Am_0005_Dwgs_Vol-2.pdf

PDF 728 KB Posted

Attached to
B-21 Radio Frequency Facility (RF-Hangar) Federal contract opportunity
Solicitation number
W9128F22R0054_Volume-1
Issued by
Department of the Army Corps of Engineers Engineering District Omaha

About this file

This solicitation is seeking proposals for the construction of a Radio Frequency Facility (RF Hangar) at Ellsworth Air Force Base in South Dakota. Key details include:

  • The project scope is to construct an approximately 64,500 square foot RF Hangar with a single aircraft measurement bay, back shop spaces, administrative areas, and support facilities. The facility is to be designed to secure area standards and comply with DoD antiterrorism requirements.

  • The delivery method is design-bid-build, requiring the contractor to provide the completed facility and warranty based on the request for proposal documents. Documents are accessible through the Projnet plan room using the provided quick key.

  • The facility is to be designed as permanent construction adhering to DoD and Air Force design standards, including UFC 1-200-01 for general building requirements and UFC 1-200-02 for high-performance and sustainable building. Local materials and techniques should be utilized where cost-effective.

  • An anticipated completion date is not provided. The solicitation will remain open until the submission deadline stated in the RFP documents accessible through Projnet.

View the file

Other files for this federal contract opportunity

Show all 16

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

1 2 3 4 6 1210987 13 145

A

B

C

D

E

F

G

H

111115

107 108

112 116

MGB PBB

SBB

GROUND RING BURIED MIN. 30"

BELOW GRADE. COORDINATE

WITH STRUCTURAL FOOTINGS.

COUNTERPOISE TO BE LOCATED

AT MIN. 3" PAST FOOTING OUTER

EDGE.

F1

EG501

A7

EG501

(TYP)

(TYP)

#4/0 AWG BARE COPPER (TYP)

K

J

F7

EG501(TYP)

RF SITE

XFMR1

PLAN

NORTH

US Army Corps of Engineers ®

SHEET ID

U .S

A

R M

Y C

O R

P S

O F

E N

G

IN

E E

R S

O

M A

H A

D

IS

T R

IC

T

C

A P

IT

O

L A

V E

N U

E O

M A

H A

N

E

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

S U

B M

IT

T

E D

B Y

S

IZ

E

C H

E C

K E

D B

Y

A N

S I D

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

S O

L

IC

IT

A

T

IO

N N

O

N

3 5 7 9 11 13 15 17 19

L

J

G

E

C

A

D A

T E

M A

R K

D E

S C

R

IP

T

IO

N

2 4 6 8 10 12 14 16 18 20

P

M

K

H

F

D

B

W

A R

D P

A R

K W

A Y

K

A N

S A

S C

IT

Y

M

O

A M

A S

H E

K E

L

A F

D R

A W

IN

G

C O

D E

E L L S

W O

R T

H A

IR

F

O R

C E

B A

S E

S

D

P N

F X

B M

B -2

R

A D

IO

F

R E

Q U

E N

C Y

F A

C

IL

IT

Y

R

F H

A N

G A

R

(F Y

O C

T O

B E

R

A D

V E

R T

IS

E

M E

N T

D

E S

IG

N

A B C

E F

KEY PLAN

NOT TO SCALE

D

W F

-2 -R

-0

EG101

O V

E R

A L

L G

R O

U N

D

IN

G P

L A

N

M H

A R

A L S

O N

M B

A X

P O

'G O

R M

A N

GENERAL SHEET NOTES:

1. SEE SHEETS E-001 AND E-002 FOR GENERAL NOTES,

LEGEND, AND ABBREVIATIONS.

SCALE: 1/16" = 1'-0"

A1

OVERALL GROUND FLOOR PLAN

0 8' 16' 32'

GROUNDING SYSTEM NOTES:

1. ELECTRICAL DISTRIBUTION GROUNDING MUST

COMPLY WITH NEC ART. 250.

2. TELECOMMUNICATIONS GROUNDING SYSTEM MUST

COMPLY WITH NEC ART. 800, TIA-607-D, AND UFC

3-520-01.

3. THIS SHEET DOES NOT PRECLUDE THE

REQUIREMENTS OF NEC ART. 250, ART. 800, OR NFPA

780.

4. GROUND BUILDING STEEL AT EVERY OTHER COLUMN

AND NO MORE THAN 60 FEET APART. BOND WITH #4/0

AWG BARE COPPER. SEE DETAIL A13 ON SHEET

EG501.

5. ALL ELECTRICAL WORK IN HAZARDOUS AREAS MUST

BE PER NEC ART. 501 AND 513 FOR EACH AREA

WHERE WORK IS BEING PERFORMED.

6. COUNTERPOISE TO BE INSTALLED 3 FEET TO 8 FEET

FROM FOUNDATION.

7. SEE SHEET EG601 FOR GROUNDING RISER

DIAGRAMS.

SHEET KEYNOTES:

1. COPPER GROUND BAR PER DETAIL F14 ON SHEET

EG501.

2. BOND THE RAILS FOR DOOR TRACK USING #4/0 AWG

BARE COPPER.

