STRUCTURAL GENERAL NOTES:
1. GENERAL:
A. THESE NOTES, AND OTHER DRAWING NOTES CONTAINED WITHIN, ARE PROVIDED
TO MEET SPECIFIC REQUIREMENTS AND TO SUPPLEMENT THE CONTRACT
SPECIFICATIONS. THESE NOTES NEITHER REPLACE NOR OVERRIDE THE
PROVISIONS AND REQUIREMENTS OF THE CONTRACT SPECIFICATIONS.
B. CONTRACTOR SHALL COORDINATE ALL STRUCTURAL WORK WITH WORK SHOWN
ON ALL OTHER DRAWINGS. COORDINATE FOR EMBEDDED ITEMS AND OTHER
MISCELLANEOUS CONCRETE AND STEEL REQUIRED BUT NOT INDICATED ON
STRUCTURAL DRAWINGS.
C. CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND CONDITIONS OF EXISTING
CONSTRUCTION PRIOR TO COMMENCING WITH WORK/FABRICATION.
REPORT ANY DISCREPANCIES FROM THE CONTRACT DRAWINGS TO THE CONTRACTING
OFFICER.
D. SCALING OF WORKING DIMENSIONS FROM THE STRUCTURAL DRAWINGS IS PROHIBITED.
E. CONTRACT DRAWINGS AND SPECIFICATIONS REPRESENT THE FINISHED
STRUCTURE. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL MEANS AND METHODS
OF CONSTRUCTION INCLUDING, BUT NOT LIMITED TO, SHORING AND TEMPORARY
BRACING. CONTRACTOR SHALL UNDERTAKE ALL NECESSARY MEASURES TO ENSURE
SAFETY OF ALL PERSONS AND STRUCTURES AT THE SITE AND ADJACENT TO THE SITE.
VISITS TO THE SITE BY THE GOVERNMENT OR THE ENGINEER SHALL NOT RELIEVE THE
CONTRACTOR OF SUCH RESPONSIBILITY.
F. IF CERTAIN FEATURES ARE NOT FULLY SHOWN OR CALLED FOR ON THE CONTRACT
DRAWINGS OR SPECIFICATIONS, THEIR CONSTRUCTION SHALL BE OF THE SAME
CHARACTER AS FOR SIMILAR CONDITIONS THAT ARE SHOWN OR CALLED FOR, WITH
THE APPROVAL OF THE ENGINEER. WHERE SECTIONS VARY, CONTRACTOR SHALL
PROVIDE FOR SMOOTH TRANSITIONS BETWEEN THEM, UNLESS NOTED OTHERWISE.
G. ALL PRODUCTS SHALL BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURERS'
WRITTEN INSTRUCTIONS AND RECOMMENDATIONS, UNLESS NOTED OTHERWISE.
H. UNLESS INDICATED AS A BID OPTION OR NOT IN CONTRACT, ALL ITEMS SHOWN SHALL
BE INCLUDED UNDER THE BASE BID CONTRACT.
2. DESIGN CODES AND STANDARDS
A. UFC 1-200-01 GENERAL BUILDING REQUIREMENTS
B. UFC 3-301-01 STRUCTURAL ENGINEERING
C. UFC 3-310-04 SEISMIC DESIGN FOR BUILDINGS
D. UFC 3-460-01 DESIGN: PETROLEUM FUEL FACILITIES
E. IBC 2015 INTERNATIONAL BUILDING CODE
F. ASCE 7-10 MINIMUM DESIGN LOADS FOR BUILDINGS AND OTHER STRUCTURES
G. ACI 318-14 BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE
H. ACI 350-06 ENVIRONMENTAL ENGINEERING CONCRETE STRUCTURES
I. ACI 530-13 BUILDING CODE REQUIREMENTS AND SPECIFICATION FOR MASONRY STRUCTURES J. AISC 325 STEEL CONSTRUCTION MANUAL, 14th EDITION
3. DESIGN LOADS
A. DEAD LOAD:
1. NEW ROOFING SYSTEM: 4 PSF
2. CONCRETE STRUCTURES: 150 PCF
3. EQUIPMENT LOADS: ACTUAL WEIGHT
B. LIVE LOAD:
1. MIN ROOF LIVE LOAD: 20 PSF
2. MECHANICAL/ELECTRICAL COLLATERAL SUPPORTED FROM ROOF: 5 PSF
3. PLATFORM, ACCESS STAIRS: 60 PSF
4. SLABS ON GRADE: 250 PSF
5. HYDRANT PITS AND ISOLATION VALVE PIT:
- AASHTO HS20-44 TRUCK WHEELS (32 KIPS PER AXLE)
- AIRCRAFT LOADING
C. SNOW LOAD: (ASCE 7-10)
1. GROUND SNOW LOAD: 10 PSF
2. FLAT-ROOF SNOW LOAD: 10.1 PSF
3. EXPOSURE FACTOR: 1.0
4. RISK CATEGORY: IV - ESSENTIAL
5. THERMAL FACTOR: 1.2
D. WIND LOAD: (ASCE 7-10)
1. BASIC WIND SPEED: 120 MPH (STRENGTH DESIGN)
2. EXPOSURE: C
3. RISK CATEGORY: IV - ESSENTIAL
4. TOPOGRAPHIC FACTOR: 1.00
E. SEISMIC LOAD: (ASCE 7-10)
1. MAXIMUM CONSIDERED EARTHQUAKE SPECTRAL RESPONSE ACCELERATIONS:
Ss =0.241, S1 = 0.103
2. RISK CATEGORY: IV - ESSENTIAL
3. USE GROUP III FOR FUEL STARAGE TANKS (API 650)
4. IMPORTANCE FACTOR: 1.50
5. SITE CLASSIFICATION: C
6. SEISMIC DESIGN CATEGORY: C
7. DESIGN EARTHQUAKE SPECTRAL RESPONSE ACCELERATIONS:
SDS = 0.193, SD1 = 0.117
8. FOR OTHER SEISMIC DESIGN PARAMETERS, SEE STRUCTURE SPECIFIC PLANS.
5. MATERIALS: SEE THE CONTRACT SPECIFICATIONS FOR COMPLETE REQUIREMENTS
A. REINFORCED CONCRETE: SPECIFICATION SECTION 03 30 00
1. REINFORCED CONCRETE SHALL BE PREPARED AND PLACED IN ACCORDANCE WITH
ACI MANUAL OF CONCRETE PRACTICE.
a. NORMAL WEIGHT CONCRETE USING TYPE I/II OR II (MODERATE SULFATE RESISTANT)
PORTLAND CEMENT WITH MINIMUM 28-DAY COMPRESSIVE STRENGTH OF:
i. ALL REINFORCED CONCRETE: 5000 PSI
ii. UNREINFORCED CONCRETE: 2500 PSI
b. W/C RATIO = 0.40 MAX FOR ALL REINFORCED CONCRETE.
2. FORMWORK
a. CONTRACTOR SHALL BE RESPONSIBLE FOR DESIGN, ENGINEERING, STRUCTURAL
ADEQUACY, AND CONSTRUCTION OF ALL CONCRETE FORMWORK IN ACCORDANCE
WITH THE CONTRACT SPECIFICATIONS.
b. COORDINATE ALL CONCRETE WORK WITH THE PLACEMENT OF PIPING, INSERTS, FLOOR DRAINS, AND OTHER EMBEDDED ITEMS INDICATED ON THE CONTRACT
DRAWINGS OR IN THE CONTRACT SPECIFICATIONS.
c. WITH THE EXPLICIT PRIOR APPROVAL IN WRITING FROM THE CONTRACTING OFFICER, COLUMN
AND WALL FOOTINGS MAY BE EARTH-FORMED USING UNDISTURBED NATIVE SOIL.
PROVIDE A MINIMUM EXCAVATION WIDTH OF 4", AND A DEPTH OF 2" GREATER THAN
THE STRUCTURE DIMENSIONS INDICATED.
d. UNLESS INDICATED OTHERWISE, ALL EXPOSED EDGES SHALL BE CHAMFERED 3/4".
3. REINFORCING STEEL
a. STEEL REINFORCING BARS SHALL BE DEFORMED AND CONFORM TO THE REQUIREMENTS OF
ASTM A615 GRADE 60 UNO. NO. 3 BARS MAY CONFORM TO GRADE 40.
b. WELDED WIRE FABRIC SHALL CONFORM TO THE REQUIREMENTS OF ASTM A1064.
ONLY FLAT MAT GALVANIZED WELDED WIRE FABRIC SHALL BE USED.
c. ROUND DOWELS FOR USE AT SLAB JOINTS SHALL BE ASTM A615 GRADE 60 SMOOTH
ROUND BARS WITH ASTM A1078 TYPE 1 FACTORY APPLIED EPOXY COATING.
d. CONTRACTOR SHALL DETAIL AND PLACE ALL REINFORCEMENT IN ACCORDANCE WITH
ACI SP-66, ACI 301, ACI 318, AND CRSI MANUAL OF STANDARD PRACTICE.
e. UNLESS NOTED OTHERWISE, CONCRETE CLEAR COVER OVER REINFORCEMENT
SHALL CONFORM TO THE MINIMUMS REQUIRED BY ACI 318.
f. ALL CONCRETE STRUCTURES SHALL BE REINFORCED, UNLESS SPECIFICALLY
INDICATED TO BE UNREINFORCED.
g. PROVIDE ADDITIONAL REINFORCEMENT AT ALL OPENINGS AS SHOWN ON DRAWING
S-501, AND CORNER BARS AT ALL CORNERS AND INTERSECTING GRADE BEAMS,
WALLS, AND CURBS AS SHOWN ON DRAWING S-502, UNLESS NOTED OTHERWISE.
h. UNLESS NOTED OTHERWISE, REINFORCEMENT LAP SPLICES AND EMBEDMENT
LENGTHS SHALL CONFORM TO THE LENGTHS SHOWN IN THE SPLICE TABLE SHOWN
ON DRAWING S-501. FOR CONDITIONS NOT COVERED BY THE SPLICE TABLE, PROVIDE
LENGTHS CONFORMING TO ACI 318.
4. JOINTS
a. LOCATE ALL CONSTRUCTION, CONTRACTION, ISOLATION, EXPANSION, AND OTHER
JOINTS AS INDICATED OR SPECIFIED. JOINTS NOT SHOWN SHALL BE APPROVED BY
THE CONTRACTING OFFICER.
b. WHERE ROUGHENED JOINT IS INDICATED, PROVIDE A MECHANICALLY ROUGHENED
CONCRETE SURFACE WITH A MINIMUM OF 1/4" AMPLITUDE.
c. SURFACES OF ALL HORIZONTAL AND VERTICAL CONSTRUCTION JOINTS SHALL BE
CLEANED OF LAITANCE AND SHALL EXPOSE CLEAN COARSE AGGREGATE SOLIDLY
EMBEDDED IN MORTAR MIX. JUST PRIOR TO DEPOSITING CONCRETE, SURFACE OF
CONSTRUCTION JOINT SHALL BE THOROUGHLY CLEANED AND WETTED.
d. THESE PROVISIONS SHALL ALSO APPLY WHEN NEW CONCRETE IS PLACED AGAINST
EXISTING CONCRETE. IN ADDITION, EXISTING CONCRETE SURFACE SHALL BE
ADEQUATELY PREPARED BY APPLICATION OF A BONDING AGENT.
e. ROUND DOWELS FOR USE AT JOINTS SHALL BE ASTM A615 GRADE 40 SMOOTH
ROUND BARS WITH ASTM A1078 TYPE 1 FACTORY APPLIED EPOXY COATING.
f. PROVIDE WATERSTOPS AT JOINTS AS INDICATED. UNLESS INDICATED OTHERWISE, PROVIDE JET FUEL (F-24) RESISTANT TYPE WATERSTOPS.
