CONC. STRUCTURE TYPE STRENGTH (PSI) DENSITY (PCF) W/C RATIO
ALL CONCRETE FOOTINGS,
TIE BEAMS, SLAB ON GRADE,
STRUCTURAL SLABS,
COLUMNS AND BEAMS.
4000 150 0.45
NON-STRUCTURAL CONCRETE
SLABS AND STAIRS ON GRADE,
CURBS, AND OTHER
NON-STRUCTURAL CONCRETE
3000 150 0.45
5. CONTRACTOR SHALL SUBMIT SHOP DRAWINGS AND OBTAIN APPROVAL
PRIOR TO FABRICATION.
6. ALL REBAR SHALL BE EPOXY-COATED FOR CORROSION RESISTANCE, UNO.
FABRICATION, HANDRAILING AND REPAIR OF EPOXY-COATED REINFORCING
BARS SHALL COMPLY WITH THE REQUIREMENTS OF ASTM D3963 AND
ASTM A934.
7. U.N.O. ON STRUCTURAL DRAWINGS, PROVIDE MINIMUM CONCRETE
PROTECTION FOR REINFORCING AS FOLLOWS:
CAST AGAINST EARTH 3"
EXPOSED TO EARTH OR WEATHER:
#5 AND SMALLER BARS AND W.W.F. 1-1/2" (U.N.O.)
#6 AND LARGER BARS 2"
NOT EXPOSED TO EARTH OR WEATHER:
SLABS AND WALLS:
#6 AND LARGER BARS AND W.W.F. 3/4"
#7 AND #8 BARS 1"
#9 AND LARGER BARS 1-1/2"
BEAMS AND COLUMNS 1-1/2"
SLABS SUBJECT TO VEHICULAR TRAFFIC:
FRAMED SLABS TOP COVER 2"
BOTTOM COVER 3/4"
8. WHERE CONSTRUCTION JOINTS ARE PROVIDED, THE REINFORCEMENT
SHALL PASS CONTINUOUSLY THROUGH THE JOINT.
9. ALL WELDING OF REINFORCING TO BE DONE WITH E90XX ELECTRODES IN
ACCORDANCE WITH A.W.S. SPECIFICATIONS D1.4 (LATEST EDITION).
REINFORCING STEEL, CONT:
1. 2012 INTERNATIONAL BUILDING CODE
2. ACI 318-11
3. ACI 530-11
4. AWS D1.1, D1.3, D1.4
5. ASTM CURRENT EDITION
6. ASCE 7-10
7. AISC 341-10
8. AISC 360-10
9. UFC 3-301-01
10. UFC 3-301-04
11. STEEL DECK INSTITUTE DESIGN MANUAL FOR COMPOSITE DECK,
FORM DECK AND ROOF DECK.
MAJOR CODES AND STANDARDS:
1. ALL REINFORCING STEEL INCLUDING STIRRUPS AND TIES,
SHALL BE HIGH STRENGTH, CONFORMING TO ASTM A615 GRADE 60 (FY =
60,000PSI). ALL REINFORCING TO BE WELDED SHALL CONFORM TO ASTM
A706 GRADE 60. ALL REINFORCING BARS SHALL BE EPOXY COATED FOR
BOTH ON-SHORE AND PIER BUILDINGS UNO. SEE NOTE 6.
2. ALL REINFORCING SHALL BE DETAILED, FABRICATED, AND PLACED IN
ACCORDANCE WITH ACI-SP-66 ACI DETAILING MANUAL (LATEST EDITION),
SEE SPEC SECTION 03 20 00.00 10.
3. REINFORCING BARS SHALL BE SPLICED AS SHOWN ON DRAWINGS. ANY
ADDITIONAL SPLICING SHALL REQUIRE PRIOR APPROVAL FROM THE
STRUCTURAL ENGINEER. WHERE SPLICE LENGTHS ARE NOT EXPLICITLY
CALLED OUT ON DETAILS, THE MINIMUM SPLICE (IN COMPRESSION) IS 45
DIAMETERS IN CONCRETE; AND IN TENSION (FOR CONCRETE) AS NOTED ON
DETAILS. EMBEDMENT AND HOOK LENGTHS SHALL BE PER ACI 318-08.
4. ALL BARS SHALL BE CLEAN OF RUST, GREASE AND OTHER MATERIALS
LIKELY TO IMPAIR BOND. ALL BENDS SHALL BE MADE COLD.
REINFORCING STEEL:
R E G
IS
T E R E
D
PR
OFESS IONAL
E N G
IN
E E R
S T A
T E
O F CA L I F
OR
N I A
C T U R A
L
URT
S
OF
D E
S
IG
N E
D B
Y
US Army Corps of Engineers Honolulu District
A E
C O
M B
IS
H
O P
S Q
U A
R E
A
S B
T O
W E
R B
IS
H
O P
S T
R E
E T
S
U
IT
E
H O
N O
L U
L U
H
A W
A
II
/2 /2
F
Y
M
C A
P N
E C
H O
P
IE
R R
E S
T O
R A
T
IO
N U
S A
R M
Y K
W A
J A
L E
IN
A
T O
L L
U S
A K
A
A
B
C
D
2 3 4 5
P L
O T
S C
A L E
S U
B M
IT
T
E D
B Y
D R
A W
N B
Y
S
IZ
E
A N
S I D
P L
O T
D A
T E
C H
E C
K E
D B
Y
D A
T E
D R
A W
IN
G
N U
M B
E R
L O
C A
T
IO
N C
O D
E
S O
L
IC
IT
C
O N
T R
A C
T N
O
R E
V
IS
IO
N
F
IL
E N
A M
E
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E A
P P
R
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E A
P P
R
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
R S
H O
N O
L U
L U
D
IS
T R
IC
T
F T
S H
A F
T E
R H
A W
A
II
SHEET
IDENTIFICATION
SHEET
/0
/1
W
A -0
-D
-0
-0
R T
A S
U B
M
IT
T A
L
MOHAMED S.
ALAM
No. S 3648
Exp. 03-31-16
O N
-S H
O R
E
P
IE
R B
U
IL
D
IN
G
K W
A J -E
C H
O -P
IE
R
O
S
S
C E
N T
R A
L
2"
'-0
A
M -0
/2
6/
S-011
G E
N E
R A
L N
O T
E S
K
N G
U Y
E N
M
R A
M
IR
E Z
S
A
LA
M
1-
-0
S
A
LA
M
A F
1. THE STRUCTURAL DESIGN IS BASED ON THE STRUCTURE IN ITS
COMPLETED STATE. THE CONTRACTOR AND HIS SUBS SHALL BE
RESPONSIBLE FOR PROVIDING TEMPORARY BRACING AND SHORING,
AS REQUIRED, TO ENSURE VERTICAL AND LATERAL STABILITY OF THE
ENTIRE STRUCTURE OR PORTION THEREOF DURING CONSTRUCTION.
2. STRUCTURAL DRAWINGS SHALL BE READ IN CONJUNCTION WITH
SPECIFICATIONS AND ALL OTHER DRAWINGS RELATING TO THE WORK.
3. LOCATION AND SIZES OF OPENINGS IN FLOORS, ROOFS AND WALLS
SHALL BE VERIFIED WITH ARCHITECTURAL, MECHANICAL, PLUMBING,
FIRE PROTECTION AND ELECTRICAL DRAWINGS.
4. NO PIPES, CONDUITS OR DUCTS SHALL BE PLACED IN SLABS, BEAMS,
FOOTINGS OR WALLS, UNLESS SPECIFICALLY DETAILED ON
STRUCTURAL DRAWINGS FOR THAT PURPOSE.
5. LOCATION AND SIZE OF EQUIPMENT SHALL BE VERIFIED WITH
PLUMBING, FIRE PROTECTION, MECHANICAL, ELECTRICAL &
MANUFACTURER'S DRAWINGS.
6. SEE PLUMBING, FIRE PROTECTION, MECHANICAL, ELECTRICAL AND
MANUFACTURER'S DRAWINGS FOR SIZE, LOCATION AND ANCHOR BOLT
REQUIREMENTS OF ALL EQUIPMENT. THE CONTRACTOR SHALL
OBTAIN MANUFACTURER'S TEMPLATES SHOWING ANCHOR BOLT
LOCATION FOR ALL EQUIPMENT.
7. SEE ARCHITECTURAL PLANS FOR LOCATION OF ALL NON-BEARING
PARTITIONS, CONCRETE CURBS, FLOOR AND ROOF SLOPES, DRAINS
AND LOCATION AND DETAILS FOR ALL MISCELLANEOUS HANDRAILS,
LADDERS HANGERS & STEEL GRATINGS. FOR LOCATION AND DETAIL
OF MISCELLANEOUS YARD WORK INCLUDING WALKS, CURBS &
DRIVEWAYS, SEE CIVIL DRAWINGS.
8. FOR UNDERGROUND UTILITIES, SEE CIVIL DRAWINGS.
9. SPECIFIC NOTES AND DETAILS SHALL TAKE PRECEDENCE OVER
GENERAL NOTES AND TYPICAL DETAILS. DO NOT SCALE DRAWINGS.
10. THE CONTRACTOR SHALL MEASURE AND PROVIDE ALL EXISTING FIELD
DIMENSIONS, ELEVATIONS AND CONDITIONS AT THE JOB SITE PRIOR
TO CONSTRUCTION AND THE SUBMISSION OF SHOP DRAWINGS AND
SHALL NOTIFY THE CONTRACTING OFFICER IMMEDIATELY OF ANY
DISCREPANCIES. VERIFICATION AND NOTIFICATION SHALL PROCEED
PRIOR TO THE START OF THE WORK SO THAT ANY NECESSARY
CHANGES CAN BE MADE WITHOUT DELAYING THE PROJECT
SCHEDULE.
11. THE CONTRACTOR SHALL REVIEW AND COORDINATE DIMENSIONS
PROVIDED IN THE CONTRACT DOCUMENTS LAYOUT OF BUILDING
FOUNDATIONS AND OTHER STRUCTURAL MEMBERS SHALL BE BASED
ON THE FULL SET OF CONTRACT DOCUMENTS, INCLUDING BUT NOT
LIMITED TO THE ARCHITECTURAL, CIVIL AND STRUCTURAL DRAWINGS
AND THE PROJECT SPECIFICATIONS, INCONSISTENCIES OR OMISSIONS
IN DIMENSIONS SHALL BE FORWARDED TO THE CONTRACTING
OFFICER FOR REVIEW AND RESOLUTION.
12. DETAILS, SECTIONS AND NOTES SHOWN ON THESE DRAWINGS ARE
INTENDED TO BE TYPICAL AND SHALL APPLY TO SIMILAR CONDITIONS
ELSEWHERE UNLESS OTHERWISE SHOWN OR NOTED.
13. ALL WALLS ARE DESIGNED AS LATERALLY BRACED BY THE FLOOR AND
ROOF SYSTEMS. CONTRACTOR SHALL ENSURE THAT WALLS ARE
ADEQUATELY BRACED DURING CONSTRUCTION.
14. TEMPORARY BRACING SHALL BE PROVIDED FOR ALL WALLS SUBJECT
TO UNBALANCE BACKFILL. BRACE WALL PLUMB UNTIL STABILIZING
ELEMENT ABOVE IS IN PLACE.
15. ANY REQUIRED TEMPORARY SHEETING AND SHORING SHALL BE IN
CONFORMANCE WITH OSHA REGULATIONS UNBRACED EXCAVATIONS
SHALL BE SLOPED NOT GREATER THAN (1.5) HORIZONTAL TO (1)
VERTICAL.
16. IT IS THE CONTRACTOR'S RESPONSIBILITY TO RETAIN THE SERVICES
OF A REGISTERED CIVIL ENGINEER TO DETERMINE THE ALLOWABLE
TEMPORARY CONSTRUCTION LOADS AND TO PROVIDE A DESIGN FOR
ALL FALSE WORK, FORMWORK, STAGING'S, BRACING, SHEETING AND
SHORING WHENEVER THE LOADING FROM THE CONTRACTOR'S WORK
EXCEEDS THE ALLOWABLE LOAD CAPACITIES OF THE EXISTING
STRUCTURE.
17. CONTRACTOR SHALL LOCATE ALL UNDERGROUND UTILITIES IN THE
VICINITY OF FOUNDATIONS AND DETERMINE IF A CONFLICT EXISTS.
PROVIDE INFORMATION ON LOCATION SIZE AND ELEVATIONS OF
UTILITIES PRIOR TO START OF WORK SO THAT ANY NECESSARY
CHANGES CAN BE MADE WITHOUT DELAYING THE PROJECT
SCHEDULE.
18. THE DEVELOPMENT AND IMPLEMENTATION OF JOB SITE SAFETY AND
CONSTRUCTION PROCEDURES ARE THE SOLE RESPONSIBILITY OF THE
GENERAL CONTRACTOR.
