C P
CP
A
2 3 4
B
C
D
CONTROL ROOM
MEN'S/WOMEN'S
TOILET
MECH ROOM
STORAGE
PUMP ROOM
25'CP:8'
33.5" 32"
68.0" 32"
33.5" 32"
68.0" 32"
OCCUPANCY TYPES
BUSINESS
STORAGE USE IN OTHER THAN
STORAGE AND MERCANTILE
FE:BR
FE:BR
FE:SR
EXTENT OF ROOF
OVERHANG
2A:10B:C
FE:BR
4A:40B:C
2A:10B:C
FE:BR
4A:40B:C
31'CP:0'
C P
:0
3 HR FIRE BARRIER
CLEAR WIDTH
EXIT CAPACITY
OCCUPANTS SERVED
COMMON PATH
OF TRAVEL
TRAVEL
DISTANCE
EGRESS
PATH
COMMON PATH
TERMINATION
POINT
EXIT DOOR /
POINT OF EXIT AT
UNENCLOSED AREAS
REQUIRED WIDTH
36"
22"
GENERAL NOTES: THIS DRAWING ONLY
REFER TO ARCHITECTURAL LEGEND FOR ADDITIONAL INFORMATION
REGARDING SYMBOLS AND ABBREVIATIONS.
REFER TO THE ELECTRICAL LIGHTING PLANS FOR LOCATION OF EXIT
SIGNS AND EMERGENCY LIGHTING.
FINAL LOCATIONS OF FIRE EXTINGUISHERS SHALL BE APPROVED BY
THE AHJ PRIOR TO INSTALLATION.
DOOR EGRESS TAG
FIRE AND SMOKE RESISTIVE CONSTRUCTION
EGRESS PATH
100'CP:75'
1.
2.
3.
A:B:C: TYPE DRY CHEMICAL
(SEE PLAN FOR MINIMUM RATINGS)
CLEAN AGENT
2A:C
PORTABLE FIRE EXTINGUISHERS
FE:SR
EXTINGUISHER TYPE
EXTINGUISHER
MOUNTING
-FE: FIRE EXTINGUISHER
-SR: SEMI-RECESSED CABINET
-BR: BRACKET MOUNTED
FIRE EXTINGUISHER
RATING
2A:B:C date detailed checkeddesigned ofsheet sheets project contract rev.drawing file
DESCRIPTION
1 5432
A
B
C
D
C O
P Y
R
IG
H T
B
U R
N S
M
C D
O N
N E
L L E
N G
IN
E
E R
IN
G
C O
M P
A N
Y
IN
C
C-17 TYPE III HYDRANT
REFUELING SYSTEM/
RAMP EXPANSION
KANSAS CITY, MISSOURI
INITDATEREV.
REVISIONS
ENGINEERS ARCHITECTS & CONSULTANTS
NORTH CAROLINA AIR NATIONAL GUARD
DOUGLAS INTERNATIONAL AIRPORT
CHARLOTTE, NORTH CAROLINA
Project No. - FJRP159073
/6
/2
:0
:3
A
M
FJRP159073-G-101.dwg
G-101
94893
LIFE SAFETY PLAN & CODE SUMMARY
OCTOBER 2017
L. SUNDERLAND E. VELAZQUEZ
A. CANTORIA
SCALE: 1/8" = 1'-0"C2
LIFE SAFETY PLAN
SCALE IN FEET
0 4' 8' 16'
N
1. APPLICABLE CODES AND STANDARDS
ABBREVIATIONS TITLE EDITION
IBC INTERNATIONAL BUILDING CODE 2015
ABA ACCESSBILITY STANDARDS FOR DEPARTMENT OF DEFENSE
FACILITY
IPC INTERNATIONAL PLUMBING CODE 2015
NFPA 10 STANDARD FOR PORTABLE FIRE EXTINGUISHERS 2013
NFPA 30 FLAMMABLE AND COMBUSTIBLE LIQUIDS CODE 2015
NFPA 72 FIRE ALARM AND SIGNALING CODE 2016
NFPA 101 LIFE SAFETY CODE 2015
UFC 1-200-01 DOD BUILDING CODE (GENERAL BUILDING REQUIREMENTS) 20 JUNE 2016
UFC 3-600-01 FIRE PROTECTION ENGINEERING FOR FACILITIES CHANGE 1, 28 NOV 2016
