Attachment 65b - Log Cat A Binder Set 2 2018 0118_Part2.pdf

PDF 44 MB Posted

Attached to
Pre-Solicitation Notice Initial Outfitting Medical Center Addition and Alteration (MCAA), Naval Support Activity Bethesda Campus, Bethesda, MD
Solicitation number
W9127S22R6001
Issued by

About this file

This document provides details on a pre-solicitation notice for initial outfitting and transition services related to the Medical Center Addition and Alteration project at the Naval Support Activity Bethesda Campus in Bethesda, Maryland. The United States Army Corps of Engineers seeks a service-disabled veteran-owned small business to provide firm-fixed price initial outfitting, transition, and commissioning services for the 590,000 gross square foot Medical Center Addition and Alteration project. Services include validating designer plans, procuring and installing room contents, relocating equipment and personnel during various demolition and renovation phases, and excess property disposal. The project involves transition and outfitting of multiple existing and new buildings over approximately 1870 days following contract award. The pre-solicitation notice estimates a February 2022 posting of the request for proposal on SAM.gov to procure these services.

View the file

Other files

File Type Posted
Draft Solicitation 27January2022.pdf PDF
Attachment 65a - Log Cat A Binder Set 2 2018 0118_Part1.pdf PDF
Attachment 66b - Log Cat C Binder_Part2.pdf PDF
Attachment 66c - Log Cat C Binder_Part3.pdf PDF
Attachment 66d - Log Cat C Binder_Part4.pdf PDF
Attachment 66a - Log Cat C Binder_Part1.pdf PDF
Attachment 29 - B.08.02_DMLSS P1 DCAA.xls XLS spreadsheet
Attachment 19 - BLDG 10 FLOOR PLAN SET.pdf PDF
Attachment 23 - CID Supporting Documents Redacted.pdf PDF
Attachment 52 - DMLSS P2-3 BHDA01.xls XLS spreadsheet
Attachment 40 - DMLSS P1 OB GYN3.xls XLS spreadsheet
Attachment 26 - Design Analysis 65Percent Basis of Design.pdf PDF
Attachment 9 - 1171746drwg600021.pdf PDF
Attachment 68 - Log Cat R Binder.pdf PDF
Attachment 57 - DMLSS P2-3 EBFA00 HC.xls XLS spreadsheet
Attachment 36 - DMLSS P1 METERNAL.xls XLS spreadsheet
Attachment 83 - Updated Artwork Package.pdf PDF
Draft Solicitation 22R6001.pdf PDF
Attachment 72 - MCAA PHASE 1_28OCT21 Redated V4.xlsx XLSX spreadsheet
Attachment 75 - MilCon Pre-Bid Site Visit Presentation for Construction Contractors (June 2019).pdf PDF
Attachment 54 - DMLSS P2-3 BLAA00 PI.xls XLS spreadsheet
Attachment 8 - 1171746drwg60007I.pdf PDF
Attachment 3 - GC Schedule 113782 - June 2021 - Full WBS.pdf PDF
Attachment 41 - DMLSS P1 PRIMARY.xls XLS spreadsheet
Attachment 17 - BLDG 07 FLOOR PLAN SET.pdf PDF
Attachment 81 - SECNAV_5512_1_11787 APPROVED AC PASS ID FORM 05282014.pdf PDF
Attachment 46 - DMLSS P2-3 BBDA01.xls XLS spreadsheet
Attachment 53 - DMLSS P2-3 BHGA00.xls XLS spreadsheet
Attachment 50 - DMLSS P2-3 BHAAWW.xls XLS spreadsheet
Attachment 51 - DMLSS P2-3 BHCA00.xls XLS spreadsheet
Attachment 84 - Wayfinding and Signage.docx DOCX document
Attachment 15 - BLDG 02 FLOOR PLAN SET.pdf PDF
Attachment 49 - DMLSS P2-3 BFFA00.xls XLS spreadsheet
Attachment 6 - 1171746drwg60005.pdf PDF
Attachment 16 - B.08.02_BLDG 05 FLOOR PLAN SET.pdf PDF
Attachment 55 - DMLSS P2-3 BLBA00 OC.xls XLS spreadsheet
Attachment 20 - BLDG 84T_FLOOR PLAN SET_20130111.pdf PDF
Attachment 11 - 20201130 PFD WR MCAA BLDG 9-10.pdf PDF
Attachment 25 - DBIDs-Process-Guide.pdf PDF
Attachment 62 - DMLSS Phase 1 OBGYN.xls XLS spreadsheet
Attachment 21 - BLDG 85T OUTPT MED FAC OVERALL 2.pdf PDF
Attachment 4 - 1171746drwg60001.pdf PDF
Attachment 22 - BLDG 85T OUTPT MED FAC OVERALL.pdf PDF
Attachment 12 - 20201135 PFD WR MCAA BLDG C.pdf PDF
Attachment 77 - NSA-Bethesda Installation and Maps.pdf PDF
Attachment 70 - MCAA IOR Weekly Risk Report Template.xlsx XLSX spreadsheet
Attachment 27 - DMLSS P1 ANESTHESIA.xls XLS spreadsheet
Attachment 45 - DMLSS P2-3 BBDA00.xls XLS spreadsheet
Attachment 82 - Submittal Examples.pdf PDF
Attachment 31 - DMLSS P1 ER.xls XLS spreadsheet
Show 40 more

Latest 50 of 90 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Page 3June 7, 2016

Equipment Data Sheet Report

Naval Facilities Engineering Command

WRNMMC P114 Medical Center Addition/Alteration

WRNMMC P114 MEDICAL CENTER ADDITION / ALTERATIONS

A D0900LOG CAT

Workstation, Dental Lab, Receiving

Workstation, Dental Lab, Receiving Revised 12/2/2009

Modular workstation for receiving supplies in a dental laboratory. The unit stands on the floor and consists of a 24" wide base cabinet unit with 4 drawers, a 24" wide single or double door base cabinet unit with an adjustable shelf and a 74" wide laminate counter supported by the two base cabinets. The working space between the two cabinets contains an undercounter single drawer unit.

Nevin Laboratories, Inc.(NEVIN)Manufacturer/ID

Model

2404,2407,2420,24PL

Product Number

Dimensions 74"w x 24"d x 34"h

( 188 cm w x 61 cm d x 86 cm h)

Clearance

460 lbs. (209 Kgs.)Weight

6 Movable or Above Floor - Minor Building ImpactMounting

Notes Project Notes

Finish

DPrime Equipment

60Lead Time

Group IIGroup Code

Acceptance Time 0

0Installation Time

BENWK Bench, Work

EN ENT/Dental EquipmentBid Package

Class Code

Gases

Medical Gases Laboratory / Misc. Gases

Gas Type Desc Quantity Outlet CFM PSIG Connection

Compressed Air

Natural Gas

Confirm requirements with manufacturer. Workbench comes prepiped.

A Log Cat

Unit of Issue

NSN 6520

EA

Utilities 1 2 3 4 5 6

Energy Star No

D0900 Page 1June 7, 2016

Equipment Data Sheet Report

Naval Facilities Engineering Command

D0900

Page 2June 7, 2016

A D0905LOG CAT

Workstation, Dental Lab, Four Station

Workstation, Dental Lab, Four Station Revised 1/4/2016

Dental Lab workstation custom layout for 4 techs. Dimensions are for 1 workstation. User will need to verify final layout for 4.

Nevin Laboratories, Inc.(NEVIN)Manufacturer/ID

Model 9748 (4)

Product Number

Dimensions 48"w x 24"d x 72"h

( 122 cm w x 61 cm d x 183 cm h)

Clearance

Weight

6 Movable or Above Floor - Minor Building ImpactMounting

Notes Project Notes

Finish

DPrime Equipment

60Lead Time

Group IIGroup Code

Acceptance Time 0

0Installation Time

DENWK Dental Lab Workstations

EN ENT/Dental EquipmentBid Package

Class Code

Line Cord & Plug

Normal

N

N

No

FLA

Circuit Size

Phase Watts

Hp.

Surge Prot.

UPS

Dedicated CircuitPower Source

Connection

Data Port

N

Volts

US Intl.

Electrical 1/4/2016Revised to SinkDrain Type Drain Size GPM

Plumbing

Water Type GPM PSIG Temp (F) Size

Domestic Water Cold

Domestic Water Hot

A Log Cat

Unit of Issue

NSN 6520

EA

Utilities A D A

1 2 3 4 5 6

Energy Star No

D0905 Page 1June 7, 2016

Equipment Data Sheet Report

Naval Facilities Engineering Command

D0905

A D0960LOG CAT

Workstation, Dental Lab, Plaster

Workstation, Dental Lab, Plaster Revised 10/29/2015

Dental Lab workstation, plaster.