19. OPENINGS, POCKETS, ETC. SHALL NOT BE PLACED IN STRUCTURAL
MEMBERS UNLESS SPECIFICALLY DETAILED ON THE STRUCTURAL
DRAWINGS. NOTIFY THE CONTRACTING OFFICER WHEN DRAWINGS BY
OTHERS INDICATE OPENINGS, POCKETS, ETC., NOT INDICATED ON THE
STRUCTURAL DRAWINGS, BUT WHICH ARE LOCATED IN STRUCTURAL
MEMBERS.
20. STRUCTURAL OBSERVATIONS PERFORMED BY GOVERNMENT DURING
CONSTRUCTION ARE NOT THE CONTINUOUS AND SPECIAL INSPECTION
SERVICES AND DO NOT WAIVE THE RESPONSIBILITY FOR THE
INSPECTIONS REQUIRED AS PART OF THE QUALITY CONTROL BY THE
CONTRACTOR. OBSERVATIONS ALSO DO NOT GUARANTEE
CONTRACTOR'S PERFORMANCE AND SHALL NOT BE CONSIDERED AS
SUPERVISION OF CONSTRUCTION.
21. DO NOT SPLICE STRUCTURAL MEMBERS UNLESS SPECIFICALLY
DETAILED AND INDICATED IN THIS SET OF DRAWINGS.
22. FOR FIREPROOFING REQUIREMENTS, SEE SPECIFICATIONS.
23. CONTINUOUS SPECIAL INSPECTION AND TESTING ON AS002, AS003
REQUIRED TO BE PERFORMED BY THE GOVERNMENT. CONTRACTOR
TO PROVIDE MINIMUM OF 2 WEEKS NOTICE IN ADVANCE TO SCHEDULE
INSPECTION REQUIRING GOVERNMENT ACTION.
GENERAL
1. ALL CONCRETE SHALL BE CONTROLLED CONCRETE, NORMAL WEIGHT (UNLESS
OTHERWISE NOTED) AND SHALL BE SUBMITTED TO THE CONTRACTOR BEFORE
USE, WITH COMPRESSIVE STRENGTH AS FOLLOWS:
2. ALL CONCRETE MIXES SHALL BE DESIGNED BY A VALIDATED TESTING
LABORATORY, AND STAMPED SEALED BY A LICENSED CIVIL ENGINEER AND
SUBMITTED TO THE CONTRACTING OFFICER FOR REVIEW PRIOR TO PLACING
CONCRETE. MIX DESIGNS FOR CAST-IN-PLACE CONCRETE SHALL BE PER THE
PROCEDURE SPECIFIED IN SPEC SECTION 03 30 00, PARAGRAPH 2.3.1.2
PROPORTIONING STUDIES NORMAL WEIGHT CONCRETE. CONCRETE
SPECIFICATIONS SECTION 03 30 00 TO BE USED FOR BOTH ON-SHORE AND PIER
BUILDINGS.
3. CALCIUM CHLORIDE SHALL NOT BE PERMITTED IN CONCRETE IN ANY FORM.
4. ALL CONCRETE SHALL INCLUDE MIGRATORY CORROSION INHIBITOR
ADMIXTURES.
5. CURING COMPOUND MUST BE APPLIED IMMEDIATELY FOLLOWING FINAL
FINISHING.
6. CONCRETE SHALL NOT BE DROPPED THROUGH REINFORCING STEEL SO AS TO
CAUSE SEGREGATION OF AGGREGATES. HOPPERS, VERTICAL CHUTES, OR
TRUNKS SHALL BE USED IN SUFFICIENT NUMBERS SO THAT THE FREE
UNCONFINED FALL OF CONCRETE SHALL NOT EXCEED SIX FEET AND TO ENSURE
THAT THE CONCRETE IS KEPT LEVEL AT ALL TIMES.
7. POWER WASH CONCRETE BEFORE FRESH CONCRETE IS POURED AGAINST
CONCRETE IN PLACE, THE CONTACT SURFACES OF CONCRETE IN-PLACE SHALL
BE THOROUGLY CLEANED. ALL LAITANCE SHALL BE REMOVED AND THE
CONTACT SURFACES SHALL BE THOROUGLY SLOSHED WITH GROUT CONSISTING
OF ONE PART SAND TO ONE PART CEMENT WITH MINIMUM AMOUNT OF WATER.
8. ALL KEYS SHALL BE 2" X 4" (NOMINAL) UNLESS OTHERWISE SHOWN ON THE
DRAWINGS.
9. ALL PLUMBING SLOTS AROUND SLEEVES SHALL BE FILLED WITH FIRE RATED
MATERIAL WITH AN EQUIVALENT RATING OF THE ADJACENT FLOOR
CONSTRUCTION.
10. ALUMINUM CONDUITS ARE NOT PERMITTED IN CONCRETE ELEMENTS.
11. ALL REINFORCING BARS, ANCHOR BOLTS AND OTHER CONCRETE INSERTS
SHALL BEWELL SECURED IN POSITION PRIOR TO PLACING CONCRETE AND
INSPECTION.
12. REFER TO ARCHITECTURAL DRAWINGS FOR MOLDS, GROOVES, ORNAMENTS,
CLIPS OR GROUNDS REQUIRED TO BE CAST INTO THE CONCRETE AND FOR
EXTENT OF DEPRESSIONS, RAMPS, ETC.
13. SLEEVE PLUMBING OPENINGS IN CONCRETE WALLS AND SLABS BEFORE
PLACING CONCRETE AND BEND REINFORCING AROUND SLEEVES. CORING IS
NOT PERMITTED IN FLOOR, ROOF, SLABS, COLUMNS AND WALLS UNLESS
APPROVED IN ADVANCE.
14. EXPOSED PROJECTION CORNERS OF SLABS, BEAMS, WALLS, COLUMNS, ETC.
SHALL BE FORMED WITH A 3/4" CHAMFER, UNLESS SHOWN OR NOTED
OTHERWISE.
15. CURING COMPOUNDS USED ON CONCRETE THAT IS TO RECEIVE FINISHES SHALL
BE COMPATIBLE WITH FINISH PAINT.
16. ALL TESTING AND INSPECTION OF CONCRETE SHALL CONFORM WITH THE
REQUIREMENTS OF SPEC SECTION 03 30 00. ALL CONCRETE MATERIALS, AND
THE MIXING AND PLACEMENT OF CONCRETE SHALL CONFORM WITH THE
REQUIREMENTS OF SPEC SECTION 03 30 00.
17. LOCATION OF ALL CONSTRUCTION JOINTS SHALL BE REVIEWED BY THE
CONTRACTING OFFICER.
18. ROUGHEN ALL CONSTRUCTION JOINTS TO A MINIMUM 1/4" AMPLITUDE, EXPOSING
AGGREGATE FIRMLY EMBEDDED IN THE CEMENT.
19. CONDUIT OR PIPE SIZE (O.D.) SHALL NOT EXCEED ONE THIRD OF SLAB
THICKNESS AND SHALL BE PLACED BETWEEN THE TOP AND BOTTOM
REINFORCING, UNLESS SPECIFICALLY DETAILED OTHERWISE. CONCENTRATIONS
OF CONDUITS OR PIPES SHALL BE AVOIDED EXCEPT WHERE DETAILED OPENINGS
ARE PROVIDED. PLACEMENT OF CONDUIT AND PIPES WITHIN WHERE DETAILED
OPENINGS ARE PROVIDED. PLACEMENT OF CONDUIT AND PIPES WITHIN SLABS
SUBJECT TO REVIEW AND ACCEPTANCE BY THE CONTRACTING OFFICER.
20. CONDUITS HAVING OUTSIDE DIAMETER LARGER THAN ONE THIRD OF THE SLAB
THICKNESS SHALL NOT BE PERMITTED. CONDUITS THAT CROSS EACH OTHER IN
SLAB SHALL NOT CONSUME AT POINT OF INTERSECTION MORE THAN ONE THIRD
OF THE SLAB THICKNESS.
CONCRETE:
STRUCTURAL STEEL & MISC METALS:
1. MATERIAL AND WORK SHALL CONFORM TO AISC "SPECIFICATION FOR
STRUCTURAL STEEL BUILDINGS", LATEST EDITION.
2. ALL STRUCTURAL STEEL CONNECTIONS SHALL BE MADE WITH HIGH STRENGTH
TYPE BOLTS CONFORMING TO ASTM A320 CLASS 2 B8M UNO.
3. ALL BOLTED CONNECTIONS SHALL HAVE A MINIMUM OF TWO (2) BOLTS, UNO.
4. MINIMUM EDGE DISTANCE (DISTANCE FROM CENTER OF BOLT TO NEAREST EDGE
OF PLATE OR STRUCTURAL ELEMENT) SHALL BE 2 BOLT DIAMETERS OR 1-1/2",
WHICHEVER IS GREATER, UNLESS NOTED OTHERWISE.
5. ANCHOR BOLTS SHALL BE CLASS 1 B8M (ASTM A320) STAINLESS STEEL TYPE 316
HEX HEAD BOLTS WITH FLAT WASHERS UNO ON DWGS. ALL EXPOSED ANCHORS
SHALL BE TYPE 316 STAINLESS STEEL.
6. ALL WELDING SHALL CONFORM TO STANDARDS OF AISC, AWS D1.1 & D1.3 USING
E70 LOW-HYDROGEN ELECTRODES AND SHALL BE PERFORMED BY WELDERS
CERTIFIED PER AWS REQUIREMENTS.
7. ALL STRUCTURAL AND MISC STEEL NOT EXPOSED TO WEATHER SHALL BE
PRIMED PER SPEC SECTION 09 97 13.27. ALL BOLTS, NUTS AND WASHERS TO BE
TYPE 316 STAINLESS STEEL. ALL MISCELLANEOUS STEEL EXPOSED TO WEATHER
SHALL BE TYPE 316 STAINLESS STEEL.
8. AUTOMATICALLY END WELD SHEAR CONNECTORS (HEADED STUDS) THROUGH
DECK TO SUPPORTING STRUCTURAL MEMBERS IN FIELD, ACCORIDNG TO
MANUFACTURER'S RECOMMENDATIONS AND AWS D1.1. REMOVE CERAMIC
FERRULES FROM CONNECTOR AND DECK BEFORE PLACING CONCRETE.
9. AUTOMATICALLY END WELD ALL DEFORMED BAR ANCHORS (DBA). USE SAME
TESTING AND INSPECTION REQUIREMENTS AS FOR SHEAR CONNECTORS.
10. ALL TESTING AND INSPECTION OF STRUCTURAL STEEL SHALL CONFORM WITH
THE REQUIREMENTS OF SPEC SECTION 05 12 00.
11. ALL STRUCTURAL STEEL WIDE FLANGE MEMBERS SHALL CONFORM TO ASTM
SPECIFICATIONS A-992 GRADE 50 KSI U.N.O. PLATES, ANGLES, CHANNELS AND
BARS SHALL BE ASTM A-36. SEE NOTE 7 FOR COATING REQUIREMENTS.
12. TUBES TO CONFORM TO ASTM A-500 GRADE B. PIPES TO CONFORM TO ASTM
A-53 TYPE E OR S GRADE B. SEE NOTE 7 FOR COATING REQUIREMENTS.
13. HIGH STRENGTH STEEL BOLTS TO CONFORM TO ASTM A320 CLASS 2 B8M,
STAINLESS STEEL TYPE 316 UNLESS OTHERWISE NOTED.
14. ALL BUTT WELDS SHALL BE FULL PENETRATION BUTT WELDS.
15. SPLICING OF STRUCTURAL STEEL MEMBERS WHERE NOT DETAILED IS
PROHIBITED WITHOUT PRIOR APPROVAL.
16. THE MINIMUM PLATE THICKNESS SHALL BE 3/8" (U.N.O.) THE MINIMUM BOLT
DIAMETER SHALL BE 3/4" (U.N.O.) THE MINIMUM WELD THROAT SHALL BE 3/16"
(U.N.O.)
17. THE CONTRACTOR SHALL SUBMIT SHOP DRAWINGS AND OBTAIN APPROVAL
PRIOR TO FABRICATION.
18. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE CONTROL OF ALL
ERECTION PROCEDURES AND SEQUENCES.
1. REQUIRED DESIGN STRENGTH F'm = 2500 PSI; PROVIDE CONCRETE
MASONY UNITS W/ MIN. COMPRESSIVE STRENGTH OF 3750 PSI.
2. USE OPEN END UNITS, BOND BEAM UNITS AT HORIZONTAL
REINFORCING.UNITS SHALL BE PLACED IN RUNNING BOND PATTERN.
3. REINFORCING BARS IN MASONY SHALL CONFORM TO THE
REQUIREMENTS OF ASTM A615, GRADE 60 AND EPOXY COATED PER
USAKA IDG. LAP SPLICES IN HORIZONTAL REINFORCING SHALL BE 48
DIAMETERS & 2'-0" MINIMUM TYPICAL UNLESS OTHERWISE NOTED ON
PLAN. VERTICAL REINFORCING TO BE ONE PIECE, NO SPLICE, UNLESS
OTHERWISE NOTED ON PLANS.
