A1.2_Drawings_Part9.pdf
PDF 9 MB Posted
- Attached to
- Fort Hood 69th ADA SSA Warehouse Federal contract opportunity
- Solicitation number
- W9126G19B0029
About this file
This document provides electrical drawings and specifications for the Fort Hood 69th ADA SSA Warehouse project. The project involves electrical work for a warehouse facility including power distribution equipment, lighting plans, panel schedules, telecommunications plans, and equipment connection details. Specific requirements include installation of a 600A 480/277V main distribution panel, numerous 208/120V branch circuit panels, lighting fixtures, receptacles, and a telecommunications system with data, voice, and CATV cabling. The solicitation number is W9126G19B0029 and was issued by the U.S. Army Corps of Engineers Engineering District Fort Worth for the Fort Hood supply support activity warehouse.
Part 9 of 10
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| C1_Bid_Abstract_19B0029.pdf | ||
| Amendment_3.pdf | ||
| Amendment_2.pdf | ||
| Amendment_1.pdf | ||
| G2_W9126G19B0029.pdf | ||
| A1.2_Drawings_Part1.pdf | ||
| A1.2_Drawings_Part4.pdf | ||
| A1.2_Drawings_Part10.pdf | ||
| A1.2_Drawings_Part2.pdf | ||
| A1.2_Drawings_Part3.pdf | ||
| A1.2_Drawings_Part8.pdf | ||
| A1.2_Drawings_Part5.pdf | ||
| A1.2_Drawings_Part6.pdf | ||
| A1.2_Drawings_Part7.pdf | ||
| G2.20_W9126G19B0029.pdf |
Show all 15
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
EL502
Fort Worth District
L
IG
H T
IN
G D
E T
A
IL
S
US Army Corps of Engineers
A P
P R
D A
T E
D E
S C
R
IP
T
IO
N S
Y M
$FILEL$
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
$DATE$ $TIME$
S u b m it te d b y
C h e c k e d b y
D ra w n b y
D e s ig n e d b y
P L
O T D
A T
E
P L
O T S
C A
L E
F O
R T H
O O
D T
E X
A S
T
H A
IR
D
E F
E N
S E A
R T
IL
L E
R Y D
IV
IS
IO
N
P N
U .S
A R
M Y C
O R
P S O
F E
N G
IN
E E
R S
T
A Y
L O
R S
T
F O
R T W
O R
T H T
X
S U
P P
L Y S
U P
P O
R T A
C T
IV
IT
Y W
A R
E H
O U
S E
S o li c it a ti o n N o
C o n tr a c t
N o
Is s u e D a te
G
C H
O A
T E
G
C H
O A
T E
E N
G
IN
E E
R
IN
G B
R A
N C
H
C O
N S
T R
U C
T
IO
N D
IV
IS
IO
N
E N
G
IN
E E
R
IN
G
NUMBER
SHEET
D
B R
O W
N P .E
C H
IE
F E
L E
C T
R
IC
A L S
E C
T
IO
N D
A R
E N A
B R
O W
N P .E
W
G -1
-B -0
A U
G U
S T
FEATURES
PROFILE:
HIGH EFFICIENCY ELECTRONIC LED DRIVER
MIN. LUMENS PER WATT (EFFICACY): 135
NOM. DIMENSIONS: W2 = 5" H X 3" D X 25" L
GENERAL DESCRIPTION
HOUSING: EXTRUDED ALUMINUM WITH ALUMINUM END CAPS
MOUNTING: SEMI-RECESSED WALL
FROSTED ACRYLIC LENS SHIELDS LED FROM VIEW.
ELECTRICAL: 277 VOLT
UL LISTED FOR DAMP LOCATION.
FINISH: WHITE.
WARRANTY: 10 YEARS COVERAGE OF LUMINAIRE INCLUDES
FIXTURE CONSTRUCTION, LED, DRIVER, CONTROL DEVICE
TYPE W2: 30W, 3310 LUMEN , 110 LUMEN/WATT MIN
TYPE W4: 32W, 4273 LUMEN , 133 LUMEN/WATT MIN
W4 = 5" H X 3" D X 49" L
OTHER
MINIMUM BRIGHTNESS 20 CD/SQ METER ON FACE OF SIGN. EXIT SIGNS SHALL BE OF THE LIGHT
EMITTING DIODE (LED) TYPE RATED FOR REQ'D VOLTAGE. CASE SHALL BE BLACK WITH RED
LETTERING. LED LIGHT SOURCE SHALL BE VIBRATION RESISTANT. ENTIRE UNIT SHALL HAVE A
MINIMUM THREE YEAR FULL WARRANTY FROM DATE OF INSTALLATION. FIXTURE SHALL BE
PREWIRED, WITH WIRING CONCEALED IN THE ILLUMINATED PORTION OF THE FIXTURE HOUSING.
FEATURES
LAMP TYPE: LED
MOUNTING: UNIVERSAL
SHIELDING: FLAT SHEET ACRYLIC
LETTERS: RED
HIGH EFFICIENCY ELECTRONIC LED DRIVER
NOM. DIMENSIONS 11 3/8 " W X 7 7/8 " H X 1 3/4 " D
GENERAL DESCRIPTION
HOUSING: DIE-CAST ALUMINUM OR 20 GA. COLD ROLLED STEEL, HARDWARE
FINISH TO MATCH HOUSING FINISH. (6") H LETTERS WITH (3/4") STROKE.
DIRECTIONAL ARROWS AS SHOWN. "X1" IS BACK MOUNTED, "X2" IS TOP
MOUNTED.
ELECTRICAL: 277 VOLT
X1 X2
FEATURES
PROFILE: 29W, 2187 DELIVERED LUMEN NORMAL
DISTRIBUTION: IES SHARP CUTOFF, TYPE II.
HIGH EFFICIENCY ELECTRONIC LED DRIVER
MIN. LUMENS PER WATT (EFFICACY): 89
NOM. DIMENSIONS 16" W X 16" H X 8" D
UL LISTED FOR WET LOCATION.
DUST AND WATER PROTECTED TO IP64 STANDARDS
GENERAL DESCRIPTION
HOUSING: DIE CAST ALUMINUM HOUSING, WITH INTEGRAL HEAT SINKS.
MOUNTING: WALL
UV STABILIZED, HIGH IMPACT RESISTANT MOLDED POLYCARBONATE
LENS. LENS BASE SHIELDS LAMPS FROM VIEWING ANGLES. LENS SECURED
WITH CONCEALED CAPTIVE TORX WITH CENTER PIN FASTENERS.
ELECTRICAL: 277 VOLT
FINISH: DARK BRONZE.
WARRANTY: 10 YEARS COVERAGE OF LUMINAIRE INCLUDES
FIXTURE CONSTRUCTION, LED, DRIVER, CONTROL DEVICE
SCALE: NOT TO SCALE SCALE: NOT TO SCALE
SCALE: NOT TO SCALE
TYPE "W2" & "W4" WALL MOUNTED LED TYPE "Y" WALL PACK FIXTURE
TYPE "X1" & "X2" EXIT LIGHT
2 3
EL502 EL502
EL502
FEATURES
GENERAL DESCRIPTION
SCALE: NOT TO SCALE
EL502
LAMP TYPE: 18W LED, 5000K, 12 DEGREE FLOOD LED
LISTED TO UL 1598 FOR WET LOCATION, IP66.
FINISH: YELLOW HEAD AND ARM.
ELECTRICAL: 277 VOLT
DOUBLE STRUT SWING ARM.
GLASS LENS. STAINLESS STEEL FASTENERS AND 40"
DIE CAST ALUMINUM HOUSING WITH SEALED TEMPERED
TYPE "Z" WALL MOUNTED DOCK LIGHT
DIMMING: 0-10V DIMMING DRIVER, 10% MIN. LIGHT OUTPUT
FEATURES
PROFILE: INDIRECT
HIGH EFFICIENCY ELECTRONIC LED DRIVER
MIN. LUMENS PER WATT: 108
NOM. DIMENSIONS 24" W X 24" L X 3-3/4" D
GENERAL DESCRIPTION
HOUSING: COLD ROLLED STEEL
MOUNTING: RECESSED
LED LIGHT SOURCES SHALL BE SHIELDED FROM VIEW
ELECTRICAL: 277 VOLT
FINISH: BAKED WHITE ACRYLIC ENAMEL.
WARRANTY: 10 YEARS COVERAGE OF LUMINAIRE INCLUDES
FIXTURE CONSTRUCTION, LED, DRIVER, CONTROL DEVICE
SCALE: NOT TO SCALEEL501
1 TYPE "R1" & "R2" 2X2 RECESSED FIXTURE
TYPE R2: 29W, 3300 DELIVERED LUMEN NORMAL
TYPE R1: 18W, 2000 DELIVERED LUMEN NORMAL
IN THE EVENT OF FAILURE OF NORMAL POWER SUPPLY.
A MINIMUM OF 400 LUMENS FOR A MINIMUM OF 90 MINUTES
EMERGENCY BATTERY PACK CAPABLE OF PRODUCING
BATTERY PACK SHALL HAVE A FACTORY INSTALLED
FIXTURES INDICATED TO HAVE INTEGRAL EMERGENCY
IN THE EVENT OF FAILURE OF NORMAL POWER SUPPLY.
A MINIMUM OF 400 LUMENS FOR A MINIMUM OF 90 MINUTES
EMERGENCY BATTERY PACK CAPABLE OF PRODUCING
BATTERY PACK SHALL HAVE A FACTORY INSTALLED
FIXTURES INDICATED TO HAVE INTEGRAL EMERGENCY
INLINE ROCKER SWITCH
HIGH EFFICIENCY ELECTRONIC LED DRIVER
MOUNTING: WALL
LAMP LIFE: , L70 - 100,000 LIFE HOURS AT 98 DEG F.
LAMP TYPE: LED, 4000K, CRI: SEE SPEC FOR REQUIREMENT, L90 - 60,000 LIFE HOURS
LAMP TYPE: LED, 4000K, CRI: SEE SPEC FOR REQUIREMENT, L80 - 60,000 LIFE HOURS LAMP TYPE: LED, 4000K, CRI: SEE SPEC FOR REQUIREMENT, L70 - 85,000 LIFE HOURS
EL103
EL102
EL101
EL103
EL102
EL101
EL103
EL102
EL101
EL103
EL102
EL101
EL103
EL102
EL101
US Army Corps of Engineers
A P
P R
D A
T E
D E
S C
R
IP
T
IO
N S
Y M
$FILEL$
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
$DATE$ $TIME$
S u b m it te d b y
C h e c k e d b y
D ra w n b y
D e s ig n e d b y
P L
O T D
A T
E
P L
O T S
C A
L E
F O
R T H
O O
D T
E X
A S
T
H A
IR
D
E F
E N
S E A
R T
IL
L E
R Y D
IV
IS
IO
N
P N
U .S
A R
M Y C
O R
P S O
F E
N G
IN
E E
R S
T
A Y
L O
R S
T
F O
R T W
O R
T H T
X
S U
P P
L Y S
U P
P O
R T A
C T
IV
IT
Y W
A R
E H
O U
S E
S o li c it a ti o n N o
C o n tr a c t
N o
Is s u e D a te
G
C H
O A
T E
G
C H
O A
T E
E N
G
IN
E E
R
IN
G B
R A
N C
H
C O
N S
T R
U C
T
IO
N D
IV
IS
IO
N
E N
G
IN
E E
R
IN
G
NUMBER
SHEET
D
B R
O W
N P .E
C H
IE
F E
L E
C T
R
IC
A L S
E C
T
IO
N D
A R
E N A
B R
O W
N P .E
W
G -1
-B -0
A U
G U
S T
EL601
A N
D C
O N
T R
O L M
A T
R
IX
L
IG
H T
IN
G F
IX
T U
R E S
C H
E D
U
E
LIGHT FIXTURE SCHEDULE
FIXTURE LAMP MOUNTING
TYPE DESCRIPTION FINISH VOLTAGE WATTS
INPUT
TYPE FIXTURE
PER
LUMENS
TOTAL
TYPE HEIGHT
A HIGH BAY 16" NOMINAL DIAMETER WHITE 277 162 LED 14628 PENDANT FIXTURE 16'-0" AFF
BOTTOM OF THE
A1 HIGH BAY 16" NOMINAL DIAMETER WHITE 277 210 LED 19073 PENDANT FIXTURE 16'-0" AFF
BOTTOM OF THE
D1 6" LED RECESSED DOWNLIGHT WHITE 277 13.6 LED 1200 RECESSED N/A
D2 6" LED RECESSED DOWNLIGHT WHITE 277 18.8 LED 1655 RECESSED N/A
D4 4" LED RECESSED DOWNLIGHT WHITE 277 10 LED 765 RECESSED N/A
R1 2X2 RECESSED INDIRECT WHITE 277 18 LED 2000 RECESSED N/A
R2 2X2 RECESSED INDIRECT WHITE 277 29 LED 3300 RECESSED N/A
R3 2x4 RECESSED INDIRECT WHITE 277 31 LED 3191 RECESSED N/A
R4 2x4 RECESSED INDIRECT WHITE 277 39 LED 4305 RECESSED N/A
R6 2x4 RECESSED INDIRECT WHITE 277 56 LED 5689 RECESSED N/A
S1 1X4 SURFACE-MOUNT VOLUMETRIC WHITE 277 27 LED 3195 SURFACE N/A
S2 2FT LENSED LED STRIPLIGHT WHITE 277 17.13 LED 1907 SURFACE N/A
S3 4FT LENSED LED STRIPLIGHT WHITE 277 15 LED 2038 SURFACE N/A
S3P 4FT LENSED LED STRIPLIGHT WHITE 277 15 LED 2038 PENDANT 9'-0" AFF
S4 4FT LENSED LED STRIPLIGHT WHITE 277 25 LED 3061 SURFACE N/A
S4P 4FT LENSED LED STRIPLIGHT WHITE 277 25 LED 3061 PENDANT 9'-0" AFF
S5 4FT LENSED LED STRIPLIGHT WHITE 277 41 LED 4615 SURFACE N/A
S5P 4FT LENSED LED STRIPLIGHT WHITE 277 41 LED 4615 PENDANT 9'-0" AFF
W2 LINEAR FIXTURE WITH DIFFUSE LENS WHITE 277 30 LED 3310 WALL 7'-0" AFF
W4 LINEAR FIXTURE WITH DIFFUSE LENS WHITE 277 32 LED 4273 WALL 7-0" AFF
Y WALL PACK DARK BRONZE 277 30 LED 2187 WALL 10'-0" AFF
Z DOCK LIGHTING YELLOW 277 18 LED 1560 WALL 8'-10" AFF
NOTE: REFER TO EL501 AND EL502 FOR ADDITIONAL LIGHTING INFORMATION AND REQUIREMENTS.
