C-17 Type III Hydrant Refueling System and Ramp Expansion
PN FJRP159073
145th Airlift Wing Charlotte, NC
North Carolina Air National Guard
Type B.3 Final Submittal Technical Specifications (Vol 2 of 2)
Burns & McDonnell Engineering Co., Inc.
Kansas City, Missouri
October 2017
W9133L-15-D-0003 Delivery Order D301
C- 17 Type I I I Fuel Syst em & Ramp Expansi on FJRP159073 145t h Ai r l i f t Wi ng, Nor t h Car ol i na Ai r Nat i onal Guar d
PROJECT TABLE OF CONTENTS
DI VI SI ON 01 - GENERAL REQUI REMENTS
01 11 00 SUMMARY OF WORK
01 14 00 WORK RESTRI CTI ONS
01 20 00. 00 20 PRI CE AND PAYMENT PROCEDURES
01 30 00 ADMI NI STRATI VE REQUI REMENTS
01 32 16. 00 20 PROJECT CONSTRUCTI ON PROGRESS SCHEDULES
01 33 00 SUBMI TTAL PROCEDURES
01 33 23. 33 AVI ATI ON FUEL SYSTEM SPECI FI C SUBMI TTAL REQUI REMENTS
01 33 29 SUSTAI NABI LI TY REPORTI NG
01 35 13 SPECI AL PROJECT PROCEDURES
01 35 26 GOVERNMENTAL SAFETY REQUI REMENTS
01 35 29. 13 HEALTH, SAFETY, AND EMERGENCY RESPONSE PROCEDURES FOR
CONTAMI NATED SI TES
01 45 00. 00 20 QUALI TY CONTROL
01 45 35 SPECI AL I NSPECTI ONS
01 50 00 TEMPORARY CONSTRUCTI ON FACI LI TI ES AND CONTROLS
01 57 19 TEMPORARY ENVI RONMENTAL CONTROLS
01 74 19 CONSTRUCTI ON AND DEMOLI TI ON WASTE MANAGEMENT
01 78 00 CLOSEOUT SUBMI TTALS
01 78 23 OPERATI ON AND MAI NTENANCE DATA
01 78 23. 33 OPERATI ON AND MAI NTENANCE MANUALS FOR AVI ATI ON FUEL
SYSTEMS
DI VI SI ON 02 - EXI STI NG CONDI TI ONS
02 41 00 DEMOLITION
02 61 13 EXCAVATI ON AND HANDLI NG OF CONTAMI NATED MATERI AL
02 81 00 TRANSPORTATI ON AND DI SPOSAL OF HAZARDOUS MATERI ALS
DI VI SI ON 03 - CONCRETE
03 30 00 CAST- I N- PLACE CONCRETE
DI VI SI ON 04 - MASONRY
04 20 00 UNI T MASONRY
DI VI SI ON 05 - METALS
05 12 00 STRUCTURAL STEEL
05 40 00 COLD- FORMED METAL FRAMI NG
05 50 13 MI SCELLANEOUS METAL FABRI CATI ONS
05 59 10 ROLLI NG COVER FOR AVI ATI ON REFUELI NG VAULTS
DI VI SI ON 06 - WOOD, PLASTI CS, AND COMPOSI TES
06 10 00 ROUGH CARPENTRY
DI VI SI ON 07 - THERMAL AND MOI STURE PROTECTI ON
07 11 13 BI TUMI NOUS DAMPPROOFI NG
07 21 13 BOARD AND BLOCK I NSULATI ON
07 27 26 FLUI D- APPLI ED AI R AND VAPOR BARRI ERS
07 60 00 FLASHI NG AND SHEET METAL
07 61 14. 00 20 STEEL STANDI NG SEAM ROOFI NG
07 84 00 FIRESTOPPING
PROJECT TABLE OF CONTENTS Page 1
07 92 00 JOI NT SEALANTS
DI VI SI ON 08 - OPENI NGS
08 11 13 STEEL DOORS AND FRAMES
08 51 13 ALUMI NUM WI NDOWS
08 71 00 DOOR HARDWARE
08 81 00 GLAZING
08 91 00 METAL WALL LOUVERS
DI VI SI ON 09 - FI NI SHES
09 22 00 SUPPORTS FOR PLASTER AND GYPSUM BOARD
09 29 00 GYPSUM BOARD
09 51 00 ACOUSTI CAL CEI LI NGS
09 65 00 RESI LI ENT FLOORI NG
09 77 20 DECORATI VE FI BERGLASS REI NFORCED WALL PANELS
09 90 00 PAI NTS AND COATI NGS
09 96 00 HI GH- PERFORMANCE COATI NGS
09 97 13. 17 THREE COAT EPOXY I NTERI OR COATI NG OF WELDED STEEL
PETROLEUM FUEL TANKS
09 97 13. 27 EXTERI OR COATI NG OF STEEL STRUCTURES
DI VI SI ON 10 - SPECI ALTI ES
10 14 00. 20 I NTERI OR/ EXTERI OR SI GNAGE
10 28 13 TOI LET ACCESSORI ES
10 44 16 FI RE EXTI NGUI SHERS
DI VI SI ON 13 - SPECI AL CONSTRUCTI ON
13 34 19 METAL BUI LDI NG SYSTEMS
13 48 00 SEI SMI C PROTECTI ON FOR MI SCELLANEOUS EQUI PMENT
13 48 00. 00 10 SEI SMI C PROTECTI ON FOR MECHANI CAL EQUI PMENT
13 73 19 JET BLAST DEFLECTOR FENCE FOR HI GH POWER RUN- UP VELOCI TI ES
DI VI SI ON 22 - PLUMBI NG
22 00 00 PLUMBI NG, GENERAL PURPOSE
DI VI SI ON 23 - HEATI NG, VENTI LATI NG, AND AI R CONDI TI ONI NG ( HVAC)
23 00 00 AI R SUPPLY, DI STRI BUTI ON, VENTI LATI ON, AND EXHAUST SYSTEMS
23 03 00. 00 20 BASI C MECHANI CAL MATERI ALS AND METHODS
23 07 00 THERMAL I NSULATI ON FOR MECHANI CAL SYSTEMS
23 82 02. 00 10 UNI TARY HEATI NG AND COOLI NG EQUI PMENT
23 82 46. 00 40 ELECTRI C UNI T HEATERS
DI VI SI ON 26 - ELECTRI CAL
26 00 00. 00 20 BASI C ELECTRI CAL MATERI ALS AND METHODS
26 05 48. 00 10 SEI SMI C PROTECTI ON FOR ELECTRI CAL EQUI PMENT
26 08 00 APPARATUS I NSPECTI ON AND TESTI NG
26 12 19. 10 THREE- PHASE PAD- MOUNTED TRANSFORMERS
26 20 00 I NTERI OR DI STRI BUTI ON SYSTEM
26 24 13 SWITCHBOARDS
26 28 01. 00 10 COORDI NATED POWER SYSTEM PROTECTI ON
26 32 15. 00 10 DI ESEL- GENERATOR SET STATI ONARY 100- 2500 KW, WI TH
AUXILIARIES
PROJECT TABLE OF CONTENTS Page 2
26 36 00. 00 10 AUTOMATI C TRANSFER SWI TCH AND BY- PASS/ I SOLATI ON SWI TCH
26 41 00 LI GHTNI NG PROTECTI ON SYSTEM
26 42 19. 00 10 CATHODI C PROTECTI ON BY I MPRESSED CURRENT
26 51 00 I NTERI OR LI GHTI NG
26 56 00 EXTERI OR LI GHTI NG
DI VI SI ON 28 - ELECTRONI C SAFETY AND SECURI TY
28 31 64. 00 10 FI RE DETECTI ON AND ALARM SYSTEM, ADDRESSABLE
DI VI SI ON 31 - EARTHWORK
31 00 00 EARTHWORK
31 11 00 CLEARI NG AND GRUBBI NG
31 24 00 SETTLEMENT MONI TORI NG
31 32 11 SOI L SURFACE EROSI ON CONTROL
31 36 00 WI RE MESH GABI ONS
31 63 26 DRI LLED SHAFTS
DI VI SI ON 32 - EXTERI OR I MPROVEMENTS
32 01 16. 71 COLD MI LLI NG ASPHALT PAVI NG
32 01 19 FI ELD MOLDED SEALANTS FOR SEALI NG JOI NTS I N RI GI D
PAVEMENTS
32 05 33 LANDSCAPE ESTABLI SHMENT
32 11 23 GRADED- CRUSHED AGGREGATE BASE COURSE
32 12 10 BI TUMI NOUS TACK AND PRI ME COATS
32 12 15. 13 HOT- MI X ASPHALT AI RFI ELD PAVI NG
32 12 16 HOT- MI X ASPHALT ( HMA) FOR ROADS
32 13 11 CONCRETE PAVEMENT FOR AI RFI ELDS AND OTHER HEAVY- DUTY
PAVEMENTS
32 16 13 CONCRETE SI DEWALKS AND CURBS AND GUTTERS
