SB Bldg. 780 Fire Suppression Semi-Annual Rpt. (Updated Mar. 2026).pdf

PDF 242 KB Posted

Attached to
DFAC Bldg. 780 Fire Alarm System Modernization
Solicitation number
W912CN-26-Q-A050
Issued by

About this file

Kitchen Hood Inspection Report Summary

These are kitchen hood service and inspection reports for Building 780 at Schofield Barracks dated March 23, 2026. The reports document inspections of seven kitchen hood fire suppression systems (Kitchen Hoods #1-#7) by Kinetix Fire & Life Safety Experts, with service technician Eddie Brown performing the inspections under the authorization of SGT Jamie Felty. All systems are Ansul R-102 wet chemical suppression systems with 3-gallon master cylinders and corresponding slave cylinders, equipped with shunt trip electrical shut-offs and mechanical gas valves. The inspection dates are all March 23, 2026, at 08:00 hours, and each system was tested and inspected in accordance with NFPA 17, 17A, and 96 standards and manufacturer manuals.

Kitchen Hood #1 has a documented deficiency requiring corrective action: an (x6) electric burner was switched to an (x8) electric burner with incorrect nozzle coverage, requiring additional nozzles for proper coverage. This system was marked as non-compliant. Kitchen Hoods #2 through #7 all passed inspection with no discrepancies noted. Kitchen Hood #3 had minor observations regarding appliance positioning and heavy oil dripping from the duct (noted as cleanable). Systems #2, #4, #5, #6, and #7 have unreadable serial numbers for their master cylinders. All systems have hydrostatic test dates and last recharge dates of 2020, with fusible links quantities ranging from 0-5 units depending on the system configuration.

View the file

Other files

Show all 19

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

KITCHEN HOOD REPORT

Phone: (610) 627-1600

Fax: (610) 627-1657 www.kinetixfire.com

CUSTOMER & SYSTEM LOCATION

Building 780

Schofield Barracks

GENERAL INFORMATION YES NO N/A

1. All appliances properly covered w/ correct nozzles? DATE & TIME OF SERVICE

2. Duct and plenum covered w/ correct nozzles?

3. Check positioning of all nozzles. SERVICE TYPE

4. System installed in accordance w/ MFG UL listing?

5. Hood/duct penetrations sealed w/weld or UL device? MANUFACTURER

6. Check if seals intact, evidence of tampering? MODEL NUMBER

7. If system has been discharged, report same? SYSTEM AGENT

8. Pressure gauge in proper range (if gauged)? SYSTEM SERIAL NUMBER

9. Check cartridge weight (if applicable). CYLINDER SIZE - MASTER

10. Hydrostatic test date?

11. Inspected cylinder and mount? CYLINDER SIZE - SLAVE

12. Operation of system from terminal link?

13. Test for proper operation from remotes? CYLINDER SIZE - SLAVE

14. Check operation of micro switch?

15. Check operation of gas valve?

16. Are the nozzles clean? LAST HYDRO TEST DATE

17. Are the proper nozzle covers in place? LAST RECHARGE DATE

18. Check fuse links and clean? 360 ° 450 ° 500 °

19. Replaced fuse links? 0 5 0

20. Check travel of cable nuts/S-hooks? FUEL SHUT-OFF

21. Piping & conduit securely bracketed? ELECTRIC

22. Proper separation between fryers and flame? GAS

23. Proper clearance-flame to filters? SIZE

24. Exhaust fan in operating order?

25. All filters replaced?

26. Fuel shut-off in on position?

27. Manual & remote set/seals in place?

28. Replace systems covers?

29. System operational & seals in place?

30. Slave system operational?

31. Clean cylinder and mount?

32. Fan warning sign on hood?

33. Personnel instructed in manual operation of system?

34. Proper hand portable extinguishers?

35. Portable extinguishers properly serviced?

36. Service & Certification tag on system?

PRINT NAME:

March-23-2026

DISCREPANCIES AND/OR DEFICIENCIES

N/A

08:00

MASTER CYLINDER SERIAL NUMBER

SLAVE CYLINDER SERIAL NUMBER

3 gallons

Ansul

R-102

Wet chemical

2020055954

3 gallons

71464

On this date, the system was tested and inspected and operated in accordance with procedures of the presently adopted editions of NFPA 17, 17A, 96 and the manufacturer’s manual.