4. ALL REINFORCING SHALL HAVE A MINIMUM COVERAGE OF 1/2" GROUT,
PROVIDE A MINIMUM GROUT COVER EQUAL TO 1 1/2" NOT LESS THAN
2.5db AROUND MASONRY DOWELS.
5. LOW LIFT CONSTRUCTION, MAXIMUM GROUT POUR HEIGHT IS 4 FEET.
HIGH LIFT GROUTED CONSTRUCTION MUST BE USED IN
CONFORMANCE WITH THE ACI 530-08.
6. ALL CELLS IN CONCRETE BLOCKS SHALL BE FILLED SOLID WITH
GROUT U.N.O.
7. CELLS SHALL BE IN VERTICAL ALIGNMENT. DOWELS SHALL BE SET TO
ALIGN WITH CORES CONTAINING REINFORCING STEEL.
8. ALL ISOLATED BOLTS EMBEDDED IN MASONRY SHALL BE GROUTED
SOLIDLY IN PLACE WITH NOT LESS THAN 1" OF GROUT SUROUNDING
THE BOLT & SHALL BE SET W/ TEMPLATES.
9. REFER TO ARCHITECTURAL DRAWINGS FOR SURFACE AND HEIGHTS
OF UNIT, LAYING PATTERN AND JOINT TYP.
10. PROVIDE SHORING AND BRACING AS REQUIRED FOR MASONRY WALL
CONSTRUCTION WORK.
11. TESTING OF CMU MUST CONFORM TO ASTM C140-02a & ASTM C426-99.
12. MORTAR SHALL BE TYPE 'S' PER ACI 530-08.
13. COMPRESSIVE STRENGTH OF MORTAR SHALL BE 2500 PSI AND GROUT
SHALL BE 2500 PSI.
REINFORCED CONCRETE MASONRY UNIT (CMU):
STEEL DECK:
1. STEEL DECKING SHALL REST TIGHTLY UPON THE TOP FLANGE OF THE
SUPPORTING MEMBERS.
2. STEEL DECK MATERIAL AND INSTALLATION SHALL MEET THE REQUIREMENTS OF
THE STEEL DECK INSTITUTE'S DESIGN MANUAL.
3. ALL DECKING MATERIAL AND THE FLANGES OF SUPPORTING MEMBERS SHALL
BE FREE OF DIRT, SAND, AND OTHER FOREIGN MATERIALS.
4. WATER ON THE DECK OR BETWEEN THE DECK AND SUPPORTING MEMBERS
SHALL BE REMOVED BEFORE WELDING.
5. ALL STEEL DECK SHALL BE CONTINUOUS OVER 3 OR MORE SPANS UNLESS
NOTED OTHERWISE SHORE DECK FOR WET CONCRETE WEIGHT AS REQUIRED
BY THE DECK MANUFACTURER.
6. DECK MANUFACTURER TO IDENTIFY SHORING REQUIREMENTS. PROVIDE
SHORING DETAILS ON SHOP DRAWINGS.
7. MATERIAL FOR STEEL DECK SHALL HAVE A MIN. YIELD STRENGTH OF 33,000 PSI
AND CONFORM TO ASTM A653 SQ, GRADE 33 WITH G90 COATING.
8. THE STEEL DECK SUPPLIER SHALL INCLUDE BUT MAY NOT BE LIMITED TO THE
FOLLOWING:
A. SUPPORTS FOR DECK AROUND DISCONTINUITIES.
9. INSTALL DECK BY WELDING PER TYPICAL DETAIL.
10. DECK WELDING SHALL BE PERFORMED BY CERTIFIED WELDERS IN
ACCORDANCE WITH AWS D1.3 WITH CONTINUOUS INSPECTION.
11. NO LOADS SHALL BE HUNG FROM DECK WITHOUT APPROVAL.
12. STEEL DECK SHALL HAVE A 2.5" MINIMUM BEARING ON SUPPORT STEEL.
13. DECK SHALL BE LAID OUT SO THAT A RIB FALLS ON EACH PARALLEL SUPPORT.
14. END LAPS OF STEEL DECK SHALL BE A MINIMUM OF 4" AND SHALL OCCUR OVER
SUPPORTS.
15. PROVIDE SHOP DRAWINGS FOR REVIEW PRIOR TO FABRICATION.
1. WELD LENGTHS SHOWN ARE EFFECTIVE LENGTH PER CODE. WHERE LENGTHS
ARE NOT SHOWN, THE WELD SHALL BE FULL LENGTH OF JOINT.
2. ALL WELDING REQUIREMENTS SHOWN OR INDICATED ON THE DRAWINGS MAY BE
FIELD OR SHOP WELDED AS REQUIRED FOR EFFICIENT ERECTION, SUBJECT TO
THE CONTRACTING OFFICER'S APPROVAL.
3. ALL WELDING, OF STRUCTURAL STEEL, SHALL BE PER LATEST EDITION OF AWS
D1.1.
4. CONTINUOUS INSPECTION IS REQUIRED FOR ALL FIELD WELDING AND SHALL BE
PERFORMED BY THE CONTRACTOR QUALITY CONTROL PROGRAM.
5. ALL WELDERS SHALL BE CERTIFIED PER AWS REQUIREMENTS. SUBMIT WELDER
CERTIFICATIONS USE BY WELDING INSPECTOR.
WELDING (STRUCTURAL STEEL):
3" MAX1 1/2" TYP
10" AND SMALLER
12" TO 14"
16"
18" TO 21"
DEPTH OF BEAM
3/8"2 5/16"
3/8"
3/8"
3/8"
5/16"
5/16"
5/16"
BEAM CONN BOLTING SCHEDULE
CONN PL, t MIN No OF
7/8" DIA BOLTS WELD SIZE "A"
PLATE, t
SEE NOTE 1
SEE SCHED
1. PROVIDE FULL HEIGHT CONN PLATE WHEN BEAM OCCURS ON
ONE SIDE ONLY AND AT MOMENT FRAME BEAMS
2. ALL BOLTS SHALL BE 7/8" DIA ASTM A320, CLASS 2 B8M, STAINLESS STEEL TYPE 316, UNO.
3. USE STANDARD HOLES. (SHORT SLOTTED HOLES ARE PERMITTED)
4. FILLET WELDS SHALL BE SIZED AS SHOWN IN SCHEDULE
UNLESS A GREATER SIZE IS REQUIRED BY AISC.
TYP
FOR BM SIZE
SEE PLAN
NOTES:
1 1/2" TYP
BOLTS SEE SCHED
FOR SIZE & NUMBER OF
GIRDER BM, SEE PLAN
"A"
"A" FOR BM SIZE
SEE PLAN
STD GA
"A"
"A"
TYP SEE SCHED
TYP
THIS IS CONSIDERED
TO BE A SINGLE OPNG
NOTES:
ANGLES SHALL BE PLACED UNDER DECK.
IF DIMENSION "A" IS GREATER THAN 4D , 4D , OR 32", WHICHEVER IS
LARGER, THEN THERE IS NO RESTRICTION ON DIMENSION "B".
IF DIMENSION "B" IS GREATER THAN 4D , 4D , OR 32", WHICHEVER IS
LARGER, THEN THERE IS NO RESTRICTION ON DIMENSION "A".
IF DIMENSIONS "A" AND "B" ARE LESS THAN 4D , 4D , OR 32", WHICHEVER
IS LARGER, THE OPENING GROUP WILL BE CONSIDERED AS A SINGLE HOLE,
AND MUST BE REINFORCED AS REQUIRED FOR THE LARGER OPENING.
3.
2.
1.
O P
N G
D E
C K
U
N
IT
S
(T
Y P
IC
A
L
F
L U
T E
S
L3x3 x 1/4 UNDER
DECK ALL SIDES
LARGER HOLES, RECTANGULAR OR SQUARE
3 ADJACENT WEBS FOR 6" AND 8" MODULE DECK,
1 2
1 2
2 ADJACENT WEBS FOR 12" MODULE DECK
1 2
L1 3/4 x1 3/4 x 1/4 - TYP (ANGLES MUST
DECKING
HOLES CUTTING NO MORE THAN:
BEAM BELOW (TYP) EXTEND 3 WEBS PAST THE OPENING)
O P
N G
D
WEBS OF STEEL
"B
< 20"D1 D2 < 20"
OPNG
F
L U
T E
S D
ADJACENT TO
EACH CUT WEB
TYP AT
EACH LOW
FLUTE
D
"A"
1/8 1/8 1/2
1/2
5/8"Ø D1
(TYP)
TYP
L3x3 TO L3x3 3/16
3/16
FOR LOCATIONS AND SIZE OF OPENINGS, SEE ARCHITECTURAL AND
MECHANICAL DRAWINGS.
4.
3'-0"
SHEET WIDTH
6"
/2
SPLICE AT SPAN
DIRECTION CHANGE
SECTION PROPERTIES
(FOR WIDTHS SHOWN)
PERPENDICULAR TO SUPPORTS
PARALLEL TO SUPPORT
END
WELD
W BM
W BM
1 1/2" x 18 GA
INTERIOR BEAMSEDGE BEAMS
-S
+S
0.305 INI
0.331 IN
0.318 IN
W BM
BUTT ENDS
@ DECK SPLICE
CONNECTIONS
W BM
TRANSVERSE
FASTENERS
BUTTON PUNCH
METHOD OF CONNECTIONS
BEAM
BEAM
FASTENERS AT ALL
SUPPORTS PARALLEL
TO DECK SPAN UNO
TRANSVERSE FASTENERS
PLB
ROOF DECK
1 1/2" TYPE B - (ROOF DECKS)
(5) 5/8" DIA WELDS PATTERN @ SUPPORTS
AT TRANSVERSE MEMBERS.
SIDELAPS CONNECTED WITH PUNCHLOK®
TOOL @ 12" OC
5/8" DIA WELDS, PATTERNS AT PARALLEL
SUPPORTS @ 12" OC
1.
2.
3.
SECTION A-A
11"
1/2" PL
EQ EQ
1 1/2" 8" 1 1/2"
/2
S H
E A
R P
L
/2
Wx BM
PER PLAN/ELEV
SHEAR PLATE
PER DETAIL
CMU WALL ABOVE
WHERE OCCURS
CMU WALL
PER PLAN
(4)-3/4"Ø STUDS x 6" LONG
ADD (2) #5 CONT
VERT AT EMBED
PLATE, TYP
/A2 S-514
R E G
IS
T E R E
D
PR
OFESS IONAL
E N G
IN
E E R
S T A
T E
O F CA L I F
OR
N I A
C T U R A
L
URT
S
OF
D E
S
IG
N E
D B
Y
US Army Corps of Engineers Honolulu District
A E
C O
M B
IS
H
O P
S Q
U A
R E
A
S B
T O
W E
R B
IS
H
O P
S T
R E
E T
S
U
IT
E
H O
N O
L U
L U
H
A W
A
II
/1 /2
F
Y
M
C A
P N
E C
H O
P
IE
R R
E S
T O
R A
T
IO
N U
S A
R M
Y K
W A
J A
L E
IN
A
T O
L L
U S
A K
A
A
B
C
D
2 3 4 5
P L
O T
S C
A L E
S U
B M
IT
T
E D
B Y
D R
A W
N B
Y
S
IZ
E
A N
S I D
P L
O T
D A
T E
C H
E C
K E
D B
Y
D A
T E
D R
A W
IN
G
N U
M B
E R
L O
C A
T
IO
N C
O D
E
S O
L
IC
IT
C
O N
T R
A C
T N
O
R E
V
IS
IO
N
F
IL
E N
A M
E
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E A
P P
R
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E A
P P
R
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
R S
H O
N O
L U
L U
D
IS
T R
IC
T
F T
S H
A F
T E
R H
A W
A
II
SHEET
IDENTIFICATION
SHEET
/0
/1
W
A -0
-D
-0
-0
R T
A S
U B
M
IT
T A
L
MOHAMED S.
