A1.2_Drawings_Part6.pdf

PDF 9 MB Posted

Attached to
Fort Hood 69th ADA SSA Warehouse Federal contract opportunity
Solicitation number
W9126G19B0029
Issued by
Department of the Army Corps of Engineers Engineering District Fort Worth

About this file

This package includes construction drawings and specifications for a new 69th ADA SSA Warehouse project at Fort Hood, Texas. The project involves construction of a new warehouse facility including architectural, structural, fire protection, fire alarm, and plumbing systems. The solicitation number is W9126G19B0029 and was issued by the U.S. Army Corps of Engineers Fort Worth District for the Department of the Army. The response due date is not provided. The drawings depict site plans, floor plans, sections, and details of building systems. Specifications reference applicable codes and standards.

Part 6 of 10

View the file

Other files for this federal contract opportunity

Other files attached to Fort Hood 69th ADA SSA Warehouse, newest first.
File Type Posted
C1_Bid_Abstract_19B0029.pdf PDF
Amendment_3.pdf PDF
Amendment_2.pdf PDF
Amendment_1.pdf PDF
G2_W9126G19B0029.pdf PDF
A1.2_Drawings_Part1.pdf PDF
A1.2_Drawings_Part4.pdf PDF
A1.2_Drawings_Part10.pdf PDF
A1.2_Drawings_Part8.pdf PDF
A1.2_Drawings_Part9.pdf PDF
A1.2_Drawings_Part5.pdf PDF
A1.2_Drawings_Part2.pdf PDF
A1.2_Drawings_Part3.pdf PDF
A1.2_Drawings_Part7.pdf PDF
G2.20_W9126G19B0029.pdf PDF
Show all 15

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

US Army Corps of Engineers

A P

P R

D A

T E

D E

S C

R

IP

T

IO

N S

Y M

$FILEL$

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

$DATE$ $TIME$

KEY PLAN

A B C

S u b m it te d b y

C h e c k e d b y

D ra w n b y

D e s ig n e d b y

P L

O T D

A T

E

P L

O T S

C A

L E

F O

R T H

O O

D T

E X

A S

T

H A

IR

D

E F

E N

S E A

R T

IL

L E

R Y D

IV

IS

IO

N

P N

U .S

A R

M Y C

O R

P S O

F E

N G

IN

E E

R S

T

A Y

L O

R S

T

F O

R T W

O R

T H T

X

S U

P P

L Y S

U P

P O

R T A

C T

IV

IT

Y W

A R

E H

O U

S E

S o li c it a ti o n N o

C o n tr a c t

N o

Is s u e D a te

C H

IE

F

A R

C H

IT

E C

T U

R A

L S

E C

T

IO

N J E

N N

IF

E R D

E W

IT

T

R .A

J

D E

W

IT

T

R .A

J

M E

T O

Y E

R

J

M E

T O

Y E

R

E N

G

IN

E E

R

IN

G B

R A

N C

H

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N

E N

G

IN

E E

R

IN

G

NUMBER

SHEET

W

G -1

-B -0

J U

N E

0 1648 3216

" = 1'-0"16

1SCALE:

AE700

1 AIR BARRIER PLAN

SCALE: N.T.S.

TESTED AREA

UNTESTED AREA

UNTESTED AREA

Fort Worth District

A

IR

B

A R

R

IE

R P

L A

N

AE700

UNTESTED AREA UNTESTED AREA

TESTED AREAUNTESTED AREA

AE700

AIR BARRIER SCHEMATIC SECTION

" = 1'-0"16

1SCALE:

UNTESTED AREA

N

NORTH

TRUE

GENERAL NOTES

BETWEEN STRUCTURE.

PLUMBING PENETRATIONS, AND OPENINGS

BE LIMITED TO: WELD HOLES, MECHANICAL/

SPRAY FOAM INSULATION TO INCLUDE, BUT NOT

PENETRATIONS OR ANY RESIDUAL OPENING WITH

1. SEAL ALL ROOF, FLOOR, AND WALL

:1

/1

/2

:3

:5

P

M

AIR BARRIER LEGEND

AIR BARRIER ZONE AND BOUNDARY

TESTED AREA

AE700

AE700

SIM

AE700

SIM

m "' i I

"T1

...Ji.

...Ji.

o, r,:, OJ

II

z

C

CI)

S::

CJ

m

;;o -I

=i ;o

;o

Z r

"Tl

� r r,:, � - � "l II

:::u

'Tl

'Tl

"U

7J z :c

F O

R T

H O

O D

T

E X

S

T H

A

IR

D E

F E

N S

E A

R T

IL

L

E R

Y D

IV

IS

IO

U P

P L Y

S U

P P

O R

T A

C T

IV

IT

Y W

A R

E H

O U

E

P

O V

E R

A L L F

U R

N

IT

U R

E F

L O

O R

P L A

Cl iil oi� m=o

Wi:n mm

Wi:n

I 1

LJJD

I I t=1

J

SI

r-, IX

L J

ID

w ll 11 1

.;J

!I:

I -l'0

1f ill ' 0 il l 0

�Jl •1 : 0

I I I I

.Jl ..1 1: I L

.1

-!.11 •1' 0 lo u

J□

=4..

J

L J

I

L

I I

'ill : a

I I I I I I I I I

11 :o , __

-,"ll ; o I I I I

11(

,0

De si gn ed b y:

Is su e

Da te

U

.S

A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

H . K

IM

BR

O W

, R .I.

D

AU

GU

ST

T

A Y

L O

R S

T

Dr aw n by

So lic ita tio n

No

F O

R T

W O

R T

H T

X

K

IM

B R

O W

R

I.

W G

-1 -R

-0

G

IN

E E

R

IN

G

C he ck ed on tra ct N o.

A A

N Y

A E

G B

U N

M

N S

T R

U C

T

IO

N D

IV

IS

Su bm itt ed

O

T D

A T

E

E N

G

IN

E E

R

IN

G B

R A

N

N N

IF

E

R D

E W

ITT

A.

PL

T

S C

A

LE

C

H

IE

F

AR

C H

IT

EC

TU

RA

L

SE

C

TI

SY

DE

SC

R

IP

TI

O

N

DAT

E A

PP

R e e l en ce . 3

CD

ii!

.I>, 0, C)

-..J

(0

1 2

F

E

D

C

B

A

$DATE$ $TIME$ $FILEL$

MECH

[Jill

ELEC

[II§]

JAN

1109 1

FORKLIFT CHARGE

STATION

I 120 I

CORRIDOR

!104A !

I

I

I I 1- - - - - - - - - - - - - _ I

CONF ROOM

[@] [E3J SECURE STOR_.,.... .... A 1

TER

OJI]

I 111 I

E1

(9 W3

VESTIBULE(§ CUSTOMER

! 101 ! � SERVICE AREA

[E3J 103

I

I

I I

1 _____ 1

CUSTOMER

ISSUE BAY

Dill

WAREHOUSE

Dill

TURN-IN BAY

I 121 I

I

I

RECEIVING/

ISSUE BAY

Ofil

W4 W4

D

A

0 0 0

0 0

I

0 0

0 0

0 0

0 0

0 0 0 0

0 0

0 0 0

I. .

[ ______ _ ______________________________________________________ J ________ _

PARTIAL FURNITURE PLAN AREA A A

SCALE: 1/8" = 1'-0"

8 9

FURNITURE LIST

CODE DESCRIPTION

ACCESSORIES

A1 RECYCLING BIN

A2. WASTE BASKET (ONE AT EACH DESK)

SEATING

C1 TASK CHAIR

C2 SIDE CHAIR

FILES

F1 LATERAL FILE

TABLES

T1 TRAINING/ CONF TABLE

WORKSTATIONS

W1 L-SHAPED WORKSTATION

W2 L-SHAPED WORKSTATION

W3 RECEPTION WORKSTATION

W4 L-SHAPED METAL DESK

EQUIPMENT

E1 COPY MACHINE

E2 VENDING MACHINE

E3 CABLE TV

E4 PA CABINET

VISUAL COMMUNICATIONS

V1 PROJECTION SCREEN

V2 MARKER BOARD (4'x4') V3 MARKER BOARD (4'x6')

GENERAL NOTES:

1. ALL FURNISHINGS AND EQUIPMENT ON THIS PLAN

ARE PROVIDED FOR COORDINATION AND SPACE

PLANNING PURPOSES ONLY, AND SHALL BE

CONSIDERED NOT IN CONTRACT (N.I.C.) FOR

THE CONSTRUCTION CONTRACT.

2. VISUAL COMMUNICATIONS ITEMS REQUIRE

ADDITIONAL SUPPORT BLOCKING, PROVIDE

SUFFICIENT SUPPORT FOR INSTALLED ITEM.

3. ALL WORKSTATIONS SHALL HAVE INDIVIDUALLY

CONTROLED TASK LIGHTING.

4. RECYCLABLE MATERIAL RECEPTACLES AND

STORAGE AREA SHALL INCLUDE AT A MINIMUM

SEPARATE BINS FOR "PAPER", "CARDBOARD",

"GLASS", "PLASTICS", AND "METALS." STATION SHALL

SHALL ALSO INCLUDE COLLECTION BINS FOR

BATTERIES AND ELECTRONIC WASTE AS DEFINED

BY THE LEED VERSION FOR THIS PROJECT.

5. ALL FURNITURE FINISHES SHALL MEET THE

FOLLOWING THRESHOLDS FOR AREA-WEIGHTED

AVRAGE SURFACE REFLECTANCE: 45% FOR WORK

SURFACES, AND 50% FOR MOVABLE PARTITIONS.

KEY PLAN

RE: CIVIL FOR

SITE ORIENTATION

8 4 2 0 8 16

�I -��11111111111111111111111111-----1 SCALE: )t" = 1'-0"

PLAN

NORTH

US Army Corps of Engineers Fort Worth District ci 0

.. m Z'i' C: a;: ., -- 0., '" 0 "'

E� Cl I-., "' => ::, •- ID

.!:2 N i:! g om"' ,: - "

>, Q 0 �� al� C � c, m C: �

,: m 'iii ., Cl

I Cl I ww z N a 0 z . "' w t- IL en X 0 0:: t-en o :i::

[l_ ..J t- 0:: :.: 0::

0 t- 0 u "'s:

>- � t- :::; '° 0::

0:: 0

<( IL

lo

L!J

Cl z

L!J z wu w

C:

5 5

8 � � � � i< >.t:l> .c -w "CJ �t::

'O � Q) OI "

"' ·- ffi� <.> E�-., .c ztt w .c: 0

=> z- Cl) wI �<.> z

QI

Cl) z

Z Cl ID o:'. z

(!)wo 2w .,_ _ z (.) o:'.

(!) ::::) w z o:'. w w 1-- z

C/)(!)

Zz Ow

UJ

0::

::J 1-z

0::

::J

LL

;i r't

SHEET

NUMBER

IF110

E 0

D

C

B

A

$DATE$ $TIME$ $FILEL$

A I..

I.

0 0

I

0 I

4 5

1144 I

WAREHOUSE SECURE STOR

0 0

FEB

RECEIVING/

ISSUE BAY

1145 I

W4 W4

[ill]

------ i-------,.;;;i;;;..;;;====-------___ci_ ______ 1.;;L;;.;;;.;;.;;;.;;.;;;.;;.;;;.;;;.;;;JC.,. . .----------------------------------------------------------- 1..

I.

I

!w i�·---' "I •u a:!---'.

�1<C u:::� �1<>'.

W•Q0::::LL

TURN-IN BAY

[Jill

--1----- _J

141 A1,����

CUSTOMER

ISSUE BAY

1139 I

CUSTOMER

SERVICE AREA

V2

E1

C1

W3

PARTIAL FURNITURE PLAN AREA B

SCALE: 1/8" = 1 '-0"

CORRIDOR

1121 I

CONF ROOM

CE3:l I 136 I

ELEC

1133 I

F1

B

I

F1 Vi

-v2�F1,_.,..cF�1_ vr oFF1cE

� �I§=:;!:=*=§ TER

1131 I 0 lg

E1U �

VESTIBULE

! 124 ! �

F1 F1

F1 F1

I. .

8 9

FURNITURE LIST

CODE DESCRIPTION

ACCESSORIES

A1 RECYCLING BIN

A2 WASTE BASKET (ONE AT EACH DESK)

SEATING

C1 TASK CHAIR

C2 SIDE CHAIR

FILES

F1 LATERAL FILE

TABLES

T1 TRAINING/ CONF TABLE

WORKSTATIONS

W1 L-SHAPED WORKSTATION

W2 L-SHAPED WORKSTATION

W3 RECEPTION WORKSTATION

W4 L-SHAPED METAL DESK

EQUIPMENT

E1 COPY MACHINE

E2 VENDING MACHINE

E3 CABLE TV

E4 PA CABINET

VISUAL COMMUNICATIONS

V1 PROJECTION SCREEN

V2 MARKER BOARD (4'x4') V3 MARKER BOARD (4'x6')

GENERAL NOTES:

1. ALL FURNISHINGS AND EQUIPMENT ON THIS PLAN

ARE PROVIDED FOR COORDINATION AND SPACE

PLANNING PURPOSES ONLY, AND SHAILL BE

CONSIDERED NOT IN CONTRACT (N.I.C.) FOR

THE CONSTRUCTION CONTRACT.

