEST

CYLINDERS MUST BE TAKEN EVERY 50 CUBIC YARDS OR LESS OF CONCRETE

PRIOR TO POURING. TESTS SHALL BE MADE FOR 7 DAYS, TWO AT 28 DAYS & ONE

HELD IN RESERVE. CONTRACTOR SHALL PROVIDE THE STRUCTURAL ENGINEER'S

OFFICE COPIES OF THE CONCRETE TEST RESULTS FOR REVIEW, AS WELL AS

COPIES OF THE CONCRETE MIX DESIGN ALREADY APPROVED PRIOR TO USE.

7. MINIMUM CONCRETE COVER TO REINFORCING STEEL SHALL BE IN ACCORDANCE

WITH ACI 350-06 AND SHALL BE AS FOLLOWS:

ELEMENT: BOTTOM: TOP: SIDES:

FOUNDATION 3'' 2'' 2''

COLUMNS/WALLS - 2'' 3'' & 2''

SLAB ON GRADE 3'' 2'' 2''

EXTERIOR STRUCT. SLAB 2'' 2'' 2''

8. WALL & SLAB OPENINGS SHALL BE MADE BY BLOCKING BY INSTALLING THE

SLEEVES IN THE FORMWORK PRIOR TO PLACING CONCRETE. NEITHER CORE

DRILLING NOR CHIPPING OF ANY TYPE WILL BE PERMITTED. THE LOCATION OF ALL

OPENINGS SHALL BE COORDINATED WITH THE CIVIL, PLUMBING, ELECTRICAL &

MECHANICAL DRAWINGS.

9. IF REQUIRED, PROVIDE SLEEVES FOR PLUMBING AND ELECTRICAL OPENINGS IN

CONCRETE BEFORE PLACING IT. DO NOT CUT ANY REINFORCING WHICH MAY

CONFLICT. NOTIFY THE STRUCTURAL ENGINEER IN ADVANCE OF CONDITIONS NOT

SHOWN ON THE DRAWINGS.

10. IF APPLICABLE, CONCRETE ON EXPOSED BALCONIES, SLABS, BEAMS AND STAIRS

SHALL HAVE THE TOP SURFACE COATED WITH "ALKYL-ALKYOXY SILANE SEALER"

OR ENGINEER-APPROVED EQUAL.

11. THE CONTRACTOR SHALL EVACUATE ALL WATER FROM WITHIN FORMWORK

BEFORE PLACEMENT OF ANY CONCRETE. AFTER DEWATERING AND BEFORE

PLACING CONCRETE, RINSE THE REINFORCING STEEL CLEAN AND FREE OF ALL

DELETERIOUS MATERIAL.

12. THE MAXIMUM TIME ALLOWED FROM THE TIME THE MIXING WATER IS ADDED UNTIL

IT IS DEPOSITED IN ITS FINAL POSITION SHALL NOT EXCEED 1.5 HOURS (90 MINS.). IF

FOR ANY REASON THERE IS A LONGER DELAY, THE CONCRETE MUST BE

DISCARDED.

REINFORCING STEEL:

1. TO BE NEW BILLET STEEL CONFORMING TO THE LATEST ASTM A615 GRADE 60

SPECIFICATIONS, FABRICATED IN ACCORDANCE WITH MANUAL OF STANDARD

PRACTICE OF THE CRSI & PLACED IN ACCORDANCE WITH ACI 315 & ACI MANUAL OF

STANDARD PRACTICE.

2. COLUMN REINFORCEMENT: DOWELS TO BE SAME SIZE AND NUMBER AS VERTICALS

ABOVE. LAP 36 BAR DIAMETER OR MINIMUM OF 18" U.O.N. PROVIDE STANDARD

HOOKS FOR ALL VERTICAL REINFORCEMENT AT NON-CONTINUOUS COLUMNS.

3. ALL REINFORCING STEEL SHALL BE TIED DOWN AND INDEPENDENTLY SUPPORTED

ON CHAIRS AND SUPPORT BARS. REINFORCEMENT SHALL BE FREE OF MUD OIL OR

OTHER NONMETALLIC COATINGS THAT ADVERSELY AFFECT BONDING CAPACITY.

4. ALL DOWELS FOR COLUMNS AND WALLS TO BE SECURED IN POSITION PRIOR TO

CONCRETING. DRILLING OR PUSHING THE DOWELS INTO POSITION IN WET

CONCRETE IS NOT PERMITTED.

5. WELDED WIRE FABRIC (W.W.F.) SHALL CONFORM TO ASTM A-185. MINIMUM LAP OF

W.W.F. SHALL BE 6 IN. OR ONE FULL MESH, WHICHEVER IS GREATER.

6. ALL REINFORCING BARS MARKED "CONTINUOUS" SHALL BE LAPPED 36 BAR DIA. AT

SPLICES AND CORNERS UNLESS OTHERWISE NOTED. LAP CONTINUOUS TOP BARS

AT CENTER BETWEEN SUPPORTS AS REQUIRED. TERMINATE CONTINUOUS BARS

AT NON-CONTINUOUS ENDS WITH STANDARD HOOKS. U.O.N.

7. ALL WALLS AND COLUMNS SHALL BE DOWELED INTO FOOTINGS, WALLS, BEAMS,

OR SLABS WITH BARS OF THE SAME SIZE AND SPACING AS THE BARS ABOVE. USE

A (30) BAR DIAMETER LAP EXCEPT WHERE SPECIFICALLY INDICATED.

8. ALL REINFORCEMENT SHALL BE BENT COLD, UNLESS OTHERWISE PERMITTED BY

THE PROFESSIONAL ENGINEER IN WRITING. ALL TIES SHALL HAVE A 135 DEGREE

HOOKS.

9. ALL NEW REINFORCING STEEL THAT WILL BE WELDED SHALL MEET THE

REQUIREMENTS OF ASTM A706 GRADE 60 DEFORMED BARS.

SCALE: 1/2"=1'-0"

0 42

AutoCAD SHX Text h ON EACH SIDE OF THE COLUMN (ACI 13.5.3.2 AND 13.5.3.4).

AutoCAD SHX Text

FACE OF CONCRETE

AutoCAD SHX Text

STANDARD HOOK

AutoCAD SHX Text

REV

AutoCAD SHX Text

DATE

AutoCAD SHX Text

DESCRIPTION

AutoCAD SHX Text

BY

AutoCAD SHX Text US Army Corps

AutoCAD SHX Text of Engineers

AutoCAD SHX Text

A/E PRINCIPAL

AutoCAD SHX Text

SEAL:

AutoCAD SHX Text

APPROVED:

AutoCAD SHX Text

CIVIL

AutoCAD SHX Text

PRESSURIZED MANHOLE STRUCTURE DETAILS

AutoCAD SHX Text

SCALE : 1/2''=1'-0''

AutoCAD SHX Text C-09

AutoCAD SHX Text

AutoCAD SHX Text

SCALE : NTS

AutoCAD SHX Text C-11

AutoCAD SHX Text

AutoCAD SHX Text N

AutoCAD SHX Text N

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 3/21

AutoCAD SHX Text

ADDENDA #1

AutoCAD SHX Text

HVA

AutoCAD SHX Text

AutoCAD SHX Text

Sheets and Views
C-11

File details come from the government source that posted it. Updated .