32 17 23 PAVEMENT MARKI NGS
32 31 13 CHAI N LI NK FENCES AND GATES
32 32 23 MECHANI CALLY STABI LI ZED EARTH RETAI NI NG WALL
32 92 19 SEEDING
DI VI SI ON 33 - UTI LI TI ES
33 08 53 AVI ATI ON FUEL DI STRI BUTI ON SYSTEM START- UP
33 09 53 AVI ATI ON FUEL PUMP CONTROL AND ANNUNCI ATI ON SYSTEM
33 11 00 WATER UTI LI TY DI STRI BUTI ON PI PI NG
33 30 00 SANI TARY SEWERS AND CONTAI NMENT DRAI NS
33 40 00 STORM DRAI NAGE UTI LI TI ES
33 52 43. 11 AVI ATI ON FUEL MECHANI CAL EQUI PMENT
33 52 43. 13 AVI ATI ON FUEL PI PI NG
33 52 43. 14 AVI ATI ON FUEL CONTROL VALVES
33 52 43. 23 AVI ATI ON FUEL PUMPS
33 52 43. 28 FI LTER SEPARATOR, AVI ATI ON FUELI NG SYSTEM
33 52 80 LI QUI D FUELS PI PELI NE COATI NG SYSTEMS
33 52 90. 00 20 WELDI NG FOR POL SERVI CE PI PI NG
33 56 10 FACTORY- FABRI CATED FUEL STORAGE TANKS
33 56 13. 13 STEEL TANKS WI TH FI XED ROOFS
33 56 19 FUEL I MPERMEABLE LI NER SYSTEM
33 65 00 CLEANI NG PETROLEUM STORAGE TANKS
33 71 02 UNDERGROUND ELECTRI CAL DI STRI BUTI ON
33 82 00 TELECOMMUNI CATI ONS OUTSI DE PLANT ( OSP)
DI VI SI ON 34 - TRANSPORTATI ON
PROJECT TABLE OF CONTENTS Page 3
34 73 16 JET BLAST DEFLECTOR FENCE FOR HI GH POWER RUN- UP VELOCI TI ES
- - End of Pr oj ect Tabl e of Cont ent s - -
PROJECT TABLE OF CONTENTS Page 4
SECTI ON 26 24 13
SWITCHBOARDS
05/15
PART 1 GENERAL
1. 1 REFERENCES
The publ i cat i ons l i s t ed bel ow f or m a par t of t hi s speci f i cat i on t o t he ext ent r ef er enced. The publ i cat i ons ar e r ef er r ed t o i n t he t ext by t he basi c desi gnat i on onl y.
AMERI CAN NATI ONAL STANDARDS I NSTI TUTE ( ANSI )
ANSI C12. 1 ( 2008) El ect r i c Met er s Code f or El ect r i c i t y Met er i ng
ASTM I NTERNATI ONAL ( ASTM)
ASTM A780 ( 2009; R 2015) St andar d Pr act i ce f or Repai r of Damaged and Uncoat ed Ar eas of Hot - Di p Gal vani zed Coat i ngs
ASTM D1535 ( 2014) Speci f y i ng Col or by t he Munsel l System
ASTM D709 ( 2016) St andar d Speci f i cat i on f or Lami nat ed Ther moset t i ng Mat er i al s
I NSTI TUTE OF ELECTRI CAL AND ELECTRONI CS ENGI NEERS ( I EEE)
I EEE 100 ( 2000; Ar chi ved) The Aut hor i t at i ve Di ct i onar y of I EEE St andar ds Ter ms
I EEE C2 ( 2017) Nat i onal El ect r i cal Saf et y Code
I EEE C37. 90. 1 ( 2013) St andar d f or Sur ge Wi t hst and Capabi l i t y ( SWC) Test s f or Rel ays and Rel ay Syst ems Associ at ed wi t h El ect r i c Power Appar at us
I NTERNATI ONAL ELECTRI CAL TESTI NG ASSOCI ATI ON ( NETA)
NETA ATS ( 2013) St andar d f or Accept ance Test i ng Speci f i cat i ons f or El ect r i cal Power Equi pment and Syst ems
NATI ONAL ELECTRI CAL MANUFACTURERS ASSOCI ATI ON ( NEMA)
ANSI / NEMA PB 2. 1 ( 2013) Gener al I nst r uct i ons f or Pr oper Handl i ng, I nst al l at i on, Oper at i on and Mai nt enance of Deadf r ont Di st r i but i on Swi t chboar ds Rat ed 600 V or Less
NEMA I CS 6 ( 1993; R 2011) I ndust r i al Cont r ol and Syst ems: Encl osur es
SECTI ON 26 24 13 Page 1
NEMA PB 2 ( 2011) Deadf r ont Di st r i but i on Swi t chboar ds
NATI ONAL FI RE PROTECTI ON ASSOCI ATI ON ( NFPA)
NFPA 70 ( 2017) Nat i onal El ect r i cal Code
UNDERWRI TERS LABORATORI ES ( UL)
UL 489 ( 2016) UL St andar d f or Saf et y Mol ded- Case Ci r cui t Br eaker s, Mol ded- Case Swi t ches and Ci r cui t - Br eaker Encl osur es
UL 891 ( 2005; Repr i nt Oct 2012) Swi t chboar ds
1. 2 RELATED REQUI REMENTS
Sect i on 26 08 00 APPARATUS I NSPECTI ON AND TESTI NG appl i es t o t hi s Sect i on, wi t h t he addi t i ons and modi f i cat i ons speci f i ed her ei n.
1. 3 DEFINITIONS
Unl ess ot her wi se speci f i ed or i ndi cat ed, el ect r i cal and el ect r oni cs t er ms used i n t hese speci f i cat i ons, and on t he dr awi ngs, ar e as def i ned i n
I EEE 100.
1. 4 SUBMITTALS
Gover nment appr oval i s r equi r ed f or submi t t al s wi t h a " G" desi gnat i on;
submi t t al s not havi ng a " G" desi gnat i on ar e f or Cont r act or QC appr oval .
Submi t t al s wi t h an " S" ar e f or i ncl usi on i n t he Sust ai nabi l i t y eNot ebook, i n conf or mance t o Sect i on 01 33 29 SUSTAI NABI LI TY REPORTI NG. Submi t t he f ol l owi ng i n accor dance wi t h Sect i on 01 33 00 SUBMI TTAL PROCEDURES:
SD- 02 Shop Dr awi ngs
Swi t chboar d Dr awi ngs; G
SD- 03 Pr oduct Dat a
Swi t chboar d; G
SD- 06 Test Repor t s
Swi t chboar d Desi gn Test s; G
Swi t chboar d Pr oduct i on Test s; G
Accept ance Checks and Test s; G
SD- 10 Oper at i on and Mai nt enance Dat a
Swi t chboar d Oper at i on and Mai nt enance, Dat a Package 5; G
SD- 11 Cl oseout Submi t t al s
Assembl ed Oper at i on and Mai nt enance Manual s; G
Equi pment Test Schedul e; G
SECTI ON 26 24 13 Page 2
Ser vi ce Ent r ance Avai l abl e Faul t Cur r ent Label ; G
1. 5 QUALI TY ASSURANCE
1. 5. 1 Pr oduct Dat a
I ncl ude manuf act ur er ' s i nf or mat i on on each submi t t al f or each component , devi ce and accessor y pr ovi ded wi t h t he swi t chboar d i ncl udi ng:
a. Ci r cui t br eaker t ype, i nt er r upt i ng r at i ng, and t r i p devi ces, i ncl udi ng avai l abl e set t i ngs.
b. Manuf act ur er ' s i nst r uct i on manual s and publ i shed t i me- cur r ent cur ves ( i n el ect r oni c f or mat ) of t he mai n secondar y br eaker and l ar gest secondar y f eeder devi ce.
