S c a l e
F o r
M i c r o f i l m i n g
I n c h e s
M i l l i m e t e r s date detailed checkeddesigned ofsheet sheets project contract rev.drawing file
NORTH CAROLINA AIR NATIONAL GUARD
DOUGLAS INTERNATIONAL AIRPORT
CHARLOTTE, NORTH CAROLINA
KANSAS CITY, MISSOURI
ENGINEERS ARCHITECTS & CONSULTANTS
Project No. - FJRP159073
C-17 TYPE III HYDRANT
REFUELING SYSTEM/
RAMP EXPANSION
94893
C O
P Y
R I G
H T
B U
R N
M
D
O N
N E
L L
E
N G
I N
E E
R I N
G
C
O M
P A
N Y
I N
C
D
2 3
C
4 5
A
B
FA001
94893_FA-001.DWG
FIRE ALARM LEGEND, GENERAL
NOTES, ABBREVIATIONS, SYMBOLS,
RISER AND MATRIX
Z. ATAIYAN
10/4/17 A. HANKINS
A. SCHOENECKER
FIRE ALARM SYSTEM LEGEND GENERAL NOTES: AUDIBLE AND VISIBLE DESIGN
CRITERIAABBREVIATIONS
SECTION, DETAIL OR ELEVATION
IDENTIFICATION MARK
PLATE NUMBER WHERE SECTION,
DETAIL OR ELEVATION IS TAKEN
SECTION, DETAIL OR
ELEVATION TITLE
PLATE NUMBER WHERE DETAIL IS
DRAWN
DETAIL
NUMBER
DETAIL CALLOUT SYMBOL
DETAIL/SECTION TITLE
SECTION CUT SYMBOL
SECTION
LETTER
PLATE NUMBER
WHERE SECTION IS
DRAWN
VIEW
SECTION
F
HEAT DETECTOR
F = FIXED TEMPERATURE
XP = EXPLOSION PROOF / RATE COMPENSATING
P = PHOTOELECTRIC
S
P
SMOKE DETECTOR
F MANUAL FIRE ALARM PULL STATION
FAC FIRE ALARM COMMUNICATOR (e.g. RF TRANSMITTER)
FACU
FIRE ALARM CONTROL UNIT
SS
SURGE SUPPRESSOR (TRANSIENT VOLTAGE
SURGE SUPPRESSOR)
EPDS SYSTEM (BY DIV. 26)
F HORN
XP = EXPLOSION PROOF
HORN / STROBE COMBINATION
CLEAR STROBE
XP = EXPLOSION PROOF
AOM
ADDRESSABLE OUTPUT CONTROL MODULE
AIM
ADDRESSABLE INPUT MONITOR MODULE
ANTENNA
BATT
SECONDARY POWER SUPPLY (BATTERY)
GROUND
ACH AIR CHANGES PER HOUR
AFF ABOVE FINISHED FLOOR
AHJ AUTHORITY HAVING JURISDICTION
AWG AMERICAN WIRE GAGE
CD CANDELA
CO² CARBON DIOXIDE
dBA DECIBEL A-WEIGHTED
EMCS ENERGY MONITORING AND CONTROL SYSTEM
EPDS EMERGENCY POWER DOWN SYSTEM
FA FIRE ALARM
FAC FIRE ALARM COMMUNICATOR
FACU FIRE ALARM CONTROL UNIT
IAW IN ACCORDANCE WITH
IDC INITIATING DEVICE CIRCUIT
NAC NOTIFICATION APPLIANCE CIRCUIT
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION
RTS REMOTE TEST SWITCH
SLC SIGNALING LINE CIRCUIT
TYP TYPICAL
UL UNDERWRITERS LABORATORIES
XP EXPLOSION PROOF CLASS I, DIV 2, GROUP D
1. PROVIDE AUDIBLE NOTIFICATION APPLIANCES AS INDICATED TO
ACCOMPLISH THE FOLLOWING DESIGN CRITERIA WITH ALL DOORS,
FIRE SHUTTERS, AND WINDOWS CLOSED. WHERE THIS DESIGN
CRITERIA IS NOT ACCOMPLISHED DURING COMMISSIONING,
PROVIDE ADDITIONAL DEVICES TO MEET THE MINIMUM DESIGN
CRITERIA WITHOUT EXCEEDING THE LIMITATIONS OF THE FACU AND
FAC (INCLUSIVE OF PRESCRIBED SAFETY FACTORS).