SCHEDULE MAY APPEAR ON THE LIGHTING PLAN DRAWINGS.
NOT ALL LIGHTING TYPE SHOWN ON LIGHT FIXTURE
GENERAL SHEET NOTES
LIGHTING CONTROL STRATEGY
ROOM NAME ROOM #
SCENARIO
CONTROL
LIGHTING
CLS OFFICE 102, 125, 148 5
TELECOM 117, 137, 159 1
CONF ROOM 113, 136, 158 6
CORRIDOR 104, 104A, 127, 127A, 147A, 150, 150A 2
CUSTOMER ISSUE BAY 116, 139, 161 3
CUSTOMER SERVICE 103, 126, 149 3
ELECTRICAL 110, 133 1
ENTRANCE/VESTIBULE 101, 124, 147 2
FIRE PUMP/RISER ROOM 143 1
FORKLIFT CHARGING STATI120, 144, 164 4
JANITOR 109, 132, 155 3
OFFICE 105-108, 151-154, 128-131 5
MECHANICAL 123, 167 1
RECEVING /ISSUE BAY 122, 145, 166 3
RESTROOM: MEN 111, 134, 156 3
RESTROOM: WOMEN 112, 135, 157 3
SECURE STORAGE 141, 117 4
STOCK CONTROL OFFICE 116, 138, 160 9
TURN-IN BAY 165, 121, 140 3
WAREHOUSE 118, 142, 163 7
LIGHTING CONTROL STRATEGIES
NUMBER
SCENARIO
CONTROL STRATEGY NAME CONTROL STRATEGY DESCRIPTION
1 MANUAL ON / MANUAL OFF
SPACE AND OCCUPANT MANUALLY TURNS THE LIGHT OFF WHEN EXITING.
OCCUPANT MANUALLY TURNS THE LIGHTS ON UPON ENTERING THE
50% OFF
OCCUPANCY ON / VACANCY TO
MINUTES.
LEAST 50% WHEN NO OCCUPANT ACTIVITY IS DETECTED WITHIN 15
ACTIVITY IS SENSED. AUTOMATICALLY REDUCE LIGHT OUTPUT BY AT
AUTOMATIC ON TO FULL DESIGN LIGHTING POWER WHEN OCCUPANT
(OCCUPANCY SENSOR)
OFF
OCCUPANCY ON / VACANCY
OCCUPANT ACTIVITY.
ACTIVITY IS SENSED. AUTOMATIC OFF WITHIN 15 MINUTES OF NO
AUTOMATIC ON TO FULL DESIGN LIGHTING POWER WHEN OCCUPANT
(VACANCY SENSOR)
MANUAL ON / VACANCY OFF
SPACE. AUTOMATIC OFF WITHIN 15 MINUTES OF NO OCCUPANT ACTIVITY.
OCCUPANT MANUALLY TURNS THE LIGHTS ON UPON ENTERING THE
5 MANUAL ON / VACANCY OFF
ROOM.
SPACE. AUTOMATIC OFF WITHIN 15 MINUTES OF OCCUPANT LEAVING
OCCUPANT MANUALLY TURNS THE LIGHTS ON UPON ENTERING THE
DIMMER
MANUAL ON / VACANCY OFF /
AUTOMATIC OFF WITHIN 15 MINUTES OF OCCUPANT LEAVING ROOM.
OFF.
BETWEEN 30% AND 70% OF DESIGN LIGHTING POWER IN ADDITION TO ALL
CONTROL GENERAL LIGHTING WITH AT LEAST ONE CONTROL STEP
SPACE. PROVIDE MANUAL CONTROL DEVICE TO INDEPENDENTLY
OCCUPANT MANUALLY TURNS THE LIGHTS ON UPON ENTERING THE
VACANCY OFF
OCCUPANCY ON
ZONE CONTROLLED
MANUAL ON-OFF ALL ON/OFF MANUAL SWITCHING OVERRIDING AUTOMATIC CONTROLS.
15 MINUTES WHEN NO OCCUPANT ACTIVITY IS SENSED IN THE ZONE.
SENSED IN THE ZONE. LIGHTS IN THE ZONE ARE AUTOMATIC OFF WITHIN
ON TO FULL DESIGN LIGHTING POWER WHEN OCCUPANT ACTIVITY IS
LIGHTS ARE ZONE CONTROLLED. LIGHTS IN THE ZONE ARE AUTOMATIC
TIMMER
ON AT DUSK / OFF AT DAWN /
IN COMBINE WITH TIMER CONTROL.
AUTOMATICALLY TURN OFF WHEN SUFFICIENT DAYLIGHT IS AVAILABLE)
DUSK TO DAWN AUTOMATIC LIGHTING CONTROL (ON AT DUSK AND
VACANCY OFF /
OCCUPANCY ON 50% /
10000SFT OR LESS.
MUST CONTROL A MAXIMUM OF 2500SFT AREA FOR A SPACE
15 MINUTES OF NO OCCUPANT ACTIVITY.EACH CONTROL DEVICE
.AUTOMATIC OFF WITHIN
MANUAL ON SWITCHING, WHEN OCCUPANT ACTIVITY IS SENSED.
AUTO ON TO 50% DESIGN LIGHTING POWER, COMBINED WITH
IG
H T
IN
G C
O N
T R
O L
W
IR
IN
G D
IA
G R
A M
S
EL602
Fort Worth District
US Army Corps of Engineers
A P
P R
D A
T E
D E
S C
R
IP
T
IO
N S
Y M
$FILEL$
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
$DATE$ $TIME$
S u b m it te d b y
C h e c k e d b y
D ra w n b y
D e s ig n e d b y
P L
O T D
A T
E
P L
O T S
C A
L E
F O
R T H
O O
D T
E X
A S
T
H A
IR
D
E F
E N
S E A
R T
IL
L E
R Y D
IV
IS
IO
N
P N
U .S
A R
M Y C
O R
P S O
F E
N G
IN
E E
R S
T
A Y
L O
R S
T
F O
R T W
O R
T H T
X
S U
P P
L Y S
U P
P O
R T A
C T
IV
IT
Y W
A R
E H
O U
S E
S o li c it a ti o n N o
C o n tr a c t
N o
Is s u e D a te
G
C H
O A
T E
G
C H
O A
T E
E N
G
IN
E E
R
IN
G B
R A
N C
H
C O
N S
T R
U C
T
IO
N D
IV
IS
IO
N
E N
G
IN
E E
R
IN
G
NUMBER
SHEET
D
B R
O W
N P .E
C H
IE
F E
L E
C T
R
IC
A L S
E C
T
IO
N D
A R
E N A
B R
O W
N P .E
W
G -1
-B -0
A U
G U
S T
NO SCALE
SENSOR WITH 3-WAY SWITCHING
CEILING-MOUNTED OCCUPANCY
COMMON
+24 VDC
NEUTRAL
LOAD
POWER PACK
WHT
BLKHOT
OUTPUT
CONTROL
TRAVELERS
NO SCALE
OCCUPANCY SENSORS USING ONE POWER PACK
LIGHTING CONTROL ONE-LINE: MULTIPLE
WHITE (NEUTRAL)
HOT BLK
WHT POWER PACK
LOAD
RED
(ONE-LINE SHOWN)
RECOMMENDATION
MANUFACTURER
WIRING PER
24 VOLT CONTROL
RED
RED (LINE)
EL602
EL602
SWITCHES
3-WAY
SHOWN
SWITCH WHERE
MOUNTED
LOCAL WALL
SENSOR
OCCUPANCY
24 VDC
SENSOR
OCCUPANCY
24 VDC
SENSOR
OCCUPANCY
24 VDC SENSOR
OCCUPANCY
VDC
EL103
EL102
EL101
EL103
EL102
EL101
H A
N D
O F F
A U
T O
B A
L L
A S
T E
M E
R G
E N
C Y
TIMECLOCK
ASTRONOMIC
H
N
PC
T
NO SCALEEL602
3 EXTERIOR LIGHTING CONTROL
EL101
ENCLOSURE.
ON COVER OF
LOCATED
SWITCH
HAND-OFF-AUTO
PHOTOCELL
VOLTAGE
LINE
T
Y P
B L
D G L
T G
E X
T E
R
IO
R
CONTROL"
LIGHTING
ELECTRICAL ROOM (ROOM 133). LABEL ENCLOSURE "EXTERIOR BUILDING
NEMA 1, 12 GAUGE ENCLOSURE WITH HINGED DOOR AND LOCKING HANDLE IN
C
(MECH. HELD)
20 AMP, 4 POLE, 277 VOLT
LIGHTING CONTACTOR
LIGHTS. TYPICAL.