1. 5. 2 Swi t chboar d Dr awi ngs
I ncl ude wi r i ng di agr ams and i nst al l at i on det ai l s of equi pment i ndi cat i ng pr oposed l ocat i on, l ayout and ar r angement , cont r ol panel s, accessor i es, pi pi ng, duct wor k, and ot her i t ems t hat must be shown t o ensur e a coor di nat ed i nst al l at i on. I dent i f y c i r cui t t er mi nal s on wi r i ng di agr ams and i ndi cat e t he i nt er nal wi r i ng f or each i t em of equi pment and t he i nt er connect i on bet ween each i t em of equi pment . I ndi cat e on t he dr awi ngs adequat e c l ear ance f or oper at i on, mai nt enance, and r epl acement of oper at i ng equi pment devi ces. I ncl ude t he namepl at e dat a, s i ze, and capaci t y on submi t t al . Al so i ncl ude appl i cabl e f eder al , mi l i t ar y, i ndust r y, and t echni cal soci et y publ i cat i on r ef er ences on submi t t al s. I ncl ude t he following:
a. One- l i ne di agr am i ncl udi ng br eaker s, cur r ent t r ansf or mer s, and met er s.
b. Out l i ne dr awi ngs i ncl udi ng f r ont el evat i on, sect i on v i ews, f oot pr i nt , and over al l di mensi ons.
c. Bus conf i gur at i on i ncl udi ng di mensi ons and amper e r at i ngs of bus bar s.
d. Mar ki ngs and NEMA namepl at e dat a.
e. Ci r cui t br eaker t ype, i nt er r upt i ng r at i ng, and t r i p devi ces, i ncl udi ng avai l abl e set t i ngs.
f . Wi r i ng di agr ams and el ement ar y di agr ams wi t h t er mi nal s i dent i f i ed, and i ndi cat i ng pr ewi r ed i nt er connect i ons bet ween i t ems of equi pment and t he i nt er connect i on bet ween t he i t ems.
g. Manuf act ur er ' s i nst r uct i on manual s and publ i shed t i me- cur r ent cur ves ( i n el ect r oni c f or mat ) of t he mai n secondar y br eaker and l ar gest secondar y f eeder devi ce. Use t hi s i nf or mat i on ( desi gner of r ecor d) t o pr ovi de br eaker set t i ngs t hat ensur es pr ot ect i on and coor di nat i on ar e achieved.
1. 5. 3 Regul at or y Requi r ement s
I n each of t he publ i cat i ons r ef er r ed t o her ei n, consi der t he advi sor y pr ovi s i ons t o be mandat or y, as t hough t he wor d, " shal l " or " must " had been subst i t ut ed f or " shoul d" wher ever i t appear s. I nt er pr et r ef er ences i n t hese publ i cat i ons t o t he " aut hor i t y havi ng j ur i sdi ct i on, " or wor ds of s i mi l ar meani ng, t o mean t he Cont r act i ng Of f i cer . Pr ovi de equi pment , SECTI ON 26 24 13 Page 3 mat er i al s, i nst al l at i on, and wor kmanshi p i n accor dance wi t h t he mandat or y and advi sor y pr ovi s i ons of NFPA 70 unl ess mor e st r i ngent r equi r ement s ar e speci f i ed or i ndi cat ed.
1. 5. 4 St andar d Pr oduct s
Pr ovi de mat er i al s and equi pment t hat ar e pr oduct s of manuf act ur er s r egul ar l y engaged i n t he pr oduct i on of such pr oduct s whi ch ar e of equal mat er i al , desi gn and wor kmanshi p, and:
a. Have been i n sat i sf act or y commer ci al or i ndust r i al use f or 2 year s pr i or t o bi d openi ng i ncl udi ng appl i cat i ons of equi pment and mat er i al s under s i mi l ar c i r cumst ances and of s i mi l ar s i ze.
b. Have been on sal e on t he commer ci al mar ket t hr ough adver t i sement s, manuf act ur er s ' cat al ogs, or br ochur es dur i ng t he 2- year per i od.
c. Wher e t wo or mor e i t ems of t he same cl ass of equi pment ar e r equi r ed, pr ovi de pr oduct s of a s i ngl e manuf act ur er ; however , t he component par t s of t he i t em need not be t he pr oduct s of t he same manuf act ur er unl ess st at ed i n t hi s Sect i on.
1. 5. 4. 1 Al t er nat i ve Qual i f i cat i ons
Pr oduct s havi ng l ess t han a 2- year f i el d ser vi ce r ecor d wi l l be accept abl e i f a cer t i f i ed r ecor d of sat i sf act or y f i el d oper at i on f or not l ess t han 6000 hour s, excl usi ve of t he manuf act ur er s ' f act or y or l abor at or y t est s, i s furnished.
1. 5. 4. 2 Mat er i al and Equi pment Manuf act ur i ng Dat e
Pr oduct s manuf act ur ed mor e t han 1 year pr i or t o dat e of del i ver y t o s i t e ar e not accept abl e.
1. 6 MAINTENANCE
1. 6. 1 Swi t chboar d Oper at i on and Mai nt enance Dat a
Submi t Oper at i on and Mai nt enance Manual s i n accor dance wi t h Sect i on 01 78 23
OPERATI ON AND MAI NTENANCE DATA.
1. 6. 2 Assembl ed Oper at i on and Mai nt enance Manual s
Assembl e and secur el y bi nd manual s i n dur abl e, har d cover ed, wat er r esi st ant bi nder s. Assembl e and i ndex t he manual s i n t he f ol l owi ng or der wi t h a t abl e of cont ent s:
a. Manuf act ur er ' s O&M i nf or mat i on r equi r ed by t he par agr aph SD- 10, OPERATI ON AND MAI NTENANCE DATA.
b. Cat al og dat a r equi r ed by t he par agr aph SD- 03, PRODUCT DATA.
c. Dr awi ngs r equi r ed by t he par agr aph SD- 02, SHOP DRAWI NGS.
d. Pr i ces f or spar e par t s and suppl y l i s t .
e. I nf or mat i on on met er i ng.
f . Desi gn t est r epor t s.
SECTI ON 26 24 13 Page 4
g. Pr oduct i on t est r epor t s.
1. 7 WARRANTY
Pr ovi de equi pment i t ems t hat ar e suppor t ed by ser v i ce or gani zat i ons r easonabl y conveni ent t o t he equi pment i nst al l at i on i n or der t o r ender sat i sf act or y ser vi ce t o t he equi pment on a r egul ar and emer gency basi s dur i ng t he war r ant y per i od of t he cont r act .
PART 2 PRODUCTS
2. 1 PRODUCT COORDI NATI ON
Pr oduct s and mat er i al s not consi der ed t o be swi t chboar ds and r el at ed accessor i es ar e speci f i ed i n Sect i on 33 71 02 UNDERGROUND ELECTRI CAL DI STRI BUTI ON and Sect i on 26 20 00 I NTERI OR DI STRI BUTI ON SYSTEM.
2. 2 SWITCHBOARD
NEMA PB 2 and UL 891.
2. 2. 1 Ratings
Pr ovi de equi pment wi t h t he f ol l owi ng r at i ngs:
a. Vol t age r at i ng: 480Y/ 277 vol t s AC, t hr ee- phase, 4- wi r e.
b. Cont i nuous cur r ent r at i ng of t he mai n bus: 1200 amper es as i ndi cat ed.
c. Shor t - c i r cui t cur r ent r at i ng: 50k r ms symmet r i cal amper es as i ndi cat ed.
d. UL l i s t ed and l abel ed as ser v i ce ent r ance equi pment .
2. 2. 2 Construction
Pr ovi de t he f ol l owi ng:
a. Swi t chboar d: Consi st i ng of one ver t i cal sect i on and al i gned as indicated.
b. Al l c i r cui t br eaker s: Fr ont accessi bl e.
c. Rear al i gned swi t chboar ds: Fr ont accessi bl e l oad connect i ons.
d. Wher e i ndi cat ed, " space f or f ut ur e" or " space" means t o i ncl ude a ver t i cal bus pr ovi ded behi nd a bl ank f r ont cover . Wher e i ndi cat ed, " pr ovi s i on f or f ut ur e" means f ul l har dwar e pr ovi ded t o mount a br eaker sui t abl e f or t he l ocat i on.
e. Compl et el y f act or y engi neer ed and assembl ed, i ncl udi ng pr ot ect i ve devi ces and equi pment i ndi cat ed wi t h necessar y i nt er connect i ons, i nst r ument at i on, and cont r ol wi r i ng.
