This document is a presentation on recommendations for improving water treatment systems at various Department of Defense medical facilities. It provides an overview of case studies and lessons learned from issues at Fort Bliss, Camp Pendleton, and NAS Pensacola/Minot Air Force Base related to water quality, corrosion, and Legionella outbreaks. It then makes recommendations for softening equipment, dental equipment, and sterile processing departments to address total dissolved solids levels, bacteria and endotoxin treatment, and compliance with standards like AAMI TIR34. The presentation also outlines a typical water treatment system layout and the components of an effective water management plan following ASHRAE 188 guidelines.
View the file
Other files
Show all 21
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Medically Ready Force… Ready Medical Force
UNCLASSIFIED/CUI
DHA Water Treatment Program
DHA Water Treatment Program
Agenda
1) Case Studies and Key Issues
2) Lesson’s Learned
3) Recommendations for Softening Equipment
4) Dental Equipment Recommendation’s
5) Sterile Processing Department (SPD) Equipment
Recommendations and Layout
6) Water Management Plan & ASHRAE 188
7) DHA Policy Guidelines vs. Contractor Guidelines
DHA Water Treatment Program
Who is on the Team
Kelly Mollenkopf PE (FPE/ME) Chief, Engineering and Design
Joey Bass Senior Program Manager
Miro Uhrik Quality Control Specialist
Jaclyn Kiehl Mechanical Engineer/Water SME
Paul Cherry PE (ME) Deputy, Engineering and Design
Alok Kumar PE, EMP Sr. Director, Energy Services
Chris Bosch
VP, IT
Kenneth Cruz Program Manager
DHA Water Treatment Program
Case Studies and Key Issues
Site
Legionella Outbreak
Residual Chlorine
Levels Low after softener
Iron Reducing Bacteria/ Positive
Total Coliform
Reverse Osmosis system is considered a dead leg
Salt Not
NSF
compliant
Zero Hardness
Soft Water System has no Blending
Water quality TDS needs to be between 50-
150ppm
AAMI
TIR34
Complia nt
Water Quality is
Highly Corrosive
Lead Count over the 90th percentile
Long Pipe Run's
Lack of Pipe insulation on Cold Pipes
HW
System was 93°F- 111°F
Fort Bliss X X X X X X X X Camp Pendleton X X X X X X X X
Pensacola/ Minot X X
DHA Water Treatment Program
Lessons Learned (Fort Bliss)
• Potable water system showed corrosion due to zero hardness and no proper bypass system installed
• Site did not have a constant chlorine disinfectant residual
• Corrosion inhibitor needed to be installed due to elevated levels of lead in domestic water system
• Not all water quality parameters have been tested
• Operation wastes salt and regenerates each softener before it is exhausted of salt
• Galvanized Pipe fittings were installed
• CSI system was not piped properly
• No operators where properly licensed under TCEQ
• Salt in Brine tank was not NSF compliant
DHA Water Treatment Program
Lessons Learned (Camp Pendleton)
• Water Softening System removed over
50% of free chlorine coming from the water utility
• Long pipe runs that reduce in pipe diameter along route
• The infrequent use of the RO system effectively creates a dead leg
• Legionella was found in low-use taps.
• Lack of pipe insulation on cold pipes
• Hot Water System were found between
93°F and 111 °F
• The CSI system at NHCP was demonstrated to be ineffective in controlling Legionella in the hospital water supply, with 45% of POU taps positive
• POU filtration may be effective at retaining bacteria from water piped to a water tap
DHA Water Treatment Program
Lessons Learned (NAS Pensacola/Minot AFB )
• Sterile Processing Department water not up to AAMI TIR 34 Standard
• Blending TDS level’s must be within
50-150 ppm for certain type of equipment
• Process water must be either “Utility” or “Critical”
• Feedwater Quality is different for Carbon-Steel and Stainless Steam Generators
DHA Water Treatment Program
Potable Water
Condenser Water System
(Cooling Towers)
Steam System (Steam Boilers)
Chilled Water System (Chillers)
Heating Hot Water System
(Hot Water Boilers)
Heat Pump System (Process Cooling)
Domestic Hot and Cold water, RO/DI (Sterilizer, Dental, Special Medical Use, Plumbing Fixtures (Sink, Toilet, Drinking Fountain
Cooling Tower, Condensers Open Loop.
Make-Up Water System
Steam for Boiler Make-up Water System
Chillers Closed Loop Water
Heating Hot Water Boiler Closed Loop Water
Process Cooling Closed Loop Water
DHA Water Treatment Program
Recommendations for Softening Equipment
• Provide a minimum hardness of 51.3 mg/L. Typical softener’s produce water hardness between 0-30 mg/L
• The water softening system must include a hard water bypass and blending system consisting of a proportioning valve and a bypass meter
• Any treatment additives used for potable water should follow NSF certification and approval for use in drinking water
• 10% of cross-linked resin has high performances with a chlorine environment. Few chances are available to break down the beads with chlorine
• When installing Copper/Silver Ionization; Install after softener
DHA Water Treatment Program
Dental Equipment Recommendations
• Dental water purification systems may be direct feed or bottle-fill systems
• A source water bypass should be installed
• Manufacturer’s may recommend any required pre-filters, booster pumps, water storage tanks, and dental water faucets
• A pre-filter is preferred if the source water quality is >250 PPM TDS
DHA Water Treatment Program
Sterile Processing Department (SPD) Equipment Recommendations and Layout
• Will need a softener system if Stainless-Steel Steam Generators are installed in equipment
• If a Large system is required, a recirculating loop must be installed with tank and booster pump that flows at 3 to 5 feet per Second
• Both Large and Small system need bacterial and endotoxin treatment
• Blending Valve must be installed on Reverse Osmosis system that need Total
Dissolved Solid levels between 50-150 ppm
• Small volume system’s have be installed without recirculation loop however must still comply with AAMI TIR34 quality
DHA Water Treatment Program
Typical Layout of Water Treatment System for Critical Water
DHA Water Treatment Program
Water Management Plan & ASHRAE 188 Water Management Plan
• Create a Team
• Map the Water System
• Identify Risk and Create a
Plan
• Develop Standard
Operating Procedures
Monitoring Control Measure Example
DHA Water Treatment Program
DHA Policy Guidelines vs. Contractor Guidelines
DHA Water Treatment Program
Questions?
| DHA Water Treatment Program |
| DHA Water Treatment Program |
| DHA Water Treatment Program |
| DHA Water Treatment Program |
| DHA Water Treatment Program |
| DHA Water Treatment Program |
| DHA Water Treatment Program |
| DHA Water Treatment Program |
| DHA Water Treatment Program |
| DHA Water Treatment Program |
| DHA Water Treatment Program |
| DHA Water Treatment Program |
| DHA Water Treatment Program |
| DHA Water Treatment Program |
| DHA Water Treatment Program |