BALLASTS, IN EMERGENCY
FOR EMERGENCY
PHASE CONDUCTOR
PROVIDE UNSWITCHED
FOR CIRCUITING INFO
SEE LIGHTING FLOORPLAN
C
IR
C U
IT
IN
G I
N F
O F
L O
O R
P L
A N F
O R
S
E L
IG
H T
IN
G
A P
P R
D A
T E
D E
S C
R
IP
T
IO
N S
Y M
$FILEL$
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
$DATE$ $TIME$
KEY PLAN
A B C
S u b m it te d b y
C h e c k e d b y
D ra w n b y
D e s ig n e d b y
P L
O T D
A T
E
P L
O T S
C A
L E
F O
R T H
O O
D T
E X
A S
T
H A
IR
D
E F
E N
S E A
R T
IL
L E
R Y D
IV
IS
IO
N
P N
U .S
A R
M Y C
O R
P S O
F E
N G
IN
E E
R S
T
A Y
L O
R S
T
F O
R T W
O R
T H T
X
S U
P P
L Y S
U P
P O
R T A
C T
IV
IT
Y W
A R
E H
O U
S E
S o li c it a ti o n N o
C o n tr a c t
N o
Is s u e D a te
G
C H
O A
T E
G
C H
O A
T E
E N
G
IN
E E
R
IN
G B
R A
N C
H
C O
N S
T R
U C
T
IO
N D
IV
IS
IO
N
E N
G
IN
E E
R
IN
G
NUMBER
SHEET
N
NORTH
TRUE
D
B R
O W
N P .E
C H
IE
F E
L E
C T
R
IC
A L S
E C
T
IO
N D
A R
E N A
B R
O W
N P .E
W
G -1
-B -0
A U
G U
S T
AC
EWC
AC
L2A L1A
GFCI
L3A
WP
TV
J
WP
WP
WP
TV
CLOSET
JANITOR'S
CUSTOMER SERVICE AREA
VESTIBULE
CLS OFFICE
TURN IN BAY
CUSTOMER ISSUE BAY
STOCK CONTROL OFFICE
OFFICE SUPPORT
CONFERENCE ROOM
STORAGE WAREHOUSE
RECEIVING / ISSUE BAY
ROOM
MECHANICAL
CLS OFFICE
CLS OFFICE
C O
R R
ID
O R A
CORRIDOR A
WOMEN
RESTROOM
CHARGING STATION
& FORKLIFT
MAINTENANCE SHOP
MEN
RESTROOM
L
L
L
L
L
L
L
L
H1A
LDPA
L
L
L
L
L
L
GFCI
H1A-20,22,24
L4A-24
L4A-24
L4A-24
L4A-20L4A-20
L4A-20
L4A-20
L4A-30
L4A-30
L4A-30
L4A-30
L4A-30
L4A-22
L4A-22
L4A-22L4A-22
L2A-7
L2A-7
L2A-11
L2A-7
L2A-11
L2A-11
L2A-9
L2A-3
L2A-3
L2A-3 L2A-3
L2A-3
L2A-14 L2A-14
L2A-16
L2A-10L2A-16L2A-16
L2A-19
L2A-19
L2A-19
L2A-8
L2A-13
L2A-13
L2A-13
L2A-13
L2A-6
L2A-21
L2A-1
L2A-1
L2A-1
L2A-4
L2A-6 L2A-6
L2A-2
L2A-2 L2A-2
L2A-2
L2A-18
L2A-18
L2A-18
L2A-18
L2A-19
L2A-21
L2A-21
L2A-1
L2A-1
L2A-23
L2A-23
L2A-23
L2A-23
L2A-15
L2A-12
L2A-15
L2A-17 L2A-17 L2A-17
L2A-21
TV
L2A-11
H1A-19,21,23
WP
L2A-21
L2A-27
CLS OFFICE
CLS OFFICE
WP
ILON
L4B-22
L4B-24
L3A
L3A-4
L3A-4
L3A-16
L3A-16
L3A-16
L3A-4
L3A-15
L3A-17
L2A-7
L3A-8,10
L3A-7,9
J
J
ROOM
ELECTRICAL
L3A-2
SECURE STORAGE
L4A-22
L2A-25
WH
L2A-29
GFCI
GFCI
T
A L
A
T
B L
B
T1A
ROOM
TELECOMM
SM
AC
EWC
AC
L2A L1A
GFCI
L3A
WP
TV
J
WP
WP
WP
JANITOR'S
CUSTOMER SERVICE AREA
VESTIBULE
CLS OFFICE
TURN IN BAY
CUSTOMER ISSUE BAY
STOCK CONTROL OFFICE
OFFICE SUPPORT
CONFERENCE ROOM
STORAGE WAREHOUSE
RECEIVING / ISSUE BAY
ROOM
MECHANICAL
CLS OFFICE
CLS OFFICE
C O
R R
ID
O R A
CORRIDOR A
WOMEN
RESTROOM
CHARGING STATION
& FORKLIFT
MAINTENANCE SHOP
MEN
RESTROOM
L
L
L
L
L
L
L
L
H1A
LDPA
L
L
L
L
L
L
GFCI
H1A-20,22,24
L4A-24
L4A-24
L4A-24
L4A-20L4A-20
L4A-20
L4A-20
L4A-30
L4A-30
L4A-30
L4A-30
L4A-30
L4A-22
L4A-22
L4A-22L4A-22
L2A-7
L2A-7
L2A-11
L2A-7
L2A-11
L2A-11
L2A-9
L2A-3
L2A-3
L2A-3 L2A-3
L2A-3
L2A-14 L2A-14
L2A-16
L2A-10L2A-16L2A-16
L2A-19
L2A-19
L2A-19
L2A-8
L2A-13
L2A-13
L2A-13
L2A-13
L2A-6
L2A-21
L2A-1
L2A-1
L2A-1
L2A-4
L2A-6 L2A-6
L2A-2
L2A-2 L2A-2
L2A-2
L2A-18
L2A-18
L2A-18
L2A-18
L2A-19
L2A-21
L2A-21
L2A-1
L2A-1
L2A-23
L2A-23
L2A-23
L2A-23
L2A-15
L2A-12
L2A-15
L2A-17 L2A-17 L2A-17
L2A-21
TV
L2A-11
H1A-19,21,23
WP
L2A-21
L2A-27
CLS OFFICE
CLS OFFICE
ROOM
TELECOMM
WP
ILON
L3A
L3A-4
L3A-4
L3A-16
L3A-16
L3A-16
L3A-4
L3A-15
L3A-17
L2A-7
L3A-8,10
L3A-7,9
J
J
ROOM
ELECTRICAL
L3A-2
SECURE STORAGE
L4A-22
L2A-25
WH
L2A-29
GFCI
GFCI
T
A L
A
T1A
EP101
GENERAL SHEET NOTES
POWER PLAN - AREA A
EP101 SCALE: 1/8" = 1'-0"
KEY NOTES:
P O
W E
R P
L A
N
A R
E A
0 824 168
" = 1'-0"8
1SCALE:
INACTIVITY.
RECEPTACLES OFF AFTER 15 MINUTES OF
OCCUPANCY SENSOR(S) SHALL TURN
OCCUPANCY SENSOR(S) WITHIN THE ROOM:
DEVICE SHALL BE CONTROLLED BY
"L" NEXT TO RECEPTACLE INDICATES THE 5.
PENETRATED THE WALL.
OR GREATER VALUE THAN THE FIRE RATING OF
STOP ASSEMBLIES WITH RATINGS OF EQUAL
SHALL BE FIRE STOPPED WITH UL TESTED FIRE
PENETRATIONS THROUGH FIRE RATED WALLS
ALL WALL PENETRATIONS SHALL BE SEALED. 4.
LOCATIONS.
LOCATIONS OF VOICE/DATA AND CATV OUTLET
SEE TELECOMMUNICATIONS PLANS FOR
EACH DESK AND TO CATV OUTLETS ON WALLS.
POSSIBLE TO VOICE/DATA JACK OUTLET AT
INSTALL POWER RECEPTACLES AS CLOSE AS 3.
STRUCTURAL PLANS.
COORDINATE ALL FLOOR PENETRATIONS WITH 2.
SEE SHEET E-001.
FOR ELECTRICAL LEGEND AND ABBREVIATIONS 1.
6 6
OCCUPANCY CONTROLLED TYPE.
RECEPTACLE FOR EACH WORKSTATION AS
FURNITURE. PROVIDE 50% OF THE
EXACT LOATION OF THE MODULAR SYSTEM
COORDINATE WITH FURNITURE LAYOUT FOR
CONDUCTOR ROLLED UP IN J-BOX.
& 1 NEUTRAL) AND 1 #12 G. LEAVE 12" OF
#12 (1 HOT, 1 SWITCH BY OCCUPANCY SENSOR
POWER FOR MODULAR SYSTEM FURNITURE. 3 6
CHAINLINK WALL.
PROVIDE RECEPTACLE AND CONDUIT FOR 5
CHARGER.
INOPERABILITY DISABLES THE BATTERY
THAT ANY EXHAUST FAN FAULT OR
WITH THE EXHAUST FAN FOR THIS ROOM, SUCH
CHARGING. POWER SHALL BE INTERLOCKED
DISCONNECT FOR FORK LIFT BATTERY 4
CONTROLS.
CONNECT AUTOMATED TOILET FIXTURE
ONE JUNCTION BOX FOR EACH RESTROOM, TO 3
NEMA 6-20
RECEPTACLES IT RACKS. RECEPTACLES TO BE
DEDICATED, 240-V NEMA 6-20, FLOOR MOUNTED 2
LOCATION WITH USER.
FUTURE SECURITY WIRING. COORDINATE FINAL
SURFACE-MOUNTED JUNCTION BOX, FOR 1
F O
R M
A T
C H L
IN
E R
E E
P
A P
P R
D A
T E
D E
S C
R
IP
T
IO
N S
Y M
$FILEL$
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
$DATE$ $TIME$
KEY PLAN
A B C
S u b m it te d b y
C h e c k e d b y
D ra w n b y
D e s ig n e d b y
P L
O T D
A T
E
P L
O T S
C A
L E
F O
R T H
O O
D T
E X
A S
T
H A
IR
D
E F
E N
S E A
R T
IL
L E
R Y D
IV
IS
IO
N
P N
U .S
A R
M Y C
O R
P S O
F E
N G
IN
E E
R S
T
A Y
L O
R S
T
F O
R T W
O R
T H T
X
S U
P P
L Y S
U P
P O
R T A
C T
IV
IT
Y W
A R
E H
O U
S E
S o li c it a ti o n N o
C o n tr a c t
N o
Is s u e D a te
G
C H
O A
T E
G
C H
O A
T E
E N
G
IN
E E
R
IN
G B
R A
N C
H
C O
N S
T R
U C
T
IO
N D
IV
IS
IO
N
E N
G
IN
E E
R
IN
G
NUMBER
SHEET
N
NORTH
TRUE
D
B R
O W
N P .E
C H
IE
F E
L E
C T
R
IC
A L S
E C
T
IO
N D
A R
E N A
B R
O W
N P .E
W
G -1
-B -0
A U
G U
S T
L1B
L2B L2C
L1C
T1CT1B
MDP
GFCI
ACAC
EWC
LDP-B
LDP-C
WPWP
GFCI
J
GFCI
C O
R R
ID
O R
RECEIVING / ISSUE BAY
STOCK CONTROL OFFICE
OFFICE SUPPORT
CONFERENCE ROOM
A
C O
R R
ID
O
B
CONTCTR
LIGHTING
VESTIBULE
ROOM
TELECOMM
CLOSET
JANITOR'S
WOMEN
RESTROOM
ROOM
ELECTRICAL
MEN
RESTROOM
WP
L
L
L
L
L
L
L
L
H1B H1C
L L
L
L
L
TV
ILON
L3B
L2B-25
EF-1B
L2B-27 L2B-29
GFCI GFCI
L4B-22
L4B-22
L4B-24
WP
L4B-24
L4B-30
L4B-30
L4B-30
L4B-20
L4B-20
L4B-20
L3B-4 L3B-4
L3B-17 L3B-4
L3B-15
L3B-16 L3B-16
L3B-16
L4B-22 L4B-22
L4B-20L4B-24
WP
L4B-30
L2C-1
L4B-22 L2B-1
WP
H1B-19,21,23
H1B-20,22,24
L2B-6 L2B-6
L2B-1
L2B-6
L2B-1
L
L2B-15
L2B-15
L2B-12
L2B-17
L2B-17 L2B-17
L2B-21
L2B-19
L2B-19
L2B-21
L2B-21L2B-19
L2B-19
TV
L2B-21
L2B-14 L2B-14
L2B-10L2B-16L2B-16
L2B-16
L2B-7
L2B-7
L2B-7
L2B-11
L2B-11
L2B-11
L2B-11
L2B-9
L2B-3 L2B-3
L2B-3
L2B-3
L2B-3
L2B-8
L2B-18
L2B-18
L2B-13
L2B-13
L2B-18
L2B-18
L2B-13
L2B-13
L2B-23
L2B-23 L2B-23
L2B-23
L2B-2
L2B-2
L2B-2
L2B-2
L2B-4
L2B-7
L3B-2
L3B-7,9
L3B-8,10
J
J
WH
L2B-25
WATTNODE
T
B L
B
CHARGING STATION
& FORKLIFT
MAINTENANCE SHOP
FIRE / RISER PUMP
MECHANICAL
CORRIDOR B
CLS OFFICE
CUSTOMER ISSUE BAY
TURN IN BAY
STORAGE WAREHOUSE
SECURE STORAGE
CUSTOMER SERVICE AREA
EP102
0 824 168
" = 1'-0"8
1SCALE:
POWER PLAN - AREA B
EP102 SCALE: 1/8" = 1'-0"
R
P O
W E
R P
L A
N
CLS OFFICE
CLS OFFICE
CLS OFFICE
CLS OFFICE
GENERAL SHEET NOTES
INACTIVITY.
RECEPTACLES OFF AFTER 15 MINUTES OF
OCCUPANCY SENSOR(S) SHALL TURN
OCCUPANCY SENSOR(S) WITHIN THE ROOM:
DEVICE SHALL BE CONTROLLED BY
"L" NEXT TO RECEPTACLE INDICATES THE 5.
PENETRATED THE WALL.
OR GREATER VALUE THAN THE FIRE RATING OF
STOP ASSEMBLIES WITH RATINGS OF EQUAL
SHALL BE FIRE STOPPED WITH UL TESTED FIRE
PENETRATIONS THROUGH FIRE RATED WALLS
ALL WALL PENETRATIONS SHALL BE SEALED. 4.
LOCATIONS.
LOCATIONS OF VOICE/DATA AND CATV OUTLET
SEE TELECOMMUNICATIONS PLANS FOR
EACH DESK AND TO CATV OUTLETS ON WALLS.
POSSIBLE TO VOICE/DATA JACK OUTLET AT
INSTALL POWER RECEPTACLES AS CLOSE AS 3.
STRUCTURAL PLANS.
COORDINATE ALL FLOOR PENETRATIONS WITH 2.
SEE SHEET E-001.
FOR ELECTRICAL LEGEND AND ABBREVIATIONS 1.
KEY NOTES:
OCCUPANCY CONTROLLED TYPE.
RECEPTACLE FOR EACH WORKSTATION AS
SYSTEM FURNITURE. PROVIDE 50% OF THE
FOR EXACT LOATION OF THE MODULAR
J-BOX. COORDINATE WITH FURNITURE LAYOUT
G. LEAVE 12" OF CONDUCTOR ROLLED UP IN
OCCUPANCY SENSOR & 1 NEUTRAL) AND 1 #12
MOUNTED 6" AFF. 3 #12 (1 HOT, 1 SWITCH BY
POWER FOR MODULAR SYSTEM FURNITURE. 6
CHAINLINK WALL.