3. SEE ENLARGED PLAN J1 ON SHEET TN401 FOR

DETAILED LOCATION.

4. SEE ENLARGED PLAN H1 ON SHEET TN402 FOR

DETAILED LOCATION.

5. TELECOMMUNICATIONS BONDING CONDUCTOR (TBC).

6. TELECOMMUNICATIONS BONDING BACKBONE (TBB).

7. BOND CEILING GRID SYSTEM WITHIN THIS SPACE TO

BUILDING STEEL WITH LISTED BONDING HARDWARE.

USE A BEAM CLAMP INSTALLED ON GRID SYSTEM

MAIN BEAM, PROVIDE #6 BONDING JUMPER AND

BOND TO STEEL UTILIZING A BEAM CLAMP. BOND AT

NO MORE THAN 25FT APART ALONG THE ENTIRE

PERIMETER OF THE CEILING GRID SYSTEM.

8. BOND EXPOSED DUCTWORK ALONG PLAN NORTH

WALL WITHIN SPACE TO BUILDING STEEL. SEE

DETAIL G1 ON SHEET EG503.

2 (TYP)

5 6

7 8

A

M -0

D

E S

IG

N

I S

S U

E F

O R

P R

IC

IN

G N

O V

A

M E

N D

M E

N T

J a n

M

M

M

M

M

M

M

M

M

M

M

M

M

M

M

M

M M

M

M

M

M

M

M

M

M

M

M

M

M

M

6 875

F

G

H

MATCH LINE

EP112

M A

T C

H L

IN

E

E P

M A

T C

H L

IN

E

E P

MEASUREMENT BAY

MECH

FOAM

AIRCRAFT POWER

SUPPLY

K

J

DWH-101

MR1-5UH-102

MR1-1

UH-101

MR1-1

UH-104

MR1-3 UH-105

MR1-3

CHWP-102

MP1-25,27,29

CHWP-101

MP1-19,21,23

HWP-101

MP1-7,9,11

HWP-102

MP1-13,15,17

AHU-101

MP2-13,15,17

HWB-102

MR1-37,39,41

HWB-101

MR1-31,33,35

HWP-104

MP1-37,39,41

HWP-103

MP1-31,33,35

SF-101

MP1-8,10,12 AHU-102

MP2-19,21,23

DOAS-101 FAN 1

MP2-1,3,5

EF-102

MR1-29

SF-103

MP2-2,4,6

D O

A S

-1

M P

-7

,9 ,1

A C

-1

M

P

-2

,2

,2

R A

D -1

M R

-2

SG-101

MP2-37,39,41

HWP-105

MP1-2,4,6

HWB-103

MR1-2

UH-103

MR1-1

HWP-106

MP2-8,10,12

R F

-1

M

P

-2

,2

,2

RP-1

MR1-23

SG-103

MR1-53

SG-102

MR1-51

R O

-1

M

P

-2

,2

,2

DOAS-101 FAN 2

MP2-14,16,18

PLAN

NORTH

US Army Corps of Engineers ®

SHEET ID

U .S

A

R M

Y C

O R

P S

O F

E N

G

IN

E E

A

H A

D

IS

T R

IC

T

C

A P

IT

O

L A

V E

N U

E O

M A

H A

N

E

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

S U

B M

IT

T

E D

B Y

S

IZ

E

C H

E C

K E

D B

Y

A N

S I D

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

S O

L

IC

IT

A

T

IO

N N

O

N

3 5 7 9 11 13 15 17 19

L

J

G

E

C

A

D A

T E

M A

R K

D E

S C

R

IP

T

IO

N

2 4 6 8 10 12 14 16 18 20

P

M

K

H

F

D

B

W

A R

D P

A R

K W

A Y

K

A N

S A

S C

IT

Y

M

O

A M

A S

H E

K E

L

A F

D R

A W

IN

G

C O

D E

E L L S

W O

R T

H A

IR

F

O R

C E

B A

S E

S

D

P N

F X

B M

B -2

R

A D

IO

F

R E

Q U

E N

C Y

F A

C

IL

IT

Y

R

F H

A N

G A

R

(F Y

O C

T O

B E

R

A D

V E

R T

IS

E

M E

N T

D

E S

IG

N

A B C

E F

KEY PLAN

NOT TO SCALE

D

W F

-2 -R

-0

EP115

H V

A C

P O

W E

R P

L A

N

A R

E A

E

M H

A R

A L S

O N

M B

A X

P O

'G O

R M

A N

GENERAL SHEET NOTES:

1. SEE SHEETS E-001 AND E-002 FOR GENERAL NOTES,

LEGEND, AND ABBREVIATIONS.

2. SEE SHEET EP710 FOR MECHANICAL EQUIPMENT

CONNECTION SCHEDULE.