5. WHERE NECESSARY OR INDICATED ON THE DRAWINGS, PROVIDE CONCRETE EQUIPMENT/
HOUSEKEEPING PADS FOR MECHANICAL/ELECTRICAL EQUIPMENT PER DETAIL ON S-501.
6. CONCRETE SLABS AND WALLS IN SECONDARY CONTAINMENT AREAS SHALL BE
CONSTRUCTED TO BE FREE OF CRACKS. CONTRACTOR SHALL TAKE REASONABLE
MEASURES (BY USE OF APPROPRIATE MATERIALS, PLACEMENT TECHNIQUES AND
CURING METHODS ABOVE AND BEYOND THOSE SHOWN/SPECIFIED IN CONTRACT
DOCUMENTS) TO PREVENT CRACK FORMATIONS IN THESE STRUCTURES. UNLESS
ACCEPTED AS-IS BY THE CONTRACTING OFFICER, ALL VISIBLE CRACKS SHALL BE
REPAIRED BY THE CONTRACTOR USING METHODS APPROVED BY THE CONTRACTING OFFICER.
7. ALL PENETRATIONS (CONDUIT, CABLE, PIPES) THROUGH CONTAINMENT SLABS AND
WALLS SHALL BE LOCATED A MINIMUM OF 8" AWAY FROM ALL JOINTS.
B. STRUCTURAL AND MISCELLANEOUS STEEL: SPECIFICATION SECTION 05 12 00 AND 05 50 13
1. MATERIAL:
a. WIDE FLANGE AND WT SECTIONS: ASTM A992
b. PLATES AND OTHER SHAPES: ASTM A36
c. STRUCTURAL TUBES/HSS: ASTM A500 GRADE B
d. ROUND PIPES: ASTM A53 TYPE E OR S, GRADE B
e. STAINLESS STEEL BARS/SHAPES: ASTM A240 OR 276 TYPE 304
f. STRUCTURAL BOLTS: ASTM A325
g. NON-STRUCTURAL BOLTS: ASTM A307 OR A325
h. ANCHOR BOLTS: ASTM F1554 GRADE 36 (UNLESS INDICATED AS GRADE 55)
i. WELD ELECTRODES: 70 KSI MIN TENSILE STRENGTH
2. STRUCTURAL AND MISCELLANEOUS STEEL SHALL BE FABRICATED AND ERECTED IN
ACCORDANCE WITH AISC STEEL CONSTRUCTION MANUAL, 14th EDITION.
3. TEMPORARY ERECTION BRACING SHALL BE DESIGNED AND PROVIDED BY THE
CONTRACTOR AS REQUIRED AND SHALL NOT BE REMOVED UNTIL ALL PERMANENT
LATERAL-LOAD-RESISTING ELEMENTS AND CONNECTIONS ARE COMPLETELY
INSTALLED.
4. STRUCTURAL BOLTS:
a. 3/4" DIAMETER, UNLESS NOTED OTHERWISE.
b. STRUCTURAL FRAMING CONNECTIONS: A325-N BOLTS IN SNUG-TIGHTENED JOINTS
IN STANDARD HOLES, UNLESS INDICATED OTHERWISE.
c. BRACING CONNECTIONS: SNUG-TIGHTENED JOINTS IN STANDARD HOLES, UNLESS
NOTED OTHERWISE.
d. ON ONE SIDE OF EACH DOUBLE CONNECTION OF BEAMS TO A COLUMN WEB OR A
GIRDER WEB DIRECTLY OVER A COLUMN, PROVIDE A TEMPORARY SEAT ANGLE
ATTACHED TO COLUMN OR GIRDER WEB AND TO BOTTOM FLANGE OF BEAM.
MINIMUM SEAT CONNECTION SHALL BE L4x3x3/8" LLH WITH TWO 3/4" DIAMETER
A307 OR A325-ST BOLTS EACH LEG. SINGLE AND DOUBLE STAGGERED
CONNECTIONS ARE PROHIBITED WITHOUT THE EXPLICIT PRIOR APPROVAL IN
WRITING FROM THE STRUCTURAL ENGINEER OF RECORD.
5. WELDING SHALL BE PERFORMED IN ACCORDANCE WITH AWS D1.1 USING E70
ELECTRODES. PROVIDE SEAL WELDS ALONG PERIMETER OF COMPONENTS WELDED TO
MEMBERS TO BE INSTALLED OUTDOORS TO PREVENT CORROSION IN JOINT CREVICES.
6. ALL DOUBLE ANGLE MEMBERS SHALL HAVE SPACER PLATES TO COMPLY WITH AISC
PARAGRAPH E6.
a. THICKNESS: TO MATCH END GUSSET PLATES.
b. MINIMUM ATTACHMENT: CONNECT TO HEEL AND TOE OF EACH ANGLE USING
3/16" x 1" LONG FILLET WELDS, OR ONE 3/4" DIAMETER BOLT.
7. ANCHOR BOLTS
a. LOCATE ANCHOR BOLTS ACCURATELY, SET WITH TEMPLATES, AND SECURELY HOLD
IN POSITION WHILE PLACING CONCRETE. PROTECT IN-PLACE ANCHOR BOLTS FROM
CONSTRUCTION ACTIVITY.
b. THE FOLLOWING ARE PROHIBITED WITHOUT THE EXPLICIT PRIOR APPROVAL IN
WRITING FROM THE STRUCTURAL ENGINEER OF RECORD:
i. INSERTING ANCHOR BOLTS INTO FRESH OR PARTIALLY HARDENED CONCRETE.
ii. SUBSTITUTING POST-INSTALLED ANCHORS WHERE EMBEDDED ANCHOR BOLTS
ARE INDICATED.
iii. REPAIRING, REPLACING, OR MODIFYING INSTALLED ANCHOR BOLTS.
iv. UNLESS NOTED TO BE MORE STRINGENT ELSEWHERE, EMBEDDED ANCHOR
BOLTS SHALL BE INSTALLED WITHIN THE FOLLOWING MAXIMUM TOLERANCES:
(1) 1/8" BETWEEN ANY ANCHOR BOLT CENTERLINES WITHIN A GROUP.
(2) 1/4" BETWEEN THE CENTERS OF ADJACENT ANCHOR BOLT GROUPS.
(3) 1/2" VARIATION IN THE TOP OF ANCHOR BOLTS.
(4) 1/4" PER 100'-0", BUT NOT TO EXCEED 1" TOTAL IN ACCUMULATED
VARIATION IN DIMENSION BETWEEN CENTERS OF ANCHOR BOLT
GROUPS ALONG A COLUMN LINE.
(5) 1/4" VARIATION IN THE CENTER OF ANY ANCHOR BOLT GROUP TO THE
COLUMN CENTERLINE FOR THAT GROUP.
8. POST-INSTALLED ANCHORS
a. CONCRETE ANCHORS: STAINLESS STEEL MANUALLY EXPANDED WEDGE TYPE, UNLESS NOTED OTHERWISE.
b. ADHESIVE ANCHORS: ASTM A36 CARBON STEEL THREADED ROD WITH
HYBRID ADHESIVE ANCHORING COMPOUND, UNLESS NOTED OTHERWISE.
c. MASONRY ANCHORS: ASTM A36 CARBON STEEL THREADED ROD WITH
CYLINDRICAL WIRE MESH SCREEN TUBE AND INJECTABLE HYBRID ADHESIVE
ANCHORING COMPOUND, UNLESS NOTED OTHERWISE.
d. ANCHORS SHALL ONLY BE INSTALLED BY PERSONNEL TRAINED BY THE ANCHOR
MANUFACTURER.
9. GROUT: CEMENTITIOUS NON-SHRINK, NON-METALIC.
10.UNLESS NOTED OTHERWISE, ALL EXTERIOR STEEL SHALL BE HOT-DIPPED GALVANIZED IN
ACCORDANCE WITHT THE FOLLOWING:
a. STRUCTURAL STEEL: ASTM A123
b. STEEL HARDWARE: ASTM A153
c. THREADED PARTS: ASTM F2329
C. MASONRY: SPECIFICATION SECTION 04 20 00.
1. SEE S-531 FOR NOTES.
4. GEOTECHNICAL INFORMATION
A. SOURCE: BASED ON DRAFT GEOTECHNICAL REPORT PROVIDED BY SUMMIT ENGINEERING,
LABORATORY & TESTING, INC. (JULY 2017)
B. SITE PREPARATION
1. EXCAVATION, FILL, AND BACKFILL SHALL BE IN ACCORDANCE WITH THE CONTRACT
DRAWINGS AND SPECIFICATIONS, DIVISION 31.
2. CONTRACTOR SHALL NOTIFY THE CONTRACTING OFFICER WHEN LOOSE OR SOFT
SOILS ARE EXPOSED WHERE SLABS, MATS, OR FOOTINGS ARE TO BE PLACED SO
THAT A DETERMINATION MAY BE MADE REGARDING IMPROVEMENT OF THIS
POTENTIALLY UNDESIRABLE CONDITION.
C. SOIL CHARACTERISTICS
1. UNIT WEIGHT: 120 PCF (MOIST)
2. WATER TABLE DEPTH: 18.5' BELOW EXISTING GRADE.
D. SLAB, MAT, AND FOOTING DESIGN PARAMETERS
1. MODULUS OF SUBGRADE REACTION: 150 PCI
2. ALLOWABLE BEARING CAPACITIES
a. GRAVITY LOADS: 3000 PSF
b. WIND OR SEISMIC LOADS: 4000 PSF
3. FROST DEPTH: 12"
4. MIN DEPTH TO BOTTOM OF FOOTINGS: 12"
5. CONCRETE-SOIL STATIC COEFFICIENT OF FRICTION: 0.4
6. MINIMUM STABILITY FACTORS OF SAFETY
a. OVERTURNING: 1.5.
b. UPLIFT: 1.5.
c. SLIDING: 1.5.
E. STATIC LATERAL EARTH PRESSURE COEFFICIENTS (ON-SITE SOILS)
1. AT-REST CONDITION, Ko: 0.59
2. ACTIVE CONDITION, Ka: 0.42
3. PASSIVE CONDITION, Kp: 2.37
F. SOIL BACKFILL AGAINST STRUCTURES AND WALLS SHALL NOT BE PLACED UNTIL THE WALLS
HAVE BEEN CURED FOR A MINIMUM OF 7 DAYS AND HAS REACHED 75% OF THE DESIGN
STRENGTH. LIMIT THE DIFFERENTIAL HEIGHT OF THE SOIL BACKFILL ON EACH SIDE OF THE
WALLS TO 18" MAXIMUM. SOIL BACKFILL WITHIN 5'-0" OF THE WALLS SHALL ONLY BE
COMPACTED USING LIGHT MANUALLY-OPERATED/WALK-BEHIND COMPACTORS.
date detailed checkeddesigned ofsheet sheets project contract rev.drawing file
DESCRIPTION
1 5432
A
B
C
D
C O
PY
R
IG
H
T
BU
R
N S
M
C D
O N
N
EL
L
EN
G
IN
EE
R
IN
G
C O
M
PA
N Y, IN
C
C-17 TYPE III HYDRANT
REFUELING SYSTEM/
RAMP EXPANSION
KANSAS CITY, MISSOURI
INITDATEREV.