PROVIDE RECEPTACLE AND COUNDUIT FOR 5
CHARGER.
INOPERABILITY DISABLES THE BATTERY
THAT ANY EXHAUST FAN FAULT OR
WITH THE EXHAUST FAN FOR THIS ROOM, SUCH
CHARGING. POWER SHALL BE INTERLOCKED
DISCONNECT FOR FORK LIFT BATTERY 4
CONTROLS.
CONNECT AUTOMATED TOILET FIXTURE
ONE JUNCTION BOX FOR EACH RESTROOM, TO 3
RECEPTACLES FOR IT RACKS.
DEDICATED, 240-V NEMA 6-20, FLOOR MOUNTED 2
LOCATION WITH USER.
FUTURE SECURITY WIRING. COORDINATE FINAL
SURFACE-MOUNTED JUNCTION BOX, FOR 1
F O
R M
A T
C H L
IN
E
R E E
P
F O
R M
A T
C H L
IN
E
R E E
P
A P
P R
D A
T E
D E
S C
R
IP
T
IO
N S
Y M
$FILEL$
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
$DATE$ $TIME$
KEY PLAN
A B C
S u b m it te d b y
C h e c k e d b y
D ra w n b y
D e s ig n e d b y
P L
O T D
A T
E
P L
O T S
C A
L E
F O
R T H
O O
D T
E X
A S
T
H A
IR
D
E F
E N
S E A
R T
IL
L E
R Y D
IV
IS
IO
N
P N
U .S
A R
M Y C
O R
P S O
F E
N G
IN
E E
R S
T
A Y
L O
R S
T
F O
R T W
O R
T H T
X
S U
P P
L Y S
U P
P O
R T A
C T
IV
IT
Y W
A R
E H
O U
S E
S o li c it a ti o n N o
C o n tr a c t
N o
Is s u e D a te
G
C H
O A
T E
G
C H
O A
T E
E N
G
IN
E E
R
IN
G B
R A
N C
H
C O
N S
T R
U C
T
IO
N D
IV
IS
IO
N
E N
G
IN
E E
R
IN
G
NUMBER
SHEET
N
NORTH
TRUE
D
B R
O W
N P .E
C H
IE
F E
L E
C T
R
IC
A L S
E C
T
IO
N D
A R
E N A
B R
O W
N P .E
W
G -1
-B -0
A U
G U
S T
GFCI
AC AC
EWC
TV
WP
WP
WP
C O
R R
ID
O R
VESTIBULE
C O
R R
ID
O R C
CORRIDOR C
ROOM
TELECOMM
CLOSET
JANITOR'S
DDC
TXMTTR
FACP
WP
L
L
L
L
L
L
L L
L
TV TV
L3C
ILON
L3C-4
L3C-4 L3C-4
L3C-17
L3C-16L3C-15
L3C-16 L3C-16
L2C-6L2C-6
H1C-20,22,24
H1C-19,21,23
L2C-6
L2C-1
L2C-1
L2C-2
L2C-2 L2C-2
L2C-2
L
L
L2C-7
L2C-7 L2C-11
L2C-11
L2C-11
L2C-11
L2C-7
L2C-1
WP
GFCI
L2C-6
L2C-4
L2C-8
L2C-21
L2C-21
L2C-21
L2C-21
L2C-3
L2C-3
L2C-3
L2C-3
L2C-3
L2C-17
L2C-15
L2C-12
L2C-17 L2C-17
L2C-15
L
L
L
L2C-23
L2C-23
L2C-23
L2C-23
L2C-16
L2C-14 L2C-14
L2C-10L2C-16L2C-16
L2C-18
L2C-18
L2C-18
L2C-18
L2C-13
L2C-13
L2C-13
L2C-13
GFCI
L2C-27
GFCI
L2C-29
L2C-19
L2C-19
L2C-19
L2C-19
L4C-24
L4C-24
L4C-24L4C-20
L4C-22
L4C-22
L4C-20
L4C-20L4C-20
L4C-30
L4C-30
L4C-30
L4C-30
L4C-22 L4C-22
L4C-24
WP
L2C-9
L2C-7
L3C-2
L3C-8,10
L3C-7,9
J
J
J
WH
L2C-25
L4C-22
T
C L
C
STORAGE WAREHOUSE
RECEIVING / ISSUE BAY165
TURN IN BAY
CUSTOMER ISSUE BAY
CUSTOMER SERVICE AREA
CLS OFFICE
STOCK CONTROL OFFICE
OFFICE SUPPORT
CONFERENCE ROOM
SECURE STORAGE
ROOM
MECHANICAL
MEN
RESTROOM
WOMEN
RESTROOM
CHARGING STATION
& FORKLIFT
MAINTENANCE SHOP
EP103
SCALE: 1/8" = 1'-0"
0 824 168
" = 1'-0"8
1SCALE:
EP103
POWER PLAN - AREA C
R
E A C
P O
W E
R P
L A
CLS OFFICE
CLS OFFICE
CLS OFFICE
CLS OFFICE
GENERAL SHEET NOTES
INACTIVITY.
RECEPTACLES OFF AFTER 15 MINUTES OF
OCCUPANCY SENSOR(S) SHALL TURN
OCCUPANCY SENSOR(S) WITHIN THE ROOM:
DEVICE SHALL BE CONTROLLED BY
"L" NEXT TO RECEPTACLE INDICATES THE 5.
PENETRATED THE WALL.
OR GREATER VALUE THAN THE FIRE RATING OF
STOP ASSEMBLIES WITH RATINGS OF EQUAL
SHALL BE FIRE STOPPED WITH UL TESTED FIRE
PENETRATIONS THROUGH FIRE RATED WALLS
ALL WALL PENETRATIONS SHALL BE SEALED. 4.
LOCATIONS.
LOCATIONS OF VOICE/DATA AND CATV OUTLET
SEE TELECOMMUNICATIONS PLANS FOR
EACH DESK AND TO CATV OUTLETS ON WALLS.
POSSIBLE TO VOICE/DATA JACK OUTLET AT
INSTALL POWER RECEPTACLES AS CLOSE AS 3.
STRUCTURAL PLANS.
COORDINATE ALL FLOOR PENETRATIONS WITH 2.
SEE SHEET E-001.
FOR ELECTRICAL LEGEND AND ABBREVIATIONS 1.
KEY NOTES:
6 6
OCCUPANCY CONTROLLED TYPE.
RECEPTACLE FOR EACH WORKSTATION AS
SYSTEM FURNITURE. PROVIDE 50% OF THE
FOR EXACT LOATION OF THE MODULAR
J-BOX. COORDINATE WITH FURNITURE LAYOUT
G. LEAVE 12" OF CONDUCTOR ROLLED UP IN
OCCUPANCY SENSOR & 1 NEUTRAL) AND 1 #12
MOUNTED 6" AFF. 3 #12 (1 HOT, 1 SWITCH BY
POWER FOR MODULAR SYSTEM FURNITURE. 6
CHAINLINK WALL.
PROVIDE RECEPTACLE AND COUNDUIT FOR 5
CHARGERS.
INOPERABILITY DISABLES THE BATTERY
THAT ANY EXHAUST FAN FAULT OR
WITH THE EXHAUST FAN FOR THIS ROOM, SUCH
CHARGING. POWER SHALL BE INTERLOCKED
DISCONNECT FOR FORK LIFT BATTERY 4
CONTROLS.
CONNECT AUTOMATED TOILET FIXTURE
ONE JUNCTION BOX FOR EACH RESTROOM, TO 3
RECEPTACLES FOR IT RACKS.
DEDICATED, 240-V NEMA 6-20, FLOOR MOUNTED 2
LOCATION WITH USER.
FUTURE SECURITY WIRING. COORDINATE FINAL
SURFACE-MOUNTED JUNCTION BOX, FOR 1
WP
F O
R M
A T
C H L
IN
E
R E E
P
A P
P R
D A
T E
D E
S C
R
IP
T
IO
N S
Y M
$FILEL$
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
$DATE$ $TIME$
S u b m it te d b y
C h e c k e d b y
D ra w n b y
D e s ig n e d b y
P L
O T D
A T
E
P L
O T S
C A
L E
F O
R T H
O O
D T
E X
A S
T
H A
IR
D
E F
E N
S E A
R T
IL
L E
R Y D
IV
IS
IO
N
P N
U .S
A R
M Y C
O R
P S O
F E
N G
IN
E E
R S
T
A Y
L O
R S
T
F O
R T W
O R
T H T
X
S U
P P
L Y S
U P
P O
R T A
C T
IV
IT
Y W
A R
E H
O U
S E
S o li c it a ti o n N o
C o n tr a c t
N o
Is s u e D a te
G
C H
O A
T E
G
C H
O A
T E
NUMBER
SHEET
D
B R
O W
N P .E
C H
IE
F E
L E
C T
R
IC
A L S
E C
T
IO
N D
A R
E N A
B R
O W
N P .E
W
G -1
-B -0
A U
G U
S T
18 19
F
G
202018 19
F
G
0 824 168
" = 1'-0"8
1SCALE:
EP104 SCALE: 1/8" = 1'-0"
SITE ORIENTATION
REF. CIVIL FOR
EP104
Fort Worth District
GENERAL NOTES
C O
V E
R E
D H
A R
D S
T A
N D
ES101
SECURE STORAGE
COVERED
TYPICAL POWER PLAN - COVERED HARDSTAND
P O
W E
R P
L A
N
SCHEDULE FOR MORE INFO.
WAREHOUSE. REFER TO PANEL
SEPARATE PANELS INSIDE THE
BE PROVIDED FROM THREE
EACH COVERED HARDSTAND, SHALL
POWER TO THE DISCONNECTS, FOR 6.
DISCONNECT.
BE PROVIDED BY AN EXTERIOR
EACH COVERED HARDSTAND, SHALL
POWER TO THE RECEPTACLES, FOR 5.
SPECS 32 31 13, PAR 3.17.
BONDING REQUIREMENTS, SEE
FOR FENCING GROUNDING AND 4.
PLANS.
SUB-OUTS WITH STRUCTURAL
COORDINATE ALL CONCRETE 3.
ABBREVIATIONS SEE SHEET E-001.
FOR ELECTRICAL LEGEND AND 2.
SITE PLANS FOR MORE INFO.
OF THREE. REFER TO ELECTRICAL
COVERED HARDSTAND IS TYPICAL 1.
TO COLUMN FACE, 4' ABOVE GRADE.
MOUNT JUNCTION BOX AND RECEPTACLE 2
MOUNTED OUTSIDE FENCING.
NEMA 3R RATED, 120V, 20A DISCONNECT, 1
L2_-5
SHEET KEYNOTES
L2_-5
WP/GFCI
L2_-5
WP/GFCI
A P
P R
D A
T E
D E
S C
R
IP
T
IO
N S
Y M
$FILEL$
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
$DATE$ $TIME$
KEY PLAN
A B C
S u b m it te d b y
C h e c k e d b y
D ra w n b y
D e s ig n e d b y
P L
O T D
A T
E
P L
O T S
C A
L E
F O
R T H
O O
D T
E X
A S
T
H A
IR
D
E F
E N
S E A
R T
IL
L E
R Y D
IV
IS
IO
N
P N
U .S
A R
M Y C
O R
P S O
F E
N G
IN
E E
R S
T
A Y
L O
R S
T
F O
R T W
O R
T H T
X
S U
P P
L Y S
U P
P O
R T A
C T
IV
IT
Y W
A R
E H
O U
S E
S o li c it a ti o n N o
C o n tr a c t
N o
Is s u e D a te
G
C H
O A
T E
G
C H
O A
T E
E N
G
IN
E E
R
IN
G B
R A
N C
H
C O
N S
T R
U C
T
IO
N D
IV
IS
IO
N
E N
G
IN
E E
R
IN
G
NUMBER
SHEET
N
NORTH
TRUE
D
B R
O W
N P .E
C H
IE
F E
L E
C T
R
IC
A L S
E C
T
IO
N D
A R
E N A
B R
O W
N P .E
W
G -1
-B -0
J U
N E
JANITOR'S
CUSTOMER SERVICE AREA
VESTIBULE
CLS OFFICE
TURN IN BAY
CUSTOMER ISSUE BAY
STOCK CONTROL OFFICE
OFFICE SUPPORT
CONFERENCE ROOM
STORAGE WAREHOUSE
RECEIVING / ISSUE BAY
ROOM
MECHANICAL
C O
R R
ID
O R A
CORRIDOR A
CHARGING STATION
& FORKLIFT
MAINTENANCE SHOP
L1A-1,3,5
L4A-8,10,12
WOMEN
RESTROOM
MEN
RESTROOM
R
PAHU-1A
SM
GFUH-1A
L4A-1
SM
GFUH-2A
L4A-1
SM
GFUH-3A
L4A-3
SM
GFUH-4A
L4A-3
SM
GFUH-5A
L4A-5
SM
GFUH-6A
L4A-5
L1A-7,9,11
EUH-1A
EUH-2A
L1A-13,15,17
L1A-19,21,23
SM
L2A-24
DWH-1A
L1A-25,27,29
EUH-3A
REF-1A
L1A-2
REF-2A
L1A-8,10,12
REF-3A
L1A-14,16,18
SM
EF-1A
L1A-4
SM
L1A-6
EF-2A
SM
L4A-9
IRH-1A
SM
L4A-9
IRH-2A
SM
L4A-11
IRH-3A
SM
L4A-11
IRH-4A
F-1A
L4A-14,16,18
CRCA-1A
L4A-18,20
R
CRCU-1A
L4A-18,20
L4A-32
DLM-1A
L4A-36
DLM-3A
L4A-38
DLM-4A
ODM-1A
L4A-13,15,17
ODM-2A
L4A-2,4,6
ODM-3A
L4A-19,21,23
ODM-4A
L4A-8,10,12
ODM-5A
L4A-25,27,29
L4A-34
DLM-2A
E R
V -1
A
ROOM
TELECOMM
ODM-4A
ROOM
ELECTRICAL
CLS OFFICE
CLS OFFICE
CLS OFFICE
SECURE STORAGE
CLS OFFICE
EP105
GENERAL SHEET NOTES
SCALE: 1/8" = 1'-0"
0 824 168
" = 1'-0"8
1SCALE:
A R
E A A
POWER EQUIPMENT PLAN - AREA A
EP105
P O
W E
R E
Q U
IP
M E
N T P
L A
N
START OF INSTALLATION.
