This document summarizes questions received from potential offerors regarding solicitation number W912DR21B0007 for maintenance and improvements to the Third High Reservoir. Key details include the following:
The solicitation is for repair of an expansion joint, construction of new inlet and outlet buildings, installation of a reservoir mixing system and valves. Questions were asked regarding concrete repair requirements, availability of pricing schedules, geotechnical information, material types for existing infrastructure, cleaning requirements after work completion, progress payment terms, and attached documents referenced in the solicitation. The responses clarified scope details such as expansion joint repair being the only concrete work, no geotechnical data availability, materials types, and cleaning/disinfection requirements. Modifications to specifications removed soil overburden removal and clarified bypass pumping needs. Only expansion joint repairs are to be priced per the structural drawings.
View the file
Other files for this federal contract opportunity
Show all 17
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
3/5/2021 ProjNet: Logged In User https://www.projnet.org/projnet/binKornHome/index.cfm?strKornCob=BicAdminReportAll&strReportType=AllCOR 1/6
UNCLASSIFIED\\FOR OFFICIAL USE ONLY
Bid Inquiry Contracting Officers Report All Inquiries
Project: Third High Reservoir Maint and Imps Review: W912DR21B0007 (00001) (sorted by CommentID ) Displaying 15 inquiries.
Id Discipline Sheet Detail Spec 9068301 Construction Management S-04A 030135 Comment Classification: Unclassified\\For Official Use Only (U\\FOUO)
Section 030135.1.3, Concrete Repair Requirements, states that contractors shall base bid on estimated quantities of each type of concrete or joint repair as defined on the Contract Drawings and on the Price Schedule and as specified herein. Can you provide a copy of the Price Schedule or direct us to where this can be found in the contract documents? No estimated quantities have been published within the drawings or specifications.
By: James Claremont; Crom Corporation; (9199693084). On: Feb 17 2021. Forward request by email.
1-0 Evaluation Concurred. The entire expansion joint will be repaired per Contract Drawings (Sheet 04A can be used to calculate the LF of expansion joint. About
658LF). The cost is to be included in Item No. 0001 of the Price Schedule. There is no concrete repair included in the Scope of Work. The Price Schedule should be included in the Contract Bid Documents. By: Juan Prieto; Nova Consulting - Washington, DC; (2024992140) On: Feb 22 2021
2-0 Evaluation Concurred. Potential Cost Impact. The entire expansion joint will be repaired per Contract Drawings (Sheet 04A can be used to calculate the LF of expansion joint. About 658LF). The cost is to be included in Item No. 0001 of the Price Schedule. There is no concrete repair included in the Scope of Work.
The Price Schedule should be included in the Contract Bid Documents. Potential concrete repairs should not be included in bid estimates. Any required concrete repairs identified during construction would be addressed in a change order. There is no impact to the Scope because the Scope does not include concrete repairs. There is no amendment needed because the Concrete Repairs Specs defined in Section 03 01 35 will be applicable for any needed repair work identified during the field investigation. By: Nikolai Gurdian; Washington Aqueduct; (202-345-2734) On: Mar 04 2021
2-1 Government Response. The entire expansion joint will be repaired per Contract Drawings (Sheet 04A can be used to calculate the LF of expansion joint.
About 658LF). The cost is to be included in Item No. 0001 of the Price Schedule. There is no concrete repair included in the Scope of Work. The Price Schedule should be included in the Contract Bid Documents. Potential concrete repairs should not be included in bid estimates. Any required concrete repairs identified during construction would be addressed in a change order. There is no impact to the Scope because the Scope does not include concrete repairs. There is no amendment needed because the Concrete Repairs Specs defined in Section 03 01 35 will be applicable for any needed repair work identified during the field investigation By: Mark Andrews; Contracting Division; (4435258229) On: Mar 04 2021
2-2 Government Response. The text below appends or clarifies ALL previous replies.
Note that an amendment was added to Specs Section 03 01 35 Par. 1.3 to clarify that bid amount should be based only on joint repair and necessary concrete repair quantity and pricing would be determined after contract award. By: Nikolai Gurdian; Washington Aqueduct; (202-345-2734) On: Mar 04 2021
Current Request Status: Request Closed Information for this report is procurement sensitive.
9083827 Civil 31 23 00.00 20 Comment Classification: Unclassified\\For Official Use Only (U\\FOUO)
Can any geotechnical information be provided for the areas of deep excavation for the new structures and drain line? If not, please confirm bidders should assume the excavation for the pressurized manhole and 24" drain line contain imported borrow material from when the reservoir was constructed and all material is acceptable for reuse.