REVISIONS
ENGINEERS ARCHITECTS & CONSULTANTS
NORTH CAROLINA AIR NATIONAL GUARD
DOUGLAS INTERNATIONAL AIRPORT
CHARLOTTE, NORTH CAROLINA
Project No. - FJRP159073
/5
/2
3:
:0
PM
FJRP159073-S-001.dwg
S-001 94893
STRUCTURAL GENERAL NOTES
11/16/2016
H. SAHUDIN J. HEIM
M. PATEL
0 10/13/17 B-3 FINAL SUBMITTAL HS
AB - ANCHOR BOLT
APPROX - APPROXIMATE
ARCH - ARCHITECT
BM - BEAM
B OR BOT - BOTTOM
B/P - BASE OF PIER
BRG - BEARING
BRKT - BRACKET
CFS - COLD-FORMED STEEL
CJ - CONSTRUCTION JOINT
CL - CENTER LINE
CLR - CLEAR
CLJ - CONTROL JOINT
CMU - CONCRETE MASONRY UNIT
COL - COLUMN
COMP - COMPRESSION
CONC - CONCRETE
CONT - CONTINUOUS
CP - CATHODIC PROTECTION
CTRD - CENTERED
DIA - DIAMETER
DBL - DOUBLE
DL - DEAD LOAD
DWL - DOWEL
DET - DETAIL
EF - EACH FACE
EL - ELEVATION
EA - EACH
EJ - EXPANSION JOINT
EW - EACH WAY
EXP - EXPANSION
EXT - EXTERIOR
EQ - EQUAL
FS - FAR SIDE
FDN - FOUNDATION
FML - FLEXIBLE MEMBRANE LINER
FT - FEET
FTG - FOOTING
FD - FLOOR DRAIN
GA - GAGE
GALV - GALVANIZED
GB - GRADE BEAM
GRTG - GRATING
HORIZ - HORIZONTAL
HEF - HORIZONTAL EACH FACE
HSS - HOLLOW STRUCTURAL SECTIONS
ID - INSIDE DIAMETER
IF - INSIDE FACE
IJ - ISOLATION JOINT
IN - INCHES
INTR - INTERIOR
IR - INSIDE RADIUS
KSI - KIPS PER SQUARE INCH
L - ANGLE
LLO - LONG LEG OUTSTANDING
LLV - LONG LEG VERTICAL
LONG - LONGITUDINAL
LT - LEFT
MAX - MAXIMUM
MECH - MECHANICAL
MFR - MANUFACTURER
MIN - MINIMUM
NDT - NONDESTRUCTIVE TESTING
NIC - NOT IN CONTRACT
NTS - NOT TO SCALE
NO - NUMBER
NS - NEAR SIDE
OC - ON CENTER
OF - OUTSIDE FACE
OPNG - OPENING
% - PERCENT
PCF - POUNDS PER CUBIC FOOT
PL - PLATE
PSF - POUNDS PER SQUARE FOOT
PSI - POUNDS PER SQUARE INCH
RAD - RADIUS
RST - REINFORCEMENT STEEL
REQD - REQUIRED
SLO - SHORT LEG OUTSTANDING
SLV - SLEEVE
SIM - SIMILAR
SHT - DRAWING
SPA - SPACE OR SPACING
SS - STAINLESS STEEL
STD - STANDARD
STR - STIRRUP
T - TOP OR TON
T/C - TOP OF CONCRETE
T/S - TOP OF STEEL
TRANS - TRANSVERSE
TYP - TYPICAL
UNO - UNLESS NOTED OTHERWISE
VERT - VERTICAL
VEF - VERTICAL EACH FACE
WP - WORK POINT
WWF - WELDED WIRE FABRIC
WS - WATERSTOP
@ - AT
& - AND
# - POUNDS OR NUMBER
UNDISTURBED EARTH/
COMPACTED BACKFILL
CAST CONCRETE
STEEL
CAPILLARY WATER BARRIER OR
AGGREGATE BASE COURSE
GROUT OR PRECAST CONCRETE
CONCRETE MASONRY UNIT
ROCK OR COMPACTED FILL
FOR STRUCTURAL USE
NOTE:
FOR DRAWING CLARITY, SYMBOLS MAY BE
OMITTED.
SECTION, DETAIL, AND ELEVATION SYMBOL IDENTIFIERS:
LETTER OR NUMBER
DESIGNATOR
WALL SECTION CALLOUT EXAMPLE:
DETAIL CALLOUT EXAMPLE:
SECTION, DETAIL, AND ELEVATION TITLE EXAMPLE:
N
NORTH ARROW EXAMPLE:
LETTER OR NUMBER
INDICATES DETAIL
DRAWING NUMBER WHERE
SECTION IS DRAWN
LETTER OR NUMBER
INDICATES DETAIL
DRAWING NUMBER WHERE
SECTION IS DRAWN
BUILDING SECTION CALLOUT EXAMPLE:
SIM
DRAWING SEQUENCE NUMBER INDICATES
WHERE TITLE IS LOCATED (MAY NOT BE
PRESENT IF CALLOUT AND TITLE ARE ON
THE SAME DRAWING)
ONE OR TWO CHARACTER DISCIPLINE
DESIGNATOR (MAY NOT BE PRESENT IF
CALLOUT AND TITLE ARE ON DRAWINGS
WITHIN THE SAME DISCIPLINE)
S1 S001
S1 S-002
S1 S-002
S1 S-002
LETTER OR NUMBER
INDICATES DETAIL
DRAWING NUMBER
WHERE DETAIL IS DRAWN
S1 S-002
S1 S-002 date detailed checkeddesigned ofsheet sheets project contract rev.drawing file
DESCRIPTION
1 5432
A
B
C
D
C O
PY
R
IG
H
T
N S
M
C D
O N
N
EL
L
EN
G
IN
EE
R
IN
G
C O
M
PA
N Y, IN
C
C-17 TYPE III HYDRANT
REFUELING SYSTEM/
RAMP EXPANSION
KANSAS CITY, MISSOURI
INITDATEREV.
REVISIONS
ENGINEERS ARCHITECTS & CONSULTANTS
NORTH CAROLINA AIR NATIONAL GUARD
DOUGLAS INTERNATIONAL AIRPORT
CHARLOTTE, NORTH CAROLINA
Project No. - FJRP159073
/5
/2
3:
:1
PM
FJRP159073-S-002.dwg
S-002 94893
LEGENDS AND ABBREVIATIONS
11/16/2016
H. SAHUDIN J. HEIM
M. PATEL
ABBREVIATIONSCALL OUT IDENTIFICATION MATERIAL SYMBOLS
SCALE: 1 1/2" = 1'-0"S1 PLAN
FOR SI: 1 INCH = 25.4 mm
a. WHERE APPLICABLE, SEE ALSO SECTION 1705.12, SPECIAL INSPECTIONS FOR SEISMIC RESISTANCE.
b. SPECIFIC REQUIREMENTS FOR SPECIAL INSPECTION SHALL BE INCLUDED IN THE RESEARCH REPORT FOR THE ANCHOR ISSUED BY AN
APPROVED SOURCE IN ACCORDANCE WITH 17.8.2 IN ACI 318, OR OTHER QUALIFICATION PROCEDURES. WHERE SPECIFIC REQUIREMENTS ARE NOT PROVIDED, SPECIAL INSPECTION REQUIREMENTS SHALL BE SPECIFIED BY THE REGISTERED DESIGN PROFESSIONAL AND SHALL BE
APPROVED BY THE BUILDING OFFICIAL PRIOR TO THE COMMENCEMENT OF THE WORK.
c. WHEN DIRECTED BY THE CONTRACT DOCUMENTS TO PROVIDE POST-INSTALLED ANCHORAGES THE FOLLOWING GUIDELINES SHALL BE
FOLLOWED:
1. A REPRESENTATIVE OF THE ANCHOR MANUFACTURER OR PROJECT SPECIAL INSPECTOR SHALL BE ON SITE TO OVERSEE THE
INSTALLATION OF THE FIRST FOUR ANCHORS FOR EACH TYPE OF ANCHOR INSTALLED. THIS MEASURE SHALL BE TAKEN FOR EACH INSTALLER OF THE ANCHORS. THIS SERVICE IS TYPICALLY PROVIDED FREE BY THE LOCAL ANCHOR REPRESENTATIVE.
2. THE FIRST FOUR ANCHORS SHALL BE TENSION TESTED ONCE INSTALLATION IS COMPLETE FOR 200% OF THE SERVICE LEVEL LOAD
CAPACITY AS SPECIFIED BY THE MANUFACTURER.
NOTES:
1. STATEMENT OF SPECIAL INSPECTIONS
A. THIS "STATEMENT OF SPECIAL INSPECTIONS"
HAS BEEN PREPARED IN ACCORDANCE WITH
IBC 2015, SECTION 1704.
B. CONTRACTOR SHALL RETAIN PRE-COORDINATED
AND GOVERNMENT-APPROVED THIRD-PARTY QUALITY
ASSURANCE AGENCIES TO PROVIDE SPECIAL
INSPECTIONS DURING CONSTRUCTION IN
ACCORDANCE WITH IBC 2015, CHAPTER 17.
C. EACH SPECIAL INSPECTOR SHALL BE A QUALIFIED
PERSON WHO SHALL DEMONSTRATE COMPETENCE,
TO THE SATISFACTION OF THE CONTRACTING
OFFICER'S REPRESENTATIVE, FOR INSPECTION OF
THE PARTICULAR TYPE OF CONSTRUCTION OR
OPERATION REQUIRING SPECIAL INSPECTION.
D. SPECIAL INSPECTION AGENCY SHALL SUBMIT
INSPECTION REPORTS DURING CONSTRUCTION FOR
VERIFICATION, INCLUDING FINAL REPORTS IN
ACCORDANCE WITH IBC 2015, SECTION 1704.2.4.
IBC 2015 TABLE 1705.3 REQUIRED VERIFICATION AND INSPECTION OF CONCRETE CONSTRUCTION
VERIFICATION AND INSPECTION CONTINUOUS PERIODIC
REFERENCED
STANDARD
IBC
REFERENCE
1. INSPECT REINFORCEMENT, INCLUDING PRESTRESSING TENDONS, AND
VERIFY PLACEMENT.
- X ACI 318: 20, 25.2,
25.3, 26.5.1-26.5.3 1908.4
2. REINFORCING BAR WELDING. AWS D1.4 ACI 318:
26.5.4
a. VERIFY WELDABILITY OF REINFORCING BARS OTHER THAN ASTM A706. - X
b. INSPECT SINGLE-PASS FILLET WELDS, MAXIMUM 5/16". - X
c. INSPECT ALL OTHER WELDS. X -
3. INSPECTION OF ANCHORS CAST IN CONCRETE. - X ACI 318: 17.8.2
4. INSPECTION OF ANCHORS POST-INSTALLED IN HARDENED CONCRETE
MEMBERS.
a. ADHESIVE ANCHORS INSTALLED IN HORIZONTALLY OR UPWARDLY INCLINED
ORIENTATIONS TO RESIST SUSTAINED TENSION LOADS.
