"BUILDING STRONG"

DEGLANDON.TERRY.L.1246002483

Digitally signed by DEGLANDON.TERRY.L.1246002483 DN: c=US, o=U.S. Government, ou=DoD, ou=PKI, ou=USA, cn=DEGLANDON.TERRY.L.1246002483 Date: 2018.06.04 13:57:38 -04'00'

MILLER.WAYNE.K.1391889712 Digitally signed by MILLER.WAYNE.K.1391889712 DN: c=US, o=U.S. Government, ou=DoD, ou=PKI, ou=USA, cn=MILLER.WAYNE.K.1391889712 Date: 2018.06.04 14:02:38 -04'00'

Digitally signed by FROMME.CHERYL.L.1088650537 DN: c=US, o=U.S. Government, ou=DoD, ou=PKI, ou=USA, cn=FROMME.CHERYL.L.1088650537 Date: 2018.06.06 06:21:07 -05'00'

US Army Corps of Engineers ®

SHEET ID

US

A

RM

Y

CO

RP

S O

F

EN

G

IN

EE

RS

D R

A W N

B Y:

D

ES

IG

N

ED

B

Y:

SU

B M

IT

TE

D B

Y:

SI

ZE

C H

E C

KE

D B

Y:

AN

S I

'D

FI

LE

N

AM

E:

IS

SU

E D

AT

E :

FI

LE

N U

M

BE

R

1 2 3 4 5

D

C

B

A

SHEET OF

G-005

IN

D

EX

O

F D

R A W

IN

G

S

- V

O

LU

M E

AV

IA

TI

O

N M

AI

NT

EN

AN

CE

T

RA

IN

IN

G

F

AC

IL

IT

Y F O

RT

E

US

TI

S, V

A .

N O

RF

O

LK

D

I S

TR

IC

T

NO

R F

O

LK

, V A.

RT

A

SU

BM

IT

TA

L

D . G

EB

LE

R

J.

W

EH

R

LE

L.

M

U

LÉ

W . M

IL

LE

R

JU

N

E

PR

O

JE

C T

N O

C O

N

TR

AC

T

N O

G -0

648386

INDEX OF DRAWINGS

SHEET ID

SHEET

NUMBER SHEET TITLE

TELECOMMUNICATIONS

T-111 623 FIRST FLOOR PLAN - AREA A - TELECOM

T-112 624 FIRST FLOOR PLAN - AREA B - TELECOM

T-113 625 FIRST FLOOR PLAN - AREA C - TELECOM

T-114 626 FIRST FLOOR PLAN - AREA D - TELECOM

T-115 627 FIRST FLOOR PLAN - AREA E - TELECOM

T-116 628 FIRST FLOOR PLAN - AREA F - TELECOM

T-117 629 FIRST FLOOR PLAN - AREA G - TELECOM

T-121 630 SECOND FLOOR PLAN - AREA A - TELECOM

T-122 631 SECOND FLOOR PLAN - AREA B - TELECOM

T-123 632 SECOND FLOOR PLAN - AREA C - TELECOM

T-124 633 SECOND FLOOR PLAN - AREA D - TELECOM

T-125 634 SECOND FLOOR PLAN - AREA E - TELECOM

T-126 635 SECOND FLOOR PLAN - AREA F - TELECOM

T-127 636 SECOND FLOOR PLAN - AREA G - TELECOM

T-128 637 ENLARGED FLOOR PLANS

T-501 638 TELECOM DETAILS

T-502 639 TELECOM DETAILS

T-701 640 TELECOM BACKBONE CABLE RISER DIAGRAM

T-702 641 TELECOM RISER DIAGRAM - TEF ROOM 102

T-703 642 TELECOM RISER DIAGRAM - TELCOM IDF ROOM 119

T-704 643 TELECOM RISER DIAGRAM - TR ROOMS 129, 232 (TYP)