2. PROVIDE A QUANTITY OF HORNS IN EACH ROOM/AREA TO ACHIEVE
THE REQUIRED SOUND POWER OUTLINED IN THESE CONTRACT
DOCUMENTS.
3. PROVIDE A MINIMUM SOUND POWER OF 70 DBA AND 15 DBA OVER
THE AVERAGE AMBIENT SOUND LEVEL AT THE MOST REMOTE
LOCATION WITHIN THE ROOM/AREA MEASURED AT 5 FT AFF.
MEASURE THE SOUND POWER OFF THE TEMPORAL THREE TONE
PATTERN. THE FOLLOWING CRITERIA WILL BE USED FOR REVIEW
AND APPROVAL OF SHOP DRAWINGS.
A. REDUCE THE SOUND POWER BY 6 DBA EACH TIME THE
DISTANCE BETWEEN THE APPLIANCE AND THE LISTENER IS
DOUBLED. STARTING DISTANCE IS PER MANUFACTURER'S
DATASHEET, TYPICALLY 10 FT.
B. REDUCE THE SOUND POWER IN ACCORDANCE WITH THE
MANUFACTURER'S DATASHEET FOR SOUND POWER
DISTRIBUTION NOT PERPENDICULAR TO THE FACE OF THE
APPLIANCE. REFER TO MANUFACTURER'S TYPICAL SOUND
OUTPUT DISTRIBUTION DIAGRAM.
C. IN LIEU OF THE MANUFACTURER'S PUBLISHED DBA LOSS,
ASSUME A MINIMUM 15 DBA LOSS THROUGH A STANDARD
CLOSED DOOR.
4. PROVIDE VISUAL NOTIFICATION APPLIANCES AS REQUIRED TO
ACHIEVE THE COVERAGE INDICATED IN THESE CONTRACT
DOCUMENTS.
5. SPACE STROBES IN ACCORDANCE THE CRITERIA OUTLINED IN
NFPA 72, UNLESS OTHERWISE NOTED.
1. PROVIDE AN ADDRESSABLE COMBINED FIRE ALARM SYSTEM. INTEGRATE
THE SIGNAL FROM THE FACU TO THE EPDS FOR SHUTDOWN OF THE FUEL
PUMPS UPON DETECTION OF FIRE. COORDINATE FIRE ALARM
COMMUNICATIONS TO THE FIRE DEPARTMENT VIA A NEW MONICO
TRANSCEIVER.
2. COORDINATE ALL REQUIRED SYSTEMS TO THE SATISFACTION OF THE
ENGINEER AND AUTHORITY HAVING JURISDICTION. ANY DEFICIENCIES,
INCONSISTENCIES, OR POORLY COORDINATED INSTALLATIONS SHALL BE
CORRECTED BY THE CONTRACTOR AT NO ADDITIONAL COST.
3. THE FIRE ALARM DRAWINGS ARE SCHEMATIC IN NATURE AND SHOW A
MINIMAL QUANTITY OF DEVICES. DETERMINE THE FINAL QUANTITY AND
LOCATION OF ALL DEVICES IN ACCORDANCE WITH THE SPECIFICATIONS,
CONTRACT DRAWINGS, AND MANUFACTURER'S WRITTEN
RECOMMENDATIONS TO BE COMPLIANT WITH ALL APPLICABLE CODES AND
STANDARDS. PROVIDE ADDITIONAL DEVICES WHEN REQUIRED FOR A FULLY
FUNCTIONING FIRE ALARM SYSTEM AS REQUIRED BY NFPA 72, AND UFC
3-600-01.