ALAM
No. S 3648
Exp. 03-31-16
O N
-S H
O R
E
P
IE
R B
U
IL
D
IN
G
K W
A J -E
C H
O -P
IE
R
O
S
S
C E
N T
R A
L
A
M -0
/1
3/
A
F A s in di ca te d
A
M -0
/2
6/
S-514
T Y
P
IC
A L D
E T
A
IL
S S
T E
E L
D E
C K
K
N G
U Y
E N
M
R A
M
IR
E Z
S
A
LA
M
1-
-0
S
A
LA
M
A F
SCALE: N.T.S.S-514
A2
TYP BEAM CONNECTION
WITH SHEAR PLATE
SCALE: N.T.S.S-514
A5 REINFORCEMENT AT SMALL OPENINGS IN DECK
SCALE: N.T.S.S-514
C3 METAL DECK CONNECTION DETAIL
SCALE: N.T.S.S-514 REF: S-112
C4 BEAM EMBEDS
ON-SHORE BUILDING
MARINE ROAD
D
C
A
B
CONCRETE PAVING, SEE
CIVIL PLANS FOR
DIMENSIONS AND DETAILS
NEW FENCE
NEW FENCE SLIDING GATE
NEW FENCE
SEE SHEET CS-104 FOR
ADDITIONAL SITE
INFORMATION
GROUND-
MOUNTED
HVAC UNIT
SPLASH
BLOCK,
TYPICAL
5'
0"
6' - 8" 13' - 4"
5' - 10"
10' - 10" 13' - 4" 13' - 4"
2'
5'
0"
51' - 4" 12' - 0"
L I C
ENSED A RCH I T EC
T
S
TA
T E
O F CA L I FORN
I A
OF
D E
SI
G
N E
D B
Y
US Army Corps of Engineers Honolulu District
A E
C O
M B
IS
H
O P
S Q
U A
R E
A
SB
T
O W
E R
B
IS
H O
P
ST
R E
E T, S U
IT
E
H O
N O
LU
LU
, H A
W A
II
/0
9/
FY
M C
A P
N
E
C H
O P
IE
R
R
ES
TO
R
AT
IO
N U
S A
R M
Y
KW
AJ
AL
EI
N
A
TO
LL
(U
SA
KA
A
B
C
D
2 3 4 5
P
LO
T S
C A
LE
S U
BM
IT
TE
D
B Y
D R
A W
N B
Y
S
IZ
E:
A
N S
I D
P
LO
T D
A
TE
C H
EC
KE
D B
Y
D
AT
E:
D R
A W
IN
G
N U
M
BE
R
LO
C
AT
IO
N C
O D
E
S O
LI
C
IT
./C
O N
TR
A
C T
N O
R E
V
IS
IO
N
FI
LE
N A
M E
M
A R
K D
E
SC
R
IP
TI
O
N D
A
TE
A
PP
R
M A
R K
D E
SC
R
IP
TI
O N
D A
TE
A
PP
R
U .S
. A R
M Y
C O
R
PS
O F
E N
G
IN
E
ER
S H
O N
O
LU
LU
D
IS
TR
IC
T
FT
S
H A
FT
E
R , H
AW
AI
I
SHEET
IDENTIFICATION
SHEET
/0
9/
W
A-
-D
-0
3-
R
TA
S U
BM
IT
TA
L
RICHARD
LEE
SCHLUTZ
No. C10938
Exp. 01-31-17
O N
-S H
O R
E
BU
IL
D
IN
G
K W
AJ
-E
C H
O -P
IE
R
_O S
_A
_C
EN
TR
A
L
/1
6"
'-0
AM
-0
/2 1/
A-101
S
IT
E P
LA
N
D.
W
IN
ST
EA
D
E.
B
US
TA
M
AN
TE
R.
P
RA
DH
AN
R.
S
CH
LU
TZ
RL
S
0 4' 8' 16' 32' 48'
SCALE: 1/16" = 1'-0"
A-101 REF: A-201 SCALE: 1/16" = 1'-0"
1 SITE PLAN
N
A-201
A-201
A-201
A-201
A-301
30"x60"x96"
HAZMAT
LOCKER (2)
(N.I.C.)
8 INCH CONCRETE
MASONRY UNIT, TYP.
3-TIER PALLET RACK
SYSTEM AT WALL - SEE
DETAIL 8/A501
A-301
A-301
A-301
51' - 4"
D102B
D1
A
D103A
SHOP
AREA/
PARTS
CLEANING
A102
UNISEX
A103
UTILITY
VAULT
A104
12' - 0"
D1
A
9'-0" DIAMETER
FOR FORKLIFT
D
C
A-402
WAREHOUSE
A101
A-601
D102A
D105A
A
B
8'
8"
2'
0"
10" 3' - 4" 9' - 0" 3' - 4"
8" 3' - 4" 9' - 0" 3' - 4"
8" 3' - 4" 9' - 0" 3' - 4"
10"
22' - 0" R.O.
3' - 4" 26' - 0" 8"
R.O.
3' - 4" 8' - 0"
22' - 0" R.O.
3' - 4" 4' - 0"
R.O.
16' - 0" 6' - 0"
D1
C
D101B
FIRE PUMP
ROOM
A105
"4'
0"
R .O
3'
4"
1'
4"
R
.O
6'
8" 4'
8"
12"X24"X3" HIGH
CONCRETE SPLASH
BLOCK, TYP.
2' - 0"
R.O.
7' - 4"
2' - 8"
3'
4" R
.O
3'
4"
GROUND-MOUNTED
HVAC SPLIT SYSTEM
- SEE SHEET M-111
A-501
A-501
A-601
12"x24"x3" CONCRETE
SPLASH BLOCK
L I C
ENSED A RCH I T EC
T
S
TA
T E
O F CA L I FORN
I A
OF
D E
SI
G
N E
D B
Y
US Army Corps of Engineers Honolulu District
A E
C O
M B
IS
H
O P
S Q
U A
R E
A
SB
T
O W
E R
B
IS
H O
P
ST
R E
E T, S U
IT
E
H O
N O
LU
LU
, H A
W A
II
/0
9/
FY
M C
A P
N
E
C H
O P
IE
R
R
ES
TO
R
AT
IO
N U
S A
R M
Y
KW
AJ
AL
EI
N
A
TO
LL
(U
SA
KA
A
B
C
D
2 3 4 5
P
LO
T S
C A
LE
S U
BM
IT
TE
D
B Y
D R
A W
N B
Y
S
IZ
E:
A
N S
I D
P
LO
T D
A
TE
C H
EC
KE
D B
Y
D
AT
E:
D R
A W
IN
G
N U
M
BE
R
LO
C
AT
IO
N C
O D
E
S O
LI
C
IT
./C
O N
TR
A
C T
N O
R E
V
IS
IO
N
FI
LE
N A
M E
M
A R
K D
E
SC
R
IP
TI
O
N D
A
TE
A
PP
R
M A
R K
D E
SC
R
IP
TI
O N
D A
TE
A
PP
R
U .S
. A R
M Y
C O
R
PS
O F
E N
G
IN
E
ER
S H
O N
O
LU
LU
D
IS
TR
IC
T
FT
S
H A
FT
E
R , H
AW
AI
I
SHEET
IDENTIFICATION
SHEET
/0
9/
W
A-
-D
-0
3-
R
TA
S U
BM
IT
TA
L
RICHARD
LEE
SCHLUTZ
No. C10938
Exp. 01-31-17
O N
-S H
O R
E
BU
IL
D
IN
G
/8
'-0
A-111
FL
O
O R
P
LA
N
D.
W
IN
ST
EA
D
E.
B
US
TA
M
AN
TE
R.
P
RA
DH
AN
R.
S
CH
LU
TZ
0 8' 16' 24'2' 4'
SCALE: 1/8" = 1'-0"
A-111 REF: A-201 SCALE: 1/8" = 1'-0"
1 LEVEL 1 FLOOR PLAN
GENERAL SHEET NOTES
1. FOR ACCESSIBILITY RAMP INFORMATION, SEE SHEET A-101.
2. FOR ADDITIONAL BOLLARD LOCATIONS, SEE CIVIL
DRAWINGS.
N
A M
-0
A M
-0
/1
3/
R
LS
/2
1/
R
LS
K W
AJ
-E
C H
O -P
IE
R
_A -1
X
X X
.D W
G
1-
-0
A-202
A-202
A-202
A-202
B
3583 SF
WAREHOUSE
A101
100 SF
OFFICE
A102
A-401
A-302
30"x72"x96" HAZMAT
LOCKER (2) (N.I.C.)
8" CONCRETE
MASONRY UNIT, TYP.
3-TIER PALLET RACKING
SYSTEM
A-302
A-302
59 SF
UNISEX
A103
551 SF
UTILITY VAULT
A104
1D 16
132' - 8"
4'
0"
A
8'
0"
1B
103A 3'
4" 2'
0"
101C
2'
0" 3'
4"
1A
3' - 4"3' - 4"
81' - 4"
4A
2'
0"
2' - 0"
4B
A-601
2A
"9' - 0
" ø
3' - 4"
2'
8" 4'
0"
4'
0"
W W
40' - 0" 11' - 4"
6' - 8" 2' - 0"
2'
8"
3'
4"
8"8" 3'
4"
9'
0" 3'
4"
8" 3'
4"
9'
0" 3'
4"
8" 8"
STAINLESS STEEL
DOWNSPOUT
A-501
A-601
L I C
ENSED A RCH I TEC
T
S
TA
T E
O F CA L I FOR
N I A
OF
D E
SI
G
N E
D B
Y
US Army Corps of Engineers Honolulu District
A E
C O
M B
IS
H
O P
S Q
U A
R E
A
SB
T
O W
E R
B
IS
H O
P
ST
R E
E T, S U
IT
E
H O
N O
LU
LU
, H A
W A
II
/0
9/
FY
M C
A P
N
E
C H
O P
IE
R
R
ES
TO
R
AT
IO
N U
S A
R M
Y
KW
AJ
AL
EI
N
A
TO
LL
(U
SA
KA
A
B
C
D
2 3 4 5
P
LO
T S
C A
LE
S U
BM
IT
TE
D
B Y
D R
A W
N B
Y
S
IZ
E:
A
N S
I D
P
LO
T D
A
TE
C H
EC
KE
D B
Y
D
AT
E:
D R
A W
IN
G
N U
M
BE
R
LO
C
AT
IO
N C
O D
E
S O
LI
C
IT
./C
O N
TR
A
C T
N O
R E
V
IS
IO
N
FI
LE
N A
M E
M
A R
K D
E
SC
R
IP
TI
O
N D
A
TE
A
PP
R
M A
R K
D E
SC
R
IP
TI
O N
D A
TE
A
PP
R
U .S
. A R
M Y
C O
R
PS
O F
E N
G
IN
E
ER
S H
O N
O
LU
LU
D
IS
TR
IC
T
FT
S
H A
FT
E
R , H
AW
AI
I
SHEET
IDENTIFICATION
SHEET
/0
9/
W
A-
-D
-0
3-
R
TA
S U
BM
IT
TA
L
RICHARD
LEE
SCHLUTZ
No. C10938
Exp. 01-31-17
P
IE
R B
U
IL
D
IN
G
/8
'-0
A-113
FL
O
O R
P
LA
N
D.
W
IN
ST
EA
D
E.
B
US
TA
M
AN
TE
R.
P
RA
DH
AN
R.
S
CH
LU
TZ
0 8' 16' 24'2' 4'
SCALE: 1/8" = 1'-0"
A-113 REF: A-202 SCALE: 1/8" = 1'-0"
1 LEVEL 1 FLOOR PLAN
N
GENERAL SHEET NOTES
1. FOR ADDITIONAL BOLLARD LOCATIONS, SEE CIVIL
DRAWINGS.
A M
-0
A M
-0
/2 1/
R
LS
/1
3/
R
LS
K W
AJ
-E
C H
O -P
IE
R
_A -1
X
X X
.D W
G
1-
-0
LEVEL 1
0' - 0"
T.O. M.
12' - 8"
T.O.M.
24' - 0"
GUTTER AND
DOWNSPOUT
RF-1 - ALUMINUM STANDING SEAM ROOFING OVER
EXTERIOR SHEATHING W/ SELF-ADHERING
UNDERLAYMENT OVER METAL DECK
(HYDROSTATIC ROOFING SYSTEM)
CONCRETE SLAB
W/ SEALER
STRUCTURAL BEAM
2 3/4" THICK TRANSLUCENT INSULATED
FIBERGLASS SANDWICH PANEL SYSTEM
(TRANS-1)
FOUNDATION PER
STRUCTURAL
STAINLESS STEEL
GUTTER AND
DOWNSPOUT
CONCRETE
MASONRY WALL
RF-1 - ALUMINUM STANDING SEAM ROOFING OVER
EXTERIOR SHEATHING W/ SELF-ADHERING
UNDERLAYMENT OVER METAL DECK
(HYDROSTATIC ROOFING SYSTEM)
CONCRETE SLAB
W/ SEALER
T.O.M. (WEST)
19' - 4"
A-502
A-502
A-502
WAREHOUSE
A101
SHOP
AREA/
PARTS
CLEANING
A102
BACK-TO-BACK 3-TIER
PALLET RACKING
SYSTEM, SEE 6/A501
LIGHT FIXTURE, TYP. SEE
ELECTRICAL LIGHTING PLANS
LIGHT FIXTURE, TYP. SEE
ELECTRICAL LIGHTING PLANS
A-502
A-502
1 1/8"
1"
1'-0"
1'-0"
TOP OF RACK
10' - 0"
LEVEL 1
0' - 0"
RF-1 - ALUMINUM STANDING
SEAM ROOFING OVER
EXTERIOR SHEATHING W/
SELF-ADHERING
UNDERLAYMENT OVER METAL
DECK
(HYDROSTATIC ROOFING
SYSTEM)
CONCRETE
MASONRY WALL
FOUNDATION
PER
STRUCTURAL
CONCRETE
SLAB
C
A-503
TOP OF RACK
10' - 0"
LEVEL 1
0' - 0"
T.O.M.