MECHANICAL EQUIPMENT PRIOR TO
COORDINATE MOTOR CONTROLS WITH 2.
CONNECTION SCHEDULE.
SEE EP604 FOR MECHNICAL EQUIPMENT 1.
Fort Worth District
F O
R M
A T
C H L
IN
E
R E E
P
A P
P R
D A
T E
D E
S C
R
IP
T
IO
N S
Y M
$FILEL$
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
$DATE$ $TIME$
KEY PLAN
A B C
S u b m it te d b y
C h e c k e d b y
D ra w n b y
D e s ig n e d b y
P L
O T D
A T
E
P L
O T S
C A
L E
F O
R T H
O O
D T
E X
A S
T
H A
IR
D
E F
E N
S E A
R T
IL
L E
R Y D
IV
IS
IO
N
P N
U .S
A R
M Y C
O R
P S O
F E
N G
IN
E E
R S
T
A Y
L O
R S
T
F O
R T W
O R
T H T
X
S U
P P
L Y S
U P
P O
R T A
C T
IV
IT
Y W
A R
E H
O U
S E
S o li c it a ti o n N o
C o n tr a c t
N o
Is s u e D a te
G
C H
O A
T E
G
C H
O A
T E
E N
G
IN
E E
R
IN
G B
R A
N C
H
C O
N S
T R
U C
T
IO
N D
IV
IS
IO
N
E N
G
IN
E E
R
IN
G
NUMBER
SHEET
N
NORTH
TRUE
D
B R
O W
N P .E
C H
IE
F E
L E
C T
R
IC
A L S
E C
T
IO
N D
A R
E N A
B R
O W
N P .E
W
G -1
-B -0
J U
N E
EP106
SCALE: 1/8" = 1'-0"
EP106
0 824 168
" = 1'-0"8
1SCALE:
E
POWER EQUIPMENT PLAN - AREA B
GENERAL SHEET NOTES
START OF INSTALLATION.
MECHANICAL EQUIPMENT PRIOR TO
COORDINATE MOTOR CONTROLS WITH 2.
CONNECTION SCHEDULE.
SEE EP604 FOR MECHNICAL EQUIPMENT 1.
W
E R E
Q U
IP
M E
N T P
L
C
R R
ID
O R
RECEIVING / ISSUE BAY 144
CUSTOMER ISSUE BAY
CUSTOMER SERVICE AREA
STOCK CONTROL OFFICE
OFFICE SUPPORT
CLS OFFICE
C L S O
F F
IC
E
C L S O
F F
IC
E
CONFERENCE ROOM
C O
R R
ID
O R B
VESTIBULE
STORAGE WAREHOUSE
SECURE STORAGE
VESTIBULE
C L S O
F F
IC
E
C L S O
F F
IC
E
CORRIDOR B
CLOSET
JANITOR'S
CHARGING STATION
& FORKLIFT
MAINTENANCE SHOP
ROOM
ELECTRICAL
L1B-1,3,5
R
PAHU-1B
WOMEN
RESTROOM
MEN
RESTROOM
SM
GFUH-1B
L4B-1
SM
GFUH-2B
L4B-1
SM
SM
GFUH-4B
L4B-3
SM
GFUH-5B
L4B-3
SM
GFUH-6B
L4B-5
SM
GFUH-7B
L4B-5
L1B-7,9,11
EUH-1B
EUH-2B
L1B-13,15,17
L1B-19,21,23
EUH-3B
DWH-1B
L2B-24
L1B-25,27,29
SM
REF-1B
L1B-2
REF-2B
L1B-8,10,12
REF-3B
L1B-14,16,18
SM
EF-1B
L1B-4
L1B-6
EF-2B
EF-3B
L2B-20
SM
L4B-9
IRH-1B
SM
L4B-9
IRH-2B
SM
L4B-11
IRH-3B
F-1B
L4B-14,16,18
CRAC-1B
L3B-18,20
R
CRCU-1B
L3B-18,20
L4B-32
DLM-1B
L4B-34
DLM-2B
L4B-36
DLM-3B
L4B-38
DLM-4B
ODM-1B
L4B-13,15,17
ODM-2B
L4B-2,4,6
ODM-3B
L4B-19,21,23
ODM-4B
L4B-8,10,12
ODM-5B
L4B-25,27,29
R
V -1
B
FIRE / RISER PUMP
MECHANICAL
L4B-1
GFUH-3B
ROOM
TELECOMM
ROOM
TELECOMM
CUSTOMER SERVICE AREA
F O
R M
A T
C H L
IN
E
R E E
P
F O
R M
A T
C H L
IN
E
R E E
P
EP107
SCALE: 1/8" = 1'-0"
0 824 168
" = 1'-0"8
1SCALE:
EP107
POWER EQUIPMENT PLAN - AREA C
GENERAL SHEET NOTES
START OF INSTALLATION.
MECHANICAL EQUIPMENT PRIOR TO
COORDINATE MOTOR CONTROLS WITH 2.
CONNECTION SCHEDULE.
SEE EP604 FOR MECHNICAL EQUIPMENT 1.
A R
O
W E
R E
Q U
IP
M E
N T P
L A
N
US Army Corps of Engineers
A P
P R
D A
T E
D E
S C
R
IP
T
IO
N S
Y M
$FILEL$
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
$DATE$ $TIME$
KEY PLAN
A B C
S u b m it te d b y
C h e c k e d b y
D ra w n b y
D e s ig n e d b y
P L
O T D
A T
E
P L
O T S
C A
L E
F O
R T H
O O
D T
E X
A S
T
H A
IR
D
E F
E N
S E A
R T
IL
L E
R Y D
IV
IS
IO
N
P N
U .S
A R
M Y C
O R
P S O
F E
N G
IN
E E
R S
T
A Y
L O
R S
T
F O
R T W
O R
T H T
X
S U
P P
L Y S
U P
P O
R T A
C T
IV
IT
Y W
A R
E H
O U
S E
S o li c it a ti o n N o
C o n tr a c t
N o
Is s u e D a te
G
C H
O A
T E
G
C H
O A
T E
E N
G
IN
E E
R
IN
G B
R A
N C
H
C O
N S
T R
U C
T
IO
N D
IV
IS
IO
N
E N
G
IN
E E
R
IN
G
NUMBER
SHEET
N
NORTH
TRUE
D
B R
O W
N P .E
C H
IE
F E
L E
C T
R
IC
A L S
E C
T
IO
N D
A R
E N A
B R
O W
N P .E
W
G -1
-B -0
J U
N E
C O
R R
ID
O R
F O
R M
A T
C H L
IN
E
R E E
P
S O
F F
IC
E
C L S O
F F
IC
E
C L S O
F F
IC
E
CLS OFFICE
VESTIBULE
STOCK CONTROL OFFICE
OFFICE SUPPORT
CUSTOMER ISSUE BAY
TURN IN BAY
SECURE STORAGE
C L S O
F F
IC
E
C O
R R
ID
O R C
CONFERENCE ROOM
CORRIDOR C
STORAGE WAREHOUSE
RECEIVING / ISSUE BAY
ROOM
MECHANICAL
CHARGING STATION
& FORKLIFT
MAINTENANCE SHOP
CUSTOMER SERVICE AREA
CLOSET
JANITOR'S
L1C-1,3,5
R
PAHU-1C
MEN
RESTROOM
WOMEN
RESTROOM
SM
GFUH-1C
L4C-1
SM
GFUH-2C
L4C-1
SM
GFUH-3C
L4C-3
SM
GFUH-4C
L4C-3
SM
GFUH-5C
L4C-5
SM
GFUH-6C
L4C-5
EUH-1C
L1C-7,9,11
L1C-13,15,17
EUH-2C
SM
DWH-1C
L2C-24
L1C-19,21,23
SM
REF-1C
L1C-2
REF-2C
L1C-8,10,12
REF-3C
L1C-14,16,18
SM SM
EF-2C
L1C-6
EF-1C
L1C-4
L4C-9
IRH-1C
SM
L4C-9
IRH-2C
SM
L4C-11
IRH-3C
SM
L4C-11
IRH-4C
F-1C
L4C-14,16,18
CRAC-1C
L3C-18,20
R
CRCU-1C
L3C-18,20
ODM-1C
L4C-13,15,17
ODM-2C
L4C-2,4,6
ODM-3C
L4C-19,21,23
ODM-4C
L4A-8,10,12
ODM-5C
L4A-25,27,29
DLM-1C
L4C-32
DLM-2C
L4C-34
DLM-3C
L4C-36
DLM-4C
L4C-38
E R
V -1
C
ROOM
TELECOMM
ID # FEEDER SCHEDULE
3 #1/0 & 1 #6 GND IN 2" C
2 SETS OF (4 #350 KcMIL IN 4" C) & ONE 4" CONDUIT SPARE
4 #350 KcMIL & 1 #2 GND IN 3" C
4 #4 & 1 #10 GND IN 1-1/2" C
3 #2 & 1 #8 GND IN 1-1/2" C
4 #1/0 & 1 #6 GND IN 2" C
4 #2/0 & 1 #6 GND IN 2" C
4 #1 & 1 #8 GND IN 1-1/2" C
3 #4/0 & 1 #2 GND IN 2-1/2" C
DISTRIBUTION PANEL WITH FULL NEUTRAL & GROUND BUSES
LDPB, 300A, 208Y/120V, 3 PHASE,
US Army Corps of Engineers
A P
P R
D A
T E
D E
S C
R
IP
T
IO
N S
Y M
$FILEL$
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
$DATE$ $TIME$
S u b m it te d b y
C h e c k e d b y
D ra w n b y
D e s ig n e d b y
P L
O T D
A T
E
P L
O T S
C A
L E
F O
R T H
O O
D T
E X
A S
T
H A
IR
D
E F
E N
S E A
R T
IL
L E
R Y D
IV
IS
IO
N
P N
U .S
A R
M Y C
O R
P S O
F E
N G
IN
E E
R S
T
A Y
L O
R S
T
F O
R T W
O R
T H T
X
S U
P P
L Y S
U P
P O
R T A
C T
IV
IT
Y W
A R
E H
O U
S E
S o li c it a ti o n N o
C o n tr a c t
N o
Is s u e D a te
G
C H
O A
T E
G
C H
O A
T E
E N
G
IN
E E
R
IN
G B
R A
N C
H
C O
N S
T R
U C
T
IO
N D
IV
IS
IO
N
E N
G
IN
E E
R
IN
G
NUMBER
SHEET
D
B R
O W
N P .E
C H
IE
F E
L E
C T
R
IC
A L S
E C
T
IO
N D
A R
E N A
B R
O W
N P .E
W
G -1
-B -0
A U
G U
S T
KAIC = 22
RM 133
P O
W E
R R
IS
E R D
IA
G R
A M
EP601
A R
RM 133
RM 137
LAN/IT
RM 133RM 133
RM 141
SPARESPARESPARE
4 2
7 8 8
2 22
300A/3P
KAIC = 35
RM 133
A /3
P
A /3
P
A /3
P
A /3
P
RM 141
208Y/120V SEC.
480V PRI.
45 kVA
T2B
SPARE
A /3
P
480/277V
H1B
208Y/120V
L3B
208Y/120V
L2B
208Y/120V
L1B
208Y/120V
L4B
D M
D M
D M
RM 133
208Y/120V SEC.
480V PRI.
112.5 kVA
T1B
A /3
P
3 PHASE, WITH FULL NEUTRAL & GROUND BUSES
BUILDING MAIN DISTRIBUTION PANEL (MDP), 600A, 480/277V,
D M
EP602, 603
CONT. ON SHEETS
RM 133
120V SEC.