2. VISUAL COMMUNICATIONS ITEMS REQUIRE

ADDITIONAL SUPPORT BLOCKING, PROVIDE

SUFFICIENT SUPPORT FOR INSTALLED ITEM.

3. ALL WORKSTATIONS SHALL HAVE INDIVIDUALLY

CONTROLED TASK LIGHTING.

4. RECYCLABLE MATERIAL RECEPTACLES AND

STORAGE AREA SHALL INCLUDE AT A MINIMUM

SEPARATE BINS FOR "PAPER", "CARDBOARD",

"GLASS", "PLASTICS", AND "METALS." STATION SHALL

SHAILL ALSO INCLUDE COLLECTION BINS FOR

BATTERIES AND ELECTRONIC WASTE AS DEFINED

BY THE LEED VERSION FOR THIS PROJECT.

5. ALL FURNITURE FINISHES SHALL MEET THE

FOLLOWING THRESHOLDS FOR AREA-WEIGHTED

AVRAGE SURFACE REFLECTANCE: 45% FOR WORK

SURFACES, AND 50% FOR MOVABLE PARTITIONS.

KEY PLAN

4 2 0 8

I SCALE: Ji"= 1'-0"

RE: CIVIL FOR

SITE ORIENTATION

PLAN

NORTH

US Army Corps of Engineers

Fort Worth District ci 0

.. m Z'i' C: a;: ., -

- 0 ., '" 0 "'

E�Cl I-

•- ID

.!:2 N i:! g om

>, Q 0 .c � al� C � c, m C: �

,: m Cl

I Cl I ww z N - 0 (!) � z ·"'wt- LL en X 0 I>'. t-en o :i::

"- ...J t- I>'. :.: I>'. 0 t- 0 (.) "'s:

>- � t-:::; "° I>'.I>'. 0

<( LL

w

Cl z

"' w z "!l C:

i< >.t:l>

.c -w "CJ �t::" � Q) OI

., <.> "' ·- ffi� <.> E�-., .c ztt w .c: 0 (.) � => z-

Cl) wI �<.> z

QI

Cl) z

Z Cl ID o:'. z

(!) wo 2w .,_ _ z (.) o:'.

(!) ::::) w z o:'. w w 1-- z

C/)(!)

Zz Ow

SHEET

IF111

1 2

E

D

C

B

A

$DATE$ $TIME$ $FILEL$

Ct'.

B

C p

I\ C: -

FORKLIFT '

CHARGE STATION

I 1s4 I □�.... Ct'. ..,. Ct'. �

MECH � P/

MEN -

0 WOMEN

t) � w I?

I

□ D

I� I ��::::::;::l ::;:J =�:;:.ll::!.I H L.::::l;::::::=Ui. F� =i t:::±:j !.!:: I b "'- ' -

JANITO

R CORRIDOR /

I 155 [Jfil ( r.====::==;:::::::;�!tl

V1

IE�

rj7 (Ii T1 T1 {ii I_ c_J

� t- -

F1 lVi I 1"4 �FFICE· a�e-------1llfil ,-l

�. [WI IE2I

II

F1 N10FFICE. 153'!--

� i.t., 1 �

. C' --- ""' --\---L-

(Q).

�'11 � di

Ct'.

0 •

□ooCt'. "' Ct'. � t)

E1

.� � i=�=====:;i..--, V3

11iJ T1 T1 �

CONF ROOM SECURE STOR\

\ [Jfil [BJ I 1 s2 I

A1 - -f-

TER

[:ill]

--::f-

--::f-- -f-- -f-

C

[8

WAREHOUSE

[ill]

OFFICE· / 11 � ,I 9

F1 1vJ�1t�

II

� N2 w:

f--_,,_F_1�N� OFFICE STOCK CONTROL

� i�I �'1'""'1"!!!1!1r==� Y

Y u

! 15T-t-

:= OFFICE

(Q) �

� 7i,_ E4

E1

V21 � V4= y kA12 : :1 F1 s =l jll

I I • LI ,I l

--�� V2\ j • ' � ! CLS OFFICE AB

1148 I

1Vli2 I TI

E1 VESTIBULE�� ! 147 I [BJ

! : I A

• : l.--/ '---

I

I

I

I c��-

CUSTOMER

ISSUE BAY

[Jill 1 W3

I

I

I

CUSTOMER

� - SERVICE AREA

( -r---r 149

I n I

TURN-IN BAY

u

A

W4 I

I

I

0 0

0 0

RECEIVING/

ISSUE BAY

[J][] f--

1W4IIIW41

0 0 [8 !el [8 u u

!§lo 0 u u

I

I

I

□ I

I

I

I :i _ - - - - - - - - - - - - - J �--� ,_ ____ J I -�---------------------------------------------------��-�

PARTIAL FURNITURE PLAN AREA C

SCALE: 1/8" = 1'-0"

8 9

FURNITURE LIST

CODE DESCRIPTION

ACCESSORIES

A1 RECYCLING BIN

A2 WASTE BASKET (ONE AT EACH DESK)

SEATING

C1 TASK CHAIR

C2 SIDE CHAIR

FILES

F1 LATERAL FILE

TABLES

T1 TRAINING/ CONF TABLE

WORKSTATIONS

W1 L-SHAPED WORKSTATION

W2 L-SHAPED WORKSTATION

W3 RECEPTION WORKSTATION

W4 L-SHAPED METAL DESK

EQUIPMENT

E1 COPY MACHINE

E2 VENDING MACHINE

E3 CABLE TV

E4 PA CABINET

VISUAL COMMUNICATIONS

V1 PROJECTION SCREEN

V2 MARKER BOARD (4'x4') V3 MARKER BOARD (4'x6')

GENERAL NOTES:

1. ALL FURNISHINGS AND EQUIPMENT ON THIS PLAN

ARE PROVIDED FOR COORDINATION AND SPACE

PLANNING PURPOSES ONLY, AND SHALL BE

CONSIDERED NOT IN CONTRACT (N.I.C.) FOR

THE CONSTRUCTION CONTRACT.

2. VISUAL COMMUNICATIONS ITEMS REQUIRE

ADDITIONAL SUPPORT BLOCKING, PROVIDE

SUFFICIENT SUPPORT FOR INSTALLED ITEM

3. ALL WORKSTATIONS SHALL HAVE INDIVIDUALLY

CONTROLED TASK LIGHTING.

4. RECYCLABLE MATERIAL RECEPTACLES AND

STORAGE AREA SHALL INCLUDE AT A MINIMUM

SEPARATE BINS FOR "PAPER", "CARDBOARD",

"GLASS", "PLASTICS", AND "METALS." STATION SHALL

SHALL ALSO INCLUDE COLLECTION BINS FOR

BATTERIES AND ELECTRONIC WASTE AS DEFINED

BY THE LEED VERSION FOR THIS PROJECT .

5. ALL FURNITURE FINISHES SHALL MEET THE

FOLLOWING THRESHOLDS FOR AREA-WEIGHTED

AVRAGE SURFACE REFLECTANCE: 45% FOR WORK

SURFACES, AND 50% FOR MOVABLE PARTITIONS.

KEY PLAN

8 4 2 0 I �

SCALE: ¼" = 1 '-0"

I

RE: CIVIL FOR

SITE ORIENTATION

I

PLAN

NORTH

US Army Corps of Engineers Fort Worth District ci 0 Z'i' .. m C: a;: ., -

- 0 0 "' ., '" E� Cl >-

., "' •- ID

=> ::, .!:2 N i:! g om- " "' ,:

>, Q 0 .c � �

.., I i Cl ,_

!I � Cl ,_

1Q w w

N a 0 z ·"' w t- LL en X 0 0:: f-en o :i::

0. ...J t- 0:: :.: 0::

0 t- 0 u "'s: >- � t-::;; "° 0::

0:: 0<( LL

L!J

Cl

L!J

C

0 --z w '!l " C: .,, 8 ::: "' i< >.t:l> .c -w

"CJ �t:: " � Q) OI "

., <.> "' ·- ffi� <.> E�-" .c ztt w .c: 0 () � => z- Cl) wI �<.> z

QI

Cl) z

Z Cl ID o:'. z (')wo

2 Wi,--z (.) o:'.

(') ::::) w z o:'. w w 1-- z

C/)(') Zz Ow t)

Ct'.

c..

w Ct'.

=> 1-z Ct'.

=> u...