24' - 0"
ROOF FRAMING
ALUMINUM FLASHING
RF-1 - ALUMINUM STANDING SEAM
ROOFING OVER EXTERIOR SHEATHING
W/ SELF-ADHERING UNDERLAYMENT
OVER METAL DECK
(HYDROSTATIC ROOFING SYSTEM)
CONCRETE MASONRY WALL
3-TIER PALLETE RACK
CONCRETE SLAB
A-502
A-503
A-502
TOP OF RACK
10' - 0"
LEVEL 1
0' - 0"
T.O. M.
12' - 8"
T.O.M.
24' - 0"
ALUMINUM FLASHING
RF-1 - ALUMINUM STANDING SEAM
ROOFING OVER EXTERIOR
SHEATHING W/ SELF-ADHERING
UNDERLAYMENT OVER METAL
DECK
(HYDROSTATIC ROOFING SYSTEM)
CONCRETE
MASONRY WALL
FOUNDATION PER
STRUCTURAL
CONCRETE SLAB
A-502
A-502
TOP OF RACK
10' - 0"
LEVEL 1
0' - 0"
EDGE
FLASHING
RF-1 - ALUMINUM STANDING SEAM
ROOFING OVER EXTERIOR SHEATHING
W/ SELF-ADHERING UNDERLAYMENT
OVER METAL DECK
(HYDROSTATIC ROOFING SYSTEM)
CONCRETE SLAB
FINISH
GRADE
CONCRETE
MASONRY
WALL
CONCRETE SLAB
W/ SEALER
A-502
A
TOP OF RACK
10' - 0"
L I C
ENSED A RCH I T EC
T
S
TA
T E
O F CA L I FORN
I A
OF
D E
SI
G
N E
D B
Y
US Army Corps of Engineers Honolulu District
A E
C O
M B
IS
H
O P
S Q
U A
R E
A
SB
T
O W
E R
B
IS
H O
P
ST
R E
E T, S U
IT
E
H O
N O
LU
LU
, H A
W A
II
/0
9/
FY
M C
A P
N
E
C H
O P
IE
R
R
ES
TO
R
AT
IO
N U
S A
R M
Y
KW
AJ
AL
EI
N
A
TO
LL
(U
SA
KA
A
B
C
D
2 3 4 5
P
LO
T S
C A
LE
S U
BM
IT
TE
D
B Y
D R
A W
N B
Y
S
IZ
E:
A
N S
I D
P
LO
T D
A
TE
C H
EC
KE
D B
Y
D
AT
E:
D R
A W
IN
G
N U
M
BE
R
LO
C
AT
IO
N C
O D
E
S O
LI
C
IT
./C
O N
TR
A
C T
N O
R E
V
IS
IO
N
FI
LE
N A
M E
M
A R
K D
E
SC
R
IP
TI
O
N D
A
TE
A
PP
R
M A
R K
D E
SC
R
IP
TI
O N
D A
TE
A
PP
R
U .S
. A R
M Y
C O
R
PS
O F
E N
G
IN
E
ER
S H
O N
O
LU
LU
D
IS
TR
IC
T
FT
S
H A
FT
E
R , H
AW
AI
I
SHEET
IDENTIFICATION
SHEET
/0
9/
W
A-
-D
-0
3-
R
TA
S U
BM
IT
TA
L
RICHARD
LEE
SCHLUTZ
No. C10938
Exp. 01-31-17
O N
-S H
O R
E
BU
IL
D
IN
G
/4
'-0
A-301
B U
IL
D
IN
G
W
AL
L
SE
C
TI
O
N S
D.
W
IN
ST
EA
D
E.
B
US
TA
M
AN
TE
R.
P
RA
DH
AN
R.
S
CH
LU
TZ
0 8' 16' 24'2' 4'
SCALE: 1/8" = 1'-0"
A-301 REF: A-111 SCALE: 1/4" = 1'-0"
6 BUILDING SECTION
SCALE: 1/4" = 1'-0"A-301 REF: A-115
15 WALL SECTION 2
SCALE: 1/4" = 1'-0"A-301 REF: A-111
17 WALL SECTION 3
SCALE: 1/4" = 1'-0"A-301 REF: A-111
16 WALL SECTION 4
SCALE: 1/4" = 1'-0"A-301 REF: A-111
19 WALL SECTION 1
A M
-0
A M
-0
/1
3/
R
LS
/2
1/
R
LS
K W
AJ
-E
C H
O -P
IE
R
_A -3
X
X X
.D W
G
1-
-0
LEVEL 1
ALUMINUM
FLASHING
RF-1 - ALUMINUM STANDING SEAM ROOFING
OVER EXTERIOR SHEATHING W/ SELF-
ADHERING UNDERLAYMENT OVER METAL
DECK
(HYDROSTATIC ROOFING SYSTEM)
COILING
OVERHEAD DOOR
FOUNDATION PER
STRUCTURAL
FOUNDATION
SLOPED AT
EXTERIOR, SEE
STRUCT.
CONCRETE SLAB
T.O.M.
22' - 8"
LEVEL 1
0' - 0"
T.O. M.
19' - 4"
B
8 INCH CONCRETE
MASONRY UNIT
FOUNDATION PER
STRUCTURAL
CONCRETE SLAB
W/ SEALERFINISH GRADE
3-TIER
PALLETE
RACK
2 3/4" THICK TRANSLUCENT
INSULATED FIBERGLASS
SANDWICH PANEL SYSTEM
(TRANS-1)
STAINLESS STEEL
GUTTER AND
DOWNSPOUT
FOUNDATION PER
STRUCTURAL
FINISH
GRADE
1 5/32" 1'-0"
RF-1 - ALUMINUM STANDING SEAM ROOFING
OVER EXTERIOR SHEATHING W/ SELF-
ADHERING UNDERLAYMENT OVER METAL
DECK
(HYDROSTATIC ROOFING SYSTEM)
WAREHOUSE
A101
A
T.O.M.
22' - 8"
8"
LIGHT FIXTURE, TYP.
SEE ELECTRICAL
LIGHTING PLANS
LEVEL 1
0' - 0"
T.O. M.
19' - 4"
RF-1 - ALUMINUM STANDING SEAM ROOFING
OVER EXTERIOR SHEATHING W/ SELF-
ADHERING UNDERLAYMENT OVER METAL
DECK
(HYDROSTATIC ROOFING SYSTEM)
CONCRETE MASONRY
UNIT (8" THICK)
FOUNDATION PER
STRUCTURAL
CONCRETE SLAB
W/ SEALER
SLOPE AT
EXTERIOR, SEE
STRUCT.
STAINLESS STEEL
GUTTER AND
DOWNSPOUT
CONCRETE
MASONRY UNIT
FOUNDATION PER
STRUCTURAL
FINISH
GRADE
ACT CEILING
OFFICE
A102
WAREHOUSE
A101
1 5/32" 1'-0"
UNISEX
A103
L I C
ENSED A RCH I TEC
T
S
TA
T E
O F CA L I FOR
N I A
OF
D E
SI
G
N E
D B
Y
US Army Corps of Engineers Honolulu District
A E
C O
M B
IS
H
O P
S Q
U A
R E
A
SB
T
O W
E R
B
IS
H O
P
ST
R E
E T, S U
IT
E
H O
N O
LU
LU
, H A
W A
II
/0
9/
FY
M C
A P
N
E
C H
O P
IE
R
R
ES
TO
R
AT
IO
N U
S A
R M
Y
KW
AJ
AL
EI
N
A
TO
LL
(U
SA
KA
A
B
C
D
2 3 4 5
P
LO
T S
C A
LE
S U
BM
IT
TE
D
B Y
D R
A W
N B
Y
S
IZ
E:
A
N S
I D
P
LO
T D
A
TE
C H
EC
KE
D B
Y
D
AT
E:
D R
A W
IN
G
N U
M
BE
R
LO
C
AT
IO
N C
O D
E
S O
LI
C
IT
./C
O N
TR
A
C T
N O
R E
V
IS
IO
N
FI
LE
N A
M E
M
A R
K D
E
SC
R
IP
TI
O
N D
A
TE
A
PP
R
M A
R K
D E
SC
R
IP
TI
O N
D A
TE
A
PP
R
U .S
. A R
M Y
C O
R
PS
O F
E N
G
IN
E
ER
S H
O N
O
LU
LU
D
IS
TR
IC
T
FT
S
H A
FT
E
R , H
AW
AI
I
SHEET
IDENTIFICATION
SHEET
/0
9/
W
A-
-D
-0
3-
R
TA
S U
BM
IT
TA
L
RICHARD
LEE
SCHLUTZ
No. C10938
Exp. 01-31-17
P
IE
R B
U
IL
D
IN
G
/4
'-0
A-302
B U
IL
D
IN
G
W
AL
L
SE
C
TI
O
N S
D.
W
IN
ST
EA
D
E.
B
US
TA
M
AN
TE
R.
P
RA
DH
AN
R.
S
CH
LU
TZ
1900 8' 16' 24'2' 4'
SCALE: 1/8" = 1'-0"
SCALE: 1/4" = 1'-0"A-302 REF: A-113
3 WALL SECTION
A-302 REF: A-113 SCALE: 1/4" = 1'-0"
1 BUILDING SECTION
A-302 REF: A-113 SCALE: 1/4" = 1'-0"
2 BUILDING SECTION
A M
-0
A M
-0
/1
3/
R
LS
/2
1/
R
LS
K W
AJ
-E
C H
O -P
IE
R
_A -3
X
X X
.D W
G
1-
-0
45°
45° 45°
45°
SPLICE
12 GA. VERTICAL HANGER WIRE AT 4'-0" X 4'-
0" O.C. WITH 3 TIGHT TURNS IN 1-1/2" BOTH
ENDS. COMPRESSION STRUT SHALL NOT
REPLACE HANGER WIRE, SEE DETAIL 4/ A501.
W/MIN. 4 TIGHT TURNS IN 1-1/2" BOTH
ENDS OF WIRE (TYP) 12 GA. 45° SPLAY
WIRE BRACING IN PLANE OF MAIN
RUNNER. ALL WIRES ATTACHED TO MAIN
RUNNER. 4 DIRECTIONS @ 96 SF. OF
CEILING WITH MAX SPACING OF 8'X12'
O.C.
MAIN RUNNER AT 4'-
0"O/C
2" (MAX) FROM
BRACING WIRES
TO
COMPRESSION
AT 2'-0"O/C
CROSS RUNNER
SUSP. ACOUSTIC PNL CLGA
T-BAR SYSTEM MAIN
RUNNERS @ 4'-0" O.C.
ACOUSTICAL
PANEL SYSTEM
WALL ANGLE CONT. POP
RIVET TO MAIN RUNNERS
FACE OF WALL
8" MAX.
9 17/ 32"
1"3/4"
1 5/8"
7/8" MIN.