By: Brad Gribble; Maverick Construction; (4432626554). On: Feb 24 2021. Forward request by email.
1-0 Evaluation For Information Only. No geotechnical information can be provided for this project. Bidders shall assume the material can be reused as fill. By:
Juan Prieto; Nova Consulting - Washington, DC; (2024992140) On: Mar 02 2021 https://www.projnet.org/projnet/binKornHome/index.cfm?strKornCob=BicAdminReportAll&strReportType=AllCOR&RequestTimeout=1000&pagStrRowSort=CommentID https://www.projnet.org/projnet/binKornHome/index.cfm?strKornCob=BicAdminReportAll&strReportType=AllCOR&RequestTimeout=1000&pagStrRowSort=Discipline https://www.projnet.org/projnet/binKornHome/index.cfm?strKornCob=BicAdminReportAll&strReportType=AllCOR&RequestTimeout=1000&pagStrRowSort=Sheet https://www.projnet.org/projnet/binKornHome/index.cfm?strKornCob=BicAdminReportAll&strReportType=AllCOR&RequestTimeout=1000&pagStrRowSort=Detail https://www.projnet.org/projnet/binKornHome/index.cfm?strKornCob=BicAdminReportAll&strReportType=AllCOR&RequestTimeout=1000&pagStrRowSort=SpecText mailto:jclaremont@cromcorp.com https://www.projnet.org/projnet/binKornHome/index.cfm?strKornCob=BicCommentReportEmail&PKeyComment=9068301 mailto:jprieto@nova-consulting.com mailto:Nikolai.E.Gurdian@usace.army.mil mailto:mark.r.andrews@usace.army.mil mailto:Nikolai.E.Gurdian@usace.army.mil mailto:bradg@maverick-construction.com https://www.projnet.org/projnet/binKornHome/index.cfm?strKornCob=BicCommentReportEmail&PKeyComment=9083827 mailto:jprieto@nova-consulting.com https://www.projnet.org/projnet/binKornHome/index.cfm?strKornCob=BicAdminReportAll&strReportType=AllCOR 2/6
1-1 Government Response. No geotechnical information can be provided for this project. Bidders shall assume the material can be reused as fill. By: Mark Andrews; Contracting Division; (4435258229) On: Mar 04 2021
Current Request Status: Request Closed Information for this report is procurement sensitive.
9083828 General 31 23 00.00 20 Comment Classification: Unclassified\\For Official Use Only (U\\FOUO)
Can a unit price CLIN item be established for mechanical rock excavation (if encountered) as described in 31 23 00.00 20, section 1.2.4?
By: Brad Gribble; Maverick Construction; (4432626554). On: Feb 24 2021. Forward request by email.
1-0 Evaluation For Information Only. No unit price item will be included for mechanical rock excavation. By: Juan Prieto; Nova Consulting - Washington, DC;
(2024992140) On: Mar 02 2021 1-1 Government Response. No unit price item will be included for mechanical rock excavation. By: Mark Andrews; Contracting Division; (4435258229) On: Mar 04
Current Request Status: Request Closed
Information for this report is procurement sensitive.
9083829 Civil 02 41 00 Comment Classification: Unclassified\\For Official Use Only (U\\FOUO)
Is the existing 24" drain line ductile iron or concrete pipe?
By: Brad Gribble; Maverick Construction; (4432626554). On: Feb 24 2021. Forward request by email.
1-0 Evaluation For Information Only. It is Cast Iron. See attached drawing 80.3-4.4. (Attachment: 80.34.4_3rd_Res_Hatches_Details.pdf) By: Nikolai
Gurdian; Washington Aqueduct; (202-345-2734) On: Mar 01 2021 1-1 Government Response. It is Cast Iron. See attached drawing 80.3-4.4. By: Mark Andrews; Contracting Division; (4435258229) On: Mar 04 2021
Current Request Status: Request Closed Information for this report is procurement sensitive.
9083831 General C-03 01 92 10 Comment Classification: Unclassified\\For Official Use Only (U\\FOUO)
Please confirm this contract does not require any cleaning or material removal after the reservoir has been drained and prior to placing back in service. If any cleaning work is required, can you please explain more specifically what note #21 on sheet C-03 requires the contractor to do or the criteria that has been followed on similar USACE Washington Aqueduct Reservoirs.