X - ACI 318: 17.8.2.4
b. MECHANICAL ANCHORS AND ADHESIVE ANCHORS NOT DEFINED IN 4.a. X - ACI 318: 17.8.2
5. VERIFYING USE OF REQUIRED DESIGN MIX. - X ACI 318: 19, 26.4.3,
26.4.4 1904.1, 1904.2, 1908.2, 1908.3
6. PRIOR TO CONCRETE PLACEMENT, FABRICATE SPECIMENS FOR STRENGTH
TESTS, PERFORM SLUMP AND AIR CONTENT TESTS, AND DETERMINE THE
TEMPERATURE OF THE CONCRETE.
X - ASTM C 172, ASTM
C 31, ACI 318:
26.4.5, 26.12
1908.10
7. INSPECT CONCRETE PLACEMENT FOR PROPER APPLICATION TECHNIQUES. X - ACI 318: 26.4.5 1908.6, 1908.7, 1908.8
8. VERIFY MAINTENANCE OF SPECIFIED CURING TEMPERATURE AND
TECHNIQUES.
- X ACI 318:
26.4.7-26.4.9
1908.9
9. INSPECT PRESTRESSED CONCRETE. ACI 318: 26.10.1
a. APPLICATION OF PRESTRESSING FORCES. X -
b. GROUTING OF BONDED PRESTRESSING TENDONS. X -
10. INSPECT ERECTION OF PRECAST CONCRETE MEMBERS. - X ACI 318: 26.8
11. VERIFY IN-SITU CONCRETE STRENGTH, PRIOR TO STRESSING OF TENDONS
IN POST-TENSIONED CONCRETE AND PRIOR TO REMOVAL OF SHORES AND
FORMS BEAMS AND STRUCTURAL SLABS.
- X ACI 318: 26.10.2
12. INSPECT FORMWORK FOR SHAPE, LOCATION AND DIMENSIONS OF THE
CONCRETE MEMBER BEING FORMED.
X ACI 318: 26.10.1(b)
E. SPECIAL INSPECTOR SHALL USE THE LATEST ISSUE
OF THE STRUCTURAL DRAWINGS FOR ALL
INSPECTIONS. SHOP FABRICATION DRAWINGS
SHALL NOT BE USED FOR SUCH PURPOSES.
F. THE FOLLOWING TABLES IDENTIFY THE MATERIALS,
SYSTEMS, AND COMPONENTS FOR WHICH SPECIAL
INSPECTION IS REQUIRED.
2. TESTING REQUIREMENTS
A. CONTRACTOR SHALL RETAIN PRE-COORDINATED
AND GOVERNMENT-APPROVED THIRD-PARTY
TESTING AGENCIES TO PROVIDE STRUCTURAL
TESTING DURING CONSTRUCTION IN ACCORDANCE
WITH IBC 2015, CHAPTER 17.
B. TESTING AGENCY SHALL SUBMIT TEST RESULTS
DURING CONSTRUCTION FOR VERIFICATION
INCLUDING A FINAL REPORT IN ACCORDANCE WITH
IBC 2015, 1704.2.4.
C. THE TABLES BELOW IDENTIFY THE STRUCTURAL
TESTS REQUIRED FOR THIS PROJECT.
3. STRUCTURAL OBSERVATIONS
A. CONTRACTOR SHALL RETAIN PRE-COORDINATEDAND
GOVERNMENT-APPROVED THIRD-PARTY REGISTERED DESIGN
PROFESSIONALS TO PROVIDE STRUCTURAL OBSERVATIONS
DURING CONSTRUCTION IN ACCORDANCE WITH IBC 2015,
CHAPTER 17.
B. EACH STRUCTURAL OBSERVER SHALL SUBMIT WRITTEN
STATEMENTS IDENTIFYING FREQUENCY AND EXTENT OF
STRUCTURAL OBSERVATIONS AND ANY REPORTED
DEFICIENCIES WHICH, TO THE BEST OF THE STRUCTURAL
OBSERVER'S KNOWLEDGE, HAVE NOT BEEN RESOLVED.
C. O = OBSERVE THESE ITEMS ON A RANDOM BASIS. OPERATIONS
NEED NOT TO BE DELAYED PENDING THESE INSPECTIONS.
D. P = PERFORM THESE TASKS FOR EACH JOINT OR MEMBER.
E. QA = INSPECTION THAT THE WORK IS IN COMPLIANCE
WITH THE CONSTRUCTION DOCUMENTS
F. QC = INSPECTION THAT THE WORK IS PERFORMED IN
ACCORDANCE WITH THE CONSTRUCTION DOCUMENTS
G. ALL COSTS DUE TO SPECIAL INSPECTIONS IN
ACCORDANCE WITH IBC 2015, TMS 402 AND AISC 360-10
SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR.
THIS INCLUDES ALL QC AND QA REQUIREMENTS
INDICATED ON S-004, S-005, AND S-006.
H. QUALITY CONTROL: CONTROLS AND INSPECTIONS
IMPLEMENTED BY THE FABRICATOR OR ERECTOR, AS
APPLICABLE, TO ENSURE THAT THE MATERIAL PROVIDED
AND WORK PERFORMED MEET THE REQUIREMENTS OF
THE APPROVED CONSTRUCTION DOCUMENTS AND
REFERENCED STANDARDS.
J. QUALITY ASSURANCE: MONITORING AND INSPECTION TASKS
PERFORMED BY AN AGENCY OR FIRM OTHER THAN THE
FABRICATOR OR ERECTOR TO ENSURE THAT THE MATERIAL
PROVIDED AND WORK PERFORMED BY THE FABRICATIOR
AND ERECTOR MEET THE REQUIREMENTS OF THE APPROVED
CONSTRUCTION DOCUMENTS AND REFERENCED STANDARDS.
QUALITY ASSURANCE INCLUDES THOSE TASKS DESIGNATED
"SPECIAL INSPECTION" BY THE APPLICABLE BUILDING CODE.
STEEL DECK INSTITUTE QA/QC 2011
TASK QC QA
A. VERIFY COMPLIANCE OF MATERIALS (DECK AND ALL DECK ACCESSORIES) WITH CONSTRUCTION
DOCUMENTS, INCLUDING PROFILES, MATERIAL PROPERTIES, AND BASE METAL THICKNESS.
P P
B. DOCUMENTS ACCEPTANCE OR REJECTION OF DECK AND DECK ACCESSORIES. P P
A. VERIFY COMPLIANCE OF DECK AND ALL DECK ACCESSORIES INSTALLATION WITH CONSTRUCTION DOCUMENTS. P P B. VERIFY DECK MATERIALS ARE REPRESENTED BY THE MILL CERTIFICATIONS THAT COMPLY WITH THE
CONSTRUCTION DOCUMENTS.
N/A P
C. DOCUMENT ACCEPTANCE OR REJECTION OF INSTALLATION OF DECK AND DECK ACCESSORIES. P P
INSPECTION OR EXECUTION TASKS PRIOR TO DECK PLACEMENT
INSPECTION OR EXECUTION TASKS AFTER DECK PLACEMENT
A. WELDING PROCEDURE SPECIFICATIONS (WPS) AVAILABLE. O O
B. MANUFACTURER CERTIFICATIONS FOR WELDING CONSUMABLES AVAILABLE. O O
C. MATERIAL IDENTIFICATION (TYPE/GRADE). O O
D. CHECK WELDING EQUIPMENT. O O
A. USE OF QUALIFIED WELDERS. O O
B. CONTROL AND HANDLING OF WELDING CONSUMABLES. O O
C. ENVIRONMENTAL CONDITIONS (WIND SPEED, MOISTURE, TEMPERATURE). O O
D. WPS FOLLOWED. O O
A. VERIFY SIZE AND LOCATION OF WELDS, INCLUDING SUPPORT, SIDELAP, AND PERIMETER WELDS. P P
B. WELDS MEET VISUAL ACCEPTANCE CRITERIA. P P
C. VERIFY REPAIR ACTIVITIES. P P
D. DOCUMENT ACCEPTANCE OR REJECTION OF WELDS. P P
INSPECTION OR EXECUTION TASKS PRIOR TO WELDING
INSPECTION OR EXECUTION TASKS DURING WELDING
INSPECTION OR EXECUTION TASKS AFTER WELDING
A. MANUFACTURER INSTALLATION INSTRUCTIONS AVAILABLE FOR MECHANICAL FASTENERS. O O
B. PROPER TOOLS AVAILABLE FOR FASTENER INSTALLATION. O O
C. PROPER STORAGE FOR MECHANICAL FASTENERS. O O
A. FASTENERS ARE POSITIONED AS REQUIRED. O O
B. FASTENERS ARE INSTALLED IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS. O O
A. CHECK SPACING, TYPE, AND INSTALLATION OF SUPPORT FASTENERS. P P
B. CHECK SPACING, TYPE, AND INSTALLATION OF SIDELAP FASTENERS. P P
C. CHECK SPACING, TYPE, AND INSTALLATION OF PERIMETER FASTENER. P P
D. VERIFY REPAIR ACTIVITIES. P P
E. DOCUMENT ACCEPTANCE OR REJECTION OF MECHANICAL FASTENERS. P P
INSPECTION OR EXECUTION TASKS PRIOR TO MECHANICAL FASTENING
INSPECTION OR EXECUTION TASKS DURING MECHANICAL FASTENING
INSPECTION OR EXECUTION TASKS AFTER MECHANICAL FASTENING
date detailed checkeddesigned ofsheet sheets project contract rev.drawing file
DESCRIPTION
1 5432
A
B
C
D
C O
PY
R
IG
H
T
N S
M
C D
O N
N
EL
L
EN
G
IN
EE
R
IN
G
C O
M
PA
N Y, IN
C
C-17 TYPE III HYDRANT
REFUELING SYSTEM/
RAMP EXPANSION
KANSAS CITY, MISSOURI
INITDATEREV.
REVISIONS
ENGINEERS ARCHITECTS & CONSULTANTS
NORTH CAROLINA AIR NATIONAL GUARD
DOUGLAS INTERNATIONAL AIRPORT
CHARLOTTE, NORTH CAROLINA
Project No. - FJRP159073
/5
/2
3:
:1
PM
FJRP159073-S-003.dwg
S-003 94893
STATEMENT OF SPECIAL INSPECTIONS
SHEET 1
09/30/16
H. SAHUDIN J. HEIM
IBC 2015 TABLE 1705.8 REQUIRED SPECIAL INSPECTIONS AND TESTS OF CAST-IN- PLACE
DEEP FOUNDATION ELEMENTS
TYPE CONTINUOUS PERIODIC
1. INSPECT DRILLING OPERATIONS AND MAINTAIN COMPLETE AND ACCURATE RECORDS FOR EACH
ELEMENT
X -
2. VERIFY PLACEMENT LOCATIONS AND PLUMBNESS, CONFIRM ELEMENT DIAMETERS, BELL DIAMETERS (IF APPLICABLE), LENGTHS, EMBEDMENT INTO BEDROCK (IF APPLICABLE) AND ADEQUATE END-BEARING
STRATA CAPACITY. RECORD CONCRETE OR GROUT VOLUMES.
X -
3. FOR CONCRETE ELEMENTS, PERFORM TESTS AND ADDITIONAL SPECIAL INSPECTIONS IN ACCORDANCE
WITH SECTION 1705.3.
IBC 2015 TABLE 1705.6 REQUIRED VERIFICATION AND INSPECTION OF SOILS
TASKS CONTINUOUS PERIODIC
1. VERIFY MATERIALS BELOW SHALLOW FOUNDATIONS ARE ADEQUATE TO ACHIEVE THE DESIGN BEARING
CAPACITY.