Nevin Laboratories, Inc.(NEVIN)Manufacturer/ID

Model Custom

Product Number

Dimensions 87"l x 24"d x 78"h

( 221 cm l x 61 cm d x 198 cm h)

Clearance

Weight

6 Movable or Above Floor - Minor Building ImpactMounting

Notes Project Notes

Finish

DPrime Equipment

60Lead Time

Group IIGroup Code

Acceptance Time 0

0Installation Time

DENWK Dental Lab Workstations

EN ENT/Dental EquipmentBid Package

Class Code to SinkDrain Type Drain Size GPM

Plumbing

Water Type GPM PSIG Temp (F) Size

Domestic Water Cold

Domestic Water Hot

A Log Cat

Unit of Issue

NSN 6520

EA

Utilities D A D 1 2 3 4 5 6

Energy Star No

D0960 Page 1June 7, 2016

Equipment Data Sheet Report

Naval Facilities Engineering Command

D0960

A D0980LOG CAT

Workstation, Dental Lab, Polishing, Single

Workstation, Dental Lab, Polishing, Single Revised 7/18/2017

Grinder/polisher ment for dry grinding operations.

Handler Manufacturing(HANDL)Manufacturer/ID

Model 75D

Product Number

Dimensions 40"w x 24"d x 56"h

( 102 cm w x 61 cm d x 142 cm h)

Clearance

325 lbs. (148 Kgs.)Weight

6 Movable or Above Floor - Minor Building ImpactMounting

Notes Project Notes

Finish

DPrime Equipment

60Lead Time

Group IIGroup Code

Acceptance Time

Installation Time

DENWK Dental Lab Workstations

EN ENT/Dental EquipmentBid Package

Class Code

0.75

Line Cord & Plug

Normal

N

N

No

FLA

Circuit Size

Phase Watts

Hp.

Surge Prot.

UPS

Dedicated CircuitPower Source

Connection

Data Port

N

Volts

US Intl.

Electrical 7/18/2017Revised

A Log Cat

Unit of Issue

NSN 6520

EA

Utilities A

1 2 3 4 5 6

Energy Star No

D0980 Page 1July 18, 2017

Equipment Data Sheet Report

Naval Facilities Engineering Command

D0980

Page 2July 18, 2017

Page 3July 18, 2017

A D7090LOG CAT

Utility Center, Dental, Wall or Floor Mounted

Utility Center, Dental, Wall or Floor Mounted Revised 10/28/2015

Dental delivery System.

A-dec Inc.(A-DEC)Manufacturer/ID

Dimensions 14.5"w x 18"d

(53.3cm w x 51.1cm d x 68.6-99.1cm h)

Clearance

60 lbs. (24 Kgs.)Weight

15 Major InstallationMounting

Notes Project Notes

Finish

BPrime Equipment

60Lead Time

Group IIGroup Code

Acceptance Time 0

0Installation Time

DENTS Dental Delivery System

EN ENT/Dental EquipmentBid Package

Class Code

1.5

Normal

N

Y

No

FLA

Circuit Size

Phase Watts

Hp.

Surge Prot.

UPS

Dedicated CircuitPower Source

Connection

Data Port

120 230

Volts

US Intl.

60 50 Hz.

Electrical 10/28/2015Revised

Design level specification. Appropriate electrical requirements, as well as proper cord and plug, to be specified per region during procurement.

A Log Cat

Unit of Issue

NSN 6520

EA

Utilities B A H 1 2 3 4 5 6

Energy Star No

D7090 Page 1June 7, 2016

Equipment Data Sheet Report

Naval Facilities Engineering Command

D7090

Page 4June 7, 2016

Page 5June 7, 2016

A D8620LOG CAT

Bin, Plaster, 3 Compartment

Bin, Plaster, 3 Compartment Revised 2/29/2016

Wall mounted bin with 3 storage compartments. Each compartment holds 25-lbs. of stone. Gravity feed. Constructed of steel with hinged covers top and bottom.

Available in Bisque or Fashion Gray color.

Nevin Laboratories, Inc.(NEVIN)Manufacturer/ID

Dimensions 21"w x 8"d x 18"h

( 53 cm w x 20 cm d x 46 cm h)

Clearance

Weight

8 Wall - Minor Building ImpactMounting

Notes Project Notes

Finish

DPrime Equipment

60Lead Time

Group IIGroup Code

Acceptance Time 0.1

0Installation Time

CASTD Cast Plaster Dispenser

OR Orthopedic EquipmentBid Package

Class Code

A Log Cat

Unit of Issue

NSN 6520

EA

Utilities 1 2 3 4 5 6

Energy Star No

D8620 Page 1June 7, 2016

Equipment Data Sheet Report

Naval Facilities Engineering Command

D8620

A D8650LOG CAT

Chute, Waste, Plaster, Counter Mounted

Chute, Waste, Plaster, Counter Mounted Revised 3/1/2016

Rectangular thru counter waste chute.

American Dental(AMDEN)Manufacturer/ID

Model GR412

Product Number

Dimensions 5.75" w x 13.75" d

( 15 cm w x 35 cm d)

Clearance

1.5 lbs. (1 Kgs.)Weight

7 Undercounter - Minor Building ImpactMounting

Notes Project Notes

Finish

DPrime Equipment

60Lead Time

Group IIIGroup Code

Acceptance Time 0

0Installation Time

DENTP Chute, Waste, Plaster, Counter, Dental

EN ENT/Dental EquipmentBid Package

Class Code

A Log Cat

Unit of Issue

NSN 6520

EA

Utilities 1 2 3 4 5 6

Energy Star No

D8650 Page 1June 7, 2016

Equipment Data Sheet Report

Naval Facilities Engineering Command

D8650

A D9015LOG CAT

Microfinisher, Dental Counter Mounted

Microfinisher, Dental, Counter Mounted Revised 5/28/2009

This system allows the blasting start / stop process to occur within a fraction of a second. The modular construction allows expansion of the 2-tank basic unit to one with 3 or 4 tanks.

Renfert GmbH(RENFE)Manufacturer/ID

Model Basic Quattro IS

Product Number

Dimensions 17"w x 22"d x 12.25"h

( 43 cm w x 56 cm d x 31 cm h)

Clearance

27 lbs. (12 Kgs.)Weight

6 Movable or Above Floor - Minor Building ImpactMounting

Notes Project Notes

Finish

DPrime Equipment

60Lead Time

Group IIGroup Code

Acceptance Time 0

0Installation Time

BLAST Blaster, Sand

EN ENT/Dental EquipmentBid Package

Class Code

Line Cord & Plug

Normal

N

N

No

FLA

Circuit Size

Phase Watts

Hp.

Surge Prot.

UPS

Dedicated CircuitPower Source

Connection

Data Port

N

Volts

US Intl.

Electrical 10/12/2015Revised

Gases

Medical Gases Laboratory / Misc. Gases

Gas Type Desc Quantity Outlet CFM PSIG Connection

Lab Air

Air Working pressure: 14.5-87 psi; Air connecting pressure (external): 87-116 psi. Refer to data sheet.

A Log Cat

Unit of Issue

NSN 6520

EA

Utilities A D

1 2 3 4 5 6

Energy Star No

D9015 Page 1June 7, 2016

Equipment Data Sheet Report

Naval Facilities Engineering Command

D9015

A F0190M2LOG CAT

Chair, Auditorium, With Tablet Arm

J30

866.892.6130 www.sediasystems.com

S S

J

S e d ia S ys te m s I n c P ri n te d o n F

S C c e rt ifi e d r e c yc le d p a p e r

Standard Back-Short Panel

High Back-Short Panel

Standard Back-Long Panel

High Back-Long Panel

Tablet

Options

• Anti-panic Tablet Arm

• Riser Mount

• Wire Management

• Short or Long End Panel

• Row Letters & Seat Numbers

• Aisle Light

• Cup Holder

• Transfer Arm

Features

• Standard or High Back

• Gravity Uplift Seat

• Tri-Pivot Mechanism

• Straight or Radius Row Configurations

• Flat, Sloped or Tiered Floor Installations

Finishes

• SEAT & BACK PANELS: Upholstery, Laminate or Wood

• END & INTERMEDIATE PANELS:

Upholstery, Laminate or Wood

• ARMRESTS: Upholstery or Wood

• TABLET: Black Phenolic

• FRAME: Silver or Black

• TEXTILES: Fabric or Coated Fabric

J30 Morrow Design

Developed to complement today’s architecturally refined interiors, the J30 auditorium chair delivers contemporary design and comfort with a variety of options and finishes.

20-26

20-26

19.5

19.5

.5

.5

.5

.5

.5

.5

.5

A K2515M2LOG CAT

Dishwasher, ADA

Dishwasher, ADL Revised 1/6/2016

ADA compliant stainless steel dishwasher

Whirlpool Corporation(WHIRL)Manufacturer/ID

Model WDF550SSAS

Product Number

Dimensions 23.6"w x 24"d x 32.5"-34.5"h

( 60 cm w x 61 cm d x 83 cm -34.5cm h)

Clearance

Weight

10 Floor (fixed) - Major Building ImpactMounting

Notes Project Notes

Stainless SteelFinish

DPrime Equipment

60Lead Time

Group IGroup Code

Acceptance Time 0

0Installation Time

DISWA Dishwasher

DA Domestic AppliancesBid Package

Class Code

Line Cord & Plug

Normal

N

N

No

FLA

Circuit Size

Phase Watts

Hp.

Surge Prot.

UPS

Dedicated CircuitPower Source

Connection

Data Port

N

Volts

US Intl.