T-705 644 TELECOM RISER DIAGRAM - TR ROOM 202

T-706 645 TELECOM RISER DIAGRAM - TR ROOM 224

T-901 646 FIRST FLOOR PLAN - AREA A - TELECOM - BID OPTION 1

TS101 647 TELECOM SITE PLAN

TS501 648 TELECOM SITE DETAILS

INDEX OF DRAWINGS

SHEET ID

SHEET

NUMBER SHEET TITLE

M-620 543 AHU-1,2,3,4 POINTS SCHEDULE PART 2

M-621 544 AHU-1,2,3,4 POINTS SCHEDULE PART 3

M-622 545 CHILLED WATER CONTROL SCHEMATIC

M-623 546 CHILLED WATER SEQUENCE OF OPERATIONS

M-624 547 BOILER CONTROL SCHEMATIC

M-625 548 BOILER SEQUENCE OF OPERATIONS

M-626 549 HYDRONIC PLANTS POINTS SCHEDULES

M-627 550 FAN & BLOWER COIL UNIT CONTROL SCHEMATIC AND

SEQUENCE OF OPERATIONS

M-628 551 FAN & BLOWER COIL UNIT POINTS SCHEDULES

M-629 552 MISCELLANEOUS CONTROL SCHEMATICS AND

SEQUENCES

M-630 553 MISCELLANEOUS CONTROL POINTS SCHEDULES

M-631 554 VALVE SCHEDULE

M-632 555 DAMPER AND OCCUPANCY SCHEDULES

ELECTRICAL

E-001 556 GENERAL INFORMATION SHEET

ED101 557 ELECTRICAL SITE PLAN - DEMOLITION

ED901 558 ELECTRICAL SITE PLAN - DEMOLITION - BID OPTION 3

ED902 559 ELECTRICAL SITE PLAN - DEMOLITION - BID OPTION 3

EL111 560 FIRST FLOOR PLAN - AREA A - LIGHTING

EL112 561 FIRST FLOOR PLAN - AREA B - LIGHTING

EL113 562 FIRST FLOOR PLAN - AREA C - LIGHTING

EL114 563 FIRST FLOOR PLAN - AREA D - LIGHTING

EL115 564 FIRST FLOOR PLAN - AREA E - LIGHTING

EL116 565 FIRST FLOOR PLAN - AREA F - LIGHTING

EL117 566 FIRST FLOOR PLAN - AREA G - LIGHTING

EL121 567 SECOND FLOOR PLAN - AREA A - LIGHTING

EL122 568 SECOND FLOOR PLAN - AREA B - LIGHTING

EL123 569 SECOND FLOOR PLAN - AREA C - LIGHTING

EL124 570 SECOND FLOOR PLAN - AREA D - LIGHTING

EL125 571 SECOND FLOOR PLAN - AREA E - LIGHTING

EL126 572 SECOND FLOOR PLAN - AREA F - LIGHTING

EL127 573 SECOND FLOOR PLAN - AREA G - LIGHTING

EL501 574 LIGHTING DETAILS

EL502 575 LIGHTING DETAILS

EL503 576 LIGHTING DETAILS

EL901 577 FIRST FLOOR PLAN - LIGHTING - BID OPTION 1

EL902 578 PARKING - LIGHTING - BID OPTION 2

EL903 579 WALKWAY - LIGHTING - BID OPTION 2

EL904 580 FIRST FLOOR PLAN - AREA G - LIGHTING - BID OPTION 4

EP111 581 FIRST FLOOR PLAN - AREA A - POWER

EP112 582 FIRST FLOOR PLAN - AREA B - POWER

EP113 583 FIRST FLOOR PLAN - AREA C - POWER

EP114 584 FIRST FLOOR PLAN - AREA D - POWER

EP115 585 FIRST FLOOR PLAN - AREA E - POWER

EP116 586 FIRST FLOOR PLAN - AREA F - POWER

EP117 587 FIRST FLOOR PLAN - AREA G - POWER

EP118 588 FIRST FLOOR PLAN - STATIC GROUNDING

EP121 589 SECOND FLOOR PLAN - AREA A - POWER

EP122 590 SECOND FLOOR PLAN - AREA B - POWER

EP123 591 SECOND FLOOR PLAN - AREA C - POWER

EP124 592 SECOND FLOOR PLAN - AREA D - POWER

EP125 593 SECOND FLOOR PLAN - AREA E - POWER

EP126 594 SECOND FLOOR PLAN - AREA F - POWER

EP127 595 SECOND FLOOR PLAN - AREA G - POWER

EP131 596 ROOF PLAN - AREA A - POWER

EP132 597 ROOF PLAN - AREA B - POWER

EP133 598 ROOF PLAN - AREA C - POWER

EP134 599 ROOF PLAN - AREA D - POWER

EP135 600 ROOF PLAN - AREA E - POWER

EP136 601 ROOF PLAN - AREA F - POWER

EP401 602 ENLARGED FLOOR PLANS

EP402 603 SPECIAL PURPOSE RECEPTACLES SECTION DETAILS

EP501 604 ELECTRICAL DETAILS

EP601 605 PANELBOARD SCHEDULES

EP602 606 PANELBOARD SCHEDULES

EP603 607 PANELBOARD SCHEDULES

EP604 608 PANELBOARD SCHEDULES

EP605 609 PANELBOARD SCHEDULES

EP606 610 PANELBOARD SCHEDULES

EP607 611 PANELBOARD SCHEDULES

EP608 612 PANELBOARD SCHEDULES

EP609 613 PANELBOARD SCHEDULES

EP610 614 PANELBOARD SCHEDULES

EP611 615 PANELBOARD SCHEDULES

EP612 616 PANELBOARD SCHEDULES

EP613 617 EQUIPMENT CONNECTION SCHEDULE

EP701 618 POWER RISER DIAGRAM

EP901 619 FIRST FLOOR PLAN - AREA A - POWER - BID OPTION 1

EP902 620 PANELBOARD SCHEDULES - BID OPTION 1

EP903 621 FIRST FLOOR PLAN - AREA G - POWER - BID OPTION 4

ES101 622 ELECTRICAL SITE PLAN

INDEX OF DRAWINGS

SHEET ID

SHEET

NUMBER SHEET TITLE

P-609 465 SANITARY RISER DIAGRAM ELEVATOR