2. 2. 2. 1 Enclosure
Pr ovi de t he f ol l owi ng:
a. Encl osur e: NEMA I CS 6 Type 1.
SECTI ON 26 24 13 Page 5
b. Encl osur e: Bol t ed t oget her wi t h r emovabl e bol t - on s i de and r ear cover s.
c. Fr ont door s: Pr ovi ded wi t h padl ockabl e vaul t handl es wi t h a t hr ee poi nt cat ch.
d. Base: I ncl udes any par t of encl osur e t hat i s wi t hi n 3 i nches of concr et e pad.
e. Pai nt col or : ASTM D1535 l i ght gr ay No. 61 or No. 49 over r ust inhibitor.
2. 2. 2. 2 Bus Bar s
Pr ovi de t he f ol l owi ng:
a. Bus bar s: Copper wi t h s i l ver - pl at ed cont act sur f aces.
( 1) Phase bus bar s: Uni nsul at ed.
( 2) Neut r al bus: Rat ed 100 per cent of t he mai n bus cont i nuous cur r ent r at i ng. Neut r al bus f or ser vi ce ent r ance onl y.
b. Make bus connect i ons and j oi nt s wi t h har dened st eel bol t s.
c. Mai n- bus ( t hr ough bus) : Rat ed at t he f ul l ampaci t y of t he mai n t hr oughout t he swi t chboar d.
d. Mi ni mum 1/ 4 by 2 i nch copper gr ound bus secur ed t o each ver t i cal sect i on al ong t he ent i r e l engt h of t he swi t chboar d.
2. 2. 2. 3 Mai n Sect i on
Pr ovi de t he mai n sect i on consi st i ng of a combi nat i on sect i on wi t h mol ded- case ci r cui t br eaker s f or t he mai n devi ces as i ndi cat ed.
2. 2. 3 Pr ot ect i ve Devi ce
Pr ovi de mai n pr ot ect i ve devi ces as i ndi cat ed.
2. 2. 3. 1 Mol ded- Case Ci r cui t Br eaker
Pr ovi de t he f ol l owi ng:
a. UL 489. UL l i s t ed and l abel ed, st andar d r at ed br anch br eaker s, el ect r i cal l y oper at ed, l ow vol t age mol ded- case ci r cui t br eaker , wi t h a shor t - c i r cui t cur r ent r at i ng of 50k r ms symmet r i cal amper es.
b. Br eaker f r ame si ze: 1200 amper es.
c. Ser i es r at ed c i r cui t br eaker s ar e unaccept abl e.
2. 2. 4 El ect r oni c Tr i p Uni t s
Equi p mai n br eaker s wi t h a sol i d- st at e t r i ppi ng syst em consi st i ng of t hr ee cur r ent sensor s and a mi cr opr ocessor - based t r i p uni t t hat pr ovi des t r ue r ms sensi ng adj ust abl e t i me- cur r ent c i r cui t pr ot ect i on. I ncl ude t he f ol l owi ng:
SECTI ON 26 24 13 Page 6
a. Cur r ent sensor s amper e r at i ng: The same as t he br eaker f r ame r at i ng.
b. Tr i p uni t amper e r at i ng: As i ndi cat ed.
c. El ect r oni c t r i p uni t s: Pr ovi de addi t i onal f eat ur es:
( 1) Br eaker s: I ncl ude l ong del ay pi ck- up and t i me set t i ngs, and LED i ndi cat i on of cause of c i r cui t br eaker t r i p.
( 2) Mai n br eaker s: I ncl ude shor t del ay pi ck- up and t i me set t i ngs, i nst ant aneous set t i ngs, and gr ound f aul t set t i ngs.
2. 2. 5 Metering
2. 2. 5. 1 Di gi t al Met er s
I EEE C37. 90. 1 f or sur ge wi t hst and. Pr ovi de t r ue r ms, pl us/ mi nus one per cent accur acy, pr ogr ammabl e, mi cr opr ocessor - based met er encl osed i n a seal ed case wi t h t he f ol l owi ng f eat ur es.
a. Di spl ay capabi l i t y :
( 1) Mul t i - Funct i on Met er : Di spl ay a sel ect ed phase t o neut r al vol t age, phase t o phase vol t age, per cent phase t o neut r al vol t age THD, per cent phase t o phase vol t age THD; a sel ect ed phase cur r ent , neut r al cur r ent , per cent phase cur r ent THD, per cent neut r al cur r ent ; sel ect ed t ot al PF, kW, KVA, kVAR, FREQ, kVAh, kWh.
Det ect ed al ar m condi t i ons i ncl ude over / under cur r ent , over / under vol t age, over / under KVA, over / under f r equency, over / under sel ect ed PF/ kVAR, vol t age phase r ever sal , vol t age i mbal ance, r ever se power , over per cent THD. I ncl ude a For m C KYZ pul se out put r el ay on t he meter.
b. Desi gn met er s t o accept i nput f r om st andar d 5A secondar y i nst r ument t r ansf or mer s and vol t age moni t or i ng r ange t o 600 vol t s, phase t o phase.
c. Pr ovi de pr ogr ammi ng vi a a f r ont panel di spl ay and a communi cat i on i nt er f ace accessi bl e by a comput er .
d. Pr ovi de passwor d secur ed pr ogr ammi ng st or ed i n non- vol at i l e EEPROM memory.
e. Pr ovi de di gi t al communi cat i ons i n a Modbus [ RTU] pr ot ocol v i a a RS485 ser i al por t .
f . Pr ovi de met er t hat cal cul at es and st or es aver age max/ mi n demand val ues wi t h t i me and dat e f or al l r eadi ngs based on a user sel ect abl e s l i di ng wi ndow aver agi ng per i od.
g. Pr ovi de met er wi t h pr ogr ammabl e hi / l ow set l i mi t s wi t h t wo For m C dr y cont act r el ays when exceedi ng al ar m condi t i ons.
h. I ncl ude hi st or i cal t r end l oggi ng capabi l i t y wi t h t he abi l i t y t o st or e up t o 100, 000 dat a poi nt s wi t h i nt er val s of 1 second t o 180 mi nut es.
Pr ovi de a uni t t hat can st or e and t i me st amp up t o 1000 pr ogr ammabl e t r i gger ed condi t i ons.
i . Pr ovi de event wavef or m r ecor di ng t r i gger ed by t he r ms of 2 cycl es of vol t age or cur r ent exceedi ng pr ogr ammabl e set poi nt s. St or e wavef or ms
SECTI ON 26 24 13 Page 7 f or al l 6 channel s of vol t age and cur r ent f or a mi ni mum of 10 cycl es pr i or t o t he event and 50 cycl es past t he event .
2. 2. 6 Ter mi nal Boar ds
Pr ovi de wi t h engr aved pl ast i c t er mi nal st r i ps and scr ew t ype t er mi nal s f or ext er nal wi r i ng bet ween component s and f or i nt er nal wi r i ng bet ween r emovabl e assembl i es. Pr ovi de shor t - c i r cui t i ng t ype t er mi nal boar ds associ at ed wi t h cur r ent t r ansf or mer . Ter mi nat e conduct or s f or cur r ent t r ansf or mer s wi t h r i ng- t ongue l ugs. Pr ovi de t er mi nal boar d i dent i f i cat i on t hat i s i dent i cal i n s i mi l ar uni t s. Pr ovi de col or coded ext er nal wi r i ng t hat i s col or coded consi st ent l y f or s i mi l ar t er mi nal boar ds.
2. 2. 7 Wi r e Mar ki ng
Mar k cont r ol and met er i ng conduct or s at each end. Pr ovi de f act or y i nst al l ed, whi t e, pl ast i c t ubi ng, heat st amped wi t h bl ack bl ock t ype l et t er s on f act or y- i nst al l ed wi r i ng. On f i el d- i nst al l ed wi r i ng, pr ovi de whi t e, pr epr i nt ed, pol yvi nyl chl or i de ( PVC) s l eeves, heat st amped wi t h bl ack bl ock t ype l et t er s. Pr ovi de a s i ngl e l et t er or number on each sl eeve, el l i pt i cal l y shaped t o secur el y gr i p t he wi r e, and keyed i n such a manner t o ensur e al i gnment wi t h adj acent s l eeves. Pr ovi de speci f i c wi r e mar ki ngs usi ng t he appr opr i at e combi nat i on of i ndi v i dual s l eeves. I ndi cat e on each wi r e mar ker t he devi ce or equi pment , i ncl udi ng speci f i c t er mi nal number t o whi ch t he r emot e end of t he wi r e i s at t ached.