Inspection

SLAVE CYLINDER SERIAL NUMBER

SYSTEM DETAILS

System Red-Tagged (Non-Compliant)?

LOCATION OF SYSTEM CYLINDERS Right side of the Hood

(x6) Electric Burner has been switched out for an (x8) Electric Burner. Nozzle coverage is not correct. More nozzles are required for proper coverage.

APPLIANCE LAYOUT (LEFT TO RIGHT)

(x8) Electric Burner, Tilt Skillet, Tilt Skillet

SGT Jamie Felty

AUTHORIZED SERVICE COMPANY REPRESENTATIVE

QTY

Shunt Trip Mechanical Gas Valve

FUSABLE LINKS OTHER

N/A

Eddie Brown This service technician certifies that the system was personally inspected and found conditions to be as indicated on this report.

GENERAL COMMENTS

PHONE NUMBER

915-801-0228

SERVICE DETAILS

CONTACT PERSON

SGT Jamie Felty

See general comment

SIGNATURE:

AUTHORIZED CUSTOMER'S REPRESENTATIVE

AREA COVERED

Kitchen Hood #1 (Main)

No

Fax: (610) 627-1657 www.kinetixfire.com

CUSTOMER & SYSTEM LOCATION

Building 780

Schofield Barracks

GENERAL INFORMATION YES NO N/A

1. All appliances properly covered w/ correct nozzles? DATE & TIME OF SERVICE

2. Duct and plenum covered w/ correct nozzles?

3. Check positioning of all nozzles. SERVICE TYPE

4. System installed in accordance w/ MFG UL listing?

5. Hood/duct penetrations sealed w/weld or UL device? MANUFACTURER

6. Check if seals intact, evidence of tampering? MODEL NUMBER

7. If system has been discharged, report same? SYSTEM AGENT

8. Pressure gauge in proper range (if gauged)? SYSTEM SERIAL NUMBER

9. Check cartridge weight (if applicable). CYLINDER SIZE - MASTER

10. Hydrostatic test date?

11. Inspected cylinder and mount? CYLINDER SIZE - SLAVE

12. Operation of system from terminal link?

13. Test for proper operation from remotes? CYLINDER SIZE - SLAVE

14. Check operation of micro switch?

15. Check operation of gas valve?

16. Are the nozzles clean? LAST HYDRO TEST DATE

17. Are the proper nozzle covers in place? LAST RECHARGE DATE

18. Check fuse links and clean? 360 ° 450 ° 500 °

19. Replaced fuse links? 0 2 0

20. Check travel of cable nuts/S-hooks? FUEL SHUT-OFF

21. Piping & conduit securely bracketed? ELECTRIC

22. Proper separation between fryers and flame? GAS

23. Proper clearance-flame to filters? SIZE

24. Exhaust fan in operating order?

25. All filters replaced?

26. Fuel shut-off in on position?

27. Manual & remote set/seals in place?

28. Replace systems covers?

29. System operational & seals in place?

30. Slave system operational?

31. Clean cylinder and mount?

32. Fan warning sign on hood?

33. Personnel instructed in manual operation of system?

34. Proper hand portable extinguishers?

35. Portable extinguishers properly serviced?

36. Service & Certification tag on system?

PRINT NAME:

March-23-2026

DISCREPANCIES AND/OR DEFICIENCIES

N/A

08:00

MASTER CYLINDER SERIAL NUMBER

SLAVE CYLINDER SERIAL NUMBER

3 gallons

Ansul

R-102

Wet chemical

Unreadable

On this date, the system was tested and inspected and operated in accordance with procedures of the presently adopted editions of NFPA 17, 17A, 96 and the manufacturer’s manual.

Inspection

SLAVE CYLINDER SERIAL NUMBER

SYSTEM DETAILS

System Red-Tagged (Non-Compliant)?

LOCATION OF SYSTEM CYLINDERS (Left) of the hood

None at this time.

APPLIANCE LAYOUT (LEFT TO RIGHT)

Only ducts and plenum coverage.

SGT Jamie Felty

AUTHORIZED SERVICE COMPANY REPRESENTATIVE

QTY

Shunt Trip Mechanical Gas Valve

FUSABLE LINKS OTHER

N/A

Eddie Brown This service technician certifies that the system was personally inspected and found conditions to be as indicated on this report.

GENERAL COMMENTS

PHONE NUMBER

915-80-10228

SERVICE DETAILS

CONTACT PERSON

SGT Jamie Felty

None at this time.