- X
2. VERIFY EXCAVATIONS ARE EXTENDED TO PROPER DEPTH AND HAVE REACHED PROPER MATERIAL. - X
3. PERFORM CLASSIFICATION AND TESTING OF COMPACTED FILL MATERIALS. - X
4. VERIFY USE OF PROPER MATERIALS, DENSITIES AND LIFT THICKNESSES DURING PLACEMENT AND
COMPACTION OF COMPACTED FILL.
X -
5. PRIOR TO PLACEMENT OF COMPACTED FILL, INSPECT SUBGRADE AND VERIFY THAT SITE HAS BEEN
PREPARED PROPERLY.
- X date detailed checkeddesigned ofsheet sheets project contract rev.drawing file
DESCRIPTION
1 5432
A
B
C
D
C O
PY
R
IG
H
T
N S
M
C D
O N
N
EL
L
EN
G
IN
EE
R
IN
G
C O
M
PA
N Y, IN
C
C-17 TYPE III HYDRANT
REFUELING SYSTEM/
RAMP EXPANSION
KANSAS CITY, MISSOURI
INITDATEREV.
REVISIONS
ENGINEERS ARCHITECTS & CONSULTANTS
NORTH CAROLINA AIR NATIONAL GUARD
DOUGLAS INTERNATIONAL AIRPORT
CHARLOTTE, NORTH CAROLINA
Project No. - FJRP159073
/5
/2
3:
:1
PM
FJRP159073-S-004.dwg
S-004 94893
STATEMENT OF SPECIAL INSPECTIONS
SHEET 2
09/30/16
H. SAHUDIN J. HEIM
AISC 360-10
FABRICATOR AND ERECTOR QUALITY CONTROL PROGRAM
FABRICATOR INSPECTION TASKS QC QA
DETAILS IN ACCORDANCE WITH SECTION N5
SHOP CUT AND FINISHED SURFACES IN ACCORDANCE WITH SECTION M2
SHOP HEATING FOR STRAIGHTENING, CAMBERING AND CURVING IN ACCORDANCE
WITH SECTION M2.1
TOLERANCES FOR SHOP FABRICATION IN ACCORDANCE WITH SECTION 6 OF THE
CODE OF STANDARD PRACTICE
-P
-P
-P
-P
ERECTOR INSPECTION TASKS
DETAILS IN ACCORDANCE WITH SECTION N5
FIELD CUT SURFACES IN ACCORDANCE WITH SECTION M2.2
STEEL DECK HEADED STEEL STUD ANCHOR PLACEMENT AND ATTACHMENT IN
ACCORDANCE WITH SECTION N6
FIELD HEATING FOR STRAIGHTENING IN ACCORDANCE WITH SECTION M2.1
TOLERANCES FOR FIELD ERECTION IN ACCORDANCE WITH SECTION 7.13 OF THE
CODE OF STANDARD PRACTICE
-P
-P
-P
-P
-P
-P
INSPECT THE ERECTED STEEL FRAME TO VERIFY COMPLIANCE WITH THE DETAILS
SHOWN ON THE ERECTION DRAWINGS, SUCH AS BRACES, STIFFENERS, MEMBER
LOCATIONS AND PROPER APPLICATION OF JOINT DETAILS AT EACH CONNECTION
INSPECT THE FABRICATED STEEL TO VERIFY COMPLIANCE WITH DETAILS SHOWN ON
SHOP DRAWINGS, SUCH AS PROPER APPLICATION OF JOINT DETAILS AT EACH
CONNECTION
-P
INSPECT PLACEMENT OF ANCHOR RODS AND OTHER EMBEDMENTS SUPPORTING
STRUCTURAL STEEL FOR COMPLIANCE WITH CONSTRUCTION DOCUMENTS. AS A
MINIMUM, THE DIAMETER, GRADE, TYPE AND LENGTH OF THE ANCHOR ROD OR
EMBEDDED ITEM, AND THE EXTENT OR DEPTH OF EMBEDMENT INTO CONCRETE,
SHALL BE VERIFIED PRIOR TO PLACEMENT OF CONCRETE
P-
O-
INSPECT THE FABRICATED STEEL OR ERECTED STEEL FRAME, AS APPROPRIATE,
TO VERIFY COMPLIANCE WITH THE DETAILS SHOWN ON CONSTRUCTION
DOCUMENTS, SUCH AS BRACES, STIFFENERS, MEMBER LOCATIONS AND PROPER
APPLICATION OF JOINT DETAILS AT EACH CONNECTION
P-REVIEW THE MATERIAL TEST REPORTS AND CERTIFICATIONS FOR COMPLIANCE
WITH THE CONSTRUCTION DOCUMENTS
AISC 360-10 INSPECTIONS FOR WELDING
TABLE N5.4-1 INSPECTION TASKS PRIOR TO WELDING QC QA
WELDING PROCEDURE SPECIFICATION (WPSs) AVAILABLE P
MANUFACTURER CERTIFICATIONS FOR WELDING CONSUMABLES AVAILABLE
MATERIAL IDENTIFICATION (TYPE/GRADE)
WELDER IDENTIFICATION SYSTEM (1)
FIT-UP OF GROOVE WELDS (INCLUDING JOINT GEOMETRY)
• JOINT PREPARATION
• DIMENSIONS (ALIGNMENT, ROOT OPENING, ROOT FACE, BEVEL)
• CLEANLINESS (CONDITION OF STEEL SURFACES)
• TACKING (TACK WELD QUALITY AND LOCATION)
• BACKING TYPE AND FIT (IF APPLICABLE)
CONFIGURATION AND FINISH OF ACCESS HOLES
FIT-UP OF FILLET WELDS
CHECK WELDING EQUIPMENT
P
• DIMENSIONS (ALIGNMENT, GAPS AT ROOT)
• CLEANLINESS (CONDITION OF STEEL SURFACES)
• TACKING (TACK WELD QUALITY AND LOCATION)
PP
OO
OO
OO
OO
OO
—O
TABLE N5.4-2 INSPECTION TASKS DURING WELDING
USE OF QUALIFIED WELDERS O
NO WELDING OVER CRACKED TACK WELDS
ENVIRONMENTAL CONDITIONS
• WIND SPEED WITHIN LIMITS
• PRECIPITATION AND TEMPERATURE
WELDING TECHNIQUES
O
• INTERPASS AND FINAL CLEANING
• EACH PASS WITHIN PROFILE LIMITATIONS
• EACH PASS MEETS QUALITY REQUIREMENTS
OO
OO
OO
OO
OO
CONTROL AND HANDLING OF WELDING CONSUMABLES
• PACKAGING
• EXPOSURE CONTROL
WPS FOLLOWED
• SETTINGS ON WELDING EQUIPMENT
• TRAVEL SPEED
• SELECTED WELDING MATERIALS
• SHIELDING GAS TYPE/FLOW RATE
• PREHEAT APPLIED
• INTERPASS TEMPERATURE MAINTAINED (MIN./MAX.)
• PROPER POSITION (F, V, H, OH)
TABLE N5.4-3 INSPECTION TASKS AFTER WELDING
WELDS CLEANED O
ARC STRIKES
O
PP
PP
WELDS MEET VISUAL ACCEPTANCE CRITERIA
• CRACK PROHIBITION
• WELD/BASE-METAL FUSION
• CRATER CROSS SECTION
• WELD PROFILES
• WELD SIZE
• UNDERCUT
• POROSITY
SIZE, LENGTH AND LOCATION OF WELDS PP
K-AREA (2) PP
BACKING REMOVED AND WELD TABS REMOVED (IF REQUIRED) PP
REPAIR ACTIVITIES PP
DOCUMENT ACCEPTANCE OR REJECTION OF WELDED JOINT OR MEMBER PP
(2) WHEN WELDING OF DOUBLER PLATES, CONTINUITY PLATES OR STIFFENERS HAS BEEN PERFORMED IN THE K-AREA, VISUALLY INSPECT THE WEB K-AREA FOR CRACKS WITHIN 3 IN. (75 MM) OF THE WELD.
(1) THE FABRICATOR OR ERECTOR, AS APPLICABLE, SHALL MAINTAIN A SYSTEM BY WHICH A WELDER WHO HAS WELDED A JOINT OR MEMBER CAN BE IDENTIFIED. STAMPS, IF USED, SHALL BE THE LOW-STRESS TYP.
AISC 360-10 INSPECTIONS FOR BOLTING
TABLE N5.6-1 INSPECTION TASKS PRIOR TO BOLTING QC QA
MANUFACTURER'S CERTIFICATIONS AVAILABLE FOR FASTENER MATERIALS P
PROPER FASTENERS SELECTED FOR THE JOINT DETAIL (GRADE, TYPE, BOLT LENGTH
IF THREADS ARE TO BE EXCLUDED FROM SHEAR PLANE)
O
FASTENERS MARKED IN ACCORDANCE WITH ASTM REQUIREMENTS
PROPER BOLTING PROCEDURE SELECTED FOR JOINT DETAIL
CONNECTING ELEMENTS, INCLUDING THE APPROPRIATE FAYING SURFACE CONDITION
AND HOLE PREPARATION, IF SPECIFIED, MEET APPLICABLE REQUIREMENTS
PRE-INSTALLATION VERIFICATION TESTING BY INSTALLATION PERSONNEL OBSERVED
AND DOCUMENTED FOR FASTENER ASSEMBLIES AND METHODS USED
PROPER STORAGE PROVIDED FOR BOLTS, NUTS, WASHERS AND OTHER FASTENER
COMPONENTS
OO
OO
OO
OO
OP
OO
TABLE N5.6-2 INSPECTION TASKS DURING BOLTING
FASTENER ASSEMBLIES, OF SUITABLE CONDITION, PLACED IN ALL HOLES AND
WASHERS (IF REQUIRED) ARE POSITIONED AS REQUIRED
JOINT BROUGHT TO THE SNUG-TIGHT CONDITION PRIOR TO THE PRETENSIONG
OPERATION
FASTENER COMPONENT NOT TURNED BY THE WRENCH PREVENTED FROM ROTATING
FASTENERS ARE PRETENSIONED IN ACCORDANCE WITH THE RCSC SPECIFICATION,
PROGRESSING SYSTEMATICALLY FROM THE MOST RIGID POINT TOWARD THE FREE
EDGES
OO
OO
OO
OO
TABLE N5.6-3 INSPECTION TASKS AFTER BOLTING
DOCUMENT ACCEPTANCE OR REJECTION OF BOLTED CONNECTIONS PP
date detailed checkeddesigned ofsheet sheets project contract rev.drawing file
DESCRIPTION
1 5432
A
B
C
D
C O
PY
R
IG
H
T
N S
M
C D
O N
N
EL
L
EN
G
IN
EE
R
IN
G
C O
M
PA
N Y, IN
C
C-17 TYPE III HYDRANT
REFUELING SYSTEM/
RAMP EXPANSION
KANSAS CITY, MISSOURI
INITDATEREV.