2. 3 MANUFACTURER' S NAMEPLATE
Pr ovi de a namepl at e on each i t em of equi pment bear i ng t he manuf act ur er ' s name, addr ess, model number , and ser i al number secur el y af f i xed i n a conspi cuous pl ace; t he namepl at e of t he di st r i but i ng agent i s not accept abl e. Thi s namepl at e and met hod of at t achment may be t he manuf act ur er ' s st andar d i f i t cont ai ns t he r equi r ed i nf or mat i on.
2. 4 FI ELD FABRI CATED NAMEPLATES
ASTM D709. Pr ovi de l ami nat ed pl ast i c namepl at es f or each swi t chboar d, equi pment encl osur e, r el ay, swi t ch, and devi ce; as speci f i ed i n t hi s sect i on or as i ndi cat ed on t he dr awi ngs. I dent i f y on each namepl at e i nscr i pt i on t he f unct i on and, when appl i cabl e, t he posi t i on. Pr ovi de namepl at es of mel ami ne pl ast i c, 0. 125 i nch t hi ck, whi t e wi t h bl ack cent er cor e. Pr ovi de mat t e f i ni sh sur f ace. Pr ovi de squar e cor ner s. Accur at el y al i gn l et t er i ng and engr ave i nt o t he cor e. Pr ovi de namepl at es wi t h mi ni mum si ze of one by 2. 5 i nches. Pr ovi de l et t er i ng t hat i s a mi ni mum of 0. 25 i nch hi gh nor mal bl ock st y l e.
2. 5 SOURCE QUALI TY CONTROL
2. 5. 1 Equi pment Test Schedul e
The Gover nment r eser ves t he r i ght t o wi t ness t est s. Pr ovi de equi pment t est schedul es f or t est s t o be per f or med at t he manuf act ur er ' s t est f aci l i t y .
Submi t r equi r ed t est schedul e and l ocat i on, and not i f y t he Cont r act i ng Of f i cer 30 cal endar days bef or e schedul ed t est dat e. Not i f y Cont r act i ng Of f i cer 15 cal endar days i n advance of changes t o schedul ed dat e.
Pr ovi de t he f ol l owi ng as par t of t est equi pment cal i br at i on:
a. Pr ovi de a cal i br at i on pr ogr am whi ch assur es t hat al l appl i cabl e t est
SECTI ON 26 24 13 Page 8 i nst r ument s ar e mai nt ai ned wi t hi n r at ed accur acy.
b. Accur acy: Tr aceabl e t o t he Nat i onal I nst i t ut e of St andar ds and Technology.
c. I nst r ument cal i br at i on f r equency schedul e: Less t han or equal t o 12 mont hs f or bot h t est f l oor i nst r ument s and l eased speci al t y equi pment .
d. Dat ed cal i br at i on l abel s: Vi s i bl e on al l t est equi pment .
e. Cal i br at i ng st andar d: Hi gher accur acy t han t hat of t he i nst r ument tested.
f . Keep up- t o- dat e r ecor ds t hat i ndi cat e dat es and t est r esul t s of i nst r ument s cal i br at ed or t est ed. For i nst r ument s cal i br at ed by t he manuf act ur er on a r out i ne basi s, i n l i eu of t hi r d par t y cal i br at i on, i ncl ude t he f ol l owi ng:
( 1) Mai nt ai n up- t o- dat e i nst r ument cal i br at i on i nst r uct i ons and pr ocedur es f or each t est i nst r ument .
( 2) I dent i f y t he t hi r d par t y/ l abor at or y cal i br at ed i nst r ument t o ver i f y t hat cal i br at i ng st andar d i s met .
2. 5. 2 Swi t chboar d Desi gn Test s
NEMA PB 2 and UL 891.
2. 5. 2. 1 Desi gn Test s
Fur ni sh document at i on showi ng t he r esul t s of desi gn t est s on a pr oduct of t he same ser i es and r at i ng as t hat pr ovi ded by t hi s Speci f i cat i on.
a. Shor t - c i r cui t cur r ent t est .
b. Encl osur e t est s.
c. Di el ect r i c t est .
2. 5. 3 Swi t chboar d Pr oduct i on Test s
NEMA PB 2 and UL 891. Fur ni sh r epor t s whi ch i ncl ude r esul t s of pr oduct i on t est s per f or med on t he act ual equi pment f or t hi s Pr oj ect . These t est s include:
a. 60- her t z di el ect r i c t est s.
b. Mechani cal oper at i on t est s.
c. El ect r i cal oper at i on and cont r ol wi r i ng t est s.
d. Gr ound f aul t sensi ng equi pment t est .
2. 6 ARC FLASH WARNI NG LABEL
Pr ovi de war ni ng l abel f or swi t chboar ds. Locat e t hi s sel f - adhesi ve war ni ng l abel on t he out s i de of t he encl osur e war ni ng of pot ent i al el ect r i cal ar c f l ash hazar ds and appr opr i at e PPE r equi r ed. Pr ovi de l abel f or mat as indicated.
SECTI ON 26 24 13 Page 9
2. 7 SERVI CE ENTRANCE AVAI LABLE FAULT CURRENT LABEL
Pr ovi de l abel on ext er i or of swi t chboar ds used as ser vi ce equi pment l i s t i ng t he maxi mum avai l abl e f aul t cur r ent at t hat l ocat i on. I ncl ude on t he l abel t he dat e t hat t he f aul t cal cul at i on was per f or med and t he cont act i nf or mat i on f or t he or gani zat i on t hat compl et ed t he cal cul at i on. Locat e t hi s sel f - adhesi ve war ni ng l abel on t he out s i de of t he swi t chboar d.
Pr ovi de l abel f or mat as i ndi cat ed.
PART 3 EXECUTI ON
3. 1 INSTALLATION
Conf or m t o I EEE C2, NFPA 70, and t o t he r equi r ement s speci f i ed her ei n.
Pr ovi de new equi pment and mat er i al s unl ess i ndi cat ed or speci f i ed ot her wi se.
3. 2 I NSTALLATI ON OF EQUI PMENT AND ASSEMBLI ES
I nst al l and connect equi pment f ur ni shed under t hi s sect i on as i ndi cat ed on pr oj ect dr awi ngs, t he appr oved shop dr awi ngs, and as speci f i ed her ei n.
3. 2. 1 Switchboard
ANSI / NEMA PB 2. 1.
3. 2. 2 Met er s and I nst r ument Tr ansf or mer s
ANSI C12. 1.
3. 2. 3 Fi el d Appl i ed Pai nt i ng
Wher e f i el d pai nt i ng of encl osur es i s r equi r ed t o cor r ect damage t o t he manuf act ur er ' s f act or y appl i ed coat i ngs, pr ovi de manuf act ur er ' s r ecommended coat i ngs and appl y i n accor dance wi t h manuf act ur er ' s i nst r uct i ons.
3. 2. 4 Gal vani z i ng Repai r
Repai r damage t o gal vani zed coat i ngs usi ng ASTM A780, z i nc r i ch pai nt , f or gal vani z i ng damaged by handl i ng, t r anspor t i ng, cut t i ng, wel di ng, or bol t i ng. Do not heat sur f aces t hat r epai r pai nt has been appl i ed t o.
3. 2. 5 Fi el d Fabr i cat ed Namepl at e Mount i ng
Pr ovi de number , l ocat i on, and l et t er desi gnat i on of namepl at es as i ndi cat ed. Fast en namepl at es t o t he devi ce wi t h a mi ni mum of t wo sheet - met al scr ews or t wo r i vet s.
3. 3 FOUNDATI ON FOR EQUI PMENT AND ASSEMBLI ES
3. 3. 1 I nt er i or Locat i on
Mount swi t chboar d on concr et e s l ab as f ol l ows:
a. Unl ess ot her wi se i ndi cat ed, pr ovi de t he s l ab wi t h di mensi ons at l east 4 i nches t hi ck.
b. I nst al l s l ab such t hat t he t op of t he concr et e s l ab i s appr oxi mat el y 4 i nches above t he f i ni shed gr ade.