i

SHEET

IF112

D

C

B

A

$DATE$

1 2

INTERIOR ROOM FINISH SCHEDULE

FLOOR BASE NORTI-1 WALL EAST WALL

ROOM NO. ROOM NAME

MAT MAT MAT FIN MAT FIN

101 VESllBULE EM RB GWBI PNT-1 GWBI PNT-1

102 CLS OFFICE LVT-1 RB GWBI PNT-1 MP PNT-1

103 CUSTOMER SERVICE AREA LVT-2 RB GWBI PNT-1 GWBI PNT-1

104 CORRIDOR LVT-2 RB GWBI PNT-1 GWBI PNT-1

104A CORRIDOR LVT-2 RB GWBI PNT-1 GWBI PNT-1

105 OFFICE LVT-1 RB GWBI PNT-1 MP PNT-1

106 OFFICE LVT-1 RB GWBI PNT-1 MP PNT-1

107 OFFICE LVT-1 RB GWBI PNT-1 MP PNT-1

108 OFFICE LVT-1 RB GWBI PNT-1 MP PNT-1

109 JANITOR SC RB GWBI FRP/PNT-1 GWBI PNT-1

110 ELEC. SC MB GWBI PNT-1 MP PNT-1

111 MEN FT CVB GWBI WT-1,WT-2 GWBI WT-1, WT-2

112 WOMEN FT CVB GWBI WT-1, WT-2 GWBI WT-1, WT-2

113 CONF ROOM LVT-1 RB GWBI PNT-1 GWBI PNT-1

114 TER SC RB GWBI PNT-1 GWBI PNT-1

115 STOCK CONTROL OFFICE LVT-1 RB GWBI PNT-1 GWBI PNT-1

116 CUSTOMER ISSUE BAY SC MB WM - MP -

117 SECURE STOR SC MB WM - MP -

118 WAREHOUSE SC MB MP - MP -

120 FORK LIFT CHARGE STA llON SC MB MP - MP -

121 TURN-IN BAY SC MB WM - WM -

122 RECEIVING/ ISSUE BAY SC MB - - MP -

123 MECH. SC MB MP - MP -

124 VESllBULE EM RB GWBI PNT-1 GWBI PNT-1

125 CLS OFFICE LVT-1 RB GWBI PNT-1 MP PNT-1

126 CUSTOMER SERVICE AREA LVT-2 RB GWBI PNT-1 GWBI PNT-1

127 CORRIDOR LVT-2 RB GWBI PNT-1 GWBI PNT-1

127A CORRIDOR LVT-2 RB GWBI PNT-1 GWBI PNT-1

128 OFFICE LVT-1 RB GWBI PNT-1 MP PNT-1

129 OFFICE LVT-1 RB GWBI PNT-1 MP PNT-1

130 OFFICE LVT-1 RB GWBI PNT-1 MP PNT-1

131 OFFICE LVT-1 RB GWBI PNT-1 MP PNT-1

132 JANIITOR SC RB GWBI FRP/PNT-1 GWBI PNT-1

133 ELECT SC MB GWBI PNT-1 MP PNT-1

134 MEN FT CVB GWBI WT-1, WT-2 GWBI WT-1, WT-2

135 WOMEN FT CVB GWBI WT-1, WT-2 GWBI WT-1, WT-2

136 CONF ROOM LVT-1 RB GWBI PNT-1 GWBI PNT-1

137 TER SC RB GWBI PNT-1 GWBI PNT-1

138 STOCK CONTROL OFFICE LVT-1 RB GWBI PNT-1 GWBI PNT-1

139 CUSTOMER ISSUE BAY SC MB WM - MP -

140 TURN-IN BAY SC MB WM - MP -

141 SECURE STOR SC MB MP - MP -

142 WAREHOUSE SC MB MP - MP -

143 FIRE/RISER PUMP SC MB MP - MP -

144 FORKLIFT CHARGE STA llON SC MB MP - MP -

145 RECEIVING/ISSUE BAY SC MB - - MP -

147A CORRIDOR LVT-2 RB GWBI PNT-1 GWBI PNT-1

147 VESllBULE EM RB GWBI PNT-1 GWBI PNT-1

148 CLS OFFICE LVT-1 RB GWBI PNT-1 MP PNT-1

149 CUSTOMER SERVICE AREA LVT-2 RB GWBI PNT-1 GWBI PNT-1

150 CORRIDOR LVT-2 RB GWBI PNT-1 GWBI PNT-1

150A CORRIDOR LVT-2 RB GWBI PNT-1 GWBI PNT-1

151 OFFICE LVT-1 RB GWBI PNT-1 MP PNT-1

152 OFFICE LVT-1 RB GWBI PNT-1 MP PNT-1

153 OFFICE LVT-1 RB GWBI PNT-1 MP PNT-1

154 OFFICE LVT-1 RB GWBI PNT-1 MP PNT-1

155 JANIITOR SC RB GWBI FRP/PNT-1 GWBI PNT-1

156 MEN FT CVB GWBI WT-1, WT-2 GWBI WT-1, WT-2

157 WOMEN FT CVB GWBI WT-1, WT-2 GWBI WT-1, WT-2

158 CONF ROOM LVT-1 RB GWBI PNT-1 GWBI PNT-1

159 TER SC RB GWBI PNT-1 GWBI PNT-1

160 STOCK CONTROL OFFICE LVT-1 RB GWBI PNT-1 GWBI PNT-1

161 CUSTOMER ISSUE BAY SC MB WM - MP -

162 SECURE STOR SC MB WM - MP -

163 WAREHOUSE SC MB MP - MP -

164 FORKLIFT CHARGE STA llON SC MB MP - MP -

165 TURN-IN BAY SC MB WM - WM -

166 RECEIVING/ISSUE BAY SC MB - - MP -

168 MECH SC RB GWBI PNT-1 GWBI PNT-1

NQIES

1 PROVIDE WALL TILE (WT) ON WALLS TO CEILING SEE TYPICAL WALL TILE PATTERNS

2. PROVIDE AND INSTALL MANUAL PROJECTION SCREEN 9'-0' AF.F. IN CONFERENCE ROOM

3. PROVIDE AND INSTALL MARKERBOARDS IN ALL THE OFFICES (PRIVATE AND OPEN) 7'-0" A.F.F.

4 MOISTURE RESISTANCE GYPSUM BOARD SHALL BE PROVIDED IN THE RESTROOMS

5. PAINT ALL METAL DOORS AND DOOR FRAMES PNT-4.

WEST WALL

MAT FIN

GWBI PNT-1

GWBI PNT-1

GWBI PNT-1

GWBI PNT-1

GWBI PNT-1

GWBI PNT-1

GWBI PNT-1

GWBI PNT-1

GWBI PNT-1

GWBI FRP/PNT-1

GWBI PNT-1

GWBI WT-1, WT-2

GWBI WT-1, WT-2

GWBI PNT-1

GWBI PNT-1

GWBI PNT-1

WM -

WM -

MP -

MP -

WM -

MP -

GWBI PNT-1

GWBI PNT-1

GWBI PNT-1

GWBI PNT-1

GWBI PNT-1

GWBI PNT-1

GWBI PNT-1

GWBI PNT-1

GWBI PNT-1

GWBI PNT-1

GWBI FRP/PNT-1

GWBI PNT-1

GWBI WT-1, WT-2

GWBI WT-1, WT-2

GWBI PNT-1

GWBI PNT-1

GWBI PNT-1

WM -

WM -

MP -

MP -

MP -

MP -

MP -

GWBI PNT-1

GWBI PNT-1

GWBI PNT-1

GWBI PNT-1

GWBI PNT-1

GWBI PNT-1

GWBI PNT-1

GWBI PNT-1

GWBI PNT-1

GWBI PNT-1

GWBI FRP/PNT-1

GWBI WT-1, WT-2

GWBI WT-1, WT-2

GWBI PNT-1

GWBI PNT-1

GWBI PNT-1

WM -

WM -

MP -

MP -

WM -

MP -

GWBI PNT-1

6 NORTH, SOUTH, EAST, AND WEST AS NOTED ON THE ROOM FINISH SCHEDULE SHALL BE IN ACCORDANCE WITH

PLAN NORTH AS INDICATED ON THE ARCHITECTURAL FLOOR PLANS IN THIS DRAWING SET

7 PAINT ALL INTERIOR WALL AND CEILING MOUNTED ITEMS SUCH AS VENTS, GRILLS COVERS, & FIRE EXTINGUISHER CABINET FACES & FRAMES, LIGHT FIXTURE TRIM RINGS, STC TO MATCH SURFACE COLOR ON WHICH THEY

APPEAR

8 PROVIDE AND INSTALL WINDOW BLINDS (WB) FOR ALL 'MNDOWS IN ADMIN AREA EXCLUDING VESTIBULE STORE FRONTS AND CLERESTORY 'MN DOWS. ALL WINDOW BLINDS SHALL UTILIZE AN "INSIDE" MOUNT METHOD

9. RE: ARCH FOR WALL TYPES AND CONSTRUCTION.

10. PROVIDE (CG) CORNER GUARDS AT ALL EXTERIOR CORNERS IN ADMIN AREA

$TIME$ $FILEL$

3 4

CATEGORY

SOUTI-1 WALL CEILING

REMARKS

MAT FIN MAT FIN HEIGHT

GWBI PNT-1 ACT - 10'-0" FLOORING

MP PNT-1 ACT - 10'-0"

GWBI PNT-1 ACT - 10'-0"

GWBI PNT-1 ACT - 10'-0"

GWBI PNT-1 ACT - 10'-0"

GWBI PNT-1 ACT - 10'-0" WALL BASE

GWBI PNT-1 ACT - 10'-0"

GWBI PNT-1 ACT - 10'-0"

GWBI PNT-1 ACT - 10'-0"

GWBI PNT-1 GWB PNT-3 10'-0"

GWBI PNT-1 EXP - -

GWBI WT-1, WT-2 GWB PNT-3 10'-0" WALLS

GWBI WT-1, WT-2 GWB PNT-3 10'-0"

GWBI PNT-1 ACT - 10'-0"

GWBI PNT-1 EXP PNT-3 -

GWBI PNT-1 ACT - 10'-0"

MP - EXP PNT-3 - CEILINGS

MP - EXP PNT-3 -

MP - EXP PNT-3 -

MP - EXP PNT-3 -

MP - EXP PNT-3 -

MP - EXP PNT-3 - MISC

GWBI PNT-1 EXP - -

GWBI PNT-1 ACT - 10'-0"

MP PNT-1 ACT - 10'-0"

GWBI PNT-1 ACT - 10'-0"

GWBI PNT-1 ACT - 10'-0"

GWBI PNT-1 ACT - 10'-0"

GWBI PNT-1 ACT - 10'-0"

GWBI PNT-1 ACT - 10'-0"

GWBI PNT-1 ACT - 10'-0"

GWBI PNT-1 ACT - 10'-0"

GWBI PNT-1 GWB PNT-3 10'-0"

GWBI PNT-1 EXP - -

GWBI WT-1, WT-2 GWB PNT-3 10'-0"

GWBI WT-1, WT-2 GWB PNT-3 10'-0"

GWBI PNT-1 ACT - 10'-0"

GWBI PNT-1 EXP PNT-3 -

GWBI PNT-1 ACT - 10'-0"

MP - EXP PNT-3 -

MP - EXP PNT-3 -

MP - EXP PNT-3 -

MP - EXP PNT-3 -

MP - EXP PNT-3 -

MP - EXP PNT-3 -

MP - EXP PNT-3 -

GWBI PNT-1 ACT - 10'-0"

GWBI PNT-1 ACT - 10'-0"

MP PNT-1 ACT - 10'-0"

GWBI PNT-1 ACT - 10'-0"

GWBI PNT-1 ACT - 10'-0"

GWBI PNT-1 ACT - 10'-0"

GWBI PNT-1 ACT - 10'-0"

GWBI PNT-1 ACT - 10'-0"

GWBI PNT-1 ACT - 10'-0"

GWBI PNT-1 ACT - 10'-0"

GWBI PNT-1 GWB PNT-3 10'-0"

GWBI WT-1, WT-2 GWB PNT-3 10'-0"

GWBI WT-1, WT-2 GWB PNT-3 10'-0"

GWBI PNT-1 ACT - 10'-0"

GWBI PNT-1 EXP PNT-3 -

GWBI PNT-1 ACT - 10'-0"

MP - EXP PNT-3 -

MP - EXP PNT-3 -

MP - EXP PNT-3 -

MP - EXP PNT-3 -

MP - EXP PNT-3 -

MP - EXP PNT-3 -

GWBI PNT-1 EXP - -

SYMBOL

EM

SC

LVT-1

LVT-2

SDT

FT

CB

RB

MB

CVB

GWBI

MP

WT-1

WT-2

PNT-1

PNT-2

FRP

WM

ACT

PNT-3

OTS

CG

PNT-4

TP

TR

WB

io

MATERIAL

ENTRANCE MAT

SEALED CONCRETE

LUXURY VINYL TILE

LUXURY VINYL TILE

STATIC DISSIPATIVE TILE

FLOOR TILE

CONCRETE BASE

RUBBER BASE

METAL BASE

COVE BASE

IMPACT RESISTANT GYPSUM WALL BOARD

METAL PANEL

WALL TILE

WALL TILE

PAINT

PAINT

FIBERGLASS REINFORCED PLASTIC

WIRE MESH

ACOUSTICAL CEILING TILE

PAINT

OPEN TO STRUCTURE

CORN ER GUARD

PAINT (TRIM)

SOLID SURFACE

TOILET PARTITION

TILE TRIM PIECE

WINDOW BLINDS

l 24" l"I i\

6 7

INTERIOR FINISH MATERIAL LEGEND

MANUFACTURER MODEL NO,/FINISH COLOR

CONSTRUCTION SPECIALTIES PEDIMAT, 732SWROUGHT IRON

TO MARKET OZOGRIP, INDUSTRIA OG 2593

TO MARKET OZOGRIP, OLIO OG 2338

AMERICAN BILTRITE ESD TILE TAUPE SDT-145

DAL TILE EXHIBITION, GREY EX02, UNPOLISHED

JOHNSONITE WALL BASE BURNT UMBER

4" 22 GAGE STAINLESS STEEL METAL BASE

SCHLUTER COVE BASE, DILEX-AHK, BRUSHED NICKEL, AHK15100ATGB

VARCO PRUDEN COOL COTTON WHITE

DAL TILE EXHIBITION, GREY EX02, UNPOLISHED

DAL TILE SEMI-GLOSS WALL TILE, NAVY K189

SHERWIN WILLIAMS REPOSE GRAY SW7015 SATIN FINISH

SHERWIN WILLIAMS FUNCTIONAL GRAY SW7024 SATIN FINISH

MARLITE SYMMETRIX, A 916 G63

ARMSTRONG FINE FISSURED 1713, WHITE / GRID: PRELUDE XL 15/16" EXPOSED TEE, WHITE

SHERWIN WILLIAMS BRIGHT CEILING WHITE SW7006 FLAT

INPRO CORPORATION TAUPE 0113, G2-159R, G2 BIO BLEND RETAINER SURFACE MOUNTED

SHERWIN WILLIAMS IRON ORE SW7069 ALYKD ENAMEL FORMULA

CORIAN LINEN

SCRANTRON PRODUCTS HINY HIDERS PARTITIONS, SHALE

SCHLUTER JOLLY 1/4" EDGE TRIM, BRUSHED NICKEL A60ATGB

SWF CONTRACT 1" ALUMINUM BLINDS, SRUSHED ALU MIN UM FINISH

WT-2

WT-1

TYPICAL WALL TILE PATTERN

NOT TO SCALE

8 9

SIZE NOTES

23" X 23" Tl LES OFFICES

7" X 47" PLAN KS CORRIDORS

12" X 12" 12" X 24"

4"

12" X 24"

6" X8

INSTALL TO 4' AFF

24" X 24"

3"WING X 4'HIGH

ACCURS AT ALL EXTERIOR WIN DOWS

LIS Army Corps of Engineers Fort Worth District ci 0

,, m Z'i' ., - C: a;:

- 0 0 "' ., '" E� Cl I-

., "' ,_ ID

=> ::, .!:2 N i:! g om

>, Q 0 � � al � � � C � C: � c, m ,: m 'iii � � �., � Cl I Cl I ww z N a 0 z ' "'w t- ,.._ LL en X 0 0:: t-en o :i::

O,_ ..J t-0:: :.: 0::

0 t- 0u "'s:>- � t- :::; '° 0::0:: 0

<( LL

L!J

Cl z

L!J z w'!l w C:

5 5 8 � � � � i< >.t:l>

,c -w "CJ �t:: " � Q) OI

., '-' "' ·- ffi� '-' E�- " .c zttw ,c: 0

() � => z- Cl) wI �'-' z

QI

Cl) z

Z Cl ID o:'. z

(!)wo 2w .,_ _ z (.) o:'.