REVISIONS
ENGINEERS ARCHITECTS & CONSULTANTS
NORTH CAROLINA AIR NATIONAL GUARD
DOUGLAS INTERNATIONAL AIRPORT
CHARLOTTE, NORTH CAROLINA
Project No. - FJRP159073
/5
/2
3:
:1
PM
FJRP159073-S-005.dwg
S-005 94893
STATEMENT OF SPECIAL INSPECTIONS
SHEET 3
03/17/17
H. SAHUDIN J. HEIM
TMS 402 TABLE 3.1.2 - LEVEL B QUALITY ASSURANCE - MASONRY
CONTINUOUS PERIODIC
ART. 1.5X—1. VERIFY COMPLIANCE WITH THE APPROVED SUBMITTALS
MINIMUM TESTS
MINIMUM INSPECTION
VERIFICATION OF SLUMP FLOW AND VISUAL STABILITY INDEX (VSI) AS DELIVERED TO THE PROJECT SITE IN ACCORDANCE WITH SPECIFICATION ARTICLE 1.5 B.1b.3 FOR SELF-CONSOLIDATING GROUT
VERIFICATION OF f' m IN ACCORDANCE WITH SPECIFICATION ARTICLE 1.4 B PRIOR TO
CONSTRUCTION, EXCEPT WHERE SPECIFICALLY EXEMPTED BY THIS CODE
INSPECTION TASK
FREQUENCY (a) REFERENCE FOR CRITERIA
TMS 402/
ACI 530/
ASCE 5
TMS 602/
ACI 530.1/
ASCE 6
2. AS MASONRY CONSTRUCTION BEGINS, VERIFY THAT THE
FOLLOWING ARE IN COMPLIANCE:
ART. 2.1, 2.6 Aa. PROPORTIONS OF SITE-PREPARED MORTAR X—
ART. 3.3 Bb. CONSTRUCTION OF MORTAR JOINTS X—
c. LOCATION OF REINFORCEMENT, CONNECTORS X— ART. 3.4,
3.6 A
3. PRIOR TO GROUTING, VERIFY THAT THE FOLLOWING ARE IN
COMPLIANCE:
a. GROUT SPACE X—
b. GRADE, TYPE, AND SIZE OF REINFORCEMENT AND ANCHOR
BOLTS X—
c. PLACEMENT OF REINFORCEMENT, CONNECTORS X—
d. PROPORTIONS OF SITE-PREPARED GROUT X— ART. 2.6 B,
2.4 G.1.b
ART. 3.3 Be. CONSTRUCTION OF MORTAR JOINTS X—
ART. 3.2 D,
3.2 F
SEC. 1.16
SEC. 1.16
ART. 2.4, 3.4
ART. 3.2 E,
3.4, 3.6 A
4. VERIFY DURING CONSTRUCTION:
a. SIZE AND LOCATION OF STRUCTURAL ELEMENTS X—
b. TYPE, SIZE, AND LOCATION OF ANCHORS, INCLUDING OTHER
DETAILS OF ANCHORAGE OF MASONRY TO STRUCTURAL
MEMBERS, FRAMES, OR OTHER CONSTRUCTION
X—
c. PREPARATION, CONSTRUCTION, AND PROTECTION OF
MASONRY DURING COLD WEATHER (TEMPERATURE BELOW
40°F (4.4°C)) OR HOT WEATHER (TEMPERATURE ABOVE
90°F (32.2°C))
X—
d. PLACEMENT OF GROUT X— ART. 2.6 B,
2.4 G.1.b
ART. 3.2 D,
3.2 F
SEC. 1.16
SEC. 1.16
ART. 2.4, 3.4
ART. 3.2 E,
3.4, 3.6 A
3. OBSERVE PREPARATION OF GROUT SPECIMENS, MORTAR
SPECIMENS, AND/OR PRISMS X— ART. 1.4
B32.a.3,
1.4 B.2.b.3,
1.4 B.2.c.3,
1.4 B.3,
1.4 B.4
(a) FREQUENCY REFERS TO THE FREQUENCY OF INSPECTION, WHICH MAY BE CONTINUOUS DURING THE TASK LISTED OR
PERIODICALLY DURING THE LISTED TASK, AS DEFINED IN THE TABLE.
CONTINUOUS PERIODIC
ART. 1.5X—1. VERIFY COMPLIANCE WITH THE APPROVED SUBMITTALS
INSPECTION TASK
FREQUENCY (a) REFERENCE FOR CRITERIA
TMS 402/
ACI 530/
ASCE 5
TMS 602/
ACI 530.1/
ASCE 6
2. VERIFY THAT THE FOLLOWING ARE IN COMPLIANCE:
ART. 2.1, 2.6 A,
2.6 B, 2.6 C,
2.4 G 1.b
a. PROPORTIONS OF SITE-MIXED MORTAR, GROUT AND
PRESTRESSING GROUT FOR BONDED TENDONS
X—
ART. 2.4, 3.4b. GRADE, TYPE, AND SIZE OR REINFORCEMENT AND ANCHOR
BOLTS, AND PRESTRESSING TENDONS AND ANCHORAGES
X—
c. PLACEMENT OF MASONRY UNITS AND CONSTRUCTION OF
MORTAR JOINTS
X— ART. 3.3 B
e. GROUT SPACE PRIOR TO GROUTING —X
f. PLACEMENT OF GROUT AND PRESTRESSING GROUT FOR
BONDED TENDONS —X
g. SIZE AND LOCATION OF STRUCTURAL ELEMENTS X—
h. TYPE, SIZE, AND LOCATION OF ANCHORS INCLUDING OTHER
DETAILS OF ANCHORAGE OF MASONRY TO STRUCTURAL
MEMBERS, FRAMES, OR OTHER CONSTRUCTION
—X
i. WELDING OF REINFORCEMENT —X
ART. 3.2 D,
3.2 F
SEC. 1.2.1(e), 6.1.4.3, 6.2.1
SEC. 8.1.6.7.2,
9.3.3.4 (c), 11.3.3.4(b)
ART. 3.5, 3.6 C
ART. 3.3 F
3. OBSERVE PREPARATION OF GROUT SPECIMENS, MORTAR
SPECIMENS, AND/OR PRISMS
(a) FREQUENCY REFERS TO THE FREQUENCY OF INSPECTION, WHICH MAY BE CONTINUOUS DURING THE TASK LISTED OR
PERIODICALLY DURING THE LISTED TASK, AS DEFINED IN THE TABLE.
d. PLACEMENTS OF REINFORCEMENT, CONNECTORS, AND
PRESTRESSING TENDONS AND ANCHORAGES
ART. 1.8 C,
1.8 D
j. PREPARATION, CONSTRUCTION, AND PROTECTION OF MASONRY
DURING COLD WEATHER (TEMPERATURE BELOW 40°F (4.4°C))
OR HOT WEATHER (TEMPERATURE ABOVE 90°F (32.2°C))
X—
ART. 3.6 Bk. APPLICATION AND MEASUREMENT OF PRESTRESSING FORCE —X
ART. 3.3 B.9,
3.3 F.1.b
l. PLACEMENT OF AAC MASONRY UNITS AND CONSTRUCTION OF
THIN-BED MORTAR JOINTS
—X
ART. 2.1 C.1m. PROPERTIES OF THIN-BED MORTAR FOR AAC MASONRY —X
X —
—X
SEC. 6.1
SEC. 6.1,
6.2.1, 6.2.6, 6.2.7
SEC. 3.2 E,
3.4, 3.6 A
ART. 1.4 B.2.a.3,
1.4 B.2.b.3,
1.4 B.2.c.3,
1.4 B.3, 1.4 B.4
TMS 402 TABLE 3.1.3 - LEVEL C QUALITY ASSURANCE - MASONRY
MINIMUM TESTS
MINIMUM INSPECTION
VERIFICATION OF f' m AND f' aac IN ACCORDANCE WITH SPECIFICATION ARTICLE 1.4 B PRIOR TO
CONSTRUCTION AND FOR EVERY 5,000 SQ. FT (465 SP. M) DURING CONSTRUCTION
VERIFICATION OF SLUMP FLOW AND VISUAL STABILITY INDEX (VSI) AS DELIVERED TO THE PROJECT SITE IN ACCORDANCE WITH SPECIFICATION ARTICLE 1.5 B.1b.3 FOR SELF-CONSOLIDATING GROUT
VERIFICATION OF PROPORTIONS OF MATERIALS IN PREMIXED OR PREBLENDED MORTAR, PRESTRESSING GROUT, AND GROUT OTHER THAN SELF-CONSOLIDATING GROUT, AS DELIVERED TO THE PROJECT SITE date detailed checkeddesigned ofsheet sheets project contract rev.drawing file
DESCRIPTION
1 5432
A
B
C
D
C O
PY
R
IG
H
T
N S
M
C D
O N
N
EL
L
EN
G
IN
EE
R
IN
G
C O
M
PA
N Y, IN
C
C-17 TYPE III HYDRANT
REFUELING SYSTEM/
RAMP EXPANSION
KANSAS CITY, MISSOURI
INITDATEREV.
REVISIONS
ENGINEERS ARCHITECTS & CONSULTANTS
NORTH CAROLINA AIR NATIONAL GUARD
DOUGLAS INTERNATIONAL AIRPORT
CHARLOTTE, NORTH CAROLINA
Project No. - FJRP159073
/5
/2
3:
:1
PM
FJRP159073-S-006.dwg
S-006 94893
STATEMENT OF SPECIAL INSPECTIONS
SHEET 4
03/17/17
H. SAHUDIN J. HEIM
NEW HYDRANT
PIT A1. SEE S-527
NEW HYDRANT
PIT A2. SEE S-527
NEW HYDRANT
PIT A3. SEE S-527
NEW HYDRANT
PIT B1. SEE S-527
NEW HYDRANT
PIT B2. SEE S-527
NEW ISOLATION
VALVE VAULT
SEE S-524
NEW HHTC STAND
SEE S-109
NEW PUMP SHELTER
SEE S-103
EXISTING TANKS. SEE S-102
NEW TANK AND
CONTAINMENT AREA
SEE S-101
NEW SEGMENTAL
RETAINING WALL.
SEE CIVIL
NEW PRODUCT RECOVERY
TANK VAULT AND CANOPY.
SEE S-108
NEW PIG LAUNCHER
VALVE PAD. SEE S-104
NEW ISOLATION
VALVE PIT. SEE S-526
NEW SPILL CONTROL
PIT. SEE S-110NEW LOW POINT
DRAIN PIT. SEE S-530
NEW DIVERSION PIT
SEE S-111
EXISTING PUMP
SHELTER
EXISTING TRUCK
LOAD/ OFFLOAD STATIONS
NEW REFUELER PARKING.
SEE CIVIL
EXISTING
FUELS OPERATIONS
BUILDING
NEW BLAST DEFLECTION
AND FOUNDATION.
SEE REFERENCE
DRAWING R-001
NEW HIGH POINT VENT PIT
SEE S-530
NEW LOW POINT DRAIN PIT
SEE S-530
NEW HIGH POINT VENT PIT
SEE S-530
NEW HIGH POINT VENT PIT
SEE S-530
NEW LOW POINT DRAIN PIT
SEE S-530
NEW LOW POINT
DRAIN PIT SEE S-530
NEW HIGH POINT VENT PIT
SEE S-530
date detailed checkeddesigned ofsheet sheets project contract rev.drawing file
DESCRIPTION
1 5432
A
B
C
D
C O
PY
R
IG
H
T
N S
M
C D
O N
N
EL
L
EN
G
IN
EE
R
IN
G
C O
M
PA
N Y, IN
C
C-17 TYPE III HYDRANT
REFUELING SYSTEM/
RAMP EXPANSION
KANSAS CITY, MISSOURI
INITDATEREV.