P-610 466 SANITARY RISER DIAGRAM BREAKROOM

P-611 467 SANITARY RISER DIAGRAM WEST

P-612 468 NATURAL GAS RISER BREAKROOM

P-613 469 NATURAL GAS RISER WEST

P-614 470 NATURAL GAS RISER MECH ROOM

P-615 471 NATURAL GAS RISER EAST

P-616 472 PLUMBING SCHEDULES

P-901 473 FIRST FLOOR PLUMBING PLAN - BID OPTION 1

P-902 474 FIRST FLOOR SANITARY PLAN - BID OPTION 1

P-903 475 FIRST FLOOR GAS PLAN - BID OPTION 1

P-904 476 DOMESTIC RISER DIAGRAM - BID OPTION 1

P-905 477 SANITARY RISER DIAGRAM - BID OPTION 1

P-906 478 NATURAL GAS RISER - BID OPTION 1

P-907 479 FIRST FLOOR PLUMBING PLAN - BID OPTION 4

P-908 480 DOMESTIC RISER DIAGRAM - BID OPTION 4

MECHANICAL

M-001 481 GENERAL INFORMATION SHEET

M-002 482 GENERAL INFORMATION SHEET

M-003 483 GENERAL INFORMATION SHEET

MH111 484 FIRST FLOOR HVAC PLAN - AREA A

MH112 485 FIRST FLOOR HVAC PLAN - AREA B

MH113 486 FIRST FLOOR HVAC PLAN - AREA C

MH114 487 FIRST FLOOR HVAC PLAN & SECTION- AREA G

MH121 488 SECOND FLOOR HVAC PLAN - AREA A

MH122 489 SECOND FLOOR HVAC PLAN - AREA B

MH123 490 SECOND FLOOR HVAC PLAN - AREA C

MH131 491 ROOF HVAC PLAN - AREA A

MH132 492 ROOF HVAC PLAN - AREA B

MH133 493 ROOF HVAC PLAN - AREA C

MH134 494 HIGH BAY HVAC PLAN - AREA D

MH135 495 HIGH BAY HVAC PLAN - AREA E

MH136 496 HIGH BAY HVAC PLAN - AREA F

MH901 497 FIRST FLOOR HVAC PLAN - AREA A - BID OPTION 1

MH902 498 ROOF HVAC PLAN - AREA A - BID OPTION 1

MH903 499 FIRST FLOOR HVAC PLAN - AREA G BID OPTION 4

MP111 500 FIRST FLOOR PIPING PLAN - AREA A

MP112 501 FIRST FLOOR PIPING PLAN - AREA B

MP113 502 FIRST FLOOR PIPING PLAN - AREA C

MP121 503 SECOND FLOOR PIPING PLAN - AREA A

MP122 504 SECOND FLOOR PIPING PLAN - AREA B

MP123 505 SECOND FLOOR PIPING PLAN - AREA C

MP131 506 ROOF PIPING PLAN - AREA A

MP132 507 ROOF PIPING PLAN - AREA B

MP133 508 ROOF PIPING PLAN - AREA C

MP901 509 SECOND FLOOR PIPING PLAN - AREA C - BID OPTION 4

MP902 510 FIRST FLOOR PIPING PLAN AREA G - BID OPTION 4

MP903 511 HYDRONIC RISER DIAGRAM - PART A - BID OPTION 4

MP904 512 HYDRONIC RISER DIAGRAM - PART B OPTION 1

M-301 513 HVAC SECTIONS

M-302 514 HVAC SECTIONS

M-303 515 HVAC SECTIONS

M-401 516 ENLARGED HVAC PLANS

M-402 517 ENLARGED HVAC PLANS

M-403 518 ENLARGED HVAC PLANS

M-501 519 HVAC DETAILS

M-502 520 HVAC DETAILS

M-503 521 HVAC DETAILS

M-504 522 HVAC DETAILS

M-505 523 HVAC DETAILS

M-601 524 HVAC SCHEDULES

M-602 525 HVAC SCHEDULES

M-603 526 HVAC SCHEDULES

M-604 527 HYDRONIC RISER DIAGRAM - PART A

M-605 528 HYDRONIC RISER DIAGRAM - PART B

M-606 529 HEATING AND COOLING PLANT ISOMETRICS

M-607 530 POINTS SCHEDULES INSTRUCTIONS

M-608 531 SYSTEM SCHEDULER INSTRUCTIONS

M-609 532 DEDICATED OUTDOOR AIR SYSTEM CONTROL

SCHEMATIC

M-610 533 DEDICATED OUTDOOR AIR SYSTEM CONTROL

SCHEMATIC - PART 2

M-611 534 DEDICATED OUTDOOR AIR SYSTEM CONTROL

SEQUENCE OF OPERATIONS

M-612 535 DEDICATED OUTDOOR AIR SYSTEM POINTS SCHEDULE

M-613 536 DEDICATED OUTDOOR AIR SYSTEM POINTS SCHEDULE -

PART 2

M-614 537 ACTIVE CHILLED BEAM CONTROLS

M-615 538 HUMIDIFIER CONTROLS

M-616 539 AHU-1,2,3,4 CONTROL SCHEMATIC - PART 1

M-617 540 AHU-1,2,3,4 CONTROL SCHEMATIC - PART 2

M-618 541 AHU-1,2,3,4 SEQUENCE OF OPERATIONS

M-619 542 AHU-1,2,3,4 POINTS SCHEDULE PART 1

INDEX OF DRAWINGS

SHEET ID

SHEET

NUMBER SHEET TITLE

GENERAL

G-004 385 COVER SHEET - VOLUME 2

G-005 386 INDEX OF DRAWINGS - VOLUME 2

FIRE PROTECTION

LS001 387 CODE ANALYSIS

LS002 388 LIFE SAFETY SITE PLAN

LS111 389 OVERALL FIRST FLOOR LIFE SAFETY PLAN

LS112 390 OVERALL SECOND FLOOR LIFE SAFETY PLAN

SP001 391 LEGEND, NOTES AND ABBREVIATIONS

SP002 392 SITE PLAN

SP111 393 FIRST FLOOR PLAN - AREA A

SP112 394 FIRST FLOOR PLAN - AREA B

SP113 395 FIRST FLOOR PLAN - AREA C

SP114 396 FIRST FLOOR PLAN - AREA D

SP115 397 FIRST FLOOR PLAN - AREA E

SP116 398 FIRST FLOOR PLAN - AREA F