(!) ::::) w z o:'. w w 1-- z

C/)C,!)

Zz Ow w ..J Clw :r:

Cl) z u:::

0::

0::w 1-z

SHEET

IN601

I 1 I 2 I 3 I 4 I 5 I 6 I

SIGNAGE SCHEDULE

RAISED TYPOGRAPHY

(INCLUDES CORRESPONDING BRAILLE) SIGNAGE NOTES

SIGN TYPE

ROOM

NAME NOTES

NO.

1. SIGN SHALL BE INSTALLED ON WALL ADJACENT TO THE LATCH SIDE OF THE DOOR OR TO THE RIGHT OF THE RIGHT HAND DOOR AT DOUBLE DOORS. WHERE THERE IS NO WALL SPACE ON THE LATCH SIDE OF A SINGLE DOOR

F 101 VESTIBULE OR TO THE RIGHT SIDE OF DOUBLE DOORS, SIGNS SHOULD BE ON THE NEAREST ADJACENT WALL. CHARACTER

102 CLS OFFICE B

MOUNTING HEIGHT SHALL BE 48" A.F.F (MIN.) TO 60" A.F.F. (MAX.) UNLESS OTHERWISE NOTED.

103 CUSTOMER SERVICE AREA 2. TACTILE CHARACTERS SHALL BE SANS SERIF AND SHALL BE ACCOMPANIED BY GRADE II BRAILLE. TACTILE CHARACTERS SHALL BE RAISED 1/32" MIN. ABOVE THEIR BACKGROUND. CHARACTERS SHALL BE 5/8" MIN. AND 2"

104 CORRIDOR B MAX.

104A CORRIDOR

3. PICTOGRAMS SHALL HAVE A HEIGHT OF 6". CHARACTERS OR BRAILLE SHALL NOT BE IN THE PICTOGRAM FIELD.

105 OFFICE A WHERE TEXT DISCRIPTORS FOR PICTOGRAMS ARE REQUIRED, THEY SHALL BE DIRECTLY ABOVE OR BELOW THE

106 OFFICE A

PICTOGRAM.

107 OFFICE A 4. CHARACTERS AND THEIR BACKGROUNDS SHALL HAVE A NON-GLARE FINISH. CHARACTERS SHALL CONTRAST

108 OFFICE A

WITH THEIR BACKGROUND, WITH EITHER LIGHT CHARACTERS ON A DARK BACKGROUND OR DARK CHARACTERS ON

A LIGHT BACKGROUND.

109 JANIITOR B

5. PROVIDE SIGN TYPE E (NO SMOKING WITHIN 50 FEET OF BUILDING) AT EACH ENTRANCE DOOR.

110 ELEC

111 MEN C1

6. CONTRACTOR TO SUBMIT SIGNAGE TEXT TO GARRISON FOR REVIEW AND APPROVAL PRIOR TO FABRICATION

AND INSTALLATION.

112 WOMEN C2

7. ALL SIGNAGE TO BE CONSTRUCTED AND INSTALLED ACCORDING TO DEPARTMENT OF ARMY STANDARDS FOR

E

113 CONF ROOM B SIGNAGE PROVIDED BY DPW.

114 lER B

8. INSTALL EXTERIOR NO SMOKING SIGN WITHIN 10 FEET OF ALL BUILDING ENTRANCES. SIGN SHALL READ

115 STOCK CONTROL OFFICE B - NO SMOKING WITHIN 50 FEET OF BUILDING.

116 CUSTOMER ISSUE BAY B

117 SECURE STOR B

118 WAREHOUSE

120 FORKLIFT CHARGE STATION B 9"

- 121 TIJRN-IN BAY B 8"

122 RECEIVING/ISSUE BAY

I I

123 MECH

i:

124 VESTIBULE

T

�2 1 9" �

I I 125 CLS OFFICE B \ Grade 2 Braille ,. 8' l

126 CUSTOMER SERVICE AREA �

127 CORRIDOR

D 127A CORRIDOR B

2 1 I 128 OFFICE B £:! Grade 2 Braille �

Robert Woods

129 OFFICE B

I

130 OFFICE B

131 OFFICE B

Samuel Johnson I(')

132 JANIITOR B

133 ELECT -

134 MEN C1

'� 135 WOMEN C2

136 CONF ROOM B

SIGN TYPE B 137 lER B

SIGN TYPE A NOT TO SCALE 138 STOCK CONTROL OFFICE B

139 CUSTOMER ISSUE BAY B

NOT TO SCALE

C

140 TIJRN-IN BAY B

141 SECURE STOR B ' 6" ' 6"

142 WAREHOUSE

143 FIRE/RISER PUMP

144 FORKLIFT CHARGE STATION B

145 RECEIVING/ISSUE BAY

0 147A CORRIDOR

0 -

147 VESTIBULE I I I

148 CLS OFFICE B

149 CUSTOMER SERVICE AREA

�� b L �·

150 CORRIDOR � �

150A CORRIDOR B I I

151 OFFICE A

152 OFFICE A b, m

B

153 OFFICE A

154 OFFICE A

155 JANIITOR B '.--

MEN'S WOMEN'S 156 MEN C1

157 WOMEN C2

RESTROOM RESTROOM

158 CONF ROOM B

159 lER B = = - � �

160 STOCK CONTROL OFFICE B

I I I IGrade 2 Braille Grade 2 Braille 161 CUSTOMER ISSUE BAY B = • � �

162 SECURE STOR B

163 WAREHOUSE

164 FORKLIFT CHARGE STATION B

165 TIJRN-IN BAY B

cp

SIGN TYPE C1

cp

SIGN TYPE C2

A 166 RECEIVING/ISSUE BAY

168 MECH

NOT TO SCALE NOT TO SCALE

I I I I I I I

$DATE$ $TIME$ $FILEL$

7 I 8 I 9

' 9" ,r t <o c:::::::a

SIGNAGE PLACEMENT

NOT TO SCALE

·1

I �

I I

I mI

US Army Corps of Engineers

Fort Worth District ci 0

.. m Z'i' ., -- 0

C: a;:

., '" 0 "'

Cl I-

., "' E�•- ID

i:! g

.!:2 N om - " "' ,:

>, Q 0 .c � al� C � c, m C: � ,: m ·c;; � � �., � Cl � Cl I

1Q ww N a 0 z · "'w t- LL en X 0 0:: t-en o :i:: 0.. ...J t-0:: :.: 0:: 0 t- 0 u "'s:

>- � t-::; '° 0::

0:: 0

<( LL

cti z w

0� u.iO -I ;;;: woo::

en��;:Jiw� w...J 1-:::::!-M

-�2:�0

1--"' 0 u,-..

ow<C ..

:J:(1)1-Z 1-Zll'.'.0..

0::WO

QLLo_ LL Wo_ Cl ::, o::en I ...J

.... a. "' 0..

tO::::, en

L!J

Cl c':

L!J Cl z w "!l w C: 5 5 8 � � � � z i< >.t:l> .c -w

"CJ �t:: " � Q) OI

., <.> "' ·- ffi� <.> E�-., .c zttw .c: 0 () � => z-

Cl) wI �<.> z

QI

-o Cl) z

Z Cl ID 0::: z

(!) wo 2 W1---z (.) 0:::

(!) ::::) w z 0::: w w 1-- z

C/)(!)

Zz Ow w w w J:

w

C)

SHEET

NUMBER

IN801

I m "' "' .,, ;= m :;;

CX)

CJ)

6 • z c cn

S::

CJl r;;

Cl)

G)

"l

7J r )> z

:::0

I-

I I

I I

I I

I flli:!!I-

I-

I I

I I

I I iili

�8

;o ;o

§ - OJ C

6A

I I I I I I I I

...llr:

' I

□11

1111 0 0 o c

Gi a

[.'.j o s::

C/l

- z OJ

� 0 m

C m m

ID

0 0

II

@l

!el

Cl 0 r:7

B

1-

I I

I I

I

;o 0

_J

..-J r:, p:i r, ii �

;o ;o

9 ;,:

I I

GI

Cll

"T1

-I -I o

O I jl; �

'1--r-1

IH

1n a;i

�I

I

0 , I

Ii ll

D

0- J1I

!l!

!l!

!el

.�d

I p�

��&l �C:'H li

NE

I I-

I I

I ■ r-

I I

I I I I I I I I rll" fl!!

■r ng-lfl

"' .... "' 0

C') m o iii r � cl

;,i

-< "ll

"ll

FO

RT

H O

O D, T

EX

AS

TH

A

IR

D

EF

EN

SE

A

RT

IL

LE

RY

D

IV

IS

IO

N

SU

PP

LY

S

UP

PO

RT

A

CT

IV

IT

Y

W

AR

EH

O

US

E

PN

: 7

R T

IA

L

S

IG

N A

G E

P L

A

0 en a;

-< s:: ID r r m

5;

U.

S.

A

RM

Y

CO

RP

S

O F

EN

G

IN

EE

RS

TA

YL

O R

ST

FO

RT

W O

RT

H, T X

E N

G

IN

E E

R

IN

G

C O

N S

T R

U C

T

IO

N D

IV

IS

G

IN

E E

R

IN

G B

R A

N

.Ill

De sig ne d by

Is su e D at e

H

K

IM

B

R

OW

, R

ID

AU

GU

ST

Dr aw n by

S o lic ita tio n N o

H

K

IM

B R

O W

, R

W

G

-1 -R

-0

Ch ec ke d by

C on tr ac t N o

J D

E W

ITT

R

A

Su bm itte d by

P L O

T D

A T

E

J E

N N

IF

E

R D

E W

ITT

, R

.A

CH

IE

F.

A

RC

HI

TE

CT

UR

A

L S

EC

TI

O

N P

L O

T S

CA

L

E

RI

PT

IO

DA

TE

AP

PR

S.

oo

O;:a;;

::s

::r

Cl

-a

-I>-

Io, en

(0

FEB

FEB

US Army Corps of Engineers

A P

P R

D A

T E

D E

S C

R

IP

T

IO

N S

Y M

$FILEL$

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

$DATE$ $TIME$

KEY PLAN

A B C

S u b m it te d b y

C h e c k e d b y

D ra w n b y

D e s ig n e d b y

P L

O T D

A T

E

P L

O T S

C A

L E

F O

R T H

O O

D T

E X

A S

T

H A

IR

D

E F

E N

S E A

R T

IL

L E

R Y D

IV

IS

IO

N

P N

U .S

A R

M Y C

O R

P S O

F E

N G

IN

E E

R S

T

A Y

L O

R S

T

F O

R T W

O R

T H T

X

S U

P P

L Y S

U P

P O

R T A

C T

IV

IT

Y W

A R

E H

O U

S E

S o li c it a ti o n N o

C o n tr a c t

N o

Is s u e D a te

E N

G

IN

E E

R

IN

G B

R A

N C

H

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N

E N

G

IN

E E

R

IN

G

NUMBER

SHEET

W

G -1

-B -0

A U

G U

S T

0 824 168

" = 1'-0"8

1SCALE:

KEY PLAN

Fort Worth District

IN811

CHARGE STATION

FORKLIFT

C1

B

BC2

A

A

A

A

B

B

B

P A

R T

IA

L S

IG

N A

G E P

L A

N A

R E

A B

PARTIAL SIGNAGE PLAN AREA B

SCALE: 1/8" = 1'-0"

SCALE: 1/8" = 1'-0"

PARTIAL SIGNAGE PLAN AREA B

J

D E

W

IT

T

R .A

C H

IE

F

A R

C H

IT

E C

T U

R A

L S

E C

T

IO

N J E

N N

IF

E R D

E W

IT

T

R .A

H

K

IM

B R

O W

R

ID

H

K

IM

B R

O W

R

ID

B

IN811

/1

/2

:0

:4

P

M

:1

N

NORTH

TRUE

A

F O

R M

A T

C H L

IN

E

R E :I

N

JANITOR

B

B

SYMBOL LEGEND

SYMBOL

A

DESCRIPTION

SIGNAGE TYPE

FIRE/RISER PUMP

ELEC

ISSUE BAY

CUSTOMER

WAREHOUSE

ISSUE BAY

RECEIVING/

OFFICE

STOCK CONTROL

SERVICE AREA

CUSTOMER

OFFICE

OFFICE

OFFICE

OFFICE

CLS OFFICE

A

C O

R R

ID

O R

CONF ROOM

TER

SECURE STOR

CORRIDOR

WOMEN

MEN

VESTIBULE

TURN-IN BAY

147A

CORRIDOR

F O

R M

A T

C H L

IN

E

R E :I

N

"' m z co

....I.

f1:I cn s:: :::c

CJl j!::

lei

:::0

,,. "' 00

Ol

' I --

R J.

�.1

1■

I IJla.ll

.I

M

AT

CH

L

IN

E

1-e c.n

·@ c.n

1\.)

t;;;;::

c =o = R

� R =l

D

= O = R:::;;;I l.