SIGNATURE:

AUTHORIZED CUSTOMER'S REPRESENTATIVE

AREA COVERED

Kitchen Hood #2

Fax: (610) 627-1657 www.kinetixfire.com

CUSTOMER & SYSTEM LOCATION

Building 780

Schofield Barracks

GENERAL INFORMATION YES NO N/A

1. All appliances properly covered w/ correct nozzles? DATE & TIME OF SERVICE

2. Duct and plenum covered w/ correct nozzles?

3. Check positioning of all nozzles. SERVICE TYPE

4. System installed in accordance w/ MFG UL listing?

5. Hood/duct penetrations sealed w/weld or UL device? MANUFACTURER

6. Check if seals intact, evidence of tampering? MODEL NUMBER

7. If system has been discharged, report same? SYSTEM AGENT

8. Pressure gauge in proper range (if gauged)? SYSTEM SERIAL NUMBER

9. Check cartridge weight (if applicable). CYLINDER SIZE - MASTER

10. Hydrostatic test date?

11. Inspected cylinder and mount? CYLINDER SIZE - SLAVE

12. Operation of system from terminal link?

13. Test for proper operation from remotes? CYLINDER SIZE - SLAVE

14. Check operation of micro switch?

15. Check operation of gas valve?

16. Are the nozzles clean? LAST HYDRO TEST DATE

17. Are the proper nozzle covers in place? LAST RECHARGE DATE

18. Check fuse links and clean? 360 ° 450 ° 500 °

19. Replaced fuse links? 0 4 0

20. Check travel of cable nuts/S-hooks? FUEL SHUT-OFF

21. Piping & conduit securely bracketed? ELECTRIC

22. Proper separation between fryers and flame? GAS

23. Proper clearance-flame to filters? SIZE

24. Exhaust fan in operating order?

25. All filters replaced?

26. Fuel shut-off in on position?

27. Manual & remote set/seals in place?

28. Replace systems covers?

29. System operational & seals in place?

30. Slave system operational?

31. Clean cylinder and mount?

32. Fan warning sign on hood?

33. Personnel instructed in manual operation of system?

34. Proper hand portable extinguishers?

35. Portable extinguishers properly serviced?

36. Service & Certification tag on system?

PRINT NAME:

March-23-2026

DISCREPANCIES AND/OR DEFICIENCIES

N/A

08:00

MASTER CYLINDER SERIAL NUMBER

SLAVE CYLINDER SERIAL NUMBER

3 gallons

Ansul

R-102

Wet chemical

2020055937

3 gallons

2020055938

On this date, the system was tested and inspected and operated in accordance with procedures of the presently adopted editions of NFPA 17, 17A, 96 and the manufacturer’s manual.

Inspection

SLAVE CYLINDER SERIAL NUMBER

SYSTEM DETAILS

System Red-Tagged (Non-Compliant)?

LOCATION OF SYSTEM CYLINDERS (Right) of the hood

Appliance found not underneath nozzles for proper protection. Heavy oil dripping from duct. Can be cleaned.

APPLIANCE LAYOUT (LEFT TO RIGHT)

(x4) fryers

SGT Jamie Felty

AUTHORIZED SERVICE COMPANY REPRESENTATIVE

QTY

Shunt Trip Mechanical Gas Valve

FUSABLE LINKS OTHER

N/A

Eddie Brown This service technician certifies that the system was personally inspected and found conditions to be as indicated on this report.

GENERAL COMMENTS

PHONE NUMBER

915-801-0228

SERVICE DETAILS

CONTACT PERSON

SGT Jamie Felty

None at this time.

SIGNATURE:

AUTHORIZED CUSTOMER'S REPRESENTATIVE

AREA COVERED

Kitchen Hood #3

Fax: (610) 627-1657 www.kinetixfire.com

CUSTOMER & SYSTEM LOCATION

Building 780

Schofield Barracks

GENERAL INFORMATION YES NO N/A

1. All appliances properly covered w/ correct nozzles? DATE & TIME OF SERVICE

2. Duct and plenum covered w/ correct nozzles?

3. Check positioning of all nozzles. SERVICE TYPE

4. System installed in accordance w/ MFG UL listing?

5. Hood/duct penetrations sealed w/weld or UL device? MANUFACTURER

6. Check if seals intact, evidence of tampering? MODEL NUMBER

7. If system has been discharged, report same? SYSTEM AGENT

8. Pressure gauge in proper range (if gauged)? SYSTEM SERIAL NUMBER

9. Check cartridge weight (if applicable). CYLINDER SIZE - MASTER

10. Hydrostatic test date?

11. Inspected cylinder and mount? CYLINDER SIZE - SLAVE

12. Operation of system from terminal link?

13. Test for proper operation from remotes? CYLINDER SIZE - SLAVE

14. Check operation of micro switch?

15. Check operation of gas valve?

16. Are the nozzles clean? LAST HYDRO TEST DATE

17. Are the proper nozzle covers in place? LAST RECHARGE DATE

18. Check fuse links and clean? 360 ° 450 ° 500 °

19. Replaced fuse links? 0 4 0

20. Check travel of cable nuts/S-hooks? FUEL SHUT-OFF

21. Piping & conduit securely bracketed? ELECTRIC

22. Proper separation between fryers and flame? GAS

23. Proper clearance-flame to filters? SIZE

24. Exhaust fan in operating order?

25. All filters replaced?

26. Fuel shut-off in on position?

27. Manual & remote set/seals in place?

28. Replace systems covers?

29. System operational & seals in place?

30. Slave system operational?

31. Clean cylinder and mount?

32. Fan warning sign on hood?

33. Personnel instructed in manual operation of system?

34. Proper hand portable extinguishers?

35. Portable extinguishers properly serviced?

36. Service & Certification tag on system?

PRINT NAME:

March-23-2026

DISCREPANCIES AND/OR DEFICIENCIES

N/A

08:00

MASTER CYLINDER SERIAL NUMBER

SLAVE CYLINDER SERIAL NUMBER

3 gallons

Ansul

R-102

Wet chemical

Unreadable

On this date, the system was tested and inspected and operated in accordance with procedures of the presently adopted editions of NFPA 17, 17A, 96 and the manufacturer’s manual.

Inspection

SLAVE CYLINDER SERIAL NUMBER

SYSTEM DETAILS

System Red-Tagged (Non-Compliant)?

LOCATION OF SYSTEM CYLINDERS (Left) of the hood

None at this time.

APPLIANCE LAYOUT (LEFT TO RIGHT)

Flat grill

SGT Jamie Felty

AUTHORIZED SERVICE COMPANY REPRESENTATIVE

QTY

Shunt Trip Mechanical Gas Valve

FUSABLE LINKS OTHER

N/A

Eddie Brown This service technician certifies that the system was personally inspected and found conditions to be as indicated on this report.

GENERAL COMMENTS

PHONE NUMBER

915-801-0228

SERVICE DETAILS

CONTACT PERSON

SGT Jamie Felty

None at this time.

SIGNATURE:

AUTHORIZED CUSTOMER'S REPRESENTATIVE

AREA COVERED

Kitchen Hood #4

Fax: (610) 627-1657 www.kinetixfire.com

CUSTOMER & SYSTEM LOCATION

Building 780

Schofield Barracks

GENERAL INFORMATION YES NO N/A

1. All appliances properly covered w/ correct nozzles? DATE & TIME OF SERVICE

2. Duct and plenum covered w/ correct nozzles?

3. Check positioning of all nozzles. SERVICE TYPE

4. System installed in accordance w/ MFG UL listing?

5. Hood/duct penetrations sealed w/weld or UL device? MANUFACTURER

6. Check if seals intact, evidence of tampering? MODEL NUMBER

7. If system has been discharged, report same? SYSTEM AGENT

8. Pressure gauge in proper range (if gauged)? SYSTEM SERIAL NUMBER

9. Check cartridge weight (if applicable). CYLINDER SIZE - MASTER

10. Hydrostatic test date?

11. Inspected cylinder and mount? CYLINDER SIZE - SLAVE

12. Operation of system from terminal link?

13. Test for proper operation from remotes? CYLINDER SIZE - SLAVE

14. Check operation of micro switch?

15. Check operation of gas valve?

16. Are the nozzles clean? LAST HYDRO TEST DATE

17. Are the proper nozzle covers in place? LAST RECHARGE DATE

18. Check fuse links and clean? 360 ° 450 ° 500 °

19. Replaced fuse links? 0 1 0

20. Check travel of cable nuts/S-hooks? FUEL SHUT-OFF

21. Piping & conduit securely bracketed? ELECTRIC

22. Proper separation between fryers and flame? GAS

23. Proper clearance-flame to filters? SIZE

24. Exhaust fan in operating order?

25. All filters replaced?

26. Fuel shut-off in on position?

27. Manual & remote set/seals in place?

28. Replace systems covers?

29. System operational & seals in place?

30. Slave system operational?

31. Clean cylinder and mount?

32. Fan warning sign on hood?

33. Personnel instructed in manual operation of system?

34. Proper hand portable extinguishers?

35. Portable extinguishers properly serviced?

36. Service & Certification tag on system?

PRINT NAME:

March-23-2026

DISCREPANCIES AND/OR DEFICIENCIES

N/A

08:00

MASTER CYLINDER SERIAL NUMBER

SLAVE CYLINDER SERIAL NUMBER

3 gallons

Ansul

R-102

Wet chemical

Unreadable

On this date, the system was tested and inspected and operated in accordance with procedures of the presently adopted editions of NFPA 17, 17A, 96 and the manufacturer’s manual.

Inspection

SLAVE CYLINDER SERIAL NUMBER

SYSTEM DETAILS

System Red-Tagged (Non-Compliant)?

LOCATION OF SYSTEM CYLINDERS (Left) of the hood

None at this time.

APPLIANCE LAYOUT (LEFT TO RIGHT)

Flat grill

SGT Jamie Felty

AUTHORIZED SERVICE COMPANY REPRESENTATIVE

QTY

Shunt Trip Mechanical Gas Valve

FUSABLE LINKS OTHER

N/A

Eddie Brown This service technician certifies that the system was personally inspected and found conditions to be as indicated on this report.

GENERAL COMMENTS

PHONE NUMBER

915-801-0228

SERVICE DETAILS

CONTACT PERSON

SGT Jamie Felty

None at this time.

SIGNATURE:

AUTHORIZED CUSTOMER'S REPRESENTATIVE

AREA COVERED

Kitchen Hood #5

Fax: (610) 627-1657 www.kinetixfire.com

CUSTOMER & SYSTEM LOCATION

Building 780

Schofield Barracks

GENERAL INFORMATION YES NO N/A

1. All appliances properly covered w/ correct nozzles? DATE & TIME OF SERVICE

2. Duct and plenum covered w/ correct nozzles?

3. Check positioning of all nozzles. SERVICE TYPE

4. System installed in accordance w/ MFG UL listing?

5. Hood/duct penetrations sealed w/weld or UL device? MANUFACTURER

6. Check if seals intact, evidence of tampering? MODEL NUMBER

7. If system has been discharged, report same? SYSTEM AGENT

8. Pressure gauge in proper range (if gauged)? SYSTEM SERIAL NUMBER

9. Check cartridge weight (if applicable). CYLINDER SIZE - MASTER

10. Hydrostatic test date?

11. Inspected cylinder and mount? CYLINDER SIZE - SLAVE

12. Operation of system from terminal link?

13. Test for proper operation from remotes? CYLINDER SIZE - SLAVE

14. Check operation of micro switch?

15. Check operation of gas valve?

16. Are the nozzles clean? LAST HYDRO TEST DATE

17. Are the proper nozzle covers in place? LAST RECHARGE DATE

18. Check fuse links and clean? 360 ° 450 ° 500 °

19. Replaced fuse links? 0 3 0

20. Check travel of cable nuts/S-hooks? FUEL SHUT-OFF

21. Piping & conduit securely bracketed? ELECTRIC

22. Proper separation between fryers and flame? GAS

23. Proper clearance-flame to filters? SIZE

24. Exhaust fan in operating order?

25. All filters replaced?

26. Fuel shut-off in on position?

27. Manual & remote set/seals in place?

28. Replace systems covers?

29. System operational & seals in place?

30. Slave system operational?

31. Clean cylinder and mount?

32. Fan warning sign on hood?

33. Personnel instructed in manual operation of system?

34. Proper hand portable extinguishers?

35. Portable extinguishers properly serviced?

36. Service & Certification tag on system?

PRINT NAME:

March-23-2026

DISCREPANCIES AND/OR DEFICIENCIES

N/A

08:00

MASTER CYLINDER SERIAL NUMBER

SLAVE CYLINDER SERIAL NUMBER

3 gallons

Ansul

R-102

Wet chemical

Unreadable

On this date, the system was tested and inspected and operated in accordance with procedures of the presently adopted editions of NFPA 17, 17A, 96 and the manufacturer’s manual.