SP117 399 FIRST FLOOR PLAN - AREA G

SP121 400 SECOND FLOOR PLAN - AREA A

SP122 401 SECOND FLOOR PLAN - AREA B

SP123 402 SECOND FLOOR PLAN - AREA C

SP124 403 SECOND FLOOR PLAN - AREA D

SP125 404 SECOND FLOOR PLAN - AREA E

SP126 405 SECOND FLOOR PLAN - AREA F

SP401 406 ENLARGED FIRE PUMP ROOM

SP501 407 SPRINKLER ISOMETRIC DIAGRAM

SP901 408 FIRST FLOOR PLAN - BID OPTION

SP902 409 FIRST FLOOR PLAN - AREA G - BID OPTION

FA001 410 LEGEND, NOTES AND ABBREVIATIONS

FA111 411 FIRST FLOOR PLAN - AREA A

FA112 412 FIRST FLOOR PLAN - AREA B

FA113 413 FIRST FLOOR PLAN - AREA C

FA114 414 FIRST FLOOR PLAN - AREA D

FA115 415 FIRST FLOOR PLAN - AREA E

FA116 416 FIRST FLOOR PLAN - AREA F

FA117 417 FIRST FLOOR PLAN - AREA G

FA121 418 SECOND FLOOR PLAN - AREA A

FA122 419 SECOND FLOOR PLAN - AREA B

FA123 420 SECOND FLOOR PLAN - AREA C

FA124 421 SECOND FLOOR PLAN - AREA D

FA125 422 SECOND FLOOR PLAN - AREA E

FA126 423 SECOND FLOOR PLAN - AREA F

FA501 424 DETAILS

FA601 425 RISER DIAGRAM

FA901 426 FIRST FLOOR PLAN - AREA A - BID OPTION

FA902 427 FIRST FLOOR PLAN - AREA G - BID OPTION

PLUMBING

P-001 428 GENERAL INFORMATION SHEET

P-110 429 FIRST FLOOR PLUMBING PLAN - AREA A

P-111 430 FIRST FLOOR PLUMBING PLAN - AREA B

P-112 431 FIRST FLOOR PLUMBING PLAN - AREA C

P-113 432 FIRST FLOOR PLUMBING PLAN - AREA D

P-114 433 FIRST FLOOR PLUMBING PLAN - AREA E

P-115 434 FIRST FLOOR PLUMBING PLAN - AREA F

P-116 435 FIRST FLOOR PLUMBING PLAN - AREA G

P-117 436 FIRST FLOOR SANITARY PLAN - AREA A

P-118 437 FIRST FLOOR SANITARY PLAN - AREA B

P-119 438 FIRST FLOOR SANITARY PLAN - AREA C

P-120 439 FIRST FLOOR GAS PLAN - AREA A

P-121 440 FIRST FLOOR GAS PLAN - AREA B

P-122 441 FIRST FLOOR GAS PLAN - AREA C

P-123 442 SECOND FLOOR PLUMBING PLAN - AREA A

P-124 443 SECOND FLOOR PLUMBING PLAN - AREA B

P-125 444 SECOND FLOOR PLUMBING PLAN - AREA C

P-126 445 SECOND FLOOR SANITARY PLAN - AREA A

P-127 446 SECOND FLOOR SANITARY PLAN - AREA B

P-128 447 SECOND FLOOR SANITARY PLAN - AREA C

P-129 448 SECOND FLOOR GAS PLAN - AREA A

P-130 449 SECOND FLOOR GAS PLAN - AREA C

P-131 450 ROOF PLAN - AREA A

P-132 451 ROOF PLAN - AREA B

P-133 452 ROOF PLAN - AREA C

P-501 453 PLUMBING DETAILS

P-502 454 PLUMBING DETAILS

P-503 455 PLUMBING DETAILS

P-504 456 PLUMBING DETAILS

P-601 457 DOMESTIC RISER DIAGRAM EAST

P-602 458 DOMESTIC RISER DIAGRAM WEST

P-603 459 DOMESTIC RISER DIAGRAM BREAKROOM

P-604 460 DOMESTIC RISER DIAGRAM MECH ROOM

P-605 461 DOMESTIC RISER DIAGRAM NORTH AMIB

P-606 462 DOMESTIC RISER DIAGRAM GSE

P-607 463 SANITARY RISER DIAGRAM EAST

P-608 464 SANITARY RISER DIAGRAM MECH ROOM

M

AR

K D

ES

C

R

IP

TI

O

N D

AT

E

GENERAL OCCUPANCY EGRESS

BUSINESS OCCUPANCY

ASSEMBLY OCCUPANCY

STORAGE OCCUPANCY

2 2

BUILDING DESCRIPTION

FIRE RESISTANCE RATINGS

OCCUPANCY CLASSIFICATION

FLOOR LEVEL OCCUPANCY PER IBCOCCUPANCY PER NFPA 101

MEANS OF EGRESS

REQUIRED CODE REFERENCEPROVIDED

FIRE PROTECTION ( CHAPTER 9)

REQUIRED

FIRE SPRINKLER SYSTEM

MASS NOTIFICATION

FIRE ALARM

MANUAL FIRE EXTINGUISHERS

PROVIDED

ALLOWABLE HEIGHT AND AREA

SMOKE CONTROL

(CHAPTER 7, GENERAL)

OCCUPANT LOAD & EGRESS CAPACITY

CALCULATED

OCCUPANCY (PERSONS)

OCCUPANCY FACTOR

(TABLE 7.3.1.2)

FLOOR AREA FOR

EACH TYPE (SQFT)

OCCUPANT TYPES

PRESENT

TOTAL FLOOR

AREA (GROSS)FLOOR

INTERIOR FINISH

FIRE AND SMOKE RATED CONSTRUCTION

- ALLOWABLE CONSTRUCTION TYPE

- BUILDING HEIGHT

- BUILDING AREA

- BUILDING SEPARATION DISTANCE

- OCCUPANCY SEPERATION

- FIRE/SMOKE RESISTANCE RATING OF

INTERIOR NON-LOAD BEARING PARTITIONS

- MEANS OF EGRESS

- INTERIOR FINISH

- VERTICAL OPENINGS

IBC

INTERNATIONAL BUILDING CODE

NFPA 101

LIFE SAFETY CODE

UFC 3-600-01

FIRE PROTECTION ENGINEERING

FOR FACILITIES

UFC 1-200-01

DoD BUILDING CODE

(GENERAL BUILDING REQUIREMENTS)