By: Brad Gribble; Maverick Construction; (4432626554). On: Feb 24 2021. Forward request by email.
1-0 Evaluation For Information Only. Repair of the expansion joint, construction of new influent and effluent building and associated components, installation of reservoir mixing system and butterfly and mud valves requires work within the reservoir. Because the reservoir is used for storage of potable drinking water, after work is completed the interior surfaces of the structure will need to be cleaned and disinfected prior to being put back into service. A full listing of AWWA standards, including those for disinfection, is available at https://www.awwa.org/Publications/Standards. By: Nikolai Gurdian; Washington Aqueduct; (202-345- 2734) On: Mar 02 2021
1-1 Government Response. Repair of the expansion joint, construction of new influent and effluent building and associated components, installation of reservoir mixing system and butterfly and mud valves requires work within the reservoir. Because the reservoir is used for storage of potable drinking water, after work is completed the interior surfaces of the structure will need to be cleaned and disinfected prior to being put back into service. A full listing of AWWA standards, including those for disinfection, is available at https://www.awwa.org/Publications/Standards. By: Mark Andrews; Contracting Division; (4435258229) On: Mar 04 mailto:mark.r.andrews@usace.army.mil mailto:bradg@maverick-construction.com https://www.projnet.org/projnet/binKornHome/index.cfm?strKornCob=BicCommentReportEmail&PKeyComment=9083828 mailto:jprieto@nova-consulting.com mailto:mark.r.andrews@usace.army.mil mailto:bradg@maverick-construction.com https://www.projnet.org/projnet/binKornHome/index.cfm?strKornCob=BicCommentReportEmail&PKeyComment=9083829 https://www.projnet.org/projnet/binKornHome/index.cfm?strKornCob=BicPublicFileDownload&strApp=&strPrevCob=BicAdminReportAll&strShown=80.34.4_3rd_Res_Hatches_Details.pdf&intView=1 mailto:Nikolai.E.Gurdian@usace.army.mil mailto:mark.r.andrews@usace.army.mil mailto:bradg@maverick-construction.com https://www.projnet.org/projnet/binKornHome/index.cfm?strKornCob=BicCommentReportEmail&PKeyComment=9083831 mailto:Nikolai.E.Gurdian@usace.army.mil mailto:mark.r.andrews@usace.army.mil https://www.projnet.org/projnet/binKornHome/index.cfm?strKornCob=BicAdminReportAll&strReportType=AllCOR 3/6
Current Request Status: Request Closed Information for this report is procurement sensitive.
9083832 Civil C-08 Comment Classification: Unclassified\\For Official Use Only (U\\FOUO)
The LOD shown for the new 24" drain line, manhole, and receiving structure is very narrow at 25' to realistically construct his work with enough room for material staging, stockpiling and laydown. It would also increase the support of excavation costs substantially. Will the USACE work with the contractor to expand this LOD closer to 50' in areas or is the LOD shown a required boundary?
By: Brad Gribble; Maverick Construction; (4432626554). On: Feb 24 2021. Forward request by email.
1-0 Evaluation For Information Only. The LOD has been approved by National Parks Service and cannot be adjusted due to the project being located on historic property. By: Juan Prieto; Nova Consulting - Washington, DC; (2024992140) On: Mar 02 2021 1-1 Government Response. The LOD has been approved by National Parks Service and cannot be adjusted due to the project being located on historic property.
By: Mark Andrews; Contracting Division; (4435258229) On: Mar 04 2021 Current Request Status: Request Closed
Information for this report is procurement sensitive.
9083834 Structural C-11 and C-09 Comment Classification: Unclassified\\For Official Use Only (U\\FOUO)
Please reference sheet C-11 and the pressurized manhole details. We are trying to match these details against sheet C-09 and they don't appear to match. Could you please clarify if the inlet/outlet designations are correct on C-11 Section A (plan and profile) and also which of the pipes will be coming in at a skew.
By: Brad Gribble; Maverick Construction; (4432626554). On: Feb 24 2021.
Requires Amendment.
Forward request by email.