WIRE HANGERS @ 4' O.C
MAX SUPPORT FROM STEEL
BEAMS OR SUPPLEMENTAL
STEEL
2-#8x1/2" SELF TAPPING SCREWS
STEEL STRAP 3" WIDE x 4" LONG x
12 GA
BRACING WIRE
MTL DECK PER
STRUCTURAL
A-501
A-5016
P
AL
LE
T
D
EP
TH
" N O
M
IN
AL
NO LOAD OVERHANG
PERMITTED IN AISLE
PALLETS
P
AL
LE
T
D
EP
TH
" N O
M
IN
AL
3" M
AX
IM
U
M O
VE
R
H
AN
G
LO
C
AT
E D
IN
F
LU
E
O N
R
AN
D O
M B
AS
IS
PALLET BEAM40" FORK
ENTRY BAR
8"
1 4
2LEVEL 1
0' - 0"
M
AX
. H E
IG
H
T
A
V G
. H E
IG
H
T
.8
48" NOMINAL 52" MAXIMUM
N O
M
IN
AL
108" LOAD BEAM
TOP OF RACK
10' - 0"
LEVEL 1
0' - 0"
M
AX
. H E
IG
H
T
A
VG
. H
EI
G
H T
.8
" N
O M
IN
AL
FLUE SPACE
8"
18"
CLEAR
TOP OF LOAD
11' - 5"12' - 0"
TOP OF RACK
10' - 0"
LEVEL 1
0' - 0"
M
AX
. H E
IG
H
T
A
VG
. H
EI
G
H T
.8
" N
O M
IN
AL
8" MINIMUM
STEEL BRACING
18" CLEAR
TOP OF RACK
10' - 0"
PALLET MATERIAL LEGEND
UPRIGHTS
PALLET BEAM
PALLET
FORK ENTRY BAR
CROSS BRACE
6 BACK TIE
7 WALL TIE
8 WALL
NOTE: PALLET RACK SYSTEM
L I C
ENSED A RCH I T EC
T
S
TA
T E
O F CA L I FORN
I A
OF
D E
SI
G
N E
D B
Y
US Army Corps of Engineers Honolulu District
A E
C O
M B
IS
H
O P
S Q
U A
R E
A
SB
T
O W
E R
B
IS
H O
P
ST
R E
E T, S U
IT
E
H O
N O
LU
LU
, H A
W A
II
/0
9/
FY
M C
A P
N
E
C H
O P
IE
R
R
ES
TO
R
AT
IO
N U
S A
R M
Y
KW
AJ
AL
EI
N
A
TO
LL
(U
SA
KA
A
B
C
D
2 3 4 5
P
LO
T S
C A
LE
S U
BM
IT
TE
D
B Y
D R
A W
N B
Y
S
IZ
E:
A
N S
I D
P
LO
T D
A
TE
C H
EC
KE
D B
Y
D
AT
E:
D R
A W
IN
G
N U
M
BE
R
LO
C
AT
IO
N C
O D
E
S O
LI
C
IT
./C
O N
TR
A
C T
N O
R E
V
IS
IO
N
FI
LE
N A
M E
M
A R
K D
E
SC
R
IP
TI
O
N D
A
TE
A
PP
R
M A
R K
D E
SC
R
IP
TI
O N
D A
TE
A
PP
R
U .S
. A R
M Y
C O
R
PS
O F
E N
G
IN
E
ER
S H
O N
O
LU
LU
D
IS
TR
IC
T
FT
S
H A
FT
E
R , H
AW
AI
I
SHEET
IDENTIFICATION
SHEET
/0
9/
W
A-
-D
-0
3-
R
TA
S U
BM
IT
TA
L
RICHARD
LEE
SCHLUTZ
No. C10938
Exp. 01-31-17
O N
-S H
O R
E
PI
ER
B U
IL
D
IN
G
As in di ca te d
A-501
P
AL
LE
T
R
AC
K
AN
D C
EI
LI
N G
D
ET
A
IL
S
D.
W
IN
ST
EA
D
E.
B
US
TA
M
AN
TE
R.
P
RA
DH
AN
R.
S
CH
LU
TZ
A-501 REF: A-402 SCALE: 1 1/2" = 1'-0"
9 TYP. SEISMIC CEILING
SCALE: 3" = 1'-0"A-501 REF: A-402
TYP. SUSPENDED
ACOUSTICAL CEILING DETAIL
SCALE: 6" = 1'-0"A-501
TYP. WIRE CONN @ STL ROOF
DECK
0 2' 4' 6'1'
SCALE: 1/2" = 1'-0"
0 1' 2'
SCALE: 1 1/2" = 1'-0"
SCALE: 1/2" = 1'-0"A-501 REF: A-111
18 ENLARGED PALLET PLAN
SCALE: 1/2" = 1'-0"A-501 REF: A-115
ENLARGED PALLET
ELEVATION
SCALE: 1/2" = 1'-0"A-501 REF: A-115
SIDE ELEVATION BACK TO
BACK
SCALE: 1/2" = 1'-0"A-501 REF: A-111
8 SIDE ELEVATION AT WALL
A M
-0
A M
-0
/2 1/
R
LS
/1
3/
R
LS
1-
-0
K W
A J-
E C
H O
-P
IE
R _A
-5
X X
X .D
W G
SPRINKLER RISER & FCVA
DETAIL - PIER BUILDING4
WATER SERVICE THRU FLOOR / WET PIPE RISER -
PIER BUILDING - CATHODIC PROTECTION DETAIL
WATER SERVICE THRU FLOOR / WET PIPE RISER -
ON SHORE BUILDING - CATHODIC PROTECTION DETAIL 1
SPRINKLER RISER & FCVA DETAIL
- ON SHORE BUILDING
INSPECTORS TEST AND DRAIN
DETAIL
WATER SERVICE THRU FLOOR / WET PIPE RISER -
ON SHORE BUILDING - CATHODIC PROTECTION PLAN
WATER SERVICE THRU FLOOR / WET PIPE RISER -
PIER BUILDING - CATHODIC PROTECTION PLAN
NONEFX501NONEFX501
NONEFX501 NONEFX501
NONEFX501
NONEFX501
NONEFX501
GRADE
GALV
1'-1"
TO SYSTEM
FINISH FLOOR
0'-6" ABOVE FINISH FLOOR
6'- 4"
AND SPRINKLER SYSTEM
TO PIER HYDRANT LOOP
VALVE
CONTROL
FLOOR
TEST AND
GAUGE
SUPERVISORY SWITCH
PRESSURE
TO SPRINKLERS
FLOW SWITCH
DRAIN
TO FIRE PUMP
VALVE
CONTROL
FLOOR
TEST AND
GAUGE
SUPERVISORY SWITCH
PRESSURE
TO SPRINKLERS
FLOW SWITCH
DRAIN
FIRE PUMP
TO ON SHORE BUILDING
DUCTILE IRON FLANGE
AND SPIGOT PIECE
JOINT RESTRAINT
SYSTEM RISER
1'-0"
MECHANICAL JOINT WALL
SLEEVE ISOLATED FROM
REINFORCING IN FLOOR
INSULATED FLANGE
EXTERIOR SLAB
4-WAY RISER BRACE
SEE DETAIL 2 SHEET FX502
AT GRADE TEST STATION.
REFER TO SHEET CU509 FOR
TEST STATION DETAILS
REFER TO
PROFILE: FL-B
ON SHEET
CU206 FOR PIPE
ELEVATION
17" MIN.
FOUNDATION WALL
GRADE BEAM
24" MAX.
FINISHED GRADE
FIRE MAIN, SEE
CIVIL PLAN
FOR CONT
FLEXIBLE
COUPLINGS,
TYP
COMPACTED EARTH
CONCRETE THRUST BLOCK
BY GENERAL CONTRACTOR
RODDING
BY GENERAL CONTRACTOR
FINISHED FLOOR
SEE DETAIL #5 ON SHEET CU502
8" TO FIRE PUMPMECHANICAL JOINT WALL
SLEEVE ISOLATED FROM
REINFORCING IN FLOOR
PRE-PACKAGED ZINC ANODES
INSTALLED HORIZONTALLY AT
BOTTOM OF PIPE TRENCH. NOTE 1
COAT PIPE WITH BITUMASTIC
PRIOR TO CONCRETE PLACEMENT
COAT TIE RODS AND FITTING WITH
BITUMASTIC OR WITH PETROLATUM
WAX TAPE COATING SYSTEM
INSULATING
COUPLING
CABLES EXOTHERMICALLY WELDED TO PIPE
REFER TO
PROFILE: FL-D
ON SHEET
CU207 FOR PIPE
ELEVATION
AT GRADE TEST STATION SHALL BE
INSTALLED 12" BEYOND END OF
SLOPE, REFER TO SHEET CG107 FOR
GRADE ELEVATIONS
8" SLOPE
A2
A1
A4
A3
7 6
35 4
SILVER/SILVER CHLORIDE REFERENCE ELECTRODE
INSTALLED AT BOTTOM OF PIPE TRENCH1. FOR 4" AND 6" PIPE INSTALL 2-12 LB ANODES.
FOR 8" PIPE INSTALL 3-12 LB ANODES.
FOR 12" PIPE INSTALL 4-12 LB ANODES.
2. SEE DETAIL 6 FOR PLAN VIEW OF SERVICE ENTRANCE
7 6
35 4
SILVER/SILVER CHLORIDE REFERENCE ELECTRODE
INSTALLED AT BOTTOM OF PIPE TRENCH
PRE-PACKAGED ZINC ANODES
INSTALLED HORIZONTALLY AT
BOTTOM OF PIPE TRENCH. NOTE 1
A4
A3
A2
A1
CABLES EXOTHERMICALLY
WELDED TO PIPE
METALLIC PIPENON-METALLIC PIPE
TRANSITION TO
NON-METALLIC PIPE
EXTERIOR WALL
1" GALV 45
SPLASH BLOCK
AT GRADE TEST STATION.
REFER TO SHEET CU509 FOR
TEST STATION DETAILS
NOTES:
1. FOR 4" AND 6" PIPE INSTALL 2-12 LB ANODES.
FOR 8" PIPE INSTALL 3-12 LB ANODES.
FOR 12" PIPE INSTALL 4-12 LB ANODES.
2. SEE DETAIL 7 FOR PLAN VIEW OF SERVICE ENTRANCE
NOTES:
SCALE:SCALE:
SCALE: SCALE:
SCALE:
A1
A2
A3
A4
5 FT. MIN.
1 FT. MIN.
1 PIPE DIA.
MIN.
1 IN. – 6 IN.
BUILDING WALL
BUILDING FOUNDATION SLAB
A1
A2
A3
A4
5 FT. MIN.
1 FT. MIN.
1 PIPE DIA.
MIN.
1 IN. – 6 IN.
BUILDING WALL
BUILDING GRADE BEAM
SCALE:
SCALE:
OF
D E
SI
G
N E
D B
Y
US Army Corps of Engineers Honolulu District
A E
C O
M B
IS
H
O P
S Q
U A
R E
- A
SB
T O
W E
R
B
IS
H
O P
S
TR
E E
T, S
U
IT
E
H O
N O
LU
LU
, H A
W A
II
/0
9/
FY
M C
A
PN
E C
H O
P
IE
R R
ES
TO
R
AT
IO
N
U S
A R
M Y
K W
AJ
A
LE
IN
A
TO
LL
(U
SA
KA
A
B
C
D
2 3 4 5
P
LO
T S
C A
LE
S U
BM
IT
TE
D
B Y
D R
A W
N B
Y
S
IZ
E:
A
N S
I D
P
LO
T D
A
TE
C H
EC
KE
D B
Y
D
AT
E:
D R
A W
IN
G
N U
M
BE
R
LO
C
AT
IO
N C
O D
E
S O
LI
C
IT
./C
O N
TR
A
C T
N O
R E
V
IS
IO
N
FI
LE
N A
M E
M
A R
K D
E
SC
R
IP
TI
O
N D
A
TE
A
PP
R
M A
R K
D E
SC
R
IP
TI
O N
D A
TE
A
PP
R
U .S
. A R
M Y
C O
R
PS
O F
E N
G
IN
E
ER
S H
O N
O
LU
LU
D
IS
TR
IC
T
FT
S
H A
FT
E
R , H
AW
AI
I
SHEET
IDENTIFICATION
SHEET
/0
9/
W
A-
-D
-0
3 -
R
TA
S U
B M
IT
TA
L
SHANE
HATMAKER
No. FP 1591
Exp. 06-30-16
O N
-S H
O R
E
BU
IL
D
IN
G
K W
AJ
-E
C H
O -P
IE
R
_O S
_F
_C
EN
TR
A
L
AM
-0
/2 2/
FX501
FI
R
E P
R O
TE
C
TI
O
N D
E
TA
IL
S
J.
HE
IM
J.
HE
IM
S.
H
AT
M
AK
ER
1-
-0
S.