CARBON MONOXIDE DETECTION

REFERENCE CODES & STANDARDS

CODE NUMBER CODE TITLE / LATEST VERSION

BUILDING ELEMENT OR AREA

STRUCTURAL FRAME

EXTERIOR WALLS - NON BEARING

INTERIOR WALLS - BEARING

RATING ( HOURS)

REQUIRED PROVIDED

INTERIOR WALLS - NON BEARING

SECOND FLOOR CONSTRUCTION

ROOF CONSTRUCTION

CODE REFERENCE

MIN. NUMBER OF EXITS

MIN. WIDTH OF EXIT DOORS

MAX. COMMON PATH OF TRAVEL

MAX. DEAD END

MAX. TRAVEL DISTANCE

ILLUMINATION

EMERGENCY LIGHTING

EXIT LIGHTS

STAIR WIDTH

STAIR MAX. RISER

STAIR MIN. TREAD

MIN. HEADROOM

MAX. HEIGHT BETWEEN LANDINGS

CODE REFERENCEYES

YES

YES

2 5

36 IN.

75 FT 34 FT

20 FT N/A

250 FT 226

12 FT. 8 FT.

6'-8" 7'-3"

44 IN.

7 IN.

11 IN.

51 IN.

6-7/8 IN.

11 IN.

HEIGHT (PER IBC TABLE 504.3) AREA (PER IBC TABLE 506.2)

YES NFPA 13 AND UFC - 3-600-01YES

0 IBC TABLE 601, 602

IBC TABLE 601

NO NO UFC - 3-600-01 SECTION 9-17, PARA 9-17.1

YES

YES

YES

YES UFC - 4-021-01

UFC - 3-600-01 PARAGRAPH 9-18

NO NO

IBC TABLE 601, 602

IBC TABLE 601

IBC TABLE 601

IBC TABLE 601

(CHAPTER 5)

TABLE 7.2.2.2.1.2 (B)

TABLE 7.2.2.2.1.2 (A)

TABLE 7.2.2.2.1.2 (A)

TABLE 7.2.2.2.1.2 (A)

TABLE 7.2.2.2.1.2 (A)

MIN. NUMBER OF EXITS 1 1 TABLE 42.2.4.2(1)

MAX. COMMON PATH OF TRAVEL

MAX. DEAD END

MAX. TRAVEL DISTANCE

NOT LIMITED N/A

NOT LIMITED N/A

NOT LIMITED N/A

TABLE 42.2.5

TABLE 42.2.5

TABLE 42.2.6

12.2.5.1.2 12.2.5.1.3

12.2.6.2 (1)

MIN. NUMBER OF EXITS

MAX. COMMON PATH OF TRAVEL

MAX. DEAD END

MAX. TRAVEL DISTANCE

2 3

100 FT 43 FT

50 FT N/A

300 FT 260 FT

38.2.5.3.1 38.2.5.2 38.2.6.3

YES

YES

YES

36 IN.

TABLE 7.4.1.1

767108,417

(17)100(1,657)BMULTI-PURPOSE

(BID OPTION)

18210018,118BGIB-BUSINESS

3635018,118B (CONCENTRATED)GIB-BUSINESS

2500809S2 (INCIDENTAL TO A3)STORAGE

22050 NET71,372A-3

HIGH BAY

AREA*

VERTICAL EXITS AND EXIT PASSAGEWAYS

ROOMS AND ENCLOSED SPACES

FLOOR FINISH

CLASS A OR B WITH AUTOMATIC FIRE SPRINKLER

PROTECTION. CLASS A FOR STAIRWAYS.

BUSINESS - CLASS A OR CLASS B

ASSEMBLY - EXITS : CLASS A, EXIT

ACCESS CORRIDORS : CLASS A, CLASS B

CLASS C WITH AUTOMATIC FIRE SPRINKLER PROTECTION.

BUSINESS - CLASS A, B, OR C

ASSEMBLY - CLASS A, B, OR C

FOR SPRINKLER SYSTEM INSTALLATION; CLASS B MAY

REPLACE CLASS A. CLASS C MAY REPLACE CLASS B (10.2.8.1)

INTERIOR WALL AND CEILING FINISHES

BUSINESS - EXITS : CLASS I OR CLASS II

ASSEMBLY - EXITS, EXIT ACCESS CORRIDORS AND CEILING

FINISHES : CLASS I OR CLASS II

CLASS A 0 - 25

CLASS B 26 - 75

CLASS C 76 - 200

0 - 450 0 - 450 0 - 450

1-HR FIRE BARRIER

* MIN DOOR ASSEMBLY RATING: 3/4-HR TABLE 8.3.4.2 FIRE PROTECTION

* MIN WINDOW ASSEMBLY RATING: 3/4-HR (OH-45)

HIGH-BAY AREA - ASSEMBLY ( A3 )

INSTRUCTION/LECTURE USE ABOVE 12TH

GRADE (IBC 303.4)

GIB - BUSINESS ( B ) EDUCATIONAL USE

ABOVE 12TH GRADE (IBC 304.1)

GSE - STORAGE ( S2 ) LOW HAZARD (IBC

311.3) INCIDENTAL TO HIGH-BAY AREA

MULTI-PURPOSE AREA - BUSINESS ( B )

(IBC 304.1)

62'

114,565 SQ. FEET

HIGH-BAY AREA:

BUSINESS OCCUPANCY - PER IBC 507.5:

- A BUSINESS OCCUPANCY OF TWO STORIES WITH A SPRINKLER SYSTEM

THROUGHOUT IS TO BE CONSIDERED UNLIMITED AREA.