SECTI ON 26 24 13 Page 10
c. Pr ovi de edges above gr ade 1/ 2 i nch chamf er .
d. Pr ovi de s l ab of adequat e s i ze t o pr oj ect at l east 8 i nches beyond t he equipment.
e. Pr ovi de condui t t ur nups and cabl e ent r ance space r equi r ed by t he equi pment t o be mount ed.
f . Seal voi ds ar ound condui t openi ngs i n s l ab wi t h wat er - and oi l - r esi st ant caul k i ng or seal ant .
g. Cut of f and bush condui t s 3 i nches above sl ab sur f ace.
h. Pr ovi de concr et e wor k as speci f i ed i n Sect i on 03 30 00 CAST- I N- PLACE
CONCRETE.
3. 4 FI ELD QUALI TY CONTROL
3. 4. 1 Per f or mance of Accept ance Checks and Test s
Per f or m i n accor dance wi t h t he manuf act ur er ' s r ecommendat i ons and i ncl ude t he f ol l owi ng v i sual and mechani cal i nspect i ons and el ect r i cal t est s, per f or med i n accor dance wi t h NETA ATS.
3. 4. 1. 1 Swi t chboar d Assembl i es
a. Vi sual and Mechani cal I nspect i on:
( 1) Compar e equi pment namepl at e dat a wi t h speci f i cat i ons and appr oved shop dr awi ngs.
( 2) I nspect physi cal , el ect r i cal , and mechani cal condi t i on.
( 3) Ver i f y appr opr i at e anchor age, r equi r ed ar ea c l ear ances, and cor r ect al i gnment .
( 4) Cl ean swi t chboar d and ver i f y shi ppi ng br aci ng, l oose par t s, and document at i on shi pped i nsi de cubi c l es have been r emoved.
( 5) I nspect al l door s, panel s, and sect i ons f or pai nt , dent s, scr at ches, f i t , and mi ssi ng har dwar e.
( 6) Ver i f y t hat c i r cui t br eaker s i zes and t ypes cor r espond t o appr oved shop dr awi ngs as wel l as t o t he c i r cui t br eaker ’ s addr ess f or mi cr opr ocessor - communi cat i on packages.
( 7) I nspect al l bol t ed el ect r i cal connect i ons f or hi gh r esi st ance usi ng l ow- r esi st ance ohmmet er , ver i f y i ng t i ght ness of accessi bl e bol t ed el ect r i cal connect i ons by cal i br at ed t or que- wr ench met hod, or per f or mi ng t her mogr aphi c sur vey.
( 8) Conf i r m cor r ect oper at i on and sequenci ng of el ect r i cal and mechani cal i nt er l ock syst ems.
( 9) Conf i r m cor r ect appl i cat i on of manuf act ur er ' s r ecommended lubricants.
( 10) I nspect i nsul at or s f or evi dence of physi cal damage or
SECTI ON 26 24 13 Page 11 cont ami nat ed sur f aces.
( 11) Ver i f y cor r ect bar r i er i nst al l at i on and oper at i on.
( 12) Exer ci se al l act i ve component s.
( 13) I nspect al l mechani cal i ndi cat i ng devi ces f or cor r ect oper at i on.
( 14) Ver i f y t hat f i l t er s ar e i n pl ace and vent s ar e c l ear .
( 15) Test oper at i on, al i gnment , and penet r at i on of i nst r ument t r ansf or mer wi t hdr awal di sconnect s.
( 16) I nspect cont r ol power t r ansf or mer s.
b. El ect r i cal Test s:
( 1) Per f or m i nsul at i on- r esi st ance t est s on each bus sect i on.
( 2) Per f or m di el ect r i c wi t hst and vol t age t est s.
( 3) Per f or m i nsul at i on- r esi st ance t est on cont r ol wi r i ng; Do not per f or m t hi s t est on wi r i ng connect ed t o sol i d- st at e component s.
( 4) Per f or m cont r ol wi r i ng per f or mance t est .
( 5) Per f or m pr i mar y cur r ent i nj ect i on t est s on t he ent i r e cur r ent c i r cui t i n each sect i on of assembl y.
3. 4. 1. 2 Ci r cui t Br eaker s
Low Vol t age Mol ded Case wi t h Sol i d St at e Tr i ps.
a. Vi sual and Mechani cal I nspect i on:
( 1) Compar e namepl at e dat a wi t h speci f i cat i ons and appr oved shop drawings.
( 2) I nspect c i r cui t br eaker f or cor r ect mount i ng.
( 3) Oper at e c i r cui t br eaker t o ensur e smoot h oper at i on.
( 4) I nspect case f or cr acks or ot her def ect s.
( 5) I nspect al l bol t ed el ect r i cal connect i ons f or hi gh r esi st ance usi ng l ow r esi st ance ohmmet er , ver i f y i ng t i ght ness of accessi bl e bol t ed connect i ons and/ or cabl e connect i ons by cal i br at ed t or que- wr ench met hod, or per f or mi ng t her mogr aphi c sur vey.
( 6) I nspect mechani sm cont act s and ar c chut es i n unseal ed uni t s.
b. El ect r i cal Test s:
( 1) Per f or m cont act - r esi st ance t est s.
( 2) Per f or m i nsul at i on- r esi st ance t est s.
( 3) Per f or m Br eaker adj ust ment s f or f i nal set t i ngs i n accor dance wi t h Gover nment pr ovi ded set t i ngs.
SECTI ON 26 24 13 Page 12
( 4) Per f or m l ong- t i me del ay t i me- cur r ent char act er i st i c t est s
( 5) Det er mi ne shor t - t i me pi ckup and del ay by pr i mar y cur r ent i nj ect i on.
( 6) Det er mi ne gr ound- f aul t pi ckup and t i me del ay by pr i mar y cur r ent injection.
( 7) Det er mi ne i nst ant aneous pi ckup cur r ent by pr i mar y i nj ect i on.
3. 4. 1. 3 Met er i ng and I nst r ument at i on
a. Vi sual and Mechani cal I nspect i on:
( 1) Compar e equi pment namepl at e dat a wi t h speci f i cat i ons and appr oved shop dr awi ngs.
( 2) I nspect physi cal and mechani cal condi t i on.
( 3) Ver i f y t i ght ness of el ect r i cal connect i ons.
b. El ect r i cal Test s:
( 1) Det er mi ne accur acy of met er s at 25, 50, 75, and 100 per cent of f ul l scal e.
( 2) Cal i br at e wat t hour met er s accor di ng t o manuf act ur er ' s publ i shed data.
( 3) Ver i f y al l i nst r ument mul t i pl i er s.
( 4) El ect r i cal l y conf i r m t hat cur r ent t r ansf or mer and vol t age t r ansf or mer secondar y c i r cui t s ar e i nt act .
3. 4. 2 Fol l ow- Up Ver i f i cat i on
Upon compl et i on of accept ance checks, set t i ngs, and t est s, show by demonst r at i on i n ser vi ce t hat c i r cui t s and devi ces ar e i n good oper at i ng condi t i on and pr oper l y per f or mi ng t he i nt ended f unct i on. Tr i p c i r cui t br eaker s by oper at i on of each pr ot ect i ve devi ce. Test each i t em t o per f or m i t s f unct i on not l ess t han t hr ee t i mes. As an except i on t o r equi r ement s st at ed el sewher e i n t he cont r act , pr ovi de t he Cont r act i ng Of f i cer 5 wor ki ng days advance not i ce of t he dat es and t i mes f or checks, set t i ngs, and t est s.
- - End of Sect i on - -
SECTI ON 26 24 13 Page 13
SECTI ON 26 28 01. 00 10
COORDI NATED POWER SYSTEM PROTECTI ON
10/07
PART 1 GENERAL
1. 1 REFERENCES
The publ i cat i ons l i s t ed bel ow f or m a par t of t hi s speci f i cat i on t o t he ext ent r ef er enced. The publ i cat i ons ar e r ef er r ed t o wi t hi n t he t ext by t he basi c desi gnat i on onl y.