SCALE: 1/8" = 1'-0"

A6

GROUND HVAC POWER PLAN - AREA E

0 4' 8' 16'

A

M -0

D

E S

IG

N

I S

S U

E F

O R

P R

IC

IN

G N

O V

A

M E

N D

M E

N T

J a n

US Army Corps of Engineers ®

SHEET ID

U .S

A

R M

Y C

O R

P S

O F

E N

G

IN

E E

A

H A

D

IS

T R

IC

T

C

A P

IT

O

L A

V E

N U

E O

M A

H A

N

E

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

S U

B M

IT

T

E D

B Y

S

IZ

E

C H

E C

K E

D B

Y

A N

S I D

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

S O

L

IC

IT

A

T

IO

N N

O

N

3 5 7 9 11 13 15 17 19

L

J

G

E

C

A

D A

T E

M A

R K

D E

S C

R

IP

T

IO

N

2 4 6 8 10 12 14 16 18 20

P

M

K

H

F

D

B

W

A R

D P

A R

K W

A Y

K

A N

S A

S C

IT

Y

M

O

A M

A S

H E

K E

L

A F

D R

A W

IN

G

C O

D E

E L L S

W O

R T

H A

IR

F

O R

C E

B A

S E

S

D

P N

F X

B M

B -2

R

A D

IO

F

R E

Q U

E N

C Y

F A

C

IL

IT

Y

R

F H

A N

G A

R

(F Y

O C

T O

B E

R

A D

V E

R T

IS

E

M E

N T

D

E S

IG

N

W F

-2 -R

-0

EP702

P A

N E

L B

O A

R D

S C

H E

D U

L E

S

M H

A R

A L S

O N

M B

A X

P O

'G O

R M

A N

DEMAND WITH EXPANSION: 106 A

TOTAL ESTIMATED DEMAND CURRENT: 89 A

TOTAL CONNECTED CURRENT: 89 A

TOTAL ESTIMATED DEMAND LOAD: 73705 VA

TOTAL CONNECTED LOAD: 73705 VA

PANEL TOTALS

TOTAL LOAD: 24697 VA 24730 VA 24279 VA

41 20 1 LIGHTING SECURE AREA SOUTH 2-#12 AWG, #12 AWG GND IN 3/4"C 1757 0 -- -- -- -- 42

39 20 1 MECH YARD LIGHTING 2-#12 AWG, #12 AWG GND IN 3/4"C 250 0 -- -- -- -- 40

37 20 1 LIGHTING RM 124 2-#10 AWG, #10 AWG GND IN 3/4"C 2815 0 WIRING PER MANUF. SPD* 3 30 38

35 20 1 SPARE 0 -- SPACE 1 -- 36

33 20 1 SPARE 0 -- SPACE 1 -- 34

31 20 1 SPARE 0 -- SPACE 1 -- 32

29 20 1 SPARE 0 -- SPACE 1 -- 30

27 20 1 SPARE 0 -- SPACE 1 -- 28

25 30 1 BAY LIGHTING AREA D3 2-#6 AWG, #6 AWG GND IN 3/4"C 2600 -- SPACE 1 -- 26

23 30 1 BAY LIGHTING AREA D2 2-#6 AWG, #6 AWG GND IN 3/4"C 5600 0 SPARE 1 20 24

21 30 1 BAY LIGHTING AREA D1 2-#6 AWG, #6 AWG GND IN 3/4"C 5600 0 SPARE 1 20 22

19 30 1 BAY LIGHTING AREA C3 2-#6 AWG, #6 AWG GND IN 3/4"C 5415 0 SPARE 1 20 20

17 30 1 BAY LIGHTING AREA C2 2-#6 AWG, #6 AWG GND IN 3/4"C 5600 0 SPARE 1 20 18

15 30 1 BAY LIGHTING AREA C1 2-#6 AWG, #6 AWG GND IN 3/4"C 5600 0 SPARE 1 20 16

13 30 1 BAY LIGHTING AREA B3 2-#6 AWG, #6 AWG GND IN 3/4"C 5600 0 SPARE 1 20 14

11 30 1 BAY LIGHTING AREA B2 2-#6 AWG, #6 AWG GND IN 3/4"C 5722 0 SPARE 1 20 12

9 30 1 BAY LIGHTING AREA B1 2-#6 AWG, #6 AWG GND IN 3/4"C 5600 0 SPARE 1 20 10

7 30 1 BAY LIGHTING AREA A3 2-#6 AWG, #6 AWG GND IN 3/4"C 5600 0 SPARE 1 20 8

5 30 1 BAY LIGHTING AREA A2 2-#6 AWG, #6 AWG GND IN 3/4"C 5600 0 SPARE 1 20 6

3 30 1 BAY LIGHTING AREA A1 2-#6 AWG, #6 AWG GND IN 3/4"C 5610 2070 2-#12 AWG, #12 AWG GND IN 3/4"C LIGHTING UNSECURE AREA 1 20 4

1 20 1 LIGHTING EXTERIOR 2-#10 AWG, #10 AWG GND IN 3/4"C 1906 761 2-#12 AWG, #12 AWG GND IN 3/4"C LIGHTING SECURE AREA NORTH 1 20 2

# BKR P LOAD SERVED WIRE / GROUND / CONDUIT A B C WIRE / GROUND / CONDUIT LOAD SERVED P BKR #

* SIZE PER MANUFACTURER'S RECOMMENDATIONS.