UFC 3-460-01 DESIGN: PETROLEUM FUEL FACILITIES CHANGE 2, 17 JUN 2015
ANGETL 15-01-03 FIRE PROTECTION DESIGN GUIDANCE 1 MAY 2015
UFC 3-101-01 ARCHITECTURE CHANGE 3, 20 JUNE 2016
UFC 3-420-01 PLUMBING SYSTEMS CHANGE 10, 25 OCT 2004
2. TYPE OF CONSTRUCTION (IBC 602, TABLE 601)
BUILDING ELEMENT
TYPE OF
CONSTRUCTION
FIRE RESISTANCE
RATING
PRIMARY STRUCTURAL FRAME IIB 0 HR
BEARING EXTERIOR WALL IIB 0 HR
BEARING INTERIOR WALL IIB 0 HR
NON-BEARING EXTERIOR WALL IIB 0 HR
NON-BEARING INTERIOR WALL IIB 0 HR *
FLOOR CONSTRUCTION INCLUDING SUPPORTING BEAMS AND JOISTS IIB 0 HR
ROOF CONSTRUCTION INCLUDING SUPPORTING BEAMS AND JOISTS IIB 0 HR
3. CLASSIFICATION OF OCCUPANCY
AREAS OCCUPANCY (IBC / NFPA 101) IBC NFPA 101
CONTROL ROOM, RESTROOM, STORAGE, MECH BUSINESS GROUP B / BUSINESS 304.1 6.1.11
COMBUSTIBLE LIQUID STORAGE (>15 psi) HIGH-HAZARD GROUP H-2 / STORAGE
HIGH HAZARD
307.4 6.1.13
9. OPENING PROTECTION FOR FIRE AND SMOKE RESISTIVE CONSTRUCTION
COMPONENT
FIRE DOOR /
SHUTTER
ASSEMBLIES DUCT PENETRATIONS
OTHER
PENETRATIONS IBC
3 HR FIRE BARRIER 3 HR 3 HR FIRE DAMPER 3 HR 716.5
10. OCCUPANT LOAD CALCULATIONS (NFPA 101 TABLE 7.3.1.2, UFC 3-600-01 TABLE 10-1)
AREA USE AREA (SF) SF/PERSON NET/GROSS OCCUPANTS
STORAGE, MECH
ROOM, PUMP ROOM
STORAGE - IN OTHER
OCCUPANCIES
1,518 500 GROSS 4
CONTROL ROOM,
RESTROOM
BUSINESS AREAS 518 100 GROSS 6
11. OCCUPANT LOAD SUMMARY AND MINIMUM EXITS FROM FLOOR (NFPA 101)
GROSS AREA (SF) OCCUPANTS
REQUIRED EXITS
(7.4.1.1)
REQUIRED EXIT SEPARATION
(7.5.1.3.3)
2,036 10 2 1/2 DIAGONAL
12. MINIMUM EXITS OR EXIT ACCESSES FROM A SPACE OR AREA (NFPA 101)
OCCUPANCY CONDITION PERMITTING ONE EXIT
CONDITION REQUIRING TWO
EXITS
NFPA 101
SECTION
BUSINESS * 100 PERSONS OR LESS;
COMMON PATH LESS THAN 100'
GREATER THAN 100 PERSONS;
COMMON PATH 100' OR GREATER
38.2.4.3
STORAGE - HIGH
HAZARD
N/A ALL CONDITIONS 42.2.4.1
13. COMMON PATH, DEAD-END, AND TRAVEL DISTANCE LIMITS (NFPA 101 TABLE A.7.6)
OCCUPANCY
COMMON PATH LIMIT
(FT)
DEAD END LIMIT (FT) TRAVEL DISTANCE LIMIT
(FT)
BUSINESS 75 20 200
STORAGE HIGH-HAZARD 0 0 75
14. MINIMUM EGRESS WIDTHS
COMPONENT REQUIREMENT WIDTH (IN) NFPA 101
DOORS IN EGRESS ACCESS PER COMPONENT MINIMUM 32 IN CLEAR 7.2.1.2.3.2
15. MINIMUM INTERIOR FINISH RATINGS (NFPA 101, TABLE A.10.2.2)
OCCUPANCY EXITS EXIT ACCESS CORRIDORS OTHER SPACES
BUSINESS B / II B C
STORAGE HIGH HAZARD B / II C C