Electrical 1/6/2016Revised

Unit can be direct wired or connected with a power supply cord.

to SinkDrain Type Drain Size GPM

12/18/2015Plumbing Revised

Water Type GPM PSIG Temp (F) Size

Domestic Water Hot 20-120 120

3/8" OD

copper tube

A Log Cat

Unit of Issue

NSN 7310

EA

Utilities D A 1 2 3 4 5 6

Energy Star No

K2515M2 Page 1June 7, 2016

Equipment Data Sheet Report

Naval Facilities Engineering Command

K2515M2

A K2620M1LOG CAT

Disposal, Household

Disposal, Household Revised 12/18/2015

Badger 900 features a ¾ horsepower heavy-duty quiet Dura-Drive induction motor and a space-saving compact design.

In-Sink-Erator(INSIN)Manufacturer/ID

Badger 900

Dimensions 6.34"w x 6.34"d x 12.6"h

( 16 cm w x 16 cm d x 32 cm h)

Clearance

26 lbs. (12 Kgs.)Weight

10 Floor (fixed) - Major Building ImpactMounting

Notes Project Notes

Finish

DPrime Equipment

60Lead Time

Group IGroup Code

Acceptance Time 0

0Installation Time

DISPO Disposal

FS Food Service EquipmentBid Package

Class Code

0.75

Line Cord & Plug

Normal

N

N

No

FLA

Circuit Size

Phase Watts

Hp.

Surge Prot.

UPS

Dedicated CircuitPower Source

Connection

Data Port

N

Volts

US Intl.

Electrical 12/18/2015Revised

1.5Direct ConnectDrain Type Drain Size GPM

11/21/2007Plumbing Revised

A Log Cat

Unit of Issue

NSN 7310

EA

Utilities B G 1 2 3 4 5 6

Energy Star No

K2620M1 Page 1June 7, 2016

Equipment Data Sheet Report

Naval Facilities Engineering Command

K2620M1

A K3401LOG CAT

Hood, Exhausted, Non Commercial

Hood, Exhaust, Non-Commercial Revised 12/23/2015

See cut-sheet for hood details.

Broan-NuTone LLC(BROAN)Manufacturer/ID

Model WS1530SS Allure

Product Number

Dimensions 30"w x 20"d x 7.25"h

( 76 cm w x 51 cm d x 18 cm h)

Clearance

34 lbs. (15.5 Kgs.)Weight

10 Floor (fixed) - Major Building ImpactMounting

Notes Project Notes

Stainless steelFinish

DPrime Equipment

30Lead Time

Group IIIGroup Code

Acceptance Time 0

0Installation Time

RANGH Range, Hood

DA Domestic AppliancesBid Package

Class Code

2 Junction Box

Normal

N

Y

No

FLA

Circuit Size

Phase Watts

Hp.

Surge Prot.

UPS

Dedicated CircuitPower Source

Connection

Data Port

N

Volts

US Intl.

Electrical 12/23/2015Revised

HVAC

AMBIENT CONDITIONS

Heat Gain (BTU/Hr.)

Room Temp(F)

Temp Range

Room Humidity

Humidity Range

Exhaust Type

Connection

CFM

PD (In. W.C.)

Temp(F)

Vent Connect.

EXHAUST AIR

Can be 3-1/4" X 10" ducted (170 CFM if horizontal, 200 CFM if vertical), 7" DIA ducted (220 CFM), or non-ducted.

SUPPLY AIR

Cleanliness

Connection

CFM

PD (In. W.C.)

Temp(F)

A Log Cat

Unit of Issue

NSN 7310

EA

Utilities A

1 2 3 4 5 6

Energy Star No

K3401 Page 1June 7, 2016

Equipment Data Sheet Report

Naval Facilities Engineering Command

K3401

A K4560M3LOG CAT

Oven, ADL

Oven, Convection, Double, Electric, Free Standing, ADL Revised 12/18/2015

Free standing electric range with double convection oven.

General Electric Appliances Co(GENEE)Manufacturer/ID

Model 9S950SFSS

Product Number

Dimensions 30"w x 28.9"d x 37.25"h

( 76 cm w x 73 cm d x 95 cm h)

Clearance

259 lbs. (118 Kgs.)Weight

10 Floor (fixed) - Major Building ImpactMounting

Notes Project Notes

Stainless SteelFinish

DPrime Equipment

30Lead Time

Group IIIGroup Code

Acceptance Time 0

0Installation Time

RANGG Range, Gas

DA Domestic AppliancesBid Package

Class Code

11.4

Line Cord & Plug

Normal

N

N

No

FLA

Circuit Size

Phase Watts

Hp.

Surge Prot.

UPS

Dedicated CircuitPower Source

Connection

Data Port

N

Volts

US Intl.

Electrical 12/18/2015Revised

A Log Cat

Unit of Issue

NSN

EA

Utilities C

1 2 3 4 5 6

Energy Star No

K4560M3 Page 1June 7, 2016

Equipment Data Sheet Report

Naval Facilities Engineering Command

K4560M3

A L1200LOG CAT

Cabinet, Specimen, Pass Thru, CRS

Cabinet, Specimen, Pass Thru, CRS Revised 6/26/2012

Provides convenient passage for specimen from patient area to laboratory. Mounts in walls 3" to 5 3/4" thick. Type 304 stainless steel, satin finish. Self-closing doors. Interlocking mechanism prevents both doors from being open at the same time; provides sight barrier.

Removable stainless steel tray.

Bobrick Washroom Equipment, Inc.(BOBRI)Manufacturer/ID

B-505

Dimensions 12.75"w x 6"d x 11.5"h

( 32 cm w x 15 cm d x 29 cm h)

Clearance

12 lbs. (5 Kgs.)Weight

13 Wall - Major Building ImpactMounting

Notes Rough Wall Opening: 11 1/2" W, 10 7/8" H; 3" to 5 3/4" thick.

Project Notes

Stainless SteelFinish

BPrime Equipment

30Lead Time

Group IGroup Code

Acceptance Time 0.1

0Installation Time

PASST Pass-Through Assembly

LE Laboratory EquipmentBid Package

Class Code

A Log Cat

Unit of Issue

NSN 6640

EA

Utilities 1 2 3 4 5 6

Energy Star No

L1200 Page 1April 7, 2017

Equipment Data Sheet Report

Naval Facilities Engineering Command

L1200

Page 2April 7, 2017

A L2192MLOG CAT

Purifier, Air

Purifier, Air Revised 4/15/2016

Gas Cabinet and Room Air Purifier Scrubber. Scrubs toxic exhaust gas in a 3000 CF room. Designed to meet CE and CSA electrical codes. Dimensions and weight listed are for both purifier (25"w x 24"d x 35"h; 116 lbs) and gas cylinder cabinet (25"w x 24"d x 70"h, 200 lbs). Air flow rate is 1000 CFM for 60 Hz. Locate near excimer laser system. Intake grill on front of purifier should be freely open to room air.

Spectra Gases, Inc.(SPECG)Manufacturer/ID

F5300 Series with F4007

Dimensions 25"w x 24"d x 70"h

( 64 cm w x 61 cm d x 190 cm h)

4" behind, 18" aboveClearance

316 lbs. (143 Kgs.)Weight

6 Movable or Above Floor - Minor Building ImpactMounting

Notes Project Notes

Finish

DPrime Equipment

60Lead Time

Group IIGroup Code

Acceptance Time 0

0Installation Time

PURIF Purifier/Deodorizer, Air

HD Fume/Laminar Flow/Bio. HoodsBid Package

Class Code

10 Line Cord & PlugFLA

Circuit Size

Phase Watts

Hp.

Surge Prot.

UPS

Dedicated CircuitPower Source

Connection

Data Port

115 0Volts

US Intl.

Electrical 2/20/2013Revised

115/208-230 VAC/60 Hz.

A Log Cat

Unit of Issue

NSN 4460

EA

Utilities A

1 2 3 4 5 6

Energy Star No

L2192M Page 1June 7, 2016

Equipment Data Sheet Report

Naval Facilities Engineering Command

L2192M

P ag e

Ju n e 7, E qu ip m en t D at a

S he et R ep or t

N av al F ac ili tie s

E ng in ee rin g

C om m an d

W R

N M

M C

P

M ed ic al C en te r A dd iti on /A lte ra tio n

Page 6June 7, 2016

Page 7June 7, 2016

Page 8June 7, 2016

Page 9June 7, 2016

Detector, Gas Revised 3/4/2016

Gas detector warns users of hazardous atmosphere. When incorporated with an emergency shutdown system, the series F6400 detector can turn off supply of hazardous gas if a leak is detected. Specify one (6401) or two (6402) channels and gas codes for gases to be detected. Dimensions provided are for two channel unit.

Spectra Gases, Inc.(SPECG)Manufacturer/ID

F6400

Dimensions 10"w x 4.33"d x 7.09"h

( 25 cm w x 11 cm d x 18 cm h)

Clearance

Weight

6 Movable or Above Floor - Minor Building ImpactMounting

Notes Project Notes

Finish

DPrime Equipment

60Lead Time

Group IIGroup Code

Acceptance Time 0

0Installation Time

PURIF Purifier/Deodorizer, Air

XX Other or UnassignedBid Package

Class Code

10 Line Cord & PlugFLA

Circuit Size

Phase Watts

Hp.

Surge Prot.

UPS

Dedicated CircuitPower Source

Connection

Data Port

120 0Volts

US Intl.

Electrical 2/20/2013Revised

Power supply will accept any AC or DC input from 85-270V without adjustment.