NOTES:

ENCLOSURE: NEMA 1 MCB RATING: 150 A

MOUNTING: SURFACE WIRES: 4 MAINS RATING: 250 A

SUPPLY FROM: SWBD1 PHASE: 3 MAINS TYPE: MCB

LOCATION: ELEC 107 VOLTAGE: 480Y/277V A.I.C. RATING: 35000

PANELBOARD: LP1

DEMAND WITH EXPANSION: 91 A

TOTAL ESTIMATED DEMAND CURRENT: 76 A

TOTAL CONNECTED CURRENT: 103 A

TOTAL ESTIMATED DEMAND LOAD: 62948 VA

TOTAL CONNECTED LOAD: 85443 VA

PANEL TOTALS

TOTAL LOAD: 28823 VA 27240 VA 29380 VA

41 -- -- -- -- 941 -- SPACE 1 -- 42

39 -- -- -- -- 941 -- SPACE 1 -- 40

37 20 3 HWP-104 RM 105 3-#12 AWG, #12 AWG GND IN 3/4"C 941 -- SPACE 1 -- 38

35 -- -- -- -- 941 0 -- -- -- -- 36

33 -- -- -- -- 941 0 -- -- -- -- 34

31 20 3 HWP-103 RM 105 3-#12 AWG, #12 AWG GND IN 3/4"C 941 0 SPARE 3 20 32

29 -- -- -- -- 3875 0 -- -- -- -- 30

27 -- -- -- -- 3875 0 -- -- -- -- 28

25 25 3 CHWP-102 RM 105 3-#12 AWG, #12 AWG GND IN 3/4"C 3875 0 SPARE 3 20 26

23 -- -- -- -- 3875 2104 -- -- -- -- 24

21 -- -- -- -- 3875 2104 -- -- -- -- 22

19 25 3 CHWP-101 RM 105 3-#12 AWG, #12 AWG GND IN 3/4"C 3875 2104 3-#12 AWG, #12 AWG GND IN 3/4"C RF-101 MECH 105 3 20 20

17 -- -- -- -- 3045 238 -- -- -- -- 18

15 -- -- -- -- 3045 238 -- -- -- -- 16

13 20 3 HWP-102 RM 105 3-#12 AWG, #12 AWG GND IN 3/4"C 3045 238 3-#12 AWG, #12 AWG GND IN 3/4"C SF-102 ELEC 107 3 20 14

11 -- -- -- -- 3045 830 -- -- -- -- 12

9 -- -- -- -- 3045 830 -- -- -- -- 10

7 20 3 HWP-101 RM 105 3-#12 AWG, #12 AWG GND IN 3/4"C 3045 830 3-#12 AWG, #12 AWG GND IN 3/4"C SF-101 FOAM 104 3 20 8

5 -- -- -- -- 9657 830 -- -- -- -- 6

3 -- -- -- -- 7517 830 -- -- -- -- 4

1 70 3 MT1 3-#4 AWG, #8 AWG GND IN 1-1/2"C 9100 830 3-#12 AWG, #12 AWG GND IN 3/4"C HWP-105 RM 105 3 20 2

# BKR P LOAD SERVED WIRE / GROUND / CONDUIT A B C WIRE / GROUND / CONDUIT LOAD SERVED P BKR #

NOTES:

ENCLOSURE: NEMA 1 MCB RATING: 150 A

MOUNTING: SURFACE WIRES: 4 MAINS RATING: 250 A

SUPPLY FROM: SWBD1 PHASE: 3 MAINS TYPE: MCB

LOCATION: ELEC 107 VOLTAGE: 480Y/277V A.I.C. RATING: 35000

PANELBOARD: MP1

DEMAND WITH EXPANSION: 209 A

TOTAL ESTIMATED DEMAND CURRENT: 174 A

TOTAL CONNECTED CURRENT: 174 A

TOTAL ESTIMATED DEMAND LOAD: 144696 VA

TOTAL CONNECTED LOAD: 144696 VA

PANEL TOTALS

TOTAL LOAD: 48232 VA 48232 VA 48232 VA

41 -- -- -- -- 6228 -- SPACE 1 -- 42

39 -- -- -- -- 6228 -- SPACE 1 -- 40

37 30 3 SG-101 RM 105 3-#10 AWG, #10 AWG GND IN 3/4"C 6228 -- SPACE 1 -- 38

35 -- 1 SPACE -- 0 -- -- -- -- 36

33 -- 1 SPACE -- 0 -- -- -- -- 34

31 -- 1 SPACE -- 0 SPARE 3 20 32

29 -- -- -- -- 3875 0 -- -- -- -- 30

27 -- -- -- -- 3875 0 -- -- -- -- 28

25 40 3 AC-101 RM 105 3-#8 AWG, #10 AWG GND IN 1"C 3875 0 SPARE 3 60 26

23 -- -- -- -- 3322 319 -- -- -- -- 24

21 -- -- -- -- 3322 319 -- -- -- -- 22

19 25 3 AHU-102 RM 105 3-#10 AWG, #10 AWG GND IN 3/4"C 3322 319 3-#12 AWG, #12 AWG GND IN 3/4"C RO-101 MECH 105 3 20 20

17 -- -- -- -- 12733 9522 -- -- -- -- 18

15 -- -- -- -- 12733 9522 -- -- -- -- 16

13 100 3 AHU-101 RM 105 3-#1 AWG, #8 AWG GND IN 1-1/2"C 12733 9522 3-#3 AWG, #8 AWG GND IN 1-1/2"C DOAS-101 FAN 2 MECH 105 3 20 14