1-0 Evaluation Concurred. The details have been updated to match. The existing 24" drain line (inlet) will enter from the North and the outlet will exit out the West to continue down to the air-gap. The existing 24" blow-off drain connected to DC Water will be plugged on the South side. By: Juan Prieto; Nova Consulting - Washington, DC; (2024992140) On: Mar 04 2021
2-0 Evaluation Concurred. The details have been updated to match. The existing 24" drain line (inlet) will enter from the North and the outlet will exit out the West to continue down to the air-gap. The existing 24" blow-off drain connected to DC Water will be plugged on the South side. By: Juan Prieto; Nova Consulting - Washington, DC; (2024992140) On: Mar 04 2021
2-1 Government Response. The details have been updated to match. The existing 24" drain line (inlet) will enter from the North and the outlet will exit out the West to continue down to the air-gap. The existing 24" blow-off drain connected to DC Water will be plugged on the South side. By: Rashurn Harrison; Contracting Division; (4109623526) On: Mar 04 2021
Current Request Status: Request Closed Information for this report is procurement sensitive.
9083835 General 01 11 00 Comment Classification: Unclassified\\For Official Use Only (U\\FOUO)
Will the reservoir be drained in order to allow bidders to inspect the work area prior to bidding?
By: Brad Gribble; Maverick Construction; (4432626554). On: Feb 24 2021. Forward request by email.
1-0 Evaluation For Information Only. No. Draining of the reservoir will not occur until the service outage associated with the demolition of the old and construction of the new influent and effluent buildings, repair of the expansion joint, and installation of mixer system and butterfly and mud valves. Current tentative time frame for this work is Jan-Mar 2022. By: Nikolai Gurdian; Washington Aqueduct; (202-345-2734) On: Mar 01 2021 mailto:bradg@maverick-construction.com https://www.projnet.org/projnet/binKornHome/index.cfm?strKornCob=BicCommentReportEmail&PKeyComment=9083832 mailto:jprieto@nova-consulting.com mailto:mark.r.andrews@usace.army.mil mailto:bradg@maverick-construction.com https://www.projnet.org/projnet/binKornHome/index.cfm?strKornCob=BicCommentReportEmail&PKeyComment=9083834 mailto:jprieto@nova-consulting.com mailto:jprieto@nova-consulting.com mailto:rashurn.l.harrison@usace.army.mil mailto:bradg@maverick-construction.com https://www.projnet.org/projnet/binKornHome/index.cfm?strKornCob=BicCommentReportEmail&PKeyComment=9083835 https://www.projnet.org/projnet/binKornHome/index.cfm?strKornCob=BicAdminReportAll&strReportType=AllCOR 4/6
1-1 Government Response. No. Draining of the reservoir will not occur until the service outage associated with the demolition of the old and construction of the new influent and effluent buildings, repair of the expansion joint, and installation of mixer system and butterfly and mud valves. Current tentative time frame for this work is Jan-Mar 2022. By: Mark Andrews; Contracting Division; (4435258229) On: Mar 04 2021
Current Request Status: Request Closed Information for this report is procurement sensitive.
9083836 General 52.232.16 Comment Classification: Unclassified\\For Official Use Only (U\\FOUO)
Could you please clarify 52.232.16 – Progress Payments. Part A.1. states that progress payments will be made at 80% of the Contractor's cost whether or not actually paid. Is the intention to pay off an approved schedule of values that break down the CLIN items or a different method?
By: Brad Gribble; Maverick Construction; (4432626554). On: Feb 24 2021.
Requires Amendment.
Forward request by email.
1-0 Evaluation Concurred. Progress payments can be made on the basis of costs incurred or basis of completed work, i.e. schedule of values other than the current CLIN structure. By: Rashurn Harrison; Contracting Division; (4109623526) On: Mar 02 2021
1-1 Government Response. Progress payments can be made on the basis of costs incurred or basis of completed work, i.e. schedule of values other than the current CLIN structure. By: Mark Andrews; Contracting Division; (4435258229) On: Mar 04 2021
Current Request Status: Request Closed Information for this report is procurement sensitive.
9083837 General Pg 58 of Solicitation Comment Classification: Unclassified\\For Official Use Only (U\\FOUO)
Could you please provide Attachments C, D and E that are referenced on page 58 of the solicitation.
By: Brad Gribble; Maverick Construction; (4432626554). On: Feb 24 2021.
Requires Amendment.
Forward request by email.
1-0 Evaluation Concurred. Attachments will be provided with Amendment. By: Rashurn Harrison; Contracting Division; (4109623526) On: Mar 02 2021 1-1 Government Response. Attachments will be provided with Amendment. By: Mark Andrews; Contracting Division; (4435258229) On: Mar 04 2021
Current Request Status: Request Closed Information for this report is procurement sensitive.