A Log Cat

Unit of Issue

NSN

EA

Utilities A

1 2 3 4 5 6

Energy Star No

U7076 Page 10June 7, 2016

Equipment Data Sheet Report

Naval Facilities Engineering Command

U7076

Page 11June 7, 2016

Page 12June 7, 2016

Page 13June 7, 2016

Page 14June 7, 2016

Page 15June 7, 2016

A L2250LOG CAT

Hood, Fume, Bench

Hood, Fume, Bench Revised 5/27/2016

Includes Stainless Steel liner, and electrical package including two, 110 duplex interior receptacles, and T-5 flourescent light, and cup sink. Base cabinets include 2 36" ADA compliant solvent storage cabinets.

Kewaunee Scientific Corp(KEWAU)Manufacturer/ID

Supreme Air LV Fume Hood w/ 2 36" ADA Solvent Storage CabinetsProduct Number

Dimensions 72"w x 36.75"d x 85"h

( 183 cm w x 93 cm d x 216 cm h)

Clearance

Weight

10 Floor (fixed) - Major Building ImpactMounting

Notes Height dimensions include base cabinets Project Notes

Finish

DPrime Equipment

0Lead Time

Group IGroup Code

Acceptance Time 0

0Installation Time

HOODF Hood, Fume

HD Fume/Laminar Flow/Bio. HoodsBid Package

Class Code

Junction Box

Normal

N

Y

No

FLA

Circuit Size

Phase Watts

Hp.

Surge Prot.

UPS

Dedicated CircuitPower Source

Connection

Data Port

120 0

N

Volts

US Intl.

Electrical 8/5/2009Revised

Hood comes with two 120 volt AC 20 amp duplex receptacles, two-tube fluorescent light fixture (bulbs not included) with 20 amp light switch. No wiring for the electrical is included.

HVAC Revised 5/27/2016

AMBIENT CONDITIONS

Heat Gain (BTU/Hr.)

Room Temp(F)

Temp Range

Room Humidity

Humidity Range

Medical HoodExhaust Type

Connection

CFM

PD (In. W.C.)

Temp(F)

Vent Connect.

EXHAUST AIR

100 FPM at 18" or 66 FPM at 28" on high settting

SUPPLY AIR

Cleanliness

Connection

CFM

PD (In. W.C.)

Temp(F)

A Log Cat

Unit of Issue

NSN 6640

EA

Utilities I F E 1 2 3 4 5 6

Energy Star No

L2250 Page 1June 7, 2016

Equipment Data Sheet Report

Naval Facilities Engineering Command

L2250

A L2250MLOG CAT

Hood, Fume, Bench, 4'

Hood, Fume, Bench Revised 5/27/2016

Includes Stainless Steel liner, and electrical package including two, 110 duplex interior receptacles, and T-5 flourescent light, and cup sink. Base cabinets include 2 36" ADA compliant solvent storage cabinets.

Kewaunee Scientific Corp(KEWAU)Manufacturer/ID

Supreme Air LV Fume Hood w/ 1 48" ADA Solvent Storage CabinetProduct Number

Dimensions 48"w x 36.75"d x 85"h

( 183 cm w x 93 cm d x 216 cm h)

Clearance

Weight

10 Floor (fixed) - Major Building ImpactMounting

Notes Project Notes

Finish

DPrime Equipment

0Lead Time

Group IGroup Code

Acceptance Time 0

0Installation Time

HOODF Hood, Fume

HD Fume/Laminar Flow/Bio. HoodsBid Package

Class Code

Junction Box

Normal

N

Y

No

FLA

Circuit Size

Phase Watts

Hp.

Surge Prot.

UPS

Dedicated CircuitPower Source

Connection

Data Port

120 0

N

Volts

US Intl.

Electrical 8/5/2009Revised

Hood comes with two 120 volt AC 20 amp duplex receptacles, two-tube fluorescent light fixture (bulbs not included) with 20 amp light switch. No wiring for the electrical is included.

HVAC Revised 5/27/2016

AMBIENT CONDITIONS

Heat Gain (BTU/Hr.)

Room Temp(F)

Temp Range

Room Humidity

Humidity Range

Medical HoodExhaust Type

Connection

CFM

PD (In. W.C.)

Temp(F)

Vent Connect.

EXHAUST AIR

100 FPM at 18" or 66 FPM at 28" on high settting

SUPPLY AIR

Cleanliness

Connection

CFM

PD (In. W.C.)

Temp(F)

A Log Cat

Unit of Issue

NSN 6640

EA

Utilities I F E 1 2 3 4 5 6

Energy Star No

L2250M Page 1June 7, 2016

Equipment Data Sheet Report

Naval Facilities Engineering Command

L2250M

A L2337LOG CAT

Canopy, Hood, Fume, 6 foot

Canopy, Hood, Fume, 6 foot Revised 5/12/2010

Canopy Hood 6 foot

Labconco Corporation(LABCO)Manufacturer/ID

7099000 w/ 7069200

Dimensions 72"w x 30"d x 21"h

( 183 cm w x 76 cm d x 53 cm h)

Clearance

100 lbs. (45 Kgs.)Weight

13 Wall - Major Building ImpactMounting

Notes Verify Electrical Requirements Project Notes

Finish

DPrime Equipment

60Lead Time

Group IGroup Code

Acceptance Time 0

0Installation Time

HOODC Hood, Canopy Fume

HD Fume/Laminar Flow/Bio. HoodsBid Package

Class Code

Line Cord & Plug

Emergency

N

Y

No

FLA

Circuit Size

Phase Watts

Hp.

Surge Prot.

UPS

Dedicated CircuitPower Source

Connection

Data Port

N

Volts

US Intl.

Electrical 4/27/2005Revised

This hood can be directed to the facility's exhaust system or use an optional blower, ( HOODC33--E ) to direct the airflow to an outside exhaust. If the blower is used an on/off switch is required to be placed near the hood to activate the blower motor.

HVAC

AMBIENT CONDITIONS

Heat Gain (BTU/Hr.)

Room Temp(F)

Temp Range

Room Humidity

Humidity Range

Industrial General

2.45

Exhaust Type

Connection

CFM

PD (In. W.C.)

Temp(F)

Vent Connect.

EXHAUST AIR

Requires remotely located blower for operation.

SUPPLY AIR

Cleanliness

Connection

CFM

PD (In. W.C.)

Temp(F)

A Log Cat

Unit of Issue

NSN 6640

EA

Utilities F E

1 2 3 4 5 6

Energy Star No

L2337 Page 1June 7, 2016

Equipment Data Sheet Report

Naval Facilities Engineering Command

L2337

A L2337MLOG CAT

Canopy, Hood, Fume, 6 foot

Hood, Canopy, Exhaust, 5 Foot Revised 3/30/2016

Exhaust canopy used to exhaust steam, odors and heat.

Mott Manufacturing(MOTTM)Manufacturer/ID

CIS1360

Dimensions 60"w x 36"d x 18"h

( 152 cm w x 91 cm d x 46 cm h)

Clearance

140 lbs. (64 Kgs.)Weight

13 Wall - Major Building ImpactMounting

Notes Verify Electrical Requirements for blower. Project Notes

Finish

DPrime Equipment

60Lead Time

Group IGroup Code

Acceptance Time 0

0Installation Time

HOODC Hood, Canopy Fume

HD Fume/Laminar Flow/Bio. HoodsBid Package

Class Code

Junction Box

Normal

N

Y

No

FLA

Circuit Size

Phase Watts

Hp.

Surge Prot.

UPS

Dedicated CircuitPower Source

Connection

Data Port

N

Volts

US Intl.

Electrical 4/27/2005Revised

HVAC

AMBIENT CONDITIONS

Heat Gain (BTU/Hr.)

Room Temp(F)

Temp Range

Room Humidity

Humidity Range

Industrial General

2.45

Exhaust Type

Connection

CFM

PD (In. W.C.)

Temp(F)

Vent Connect.

EXHAUST AIR

Requires remotely located blower for operation.

SUPPLY AIR

Cleanliness

Connection

CFM

PD (In. W.C.)

Temp(F)

A Log Cat

Unit of Issue

NSN 6640

EA

Utilities F E

1 2 3 4 5 6

Energy Star No

L2337M Page 1June 7, 2016

Equipment Data Sheet Report

Naval Facilities Engineering Command

L2337M

A M0041LOG CAT

Booth, Audio, Double Wall, Suite

Booth, Audio, Double Wall, Suite Revised 4/22/2016

Double Wall Control / Double Wall Exam Suite.

ETS-Lindgren(LINDG)Manufacturer/ID

Model

Project Specific

RS-240-Project Specific

Product Number

Dimensions see vendor drawings

Clearance

14550 lbs. (6606 Kgs.)Weight

10 Floor (fixed) - Major Building ImpactMounting

Notes Project Specific Project Notes

Finish

DPrime Equipment

90Lead Time

Group IGroup Code

Acceptance Time 0

0Installation Time

BOOTH Booth, Audiometric

AU Audiology/ENG/Speech TherapyBid Package

Class Code

Line Cord & Plug

Normal

N

Y

Yes

FLA

Circuit Size

Phase Watts

Hp.

Surge Prot.