Inspection

SLAVE CYLINDER SERIAL NUMBER

SYSTEM DETAILS

System Red-Tagged (Non-Compliant)?

LOCATION OF SYSTEM CYLINDERS (Right) of the hood

None at this time.

APPLIANCE LAYOUT (LEFT TO RIGHT)

Flat top grill

SGT Jamie Felty

AUTHORIZED SERVICE COMPANY REPRESENTATIVE

QTY

Shunt Trip Mechanical Gas Valve

FUSABLE LINKS OTHER

N/A

Eddie Brown This service technician certifies that the system was personally inspected and found conditions to be as indicated on this report.

GENERAL COMMENTS

PHONE NUMBER

808-787-5740

SERVICE DETAILS

CONTACT PERSON

SGT Jamie Felty

None at this time.

SIGNATURE:

AUTHORIZED CUSTOMER'S REPRESENTATIVE

AREA COVERED

Kitchen Hood #6

Fax: (610) 627-1657 www.kinetixfire.com

CUSTOMER & SYSTEM LOCATION

Building 780

Schofield Barracks

GENERAL INFORMATION YES NO N/A

1. All appliances properly covered w/ correct nozzles? DATE & TIME OF SERVICE

2. Duct and plenum covered w/ correct nozzles?

3. Check positioning of all nozzles. SERVICE TYPE

4. System installed in accordance w/ MFG UL listing?

5. Hood/duct penetrations sealed w/weld or UL device? MANUFACTURER

6. Check if seals intact, evidence of tampering? MODEL NUMBER

7. If system has been discharged, report same? SYSTEM AGENT

8. Pressure gauge in proper range (if gauged)? SYSTEM SERIAL NUMBER

9. Check cartridge weight (if applicable). CYLINDER SIZE - MASTER

10. Hydrostatic test date?

11. Inspected cylinder and mount? CYLINDER SIZE - SLAVE

12. Operation of system from terminal link?

13. Test for proper operation from remotes? CYLINDER SIZE - SLAVE

14. Check operation of micro switch?

15. Check operation of gas valve?

16. Are the nozzles clean? LAST HYDRO TEST DATE

17. Are the proper nozzle covers in place? LAST RECHARGE DATE

18. Check fuse links and clean? 360 ° 450 ° 500 °

19. Replaced fuse links? 0 4 0

20. Check travel of cable nuts/S-hooks? FUEL SHUT-OFF

21. Piping & conduit securely bracketed? ELECTRIC

22. Proper separation between fryers and flame? GAS

23. Proper clearance-flame to filters? SIZE

24. Exhaust fan in operating order?

25. All filters replaced?

26. Fuel shut-off in on position?

27. Manual & remote set/seals in place?

28. Replace systems covers?

29. System operational & seals in place?

30. Slave system operational?

31. Clean cylinder and mount?

32. Fan warning sign on hood?

33. Personnel instructed in manual operation of system?

34. Proper hand portable extinguishers?

35. Portable extinguishers properly serviced?

36. Service & Certification tag on system?

PRINT NAME:

March-23-2026

DISCREPANCIES AND/OR DEFICIENCIES

N/A

08:00

MASTER CYLINDER SERIAL NUMBER

SLAVE CYLINDER SERIAL NUMBER

3 gallons

Ansul

R-102

Wet chemical

Unreadable

On this date, the system was tested and inspected and operated in accordance with procedures of the presently adopted editions of NFPA 17, 17A, 96 and the manufacturer’s manual.

Inspection

SLAVE CYLINDER SERIAL NUMBER

SYSTEM DETAILS

System Red-Tagged (Non-Compliant)?

LOCATION OF SYSTEM CYLINDERS (Right) of the hood

None at this time.

APPLIANCE LAYOUT (LEFT TO RIGHT)

Flat top grill, (x2) Fryers

SGT Jamie Felty

AUTHORIZED SERVICE COMPANY REPRESENTATIVE

QTY

Shunt Trip Mechanical Gas Valve

FUSABLE LINKS OTHER

N/A

Eddie Brown This service technician certifies that the system was personally inspected and found conditions to be as indicated on this report.

GENERAL COMMENTS

PHONE NUMBER

915-801-0228

SERVICE DETAILS

CONTACT PERSON

SGT Jamie Felty

None at this time.

SIGNATURE:

AUTHORIZED CUSTOMER'S REPRESENTATIVE

AREA COVERED

Kitchen Hood #7