4. CONCEAL ALL CONDUITS IN WALLS OR ABOVE CEILING UNLESS OTHERWISE
INDICATED. EXCEPTION: CONDUIT IS ALLOWED TO BE SURFACE MOUNTED
ON WALLS AND CEILINGS IN UNFINISHED AREAS (SUCH AS MECHANICAL
ROOM, ELECTRICAL ROOM). WHERE A CONDUIT SUPPLIES A DEVICE NOT
MOUNTED DIRECTLY ON THE WALL OR CEILING, ROUTE THE CONDUIT AS A
SINGLE PENDENT DROP TO EACH DEVICE FROM THE CEILING SURFACE
ABOVE. DO NOT TRAPEZE CONDUIT ACROSS AN OPEN SPACE.
5. UNFINISHED AREAS: PROVIDE FACTORY PAINTED RED CONDUIT,
JUNCTION/BACK BOXES, COVERS, AND COUPLINGS IN UNFINISHED AREAS.
6. FINISHED AREAS: PAINT EXPOSED CONDUIT AND JUNCTION/BACK BOXES IN
FINISHED AREAS TO MATCH ADJACENT SURFACES. IDENTIFY THE INSIDE
COVER OF THE JUNCTION/BACK BOX AS "FIRE ALARM" AND PAINT CONDUIT
WITH RED BANDS 3/4-IN. WIDE AT 20 FT INTERVALS AND ON BOTH SIDES OF
ALL FLOOR, WALL, AND CEILING PENETRATIONS.
7. PROVIDE CONDUIT IN ACCORDANCE WITH THE REQUIREMENTS OF THE
ELECTRICAL SPECIFICATIONS, UNLESS OTHERWISE INDICATED. SUPPORT
CONDUIT IN ACCORDANCE WITH THE NEC (SUCH AS MAXIMUM 10 FT
SUPPORT INTERVALS AND 3 FT FROM A TERMINATION).
8. PROVIDE CONDUCTOR SIZING NOT LESS THAN 18 AWG FOR SLC AND IDC.
PROVIDE CONDUCTOR SIZING NOT LESS THAN 16 AWG FOR NAC.
CONSISTENTLY COLOR COORDINATE ALL CONDUCTORS THROUGH THE
SYSTEM IN RELATION TO DEVICES THEY FEED SUCH AS SLC - BLACK/RED
AND STROBE -YELLOW/BLUE. PROVIDE ALL CIRCUITS WITH LABELING AT
THE POINT OF TERMINATION SUCH AS SLC 1, NAC 8, AND IDC 4.
9. RUN CONDUCTORS FROM DEVICE TO DEVICE WITHOUT SPLICES. WIRE
NUTS ARE PROHIBITED. UTILIZE TERMINAL STRIPS WHERE CONDUCTORS
CANNOT BE DIRECTLY TERMINATED AT THE DEVICE SUCH AS PIGTAILS OFF
A HEAT DETECTOR.
10. DO NOT USE FIRE ALARM EQUIPMENT PANELS AS RACEWAY FOR ROUTING
POWER WIRING OR LOW VOLTAGE WIRING. ONLY ROUTE WIRING
TERMINATING WITHIN THE PANEL INTO THE PANEL. PROVIDE 1/4 INCH
SEPARATION BETWEEN POWER-LIMITED FIRE ALARM CIRCUITS AND POWER
CIRCUITS.
11. MOUNTING DEVICES IN THE FACU, INCLUDING ANY SUBPANELS SUCH AS
FAC. WHICH ARE NOT UL LISTED OR FM APPROVED AS PART OF THE UNIT IS
PROHIBITED.
12. PROVIDE SURGE SUPPRESSORS TO PROTECT ALL POWER SUPPLY
CIRCUITS TO THE FACU INCLUDING ANY SUBPANELS SUCH AS NAC, AND
FAC. DEVICES AND APPLIANCES MOUNTED DIRECTLY ON THE EXTERIOR OF
THE BUILDING SUCH AS WALL MOUNTED EXTERIOR SPEAKER DO NOT
REQUIRE SUPPRESSORS WHEN LIGHTNING PROTECTION IS PROVIDED.