ASSEMBLY (A3) OCCUPANCY - PER IBC 507.6:

- AN A-3 OCCUPANCY NO MORE THAN ONE STORY, FULL SPRINKLER

SYSTEM AND SURROUNDED BY 60FT OF PUBLIC WAYS IS TO BE

CONSIDERED UNLIMITED AREA.

MULTI-PURPOSE AREA - BUSINESS - (NEW)

NFPA 101 6.1.11.1

GSE - STORAGE - (NEW)

NFPA 101 6.1.13.1

HIGH BAY - ASSEMBLY - (NEW)

NFPA 101 - 6.1.2.1

GIB-BUSINESS - (NEW)

NFPA 101 - 6.1.11.1

2-STORIES - 75'

1 AND 2

MARKING AND IDENTIFICATION: STENCILING MUST BE PROVIDED AND SPACED NO

MORE THAN 10 FOOT, MEASURED EDGE TO EDGE HORIZONTALLY ALONG THE

WALL OR PARTITION.

(IBC TABLE 508.4) -

B-BUSINESS TO A3-ASSEMBLY : 1HR (FULLY SPRINKLERED) FIRE BARRIER RATING

S2-STORAGE LOW HAZARD TO A3-ASSEMBLY : 0HR (FULLY SPRINKLERED

RATING)

*TOOL ROOM STORAGE AND OTHER STORAGE AREAS WITHIN THE HIGH BAY

AND GIB SPACES ARE CONSIDERED TO BE INCIDENTAL USES. THEY ARE UNDER

10% OF THE BUILDING AREA (IBC 509.3) ARE FULLY SPRINKLERED, AND NONE

QUALIFY FOR ANY CATEGORIES UNDER IBC TABLE 509.

TRAINING FACILITY WITH CLASSROOMS, OFFICE SPACE, AND STORAGE AREA.

62 FT.

PARTITIONS AND BARRIERS

OCCUPANCY SEPERATION

CURRENT BUILDING USAGE

OVERALL HEIGHT

NUMBER OF STORIES

TYPE OF

CONSTRUCTION

II-B (NON-COMBUSTIBLE, UNPROTECTED (CHAPTER 6)

AA = 123,500 SQ. FEET

AA = 104,000 + (26,000 X .75)

AA = AT + (NS x IF)

TOTAL BUILDING AREA -

IF = .75

NS = 26,000 SQ. FEET

AT = 104,000 SQ. FEET

ACTUAL

ALLOWABLE

1 S2 (INCIDENTAL TO A3) 4988

CORRIDOR WIDTH 44 IN. 68 IN. PARA 38.2.3.2

YES YES UFC - 3-600-01 PARA 9-19.1.1

TABLE 7.4.1.1

(11)

NUMBERS REFLECT BASE BID OPTIONS ONLY.

ONE OF THE TWO STORAGE CONFIGURATIONS ARE TO BE SELECTED, NOT BOTH, THEREFORE TOTAL FLOOR AREA AND CALCULATED OCCUPANCY WILL BE AFFECTED BY THE

CHOICE.

CORRIDORS: PER NFPA 101 CHAPTER 38 (38.3.6.1) 0-HR RATING WITH AUTOMATIC SPRINKLER SYSTEM.

SHAFTS (ELEVATORS AND STAIRWAYS) : PER NFPA 101 CHAPTER 8 (8.6.5), ENCLOSURES CONNECTING 3

OR FEWER STORIES IN NEW CONSTRUCTION REQUIRE 1-HR FIRE BARRIERS.

FIRE PUMP ENCLOSURE (UFC 3-600-01 PARA. 9-5.1.2) : MUST BE LOCATED IN A

FIRE-RATED ROOM IN ACCORDANCE WITH NFPA 20 WITH DIRECT ACCESS FROM THE

EXTERIOR. PER NFPA 20 TABLE 4.13.1.1.2, EQUIPMENT PROTECTION OF THE ROOM

REQUIRES A 1-HR FIRE-RATED SEPARATION.

ELECTRICAL ROOMS: ALTHOUGH NOT HIGH HAZARD CONTENTS, ARE TO BE RATED AT 1

HOUR FIRE RATING BY NFPA 70, PARAGRAPH 450.21 DUE TO THE POSSIBLE PRESENCE OF

DRY-TYPE TRANSFORMERS OVER 112.5 KVA RATING. (KVA RATINGS SHOWN ON PLANS)

MECHANICAL ROOMS: ARE BUSINESS CLASSIFIED BY UFC 3-600-01 AS ORDINARY HAZARD OCCUPANCIES PER NFPA 101 CHAPTER 38 (38.3.2.2), ONLY HIGH HAZARD CONTENT AREAS ARE REQUIRED TO HAVE A MINIMUM

1-HR FIRE RESISTANCE RATING.

* HIGH-BAY AREA - 220 OCCUPANT LOAD. DUE TO THE LARGE SIZE OF THE MULTIPLE MOCK HELICOPTER AIRFRAMES THAT WILL BE USED FOR INSTRUCTION, THE PROGRAMMED USE IN THE HIGH-BAY AREA IS ANTICIPATED TO BE 220 TOTAL PERSONS (INCLUDES STUDENTS, INSTRUCTORS, AND SUPPORT PERSONNEL).