REVISIONS
ENGINEERS ARCHITECTS & CONSULTANTS
NORTH CAROLINA AIR NATIONAL GUARD
DOUGLAS INTERNATIONAL AIRPORT
CHARLOTTE, NORTH CAROLINA
Project No. - FJRP159073
/5
/2
3:
:2
PM
FJRP159073-S-007.dwg
S-007 94893
OVERALL STRUCTURAL LAYOUT
03/17/17
H. SAHUDIN J. HEIM
M. PATEL
NTSSCALE:A1 OVERALL STRUCTURAL LAYOUT N
T
T
4'-0" WIDE CONCRETE
SIDEWALK - SEE NOTE 10
T/SIDEWALK EL 701'-3" TYP
AROUND TANK
RINGWALL
SEE S-511
T/RINGWALL EL 702'-3"
EXISTING DIKE WALL TO REMAIN
CONCRETE
DIKE WALL
T/WALL EL 705'-2"
ACCESS
STAIR NO. 1
SEE S-541
CL TANK
C1 S-515
C L
TA
N
K
TANK BOTTOM
FML SUMP TANK BOTTOM
SUMP
'-0
'-0
'-0
4'
-1 0"
CLJ
CJ
CLJ
15'-0"
15'-0"
7'-2"
CJ
CLJ
CJ
15'-0" 6'-0"
'-0
'-0
7' -6
CLJCJ
CLJ
CJ
CLJ
CJ
CLJ
CJ
NEW FUEL
STORAGE TANK
ABOVE
SEE MECH
5'-0"
5' -0
EX
IS
TI
N
G D
IK
E
C O
N
TA
IN
M
EN
T
AR
EA
SE
E
S-
123.00°
123.00°
'-6
DIKE DRAIN
PER CIVIL
CONCRETE STAIR
LANDING PAD
T/C EL 702'-6"
IJ
IJ
19'-0"
C3 S-515
FOOTIN BELOW
T/FTG EL 699'-11", TYP2'-0"
9'-5 1/16"
0UP
TANK STAIR
8'-0"8'-0"
NEW ACCESS
STAIR NO. 2
SEE S-542
47'-5 11/16" 5'-6"
'-8
/8
4' -0
4'-0" 4'-0"
NEW SEGMENTAL RETAINING WALL
SEE CIVIL
'-1
/1
6"
147.00°
TYP
SIDEWALK JOINT (TYP)
'-1
0"
44'-4 9/16"
'-6
5/
'-0
'-0
2'- 3"
27'-2 3/8"
'-0
/1 6"
7.
PRODUCT SAVER TANK
SEE MECH
date detailed checkeddesigned ofsheet sheets project contract rev.drawing file
DESCRIPTION
1 5432
A
B
C
D
C O
PY
R
IG
H
T
N S
M
C D
O N
N
EL
L
EN
G
IN
EE
R
IN
G
C O
M
PA
N Y, IN
C
C-17 TYPE III HYDRANT
REFUELING SYSTEM/
RAMP EXPANSION
KANSAS CITY, MISSOURI
INITDATEREV.
REVISIONS
ENGINEERS ARCHITECTS & CONSULTANTS
NORTH CAROLINA AIR NATIONAL GUARD
DOUGLAS INTERNATIONAL AIRPORT
CHARLOTTE, NORTH CAROLINA
Project No. - FJRP159073
/5
/2
3:
:3
PM
FJRP159073-S-101.dwg
S-101 94893
TANK CONTAINMENT AREA
FOUNDATION AND DIKE WALL PLAN
11/16/2016
H. SAHUDIN J. HEIM
M. PATEL
SCALE: 3/16" = 1'-0"A1 FOUNDATION AND DIKE WALL PLAN
0 4' 8' 12'
N
NOTES:
1. SEE DRAWING S-001 FOR STRUCTURAL GENERAL NOTES.
2. SEE DRAWING CS-104 FOR EXACT LOCATIONS AND ORIENTATION
OF STRUCTURES.
3. ELEVATIONS INDICATED EQUAL DATUM ELEVATION AS SHOWN
ON THE CIVIL DRAWINGS.
4. SEE DRAWING S-514 FOR DIKE WALL CONSTRUCTION JOINT (CJ),
CONTROL JOINT (CLJ) AND ISOLATION JOINT (IJ) DETAILS. SEE
ELECTRICAL AND MECHANICAL DRAWINGS FOR CONDUIT AND
PIPING PENETRATIONS THROUGH THE DIKE WALLS. FOR PIPE
SLEEVE, SEE DETAIL ON DRAWING S-502.
5. CONSTRUCTION JOINTS IN THE DIKE WALL FOOTINGS SHALL BE
LOCATED AS NECESSARY BY THE CONTRACTOR AND SHALL BE
APPROVED BY ENGINEER PRIOR TO CONSTRUCTION. LOCATE
JOINTS IN THE FOOTINGS DIRECTLY BELOW THE JOINTS IN THE
DIKE WALL. SEE DETAIL ON DRAWING S-515 FOR DIKE WALL
FOOTING CJ DETAIL.
6. AT SURFACES ADJACENT TO AND/OR UNDER THE LINER, WALL
SURFACES SHALL BE SOLID AND SMOOTH AND SHALL NOT HAVE
PROJECTIONS OR RECESS OVER 1/32" FROM THE WALL
SURFACES. GRIND SMOOTH ANY PROJECTIONS AND PATCH ANY
HOLES PRIOR TO LINER INSTALLATION.
7. NOTCH BOTTOM OF DIKE WALL FOOTING/SHEARKEY AS
REQUIRED TO CLEAR THE CONTAINMENT DRAIN PIPES. SEE
CIVIL DRAWINGS FOR PIPE LOCATIONS AND ELEVATIONS.
8. SEE DRAWING S-541 AND S-542 FOR CROSSOVER STAIR
ENLARGED PLANS.
9. SEE DETAIL A1 ON DRAWING S-501 FOR EQUIPMENT /
HOUSEKEEPING PAD DETAIL. COORDINATE SIZE AND TOP OF
CONCRETE ELEVATIONS WITH THE FINAL EQUIPMENT
FURNISHED.
10. PROVIDE 4" THICK MINIMUM FIBER-REINFORCED CONCRETE
SIDEWALK. PROVIDE ONE LAYER OF GEOTEXTILE FABRIC OVER
THE LINER PRIOR TO CONCRETE SIDEWALK PLACEMENT. SEE
S-514 FOR SIDE WALK AND JOINT DETAILS.
11. SEE MECHANICAL DRAWINGS FOR PIPE SUPPORT LOCATIONS
AND TYPES.
A
EXISTING
TANK
NEW LINER OVER
EXISTING DIKE
CONTAINMENT SLAB
SEE NOTE 2
NEW LINER OVER
EXISTING DIKE
CONTAINMENT SLAB
SEE NOTE 2
NEW ACCESS
STAIR NO. 2
SEE S-542
NEW ACESS
STAIR NO. 3
SEE S-543
EXISTING
CONCRETE
DIKE WALL
'-0
NEW DIKE WALL
SEE S-101
NEW 4'-0" WIDE
CONCRETE SIDEWALK
SEE NOTE 10 ON S-101
'-7
N
EW
D
IK
E C
O N
TA
IN
M
EN
T
AR
EA
S
EE
S
-1
'-7
/1
6"
ATTACH NEW LINER TO
EXISTING RING WALL
AND DIKE WALL PER
DETAIL A1/S-513
C3 S-515
12" TALL NOTCH
IN EXISTING DIKE
WALL. SEE NOTE 4
8' -0
'-0
12" TALL NOTCH
IN EXISTING DIKE
WALL
SEE NOTE 4
EXISTING TANK
RINGWALL
EXISTING TANK
RINGWALL
ATTACH NEW LINER TO
EXISTING RING WALL
AND DIKE WALL PER
DETAIL A1/S-513
EXISTING PIPE PENETRATION
IN EXISTING DIKE WALL
(6 TOTAL)
NEW PUMP SHELTER
SEE S-103
B3 S-515
8'-0" 12'-6"
24" SQUARE EXISTING
CONTAINMENT DRAIN
UP
EXISTING
TANK
UP
TY
P4'-
0"
TYP
4'-0"
60'-11 9/16" 10" 60'-1 7/16"
NEW WALL TOP SEGMENT
NEW PRODUCT
SAVER TANK
SEE MECH
NEW PRODUCT
SAVER TANK
SEE MECH
NOTCH IN EXISTING
DIKE WALL 6" CLEAR
AROUND PIPE
SIDEWALK JOINTS (TYP)
24" SQUARE EXISTING
CONTAINMENT DRAIN
'-6
/8
'-7
NEW PIPE SLEEVE IN
EXISTING WALL SEE S-502
date detailed checkeddesigned ofsheet sheets project contract rev.drawing file
DESCRIPTION
1 5432
A
B
C
D
C O
PY
R
IG
H
T
N S
M
C D
O N
N
EL
L
EN
G
IN
EE
R
IN
G
C O
M
PA
N Y, IN
C
C-17 TYPE III HYDRANT
REFUELING SYSTEM/
RAMP EXPANSION
KANSAS CITY, MISSOURI
INITDATEREV.
REVISIONS
ENGINEERS ARCHITECTS & CONSULTANTS
NORTH CAROLINA AIR NATIONAL GUARD
DOUGLAS INTERNATIONAL AIRPORT
CHARLOTTE, NORTH CAROLINA
Project No. - FJRP159073
/5
/2
3:
:3
PM
FJRP159073-S-102.dwg
S-102 94893
EXISTING TANK CONTAINMENT AREA
PLAN
04/06/17
H. SAHUDIN J. HEIM
M. PATEL
SCALE: 3/16" = 1'-0"A1 EXISTING TANK CONTAINMENT AREA PLAN
0 4' 8' 12'
N
NOTES:
1. SEE S-101 FOR TANK AREA NOTES.
2. SEE S-513 FOR LINER DETAILS.
3. SEE S-514 FOR SIDEWALK DETAILS INSIDE THE DIKE AREA.
4. NOTCHES IN EXISTING WALL MAY BE CREATED BY SAW CUTTING
THE WALL AND REBARS NEATLY. COAT END OF CUT REBAR WITH
GREY EPOXY PAINT.
2 3 4
C
D
'-4
'-4
PUMP FOUNDATION, TYP
T/C EL 100'-0"
4'-6"4'-9"4'-6"4'-9"4'-6"
1'-6"24'-0"24'-4"24'-0"1'-6"
75'-4"
C1 S-521
C3 S-521
A1 S-521
A2 S-521
S-201 C1
S-201 C3
S-201 A1
S-201 A3
8' -6
S-202 C1
C4 S-521
A4 S-521
F3
F3 F3
F3
'-0
1' -2
1'
-2
F1
F2 F2
F1
B
1"
15'-2" 1'-6"
T/CURB EL 100'-0"
TYP, UNO
T/WALL EL 100'-0"
C1 S-522
A1 S-503
TYP
1'-2"
T/C EL 99'-2" TYP
ACROSS DOORS T/C EL 99'-11 1/2"
1'-2"
1' -2
1'
-2
4' -6
'-0
A3 S-522
F1
F2F2
F1
3' -0
1. SEE PLAN FOR FOOTING AND COLUMN
ORIENTATION.
2. FOOTING LENGTH ORIENTED PARALLEL TO
COLUMN WEB.