MOUNT SURGE SUPPRESSORS IN A SEPARATE ENCLOSURE, UNLESS IT IS
UL LISTED OR FM APPROVED INSTALLED IN THE CONTROL UNIT BY THE
FACTORY.
13. INSTALL FIRE ALARM BATTERIES IN THE ENCLOSURE OF THE DEVICE/UNIT
IT SUPPORTS SUCH AS FACU ENCLOSURE OR IN AN INDEPENDENT
DEDICATED ENCLOSURE.
FATC
FIRE ALARM TERMINAL CABINET
FIRE ALARM CONTROL PANEL (FACU) FUNCTIONAL MATRIX
ANNUNCIATION
AT LOCAL PANEL
NOTIFICATION AUXILIARY
FUNCTION
A U
D I O
V
I S
U A
L
F
I R
E
A
L A
R M
I N
D I C
A T
I O
N
B
Y
Z
O N
E
A U
D I O
V
I S
U A
L
T
R O
U B
L E
I N
D I C
A T
I O
N
B
Y
Z
O N
E
A U
D I O
V
I S
U A
L
S
U P
E R
V I S
O R
Y
I N
D I C
A T
I O
N
B
Y
Z
O N
E
F I R
E
A
L A
R
I G
N A
L
T
O
F
I R
E
D E
P A
R T
M E
N
O
A N
U A
L
F I R
E
A
L A
P
U L L
S
T A
T I O
N S
C O
M M
O
U B
L E
G
N A
L
R
E
D
E P
A R
T M
E N
T
C O
M M
P
E R
V I S
O R
Y
S I G
N A
L
T
O
F
I R
E
D
E P
A R
T M
E N
T
S H
U T
D
O W
N
S
I G
N A
L
T
O
E
P D
S
ALARM CONDITIONS
MANUAL FIRE ALARM STATIONS
SMOKE DETECTOR OVER FACP AND FAC PANELS
HEAT DETECTION IN CONTROL ROOM
AC POWER FAILURE
LOW BATTERY
OPEN CIRCUIT FAULT
GROUND FAULT
NOTIFICATION APPLIANCE CIRCUIT SHORT
TROUBLE CONDITIONS
COMPONENT COMMON TROUBLE
SUPERVISORY CONDITIONS
COMPONENT COMMON SUPERVISORY
X
X X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
F I R
E
A
L A
V
S
U A
L
N O
T I F
I C
A T
I O
N
F I R
E
A
L A
D
I B
L E
N O
T I F
I C
A T
I O
N
X
X
X
X
X
X
EPDS
XP = EXPLOSION PROOF
/XP
XP
XP
HEAT DETECTION IN FUEL PUMP AREA
XX X
XP
X
F I R
E
A
L A
G
N A
L
T
O
F
I R
E
D E
P A
R T
M E
O
K E
D E
T E
C T
O R
S
F I R
E
A
L A
G
N A
L
T
O
F
I R
E
D E
P A
R T
M E
A
T
D E
T E
C T
O R
S
X
X
X
HEAT DETECTION DESIGN CRITERIA
1. PROVIDE HEAT DETECTION DEVICES AS REQUIRED TO ACHIEVE
THE COVERAGE INDICATED IN THESE CONTRACT DOCUMENTS.
2. PROVIDE A QUANTITY OF HEAT DETECTORS IN EACH ROOM/AREA
AS NEEDED TO ACHIEVE THE SPACING REQUIREMENTS IN
ACCORDANCE WITH THE MANUFACTURER'S LISTED SPACING AND
NFPA 72..
3. PROVIDE ADDRESSABLE, FIXED TEMPERATURE, SPOT TYPE HEAT
DETECTORS RATED FOR ORDINARY TEMPERATURE
CLASSIFICATION IN ROOMS 102, 103, 104, AND 105.
4. PROVIDE RATE COMPENSATING, SPOT TYPE HEAT DETECTORS
RATED FOR CLASS I, DIV 2 ENVIRONMENTS AND 275°F IN ROOM
101.