C/)

L_:_ jlnl r-

1 I I I --

�55

1::::::;i

Fl s;:

"TI

Z -I el r

GI

[::j m �

;;o 0

0 s::

rn ll

RR

ID

!1

4 7 A !

r .t=

:i.1

El g

]t== aL!::::

d u

Io

,. 0 :::c

(l ffll

D

Lf\ gi

2: □ >- ,---

I dll qif

I c11I qJf

TI'

I L s;:

iii

;,i

:c

RT

H O

O D, T

EX

AS

TH

A

IR

D

EF

EN

SE

A

RT

IL

LE

RY

D

IV

IS

IO

N

SU

PP

LY

S

UP

PO

RT

A

CT

IV

IT

Y

W

AR

EH

O

US

E

PN

: 7

R T

IA

L

S

IG

N A

G E

P L

A N

A R

E cn m o

CJ

s::

- z

;;o m

CJ

Z

G') --

:!!l a;

s:: CJ 0

0 r

C/l

I

I

U.

S.

A

RM

Y

CO

RP

S

O F

EN

G

IN

EE

RS

TA

YL

O R

ST

FO

RT

W O

RT

H, T X

E N

G

IN

E E

R

IN

G

C O

N S

T R

U C

T

IO

N D

IV

IS

G

IN

E E

R

IN

G B

R A

N

:::c

@l

De sig ne d by

Is su e Da te

H

K

IM

B R

OW

U G

U S

T

Dr aw n by

So lic ita tio n

No

H

K

IM

B R

O W

W

G

-1 -R

-0

Ch ec ke d by

Co nt ra ct

N o.

J.

D E

W

ITT

, R A

Su bm itte d by

J E

N N

IF

E

R D

E W

ITT

R

.A

C H

IE

F

. A R

C H

IT

E

C

TU

R A

L S

E C

TI

A

A -A

E

.d g n

1tci:E'l

U1 n

'Iii

JJI

RI

PT

IO

DA

TE

AP

PR

S.

oo

O;:a;;

::s

::r

-a

I\.> "' .I>, o, C)

- I -...i

I00 co

IR

E A

L A

R M L

E G

E N

D

FA001

Fort Worth District

US Army Corps of Engineers

A P

P R

D A

T E

D E

S C

R

IP

T

IO

N S

Y M

$FILEL$

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

$DATE$ $TIME$

S u b m it te d b y

C h e c k e d b y

D ra w n b y

D e s ig n e d b y

F O

R T H

O O

D T

E X

A S

T

H A

IR

D

E F

E N

S E A

R T

IL

L E

R Y D

IV

IS

IO

N

P N

U .S

A R

M Y C

O R

P S O

F E

N G

IN

E E

R S

T

A Y

L O

R S

T

F O

R T W

O R

T H T

X

S U

P P

L Y S

U P

P O

R T A

C T

IV

IT

Y W

A R

E H

O U

S E

S o li c it a ti o n N o

C o n tr a c t

N o

Is s u e D a te

G

C H

O A

T E

G

C H

O A

T E

E N

G

IN

E E

R

IN

G B

R A

N C

H

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N

E N

G

IN

E E

R

IN

G

NUMBER

SHEET

D

B R

O W

N P .E

C H

IE

F E

L E

C T

R

IC

A L S

E C

T

IO

N D

A R

E N A

B R

O W

N P .E

W

G -1

-B -0

A U

G U

S T

CO

X

X

TS

K

P

AIM

CM

MM

ISO

SPD

GENERAL SHEET NOTES

KEYED NOTE

SCHEDULED FEEDER (RISER DIAGRAMS)

SINGLE STATION SMOKE DETECTOR WITH SOUNDER BASE, ADDRESSABLE

SMOKE DETECTOR, BEAM TRANSMITTER, ADDRESSABLE

SMOKE DETECTOR, BEAM RECEIVER, ADDRESSABLE

SMOKE DAMPER. SEE GENERAL NOTE 11.

DEGREE F. TYPICAL FOR ALL RATINGS.

HEAT DETECTOR. "120" INDICATES SPECIAL FIXED TEMPERATURE RATING IN

SPEAKER dBA RATNG AT 10 FEET. SEE GENERAL NOTE 4.

FIRE ALARM / MASS NOTIFICATION CEILING-MOUNTED SPEAKER. "Y" DENOTES

dBA RATNG AT 10 FEET. SEE GENERAL NOTE 3.

MASS NOTIFICATION WEATHERPROOF EXTERIOR SPEAKER. "Y" DENOTES SPEAKER

SPEAKER dBA RATING AT 10 FEET. SEE GENERAL NOTE 3.

FIRE ALARM / MASS NOTIFICATION WALL-MOUNTED SPEAKER. "Y" DENOTES

SPRINKLER FLOW ALARM BELL. MOUNT AT 96" AFF UNO.

KNOX BOX

FIRE ALARM/MASS NOTIFICATION CEILING-MOUNTED DEVICE. FOR USE ON REFLECTED CEILING PLAN.

NOTIFICATION LIVE AND PRE-RECORDED ANNOUNCEMENTS ACTIVATION.

LOCAL OPERATOR CONTROL STATION WITH MICROPHONE, AND BUTTONS, FOR MASS

VALVE TAMPER SWITCH

WATER FLOW SWITCH

ADDRESSABLE INTERFACE DEVICE

CONTROL MODULE

MONITORING MODULE

ISOLATION MODULE

ANTENNA

GROUND

SURGE PROTECTIVE DEVICE

S

BT

BR

GENERAL SYMBOLS

FIRE ALARM SYMBOLS

CARBON MONOXIDE DETECTOR, POWERED AND MONITORED BY THE FACP.

DUCT SMOKE DETECTOR, ADDRESSABLE.

SPRINKLER HEADS, ETC.

DEVICES SUCH AS: DIFFUSERS, LIGHTS,

FOR LOCATIONS OF CEILING-MOUNTED

ARCHITECTURAL REFLECTED CEILING PLANS

INSTALLATION, WITH ALL OTHER TRADES. SEE

COOORDINATE ALL WORK, PRIOR TO 12.

DUCTWORK INSTALLATION.

DETECTORS SHOWN ON PLANS WITH

COOORDINATE LOCATIONS OF DUCT SMOKE 11.

HVAC PLANS AND CONTROLS FOR LOCATIONS.

ON FIRE ALARM PLANS. SEE MECHANICAL

SMOKE DETECTORS, WHICH ARE NOT SHOWN

ISOLATION SMOKE DAMPERS AND DUCT

SYSTEM CONNECTION TO AIR HANDLER

PER NFPA, FURNISH AND INSTALL FIRE ALARM 10.

ONE FOOT FROM LIGHTING.

SMOKE DETECTORS SHALL BE A MINIMUM OF 9.

FEET FROM AIR DIFFUSERS.

SMOKE DETECTORS SHALL BE A MINIMUM OF 3 8.

EXTERIOR EGRESS, AND GATHERING AREAS.

PERSONNEL IN THE: IMMEDIATE VICINITY,

MASS NOTIFICATION MESSAGES TO

ON THE EXTERIOR OF BUILDING TO PROVIDE

PROVIDE WEATHERPROOF RATED SPEAKERS 7.

INTELLIGABILITY REQUIREMENTS.

PER MANUFACTURER, TO MEET THE

SPEAKER QUANTITY AND SPACING MAY VARY,

SIGNALS & MASS NOTIFICATION MESSAGES.

TO TRANSMIT FIRE ALARM NOTIFICATION

SPEAKERS SHALL BE CONNECTED, IN ORDER 6.

NOT SHOWN, BUT REQUIRED BY NFPA.

SPECIFIC. PROVIDE ANY ADDITIONAL DEVICES

LAYOUT IS GENERIC AND NOT MANUFACTURER 5.

NFPA 72 VISIBLITY REQUIREMENTS.

AMBER STROBES AS NECESSARY, TO MEET

STROBES. INCREASE CANDELLA RATING OF

PLANS, ARE FOR THE CLEAR FIRE ALARM

STROBE INTENSITIES, INDICATED ON THE 4.

UNLESS INDICATED OTHERWISE.

MOUNT DEVICES ABOVE FINISHED FLOOR 3.

NOTED OTHERWISE.

NFPA AND ADA REQUIREMENTS UNLESS

MOUNTING OF DEVICES SHALL COMPLY WITH 2.

SPECIFICATIONS, FOLLOW THE DRAWINGS.

DRAWINGS EXCEED REQUIREMENTS OF THE

THE SPECIFICATIONS. HOWEVER, WHERE THE

SPECIFICATIONS AND THE DRAWINGS, FOLLOW

FOR CONFLICTS BETWEEN THE 1.

CEILING MOUNTED DUAL-SENSOR SMOKE DETECTOR, ADDRESSABLE. SEE GENERAL NOTES 9 AND 10.

FIRE ALARM / MASS NOTIFICATION CONTROL PANEL (FACP/FMCP). MOUNT AT 5FT AFF FROM THE TOP OF THE PANEL.

FIRE ALARM ANNUNCIATOR PANEL. MOUNT AT 5FT AFF FROM THE TOP OF THE PANEL.

FIRE ALARM / MASS NOTIFICATION TRANSCEIVER. MOUNT AT 5FT AFF FROM THE TOP OF THE PANEL.

ADDRESSABLE FIRE ALARM PULL STATION, WALL MOUNTED AT 42" AFF UN.O.

10 FEET. SEE GENERAL NOTE 4.

DENOTES CANDELLA RATING OF STROBE. "Y" DENOTES SPEAKER dBA RATNG AT

MASS NOTIFICATION SPEAKER CEILING MOUNTED WITH CLEAR STROBE. "X"

TEXT SIGN / LED DISPLAY

STROBE/SPEAKER APPLIANCES. SEE GENERAL NOTE 4.

STROBE. "Y" DENOTES SPEAKER dBA RATNG AT 10 FEET. TYPICAL FOR ALL

CEILING-MOUNTED AT 17' AFF, . "X" DENOTES CANDELLA RATING OF EACH

FIRE ALARM / MASS NOTIFICATION SPEAKER WITH ONE CLEAR STROBES,

GENERAL NOTES 4.

MOUNTED AT 7'-6" AFF OR 6" BELOW CEILING, WHICHEVER IS LOWER. SEE

FIRE ALARM / MASS NOTIFICATION SPEAKER WITH ONE CLEAR STROBE. WALL

FACP

FAAP

LOC

FATR

Y

Y

Y

Y

WP

Y

Y

X

X

X

A P

P R

D A

T E

D E

S C

R

IP

T

IO

N S

Y M

$FILEL$

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

$DATE$ $TIME$

KEY PLAN

A B C

S u b m it te d b y

C h e c k e d b y

D ra w n b y

D e s ig n e d b y

P L

O T D

A T

E

P L

O T S

C A

L E

F O

R T H

O O

D T

E X

A S

T

H A

IR

D

E F

E N

S E A

R T

IL

L E

R Y D

IV

IS

IO

N

P N

U .S

A R

M Y C

O R

P S O

F E

N G

IN

E E

R S

T

A Y

L O

R S

T

F O

R T W

O R

T H T

X

S U

P P

L Y S

U P

P O

R T A

C T

IV

IT

Y W

A R

E H

O U

S E

S o li c it a ti o n N o

C o n tr a c t

N o

Is s u e D a te

G

C H

O A

T E

G

C H

O A

T E

E N

G

IN

E E

R

IN

G B

R A

N C

H

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N

E N

G

IN

E E

R

IN

G

NUMBER

SHEET

N

NORTH

TRUE

D

B R

O W

N P .E

C H

IE

F E

L E

C T

R

IC

A L S

E C

T

IO

N D

A R

E N A

B R

O W

N P .E

W

G -1

-B -0

A U

G U

S T

0 824 168

" = 1'-0"8

1SCALE:

FA101

SCALE: 1/8" = 1'-0"

F

IR

E A

L A

R M M

A S

S N

O T

IF

IC

A T

A

N A

R E

FA101

FIRE ALARM & MASS NOTIFICATION PLAN - AREA A

SHEET KEYNOTES:

Fort Worth District

F O

R M

A T

C H L

IN

E

R E F

A

T S

TS

TS TS

TS TS

PP

GENERAL SHEET NOTES

THE POST-WIDE ANNOUNCEMENTS.

VOLUME SHALL NOT INTERFERE WITH

NOTIFICATION SYSTEMS". SPEAKER

"DESIGN AND O&M: MASS

REQUIRMENTS OF UFC 4-021-01

1. SPEAKER SHALL MEET THE

FROM THE LEVEL OF DISCHARGE.

SUBSTANTIAL MEANS OF EGREES

STAIRWELL AND OVER THE

OVER THE DOOR TO EACH EGRESS

STANDARD 48. LOCATE TEXT SIGNS

6. TEXT SIGNS SHALL COMPLY WITH UL

ALSO BE USED FOR MN SYSTEM.