3. THE ASSUMED COLUMN REACTION (FACTORED
ULTIMATE LOADS) ARE THE WORST CASE
RESULTANT FORCES DUE TO A COMBINATION
OF DEAD, LIVE, CRANE, SESIMIC, AND/OR
WIND LOADS (INCUDING VERTICAL BRACING
FORCES)
P = DOWNWARD VERTICAL RACTION
-P = UPLIFT REACTION
Hx = BASE SHEAR PARALLEL TO COLUMN WEB Hy = BASE SHEAR PERPENDICULAR TO
COLUMN WEB
Hx AND Hy ARE ASSUMED TO ACT
SIMULTANEOUSLY
Mx = MOMENT ABOUT MINOR AXIS OF
COLUMN
My = MOMENT ABOUT MAJOR AXIS OF
COLUMN
4. SHEAR KEY A ORIENTED PARALLEL TO
COLUMN WEB. SHEAR KEY B ORIENTED
PERPENDICULAR TO COLUMN WEB.
5. UNLESS INDICATED OTHERWISE, FOOTINGS
SHALL BE LOCATED UNDER COLUMNS
3'-0"
3' -0
WIDTH/2 WIDTH/2
LE
N
G
TH
/2
LE
N G
TH
/2
SHEAR KEY A
SHEAR KEY B
X-BAR
Y-BAR
Hy
Hx
FOOTING SCHEDULE NOTES:
date detailed checkeddesigned ofsheet sheets project contract rev.drawing file
DESCRIPTION
1 5432
A
B
C
D
C O
PY
R
IG
H
T
N S
M
C D
O N
N
EL
L
EN
G
IN
EE
R
IN
G
C O
M
PA
N Y, IN
C
C-17 TYPE III HYDRANT
REFUELING SYSTEM/
RAMP EXPANSION
KANSAS CITY, MISSOURI
INITDATEREV.
REVISIONS
ENGINEERS ARCHITECTS & CONSULTANTS
NORTH CAROLINA AIR NATIONAL GUARD
DOUGLAS INTERNATIONAL AIRPORT
CHARLOTTE, NORTH CAROLINA
Project No. - FJRP159073
/5
/2
3:
:3
PM
FJRP159073-S-103.dwg
S-103 94893
PUMP SHELTER
FOUNDATION PLAN
11/17/2016
H. SAHUDIN J. HEIM
M. PATEL
SCALE: 1/4" = 1'-0"A1 FOUNDATION PLAN
0 2' 4' 8'
N
NOTES:
1. SEE DRAWING S-001 FOR GENERAL NOTES.
2. ELEVATION 100'-0" SHOWN FOR THE PUMP SHELTER
EQUALS DATUM ELEVATION 702'-9" AS SHOWN ON
THE CIVIL DRAWINGS.
3. SEE DRAWING CS-104 FOR EXACT BUILDING LOCATION
AND ORIENTATION.
4. COORDINATE COLUMN ANCHOR BOLT REQUIREMENTS
WITH THE PRE-ENGINEERED METAL BUILDING
MANUFACTURER. SEE DRAWING S-501 FOR ANCHOR
BOLT DETAILS.
5. THE BUILDING FOUNDATION HAS BEEN DESIGNED
USING THE ASSUMED REACTIONS INDICATED ON THIS
DRAWING. VERIFY THAT THE ACTUAL COLUMN
REACTIONS FROM THE PRE-ENGINEERED BUILDING
MANUFACTURER DO NOT EXCEED THE INDICATED
VALUES. COLUMN REACTIONS SHALL BE SUBMITTED
FOR REVIEW AND VERIFICATION AT LEAST 20 WORKING
DAYS PRIOR TO THE START OF THE FOUNDATION
CONSTRUCTION. NOTIFY CONTRACTING OFFICER IF
THE ASSUMED VALUES ARE EXCEEDED. DO NOT
START FOUNDATION CONSTRUCTION UNTIL
VERIFICATION OF THE COLUMN REACTIONS HAS BEEN
OBTAINED.
6. "F#" INDICATES FOOTING TYPE. SEE THIS DRAWING
FOR FOUNDATION SCHEDULE.
7. BUILDING STRUCTURE AND ANCHORAGE SHALL BE
DESIGNED ASSUMING AN INITIAL OPEN-CONFIGURATION
STRUCTURE AS SHOWN. PROVISIONS SHALL MADE TO
ALLOW FOR THE STRUCTURE TO BE FULLY ENCLOSED
(BY ADDITION OF METAL SIDING OR MASONRY VENEER
AND GIRT SYSTEM) IN THE FUTURE.
FOOTING SCHEDULE
MARK
FOOTING
THICKNESS
FOOTING
TOP OF
FOOTING ELEV
TOP OF
PED ELEV DETAIL
ASSUMED COLUMN
REACTIONS
COMMENTS
WIDTH LENGTH BOTTOM
REINFORCMENT
TOP
REINFORCMENT Pmax Pmin Hx Hy
F1 8'-0" 8'-0" 1'-6" #5 @ 12" EW #5 @ 12" EW 97"-6" 100'-0" A1/S-521 48 kip -12 kip 10 kip 5 kip
F2 12'-0" 12'-0" 1'-9" #5 @ 12" EW #5 @ 12" EW 97'-6" 100'-0" A2/S-521 28 kip -4 kip 17 kip 23 kip SHEAR LUG BY
BLDG MFR
F3 4'-0" 6'-0" 1'-0" #5 @ 12" EW #5 @ 12" EW 97'-6" 100'-0" A4/S-521 6.5 kip 3 kip 1.5 kip 2.5 kip
SEISMIC DESIGN PARAMETERS:
A. NORTH-SOUTH DIRECTION:
STEEL ORDINARY MOMENT FRAME
R = 3.5 Ω = 3 Cd = 3
EQUIVALENT LATERAL FORCE ANALYSIS
Cs = 0.083
BASE SHEAR = 7 KIP
B. EAST-WEST DIRECTION:
STEEL ORDINARY CONCENTRICALLY
BRACED FRAME
R = 3.25 Ω = 2 Cd = 3.25
EQUIVALENT LATERAL FORCE ANALYSIS
Cs = 0.083
BASE SHEAR = 7 KIP
2 3 4
C
D
1'-6"24'-0"24'-4"24'-0"1'-6"
75'-4" 1'
-2
'-4
'-0
'-4
1'
-2
FLOOR SLAB
SEE NOTE 9
FLOOR SLAB
12" CMU
WALL
ABOVE
PUMP FOUNDATION,
TYP (3 TOTAL)
VERTICAL BRACING
TYP, SEE NOTE 4
FUTURE WIND COLUMN (NIC),
INSTALL ANCHOR BOLTS ONLY
TYP 2 PLACES
C1 S-521
C3 S-521
S-201 C1
S-201 C3
S-201 A1
S-201 A3
S-202 C1
C4 S-521
T/CURB EL 100'-0"
T/CURB EL 100'-0" TYP UNO
PIG LAUNCHER VALVE
CONTAINMENT PAD
T/CONC EL 99'-6"
TYP UNO
T/CONC EL 100'-0"
4' -6
'-0
1' -0
"5'-6"
6'-6" 8'-0"
SLOPE
4' -0
1'
-2
4' -0
8'-0"1'-6"
'-0
TY
P
METAL STUD WALLS
SEE ARCH
1' -0
B
8'-10"
CJ
CJ
CJ
CJ
CJ IJ IJ
IJ IJ IJ
IJ IJ IJ IJ IJ IJ
C
LJ
C
LJ
C
LJ
C
LJ
C
LJ
C
LJ
C
LJ
IJ
IJ
IJ
C
LJ
TYP UNO
SEE NOTE 9
9'-2" 4'-7" 9'-3"
C1 S-522
B3 S-503
MECH ROOM
STORAGE TOILET
4'-0"
5' -0
8"
4' -4
5'
-0
XX XX
XX XX
C
LJ
C
LJ
C
LJ
PUMP ROOM
C
LJ
C
LJ
CJ
CJ
CJ CJ
CJ
CJ
CJ
IJ
CJ
CJ
CJ
CJ
CJ
1'-0"
18'-0"
'-0
IJ
CONTROL
ROOM
HOUSEKEEPING
PAD, UNDER
ELECTRICAL
EQUIPMENT
SEE A1/S-501
C3 S-521
SIM
D2 S-503
TYP
ACROSS
DOORS
A2 S-501
SIM
A1 S-503
A3 S-522
T/C EL
99'-11 1/2"
PIPE TRENCH
SEE A1/S-522
6"
CONCRETE DOOR STOOP
TYP, SEE DETAIL B1/S-503
UTILITY TRENCH
UNDER MCC
DRAIN PIPE
BELOW
3'-10"
7' -0
8'-4"
4' -1
4'-3"
7' -0
"2'-9"2'-9"
2' -9
2'
-9
2'-9"2'-9"
2' -9
2'
-9
2'-9"2'-9"
1' -4
2'
-9
2' -9
12" THICKEND SLAB
SEE DETIAL A2/S523
PIPE SUPPORT
PEDESTAL, TYP
8"
FLOOR SLAB
T/CONC EL 99'-6"
TYP UNO
SEE NOTE 9
FUTURE CORNER COLUMN (NIC),
INSTALL ANCHOR BOLTS ONLY
TYP 2 PLACES
WIND COLUMN
2 PLACES
date detailed checkeddesigned ofsheet sheets project contract rev.drawing file
DESCRIPTION
1 5432
A
B
C
D
C O
PY
R
IG
H
T
N S
M
C D
O N
N
EL
L
EN
G
IN
EE
R
IN
G
C O
M
PA
N Y, IN
C
C-17 TYPE III HYDRANT
REFUELING SYSTEM/
RAMP EXPANSION
KANSAS CITY, MISSOURI
INITDATEREV.
REVISIONS
ENGINEERS ARCHITECTS & CONSULTANTS
NORTH CAROLINA AIR NATIONAL GUARD
DOUGLAS INTERNATIONAL AIRPORT
CHARLOTTE, NORTH CAROLINA
Project No. - FJRP159073
/5
/2
3:
:4
PM
FJRP159073-S-104.dwg
S-104 94893
PUMP SHELTER
FLOOR SLAB PLAN
11/17/2016
H. SAHUDIN J. HEIM
M. PATEL
SCALE: 1/4" = 1'-0"A1 FLOOR SLAB PLAN
0 2' 4' 8'
N
NOTES:
1. SEE DRAWING S-001 FOR GENERAL NOTES.
2. ELEVATION 100'-0" SHOWN FOR THE PUMP SHELTER
EQUALS DATUM ELEVATION 702'-9" AS SHOWN ON
THE CIVIL DRAWINGS.
3. SEE DRAWING CS-104 FOR EXACT BUILDING LOCATION
AND ORIENTATION.
4. - - XX - - INDICATES BUILDING VERTICAL BRACING
LOCATION. (TENSION ONLY BRACING
ASSUMED FOR FOUNDATION DESIGN)
5. FOR SIZE, LOCATION AND DETAIL OF PIPE AND
CONDUIT PENETRATIONS NOT SHOWN, SEE
MECHANICAL, ELECTRICAL AND ARCHITECTURAL
DRAWINGS.
6. SEE MECHANICAL AND ELECTRICAL DRAWINGS FOR
REQUIRED HOUSEKEEPING PADS SIZES AND
LOCATIONS. SEE DETAIL A1/S-501 FOR TYPICAL
EQUIPMENT PAD DETAIL. WHERE EQUIPMENT PAD IS
LOC…