11 -- -- -- -- 941 830 -- -- -- -- 12

9 -- -- -- -- 941 830 -- -- -- -- 10

7 20 3 DOAS-102 RM 105 3-#12 AWG, #12 AWG GND IN 3/4"C 941 830 3-#12 AWG, #12 AWG GND IN 3/4"C HWP-106 MECH 105 3 20 8

5 -- -- -- -- 9522 941 -- -- -- -- 6

3 -- -- -- -- 9522 941 -- -- -- -- 4

1 80 3 DOAS-101 FAN 1 RM 105 3-#3 AWG, #8 AWG GND IN 1-1/2"C 9522 941 3-#12 AWG, #12 AWG GND IN 3/4"C SF-103 RM 105 3 20 2

# BKR P LOAD SERVED WIRE / GROUND / CONDUIT A B C WIRE / GROUND / CONDUIT LOAD SERVED P BKR #

NOTES:

ENCLOSURE: NEMA 1 MCB RATING: 400 A

MOUNTING: SURFACE WIRES: 4 MAINS RATING: 400 A

SUPPLY FROM: SWBD1 PHASE: 3 MAINS TYPE: MCB

LOCATION: ELEC 107 VOLTAGE: 480Y/277V A.I.C. RATING: 35000

PANELBOARD: MP2

DEMAND WITH EXPANSION: 82 A

TOTAL ESTIMATED DEMAND CURRENT: 68 A

TOTAL CONNECTED CURRENT: 73 A

TOTAL ESTIMATED DEMAND LOAD: 24537 VA

TOTAL CONNECTED LOAD: 26273 VA

PANEL TOTALS

TOTAL LOAD: 9100 VA 7517 VA 9657 VA

53 20 1 SG-103 MECH 105 2-#10 AWG, #10 AWG GND IN 3/4"C 1068 -- SPACE 1 -- 54

51 20 1 SG-102 MECH 105 2-#12 AWG, #12 AWG GND IN 3/4"C 324 -- SPACE 1 -- 52

49 20 1 SPARE 0 -- SPACE 1 -- 50

47 20 1 JB DDC PNL MECH 105 2-#12 AWG, #12 AWG GND IN 3/4"C 500 -- SPACE 1 -- 48

45 20 1 JB DDC PNL MECH 105 2-#12 AWG, #12 AWG GND IN 3/4"C 500 -- SPACE 1 -- 46

43 20 1 JB DDC PNL MECH 105 2-#12 AWG, #12 AWG GND IN 3/4"C 500 -- SPACE 1 -- 44

41 -- -- -- -- 1283 0 SPARE 1 20 42

39 -- -- -- -- 1283 0 SPARE 1 20 40

37 20 3 HWB-102 RM 105 3-#12 AWG, #12 AWG GND IN 3/4"C 1283 0 SPARE 1 20 38

35 -- -- -- -- 1283 0 SPARE 1 20 36

33 -- -- -- -- 1283 0 SPARE 1 20 34

31 20 3 HWB-101 RM 105 3-#12 AWG, #12 AWG GND IN 3/4"C 1283 0 SPARE 1 20 32

29 20 1 EF-102 RM 103 2-#10 AWG, #10 AWG GND IN 3/4"C 1176 0 SPARE 1 20 30

27 20 1 EF-101 RM 116 2-#12 AWG, #12 AWG GND IN 3/4"C 1176 0 SPARE 1 20 28

25 20 1 JB BOILER CNTRL PNL RM 105 2-#12 AWG, #12 AWG GND IN 3/4"C 500 0 SPARE 1 20 26

23 20 1 RP-1 MECH 105 2-#12 AWG, #12 AWG GND IN 3/4"C 696 0 SPARE 1 20 24

21 20 1 SPARE 0 0 SPARE 1 20 22

19 20 1 RECEPT GLY-102 MECH 105 2-#12 AWG, #12 AWG GND IN 3/4"C 180 681 2-#12 AWG, #12 AWG GND IN 3/4"C RAD-101 1 20 20

17 20 1 FCU-103 RM 116 2-#10 AWG, #10 AWG GND IN 3/4"C 1176 180 2-#12 AWG, #12 AWG GND IN 3/4"C RECEPT WCF-101 MECH 105 1 20 18