9083838 General 00 10 00 Comment Classification: Unclassified\\For Official Use Only (U\\FOUO)
Just below the bid schedule on page 3 of the solicitation, it discusses Option Items for pricing. Does this contract include any Option Items?
By: Brad Gribble; Maverick Construction; (4432626554). On: Feb 24 2021.
Requires Amendment.
Forward request by email.
1-0 Evaluation Concurred. This contract will not include Option items. By: Rashurn Harrison; Contracting Division; (4109623526) On: Mar 02 2021 1-1 Government Response. This contract will not include Option items By: Mark Andrews; Contracting Division; (4435258229) On: Mar 04 2021
Current Request Status: Request Closed mailto:mark.r.andrews@usace.army.mil mailto:bradg@maverick-construction.com https://www.projnet.org/projnet/binKornHome/index.cfm?strKornCob=BicCommentReportEmail&PKeyComment=9083836 mailto:rashurn.l.harrison@usace.army.mil mailto:mark.r.andrews@usace.army.mil mailto:bradg@maverick-construction.com https://www.projnet.org/projnet/binKornHome/index.cfm?strKornCob=BicCommentReportEmail&PKeyComment=9083837 mailto:rashurn.l.harrison@usace.army.mil mailto:mark.r.andrews@usace.army.mil mailto:bradg@maverick-construction.com https://www.projnet.org/projnet/binKornHome/index.cfm?strKornCob=BicCommentReportEmail&PKeyComment=9083838 mailto:rashurn.l.harrison@usace.army.mil https://www.projnet.org/projnet/binKornHome/index.cfm?strKornCob=BicAdminReportAll&strReportType=AllCOR 5/6
Information for this report is procurement sensitive.
9083840 Civil C-01 03 01 35 Comment Classification: Unclassified\\For Official Use Only (U\\FOUO)
Concrete Repairs specification 03 01 35, part 1.3 says that the "Field survey shall be conducted after reservoir is removed from service and soil over burden is totally removed from over the reservoir." Notes D12 and D13 on sheet C-01 also make reference to excavation and backfill on top of the reservoir roof. Please confirm if any excavation and backfill is to be performed on top of the reservoir or if these references to not apply to this contract. If the work is to be performed, could you please clarify if the work is to be priced in the base bid and if excavation of this material can take place prior to the outage. Also please clarify where the material can be stockpiled and if we are to assume reuse of the material.
By: Brad Gribble; Maverick Construction; (4432626554). On: Feb 24 2021.
Requires Amendment.
Forward request by email.
1-0 Evaluation For Information Only. Reservoir roof overburden removal is not part of the Work By: Juan Prieto; Nova Consulting - Washington, DC;
(2024992140) On: Mar 02 2021
2-0 Evaluation Concurred. Soil overburden removal will not be required because any potential concrete repair will be to the interior of the reservoir. Potential concrete repairs should not be included in bid estimates. Any required concrete repairs identified during construction would be addressed in a change order.
There is no impact to the Scope because the Scope does not include concrete repairs. The Concrete Repairs Specs defined in Section 03 01 35 will be amended to remove mention of soil over burden removal. The remainder of the Spec will be applicable for any needed concrete repair work identified during the field investigation. By: Nikolai Gurdian; Washington Aqueduct; (202-345-2734) On: Mar 03 2021
2-1 Government Response. Soil overburden removal will not be required because any potential concrete repair will be to the interior of the reservoir. Potential concrete repairs should not be included in bid estimates. Any required concrete repairs identified during construction would be addressed in a change order.
There is no impact to the Scope because the Scope does not include concrete repairs. The Concrete Repairs Specs defined in Section 03 01 35 will be amended to remove mention of soil over burden removal. The remainder of the Spec will be applicable for any needed concrete repair work identified during the field investigation. By: Mark Andrews; Contracting Division; (4435258229) On: Mar 04 2021
Current Request Status: Request Closed Information for this report is procurement sensitive.
9083842 Structural 03 41 33 Comment Classification: Unclassified\\For Official Use Only (U\\FOUO)
What item of work is the Precast Structural Pretensioned Concrete specification 03 41 33 for?
By: Brad Gribble; Maverick Construction; (4432626554). On: Feb 24 2021. Forward request by email.
1-0 Evaluation For Information Only. No precast concrete is included in the Work By: Juan Prieto; Nova Consulting - Washington, DC; (2024992140) On: Mar
02 2021 2-0 Evaluation For Information Only. No amendment is needed because Precast Structural Pretensioned Concrete Spec would be applicable to any related change order. By: Nikolai Gurdian; Washington Aqueduct; (202-345-2734) On: Mar 03 2021 2-1 Government Response. No amendment is needed because Precast Structural Pretensioned Concrete Spec would be applicable to any related change order.