5. SPEAKERS FOR FA SYSTEM SHALL

IN LEGEND, SHEET FA001.

4. FIRE ALARM SYMBOLS CAN BE FOUND

MANUFACTURER SPECIFICATIONS.

ACCORDANCE WITH NFPA 72 AND

3. MOUNT CO DETECTORS IN

FINISHED GRADE.

DOORS, AT 96 INCHES ABOVE

2. MOUNT EXTERIOR SPEAKERS ABOVE

OF MECHANICAL INFRARED HEATERS.

NOT MOUNT IN SAFETY CLEAR SPACE

WAREHOUSE, AT 17 FEET AFF UNO. DO

1. MOUNT SPEAKERS AND STROBES IN

1 1

A P

P R

D A

T E

D E

S C

R

IP

T

IO

N S

Y M

$FILEL$

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

$DATE$ $TIME$

KEY PLAN

A B C

S u b m it te d b y

C h e c k e d b y

D ra w n b y

D e s ig n e d b y

P L

O T D

A T

E

P L

O T S

C A

L E

F O

R T H

O O

D T

E X

A S

T

H A

IR

D

E F

E N

S E A

R T

IL

L E

R Y D

IV

IS

IO

N

P N

U .S

A R

M Y C

O R

P S O

F E

N G

IN

E E

R S

T

A Y

L O

R S

T

F O

R T W

O R

T H T

X

S U

P P

L Y S

U P

P O

R T A

C T

IV

IT

Y W

A R

E H

O U

S E

S o li c it a ti o n N o

C o n tr a c t

N o

Is s u e D a te

G

C H

O A

T E

G

C H

O A

T E

E N

G

IN

E E

R

IN

G B

R A

N C

H

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N

E N

G

IN

E E

R

IN

G

NUMBER

SHEET

D

B R

O W

N P .E

C H

IE

F E

L E

C T

R

IC

A L S

E C

T

IO

N D

A R

E N A

B R

O W

N P .E

W

G -1

-B -0

A U

G U

S T

F

IR

E A

L A

R M M

A S

S N

O T

IF

IC

A T

A

N A

R E

FA102

SHEET KEYNOTES:

Fort Worth District

SCALE: 1/8" = 1'-0"FA102

FIRE ALARM & MASS NOTIFICATION PLAN - AREA B

P P

TSTS

TS TS

TS

GENERAL SHEET NOTES

2. SMOKE DETECTOR FOR FACP.

THE POST-WIDE ANNOUNCEMENTS.

VOLUME SHALL NOT INTERFERE WITH

NOTIFICATION SYSTEMS". SPEAKER

"DESIGN AND O&M: MASS

REQUIRMENTS OF UFC 4-021-01

1. SPEAKER SHALL MEET THE

FROM THE LEVEL OF DISCHARGE.

SUBSTANTIAL MEANS OF EGREES

STAIRWELL AND OVER THE

OVER THE DOOR TO EACH EGRESS

STANDARD 48. LOCATE TEXT SIGNS

7. TEXT SIGNS SHALL COMPLY WITH UL

KNOX BOX AT GATE.

6. SEE SHEET CS103 FOR LOCATION OF

ALSO BE USED FOR MN SYSTEM.

5. SPEAKERS FOR FA SYSTEM SHALL

IN LEGEND, SHEET FA001.

4. FIRE ALARM SYMBOLS CAN BE FOUND

MANUFACTURER SPECIFICATIONS.

ACCORDANCE WITH NFPA 72 AND

3. MOUNT CO DETECTORS IN

FINISHED GRADE.

DOORS, AT 96 INCHES ABOVE

2. MOUNT EXTERIOR SPEAKERS ABOVE

OF MECHANICAL INFRARED HEATERS.

NOT MOUNT IN SAFETY CLEAR SPACE

WAREHOUSE, AT 17 FEET AFF UNO. DO

1. MOUNT SPEAKERS AND STROBES IN

1 1 1

F O

R M

A T

C H L

IN

E

R E F

A

F O

R M

A T

C H L

IN

E

R E F

A

FA103

SCALE: 1/8" = 1'-0"

0 824 168

" = 1'-0"8

1SCALE:

FA103

FIRE ALARM & MASS NOTIFICATION PLAN - AREA C

A

N A

R E

IR

E A

L A

R M M

A S

S N

O T

IF

IC

A T

IO

N

SHEET KEYNOTES:

Fort Worth District

TS

TSTS

TS

T S

US Army Corps of Engineers

A P

P R

D A

T E

D E

S C

R

IP

T

IO

N S

Y M

$FILEL$

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

$DATE$ $TIME$

KEY PLAN

A B C

S u b m it te d b y

C h e c k e d b y

D ra w n b y

D e s ig n e d b y

P L

O T D

A T

E

P L

O T S

C A

L E

F O

R T H

O O

D T

E X

A S

T

H A

IR

D

E F

E N

S E A

R T

IL

L E

R Y D

IV

IS

IO

N

P N

U .S

A R

M Y C

O R

P S O

F E

N G

IN

E E

R S

T

A Y

L O

R S

T

F O

R T W

O R

T H T

X

S U

P P

L Y S

U P

P O

R T A

C T

IV

IT

Y W

A R

E H

O U

S E

S o li c it a ti o n N o

C o n tr a c t

N o

Is s u e D a te

G

C H

O A

T E

G

C H

O A

T E

E N

G

IN

E E

R

IN

G B

R A

N C

H

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N

E N

G

IN

E E

R

IN

G

NUMBER

SHEET

N

NORTH

TRUE

D

B R

O W

N P .E

C H

IE

F E

L E

C T

R

IC

A L S

E C

T

IO

N D

A R

E N A

B R

O W

N P .E

W

G -1

-B -0

A U

G U

S T

GENERAL SHEET NOTES

THE POST-WIDE ANNOUNCEMENTS.

VOLUME SHALL NOT INTERFERE WITH

NOTIFICATION SYSTEMS". SPEAKER

"DESIGN AND O&M: MASS

REQUIRMENTS OF UFC 4-021-01

1. SPEAKER SHALL MEET THE

FROM THE LEVEL OF DISCHARGE.

SUBSTANTIAL MEANS OF EGRESS

STAIRWELL AND OVER THE

OVER THE DOOR TO EACH EGRESS

STANDARD 48. LOCATE TEXT SIGNS

6. TEXT SIGNS SHALL COMPLY WITH UL

ALSO BE USED FOR MN SYSTEM.

5. SPEAKERS FOR FA SYSTEM SHALL

IN LEGEND, SHEET FA001.

4. FIRE ALARM SYMBOLS CAN BE FOUND

MANUFACTURER SPECIFICATIONS.

ACCORDANCE WITH NFPA 72 AND

3. MOUNT CO DETECTORS IN

FINISHED GRADE.

DOORS, AT 96 INCHES ABOVE

2. MOUNT EXTERIOR SPEAKERS ABOVE

OF MECHANICAL INFRARED HEATERS.

NOT MOUNT IN SAFETY CLEAR SPACE

WAREHOUSE, AT 17 FEET AFF UNO. DO

1. MOUNT SPEAKERS AND STROBES IN

CLS OFFICE

CLS OFFICE

CLS OFFICE

CLS OFFICE

F O

R M

A T

C H L

IN

E

R E F

A

15Cd

85dB

15Cd

70dB 70dB

15Cd

70dB

15Cd 15Cd

70dB

70dB

15Cd

70dB

70dB

70dB

70dB

70dB

15Cd

70dB

30Cd

70dB

30Cd

80dB

70dB

15Cd

70dB

15Cd

80dB

30Cd

80dB

30Cd

75Cd 75Cd

75Cd 75Cd

75Cd

85dB

30Cd

80dB

70dB

30Cd

70dB

ROOM

ELECTRICAL

CLS OFFICE

CLS OFFICE

CLS OFFICE

CLS OFFICE

CLS OFFICE

CLS OFFICE

CLS OFFICECLS OFFICE

CLS OFFICE

VESTIBULE

GENERAL

CUSTOMER SERVICE AREA

STOCK CONTROL OFFICE

OFFICE SUPPORT

CUSTOMER ISSUE BAY

TURN IN BAY

STORAGE WAREHOUSE

CORRIDOR C

CONFERENCE ROOM

SECURE STORAGE

ROOM

TELECOMM

CLOSET

JANITOR'S

CLOSET

JANITOR'S

ENTRANCE

15Cd

85dB 85dB

85dB 85dB

15Cd

80dB

WP

WPWP

RECEIVING / ISSUE BAY

CORRIDOR

ROOM

MECHANICAL

MEN

RESTROOM

WOMEN

RESTROOM

FORKLIFT CHARGING STATION

MAINTENANCE SHOP

P

P P

P P

CO

CO

CO

COCO

CO

CO

CO

L O

C F

A A

P

L

FA601

IS

E R D

IA

G R

A M

F

IR

E A

L A

R M M

A S

S N

O T

IF

IC

A T

IO

N

Fort Worth District

US Army Corps of Engineers

A P

P R

D A

T E

D E

S C

R

IP

T

IO

N S

Y M

$FILEL$

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

$DATE$ $TIME$

S u b m it te d b y

C h e c k e d b y

D ra w n b y

D e s ig n e d b y

P L

O T D

A T

E

P L

O T S

C A

L E

F O

R T H

O O

D T

E X

A S

T

H A

IR

D

E F

E N

S E A

R T

IL

L E

R Y D

IV

IS

IO

N

P N

U .S

A R

M Y C

O R

P S O

F E

N G

IN

E E

R S

T

A Y

L O

R S

T

F O

R T W

O R

T H T

X

S U

P P

L Y S

U P

P O

R T A

C T

IV

IT

Y W

A R

E H

O U

S E

S o li c it a ti o n N o

C o n tr a c t

N o

Is s u e D a te

G

C H

O A

T E

G

C H

O A

T E

E N

G

IN

E E

R

IN

G B

R A

N C

H

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N

E N

G

IN

E E

R

IN

G

NUMBER

SHEET

D

B R

O W

N P .E

C H

IE

F E

L E

C T

R

IC

A L S

E C

T

IO

N D

A R

E N A

B R

O W

N P .E

W

G -1

-B -0

A U

G U

S T

FUNCTIONS

AUXILIARY

SIGNAL

APPLIANCES

NOTIFICATION

S

IG

N A L F

R O

M B

A S E M

A S S N

O T

IF

IC

A T

IO

N E

Q U

IP

M E

N T

FIRE ALARMS

SUPERVISORY SIGNALS

CARBON MONOXIDE DETECTORS

KNOX BOX

TROUBLE CONDITIONS

SYSTEM OUTPUTS

01 MANUAL FIRE ALARM PULLSTATIONS

SMOKE DETECTOR

01 FIRE SUPPRESSION VALVE TAMPER SWITCH

PIV TAMPER SWITCH-SEE SITE SHEETS FOR LOCATE

WATERFLOW INDICATOR

WATERFLOW INDICATOR

HEAT DETECTOR (IF INSTALLED)

TRANSCEIVER ANTENNA

A L A

TEST MODE

01 IDC, NAC, SLC OPEN

IDC, NAC, SLC SHORT

IDC, NAC, SLC GROUND

06 06LOW BATTERY VOLTAGE

AC POWER FAILURE

H V

A C S

H U

T D

O W

N A

N D C

L O S E S

M O

K E D

A M

P E

R

A L A

FA601 NO SCALE

FIRE ALARM & MASS NOTIFICATION MATRIX1

FA601

M

IN

IM

U M

FA601

NO SCALE

ANTENNA MOUNTING DETAIL

COORDINATED WITH C.O.R.

TO ACCOMMODATE EXACT LOCATION

MODIFY ANTENNA MOUNTING AS REQUIRED

NOTE:

STAINLESS STEEL STRAPS

RGS CONDUIT WITH GALVANIZED OR

WEATHERHEAD, ATTACH TO 1 INCH

ANTENNA CABLE

1 INCH RGS CONDUIT WITH

SUPPORT STRAP

GALVANIZED CONDUIT

AT JUNCTION BOX.

COAXIAL CABLE TO ANTENNA

WEATHER & DRIP LOOP FOR

INSIDE. PROVIDE SERVICE ENTRY

J-BOX WITH SURGE PROTECTOR

SLEEVE AND RACEWAY.

CONDUIT SLEEVE. WEATHERSEAL

INCH 2

1PENETRATE WALL WITH 1

J-BOX AND ENCLOSURE.

ANTENNA CABLE WIRE BETWEEN

INCH PVC CONDUIT WITH 4

TRANSCEIVER UNIT IN MECHANICAL ROOM

FA601

BELOW.