H
AT
M
AK
ER
SH
GENERAL NOTES DUCTWORK LEGEND
RETURN REGISTER
TRANSITION: RECTANGULAR
MOTORIZED DAMPER
EXHAUST REGISTER
FLEXIBLE ROUND DUCT
SUPPLY AIR OR OUTSIDE AIR
DETERMINED TYPE: 4-WAY, 3-WAY, 2-WAY)
EXHAUST AIR DUCT IN SECTION
RETURN AIR DUCT IN SECTION
ROUND SUPPLY DIFFUSER
DUCT IN SECTION
SQUARE CEILING DIFFUSER/SUPPLY
REGISTER (NUMBER OF ARROWS SHOWN
FSD FSD
W/ CONCEALED REGULATOR
MANUAL VOLUME DAMPER
WITH DUCT DETECTOR AND
FIRE SMOKE DAMPER
MANUAL VOLUME DAMPER
SINGLE LINEDOUBLE LINE
20x12 20x12
SYMBOL DESCRIPTION
DUCTWORK(FIRST FIGURE
IS SIZE OF SIDE IN VIEW)
W/ HINGED ACCESS PANEL
FIRE DAMPER
FD
FD
* LINING IS NOT SHOWN AS SYMBOL, WHERE IT IS SPECIFICALLY CALLED OUT
SHOWN IS NET CLEAR INSIDE)
LINED DUCTWORK(DIMENSION
AS LINED DUCT OR REFERRED TO DETAIL INDICATING DUCT LINING
20x12(L)* 20x12*
ELBOW UP
ELBOW DOWN
TEE UP
TEE DOWN
DRAIND
BRANCH CONNECTION UP
BRANCH CONNECTION
BRANCH CONNECTION DOWN
POD POINT OF DISCONNECTION
HWP HEATING HOT WATER PUMP
EF EXHAUST FAN
ESP EXTERNAL STATIC PRESSURE
DDC DIRECT DIGITAL CONTROL
CT COOLING TOWER
CPF CHEMICAL POT FEEDER
CH
CHP
CHILLER
CHILLED WATER PUMP
BEL BELOW
COOLING TOWER FILTERCTF
AS AIR SEPARATOR
SHUT OFF VALVESOV
SUPPLY AIR
SHEET
SECTION
SQUARE
SA
SCBA
SCHR
SQ
SP
SHT
SPECS
SECT
SCHS
SWITCH
STANDARD
STRUCTURAL
TEMPERATURE
TYPICAL
STD
SW
STRUCT
TEFC
TEMP
TOS
TYP
SS
FAN COOLED
SPECIFICATIONS
STAINLESS STEEL (TYPE 316)
STATIC PRESSURE
SELF CONTAINED
TOP OF STEEL
SECONDARY CHILLED
SECONDARY CHILLED
VENT
VERTICAL
WITH
V
UTR
VFD
VERT
W/
WEIGHTWT
WET BULBWB
VARIABLE FREQUENCY
UP THROUGH ROOF
ABOVE
AT
ARCHITECTURAL
APPROXIMATE
AAV
ABV
AC
ARCH
AFF
APPROX
BOILER
AND
AUTOMATIC
BOTTOM OF DUCT
BUILDING
B
AUTO
BOD
BLDG
BHP
BFV
AUTOMATIC AIR VENT
BUTTERFLY VALVE
AIR CONDITIONING
BRAKE HORSEPOWER
ABOVE FINISH FLOOR
CONNECTION
CONTINUATION
CONCRETE
DETAIL
DRY BULB
DIAMETER
CONN
CONT
CFM
CONC
CHWS
DIA
DET
DB
CHWR
DOWN
DETAIL
DOWN THRU ROOF
ELEVATION
ELECTRICAL
ENTERING
EXISTING
DET
DTR
DN
EA
ELEC
ENT
EL
(E)
EACH / EXHAUST AIR
CUBIC FEET PER MINUTE
CHILLED WATER SUPPLY
CHILLED WATER RETURN
FIRE DAMPER
EQUIPMENT
FLOOR
FLOOR SINK
FINISHED
FOOT / FEET
FLEXIBLE
EQUIP
FD
°F
FLR
FPM
FT
FS
FIN
FLEX
GAUGE
GALLON
GALVANIZED
GAL
GA
GPM
GALV
FACE VELOCITYFV
GALLONS PER MINUTE
FEET PER MINUTE
DEGREES FAHRENHEIT
ABBREVIATIONS
HERTZ
HOUR
HORIZONTAL
HORSEPOWER
INCH / INCHES
INSIDE DIAMETER
HVAC
HR
HZ
HP
HORIZ
IN
ID
IN WG
KILOWATT
POUND
LEAVING
KW
LVG
LRA
LB
HEATING, VENTILATING AND
LOCKED ROTOR AMPERES
INCHES WATER GAUGE
MINIMUM
MAXIMUM
MISCELLANEOUS
MECHANICAL
MOUNTING
MOUNTED
MIN
MCC
MAX
MISC
MECH
MD
NC
MTG
MTD
MVD
OUTSIDE AIR
NOT TO SCALE
PRESSURE DROP
OSA
NTS
PD
NORMALLY OPENNO
MOTOR CONTROL CENTER
NORMALLY CLOSED
MANUALLY OPERATED
MOTORIZED DAMPER
POSITIVE
PRESSURE
RETURN
REQUIRED
REFERENCE
RETURN AIR
POS
PSIG
PSI
PSIA
PRESS
REF
REQD
RET
RA
ROOM
RLA
RPM
RM
RIGHT HANDRH
RATED LOAD AMPERES
POUNDS PER SQUARE INCH
POUNDS PER SQUARE INCH
POUNDS PER SQUARE INCH
REVOLUTIONS PER MINUTE
POINT OF CONNECTIONPOC
HEIGHTHGT
FIRE SMOKE DAMPERFSD
UON UNLESS OTHERWISE
SHEET METAL SCREWSMS
WIRE MESH SCREENWMS
SIZE SHOWN ARE IN INCHES UON
SIZE SHOWN ARE IN INCHES UON
HINGED ACCESS PANEL
MD MD
DRAWINGDWG
AIR CONDITIONING
1. THE DRAWINGS AND SPECIFICATIONS REPRESENT THE FINISHED PROJECT. UNLESS OTHERWISE NOTED, THEY DO NOT INDICATE THE METHOD OF CONSTRUCTION. THE CONTRACTOR SHALL SUPERVISE AND DIRECT THE WORK AND SHALL BE SOLELY RESPONSIBLE FOR ALL CONSTRUCTION MEANS, METHODS
TECHNIQUES, SEQUENCES AND PROCEDURES IN ACCORDANCE WITH GENERALLY ACCEPTED
CONSTRUCTION PRACTICES.
2. BEFORE PERFORMING MECHANICAL WORK, THE CONTRACTOR SHALL BE FULLY ACQUAINTED WITH THE JOB CONDITIONS AFFECTING THE DEMOLITION AND INSTALLATION WORK COVERED BY THE NOTES AND
ASSOCIATED DRAWINGS AND SPECIFICATIONS.
3. CONTRACTOR SHALL COORDINATE WORK BETWEEN ALL TRADES AND WORKMEN TO CLOSE, PATCH AND REPAIR ALL HOLES WHERE ITEMS ARE REMOVED AND PROVIDE OPENINGS AS NECESSARY FOR NEW
WORK. FIRE SEAL OPENINGS AS REQUIRED.
4. DO NOT SCALE DRAWINGS, SITE CONDITIONS SHALL PREVAIL. DIMENSIONS INDICATED ARE FOR PRICING PURPOSES ONLY. ALL DIMENSIONS SHALL BE VERIFIED IN THE FIELD TO ENSURE PRECISE FIT.
5. CONTRACTOR SHALL SUBMIT THE WORKING SCHEDULE.
6. PROVIDE FIRE PENETRATION SEALS & SUPPORTS AS REQUIRED FOR EQUIPMENT & RACEWAYS.
INSTALL PER NFPA AND SMACNA REQUIREMENTS.
7. ALL DIMENSIONS SHALL HAVE PRECEDENCE OVER SCALE.
8. ENVIRONMENTAL AIR DUCT ENHAUST SHALL TERMINATE A MINIMUM OF THREE FEET FROM PROPERTY
LINE AND THREE FEET FROM OPENINGS INTO THE BUILDING.
9. ALL DUCT SIZES INDICATED ON THE DRAWINGS ARE INCHES AND NET INSIDE, WITHOUT INSULATION.
MANUAL VOLUME DAMPERS SHALL BE PROVIDED IN ALL DUCT BRANCHES UON.
10. ALL EQUIPMENT SUPPORTS AND PENETRATIONS SHALL BE VERIFIED AND ADAPTED AS REQUIRED FOR
SIZE AND FIT WITH ACTUAL PURCHASED EQUIPMENT. THE EQUIPMENT SPACES, SERVICE ACCESS AND OTHER RELATED FEATURES INDICATED ON THE DRAWING WERE SELECTED FOR ENGINEERING DESIGN
AND SPACE ALLOCATION PURPOSES. THE ACTUAL REQUIREMENTS FOR THE ABOVE DESIGN
ACCOMMODATIONS MAY VARY DEPENDING ON THE PURCHASED EQUIPMENT TO BE INSTALLED. MAKE SUCH CHANGES WITHOUT COST TO THE OWNER AS MAY BE REQUIRED FOR THE EQUIPMENT APPROVED
TO BE FURNISHED IF DIFFERENT THAN SHOWN ON THE DRAWINGS.
11. IMMEDIATELY REPORT TO THE OWNER ANY OBSERVATIONS OF EXISTING CONDITIONS WHICH ARE DISCOVERED IN THE BUILDING AND WHICH MAY INTERFERE WITH THE CORRECT INSTALLATION OF THE
SYSTEM.
12. THE CONTROLS SHOWN ON THE DRAWINGS ARE SCHEMATIC REPRESENTATIONS ONLY. ALL ADDITIONAL CONTROL ITEMS NECESSARY TO SATISFY THE FUNCTIONAL REQUIREMENTS OF THE OPERATION AND SPECIFICATIONS SHALL BE PROVIDED AS PART OF THE WORK. THE SYSTEM SHALL BE COMPLETE IN
ALL RESPECTS; TESTED FOR MEETING THE PERFORMANCE REQUIREMENTS, COMMISSIONED INTO
OPERATION AND CALIBRATED UNDER OPERATING CONDITIONS.
13. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE SAFETY OF WORK AREA DURING CONSTRUCTION
PERIOD. THE CONTRACTOR SHALL PROVIDE ALL SHORING AND BRACING NECESSARY TO INSURE
STABILITY OF THE EXISTING STRUCTURES AND NEW WORK. THE CONTRACTOR SHALL PROTECT
ADJACENT PROPERTIES AND UTILITIES IN ACCORDANCE WITH ALL NATIONAL, STATE AND LOCAL
SAFETY ORDINANCE.
14. CONTRACTOR IS TO PROVIDE NECESSARY PIPE REDUCERS IF EQUIPMENT CONNECTION SIZE IS
DIFFERENT FROM LINE SIZE SHOWN ON DRAWING.
15. SOME SYMBOLS AND ABBREVIATIONS SHOWN ON THIS SHEET ARE NOT BEING USED.
16. ALL 90° MITERED ELL'S SHALL HAVE DOUBLE THICKNESS TURNING VANES UON.
17. TEMPERATURE SENSORS SHALL BE MOUNTED AT 48 INCHES ABOVE FINISHED FLOOR, UON.
18. PROVIDE HIGH POINT VENTS AND LOW POINT DRAINS ON ALL PIPING.
19. CONTRACTOR SHALL NOT RUN WATER, OR PLUMBING PIPES ABOVE ELECTRICAL EQUIPMENT.
20. ALL SEISMIC BRACING SHALL BE IN ACCORDANCE WITH "GUIDELINES FOR SEISMIC RESTRAINTS OF
MECHANICAL SYSTEM" BY SMACNA.
21. ALL VALVES, TRAP PRIMERS, OR OTHER EQUIPMENT SHOWN IN WALLS OR ABOVE NON-ACCESSIBLE
CEILINGS SHALL BE INSTALLED WITH ACCESS PANEL.
22. ALL PIPE PENETRATIONS THROUGH FIRE WALLS OR FLOORS SHALL BE FIRE STOPPED USING U.L.
LISTED SYSTEM.
24. FLEXIBLE DUCT MAXIMUM LENGTH SHALL NOT EXCEED 5'-0".
25. MANUAL VOLUME DAMPERS SHALL BE PROVIDED IN ALL DUCT BRANCHES UNLESS NOTED OTHERWISE.
27. AIR CONDITIONING DUCTWORK SHALL BE CONSTRUCTED, INSTALLED, INSULATED, AND SEALED IN
ACCORDANCE WITH MECHANICAL CODE.
30. ALL MATERIAL EXPOSED WITHIN THE CEILING PLENUM SPACE SHALL HAVE A FLAME SPREAD INDEX OF
NOT MORE THAN 25 AND A SMOKE DEVELOPED RATING OF NOT MORE THAN 50.
31. DUCTWORK AND PIPE ROUTING AS SHOWN ON DRAWINGS IS DIAGRAMMATIC AND IS NOT TO BE SCALED. WHERE ALTERNATE ROUTING, OFFSETS AND TRANSITIONS ARE REQUIRED FOR COORDINATION
OF WORK THIS CONTRACTOR SHALL MAKE CHANGES WITHOUT ADDITIONAL COSTS.
32. CONTRACTOR SHALL USE SMACNA DUCT CONSTRUCTION STANDARDS FOR SHEET METAL DUCTS. ALL HIGH PRESSURE DUCTWORK UPSTREAM OF VAV TERMINAL BOXES SHALL BE CONSTRUCTED FOR 2" W.C. STATIC PRESSURE, SEAL CLASS "A". ALL OTHER DUCTWORK (UON ON FLOOR PLANS) SHALL BE
CONSTRUCTED OF 1" W.C. SEAL CLASS "B".
33. ALL MECHANICAL SYSTEMS SHALL BE INSTALLED IN ACCORDANCE WITH MECHANICAL
CODE AND ASHRAE STANDARD.
34. ALL ZONE DAMPERS, RATES AND DIFFUSERS MUST BE BALANCED TO THE VALUES INDICATED ON THE
FLOOR PLANS. PROVIDE BALANCE REPORT TO ENGINEER PRIOR TO PROJECT CLOSEOUT.