277 PRI.
3 kVA
TFA
A /1
P
SINGLE PHASE
120V
20A
ENCLOSED CB
GENERAL SHEET NOTES
SHEET KEYNOTES
4. CONT. ON SHEETS EP602, 603
SHEET ES101 FOR DETAILS.
CONTRACTOR; SEE ELECTRICAL
LINE SHALL BE INSTALLED BY
3. CONDUIT INSIDE THE BUILDING 5FT
REQUIREMENT
2. SEE SHEET EG601 FOR GROUDING
SPARES REQUIREMENT.
1. SEE PANEL SCHEDULES FOR
3-600-01.PAR 9-18.11.1.
PROTECTION SYSTEM PER UFC
LOCK-ON CIRCUIT BREAKER FOR FIRE 7.
PAR 3-2.7.d.
RED AND LOCKED PER UFC 3-520-01
CONTROL PANEL. LABELED, PAINTED
CIRCUIT BREAKER FOR FIRE ALARM 6.
CONDUIT INSTALLED BY DOMINION.
CT/PT, ENCLOSURE, WIRING AND 5.
CALCULATION PURPOSES.
DOMINION. 350KCMIL USED FOR
CONDUCTORS INSTALLED BY 4.
LOCATED IN ELECTRICAL ROOM.3.
LOYTEC L-IP EIA709 ROUTER .
ROUTED FROM ALL METERES TO A
LON CABLE IN 1/2" CONDUIT SHALL BE
METERS. A 2 CONDUCTOR #22 AWG
LONWORKS WNC WATTNODE
ALL DIGITAL METERS SHALL BE 2.
ENCLOSURE.
1. TO BE INSTALLED IN A NEMA 3R
600A/3P
MAIN
NF
60AF
UTILITY
500 kVA
TRANSFORMER
UTILITY
DS-1B
S P
D
SPD
LINE SIDE OF MAIN DISCONNECT
POINT OF DEMARCATION
MANUFACTURER
RATED PER
G
N
DOMINION
INSTALLED BY
WATTNODE
NOTE: REFER TO EG601 FOR WIRE SIZE.
MGB GROUND BUS
TO CONCRETE ENCASED REBAR
TO EXTERNAL GROUND ROD
TO EXTERNAL GROUND ROD
TO BUILDING STEEL COLUMN
INTERIOR METALLIC PIPE
INSTALLED BY DOMINION
NEMA 1 ENCLOSURE
FUSED DISCONNECT SWITCH
EP601 N.T.S.
RISER DIAGRAM - AREA B
TO TMGB
3 #1/0 & 1 #6 GND IN 2" C
2 SETS OF (4 #350 KcMIL IN 4" C) & ONE 4" CONDUIT SPARE
4 #350 KcMIL & 1 #2 GND IN 3" C
4 #4 & 1 #10 GND IN 1-1/2" C
3 #2 & 1 #8 GND IN 1-1/2" C
4 #1/0 & 1 #6 GND IN 2" C
4 #2/0 & 1 #6 GND IN 2" C
4 #1 & 1 #8 GND IN 1-1/2" C
3 #4/0 & 1 #2 GND IN 2-1/2" C
A P
P R
D A
T E
D E
S C
R
IP
T
IO
N S
Y M
$FILEL$
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
$DATE$ $TIME$
S u b m it te d b y
C h e c k e d b y
D ra w n b y
D e s ig n e d b y
P L
O T D
A T
E
P L
O T S
C A
L E
F O
R T H
O O
D T
E X
A S
T
H A
IR
D
E F
E N
S E A
R T
IL
L E
R Y D
IV
IS
IO
N
P N
U .S
A R
M Y C
O R
P S O
F E
N G
IN
E E
R S
T
A Y
L O
R S
T
F O
R T W
O R
T H T
X
S U
P P
L Y S
U P
P O
R T A
C T
IV
IT
Y W
A R
E H
O U
S E
S o li c it a ti o n N o
C o n tr a c t
N o
Is s u e D a te
G
C H
O A
T E
G
C H
O A
T E
E N
G
IN
E E
R
IN
G B
R A
N C
H
C O
N S
T R
U C
T
IO
N D
IV
IS
IO
N
E N
G
IN
E E
R
IN
G
NUMBER
SHEET
D
B R
O W
N P .E
C H
IE
F E
L E
C T
R
IC
A L S
E C
T
IO
N D
A R
E N A
B R
O W
N P .E
W
G -1
-B -0
J U
N E
P O
W E
R R
IS
E R D
IA
G R
A M
EP602
A R
DISTRIBUTION PANEL WITH FULL NEUTRAL & GROUND BUSES
LDPA, 300A, 208/120V, 3 PHASE,
RM 110
KAIC = 22
RM 133
GROUDING REQUIREMENT
2. SEE SHEET EG601 FOR
REQUIREMENT.
FOR SPARES
1. SEE PANEL SCHEDULES
SHEET KEYNOTES
GENERAL SHEET NOTES
ROOM.
LOCATED IN ELECTRICAL 3.
L-IP EIA709 ROUTER .
METERES TO A LOYTEC
ROUTED FROM ALL
CONDUIT SHALL BE
LON CABLE IN 1/2"
CONDUCTOR #22 AWG
METERS. A 2
WNC WATTNODE
SHALL BE LONWORKS
ALL DIGITAL METERS 2.
NEMA 3R ENCLOSURE.
1. TO BE INSTALLED IN A
RM 114
LAN/IT
SPARE
FROM MDP
SPARE
9 8
7 8 8
2 2 2
300A/3P
SPARE
RM 110
A /3
P
A /3
P
A /3
P
A /3
P
SPARE
480/277V
H1A
A /3
P
208Y/120V SEC.
480V PRI.
45 kVA
T2A
D M
D M
D M
208Y/120V SEC.
480V PRI.
112.5 kVA
T1A
A /3
P
SHEET EP601
CONT. FROM
RM 110
208Y/120V
L1A
208Y/120V
L2A
208Y/120V
L3A
208Y/120V
L4A
RM 110
NF
60AF
DS-1A
EP602 N.T.S.
RISER DIAGRAM - AREA A
RM 118
3 #1/0 & 1 #6 GND IN 2" C
2 SETS OF (4 #350 KcMIL IN 4" C) & ONE 4" CONDUIT SPARE
4 #350 KcMIL & 1 #2 GND IN 3" C
4 #4 & 1 #10 GND IN 1-1/2" C
3 #2 & 1 #8 GND IN 1-1/2" C
4 #1/0 & 1 #6 GND IN 2" C
4 #2/0 & 1 #6 GND IN 2" C
4 #1 & 1 #8 GND IN 1-1/2" C
3 #4/0 & 1 #2 GND IN 2-1/2" C
DISTRIBUTION PANEL WITH FULL NEUTRAL & GROUND BUSES
LDPC, 400A, 208/120V, 3 PHASE,
KAIC = 22
RM 133
RM 133
RM 160
LAN/IT
SPARE
FROM MDP
SPARE
4 2
7 8 8
2 2 2
US Army Corps of Engineers
A P
P R
D A
T E
D E
S C
R
IP
T
IO
N S
Y M
$FILEL$
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
$DATE$ $TIME$
S u b m it te d b y
C h e c k e d b y
D ra w n b y
D e s ig n e d b y
P L
O T D
A T
E
P L
O T S
C A
L E
F O
R T H
O O
D T
E X
A S
T
H A
IR
D
E F
E N
S E A
R T
IL
L E
R Y D
IV
IS
IO
N
P N
U .S
A R
M Y C
O R
P S O
F E
N G
IN
E E
R S
T
A Y
L O
R S
T
F O
R T W
O R
T H T
X
S U
P P
L Y S
U P
P O
R T A
C T
IV
IT
Y W
A R
E H
O U
S E
S o li c it a ti o n N o
C o n tr a c t
N o
Is s u e D a te
G
C H
O A
T E
G
C H
O A
T E
E N
G
IN
E E
R
IN
G B
R A
N C
H
C O
N S
T R
U C
T
IO
N D
IV
IS
IO
N
E N
G
IN
E E
R
IN
G
NUMBER
SHEET
D
B R
O W
N P .E
C H
IE
F E
L E
C T
R
IC
A L S
E C
T
IO
N D
A R
E N A
B R
O W
N P .E
W
G -1
-B -0
J U
N E
300A/3P
SPARE
RM 133
A /3
P
A /3
P
A /3
P
A /3
P
SPARE
480/277V
H1C
A /3
P
208Y/120V SEC.
480V PRI.
45 kVA
T2C
D M
D M
D M
208Y/120V SEC.
480V PRI.
112.5 kVA
T1C
A /3
P
GROUDING REQUIREMENT
2. SEE SHEET EG601 FOR
REQUIREMENT.
FOR SPARES
1. SEE PANEL SCHEDULES
SHEET KEYNOTES
GENERAL SHEET NOTES
ROOM.
LOCATED IN ELECTRICAL 3.
L-IP EIA709 ROUTER .
METERES TO A LOYTEC
ROUTED FROM ALL
CONDUIT SHALL BE
LON CABLE IN 1/2"
CONDUCTOR #22 AWG
METERS. A 2
WNC WATTNODE
SHALL BE LONWORKS
ALL DIGITAL METERS 2.
NEMA 3R ENCLOSURE.
1. TO BE INSTALLED IN A
P O
W E
R R
IS
E R D
IA
G R
A M
EP603
A R
SHEET EP601
CONT. FROM
RM 133 RM 133
208Y/120V
L1C
208Y/120V
L2C
208Y/120V
L3C
208Y/120V
L4C
NF
60AF
DS-1C
RM 163
1 1 1
EP603 N.T.S.
RISER DIAGRAM - AREA C
MECHANICAL EQUIPMENT CONNECTION SCHEDULE
EQUIPMENT TAG SAFETY SWITCH WIRE SIZE NOTES
PAHU-1/A,B,C 60A, 240V, 3P, NEMA 3R 3 #6 & 1 #10 GND IN 1-1/2" C.
DWH-1A, 1B, 1C 30A, 125V, 1P, NEMA 1 2 #12 & 1 #12 GND IN 1/2" C.
GFUH-1A, THRU 6A 30A, 125V, 1P, NEMA 1 2 #12 & 1 #12 GND IN 1/2" C.
GFUH-1B, THRU 7B 30A, 125V, 1P, NEMA 1 2 #12 & 1 #12 GND IN 1/2" C.
GFUH-1C, THRU 6C 30A, 125V, 1P, NEMA 1 2 #12 & 1 #12 GND IN 1/2" C.
EUH-1A, THRU 3A 30A, 240V, 3P, NEMA 1 3 #10 & 1 #10 GND IN 1" C.
EUH-1B, THRU 3B 30A, 240V, 3P, NEMA 1 3 #10 & 1 #10 GND IN 1" C.
EUH-1C AND 2C 30A, 240V, 3P, NEMA 1 3 #10 & 1 #10 GND IN 1" C.
ERV-1A, 1B, 1C 30A, 240V, 3P, NEMA 1 3 #12 & 1 #12 GND IN 3/4" C.
REF-1A, 1B, 1C 30A, 125V, 1P, NEMA 1 2 #12 & 1 #12 GND IN 1/2" C.
REF-2A, 2B, 2C 30A, 240V, 3P, NEMA 1 3 #12 & 1 #12 GND IN 3/4" C.
REF-3A, 3B, 3C 30A, 240V, 3P, NEMA 1 3 #12 & 1 #12 GND IN 3/4" C.
EF-1A, 1B, 1C 30A, 125V, 1P, NEMA 1 2 #12 & 1 #12 GND IN 1/2" C.
EF-3B 30A, 125V, 1P, NEMA 1 2 #12 & 1 #12 GND IN 1/2" C.
IRH-1A, 2A, 3A & 4A 30A, 125V, 1P, NEMA 1 2 #12 & 1 #12 GND IN 1/2" C.
IRH-1B, 2B, 3B 30A, 125V, 1P, NEMA 1 2 #12 & 1 #12 GND IN 1/2" C.
IRH-1C, 2C, 3C & 4C 30A, 125V, 1P, NEMA 1 2 #12 & 1 #12 GND IN 1/2" C.
F-1A, 1B, 1C 30A, 240V, 3P, NEMA 1 3 #12 & 1 #12 GND IN 3/4" C.