I NSTI TUTE OF ELECTRI CAL AND ELECTRONI CS ENGI NEERS ( I EEE)
I EEE 242 ( 2001; Er r at a 2003) Recommended Pr act i ce f or Pr ot ect i on and Coor di nat i on of I ndust r i al and Commer ci al Power Syst ems - Buf f Book
I EEE 399 ( 1997) Br own Book I EEE Recommended Pr act i ce f or Power Syst ems Anal ysi s
I EEE C2 ( 2017) Nat i onal El ect r i cal Saf et y Code
NATI ONAL FI RE PROTECTI ON ASSOCI ATI ON ( NFPA)
NFPA 70 ( 2017) Nat i onal El ect r i cal Code
U. S. DEPARTMENT OF DEFENSE ( DOD)
UFC 3- 310- 04 ( 2013) Sei smi c Desi gn f or Bui l di ngs
UNDERWRI TERS LABORATORI ES ( UL)
UL 489 ( 2016) Mol ded- Case Ci r cui t Br eaker s, Mol ded- Case Swi t ches, and Ci r cui t - Br eaker Enclosures
1. 2 SYSTEM DESCRI PTI ON
The power syst em cover ed by t hi s speci f i cat i on consi st s of :
a. New Type I I I Hydr ant Syst em, 12. 47, 480/ 277 vol t , pad- mount ed t r ansf or mer , gener at or , swi t ch boar d, MCC, l ow- vol t age t r ansf or mer , and panelboards.
1. 3 SUBMITTALS
Gover nment appr oval i s r equi r ed f or submi t t al s wi t h a " G" desi gnat i on;
submi t t al s not havi ng a " G" desi gnat i on ar e f or Cont r act or Qual i t y Cont r ol appr oval . Submi t t al s wi t h an " S" ar e f or i ncl usi on i n t he Sust ai nabi l i t y Not ebook, i n conf or mance t o Sect i on 01 33 29 SUSTAI NABI LI TY REPORTI NG.
Submi t t he f ol l owi ng i n accor dance wi t h Sect i on 01 33 00 SUBMI TTAL
PROCEDURES:
SD- 03 Pr oduct Dat a
SECTI ON 26 28 01. 00 10 Page 1
Faul t Cur r ent Anal ysi s
Pr ot ect i ve Devi ce Coor di nat i on St udy
Equipment
Syst em Coor di nat or
Installation
SD- 06 Test Repor t s
Fi el d Test i ng
SD- 07 Cer t i f i cat es
Devi ces and Equi pment
1. 4 QUALI TY ASSURANCE
1. 4. 1 Syst em Coor di nat or
Syst em coor di nat i on, r ecommended r at i ngs and set t i ngs of pr ot ect i ve devi ces, and desi gn anal ysi s shal l be accompl i shed by a Regi st er ed Pr of essi onal El ect r i cal Power Engi neer wi t h a mi ni mum of 3 year s of cur r ent exper i ence i n t he coor di nat i on of el ect r i cal power syst ems. Submi t ver i f i cat i on of exper i ence and l i cense number , of a r egi st er ed Pr of essi onal Engi neer as speci f i ed above. Exper i ence dat a shal l i ncl ude at l east f i ve r ef er ences f or wor k of a magni t ude compar abl e t o t hi s Cont r act , i nc l udi ng poi nt s of cont act , addr esses, and t el ephone number s.
1. 4. 2 Syst em I nst al l er
Cal i br at i on, t est i ng, adj ust ment , and pl aci ng i nt o ser vi ce of t he pr ot ect i ve devi ces shal l be accompl i shed by a manuf act ur er ' s pr oduct f i el d ser vi ce engi neer or i ndependent t est i ng company wi t h a mi ni mum of t wo year s of cur r ent pr oduct exper i ence i n pr ot ect i ve devi ces.
1. 5 DELI VERY, STORAGE, AND HANDLI NG
Devi ces and equi pment shal l be v i sual l y i nspect ed when r ecei ved and pr i or t o accept ance f r om conveyance. Pr ot ect st or ed i t ems f r om t he envi r onment i n accor dance wi t h t he manuf act ur er ' s publ i shed i nst r uct i ons. Damaged i t ems shal l be r epl aced.
1. 6 PROJECT/ SI TE CONDI TI ONS
Submi t cer t i f i cat es at t est i ng t hat al l devi ces or equi pment meet t he r equi r ement s of t he Cont r act Document s. Devi ces and equi pment f ur ni shed under t hi s sect i on shal l be sui t abl e f or t he f ol l owi ng s i t e condi t i ons.
Sei smi c det ai l s shal l conf or m t o UFC 3- 310- 04 and Sect i ons 13 48 00 SEI SMI C
PROTECTI ON FOR MI SCELLANEOUS EQUI PMENT, 13 48 00. 00 10 SEI SMI C PROTECTI ON
FOR MECHANI CAL EQUI PMENT, and 26 05 48. 00 10 SEI SMI C PROTECTI ON FOR
ELECTRI CAL EQUI PMENT.
Altitude 750 f eet
SECTI ON 26 28 01. 00 10 Page 2
Ambi ent Temper at ur e 85 degr ees F
Frequency 60 Hz
Fungus Cont r ol No
Hazar dous Cl assi f i cat i on Wher e i ndi cat ed on dr awi ngs
Humi di t y Cont r ol None
Ventilation I nt er i or : HVAC
Sei smi c Par amet er s Ref er t o Sei smi c Pr ot ect i on speci f i cat i ons l i s t ed above
Other
PART 2 PRODUCTS
2. 1 STANDARD PRODUCT
Pr ovi de pr ot ect i ve devi ces and equi pment whi ch ar e t he st andar d pr oduct of a manuf act ur er r egul ar l y engaged i n t he manuf act ur e of t he pr oduct and t hat essent i al l y dupl i cat e i t ems t hat have been i n sat i sf act or y ut i l i t y t ype use f or at l east 2 year s pr i or t o bi d openi ng. Submi t dat a consi st i ng of manuf act ur er ' s t i me- cur r ent char act er i st i c cur ves f or i ndi v i dual pr ot ect i ve devi ces, r ecommended set t i ngs of adj ust abl e pr ot ect i ve devi ces, and r ecommended r at i ngs of non- adj ust abl e pr ot ect i ve devi ces. Pr ot ect i ve devi ces ar e speci f i ed i n Sect i on 26 20 00 I NTERI OR DI STRI BUTI ON SYSTEM.
2. 2 NAMEPLATES
Pr ovi de namepl at es t o i dent i f y al l pr ot ect i ve devi ces and equi pment .
Namepl at e i nf or mat i on shal l be i n accor dance wi t h UL 489.
2. 3 CORROSI ON PROTECTI ON
Met al l i c mat er i al s shal l be pr ot ect ed agai nst cor r osi on. Fer r ous met al har dwar e shal l be z i nc or chr ome- pl at ed.
2. 4 COORDI NATED POWER SYSTEM PROTECTI ON
Anal yses shal l be pr epar ed t o demonst r at e t hat t he equi pment sel ect ed and syst em const r uct ed meet t he Cont r act Requi r ement s f or r at i ngs, coor di nat i on, and pr ot ect i on. They shal l i ncl ude a l oad f l ow anal ysi s, a f aul t cur r ent anal ysi s, ar c f l ash st udy, and a pr ot ect i ve devi ce coor di nat i on st udy. Submi t t he st udy al ong wi t h pr ot ect i ve devi ce equi pment submi t t al s. No t i me ext ensi ons or s i mi l ar cont act modi f i cat i ons wi l l be gr ant ed f or wor k ar i s i ng out of t he r equi r ement s f or t hi s st udy.
Appr oval of pr ot ect i ve devi ces pr oposed wi l l be based on r ecommendat i ons of t hi s st udy. The Gover nment shal l not be hel d r esponsi bl e f or any changes t o equi pment , devi ce r at i ngs, set t i ngs, or addi t i onal l abor f or i nst al l at i on of equi pment or devi ces or der ed and/ or pr ocur ed pr i or t o appr oval of t he st udy. The st udi es shal l be per f or med by a r egi st er ed Pr of essi onal Engi neer wi t h demonst r at ed exper i ence i n power syst em coor di nat i on i n t he l ast 3 year s. Pr ovi de a l i s t of r ef er ences compl et e wi t h poi nt s of cont act , addr esses, and t el ephone number s. The sel ect i on of t he engi neer i s subj ect t o t he appr oval of t he Cont r act i ng Of f i cer .