GROUND WIRE TO STRUCTURE

BOND CONDUIT AND J-BOX WITH #6

T R

O U

B

S S N

O T

IF

IC

A T

IO

N A

U D

IO

S

IG

N A L T

H R

O U

G H S

P E

A K E

R S -V

O

IC

E

F A N

A C I N

T E

R R

U P T E

D F

O R M

N S A

N N

O U

N C

E M

E

T

IN

E

R R

U P T F

A N

A C F

O R M

N A

N N

O U

N C

E M

E N

T

IN

T E

R R

U P T T

H E P

A S

Y S T E

M

M N S V

IS

U A L A

P P L

IA

N C

E C

L E

A R S

T R

O B E

T R

O U

B L E I N

D

IC

A T

O R F

A N

A C I N

T E

R U P T E

D F

O R M

N S A

N N

O U

N C

E M

E

FAA

FACP &

BUILDING

BUILDING

SYSTEM AND

FIRE ALARM

BETWEEN BASE

TRANSMIT SIGNAL

BUILDING

SYSTEM AND

MASS NOTIFICATION

BETWEEN BASE

TRANSMIT SIGNAL

A L A

R M I N

D

IC

A T

O R A

U D

IO

-V

IS

U A L

S U P E

R V

IS

O R

Y I N

D

IC

A T

O R A

U D

IO

-V

IS

U A L

T R

O U

B L E

IN

D

IC

A T

O R A

U D

IO

-V

IS

U A L

S U P E

R V

IS

O R

Y I N

D

IC

A T

O R A

U D

IO

-V

IS

U A L

T R

O U

B L E

MASS NOTIFICATION SYSTEM (MNS)

LIVE VOICE MESSAGE ACTIVATED BY ACU/LOC

PRE-RECORDED MESSAGE ACTIVATED BY LOC

LIVE VOICE MESSAGE BY POST-WIDE SYSTEM

04 04

F A V

IS

U A L A

P P L

IA

N C

E C

L E

A R S

T R

O B E

V

IS

U A L T

E X T S

IG

N

CCDD R X Y BBZ AAPONML Q UTS WV EE FFGGA J KIB C D E F G H

A B C D E F G H I J K L M N O P Q R S T U V W X Y Z AA BBCCDDEE FFGG

A B C D E F G H I J K L M N O P Q R S T U V W X Y Z AA BBCCDDEE FFGG

A B C D E F G H I J K L M N O P Q R S T U V W X Y Z AA BBCCDDEE FFGG

F

IR

E A

L A

R M A

U D

IO

S

IG

N A L T

H R

O U

G H S

P E

A K E

R S -A

L A

R M T

O N

E

V O

IC

E A

N N

O U

N C

E M

E N

T T

H R

O U

G H S

P E

A K E

R S

RE: PEMB MFG.

STEEL JOIST

NECESSARY PRIOR TO AWARDING THE CONTRACT FOR CONSTRUCTION.

DESIGNATION (FIRE DEPARTMENT). UPDATE DIAGRAMS AND MATRIX AS

OF FIRE ALARM SIGNALS FROM THE WAREHOUSE TO POST IDENTIFIED

VERIFY LOCAL POST REQUIREMENTS FOR TRANSMISSION

FA602

IS

E R D

IA

G R

A M

F

IR

E A

L A

R M M

A S

S N

O T

IF

IC

A T

IO

N

Fort Worth District

GENERAL SHEET NOTES

KEY NOTES:

MOUNTING DETAILS.

DIAGRAM 1 AND 6 ON SHEET FX501 FOR

SEE SHEET FA102 FOR LOCATION. SEE 2

SEE CS103 FOR LOCATION.1

US Army Corps of Engineers

A P

P R

D A

T E

D E

S C

R

IP

T

IO

N S

Y M

$FILEL$

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

$DATE$ $TIME$

S u b m it te d b y

C h e c k e d b y

D ra w n b y

D e s ig n e d b y

P L

O T D

A T

E

P L

O T S

C A

L E

F O

R T H

O O

D T

E X

A S

T

H A

IR

D

E F

E N

S E A

R T

IL

L E

R Y D

IV

IS

IO

N

P N

U .S

A R

M Y C

O R

P S O

F E

N G

IN

E E

R S

T

A Y

L O

R S

T

F O

R T W

O R

T H T

X

S U

P P

L Y S

U P

P O

R T A

C T

IV

IT

Y W

A R

E H

O U

S E

S o li c it a ti o n N o

C o n tr a c t

N o

Is s u e D a te

G

C H

O A

T E

G

C H

O A

T E

E N

G

IN

E E

R

IN

G B

R A

N C

H

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N

E N

G

IN

E E

R

IN

G

NUMBER

SHEET

D

B R

O W

N P .E

C H

IE

F E

L E

C T

R

IC

A L S

E C

T

IO

N D

A R

E N A

B R

O W

N P .E

W

G -1

-B -0

A U

G U

S T

DEACTIVATE AUDIO AND VISUAL NAC DEVICES.

SYSTEM, THE FIRE ALARM SYSTEM SHALL

UPON ACTIVATION OF MASS NOTIFICATION 4.

MESSAGES.

PRE-RECORDED MASS NOTIFICATION

FUNCTIONAL REQUIREMENTS, INCLUDING

SEE CONTRACT SPECIFICATIONS FOR 3.

VOICE SYSTEM.

CAPABLE OF BEING CONNECTED TO A GIANT

MASS NOTIFICATION SYSTEM SHALL BE 2.

MATRIX.

1/FA601, FIRE ALARM MASS NOTIFICATION

FOR ORDER OF OPERATIONS, SEE DETAIL 1.

SIGN

TEXT

SIGN

TEXT

SIGN

TEXT

TYP.

TYP.

TYP.

FIRE ALARM/

MASS NOTIFICATION

PANEL

FIRE ALARM

TRANSCEIVER

SPD

RM 156

RM 156

AIR HANDLER SHUTDOWNS

WP

EXTERIOR

BUILDING

TYP. TYP.

D

TYP. TYP.

TYP. TYP.

LINE

END OF

TYP. TYP.

D

TYP. TYP.

TYP. TYP.

LINE

END OF

TYP. TYP.

D

TYP. TYP.

TYP. TYP.

LINE

END OF

TYP.TYP.

LINE

END OF

TYP.TYP.

LINE

END OF

AREA A

AREA B

AREA C

AREA A

TYP.TYP.

LINE

END OF

AREA B

LOC

TYP.

TYP.TYP.

LINE

END OF

AREA C

TYP.

FAAP

SEE DETAIL 2/FA601

TO FIRE ALARM ANTENNA.

A LOCKABLE CIRCUIT BREAKER.

ON CKT L2B-28, WHICH SHALL BE

2#12 & 1#12 GND IN 1/2" CONDUIT

EXISTING MONACO RECEIVING SYSTEM.

EQUAL; TO BE COMPATIBLE WITH

AND SHALL BE MONACO OR APPROVED

A FREQUENCY OF 141.3625 MHZ

TRANSCEIVER SHALL TRANSMIT AT

SPD

LINE

END OF

(OUTSIDE)

PIV

CO

CO

CO

P

K

FA602FA602 NO SCALE

1 FIRE ALARM & MASS NOTIFICATION RISER DIAGRAM

FIRE PROTECTION NOTES

IN ACCORDANCE WITH NFPA 72.

UFC 3-600-01 AND NFPA 13. AUTOMATIC SPRINKLER SYSTEM WILL BE SUPERVISED

1. PROVIDE COMPLETE AUTOMATIC SPRINKLER PROTECTION IN ACCORDANCE WITH

SHALL BE CENTERED IN CEILING TILES.

RATING FOR SPACES IDENTIFIED AS LIGHT AND ORDINARY HAZARD. SPRINKLERS

2. SPRINKLERS SHALL BE QUICK RESPONSE TYPE WITH 155 DEGREES F. TEMPERATURE

AND INSTALLED ACCORDING TO NFPA 13 REQUIREMENTS.

RATED AT 200 DEGREES F. OR HIGHER. ESFR SPRINKLER SYSTEM SHALL BE DESIGNED

3. WAREHOUSE/STORAGE SPACES SHALL BE PROTECTED WITH ESFR TYPE SPRINKLERS

REQUIREMENTS. SCHEDULE 10 OR LESS TYPE PIPE IS NOT ALLOWED.

4. PIPING SHALL BE SCHEDULE 40 BLACK PIPE IN ACCORDANCE WITH ASTM A53

A DESIGN AREA OF 1500 SFT.

5. SPACES IDENTIFIED AS LIGHT HAZARD HAVE A DESIGN DENSITY OF 0.10 GPM/SFT OVER

SPRINKLERS ARE NOT REQUIRED.

STORAGE HAZARD PROTECTION USING ESFR SPRINKLER HEADS. IN-RACK

7. SPACES IDENTIFIED AS ESFR SHALL FOLLOW THE REQUIREMENTS OF NFPA 13 FOR

A DESIGN AREA OF 2500 SFT.

6. SPACES IDENTIFIED AS ORDINARY HAZARD HAVE A DESIGN DENSITY OF 0.20 GPM/SFT OVER

HAZARD LEGEND

LIGHT HAZARD

ORDINARY HAZARD

ESFR

FDC

PIV

MOUNTED

WALL

0 1648 3216

" = 1'-0"16

1SCALE:

FX101

F

IR

E P

R O

T E

C T

IO

N F

L O

O R P

L A

N

SITE ORIENTATION

RE: CIVIL FOR

NORTH

PLAN

N

FIRE PROTECTION FLOOR PLAN

SCALE: 1/16" = 1'-0"

K

W

IL

L

IA

M S P .E

C H

IE

F

M E

C H

A N

IC

A L S

E C

T

IO

N G

IL

B E

R T J

V A

L L

A P .E

C

G

IB

B O

N S P .E

C

G

IB

B O

N S P .E

SPRINKLER RISER

US Army Corps of Engineers

A P

P R

D A

T E

D E

S C

R

IP

T

IO

N S

Y M

$FILEL$

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

$DATE$ $TIME$

KEY PLAN

A B C

S u b m it te d b y

C h e c k e d b y

D ra w n b y

D e s ig n e d b y

P L

O T D

A T

E

P L

O T S

C A

L E

F O

R T H

O O

D T

E X

A S

T

H A

IR

D

E F

E N

S E A

R T

IL

L E

R Y D

IV

IS

IO

N

P N

U .S

A R

M Y C

O R

P S O

F E

N G

IN

E E

R S

T

A Y

L O

R S

T

F O

R T W

O R

T H T

X

S U

P P

L Y S

U P

P O

R T A

C T

IV

IT

Y W

A R

E H

O U

S E

S o li c it a ti o n N o

C o n tr a c t

N o

Is s u e D a te

E N

G

IN

E E

R

IN

G B

R A

N C

H

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N

E N

G

IN

E E

R

IN

G

NUMBER

SHEET

W

G -1

-B -0

A U

G U

S T

RECEIVING / ISSUE BAY

TURN IN BAY

CUSTOMER ISSUE BAY

STORAGE WAREHOUSE

CUSTOMER SERVICE AREA

STOCK CONTROL OFFICE

OFFICE SUPPORT

SECURE STORAGE

ROOM

TELECOMM

CLS OFFICE126

CLS OFFICE

CLS OFFICE

CLS OFFICE

CLS OFFICE

CLS OFFICE

CLS OFFICE130

CLS OFFICE

CONFERENCE ROOM

CORRIDOR

150C

CLS OFFICE

CLS OFFICE

CLS OFFICE

CORRIDOR C

FORKLIFT CHARGING STATION

MAINTENANCE SHOP

WOMEN

RESTROOM

MEN

RESTROOM

ROOM

MECHANICAL

CLOSET

JANITOR'S

CORRIDOR

CLOSET

JANITOR'S

ROOM

ELECTRICAL

MEN

RESTROOM

WOMEN

RESTROOM

FIRE / RISER PUMP

MECHANICAL

FORKLIFT CHARGING STATION

MAINTENANCE SHOP

CONFERENCE ROOM

SECURE STORAGE

ROOM

TELECOMM

STOCK CONTROL OFFICE

OFFICE SUPPORT

VESTIBULE

GENERAL

CUSTOMER SERVICE AREA

CORRIDOR B

STORAGE WAREHOUSE

RECEIVING / ISSUE BAY

CUSTOMER ISSUE BAY

CUSTOMER SERVICE AREA

RECEIVING / ISSUE BAY

TURN IN BAY

CUSTOMER ISSUE BAY

STORAGE WAREHOUSE

CLS OFFICE

VESTIBULE

GENERAL

CUSTOMER SERVICE AREA

CLS OFFICE

STOCK CONTROL OFFICE

OFFICE SUPPORT

SECURE STORAGE

ROOM

TELECOMMCORRIDOR

104A

CLS OFFICE

CLS OFFICE

CONFERENCE ROOM

CLS OFFICE

CORRIDOR A

CLOSET

JANITOR'S

ELECTRICAL ROOM

ROOM

MECHANICAL

MEN

RESTROOM

WOMEN

RESTROOM

FORKLIFT CHARGING STATION

MAINTENANCE SHOP &

METRIC CONVERSION TABLE

GAL

°F

1 BAR

PSI

SF

FT

FT

IN

GPM/SF

GPM/SF

GPM

GPM

L X .264

1.8°C 32

100 KPa

BARS X 14.50380

SQM X 10.76391

M X 3.28084 mm X .00328 mm X .03937

L/min/SQM X .025

L/s/SQM X 1.47258

L/min X .264

L/s X 15.85077

SAFETY FACTOR

THE SYSTEM DESIGN SHALL INCLUDE A 7 PSI

SHALL VERIFY THE HYDRAULIC INFORMATION).