15 20 1 FCU-102 RM 118 2-#12 AWG, #12 AWG GND IN 3/4"C 864 64 2-#12 AWG, #12 AWG GND IN 3/4"C UH-106 & 107 1 20 16

13 20 1 FCU-101 RM 118 2-#12 AWG, #12 AWG GND IN 3/4"C 864 360 2-#12 AWG, #12 AWG GND IN 3/4"C RECEPT LAV RM 112 & 113 1 20 14

11 20 1 CUH-101 RM 117 2-#12 AWG, #12 AWG GND IN 3/4"C 50 864 2-#12 AWG, #12 AWG GND IN 3/4"C JB SUMP CNTRL PNL RM 105 1 20 12

9 -- -- -- -- 1600 180 2-#12 AWG, #12 AWG GND IN 3/4"C RECEPT ETP-101 MECH 105 1 20 10

7 30 2 EUH-101 RM 107 2-#10 AWG, #10 AWG GND IN 3/4"C 1600 180 2-#12 AWG, #12 AWG GND IN 3/4"C JB EM SHOWER MECH 105 1 20 8

5 20 1 DWH-101 RM 105 2-#12 AWG, #12 AWG GND IN 3/4"C 1200 180 2-#12 AWG, #12 AWG GND IN 3/4"C RECEPT GLY-101 MECH 105 1 20 6

3 20 1 UH-104 & 105 2-#12 AWG, #12 AWG GND IN 3/4"C 62 180 2-#12 AWG, #12 AWG GND IN 3/4"C RECEPT WS-101 MECH 105 1 20 4

1 20 1 UH-101-103 2-#12 AWG, #12 AWG GND IN 3/4"C 96 1572 2-#10 AWG, #10 AWG GND IN 3/4"C HWB-103 RM 105 1 20 2

# BKR P LOAD SERVED WIRE / GROUND / CONDUIT A B C WIRE / GROUND / CONDUIT LOAD SERVED P BKR #

NOTES:

ENCLOSURE: NEMA 1 MCB RATING: 150 A

MOUNTING: SURFACE WIRES: 4 MAINS RATING: 250 A

SUPPLY FROM: MT1 PHASE: 3 MAINS TYPE: MCB

LOCATION: ELEC 107 VOLTAGE: 208Y/120V A.I.C. RATING: 10000

PANELBOARD: MR1

GENERAL SHEET NOTES:

1. SEE SHEETS E-001 AND E-002 FOR GENERAL NOTES, LEGEND, AND ABBREVIATIONS.

2. CONVERT WIRE SIZE TO #10 AWG PRIOR TO TERMINATING ON A 120V, 20A WIRING

DEVICE IF THE WIRE SIZE INDICATED IS LARGER THAN WHAT A 120V, 20A WIRING

DEVICE CAN ACCEPT.

A

M -0

D

E S

IG

N

I S

S U

E F

O R

P R

IC

IN

G N

O V

A

M E

N D

M E

N T

J a n

SLOPE

(SEE PLANS)

CAULKED OUTLET

SEE PLANS FOR

TYPE REQUIRED

STRAINER

COVER

CLEANOUT PLUG

MAIN LINE

FINISHED FLOOR

OR CONCRETE PAD

CAULK, BUNA-N

OR VITON SEAL

RISER EXTENSION

UP TO CLEANOUT.

NEED NOT BE

LARGER SIZE THAN 4"

FLOOR DRAIN

SERVICE SINK

OR SHOWER

THREADED OUTLET

DRAIN PIPING - SEE

PLANS FOR SIZE.

CIVIL

INTERFACE

TYPE K COPPER OR

SCH 80 CPVC PIPE

M

IN

IM

U

M C

O V

E R

5'-0"

12"

INSULATING FLANGE

SLEEVE PENETRATION.

FILL SPACE AROUND PIPE

WITH FIREPROOF MASTIC

GRADE

ALL PIPE AND FITTINGS SHALL BE AS INDICATED IN SPECIFICATIONS.

COAT UNDERGROUND PIPING WITH PE COATING FOR CORROSION PROTECTION.

FULL FACED NEOPRENE GASKETS SHALL BE REQUIRED ON ALL FLANGED

FITTINGS.

PROVIDE STRAIGHT SECTION OF PIPE BEFORE AND AFTER METER AS REQUIRED

BY METER MANUFACTURER'S WRITTEN INSTRUCTIONS.

1.

2.

3.

4.

NOTES:

CONCRETE THRUST BLOCK

(TYP) MIN 2 SF BEARING FACE

M

IN

OS&Y VALVE (TYP)

JOINT OR

TRANSITION

AIR GAP

30" MINIMUMROUTE FULL

SIZE TO NEAREST

FLOOR DRAIN

FINISHED FLOOR

SUPPORT

STAND

(TYP)

ANCHOR TO FLR (TYP)

FLOOR DRAIN WITH FUNNEL

REDUCED PRESSURE

BACKFLOW PREVENTOR

(SEE PLANS FOR SIZE)

STRAINER

2" BYPASS

NC

2" WATER

METER

BALL VALVE

PRESSURE

REDUCING

VALVE (65 PSIG)

TYPE L COPPER TYPE

GRADE

BYPASS

REDUCER

GAS METER:

HANGAR: 6800 CFH @ 45 PSIG

PRESSURE GAUGE

BACKUP PRESSURE

REDUCER VALVE (MAIN

PRESSURE IN & 13 IN

WG OUT)

UNION (TYP.)