5. CIRCUIT HEAT DETECTORS IN ROOM 101 AS A COMMON ZONE.
AutoCAD SHX Text
DATE
AutoCAD SHX Text
REV.
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
INIT
AutoCAD SHX Text
REVISIONS
AutoCAD SHX Text 10/13/17
AutoCAD SHX Text
B-3 FINAL SUBMITTAL
AutoCAD SHX Text
CONTROL
ROOM
MECH ROOM
MEN'S/WOMEN'S
TOILET
STORAGE
P
S
FACU
XP
XP
FAC FATC
F
F
F
F
F
F
S c a l e o r
M i c r o f i l m i n g
I n c h e s
M i l l i m e t e r s date detailed checkeddesigned ofsheet sheets project contract rev.drawing file
NORTH CAROLINA AIR NATIONAL GUARD
DOUGLAS INTERNATIONAL AIRPORT
CHARLOTTE, NORTH CAROLINA
KANSAS CITY, MISSOURI
ENGINEERS ARCHITECTS & CONSULTANTS
Project No. - FJRP159073
C-17 TYPE III HYDRANT
REFUELING SYSTEM/
RAMP EXPANSION
94893
C O
P Y
R I G
B U
R N
D
O N
N E
L L
E
N G
I N
E E
R I N
G
C
O M
P A
N Y
I N
C
D
2 3
C
4 5
A
B
FA101
94893_FA-101.DWG
PUMP SHELTER FIRE ALARM PLAN,
TYPICAL MOUNTING DETAIL, AND FIRE
ALARM RISER DIAGRAM
Z. ATAIYAN
10/4/17 A. EVENSON
A. SCHOENECKER
B1
PUMP SHELTER FIRE ALARM PLAN
SCALE: 3/16" = 1'-0"
8'0 4' 16'
PUMP ROOM
N
1. REFER TO FA001 FOR GENERAL NOTES, DESIGN
CRITERIA, ABBREVIATIONS AND SYMBOLS.
2. WALL MOUNTED NOTIFICATION DEVICES ARE
PERMITTED IN UNFINISHED AREAS WITH CONGESTED
CEILINGS SUCH AS THE MECHANICAL ROOM.
3. THE FIRE ALARM RISER SHOWS THE INTENT OF THE
FIRE ALARM INFRASTRUCTURE. NOT ALL DEVICES
ARE SHOWN. CONTRACTOR SHALL PROVIDE THE
QUANTITY OF DEVICES AS REQUIRED TO COMPLY
WITH NFPA 72, UFC 3-600-01, ANG ETL 15-01-03, AND
CONTRACT DOCUMENTS.
NOTES:
PROVIDE CEILING MOUNTED HORNS & STROBES AND
CEILING MOUNTED HEAT DETECTORS AS REQUIRED TO
ACHIEVE DESIGN CRITERIA.
PROVIDE CEILING MOUNTED HORNS AND CEILING
MOUNTED HEAT DETECTORS AS REQUIRED TO ACHIEVE
DESIGN CRITERIA.
FIRE ALARM HATCH LEGEND
5 FT (MIN)
12 INCHES
(MAX)
FOR CEILING HEIGHTS LESS
THAN 96 INCHES THE VISIBLE
LENS MOUNTING HEIGHT
SHALL BE WITHIN 6 INCHES
OF THE CEILING
TO EXIT DOOR
5 FT (MAX)
I N
C H
E S
M A
X
SYNCHRONIZE TWO
OR MORE
APPLIANCES IN ANY
FIELD OF VIEW
I N
C H
E S
HEAT DETECTORS
NEVER HERE
CEILING MOUNTED
SMOKE & HEAT
DETECTOR
SUPPLY OR RETURN
DIFFUSER
CEILING
FINISHED FLOOR
WALL
MOUNTED
VISIBLE
APPLIANCE
MINIMUM 12 INCHES
FROM LIGHT SWITCH
(TYPICAL FOR FOAM
APPLIANCES)
PULL STATIONS
SHALL NOT BE
LOCATED BEHIND
DOOR SWINGS.