UPS

Dedicated CircuitPower Source

Connection

Data Port

N

Volts

US Intl.

Electrical 2/24/2016Revised

Minimal power required. Fan (15 watts) and lights.

Connection is made via a standard 20' power cord located on the roof of the enclosure.

HVAC Revised 2/9/2011

AMBIENT CONDITIONS

Heat Gain (BTU/Hr.)

Room Temp(F)

Temp Range

Room Humidity

Humidity Range

Exhaust Type

Connection

CFM

PD (In. W.C.)

Temp(F)

Vent Connect.

EXHAUST AIR

Booth is equiped with a variable speed fan that circulates ambient air throughout booth at a rate of up to one complete air change every two minutes.

As an option, the booth may be privided with a duct collar for connection to the building HVAC system (by others). Two duct collars for 6" DIA flexible duct on the supply silencer and the exhaust silencer. The amount of air should be determined by Engineer, not to exceed 200 CFM. Typically, Manufacturer recommends airflow of 26 CFM of conditioned air to provide one complete air exchange every 4 to 6 minutes.

Approximate pressure drop at 26 CFM is 0.4" water.

**Please alert Equipment Planner if this option is desired.**

Host ventilation system to be connected to booth should be designed for a NC-30 to 25 environment.

SUPPLY AIR

Cleanliness

Connection

CFM

PD (In. W.C.)

Temp(F)

A Log Cat

Unit of Issue

NSN 6515

EA

Utilities F

1 2 3 4 5 6

Energy Star No

M0041 Page 1June 27, 2017

Equipment Data Sheet Report

Naval Facilities Engineering Command

WRNMMC P114 Medical Center Addition/Alteration

M0041

All doors shall swing into corridor for ADA accessibility.

Page 2June 27, 2017

Page 3June 27, 2017

Page 4June 27, 2017 joswald Rectangle

A M0041MLOG CAT

Booth, Audio Double Wall, Suite Revised 2/24/2016

Double Wall Control / Double Wall Exam Suite.

ETS-Lindgren(LINDG)Manufacturer/ID

RS-240-Project Specific

Dimensions see vendor drawings

Clearance

14550 lbs. (6606 Kgs.)Weight

10 Floor (fixed) - Major Building ImpactMounting

Notes Project Specific Project Notes

Finish

DPrime Equipment

90Lead Time

Group IGroup Code

Acceptance Time 0

0Installation Time

BOOTH Booth, Audiometric

AU Audiology/ENG/Speech TherapyBid Package

Class Code

Line Cord & Plug

Normal

N

Y

Yes

FLA

Circuit Size

Phase Watts

Hp.

Surge Prot.

UPS

Dedicated CircuitPower Source

Connection

Data Port

N

Volts

US Intl.

Electrical 2/24/2016Revised

Minimal power required. Fan (15 watts) and lights.

Connection is made via a standard 20' power cord located on the roof of the enclosure.

HVAC Revised 2/9/2011

AMBIENT CONDITIONS

Heat Gain (BTU/Hr.)

Room Temp(F)

Temp Range

Room Humidity

Humidity Range

Exhaust Type

Connection

CFM

PD (In. W.C.)

Temp(F)

Vent Connect.

EXHAUST AIR

Booth is equiped with a variable speed fan that circulates ambient air throughout booth at a rate of up to one complete air change every two minutes.

As an option, the booth may be privided with a duct collar for connection to the building HVAC system (by others). Two duct collars for 6" DIA flexible duct on the supply silencer and the exhaust silencer. The amount of air should be determined by Engineer, not to exceed 200 CFM. Typically, Manufacturer recommends airflow of 26 CFM of conditioned air to provide one complete air exchange every 4 to 6 minutes.

Approximate pressure drop at 26 CFM is 0.4" water.

**Please alert Equipment Planner if this option is desired.**

Host ventilation system to be connected to booth should be designed for a NC-30 to 25 environment.

SUPPLY AIR

Cleanliness

Connection

CFM

PD (In. W.C.)

Temp(F)

A Log Cat

Unit of Issue

NSN 6515

EA

Utilities F

1 2 3 4 5 6

Energy Star No

M0041M Page 1June 27, 2017

Equipment Data Sheet Report

Naval Facilities Engineering Command

WRNMMC P114 Medical Center Addition/Alteration

M0041M

All doors shall swing into corridor for ADA accessibility.

Page 3June 27, 2017

Page 4June 27, 2017

A M0050LOG CAT

Booth, Audio, Dbl Wall, Definitive Test, 1 Person

Booth, Audio, Dbl Wall, Definitive Test, 1 Person Revised 4/22/2016

Double walled sound room. Model includes door window, and ventilation system

ETS-Lindgren(LINDG)Manufacturer/ID

Model RE-243

Product Number

Dimensions see vendor drawings

Clearance

2240 lbs. (1017 Kgs.)Weight

5 Floor (fixed) - Minor Building ImpactMounting

Notes Project Specific Project Notes

Finish

DPrime Equipment

90Lead Time

Group IGroup Code

Acceptance Time 0

0Installation Time

BOOTH Booth, Audiometric

XX Other or UnassignedBid Package

Class Code

Junction Box

Normal

N

N

Yes

FLA

Circuit Size

Phase Watts

Hp.

Surge Prot.

UPS

Dedicated CircuitPower Source

Connection

Data Port

N

Volts

US Intl.

Electrical 11/5/2015Revised

A Log Cat

Unit of Issue

NSN 6515000659

600EA

Utilities F

1 2 3 4 5 6

Energy Star No

M0050 Page 1June 27, 2017

Equipment Data Sheet Report

Naval Facilities Engineering Command

M0050

A M0050MLOG CAT

Booth, Audio Double Wall, Single Person Revised 4/22/2016

Double walled sound room. Model includes door window, 3 ventilation systems, 7 acoustiacl foam sheets, 2 fluorecent lights, 6 cable passages and a wireless switch.

ETS-Lindgren(LINDG)Manufacturer/ID

Model RE-243

Product Number

Dimensions see vendor drawings

Clearance

2240 lbs. (1017 Kgs.)Weight

5 Floor (fixed) - Minor Building ImpactMounting

Notes Project Specific Project Notes

Finish

DPrime Equipment

120Lead Time

Group IGroup Code

Acceptance Time 0

0Installation Time

BOOTH Booth, Audiometric

AU Audiology/ENG/Speech TherapyBid Package

Class Code

Junction Box

Normal

N

N

Yes

FLA

Circuit Size

Phase Watts

Hp.

Surge Prot.

UPS

Dedicated CircuitPower Source

Connection

Data Port

N

Volts

US Intl.

Electrical 4/22/2016Revised

A Log Cat

Unit of Issue

NSN 6515000659

600EA

Utilities F

1 2 3 4 5 6

Energy Star No

M0050M Page 1June 27, 2017

Equipment Data Sheet Report

Naval Facilities Engineering Command

M0050M

A M0400LOG CAT

Screen, Projection, 144x144, Remote Control

M0400-02.pdf

A M2025LOG CAT

Rack, Storage, Cylinder, Gas

Rack, Storage, Cylinder, Gas Revised 4/8/2015

Enclosed type with hinged, lockable front gates and stationary top plates. Four-cylinder capacity.

Anthony Products(ANTHO)Manufacturer/ID

MCR-400

Dimensions 28.5"w x 20"d x 64"h

( 72 cm w x 51 cm d x 163 cm h)

Clearance

135 lbs. (61 Kgs.)Weight

3 Movable or Above Floor - No Building ImpactMounting

Notes Project Notes

Finish

DPrime Equipment

30Lead Time

Group IIIGroup Code

Acceptance Time 0

0Installation Time

RACKG Rack, Compressed Gas Cylinder Storage

GS Gas Services Equip.Bid Package

Class Code

A Log Cat

Unit of Issue

NSN 7125

EA

Utilities 1 2 3 4 5 6

Energy Star No

M2025 Page 1June 7, 2016

Equipment Data Sheet Report

Naval Facilities Engineering Command

M2025

A M3105LOG CAT

Cabinet, Warming, F/S, 1 Heated Compartment, Elect

Cabinet, Warming, F/S, 1 Heated Compartment, Elect Revised 3/1/2016

Single, countertop warming cabinet. 24" deep compartment. Features temperature range of 90 to 160 degrees, stainless steel finish, single door with universal door swing, control panel with adjustable control knob, digital temperature indicator, visual over-temperature indicator, and audible over-temperature alert system.

Steris Corporation(STERI)Manufacturer/ID

DJ03-132-013

Dimensions 30"w x 26.5"d x 24.75"h

(76 cm w x 67 cm d x 63 cm h)

Clearance

250 lbs. (114 Kgs.)Weight

13 Wall - Major Building ImpactMounting

Notes Project Notes

Finish

DPrime Equipment

90Lead Time

Group IIGroup Code

Acceptance Time 0

0Installation Time

WARMB Warmer, Blanket

NC Nursing Care AppliancesBid Package

Class Code

6.8

Line Cord & Plug

Normal

N

N

No

FLA

Circuit Size

Phase Watts

Hp.

Surge Prot.

UPS

Dedicated CircuitPower Source

Connection

Data Port

N

Volts

US Intl.

Electrical 10/26/2015Revised

HVAC Revised 8/18/2000

AMBIENT CONDITIONS

Heat Gain (BTU/Hr.)