CRAC-1A, 1B, 1C 30A, 240V, 3P, NEMA 1 3 #12 & 1 #12 GND IN 3/4" C. 1
CRCU-1A, 1B, 1C 30A, 240V, 3P, NEMA 3R 3 #12 & 1 #12 GND IN 3/4" C. 1
NOTES:
1. INDOOR & OUTDOOR UNITS ARE CONNECTED TO THE SAME CIRCUIT.
US Army Corps of Engineers
A P
P R
D A
T E
D E
S C
R
IP
T
IO
N S
Y M
$FILEL$
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
$DATE$ $TIME$
S u b m it te d b y
C h e c k e d b y
D ra w n b y
D e s ig n e d b y
P L
O T D
A T
E
P L
O T S
C A
L E
F O
R T H
O O
D T
E X
A S
T
H A
IR
D
E F
E N
S E A
R T
IL
L E
R Y D
IV
IS
IO
N
P N
U .S
A R
M Y C
O R
P S O
F E
N G
IN
E E
R S
T
A Y
L O
R S
T
F O
R T W
O R
T H T
X
S U
P P
L Y S
U P
P O
R T A
C T
IV
IT
Y W
A R
E H
O U
S E
S o li c it a ti o n N o
C o n tr a c t
N o
Is s u e D a te
G
C H
O A
T E
G
C H
O A
T E
E N
G
IN
E E
R
IN
G B
R A
N C
H
C O
N S
T R
U C
T
IO
N D
IV
IS
IO
N
E N
G
IN
E E
R
IN
G
NUMBER
SHEET
D
B R
O W
N P .E
C H
IE
F E
L E
C T
R
IC
A L S
E C
T
IO
N D
A R
E N A
B R
O W
N P .E
W
G -1
-B -0
J U
N E
EP604
M E
C H E
Q U
IP
M E
N T C
O N
N E
C T
IO
N S
C H
E D
U
A P
P R
D A
T E
D E
S C
R
IP
T
IO
N S
Y M
$FILEL$
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
$DATE$ $TIME$
S u b m it te d b y
C h e c k e d b y
D ra w n b y
D e s ig n e d b y
P L
O T D
A T
E
P L
O T S
C A
L E
F O
R T H
O O
D T
E X
A S
T
H A
IR
D
E F
E N
S E A
R T
IL
L E
R Y D
IV
IS
IO
N
P N
U .S
A R
M Y C
O R
P S O
F E
N G
IN
E E
R S
T
A Y
L O
R S
T
F O
R T W
O R
T H T
X
S U
P P
L Y S
U P
P O
R T A
C T
IV
IT
Y W
A R
E H
O U
S E
S o li c it a ti o n N o
C o n tr a c t
N o
Is s u e D a te
G
C H
O A
T E
G
C H
O A
T E
E N
G
IN
E E
R
IN
G B
R A
N C
H
C O
N S
T R
U C
T
IO
N D
IV
IS
IO
N
E N
G
IN
E E
R
IN
G
NUMBER
SHEET
D
B R
O W
N P .E
C H
IE
F E
L E
C T
R
IC
A L S
E C
T
IO
N D
A R
E N A
B R
O W
N P .E
W
G -1
-B -0
J U
N E
EP701
P A
R T I
P A
N E
L S
C H
E D
U L E
S
Fort Worth District
PANEL MDP
480/277VOLT, 3 PHASE, 4 WIRE 600AMP MCB Location: Electrical Rm 133
35KAIC BRANCH CIRCUIT
SERVED
LOAD
LOAD
PHASE
CKT BKR PHASE CKT BKR
LOAD
PHASE
SERVED
LOAD
# AMP P A B C AMP P #
SPD 10 1 100 3 A 60 3 2 10218 PANEL H1A
- 10 3 - - B - - 4 10910 -
- 10 5 - - C - - 6 8851 -
PANEL H1B 10082 7 60 3 A 60 3 8 10228 PANEL H1C
- 11033 9 - - B - - 10 10910 -
- 9604 11 - - C - - 12 8851 -
SPARE 13 100 3 A 50 3 14 10717 T2A
- 15 - - B - - 16 9599 -
- 17 - - C - - 18 10319 -
T1A 29058 19 125 3 A 50 3 20 11053 T2B
- 29393 21 - - B - - 22 9239 -
- 27538 23 - - C - - 24 9383 -
T1B 29574 25 125 3 A 50 3 26 10717 T2C
- 30393 27 - - B - - 28 9239 -
- 27538 29 - - C - - 30 9959 -
T1C 26752 31 125 3 A 100 3 32 SPARE
- 27267 33 - - B - - 34 -
- 25413 35 - - C - - 36 -
SPARE 37 60 3 A 60 3 38 SPARE
- 39 - - B - - 40 -
- 41 - - C - - 42 -
CONNECTED LOAD
DESCRIPTION
LOAD CONNECTED KVA
KVA
DEMAND
NON-CONT CONT
PHASE A KVA 148 TOTAL CONNECTED KVA 434 LIGHTING 91 113
PHASE B KVA 148 ESTIMATED DEMAND KVA 403 RECEPTACLES 116 63
PHASE C KVA 137 ESTIMATED DEMAND AMPS 485 MOTORS
TRANSFORMERS 227 227
KITCHEN
OTHER
PANEL LDPB
208/120VOLT, 3 PHASE, 4 WIRE 300AMP MCB Location: Electrical Rm 133
22KAIC BRANCH CIRCUIT
(Area B loads)
SERVED
LOAD
LOAD
PHASE
CKT BKR PHASE CKT BKR
LOAD
PHASE
SERVED
LOAD
# AMP P A B C AMP P #
PANEL L1B 16058 1 175 3 A 100 3 2 6240PANEL L2B
- 15143 3 - - B - - 4 8660-
- 15142 5 - - C - - 6 7800-
PANEL L3B 7276 7 100 3 A 60 3 8 SPARE
- 6590 9 - - B - - 10 -
- 4596 11 - - C - - 12 -
SPARE 13 60 3 A 60 3 14 SPARE
- 15 - - B - - 16 -
- 17 - - C - - 18 -
19 A 20
21 B 22
23 C 24
25 A 26
27 B 28
29 C 30
31 A 32
33 B 34
35 C 36
37 A 38
39 B 40
41 C 42
CONNECTED LOAD
DESCRIPTION
LOAD CONNECTED KVA
KVA
DEMAND
NON-CONT CONT
PHASE A KVA 30 TOTAL CONNECTED KVA 88 LIGHTING
PHASE B KVA 30 ESTIMATED DEMAND KVA 84 RECEPTACLES 41 26
PHASE C KVA 28 ESTIMATED DEMAND AMPS 233 MOTORS 46 58
TRANSFORMERS
KITCHEN
OTHER
PANEL H1B
480/277VOLT, 3 PHASE, 4 WIRE 60AMP MCB Location: Electrical Rm 133
14KAIC BRANCH CIRCUIT
(Area B loads)
SERVED
LOAD
LOAD
PHASE
CKT BKR PHASE CKT BKR
LOAD
PHASE
SERVED
LOAD
# AMP P A B C AMP P #
LTS: Warehouse 810 1 20 1 A 20 1 2 648 LTS: Rm 139,144
LTS: Warehouse 648 3 20 1 B 20 1 4 134 LTS: Rm 136, 140
SPARE 5 20 1 C 20 1 6 124 LTS: Rm 138
SPARE 7 20 1 A 20 1 8 126 LTS: Rm 126, 128, 129
LTS: Rms 130,131 72 9 20 1 B 20 1 10 123 LTS: Rms 132,133,134
LTS: Rms 135,142,143 115 11 20 1 C 20 1 12 180 LTS: Rm 124, 125, 127
LTS: Rm 137 62 13 20 1 A 20 1 14 SPARE
SPARE 15 20 1 B 20 1 16 SPARE
SPARE 17 20 1 C 20 1 18 60 Emergency Exit Lights
Forklift Battery Charger (Rm 143) 4200 19 30 3 A 30 3 20 4200 Forklift Battery Charger (Rm 143)
- 4200 21 - - B - - 22 4200 -
- 4200 23 - - C - - 24 4200 -
LTS: Dock Lights 36 25 20 A 20 1 26 SPARE
LTS: Dock Lights 36 27 20 B 20 1 28 1620 LTS: Covered Hardstand B
SPARE 29 20 C 20 1 30 725 LTS: Building Exterior Lights
31 A 32
33 B 34
35 C 36
37 A 38
39 B 40
41 C 42
CONNECTED LOAD
DESCRIPTION
LOAD CONNECTED KVA
KVA
DEMAND
NON-CONT CONT
PHASE A KVA 10 TOTAL CONNECTED KVA 31 LIGHTING 6 7
PHASE B KVA 11 ESTIMATED DEMAND KVA 38 RECEPTACLES 25 32
PHASE C KVA 10 ESTIMATED DEMAND AMPS 46 MOTORS
TRANSFORMERS
KITCHEN
OTHER
A P
P R
D A
T E
D E
S C
R
IP
T
IO
N S
Y M
S u b m it te d b y
C h e c k e d b y
D ra w n b y
D e s ig n e d b y
P L
O T D
A T
E
P L
O T S
C A
L E
F O
R T H
O O
D T
E X
A S
T
H A
IR
D
E F
E N
S E A
R T
IL
L E
R Y D
IV
IS
IO
N
P N
U .S
A R
M Y C
O R
P S O
F E
N G
IN
E E
R S
T
A Y
L O
R S
T
F O
R T W
O R
T H T
X
S U
P P
L Y S
U P
P O
R T A
C T
IV
IT
Y W
A R
E H
O U
S E
S o li c it a ti o n N o
C o n tr a c t
N o
Is s u e D a te
G
C H
O A
T E
G
C H
O A
T E
E N
G
IN
E E
R
IN
G B
R A
N C
H
C O
N S
T R
U C
T
IO
N D
IV
IS
IO
N
E N
G
IN
E E
R
IN
G
NUMBER
SHEET
D
B R
O W
N P .E
C H
IE
F E
L E
C T
R
IC
A L S
E C
T
IO
N D
A R
E N A
B R
O W
N P .E
W
G -1
-B -0
A U
G U
S T
EP702
P A
R T I I
P A
N E
L S
C H
E D
U L E
S
PANEL L4B
208/120VOLT, 3 PHASE, 4 WIRE 125AMP MCB Location: WRHSE Rm 141
10KAIC BRANCH CIRCUIT
LOAD
SERVED
PHASE
LOAD
CKT BKR PHASE CKT BKR
PHASE
LOAD
LOAD
SERVED# AMP P A B C AMP P #
GFUH-1B,2B,3B (1/30HP, 2.8FLA) 1,008 1 20 1 A 20 3 2 691 MTR: OVRHD DOOR-2B (1HP)
GFUH-4B,5B (1/30HP, 2.8FLA) 672 3 20 1 B - - 4 691 -
GFUH-6B,7B (1/30HP, 2.8FLA) 672 5 20 1 C - - 6 691 -
SPARE 7 20 1 A 20 3 8 691 MTR: OVRHD DOOR-4B (1HP)
IRH-1B,2B (120V, 5A) 1,152 9 20 1 B - - 10 691 -
IRH-3B (120V, 5A) 576 11 20 1 C - - 12 691 -
MTR: OVRHD DOOR-1B (1HP) 691 13 20 3 A 20 3 14 973 F-1B (2HP, 8.1FLA)
- 691 15 - - B - - 16 973 -
- 691 17 - C - - 18 973 -
MTR: OVRHD DOOR-3B (1HP) 691 19 20 3 A 20 1 20 1080 RCPT: Rm 144, 145
- 691 21 - - B 20 1 22 720 RCPT: Rm 141, Extr
- 691 23 - - C 20 1 24 540 RCPT: Rm 145,Extr
MTR: OVRHD DOOR-5B (1HP) 691 25 20 3 A 20 1 26 SPARE
- 691 27 - - B 20 1 28 SPARE
- 691 29 - - C 20 1 30 900 RCPT: Rm 139, Extr
DOCK SAFETY LIGHT #1B 350 31 20 1 A 20 1 32 1920 DOCK LEVELER-1B
DOCK SAFETY LIGHT #2B 350 33 20 1 B 20 1 34 1920 DOCK LEVELER-2B
DOCK SAFETY LIGHT #3B 350 35 20 1 C 20 1 36 1920 DOCK LEVELER-3B
DOCK SAFETY LIGHT #4B 350 37 20 1 A 20 1 38 1920 DOCK LEVELER-4B
SPARE 39 20 1 B 20 1 40 SPARE
SPARE 41 20 1 C 20 1 42 SPARE
CONNECTED LOAD LOAD
DESCRIPTION
CONNECTED KVA DEMAND
KVA NON-CONT CONT
PHASE A KVA 11 TOTAL CONNECTED KVA 30 LIGHTING 1 2
PHASE B KVA 9 ESTIMATED DEMAND KVA 31 RECEPTACLES 3 3
PHASE C KVA 9 ESTIMATED DEMAND AMPS 87 MOTORS 21 22
TRANSFORMERS
KITCHEN
OTHER 4 4
Fort Worth District
PANEL L1B
208/120VOLT, 3 PHASE, 4 WIRE 225AMP MLO Location: Electrical Rm 133
10KAIC BRANCH CIRCUIT
(Area B loads)
LOAD
SERVED
PHASE
LOAD
CKT BKR PHASE CKT BKR