BATT
FACU
ROUTE CONDUIT TO ACHIEVE
SEPARATION OF POWER-LIMITED
FIRE ALARM CIRCUITS AND
POWER CIRCUITS
I N
S T
A L L
N
O
G
R E
A T
E R
T H
I N
C H
F
FAC
F
SS
CEILING MOUNTED AUDIBLE
AND VISIBLE APPLIANCE
AUDIBLE
ONLY WALL
MOUNTED
APPLIANCE
4 INCHES
(MIN)
A1
TYPICAL MOUNTING DETAIL
SCALE: NTS
FACU
FAC
KEYED NOTES:
F
AOM
F
BATT SS
SS
MOUNT RADIO TRANSCEIVER ANTENNA PER
MANUFACTURERS RECOMMENDATION. PROVIDE #6
BARE COPPER TO 3/4" X 10'-0" COPPER CLAD GROUND
ROD AND TO BUILDING COUNTERPOISE, AND LIGHTNING
ARRESTOR KIT.
LOCK, LABEL "FIRE ALARM", AND PAINT CIRCUIT
BREAKER RED.
QUANTITY AND LOCATION BY CONTRACTOR'S DESIGN
TO MEET DESIGN CRITERIA.
REFER TO FIRE ALARM PLANS FOR QUANTITY AND / OR
LOCATIONS OF DEVICE(S).
PROVIDE ADDRESSABLE INPUT AND/OR OUTPUT
MODULE(S) AS REQUIRED TO ACHIEVE THE
FUNCTIONALITY INDICATED IN THE FIRE ALARM MATRIX.
LOCATE MODULE IN NORMALLY FACU OR FATC.
CONNECTION TO EPDS BY OTHERS. LOCATE AOM NEAR
EPDS SYSTEM.
IF AOM AND AIM CANNOT BE LOCATED WITHIN THE
FACU, PROVIDE A FATC ADJACENT TO THE FACU FOR
MOUNTING AIM AND AOM.
NOTIFICATION APPLIANCE CIRCUIT (CLASS B)
SIGNALING LINE CIRCUIT (CLASS B)
BATT
CIRCUIT LEGEND:
P
S
120 VAC
3 4 4
F
XP
XP
F
3 3
C3
FIRE ALARM RISER DIAGRAM
SCALE: NTS
EPDS
AOM
VAC
LOCATE ANTENNA TO MAXIMIZE
RADIO SIGNAL TRANSMISSION/
RECEPTION AND TO OPTIMIZE
MAINTAINABILITY
FIRE ALARM
ANTENNA
ROOF
TO FTR
STRAP CONDUIT WITHIN 36
INCHES OF FITTINGS AND 120
INCHES O.C. WITH STAINLESS
STEEL FASTENERS INTO WALL
MOUNT ANTENNA TO WITH
STAND 100 MPH WIND VELOCITY
BUILDING EXTERIOR
WALL
LIGHTNING ARRESTER WITH
ENCLOSURE PIPE PENETRATION
TO GROUNDING WIRE
I N
C H
E S
A4
MONACO ANTENNA MOUNTING DETAIL
SCALE: NTS
AIM
F
XP
AIM
XP
PROVIDE EXPLOSION PROOF WALL MOUNTED HORNS,
STROBES, AND CEILING MOUNTED EXPLOSION PROOF HEAT
DETECTORS AS REQUIRED TO ACHIEVE DESIGN CRITERIA.
NO FIRE ALARM
ROOF LINE
BATT
FA101
A4
5 65
AutoCAD SHX Text
DATE
AutoCAD SHX Text
REV.
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
INIT
AutoCAD SHX Text
REVISIONS
AutoCAD SHX Text 10/13/17
AutoCAD SHX Text
B-3 FINAL SUBMITTAL
AutoCAD SHX Text
| 94893_FA001_12.5.17 |
| 94893_FA101_12.5.17 |
| 2017-12-05T14:53:54-0600 | |
| Schoenecker, Anthon |
| 2017-12-05T14:53:58-0600 | |
| Schoenecker, Anthon |
File details come from the government source that posted it.