Room Temp(F)

Temp Range

Room Humidity

Humidity Range

Exhaust Type

Connection

CFM

PD (In. W.C.)

Temp(F)

Vent Connect.

EXHAUST AIR

Engineering data assumes extended (long term) use..

SUPPLY AIR

Cleanliness

Connection

CFM

PD (In. W.C.)

Temp(F)

A Log Cat

Unit of Issue

NSN 6530

EA

Utilities F

1 2 3 4 5 6

Energy Star No

M3105 Page 1June 7, 2016

Equipment Data Sheet Report

Naval Facilities Engineering Command

M3105

A M3110LOG CAT

Cabinet, Warming, F/S, 2 Heated Compartment, Elect

Cabinet, Warming, F/S, 2 Heated Compartment, Elect Revised 10/8/2012

Blanket/solution warmer - dual compartment with two stainless-steel shelves. The upper holds 20 square 2-liter flasks; the lower holds 60 square 2-liter flasks.Temperature range: 90-160 deg F (33-72 deg C). Upper and lower chamber temperatures are individually controlled. Free standing.

Steris Corporation(STERI)Manufacturer/ID

Model DJ06-012-133 w/ Glass Door

Product Number

Dimensions 30"w x 26.5"d x 74.75"h

(762mm w x 673mm d x 1899mm h)

Clearance

740 lbs. (335 Kgs.)Weight

6 Movable or Above Floor - Minor Building ImpactMounting

Notes Project Notes

Stainless steel; glass door.Finish

DPrime Equipment

90Lead Time

Group IIGroup Code

Acceptance Time 0

0Installation Time

WARMB Warmer, Blanket

NC Nursing Care AppliancesBid Package

Class Code

13.7 Line Cord & Plug

Normal

N

Y

No

FLA

Circuit Size

Phase Watts

Hp.

Surge Prot.

UPS

Dedicated CircuitPower Source

Connection

Data Port

N

Volts

US Intl.

Electrical 5/23/2013Revised

A Log Cat

Unit of Issue

NSN 6530

EA

Utilities F

1 2 3 4 5 6

Energy Star No

M3110 Page 1June 7, 2016

Equipment Data Sheet Report

Naval Facilities Engineering Command

M3110

A M5016LOG CAT

Desk, Refraction w/console, w/o Sink

Desk, Refraction w/console, w/o Sink Revised 4/22/2016

With writing surface, knee space, four drawers, large trial lens drawer, and control panel. Automatic or manual panel controls room lighting, slit lamp, and fixation lights. Three instrument wells for ophthalmoscopes. Optional indirect ophthalmoscope control. Includes two electrical outlets.

Lombart Instruments(LOMBA)Manufacturer/ID

Omega without Sink

Dimensions 74"w x 18.5"d x 42.5"h

( 188 cm w x 47 cm d x 108 cm h)

Clearance

Weight

10 Floor (fixed) - Major Building ImpactMounting

Notes Project Notes

Finish

DPrime Equipment

60Lead Time

Group IIGroup Code

Acceptance Time 0

0Installation Time

REFRD Ophthalmology Refraction Desk

OP Ophthalmology EquipmentBid Package

Class Code

Junction Box

Normal

N

N

No

FLA

Circuit Size

Phase Watts

Hp.

Surge Prot.

UPS

Dedicated CircuitPower Source

Connection

Data Port

120 0

N

Volts

US Intl.

Electrical 2/19/2013Revised

Refer to Installation instructions for additional requirements.

A Log Cat

Unit of Issue

NSN 6540

EA

Utilities F

1 2 3 4 5 6

Energy Star No

M5016 Page 1June 7, 2016

Equipment Data Sheet Report

Naval Facilities Engineering Command

M5016

A M7405LOG CAT

Light, Exam, Ceiling Mounted

Light, Exam, Ceiling Mounted Revised 10/19/2015

Ceiling mounted Exam/Procedure light. Features 40,000 lux at 1 meter, color rendering fixed at 95. Closed light head, LED bulb provides 35,000 hours of light. Ergodisk spring arm with 73.5" swivel range. Composed of 80% recyclable material. Ceiling mount kit includes anchor plate and ceiling cover. 260mm Suspension tube included.

Maquet, Inc.(MAQUE)Manufacturer/ID

Lucea LED 40

Dimensions

Clearance

Weight

14 Ceiling - Major Building ImpactMounting

Notes Project Notes

Finish

DPrime Equipment

90Lead Time

Group IGroup Code

Acceptance Time 0

0Installation Time

LIGES Light, Examination/Surgical

SL Medical LightsBid Package

Class Code

Junction Box

Emergency

N

Y

No

FLA

Circuit Size

Phase Watts

Hp.

Surge Prot.

UPS

Dedicated CircuitPower Source

Connection

Data Port

N

Volts

US Intl.

Electrical 10/19/2015Revised

HVAC Revised 1/5/2003

AMBIENT CONDITIONS

Heat Gain (BTU/Hr.)

Room Temp(F)

Temp Range

Room Humidity

Humidity Range

Exhaust Type

Connection

CFM

PD (In. W.C.)

Temp(F)

Vent Connect.

EXHAUST AIR

Engineering data assumes extended (long term) use of light.

SUPPLY AIR

Cleanliness

Connection

CFM

PD (In. W.C.)

Temp(F)

A Log Cat

Unit of Issue

NSN 6530

EA

Utilities F

1 2 3 4 5 6

Energy Star No

M7405 Page 1June 7, 2016

Equipment Data Sheet Report

Naval Facilities Engineering Command

M7405

A M7445LOG CAT

Light, Surgical, Dual, LDR/LDRP, In-Ceiling

Light, Surgical, Dual, LDR/LDRP, In-Ceiling Revised 4/22/2016

Two ceiling recessed lights appropriate for focused areas such as birthing and minor surgery. 4000 ft. candles and 5 intensity levels per light head; dichroic coated reflectors. Recessed wall control (7"w x 7-3/8"h) houses intensity and postioning controls.

Steris Corporation(STERI)Manufacturer/ID

LD202; AS70-060-000-060-030

Dimensions 22"w x 22"d x 12"h each

(56 cm w x 56 cm d x 30 cm h each)

Clearance

55 lbs. (25 Kgs.)Weight

14 Ceiling - Major Building ImpactMounting

Notes 2 separate recessing fixtures with 1 dual wall controller.

Project Notes

Finish

DPrime Equipment

90Lead Time

Group IGroup Code

Acceptance Time 0

0Installation Time

LIGPR Light, Minor Procedure

SL Medical LightsBid Package

Class Code

4.6 Junction Box

Normal

N

N

2.5

No

FLA

Circuit Size

Phase Watts

Hp.

Surge Prot.

UPS

Dedicated CircuitPower Source

Connection

Data Port

120 240

N

Volts

US Intl.

60 50 Hz.

Electrical 10/26/2015Revised

2 separate fixtures @ 2.3 amps each. Contractor to provide conduit for 24V control cabling between fixtures and wall box.

A Log Cat

Unit of Issue

NSN 6530

EA

Utilities A

1 2 3 4 5 6

Energy Star No

M7445 Page 1June 7, 2016

Equipment Data Sheet Report

Naval Facilities Engineering Command

M7445

Page 10June 7, 2016

Page 11June 7, 2016

Page 12June 7, 2016

Page 13June 7, 2016

Page 14June 7, 2016

Page 15June 7, 2016

Page 16June 7, 2016

Page 17June 7, 2016

Page 18June 7, 2016

Page 19June 7, 2016

A M7470LOG CAT

Light, Surgical, Ceiling, Single, Small

Light, Surgical, Ceiling, Single, Small Revised 4/20/2016

Ceiling mounted, single arm surgical light. Lighthead is 17.7" diameter with 108 LED's, Single Fork: for finished ceilings less than 10 ft.

Features 100,000 illumination, 95 CRI, 3,800K color temperature. 6.7" light pattern with 39.4" volume depth. >40,000 hour bulb life.

PWD30SF

Dimensions see installation drawings

(see installation drawings)

Clearance

91 lbs. (41 Kgs.)Weight

14 Ceiling - Major Building ImpactMounting

Notes Project Notes

Finish

DPrime Equipment

90Lead Time

Group IGroup Code

Acceptance Time 0

0Installation Time

LIGSU Light, Surgical

SL Medical LightsBid Package

Class Code

2.3

Junction Box

Emergency

N

Y

No

FLA

Circuit Size

Phase Watts

Hp.

Surge Prot.

UPS

Dedicated CircuitPower Source

Connection

Data Port

N

Volts

US Intl.

Electrical 4/20/2016Revised

E Log Cat

Unit of Issue

NSN 6530

EA

Utilities F

1 2 3 4 5 6

Energy Star No

M7470 Page 1June 7, 2016

Equipment Data Sheet Report

Naval Facilities Engineering Command

M7470

A M7480LOG CAT

Light, Surgical, Ceiling Mounted, Single, Medium

Light, Surgical, Ceiling Mounted, Single, Medium Revised 4/22/2016

Tandem mount dual arm 500 LED single surgical light

Maquet, Inc.(MAQUE)Manufacturer/ID

Model

PROJECT SPECIFIC TO WALTER REE

PWD50DF

Product Number

Dimensions see installation drawings

(see installation drawings)

Clearance

194 lbs. (88 Kgs.)Weight

14 Ceiling - Major Building ImpactMounting

Notes Vendor Drawing 'G' Project Notes

Finish

DPrime Equipment

90Lead Time

Group IGroup Code

Acceptance Time 0

0Installation Time

LIGSU Light, Surgical

SL Medical LightsBid Package

Class Code

4.5

Junction Box

Emergency

N

Y

Yes

FLA

Circuit Size

Phase Watts

Hp.