STRAINER

GAS COCK

(LOCKING)

GAS COCK (NON-LOCKING)

WALL

GAS MAIN

45 PSIG

ANODELESS RISER

GAS COCK

(LOCKING)

PRESSURE REDUCING

VALVE (MAIN PRESSURE

IN & 10 IN WG OUT)

NTSSCALE:A8

FLOOR DRAIN INSTALLED IN GROUND FLOOR

NTSSCALE:A14

CLEANOUT

US Army Corps of Engineers ®

SHEET ID

U .S

A

R M

Y C

O R

P S

O F

E N

G

IN

E E

A

H A

D

IS

T R

IC

T

C

A P

IT

O

L A

V E

N U

E O

M A

H A

N

E

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

S U

B M

IT

T

E D

B Y

S

IZ

E

C H

E C

K E

D B

Y

A N

S I D

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

S O

L

IC

IT

A

T

IO

N N

O

N

3 5 7 9 11 13 15 17 19

L

J

G

E

C

A

D A

T E

M A

R K

D E

S C

R

IP

T

IO

N

2 4 6 8 10 12 14 16 18 20

P

M

K

H

F

D

B

W

A R

D P

A R

K W

A Y

K

A N

S A

S C

IT

Y

M

O

A M

A S

H E

K E

L

A F

D R

A W

IN

G

C O

D E

E L L S

W O

R T

H A

IR

F

O R

C E

B A

S E

S

D

P N

F X

B M

B -2

R

A D

IO

F

R E

Q U

E N

C Y

F A

C

IL

IT

Y

R

F H

A N

G A

R

(F Y

N O

V E

M B

E R

A D

V E

R T

IS

E

M E

N T

D E

S

IG

N

W F

-2 -R

-0

P-501

P L U

M B

IN

G

D E

T A

IL

S

T K

A R

R E

N N

IE

M

A N

N

J M c C

L U

S K

E Y

NTSSCALE:A3

FLOOR DRAIN IN

SERVICE SINK OR SHOWER

NTSSCALE:G9

DOMESTIC WATER ENTRANCE AND BACKFLOW PREVENTER

NTSSCALE:G1

NATURAL GAS PRESSURE REGULATOR/METER W/ BYPASS

A

M -0

D

E S

IG

N

I S

S U

E F

O R

P R

IC

IN

G N

O V

A

M -0

A

E N

D M

E N

T

J A

N

12109 13 14

F

G

H

DATA ANALYSIS

CTK

VEST

NURSING

VEST

WOMENS

VEST

ELEC

COMM

OPEN OFFICE

SERVER

CORR

LOCKER

MENS

BREAK

MATCH LINE

TN103

M A

T C

H L

IN

E

T N

J1

TN401

J9

TN401

H1

TN402

H9

TN402

1WS

1WR

1WR

12"W X 4"D

9' - 8" AFF

(CLASSIFIED - FOR RED AND

ORANGE COMMUNICATIONS

CABLES, UON)

MEASUREMENT BAY

OFFICE

CORR

(UNCLASSIFIED - FOR

GREEN COMMUNICATIONS

CABLES)

W

R

12"W X 4"D

9' - 6" AFF

JAN

K

J

OFFICE

4WS

8WSE 8WSE

8WSE

8WSE 8WSE

8WSE

8WSE

8WSE

8WSE 8WSE 8WSE

8WSE

W

S E

W

S E

W

S E

W

S E

W

S E

W

S E

W

S

W

S E

3WS

3WS

J

JJJ J

(TYP)

(TYP)

J J

W

S

9WSE

6WSE

10WSE 10WSE 10WSE

1WS

10WSE 10WSE 10WSE

10WSE

M C

E

W

S

GROUND FLOOR

CEILING

J

J

J

JJ

OPERATOR DESK

FLAT PANEL

DISPLAY

1. PROVIDE SURFACE MOUNTED RACEWAY SYSTEM

FOR FUTURE VIDEO CONFERENCING SYSTEM.

PREPARE AND SUBMIT WALL ELEVATION

COORDINATION DRAWINGS FOR APPROVAL BY

THE COR.

NOTES:

GROUND FLOOR

J

J

OPERATOR DESK

FLAT PANEL

DISPLAY

1. PROVIDE SURFACE MOUNTED RACEWAY

SYSTEM FOR FUTURE AV SYSTEM. PREPARE

AND SUBMIT WALL ELEVATION COORDINATION

DRAWINGS FOR APPROVAL BY THE COR.