17. FIRE EXTINGUISHER DISTRIBUTION (NFPA 10)
OCCUPANCY
PRIMARY CLASSIFICATION
OF FIRE AND HAZARD MINIMUM RATING
MAXIMUM FLOOR
AREA PER A (SF)
MAX TRAVEL
DISTANCE (FT)
BUSINESS CLASS A:C - ORDINARY 2-A 1,500 75
STORAGE HIGH
HAZARD
CLASS B - EXTRA 40-B 1,000 30
5. BUILDING ALLOWABLE AREA - SEPARATED (IBC 508)
OCCUPANCY
FLOOR AREA OF
SEPARATED OCCUPANCY
(SF)
RESTRICTING OCCUPANCY MODIFIED
ALLOWABLE AREA (SF)
RATIO SUM PER FLOOR
<1.0
B 682 23,000 0.03
H-2 1,354 7,000 0.20
TOTAL 0.23
4. MULTIPLE OCCUPANCIES (IBC 508)
OCCUPANCY SEPARATION OCCUPANCY
SEPARATION
RATING IBC
BUSINESS SEPARATED H-2 3 HR BARRIER 508.4
6. MODIFIED ALLOWABLE HEIGHT (IBC 504)
OCCUPANCY
RESTRICTING ALLOWABLE
HEIGHT (FT / STORY)
SPRINKLER INCREASE
(FT / STORY)
MODIFIED ALLOWABLE
HEIGHT (FT / STORY)
B 55 / 3 N/A 55 / 3
H-2 55 / 1 N/A 55 / 1
* EXCEPT AS REQUIRED FOR OCCUPANCY SEPARATION. 19. REQUIRED PLUMBING FIXTURES (IPC TABLE 403.1, UFC 3-420-01)
OCCUPANCY OCCUPANT LOAD WATER CLOSETS * LAVATORIES *
DRINKING
FOUNTAINS
BUSINESS / STORAGE 10 1 PER 20 = 1 1 PER 20 = 1 ** N/A
TOTAL PROVIDED 1 1 ** N/A
16. FIRE SUPPRESSION REQUIREMENTS (UFC 3-600-01 9-7, 9-10, 9-17, UFC 3-460-01 2-15.3)
SPRINKLERS STANDPIPE FIRE EXTINGUISHERS
NOT REQUIRED * NOT REQUIRED FIRE EXTINGUISHERS PROVIDED
THROUGHOUT THE BUILDING
18. FIRE ALARM PROVIDED SYSTEMS
MANUAL INITIATION AUTOMATIC INITIATION OCCUPANT NOTIFICATION
MANUAL PULL STATIONS
PROVIDED AT MAIN EXITS
FROM THE BUILDING
SPOT SMOKE DETECTORS AND
HEAT DETECTORS PROVIDED
AUDIBLE AND VISUAL
NOTIFICATION PROVIDED. VISUAL
ONLY IN COMMON AREAS
* PER UFC 3-460-01 2-15.3, PUMP SHELTERS DO NOT REQUIRE FIRE SUPPRESSION SYSTEMS.
* PER IBC 2902.2, SEPARATE FACILITIES ARE NOT REQUIRED IN
STRUCTURES WITH A TOTAL OCCUPANT LOAD OF 15 OR FEWER.
** PER IBC 2902.5, DRINKING FOUNTAINS ARE NOT REQUIRED IN
STRUCTURES WITH A TOTAL OCCUPANT LOAD OF 15 OR FEWER.
7. PROTECTION FROM HAZARDS AND OTHER PASSIVE FIRE PROTECTION
NO ADDITIONAL PROTECTION REQUIRED
* EXIT MUST EGRESS DIRECTLY TO EXTERIOR.
8. BUILDING SEPARATION (IBC TABLE 602)
OCCUPANCY ELEVATION
RESTRICTIVE FIRE
SEPARATION
DISTANCE (FT)
FIRE RESISTIVE
RATING OF
EXTERIOR WALL
B, H-2 NORTH/SOUTH/WEST/EAST > 30 NO RATING
0 10/13/17 B-3 FINAL SUBMITTAL LS
| 94893_A_acantoria |
| G-101 - LIFE SAFETY PLAN & CODE SUMMARY |
| 2017-12-06T09:10:23-0600 | |
| Schoenecker, Anthon |