THE BASE OF THE RISER. (THE CONTRACTOR

FLOW OF 1100 GPM AS CALCULATED AT

A RESIDUAL PRESSURE OF 64 PSI AT A

THE STATIC PRESSURE IS 80 PSI WITH

REMOTE BRANCH LINE

1" DROP FROM END OF

BRANCH LINE

WALL STRUCTURE

TYP

WALL BRACKET

TEST VALVE

ORIFICE

SIGHT GLASS/

WALL PENETRATION

45°ELL

PAVED SURFACE)

IS ABOVE A

WHERE DISCHARGE

BLOCK (OMIT

CONCRETE SPLASH

18"X18"X4"

FLOOR

FINISHED

FLANGED CONNECTIONS.

PIPING JOINTS SHOWN ARE

CONTRACTOR'S DESIGN. ALL

RISER SHALL BE PER

SIZE OF WET PIPE SPRINKLER

NOTE:

FX501

IR

E P

R O

T E

C T

IO

N D

E T

A

IL

S

C

G

IB

B O

N S P .E

C

G

IB

B O

N S P .E

K

W

IL

L

IA

M S P .E

C H

IE

F

M E

C H

A N

IC

A L S

E C

T

IO

N G

IL

B E

R T J

V A

L L

A P .E

WET PIPE RISER

NOT TO SCALE

US Army Corps of Engineers

A P

P R

D A

T E

D E

S C

R

IP

T

IO

N S

Y M

NUMBER

SHEET

$FILEL$

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

$DATE$ $TIME$

S u b m it te d b y

C h e c k e d b y

D ra w n b y

D e s ig n e d b y

P L

O T D

A T

E

P L

O T S

C A

L E

F O

R T H

O O

D T

E X

A S

P N

U .S

A R

M Y C

O R

P S O

F E

N G

IN

E E

R S

T

A Y

L O

R S

T

F O

R T W

O R

T H T

X

S

T A

R M

O R

E D B

R

IG

A D

E C

O M

B A

T T

E A

M

S U

P P

L Y S

U P

P O

R T A

C T

IV

IT

Y W

A R

E H

O U

S E

S o li c it a ti o n N o

C o n tr a c t

N o

Is s u e D a te

E N

G

IN

E E

R

IN

G B

R A

N C

H

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N

E N

G

IN

E E

R

IN

G

W

G -1

-R -0

F E

B R

U A

R Y

W

G -1

-C

ENTRANCE

FIRE LINE

N

O P

E N

S H

U T

P R

E S

S U

I

P R

E S

S U

R S

N 1.85

WATER FLOW GPM

.344

.688

1.032

1.376

1.720

2.064

2.408

2.752

3.096

3.440

3.784

4.128

4.472

4.816

5.160

5.504

5.898

6.192

6.536

6.880

7.224

7.568

7.912

8.256

WATER FLOW L/S

SCALE C

SCALE B

SCALE A

SCALE C

SCALE B

SCALE A

25.2

12.6

6.3

50.5

25.2

12.6

75.8

37.9

18.9

101.0

50.5

25.2

126.2

63.1

31.6

151.4

75.7

37.9

176.7

88.3

44.2

201.9

101.0

50.5

227.2

113.6

56.8

252.4

126.2

63.1

TYPICAL

ITEM DESCRIPTION

BALL DRIP

TEST CONNECTION

CHECK VALVE

ELECTRIC BELL

WATER FLOW SWITCH

PRESSURE GAUGE

MAIN DRAIN

SWITCHES

ASSEMBLY W/TAMPER

BACKFLOW PREVENTER

2"O PIPE STANCHION

NOT TO SCALE

HYDRAULIC CURVE CONNECTION

INSPECTOR'S TEST

NOT TO SCALE

PITCH

INDICATOR VALVE

WALL POST

NOT TO SCALE

TOWARDS THE HANDWHEEL

IN THE END OF THE SLOT

THE LONG SCREW IS LOCATED

ROD

ACTUATOR

SWITCH

BASE

MOUNTING

12 1/4" DIA

PIPE SLEEVE

4" SCH 40

SPARE SPRINKLER CABINET

NOT TO SCALE

PROVIDE TWO SPARE SPRINKLERS.

FEWER THAN SIX OF A PARTICULAR TYPE,

APPLIES TO EACH TYPE (STYLE AND RATING) IF

2. THE REQUIRED NUMBER STIPULATED IN THE NFPA

ACCORDANCE WITH NFPA 13.

1. PROVIDE SPARE SPRINKLERS AND CABINETS IN

NOTES:

WITH NFPA 13,

IN ACCORDANCE

SIGN SHALL BE

IDENTIFICATION

CHAIN. THE

VALVE WITH

SIGN TO ALARM

SECURE SYSTEM

NOTES:

AUTOMATIC SPRINKLER SYSTEM

BY A HYDRAULICALLY DESIGNED

THIS BUILDING IS PROTECTED

HYDRAULIC SYSTEM

IDENTIFICATION

SYSTEM SIGN

NOT TO SCALE

LOCATION

NO. OF SPRINKLERS

BASIS FOR DESIGN

1. DENSITY

OF DISCHARGE

2. DESIGNED AREA

SYSTEM DEMAND

1. WATER FLOW RATE

THE RISER

AT THE BASE OF

2. RESIDUAL PRESSURE

3. STATIC PRESSURE

MOUNTED FDC

WALL

MOUNTED PIV

WALL

TEE CONNECTION

MAIN DRAIN VALVE

FLOW TEST LINE

W/ CHAINED O.S.&Y.

HYDRAULIC DESIGN DATA

PROVIDE MEANS OF ACCESS TO ALL PLUMBING AND HVAC EQUIPMENT.

G

H

I

K

V

W

U

U.N.O.- UNLESS NOTED OTHERWISE

L

SS

G

CWS

CWR

HWS

HWR

CD

F RS

RL

AIR VENT, MANUAL

FLOW METER, ORIFICE

TEST PORT)

PRESSURE/TEMPERATURE

PETE’S PLUG

BALL JOINT

GUIDE

EXPANSION JOINT

FLEXIBLE CONNECTOR

DOMESTIC COLD WATER

DOMESTIC HOT WATER

SANITARY SEWER

VENT

NATURAL GAS

CHILLED WATER SUPPLY

CHILLED WATER RETURN

FIRE PROTECTION

HEATING WATER SUPPLY

HEATING WATER RETURN

CONDENSATE DRAIN

REFRIGERANT SUCTION

REFRIGERANT LIQUIDFDC

CONNECTION

FIRE DEPARTMENT

VALVES

BALL VALVE

GATE VALVE

PLUG VALVE

AGLOBE VALVE

CHECK VALVE

SOLENOID VALVE

BUTTERFLY VALVE

S

SOLENOID TWO-WAY

MODULATING TWO-WAY

THREE-WAY

BALANCING VALVE

CALIBRATED

BALANCING VALVE

AUTOMATIC

PIPING SYSTEMS

BOP - BOTTOM OF PIPE ELEV.

BOD - BOTTOM OF DUCT ELEV.

E

D

C

B

A

N

O

P

R

S

T

VTR

CO

FD

WH

WCO

PRV

TPRV

PS

FS

AV

FLOOR DRAIN WITH TRAP

CLEANOUT

FLOOR DRAIN WITH

DIRECTION OF FLOW

FLOOR PENETRATION

WALL HYDRANT

WALL CLEANOUT

ARRESTOR/ACCESS

WATER HAMMER

THERMOMETER

THERMOMETER WELL

COCK

PRESSURE GAUGE WITH

PRESSURE SWITCH

FLOW SWITCH

AIR VENT, AUTOMATIC

AND HOSE CONNECTION

STRAINER W/BLOW-OFF

CONTINUATION

DROP IN PIPE

VALVE IN RISER

ELBOW

ELBOW UP

ELBOW DOWN

TEE

UNION

UNION, FLANGED

PIPE PITCH

VENT THRU ROOF

TOP CONNECTION

BOTTOM CONNECTION

CONCENTRIC REDUCER

ECCENTRIC REDUCER

VALVE

PRESSURE REDUCING

PRESSURE RELIEF

TEMP & PRESS RELIEF

ANCHOR

FLOOR SINKFS

DETAIL NO.

ZZ

NN

DETAIL LOCATION

ZZ

NN

S

NFHB

NON-FREEZING HOSE BIB

GENERAL NOTES:

PIPING SYMBOLSGENERAL ABBREVIATIONS

A.

B.

C.

D.

IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO COORDINATE.

DRAWINGS ARE SCHEMATIC AND ARE TO SHOW DESIGN INTENT,

IN ALL DIRECTIONS.

SHALL EXTEND 6" BEYOND THE FOOTPRINT OF THE EQUIPMENT

BE MOUNTED ON 6" HIGH HOUSEKEEPING PADS. THESE PADS

ALL FLOOR MOUNTED EQUIPMENT IN MECHANICAL ROOM SHALL

LIMITED TO 4 FPS.

LIMITED TO 5 FPS. DOMESTIC HOT WATER PIPING SHALL BE

(LATEST EDITION). DOMESTIC COLD WATER PIPING SHALL BE

ACCORDANCE WITH THE INTERNATIONAL PLUMBING CODE

WHERE PIPE SIZES ARE NOT INDICATED, THEY SHALL BE IN

REFERENCE SYMBOLOGY

REFER TO SHT. M-001 FOR ADDITIONAL GENERAL NOTES.

AP - ACCESS PANEL

AFF - ABOVE FINISHED FLOOR

OV - OUTLET VELOCITY

OD - OVERFLOW DRAIN

OC - ON CENTER

OA - OUTSIDE AIR

P-001

L

U M

B

IN

G L

E G

E N

D

LWT - LEAVING WATER TEMP.

LAT - LEAVING AIR TEMP.

kW - KILOWATTS

IE - INVERT ELEVATION

HD - HUB DRAIN

CONTRACTOR INSTALLED

GFCI - GOVERNMENT FURNISHED

GA - GAUGE

EXH - EXHAUST

EWT - ENTERING WATER TEMP.

ESP - EXTERNAL STATIC PRESSURE

SYSTEM

EMCS - ENERGY MONITORING AND CONTROL

EL - ELEVATION

EAT - ENTERING AIR TEMP.

EA - EXHAUST AIR

DN - DOWN

DISS - DIAMETER INDEX SAFTEY SYSTEM

DWC - DRINKING WATER COOLER

DX - DIRECT EXPANSION

DTC - DATA TERMINAL CABINET

DHWS - DOMESTIC HOT WATER SUPPLY

DHWR - DOMESTIC HOT WATER RETURN

DHW - DOMESTIC HOT WATER

DDC - DIRECT DIGITAL CONTROL

DCW - DOMESTIC COLD WATER

DCO - DOUBLE CLEANOUT

DB - DRY BULB TEMPERATURE

COP - CENTER OF PIPE

CONN - CONNECTION/CONNECT

COND - CONDENSATE/CONDENSER

CO2 - CARBON DIOXIDE

CLG - CEILING

CL - CENTERLINE

CFM - CUBIC FEET PER MINUTE

CAV - CONSTANT AIR VOLUME

CA - COMBUSTION AIR

CO - CLEANOUT

TSP - TOTAL STATIC PRESSURE

TMV - THERMOSTATIC MIXING VALVE

TOP OF STEEL

TOS - TOP OF SLAB/

TOP - TOP OF PIPE ELEVATION

TOD - TOP OF DUCT ELEVATION

RPM - REVOLUTIONS PER MINUTE

RD - ROOF DRAIN

RA - RETURN AIR

PD - PRESSURE DROP

E.

F.

G

W O

O D

A R

D P .E

G

W O

O D

A R

D P .E

K

W

IL

L

IA

M S P .E

G.

GUARD OR EQUAL.

PROVIDE WATER TRAP PRIMERS AT ALL FLOOR DRAINS; I.E. TRAP

H. REFER TO SHEET M-600 FOR PLUMBING EQUIPMENT SCHEDULES.

MEASURES. REFER TO SHEETS M-502 AND M-503.

SUPPORTED TO MEET…

This is the start of the file's text. The full file is on GovTribe.