By: Mark Andrews; Contracting Division; (4435258229) On: Mar 04 2021 Current Request Status: Request Closed
Information for this report is procurement sensitive.
9083844 General 01 92 10 Comment Classification: Unclassified\\For Official Use Only (U\\FOUO) mailto:bradg@maverick-construction.com https://www.projnet.org/projnet/binKornHome/index.cfm?strKornCob=BicCommentReportEmail&PKeyComment=9083840 mailto:jprieto@nova-consulting.com mailto:Nikolai.E.Gurdian@usace.army.mil mailto:mark.r.andrews@usace.army.mil mailto:bradg@maverick-construction.com https://www.projnet.org/projnet/binKornHome/index.cfm?strKornCob=BicCommentReportEmail&PKeyComment=9083842 mailto:jprieto@nova-consulting.com https://www.projnet.org/projnet/binKornHome/index.cfm?strKornCob=BicAdminReportAll&strReportType=AllCOR 6/6
Section 01 92 10, 1.6.a says that "The shutdowns describe work which requires bypasses,..". We did not notice any requirements for bypass pumping any of the reservoir water. Can you please clarify that is correct or describe where bypass pumping operations are required by the contractor. Also, please clarify that the contractor is not required to bypass pump when the 24" drain line is out of service during Phase 1 and during Phases 2 and 3, the Government will stop all water flowing into the reservoir once drained.
By: Brad Gribble; Maverick Construction; (4432626554). On: Feb 24 2021.
Requires Amendment.
Forward request by email.
1-0 Evaluation Non-concurred. The reservoir will remain in service during Phase 1 and the contractor should expect a small amount of leakage into the 24" drain line during that time that will require bypass pumping/dewatering. Phase 2 is not expected to begin until completion of Phase 1. During Phase 2 the reservoir will be drained, but the contractor should expect to have to pump any leakage introduced during this time or collecting in the low areas, due to the irregularity of the floor. Note that the Construction Phase descriptions in Spec 01 92 10 1.5 have been updated by amendment. By: Nikolai Gurdian; Washington Aqueduct; (202- 345-2734) On: Mar 04 2021
1-1 Government Response. The reservoir will remain in service during Phase 1 and the contractor should expect a small amount of leakage into the 24" drain line during that time that will require bypass pumping/dewatering. Phase 2 is not expected to begin until completion of Phase 1. During Phase 2 the reservoir will be drained, but the contractor should expect to have to pump any leakage introduced during this time or collecting in the low areas, due to the irregularity of the floor. Note that the Construction Phase descriptions in Spec 01 92 10 1.5 have been updated by amendment. By: Rashurn Harrison; Contracting Division;
(4109623526) On: Mar 04 2021
Current Request Status: Request Closed Information for this report is procurement sensitive.
9083861 Structural S-04A Comment Classification: Unclassified\\For Official Use Only (U\\FOUO)
Can you please confirm the only concrete repair work and waterproofing to be included in our price is the center expansion joint shown on Sheet S-04A.
By: Brad Gribble; Maverick Construction; (4432626554). On: Feb 24 2021. Forward request by email.
1-0 Evaluation For Information Only. Only the expansion joint repairs are included as structural Work inside reservoir By: Juan Prieto; Nova Consulting -
Washington, DC; (2024992140) On: Mar 02 2021 1-1 Government Response. Only the expansion joint repairs are included as structural Work inside reservoir By: Mark Andrews; Contracting Division;
(4435258229) On: Mar 04 2021 Current Request Status: Request Closed
Information for this report is procurement sensitive.
Report Complete
UNCLASSIFIED\\FOR OFFICIAL USE ONLY
Patent 11/892,984 ProjNet property of ERDC since 2004.
mailto:bradg@maverick-construction.com https://www.projnet.org/projnet/binKornHome/index.cfm?strKornCob=BicCommentReportEmail&PKeyComment=9083844 mailto:Nikolai.E.Gurdian@usace.army.mil mailto:rashurn.l.harrison@usace.army.mil mailto:bradg@maverick-construction.com https://www.projnet.org/projnet/binKornHome/index.cfm?strKornCob=BicCommentReportEmail&PKeyComment=9083861 mailto:jprieto@nova-consulting.com http://projnet.com/index.php