HVAC/AIR HANDLING UNITS: (NFPA 101 PARA 8.3.5.7 OPENINGS FOR AIR HANDLING DUCTWORK REFERS TO PARA 9.2.1. NPFA 101 PARA 9.2.1 AIR CONDITIONING, HEATING, VENTILATING DUCTWORK, AND RELATED EQUIPMENT REFERS TO NFPA 90A. NFPA 90A CHAPTER 5 INTEGRATION OF A VENTILATION AND AIR

CONDITIONING SYSTEM(S) WITH BUILDING CONSTRUCTION STATES:

5.3 PENETRATIONS - PROTECTION OF OPENINGS

5.3.1 FIRE RATED WALLS AND PARTITIONS

5.3.1.1 APPROVED FIRE DAMPERS SHALL BE PROVIDED WHERE AIR DUCTS PENETRATE OR TERMINATE AT OPENINGS IN WALLS OF PARTITIONS REQUIRED TO HAVE A FIRE RESISTANCE RATING OF 2 HOURS OR MORE.

WE ARE NOT ON THIS PROJECT. WE ARE ONLY 1 HOUR AT THE SEPARATION OF THE OCCUPANICES.

5.3.2 SHAFTS ARE ADDRESSED IN PARAGRAPH 5.3.4, BUT THE REQUIREMENTS ARE CONTINGENT ON "FLOORS

REQUIRED TO HAVE A FIRE RESISTANCE RATING". OUR FLOORS DO NOT REQUIRE A RATING.

5.3.3 REFERENCES FLOOR CEILING OR ROOF CEILING ASSEMBLIES, BUT I DO NOT SEE WHERE THESE ASSEMBLIES WERE UTILIZED (EXCEPT AT THE FIRE PUMP ROOM 137) SINCE THE ARCHITECTURAL PLANS SHOW CONTINUOUS FIRE BARRIERS ON BOTH FLOORS SEPARATING THE OCCUPANCIES. SINCE THIS BUILDING IS BEING CLASSIFIED AS A TYPE IIB BUILDING, ALL WALLS, FLOORS, ROOFS, ETC. (WITH THE EXCEPTION OF THE

OCCUPANCY SEPARATION) ALL ARE NOT REQUIRED TO HAVE RATINGS.

STORAGE

(BID OPTION)

FLOOR SMOKE BARRIERS: EVERY FLOOR THAT SEPARATES STORIES BARRIER (NFPA 101 8.6.1)

SMOKE DAMPER NOTE: SMOKE DAMPERS NOT REQUIRED IN DUCTWORK WHERE DUCTS PENETRATE

FLOORS THAT SERVE AS SMOKE BARRIERS (NFPA 101 PARA 8.5.5.3(5))

ILLUMINATION : (PARA 7.8.1.3) THE FLOORS AND OTHER WALKING SURFACES WITHIN AN EXIT AND WITHIN REQUIREMENTS THE PORTIONS OF THE EXIT ACCESS AND EXIT DISCHARGE SHALL BE ILLUMINATED AS FOLLOWS: -STAIRS - 10FT CANDLE (108 LUX), MEASURED AT THE WALKING SURFACE -FLOORS AND OTHER

WALKING SURFACES

- 1-FT CANDLE (10.8 LUX) MEASURED AT THE FLOOR.

-EMERGENCY LIGHTING (PARA 38.2.9.1) IS REQUIRED. THE BUILDING HAS MORE THAN 50 PERSONS ABOVE THE LEVEL OF EXIT DISCHARGE AND MORE THAN 300 PERSONS TOTAL. THE FOLLOWING REQUIREMENTS ARE

NECESSARY:

-(PARA 7.9.2.1.1) - MINIMUM DURATION OF 1-1/2 HOURS AFTER NORMAL LIGHTING FAILURE.

-(PARA 7.9.2.1.1) - PROVIDE INITIAL ILLUMINATION THAT IS NOT LESS THAN AN AVERAGE OF 1-FT CANDLE (10.8 LUX) AND, AT ANY POINT, NOT LESS THAN 0.1FT-CANDLE (1.1 LUX), MEASURED ALONG THE PATH OF EGRESS AT FLOOR LEVEL. -(PARA 7.9.2.1.2) - LEVELS AFTER 1-1/2 HOURS MAY DECLINE TO AN AVERAGE OF

.6FT-CANDLE (6.5 LUX) AND .06 FT-CANDLE (0.65 LUX) AT ANY POINT.

-(PARA 7.9.2.3) - LIGHTING SHALL AUTOMATICALLY BE PROVIDED FOR SUCH EVENTS AS FAILURE OF THE PUBLIC UTILITY, OPENING OF A CIRCUIT BREAKER, OR A MANUAL ACT INCLUDING ACCIDENTAL OPENING OF A

SWITCH CONTROLLING THE NORMAL LIGHTING FACILLITIES.

ARRANGEMENT OF EXITS (REMOTENESS) FROM EACH OTHER : IN BUILDINGS PROTECTED BY AN APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM, THE MINIMUM SEPARATION DISTANCE BETWEEN TWO EXITS, EXIT ACCESSES, OR EXIT DISCHARGES, MEASURED IN A STRAIGHT LINE BETWEEN THE NEAREST EDGE OF THE EXITS, SHALL BE NOT LESS THAN ONE-THIRD THE LENGTH OF THE MAXIMUM OVERALL DIAGONAL

DIMENSION OF THE BUILDING OR AREA TO BE SERVED. (PARA 7.5.1.3.3)

3) LESS THAN 2000 PERSONS

2) 50 OR MORE OCCUPANTS ABOVE LEVEL OF EXIT DISCHARGE - 1 1/2HRS REQUIRED AUTOMATIC AFTER

FAILURE OF NORMAL LIGHTING AVERAGE 1 FT-CANDLE

NOTES:

1) 10 FT-CANDLE FOR NEW STAIRS. 1 FT-CANDLE FOR WALKING SURFACES.