Surge Prot.

UPS

Dedicated CircuitPower Source

Connection

Data Port

Volts

US Intl.

Electrical 3/7/2011Revised

A Log Cat

Unit of Issue

NSN 6530

EA

Utilities F

1 2 3 4 5 6

Energy Star No

M7480 Page 1July 31, 2017

Equipment Data Sheet Report

Naval Facilities Engineering Command

M7480

Page 2July 31, 2017

Page 3July 31, 2017

Page 4July 31, 2017

Page 5July 31, 2017

Page 6July 31, 2017

Page 7July 31, 2017

Page 8July 31, 2017

Page 9July 31, 2017

Page 10July 31, 2017

Page 11July 31, 2017

Page 12July 31, 2017

Page 13July 31, 2017

Page 14July 31, 2017

Page 15July 31, 2017

Page 16July 31, 2017

Page 17July 31, 2017

Page 18July 31, 2017

Page 19July 31, 2017

Page 20July 31, 2017

Page 21July 31, 2017

A M7490LOG CAT

Light, Surg, Ceiling Mtd, Dual, Unequal Dia Heads

Light, Surg, Ceiling Mtd, Dual, Unequal Dia Heads Revised 3/30/2016

Dual arm LED surgical lights, ceiling mounted. 1-LED 700mm , 1-LED 500mm, single fork suspension.

PWD75SF

Dimensions see installation drawings

(see installation drawings)

Clearance

194 lbs. (88 Kgs.)Weight

14 Ceiling - Major Building ImpactMounting

Notes Vendor Drawing 'K' Project Notes

Finish

DPrime Equipment

0Lead Time

Group IGroup Code

Acceptance Time 0

0Installation Time

LIGSU Light, Surgical

SL Medical LightsBid Package

Class Code

4.5

Junction Box

Emergency

N

Y

No

FLA

Circuit Size

Phase Watts

Hp.

Surge Prot.

UPS

Dedicated CircuitPower Source

Connection

Data Port

N

Volts

US Intl.

Electrical 10/26/2015Revised

A Log Cat

Unit of Issue

NSN 6530

EA

Utilities F

1 2 3 4 5 6

Energy Star No

M7490 Page 1July 31, 2017

Equipment Data Sheet Report

Naval Facilities Engineering Command

M7490

Page 2July 31, 2017

Page 3July 31, 2017

Page 4July 31, 2017

Page 5July 31, 2017

Page 6July 31, 2017

Page 7July 31, 2017

Page 8July 31, 2017

Page 9July 31, 2017

Page 10July 31, 2017

Page 11July 31, 2017

Page 12July 31, 2017

Page 13July 31, 2017

Page 14July 31, 2017

Page 15July 31, 2017

Page 16July 31, 2017

Page 17July 31, 2017

A P1060LOG CAT

Tub/Shower, Combination, Pediatric

SALEM 14™RECESS BATH

ENAMELED STEEL

SALEM RECESS BATH

❏ 0155.017 Right hand outlet

❏ 0153.015 Left hand outlet

Product Features:

• Acid resisting, heavy gauge, enameled steel one-piece recess bath

• Integral apron

• End drain outlet

• Slip-resistant surface

• Straight tiling bead

• Fully-bonded support pad

Nominal Dimensions: 1524 x 762 x 356mm (60" x 30" x 14")

Bathing Well Dimensions: 1346 x 610 x 337mm (53" x 24" x 13-1/4")

Compliance Certifications - Meets or Exceeds the Following Specifications:

• ASME A112.19.4 for Enameled Steel Plumbing

Fixtures

• ASTM F-462 for Slip-resistant Bathing Facilities

To Be Specified

❏ Color:

❏ Bath Faucet*:

❏ Faucet Finish:

❏ Drain:

© 2000 American Standard Inc.

SPS 0153/0155

* See faucet section for additional models available

NOTES:

0153.015 LEFT HAND OUTLET (SHOWN).

0155.017 RIGHT HAND OUTLET (REVERSE DIMENSIONS).

REFER TO INSTALLATION INSTRUCTIONS SUPPLIED WITH BATH FOR ADDITIONAL

INFORMATION.

SHOWN WITH POP-UP C.D. & O.

FITTINGS NOT INCLUDED AND MUST BE ORDERED SEPARATELY.

CONCEALED PIPING NOT INCLUDED.

IMPORTANT: Dimensions of fixtures are nominal and may vary within the range of tolerances established by ANSI Standard A112.19.

These measurements are subject to change or cancellation. No responsibility is assumed for use of superseded or voided leaflet.

762mm (30)

1524mm (60)

19mm (3/4)

19mm (3/4)

365mm (14-3/8)

197mm (7-3/4)

48mm (1-7/8)

89mm (3-1/2)

13mm (1/2)

117mm (4-5/8)

305mm (12)

102 (4)

64mm (2-1/2)

356mm (14)

229 x 305mm (9x12")

CUTOUT

FINISHED

WALL

1-1/2 N.P.T.M.

THREADS

1-1/2 O.D.

TAILPIECE

C/L OF

VALVES

C/L OF

SPOUT

PLUMBER NOTE:

PROVIDE SUITABLE FULL LENGTH

SUPPORT AT THIS POINT.

C/L OF SHOWER ARM

OPTIONAL TO FINISHED

FLOOR (USALLY

BETWEEN 1651 to 1981mm ( 65" & 78')

C/L OF SUPPLIES

SEE FITTINGS

SPECS FOR

DIMENSIONS

FINISHED

WALL

ROUGH

FLOOR

FINISHED

WALL

C/L OF DRAIN

SUMP

PAD

356mm (14)

38mm (1-1/2)

C/L OF

DRAIN

BV-056

Revised 11/00

DescriptionModel # Finishes

WALL MOUNT TUB SPOUTS

Roughing-In Dimensions

BATH/SHOWER ACCESSORIES E-6

8888.033 DELUXE 5" BRASS TUB

SPOUT

.002

.020

.099

.295

Polished Chrome White Polished Brass (PVD) Satin (PVD)

DELUXE 5-1/8" BRASS

DIVERTER TUB SPOUT

8888.022

STANDARD 4" DIVERTER

TUB SPOUT

8888.025

SLIP-ON 4" DIVERTER

TUB SPOUT

.002

.020

.099

Polished Chrome White Polished Brass (PVD)

8888.026

.002

.020

.099

.221

.295

.297

.299

Polished Chrome White Polished Brass (PVD) Satin (PVD)/Chrome mix Satin (PVD) Satin w/Brass mix (PVD) Pol Chrome/Brass (PVD) mix

JASMINE BRASS TUB

SPOUT

8888.041 .002 .020 .062 .068 .099 .221 .295 .297 .299

Polished Chrome White Black Nickel/Brass mix (PVD) Blackened Bronze (PVD) Polished Brass (PVD) Satin (PVD)/Pol. Chrome mix Satin (PVD) Satin w/Brass mix (PVD) Pol. Chrome/Brass (PVD) mix

• Metal Construction

• For 1/2" Copper Water Tube

• Metal Construction

• 1/2" IPS Connection

• All Brass Construction

• 1/2" IPS Connection

• All Brass Construction

• 1/2" IPS Connection

• All Brass Construction

• 1/2" IPS Connection

159mm (6-1/4)

REF.

1/2" I.P.S.

127mm (5)

REF

1/2" I.P.S.

127mm (5)

REF.

1/2" I.P.S.

32mm(1-1/4)

DIA HOLE

121mm (4-3/4)

REF.

1/2"SPOUT

NIPPLE

.002

.020

.099

Polished Chrome White Polished Brass (PVD)

32mm(1-1/4)

DIA HOLE

159mm (6-1/4)

REF.

1/2" I.P.S.

32mm(1-1/4)

DIA HOLE

32mm(1-1/4)

DIA HOLE

32mm(1-1/4)

DIA HOLE

32mm(1-1/4)

DIA HOLE

P r o d u c t n am e s l i s t e d h e r e i n a r e t r a d em a r k s o f A m e r i c a n S t a n d a r d I n c .

© Am e r i c a n S t a n d a r d I n c . 2 0 0 2

JASMINE BRASS

DIVERTER TUB SPOUT

8888.044

•<1/2" IPS Connection

.002

.020

.062

.068

.099

.221

.295

.297

.299

Polished Chrome White Black Nickel/Brass mix (PVD) Blackened Bronze (PVD) Polished Brass (PVD) Satin (PVD)/Pol.Chrome mix Satin (PVD) Satin/Brass mixage (PVD) Pol. Chrome/Brass (PVD) mix

• For 1/2" Copper Pipe

DELUXE 4" DIVERTER

TUB SPOUT

8888.055

SLIP-ON NON DIVERTER

TUB SPOUT

8888.056

.002

.099

.221

.285

.287

.295

.297

.299

Polished Chrome Polished Brass (PVD) Satin (PVD)/Pol.Chrome mix.