NOTES:

PLAN

NORTH

US Army Corps of Engineers ®

SHEET ID

U .S

A

R M

Y C

O R

P S

O F

E N

G

IN

E E

A

H A

D

IS

T R

IC

T

C

A P

IT

O

L A

V E

N U

E O

M A

H A

N

E

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

S U

B M

IT

T

E D

B Y

S

IZ

E

C H

E C

K E

D B

Y

A N

S I D

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

S O

L

IC

IT

A

T

IO

N N

O

N

3 5 7 9 11 13 15 17 19

L

J

G

E

C

A

D A

T E

M A

R K

D E

S C

R

IP

T

IO

N

2 4 6 8 10 12 14 16 18 20

P

M

K

H

F

D

B

W

A R

D P

A R

K W

A Y

K

A N

S A

S C

IT

Y

M

O

A M

A S

H E

K E

L

A F

D R

A W

IN

G

C O

D E

E L L S

W O

R T

H A

IR

F

O R

C E

B A

S E

S

D

P N

F X

B M

B -2

R

A D

IO

F

R E

Q U

E N

C Y

F A

C

IL

IT

Y

R

F H

A N

G A

R

(F Y

O C

T O

B E

R

A D

V E

R T

IS

E

M E

N T

D E

S

IG

N

A B C

E F

KEY PLAN

NOT TO SCALE

D

W F

-2 -R

-0

TN106

T E

L E

C O

M M

U N

IC

A

T

IO

N S

P L A

N

A R

E A

F

J M

A J O

R S

M B

A X

P O

'G O

R M

A N

GENERAL SHEET NOTES:

1. SEE SHEET TN001 FOR PROJECT GENERAL NOTES,

SYMBOL LEGEND AND ABBREVIATIONS.

2. COMMUNICATIONS FACEPLATES MUST BE CABLED TO

RM 110 UNLESS OTHERWISE NOTED.

SCALE: 1/8" = 1'-0"

A1

TELECOMMUNICATION PLAN - AREA F

0 4' 8' 16'

SHEET KEYNOTES:

1. COMMUNICATIONS FACEPLATES LOCATED IN THIS

ROOM MUST BE CABLED TO RM 108.

2. ORANGE COMMUNICATIONS CABLING MUST BE

ROUTED THROUGH PDS BETWEEN ROOM 122 AND

ROOM 109.

3. PROVIDE MINIMUM 1-3/4" DEEP X 2-1/2" HIGH SINGLE

COMPARTMENT SURFACE MOUNTED RACEWAY. SEE

DETAILS A1 AND A9 ON SHEET TN505.

4. MOUNT COMMUNICATIONS FACEPLATE AT 18" AFF.

5. PROVIDE MINIMUM OF 2" DEEP X 4"TALL X 4" WIDE

METALLIC SURFACE MOUNT RACEWAY BOX, WHITE IN

COLOR, FOR FUTURE AV SYSTEM CABLING MOUNTED

AT 60" AFF.

6. SURFACE MOUNT COMMUNICATIONS CONDUIT AND

JUNCTION BOXES WITHIN THIS ROOM.

7. PROVIDE SURFACE MOUNTED RACEWAY BOX WITH

HINGED COVER, MINIMUM OF 6" WIDE X 6" TALL BY 4"

DEEP. RACEWAY BOX TO BE PROVIDED AS PART OF

SURFACE RACEWAY SYSTEM, SEE DETAIL A1 ON

SHEET TN505. MOUNT AT 18" AFF.

8. TRANSITION FROM SURFACE MOUNTED RACEWAY TO

1-1/2" CONDUIT ABOVE CEILING.

9. 4-11/16" SQUARE JUNCTION BOX WITH SCREW ON

COVER MOUNTED ABOVE CEILING FOR FUTURE VIDEO

CONFERENCING SYSTEM CABLING.

10. PROVIDE STC RATED SECURE BOUNDARY

PENETRATION. SEE DETAIL A14 ON SHEET TN504.

11. PROVIDE NON-RATED WALL CABLE TRAY

PENETRATION. SEE DETAIL J14 ON TN504.

12. DO NOT ROUTE CONDUIT UNDER SLAB IN

MEASUREMENT BAY.

13. COMMUNICATIONS FACEPLATE MUST BE CABLED TO

MCE03.

14. PROTECTIVE DISTRIBUTION SYSTEM (BASIS OF

DESIGN HOLOCOM OR WIREMOLD DATA-FENSE) FOR

RM 122 ORANGE COMMUNICATIONS CABLES.

9 (TYP)10

NTSSCALE:

K13

RM 122 - VIDEO CONFERENCING

CONDUIT RISER

9 (TYP)

6 6

NTSSCALE:

C13

RM 109 - VIDEO CONFERENCING

CONDUIT RISER

A

M

- 0

D E

S

IG

N I S

S U

E F

O R

P R

IC

I N

G N

O V

A

M E

N D

M E

N T

D E

C

A

M E

N D

M E

N T

J A

N

AM0005_Electrical
Sheets
EP115 - HVAC POWER PLAN - AREA E
EP702 - PANELBOARD SCHEDULES
AM-0005_P-501 - PLUMBING DETAILS
Sheets
P-501 - PLUMBING DETAILS
TN106.pdf
Sheets
EP115 - HVAC POWER PLAN - AREA E
EP702 - PANELBOARD SCHEDULES

File details come from the government source that posted it. Updated .