PHASE
LOAD
LOAD
SERVED# AMP P A B C AMP P #
PAHU-1B (Exterior of Rm 133) 5092 1 50 3 A 20 1 2 915 REF-1B (Rm 143)
- 5092 3 - - B 20 1 4 696 EF-1B
- 5092 5 - - C 20 1 6 696 EF-2B
EUH-1B (Rm 143) 2558 7 25 3 A 15 3 8 552 REF-2B (Rm 141)
- 2558 9 - - B - - 10 552 -
- 2558 11 - - C - - 12 552 -
EUH-2B (Rm 142) 2558 13 25 3 A 15 3 14 552 REF-3B (Rm 141)
- 2558 15 - - B - - 16 552 -
- 2558 17 - - C - - 18 552 -
EUH-3B (Rm 133) 2558 19 25 3 A 15 1 20 696 EF-3B
- 2558 21 - - B 20 1 22 SPARE
- 2558 23 - - C 20 1 24 SPARE
MTR: ERV-1B (Rm 141) 576 25 15 3 A 25 3 26 SPARE
- 576 27 - - B - - 28 -
- 576 29 - - C - - 30 -
SPARE 31 20 1 A 20 1 32 SPARE
SPARE 33 20 1 B 20 1 34 SPARE
SPARE 35 20 1 C 20 1 36 SPARE
SPACE 37 A 38 SPACE
SPACE 39 B 40 SPACE
SPACE 41 C 42 SPACE
CONNECTED LOAD LOAD
DESCRIPTION
CONNECTED KVA DEMAND
KVA NON-CONT CONT
PHASE A KVA 16 TOTAL CONNECTED KVA 46 LIGHTING
PHASE B KVA 15 ESTIMATED DEMAND KVA 50 RECEPTACLES
PHASE C KVA 15 ESTIMATED DEMAND AMPS 139 MOTORS 46 50
TRANSFORMERS
KITCHEN
OTHER
PANEL L3B
208/120VOLT, 3 PHASE, 4 WIRE 100AMP MCB Location: LAN/IT Rm 137
10KAIC BRANCH CIRCUIT
(Area B loads)
LOAD
SERVED
PHASE
LOAD
CKT BKR PHASE CKT BKR
PHASE
LOAD
LOAD
SERVED# AMP P A B C AMP P #
SPD 10 1 30 3 A 15 1 2 180 Security J-Box
- 10 3 - - B 20 1 4 540 RCPT: RM 137
- 10 5 - - C 20 1 6 SPARE
EQPMNT RACK 1 (RM 137) 2000 7 20 2 A 20 2 8 2000 EQPMNT RACK 2 (RM 137)
- 2000 9 - - B - - 10 2000 -
11 - C 20 1 12 1500 RCPT: RACK 1
ILON 13 20 1 A 20 1 14 1500 RCPT: RACK 2
RCPT: RACK 1 1500 15 20 1 B 20 1 16 540 RCPT: RM 137
RCPT: RACK 2 1500 17 20 1 C 25 2 18 1586 CRAC/CRCU-1B (RM 137, Ext 125)
SPARE 19 20 1 A - - 20 1586 -
SPARE 21 20 1 B 20 1 22 SPARE
SPARE 23 20 1 C 20 1 24 SPARE
25 A 26
27 B 28
29 C 30
31 A 32
33 B 34
35 C 36
37 A 38
39 B 40
41 C 42
CONNECTED LOAD LOAD
DESCRIPTION
CONNECTED KVA DEMAND
KVA NON-CONT CONT
PHASE A KVA 7 TOTAL CONNECTED KVA 18 LIGHTING
PHASE B KVA 7 ESTIMATED DEMAND KVA 17 RECEPTACLES 15 13
PHASE C KVA 5 ESTIMATED DEMAND AMPS 47 MOTORS 3 4
TRANSFORMERS
KITCHEN
OTHER 0 0
PANEL L2B
208/120VOLT, 3 PHASE, 4 WIRE 100AMP MLO Location: Electrical Rm 133
10KAIC BRANCH CIRCUIT
(Area B loads)
LOAD
SERVED
PHASE
LOAD
CKT BKR PHASE CKT BKR
PHASE
LOAD
LOAD
SERVED# AMP P A B C AMP P #
RCPT: Corrdr 127, Rm 133, Extr 540 1 20 1 A 20 1 2 1080 RCPT: RM 131
RCPT: RM 140, 141 900 3 20 1 B 20 1 4 1000 RCPT: Water Fountn (Corrdr 127)
RCPT: Covered Hardstand-B 180 5 20 1 C 20 1 6 540 RCPT: Rms 132, 134, 135
RCPT: RM 136 720 7 20 1 A 20 1 8 1200 RCPT: Copier (Corrdr 127)
RCPT: Srvc Mdule (Rm 136) 720 9 20 1 B 20 1 10 1200 RCPT: Copier (RM 138)
RCPT: RM 136 720 11 20 1 C 20 1 12 1200 RCPT: Copier (RM 126)
RCPT: RM 130 1080 13 20 1 A 20 1 14 720 RCPT: RM 138
RCPT: RM 126 540 15 20 1 B 20 1 16 900 RCPT: RM 138
RCPT: RM 126 900 17 20 1 C 20 1 18 1080 RCPT: RM 129
RCPT: RM 125 900 19 20 1 A 20 1 20 SPARE
RCPT: Corrdr 127, Rm 124, Extr 900 21 20 1 B 20 1 22 SPARE
RCPT: RM 128 1080 23 20 1 C 20 1 24 600 RCPT: DWH-B (Rm 142)
RCPT: WH 25 20 1 A 20 1 26 SPARE
RCPT: Vending (Wrhse) 1500 27 20 1 B 20 1 28 1000 FACP
RCPT: Vending (Wrhse) 1500 29 20 1 C 20 1 30 SPARE
SPACE 31 1 A 32 SPACE
SPACE 33 1 B 34 SPACE
SPACE 35 1 C 36 SPACE
SPACE 37 A 38 SPACE
SPACE 39 B 40 SPACE
SPACE 41 C 42 SPACE
CONNECTED LOAD LOAD
DESCRIPTION
CONNECTED KVA DEMAND
KVA NON-CONT CONT
PHASE A KVA 6 TOTAL CONNECTED KVA 23 LIGHTING
PHASE B KVA 9 ESTIMATED DEMAND KVA 15 RECEPTACLES 19 14
PHASE C KVA 8 ESTIMATED DEMAND AMPS 43 MOTORS
TRANSFORMERS
KITCHEN
OTHER 1 1
A P
P R
D A
T E
D E
S C
R
IP
T
IO
N S
Y M
$FILEL$
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
$DATE$ $TIME$
S u b m it te d b y
C h e c k e d b y
D ra w n b y
D e s ig n e d b y
P L
O T D
A T
E
P L
O T S
C A
L E
F O
R T H
O O
D T
E X
A S
T
H A
IR
D
E F
E N
S E A
R T
IL
L E
R Y D
IV
IS
IO
N
P N
U .S
A R
M Y C
O R
P S O
F E
N G
IN
E E
R S
T
A Y
L O
R S
T
F O
R T W
O R
T H T
X
S U
P P
L Y S
U P
P O
R T A
C T
IV
IT
Y W
A R
E H
O U
S E
S o li c it a ti o n N o
C o n tr a c t
N o
Is s u e D a te
G
C H
O A
T E
G
C H
O A
T E
E N
G
IN
E E
R
IN
G B
R A
N C
H
C O
N S
T R
U C
T
IO
N D
IV
IS
IO
N
E N
G
IN
E E
R
IN
G
NUMBER
SHEET
D
B R
O W
N P .E
C H
IE
F E
L E
C T
R
IC
A L S
E C
T
IO
N D
A R
E N A
B R
O W
N P .E
W
G -1
-B -0
A U
G U
S T
EP703
P A
R T I
II
P A
N E
L S
C H
E D
U L E
S
PANEL H1A
480/277VOLT, 3 PHASE, 4 WIRE 60AMP MCB Location: Electrical Rm 110
14KAIC BRANCH CIRCUIT
LOAD
SERVED
PHASE
LOAD
CKT BKR PHASE CKT BKR
PHASE
LOAD
LOAD
SERVED# AMP P A B C AMP P #
LTS: Warehouse 810 1 20 1 A 20 1 2 648 LTS: Rms 116,121
LTS: Warehouse 648 3 20 1 B 20 1 4 SPARE
SPARE 5 20 1 C 20 1 6 124 LTS: Rm 115
LTS: Rms 109, 110, 111,123 136 7 20 1 A 20 1 8 126 LTS: Rm 102, 105, 106
LTS: Rms 107, 108 72 9 20 1 B 20 1 10 134 LTS: Rm 113, 117
LTS: Rms 112, 120 97 11 20 1 C 20 1 12 170 LTS: Rm 101, 103, 104
LTS: Rm 114 62 13 20 1 A 20 1 14 SPARE
SPARE 15 20 1 B 20 1 16 SPARE
SPARE 17 20 1 C 20 1 18 60 Emergency Exit Lights
Forklift Battery Charger (Rm 120) 4200 19 30 3 A 30 3 20 4200 Forklift Battery Charger (Rm 120)
- 4200 21 - - B - - 22 4200 -
- 4200 23 - - C - - 24 4200 -
LTS: Dock Lights 36 25 20 1 A 20 1 26 SPARE
LTS: Dock Lights 36 27 20 1 B 20 1 28 1620 LTS: Covered Hardstand A
SPARE 29 20 1 C 20 1 30 SPARE
31 A 32
33 B 34
35 C 36
37 A 38
39 B 40
41 C 42
CONNECTED LOAD
LOAD
DESCRIPTION
CONNECTED KVA DEMAND
KVA NON-CONT CONT
PHASE A KVA 10 TOTAL CONNECTED KVA 30 LIGHTING 5 6
PHASE B KVA 11 ESTIMATED DEMAND KVA 41 RECEPTACLES
PHASE C KVA 9 ESTIMATED DEMAND AMPS 49 MOTORS 25 35
TRANSFORMERS
KITCHEN
OTHER
PANEL LDPA
208/120VOLT, 3 PHASE, 4 WIRE 300AMP MCB Location: Electrical Rm 110
22KAIC BRANCH CIRCUIT
LOAD
SERVED
PHASE
LOAD
CKT BKR PHASE CKT BKR
PHASE
LOAD
LOAD
SERVED# AMP P A B C AMP P #
PANEL L1A 15362 1 175 3 A 100 3 2 6420 PANEL L2A
- 15143 3 - - B - - 4 7660 -
- 15142 5 - - C - - 6 7800 -
PANEL L3A 7276 7 100 3 A 60 3 8 SPARE
- 6590 9 - - B - - 10 -
- 4596 11 - - C - - 12 -
SPARE 13 60 3 A 60 3 14 SPARE
- 15 - - B - - 16 -
- 17 - - C - - 18 -
19 A 20
21 B 22
23 C 24
25 A 26
27 B 28
29 C 30
31 A 32
33 B 34
35 C 36
37 A 38
39 B 40
41 C 42
CONNECTED LOAD
LOAD
DESCRIPTION
CONNECTED KVA DEMAND
KVA NON-CONT CONT
PHASE A KVA 29 TOTAL CONNECTED KVA 86 LIGHTING
PHASE B KVA 29 ESTIMATED DEMAND KVA 82 RECEPTACLES 40 25
PHASE C KVA 28 ESTIMATED DEMAND AMPS 229 MOTORS 46 57
TRANSFORMERS
KITCHEN
OTHER
PANEL L1A
208/120VOLT, 3 PHASE, 4 WIRE 225AMP MLO Location: Electrical Rm 110
10KAIC BRANCH CIRCUIT
LOAD
SERVED
PHASE
LOAD
CKT BKR PHASE CKT BKR
PHASE
LOAD
LOAD
SERVED# AMP P A B C AMP P #
PAHU-1A 5092 1 50 3 A 20 1 2 915 REF-1A (Rm 120)
- 5092 3 50 - B 20 1 4 696 EF-1A
- 5092 5 50 - C 20 1 6 696 EF-2A
EUH-1A (Rm 123) 2558 7 25 3 A 35 3 8 552 REF-2A (Rm 118)
- 2558 9 25 - B 35 - 10 552 -
- 2558 11 25 - C 35 - 12 552 -
EUH-2A (Rm 110) 2558 13 25 3 A 15 3 14 552 REF-3A (Rm 118)
- 2558 15 25 - B 15 - 16 552 -
- 2558 17 25 - C 15 - 18 552 -
EUH-3A (Rm 120) 2558 19 25 3 A 20 3 20 SPARE
- 2558 21 25 - B - - 22 -
- 2558 23 25 - C - - 24 -
MTR: ERV-1A (Rm 118) 576 25 15 3 A 20 1 26 SPARE
- 576 27 - - B 20 1 28 SPARE
- 576 29 - - C 20 1 30 SPARE
SPARE 31 20 1 A 20 1 32 SPARE
SPARE 33 20 1 B 20 1 34 SPARE
SPARE 35 20 1 C 20 1 36 SPARE
SPACE ONLY 37 A 38 SPACE ONLY
SPACE ONLY 39 B 40 SPACE ONLY
SPACE ONLY 41 C 42 SPACE ONLY
CONNECTED LOAD LOAD
DESCRIPTION
CONNECTED KVA DEMAND
KVA NON-CONT CONT
PHASE A KVA 15 TOTAL CONNECTED KVA 46 LIGHTING
PHASE B KVA 15 ESTIMATED DEMAND KVA 49 RECEPTACLES
PHASE C KVA 15…