Velvet Velvet/Brass (PVD) mix.

Satin (PVD) Satin/Brass mix. (PVD) Pol. Chrome/Brass (PVD) mix.

.002

.099

.221

.285

.287

.295

.297

.299

Polished Chrome Polished Brass (PVD) Satin (PVD)/Pol.Chrome mix.

Velvet Velvet/Brass (PVD) mix.

Satin (PVD) Satin/Brass mix. (PVD) Pol. Chrome/Brass (PVD) mix.

• 1/2" IPS Connection

130mm (5-1/8)

REF.

1/2" COPPER

32mm(1-1/4)

DIA HOLE

130mm (5-1/8)

REF.

1/2" COPPER

PRODUCT FEATURES:

VALVE: Cast Brass Valve Body: Durable.

Ceramic Disc Valve Cartridge: Assures a lifetime of drip-free performance.

Colony Pressure Balancing Valve Cartridge:

Maintains constant output temperature in response to changes in hot and cold supply pressure.

Back-to-Back Capability: Hot and cold can be reversed quickly and easily.

Adjustable Hot Limit Safety Stop: Limits the amount of hot water allowed to mix with cold. Reduces the risk of accidental scalding.

Integral Plaster Guard and Mounting Plate: Protects valve during installation and serves as a mounting plate for thin-wall installations.

PERSONAL SHOWER:

Lightweight, Ergonomic Design: For a sure grip even with wet, soapy hands.

SLIDE BAR: Simple Height Adjustment: Allows positioning of the personal shower anywhere along the bar.

MODEL NUMBER:

1662.601 Shower System Kit

Includes:

SUGGESTED SPECIFICATION:

Shower system shall feature a wall supply with 1/2" NPT female inlets, 1/2" NPSM male outlet, 59" hose, personal shower and a 25" Standard Slide Bar. Pressure Balance valve shall feature a cast brass body. Shall feature ceramic disc valve cartridge which is capable of back-to-back installation. Shall also feature hot limit safety stop. Fitting shall be American Standard Model # 1662.602.002.

GENERAL DESCRIPTION:

Complete personal shower system includes: a Colony pressure balance valve, a wall supply with 1/2" NPT female inlet and 1/2" NPSM male outlet; a 59" (1500mm) shower hose; a "Fixed" personal shower; and a 25" Slide Bar. Valve features a cast brass body, washerless ceramic disc valve cartridge with back-to-back capability and hot limit safety stop.

Cycles from off to hot through cold. Exclusive Colony pressure balancing cartridge maintains constant output temperature in response to changes in relative hot and cold supply pressure. One-half inch direct sweat inlets and outlets.

With screwdriver stops. Durable metal handle provides easy, certain control for all users. Rough-in plaster guard designed for use as thin-wall mounting adaptor. Fixed handshower with

2.5 gpm/9.5L/min. flow restrictor. Slide bar features an adjustable shower holder which can be set at any height or position along the bar and angle up to 45˚.

SHOWER SYSTEM KIT

32mm (1-1/4)13mm

(1/2)

1/2" NPT

1829mm (72) to 1990mm (78)

(OPTIONAL)TO FINISHED FLOOR

RUBBER GASKET

FINISHED WALL

1/2" NPSM HOSE

CONNECTION

1371SS.240

1660.505 8888.035 8888.037 1660.225 1660.400

• Colony Pressure Balance Valve w/stops

• Fixed Handshower

• Hose

• Wall Supply

• Standard Slide Bar

• In-line Vacuum Breaker

53mm (2-1/16)

146mm (5-3/4)

67mm (2-5/8)

1/2" NPSM

5/8 O.D. FOR 1/2 NOM.

COPPER SWEAT

ALL CONNECTIONS

51mm (2)

INLETS

149mm (5-7/8)

51mm (2)

SWEAT

INLETS

w/STOPS

"SEE ILLUSTRATION

BELOW"

6"

6-3/4"

C17© American Standard Inc. 2003

A P1965LOG CAT

Eyewash, Eye/Face, Sink Mounted, Hands-free

NMCGAFFI

Typewritten Text

EW-1

A P2000LOG CAT

Eyewash, Wall Mounted, Hands-Free

Eyewashes

Guardian Equipment

1140 N North Branch St

Chicago, IL 60642

312 447 8100 telephone

312 447 8101 facsimile gesafety.com

ETL Listed 101496.

Units have been tested to and comply with

ANSI Z358.1-2014.

Listed 8116. Units have been tested to and comply with

ANSI Z358.1-2014 and the Uniform Plumbing Code.

G1814 Eyewash, Wall Mounted, Stainless Steel Bowl

Application: Eyewash for wall mounting. Two GS-Plus™ spray-type spray heads deliver a flood of water for rinsing eyes.

Spray Head Assembly: Two GS-Plus™ spray heads. Each head has a “flip top” dust cover, internal flow control and filter to remove impurities from the water flow.

Valve: 1/2" IPS chrome plated brass stay-open ball valve. Valve is US-made with chrome plated brass ball and Teflon® seals.

Bowl: 11-1/2" diameter stainless steel.

Mounting: Heavy duty cast aluminum wall bracket with corrosion resistant powder coated finish.

Supply: 1/2" NPT female inlet.

Waste: 1-1/4" NPT female outlet.

Sign: ANSI-compliant identification sign.

Quality Assurance: Unit is completely assembled and water tested prior to shipment.

Available Options

BC Stainless steel bowl cover. Cover protects unit against contaminants. Cover is automatically raised when unit is activated.

DC Stainless steel dust cover for each spray head.

HS Auxiliary hand-held drench hose for rinsing eyes, face or body.

SC Self-closing ball valve. Note: Eyewashes with self-closing valves do not comply with ANSI Z358.1-2014.

T Chrome plated brass tailpiece and trap with 1-1/2" IPS waste connection.

TP 1-1/2" OD chrome plated brass tailpiece.

TMV G3600LF thermostatic mixing valve precisely blends hot and cold water to deliver warm (tepid) water as required by ANSI Z358.1-2014. Refer to “Tempering Units” section for complete technical and product selection information.

NMCGAFFI

Typewritten Text

EW-2

Eyewashes this space for architect/engineer approval

Due to continuing product improvement, the information contained in this document is subject to change without notice. All dimensions are ± 1/4" (6mm).

Sign Included

Guardian Equipment

1140 N North Branch St

Chicago, IL 60642

312 447 8100 telephone

312 447 8101 facsimile gesafety.com rev. 0115

ETL Listed 101496.

Units have been tested to and comply with

ANSI Z358.1-2014.

Listed 8116. Units have been tested to and comply with

ANSI Z358.1-2014 and the Uniform Plumbing Code.

G1814 Eyewash, Wall Mounted, Stainless Steel Bowl

5 1/4"

(162mm)

6 3/8"

8"

(117mm)

4 5/8"

(203mm)

6 7/8"

(175mm)

BRASS STAY-OPEN BALL VALVE

1/2" IPS CHROME PLATED

FEMALE OUTLET

1-1/4" NPT

6 1/2"

(165mm)

4 7/8"

STAINLESS STEEL BOWL

(133mm)

(124mm)

POWDER COATED CAST

ALUMINUM FLAG HANDLE

(2) GS-PLUS

SPRAY HEADS

4 7/8"

(124mm)

(3449mm)

1/2" NPT

FEMALE INLET

NOTES:

1. EACH GS-PLUS SPRAY HEAD HAS A

"FLIP-TOP" DUST COVER, INTERNAL FLOW

CONTROL AND FILTER TO REMOVE IMPURITIES

FROM THE WATER FLOW.

2. UNIT SHOULD BE INSTALLED SO SPRAY HEADS

ARE 33"-45" ABOVE FINISHED FLOOR.

DETAIL A

MOUNTING BRACKET

3-1/4"

(83mm)

3-1/4"

(83mm)

(3) Ø3/8"

MOUNTING

HOLES

(SEE DETAIL A)

Ø11 1/8"

(283mm)

13 3/4"

POWDER COATED

CAST ALUMINUM

WALL BRACKET

A P2450LOG CAT

Valve, Mixing, Thermostatic

Submittal Data Sheet S-176F January 2012

EMERGENCY

MIXING

Exposed Assembly for Eye/Face Wash Units 2 10 GPM (7 6 38 l/min ) flow rate

VALVES

2 - 10 GPM (7.6 - 38 l/min.) flow rate up to 45 PSI system pressure drop

TA-300

ASSE 1071 Certified

°C °F

__TA-300

EMERGENCY WATER MIXING VALVE

DURA-trol® solid bimetal thermostat directly linked to valve porting to control the intake of hot and cold water and t f l t t d fl t ticompensate for supply temperature and pressure fluctuations.

DURA-trol® is highly responsive and cannot be damaged by extremes in temperature.

Thermostatic Mixing Valve can be set to the correct temperature for the application.

Locking temperature regulator to prevent accidental movement set for 85°F (29°C)

Mixing valve will close down on failure of cold water supply

BY OTHERS

DRAIN

SUPPLIED

g pp y Mixing valve with special internal cold water bypass capable of a minimum of 4 GPM (15 l/min)…

This is the start of the file's text. The full file is on GovTribe.