29. MECHANICAL CONTRACTOR IS TO COORDINATE WITH ELECTRICAL ON SIZE/QUANTITY OF MOTORIZED
DAMPERS. I. E. FIRE/SMOKE DAMPERS, FIRE DAMPERS, MOTORIZED DAMPERS, ETC.
28. CONTRACTOR MUST PROVIDE AND INSTALL ALL ACCESS DOORS FOR FCU's, VALVES, FLOW METERS, ETC. COORDINATE LOCATION WITH GENERAL CONTRACTOR.
23. HOUSEKEEPING PADS FOR ALL EQUIPMENT ARE TO BE PROVIDED AND INSTALLED BY GENERAL
CONTRACTOR. COORDINATE LOCATION WITH MECHANICAL CONTRACTOR.
S
T
CO2
W/DUCT ACCESS PANEL
THERMOSTAT
CO2 DETECTOR
EQUIPMENT NUMBER
X
X
(SEE ABBREVIATIONS)
F
FINAL FILTER
F
COOLING COIL
EXHAUST FAN/VENTILATOR
HEATING COIL
P
F
H
C
C
PRE-FILTER
C
DESCRIPTIONSYMBOL
BTUH BRITISH THERMAL
BYPASS DAMPERBD
FAN COIL UNITFC/FCU
CONDENSING UNITCU
SD SMOKE DETECTOR
BOTTOM OF PIPEBOP
CRAC COMPUTER ROOM
FAN OR PUMP
LOUVER
DX CASSETTE UNIT
SYMBOL DESCRIPTION
VOLUME DAMPER
GAUGE
ABSOLUTE
TO ROUND
UNITS PER HOUR
WATER SUPPLY
WATER RETURN
BREATHING APPARATUS
TOTALLY ENCLOSED
NOTED
DRIVE
AIR CONDITIONING
DUCT SMOKE DETECTOR
EQUIPMENT NAME
26. ALL EQUIPMENT SHALL BE INSTALLED PER MANUFACTURER'S RECOMMENDATIONS.
BACK DRAFT DAMPERBDD
ET EXPANSION TANK
EQUIPMENT LEGEND
35. ALL OUTSIDE AIR DUCTS UPSTREAM OF THE FILTER WILL BE CONSTRUCTED OF TYPE 316 STAINLESS
STEEL IN ACCORDANCE WITH THE USAKA INSTALLATION DESIGN GUIDE.
THERMOSTATT-STAT
REFRIGERATION LIQUIDRL
REFRIGERATION SUCTIONRS
EQUIVALENTEQUIV
36. ALL INTERIOR DUCTWORK LOCATED IN "NON AIR CONDITIONED" SPACES OR ROOMS SHALL BE
TYPE 316 STAINLESS STEEL.
KEY NOTE#
OF
D E
SI
G
N E
D B
Y
US Army Corps of Engineers Honolulu District
A E
C O
M B
IS
H
O P
S Q
U A
R E
- A
SB
T O
W E
R
B
IS
H
O P
S
TR
E E
T, S
U
IT
E
H O
N O
LU
LU
, H A
W A
II
/0
9/
FY
M C
A
PN
E C
H O
P
IE
R R
ES
TO
R
AT
IO
N
U S
A R
M Y
K W
AJ
A
LE
IN
A
TO
LL
(U
SA
KA
A
B
C
D
2 3 4 5
P
LO
T S
C A
LE
S U
BM
IT
TE
D
B Y
D R
A W
N B
Y
S
IZ
E:
A
N S
I D
P
LO
T D
A
TE
C H
EC
KE
D B
Y
D
AT
E:
D R
A W
IN
G
N U
M
BE
R
LO
C
AT
IO
N C
O D
E
S O
LI
C
IT
./C
O N
TR
A
C T
N O
R E
V
IS
IO
N
FI
LE
N A
M E
M
A R
K D
E
SC
R
IP
TI
O
N D
A
TE
A
PP
R
M A
R K
D E
SC
R
IP
TI
O N
D A
TE
A
PP
R
U .S
. A R
M Y
C O
R
PS
O F
E N
G
IN
E
ER
S H
O N
O
LU
LU
D
IS
TR
IC
T
FT
S
H A
FT
E
R , H
AW
AI
I
SHEET
IDENTIFICATION
SHEET
/0
9/
W
A-
-D
-0
3 -
R
TA
S U
B M
IT
TA
L
ANDREW REED
No. M 27520
Exp. 06-30-17
O N
-S H
O R
E
P
IE
R B
U
IL
D
IN
G
K W
AJ
-E
C H
O -P
IE
R
_O S
_M
_C
EN
TR
A
L
2"
'-0
AM
-0
/2 2/
M-001
S
YM
B O
LS
, L
EG
E
N D
S, A
N D
G
EN
E R
AL
N
O
TE
S
A.
R
EE
D
J.
LE
E P.
W U
1-
-0
A.
R
EE
D
AR
T ectonic Cop yright 2007
J
A
B
D
FC
CU
M-311
EF
EF
12"Ø MAKE UP AIR, 316SS
GOOSENECK DUCT UTR SEE
36x24 RELIEF LOUVER
WITH BIRDSCREEN
AND BACKDRAFT DAMPER
48"x24" EA LOUVER
WITH BIRDSCREEN
SR-1
750 CFM
6"Ø EAD UTR WITH
BIRDSCREEN SEE
4"Ø EAD UTR WITH
BIRDSCREEN SEE
M501
SF
BDD
M-311
14"x12"
M501
M501
M501
3/4" RS & 3/8" RL DN WALL TO
CONDENSING UNIT
M501
M501
F
FILTER BOX AND
PLENUM
16"Ø MAKE UP AIR, 316SS
GOOSENECK DUCT UTR SEE
SR-1
750 CFM
(TYP.2)
SF
"x
M501
M501
F
3FILTER BOX AND
PLENUM 36x24 RELIEF LOUVER
WITH BIRDSCREEN
AND BACKDRAFT DAMPER
BDD
M501
EF
24"Ø MAKE UP AIR
DUCT 316SS
GOOSENECK UTR
FOR DETAIL SEE
18"x18"
SR-1
1150 CFM
(TYP.2)
18"x18"18"x18"
"x
18"x18"
M501
E-1
1150 CFM
(TYP.2)
S
24"ø
"x
"18"x18"
SF
F
M501
FILTER BANK AND
PLENUM BOX
M501
E-1
1200 CFM
SR-1
1200 CFM
C
10" EAD DN TO CONNECT TO
TOP OF HAZMAT LOCKER
(TYP.2)
1 TYP
1 TYP
1 TYP
TYP
TYP
OF
D E
SI
G
N E
D B
Y
US Army Corps of Engineers Honolulu District
A E
C O
M B
IS
H
O P
S Q
U A
R E
- A
SB
T O
W E
R
B
IS
H
O P
S
TR
E E
T, S
U
IT
E
H O
N O
LU
LU
, H A
W A
II
/0
9/
FY
M C
A
PN
E C
H O
P
IE
R R
ES
TO
R
AT
IO
N
U S
A R
M Y
K W
AJ
A
LE
IN
A
TO
LL
(U
SA
KA
A
B
C
D
2 3 4 5
P
LO
T S
C A
LE
S U
BM
IT
TE
D
B Y
D R
A W
N B
Y
S
IZ
E:
A
N S
I D
P
LO
T D
A
TE
C H
EC
KE
D B
Y
D
AT
E:
D R
A W
IN
G
N U
M
BE
R
LO
C
AT
IO
N C
O D
E
S O
LI
C
IT
./C
O N
TR
A
C T
N O
R E
V
IS
IO
N
FI
LE
N A
M E
M
A R
K D
E
SC
R
IP
TI
O
N D
A
TE
A
PP
R
M A
R K
D E
SC
R
IP
TI
O N
D A
TE
A
PP
R
U .S
. A R
M Y
C O
R
PS
O F
E N
G
IN
E
ER
S H
O N
O
LU
LU
D
IS
TR
IC
T
FT
S
H A
FT
E
R , H
AW
AI
I
SHEET
IDENTIFICATION
SHEET
/0
9/
W
A-
-D
-0
3 -
R
TA
S U
B M
IT
TA
L
ANDREW REED
No. M 27520
Exp. 06-30-17
O N
-S H
O R
E
BU
IL
D
IN
G
K W
AJ
-E
C H
O -P
IE
R
_O S
_M
_C
EN
TR
A
L
/8
'-0
AM
-0
/2 2/
M-111
M
EC
H
AN
IC
AL
F
LO
O R
P
LA
N
A.
R
EE
D
J.
LE
E P.
W U
1-
-0
A.
R
EE
D
AR
0 8' 16' 24'2' 4'
SCALE: 1/8" = 1'-0"
M-111 REF: M-311 SCALE: 1/8" = 1'-0"
1 MECHANICAL GROUND FLOOR PLAN
N
KEY NOTE:
1 ALL INTERIOR DUCTWORK LOCATED IN "NON AIR CONDITIONED" SPACES
OR ROOMS SHALL BE TYPE 316 STAINLESS STEEL.
Tectonic Copyright 2007
A
UTILITY VAULT
A104
551 SF
OFFICE
A102
UNISEX
A103
WAREHOUSE
A101
M-312
SF
1 2 3
B
FC
T
M-312
FC
CU
CU
FC
20"Ø MAKE UP AIR,
316SS GOOSENECK
UTR FOR DETAIL SEE
M501
CU
FC
2M501
S-1
500 CFM
3/4" RS & 3/8" RL DN WALL
TO CONDENSING UNIT
M-312
M501
4"Ø OSA DUCT THRU WALL
WITH 12"x12" OSA LOUVER
"x
12"x14"12"x14"
"x
12"x14"12"x14"
SR-1
875 CFM
(TYP.4)
M501
6E-1
1250CFM
(TYP.2)
"x
"x
F
FILTER RACK
& PLENUM
T
S
24"x18"
SR-1
1000CFM
(TYP.2) 20"x18"
"x
"x
EF
36"x24" EA LOUVER
WITH BIRDSCREEN
M501
4"Ø EA DUCT UTR FOR
DETAIL SEE
M501
1 TYP
1 TYP
1 TYP
OF
D E
SI
G
N E
D B
Y
US Army Corps of Engineers Honolulu District
A E
C O
M B
IS
H
O P
S Q
U A
R E
- A
SB
T O
W E
R
B
IS
H
O P
S
TR
E E
T, S
U
IT
E
H O
N O
LU
LU
, H A
W A
II
/0
9/
FY
M C
A
PN
E C
H O
P
IE
R R
ES
TO
R
AT
IO
N
U S
A R
M Y
K W
AJ
A
LE
IN
A
TO
LL
(U
SA
KA
A
B
C
D
2 3 4 5
P
LO
T S
C A
LE
S U
BM
IT
TE
D
B Y
D R
A W
N B
Y
S
IZ
E:
A
N S
I D
P
LO
T D
A
TE
C H
EC
KE
D B
Y
D
AT
E:
D R
A W
IN
G
N U
M
BE
R
LO
C
AT
IO
N C
O D
E
S O
LI
C
IT
./C
O N
TR
A
C T
N O
R E
V
IS
IO
N
FI
LE
N A
M E
M
A R
K D
E
SC
R
IP
TI
O
N D
A
TE
A
PP
R
M A
R K
D E
SC
R
IP
TI
O N
D A
TE
A
PP
R
U .S
. A R
M Y
C O
R
PS
O F
E N
G
IN
E
ER
S H
O N
O
LU
LU
D
IS
TR
IC
T
FT
S
H A
FT
E
R , H
AW
AI
I
SHEET
IDENTIFICATION
SHEET
/0
9/
W
A-
-D
-0
3 -
R
TA
S U
B M
IT
TA
L
ANDREW REED
No. M 27520
Exp. 06-30-17
P
IE
R B
U
IL
D
IN
G
K W
AJ
-E
C H
O -P
IE
R
_P B
_M
_C
EN
TR
A
L
/8
'-0
AM
-0
/2
2/
M-112
M
EC
H
AN
IC
AL
F
LO
O R
P
LA
N
A.
R
EE
D
J.
LE
E P.
W U
1-
-0
A.
R
EE
D
AR
M-112 REF: M-312 SCALE: 1/8" = 1'-0"
1 MECHANICAL GROUND FLOOR PLAN
N
KEY NOTE:
1 ALL INTERIOR DUCTWORK LOCATED IN "NON AIR CONDITIONED" SPACES
T ectonic Cop yright 2007
GROUND FLOOR
0' - 0"
ROOF
23' - 4"
A C
EF
SF
18"x18"14"x30"20"x20"
48"x24" EA LOUVER
WITH BIRDSCREEN
E1
1200 CFM
"ø
ROUND GOOSENECK
SEE 6/M501
WAREHOUS…