SECTI ON 26 28 01. 00 10 Page 3
2. 4. 1 Scope of Anal yses
The f aul t cur r ent anal ysi s, and pr ot ect i ve devi ce coor di nat i on st udy shal l begi n at : The sour ce bus and ext end down t o syst em buses wher e f aul t avai l abi l i t y i s 10, 000 amper es ( symmet r i cal ) f or bui l di ng/ f aci l i t y 600 vol t l evel di st r i but i on buses. The near est upst r eam devi ce i n t he exi st i ng sour ce syst em and ext end t hr ough t he downst r eam devi ces at t he l oad end.
2. 4. 2 Det er mi nat i on of Fact s
The t i me- cur r ent char act er i st i cs, f eat ur es, and namepl at e dat a f or each exi st i ng pr ot ect i ve devi ce shal l be det er mi ned and document ed.
2. 4. 3 Si ngl e Li ne Di agr am
A si ngl e l i ne di agr am shal l be pr epar ed t o show t he el ect r i cal syst em buses, devi ces, t r ansf or mat i on poi nt s, and al l sour ces of f aul t cur r ent ( i ncl udi ng gener at or and mot or cont r i but i ons) . A f aul t - i mpedance di agr am or a comput er anal ysi s di agr am may be pr ovi ded. Each bus, devi ce or t r ansf or mat i on poi nt shal l have a uni que i dent i f i er . I f a f aul t - i mpedance di agr am i s pr ovi ded, i mpedance dat a shal l be shown. Locat i on of swi t ches, br eaker s, and ci r cui t i nt er r upt i ng devi ces shal l be shown on t he di agr am t oget her wi t h avai l abl e f aul t dat a, and t he devi ce i nt er r upt i ng r at i ng.
2. 4. 4 Faul t Cur r ent Anal ysi s
2. 4. 4. 1 Method
The f aul t cur r ent anal ysi s shal l be per f or med i n accor dance wi t h met hods descr i bed i n I EEE 242, I EEE 399, and I EEE 551.
2. 4. 4. 2 Data
Act ual dat a shal l be ut i l i zed i n f aul t cal cul at i ons. Bus char act er i st i cs and t r ansf or mer i mpedance shal l be t hose pr oposed. Dat a shal l be document ed i n t he r epor t .
2. 4. 4. 3 Faul t Cur r ent Avai l abi l i t y
Bal anced t hr ee- phase f aul t , bol t ed l i ne- t o- l i ne f aul t , and l i ne- t o- gr ound f aul t cur r ent val ues shal l be pr ovi ded at each vol t age t r ansf or mat i on poi nt and at each power di st r i but i on bus. The maxi mum and mi ni mum val ues of f aul t avai l abl e at each l ocat i on shal l be shown i n t abul ar f or m on t he di agr am or i n t he r epor t .
2. 4. 5 Coor di nat i on St udy
The st udy shal l demonst r at e t hat t he maxi mum possi bl e degr ee of sel ect i v i t y has been obt ai ned bet ween devi ces speci f i ed, consi st ent wi t h pr ot ect i on of equi pment and conduct or s f r om damage f r om over l oads and f aul t condi t i ons.
The st udy shal l i ncl ude a descr i pt i on of t he coor di nat i on of t he pr ot ect i ve devi ces i n t hi s Pr oj ect . A wr i t t en nar r at i ve shal l be pr ovi ded descr i bi ng: Whi ch devi ces may oper at e i n t he event of a f aul t at each bus;
t he l ogi c used t o ar r i ve at devi ce r at i ngs and set t i ngs; s i t uat i ons wher e syst em coor di nat i on i s not achi evabl e due t o devi ce l i mi t at i ons ( an anal ysi s of any devi ce cur ves whi ch over l ap) ; coor di nat i on bet ween upst r eam and downst r eam devi ces; and r el ay set t i ngs. Recommendat i ons t o i mpr ove or enhance syst em r el i abi l i t y , and det ai l wher e such changes woul d i nvol ve
SECTI ON 26 28 01. 00 10 Page 4 addi t i ons or modi f i cat i ons t o t he Cont r act and cost damages ( addi t i on or r educt i on) shal l be pr ovi ded. Composi t e coor di nat i on pl ot s shal l be pr ovi ded on l og- l og gr aph paper .
2. 4. 6 Ar c Fl ash St udy
Per f or m st udy i n accor dance wi t h I EEE 1584.
2. 4. 7 St udy Repor t
a. The r epor t shal l i ncl ude a nar r at i ve descr i bi ng: The anal yses per f or med; t he bases and met hods used; and t he desi r ed met hod of coor di nat ed pr ot ect i on of t he power syst em.
b. The st udy shal l i ncl ude descr i pt i ve and t echni cal dat a f or exi st i ng devi ces and new pr ot ect i ve devi ces pr oposed. The dat a shal l i ncl ude manuf act ur er ' s publ i shed dat a, namepl at e dat a, and def i ni t i on of t he f i xed or adj ust abl e f eat ur es of t he exi st i ng or new pr ot ect i ve devi ces.
c. The r epor t shal l document ut i l i t y company dat a i ncl udi ng syst em vol t ages, f aul t MVA, syst em X/ R r at i o, t i me- cur r ent char act er i st i c cur ves, cur r ent t r ansf or mer r at i os, and r el ay devi ce number s and set t i ngs; and exi st i ng power syst em dat a i ncl udi ng t i me- cur r ent char act er i st i c cur ves and pr ot ect i ve devi ce r at i ngs and set t i ngs.
d. The r epor t shal l cont ai n f ul l y coor di nat ed composi t e t i me- cur r ent char act er i st i cs cur ves f or each bus i n t he syst em, as r equi r ed t o ensur e coor di nat ed power syst em pr ot ect i on bet ween pr ot ect i ve devi ces or equi pment . The r epor t shal l i ncl ude r ecommended r at i ngs and set t i ngs of al l pr ot ect i ve devi ces i n t abul at ed f or m.
e. The r epor t shal l pr ovi de cal cul at ed ar c f l ash boundar i es, i nci dent ener gy l evel s, mi ni mum cl ot hi ng r at i ngs, l i mi t ed and r est r i c t ed appr oach boundar y di st ances.
e. The r epor t shal l pr ovi de t he cal cul at i on per f or med f or t he anal yses, i ncl udi ng comput er anal ysi s pr ogr ams ut i l i zed. The name of t he sof t war e package, devel oper , and ver si on number shal l be pr ovi ded.
PART 3 EXECUTI ON
3. 1 EXAMINATION
Af t er becomi ng f ami l i ar wi t h det ai l s of t he wor k, ver i f y di mensi ons i n t he f i el d, and advi se t he Cont r act i ng Of f i cer of any di scr epancy bef or e per f or mi ng any wor k.
3. 2 INSTALLATION
Submi t pr ocedur es i ncl udi ng di agr ams, i nst r uct i ons, and pr ecaut i ons r equi r ed t o pr oper l y i nst al l , adj ust , cal i br at e, and t est t he devi ces and equi pment . I nst al l pr ot ect i ve devi ces i n accor dance wi t h t he manuf act ur er ' s publ i shed i nst r uct i ons and i n accor dance wi t h t he r equi r ement s of NFPA 70 and I EEE C2.
3. 3 FI ELD TESTI NG
Pr i or t o f i el d t est s, submi t t he pr oposed t est pl an consi st i ng of compl et e f i el d t est pr ocedur e, t est s t o be per f or med, t est equi pment r equi r ed, and
SECTI ON 26 28 01. 00 10 Page 5 t ol er ance l i mi t s, and compl et e t est i ng and ver i f i cat i on of t he gr ound f aul t pr ot ect i on equi pment , wher e used. Submi t per f or mance t est r epor t s i n bookl et f or m showi ng al l f i el d t est s per f or med t o adj ust each component and al l f i el d t est s per f or med t o pr ove compl i ance wi t h t he speci f i ed per f or mance cr i t er i a, upon compl et i on and t est i ng of t he i nst al l ed syst em.
Each t est r epor t shal l i ndi cat e t he f i nal posi t i on of cont r ol s.
3. 3. 1 General
Per f or m f i el d t est i ng i n t he pr esence of t he Cont r act i ng Of f i cer . Not i f y t he Cont r act i ng Of f i cer 30 days pr i or t o conduct i ng t est s. Fur ni sh al l mat er i al s, l abor , and equi pment necessar y t o conduct f i el d t est s.