ASSEMBLY : 2 FT-CANDLE FOR WALKING SURFACES

EXIT ACCESS CORRIDORS AND

OTHER EXIT WAYS

FLAME SPREAD

INDEX

SMOKE DEVELOPED

INDEX

IBC - - - - - - - - - - - - -

NFPA 101 - - - - - - - -

UFC 3-600-01 - - - - -

'FIRE PROTECTION ENGINEERING FOR FACILITIES' - CHANGE 2, 25 MAR 2018

NFPA 10 - - - - - - - - -

UFC 1-200-01 - - - - -

NFPA 72 - - - - - - - - -

NFPA 13 - - - - - - - - -

NFPA 70 - - - - - - - - -

ADAAG - - - - - - - - - -

UFAS - - - - - - - - - - -

UFC 4-021-01 - - - - -

UFC 4-010-01 - - - - -

UFC 4-010-05 - - - - -

CONSTRUCTION - CHANGE 1, 1 OCT 2013

INTERNATIONAL BUILDING CODE - 2015

LIFE SAFETY CODE - 2015

STANDARD FOR PORTABLE FIRE EXTINGUISHERS - 2018

STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS - 2016

NATIONAL ELECTRIC CODE - 2017

NATIONAL FIRE ALARM CODE - 2016

UNIFIED FACILITIES CRITERIA

DoD MINIMUM ANTI-TERRIORISM STANDARDS FOR BUILDINGS - CHANGE 1, 1 OCT 2013

SENSITIVE COMPARTMENTED INFORMATION FACILITIES PLANNING, DESIGN, AND

DESIGN AND O&M MASS NOTIFICATION SYSTEMS - CHANGE 1, JAN 2010

DoD BUILDING CODE - 20 JUN 2016

UNIFORM FEDERAL ACCESSIBILITY STANDARDS

ACCESSIBILITY GUIDELINES FOR ADA COMPLIANCE

NFPA 1 - - - - - - - - - - NATIONAL FIRE CODE - 2015

US Army Corps of Engineers ®

SHEET ID

US

A

RM

Y

CO

RP

S O

F

EN

G

IN

EE

RS

D R

A W N

B Y:

D

ES

IG

N

ED

B

Y:

SU

B M

IT

TE

D B

Y:

SI

ZE

C H

E C

KE

D B

Y:

AN

S I

'D

FI

LE

N

AM

E:

IS

SU

E D

AT

E :

FI

LE

N U

M

BE

R

1 2 3 4 5

D

C

B

A

SHEET OF

LS001

C O

D E

AN

AL

YS

IS

AV

IA

TI

O

N M

AI

NT

EN

AN

CE

T

RA

IN

IN

G

F

AC

IL

IT

Y F O

RT

E

US

TI

S, V

A .

N O

RF

O

LK

D

I S

TR

IC

T

NO

R F

O

LK

, V A.

RT

A

SU

BM

IT

TA

L

M .F

O R

D

C .R

O D

R

IG

U

EZ

M .F

O R

D

M .F

O R

D

JU

N

E

PR

O

JE

C T

N O

C O

N

TR

AC

T

N O

LS

0 0

1-

648387

M

AR

K D

ES

C

R

IP

TI

O

N D

C C

C

W

T

ASPHALT PARKING

PROPOSED

BUILDING LOCATION

SIGN

MARSHALL STREET

ASPHALT SURFACE

MADIS

ON A

VENUE

CONC. S

URFA

CE

S

TO

R

Y F

R A M

E D

B U

IL

D

IN

G

S

T O R

Y F

R A M

E D

B U

IL

D

IN

G

1 S

TO

RY F

RAMED

BUILD

IN

G #2

1 STORY MASONRY

BUILDING #2703

S

TO

R

Y M

E

TA

L B

U

IL

D

IN

G

S H

O W

N P

E R

G

IS

A

SP

H

AL

T S

U R

FA

C

E

A

SP

H

AL

T S

U R

FA

C

E

SURVEY LI

MITS

FH

FH

FH PIV

FIRE DEPARTMENT CONNECTION

60'-0"

60'-0"

'-0

'-0

'-1

/8

24'-0"

24'-0"

2 3

2 3

FIRE PUMP ROOM

FIRE DEPARTMENT ACCESS

5'-

3/

8"

'-9

1 THIS SPACE IS SHOWN ON THIS PLAN TO DEMONSTRATE THAT THIS BUILDING

FULFILLS THE REQUIREMENTS FOR AN UNLIMITED AREA BUILDING IN

ACCORDANCE WITH IBC 2015 PARA 507.5.

THIS FACILITY MUST HAVE AT LEAST ONE MEANS OF ALL-WEATHER GROUND

ACCESS TO THE FACILITY. ACCESS MUST BE PAVED, START FROM THE ROAD,

AND TERMINATE NO FURTHER THAN 33 FEET FROM AN EXTERIOR DOOR

ACCESSIBLE FOR FIRE DEPARTMENT INGRESS.

FIRE DEPARTMENT ACCESS ROADS CONNECTING TO ROADWAYS SHALL BE

PROVIDED WITH CURB CUTS EXTENDING AT LEAST 2 FEET BEYOND EACH EDGE

OF THE FIRE LANE. ACCESS ROAD SHALL HAVE AN UNOBSTRUCTED WIDTH OF

NOT LESS THAN 20 FEET AND UNOBSTRUCTED VERTICAL CLEARANCE OF NOT

LESS THAN 13 FEET 6 INCHES. THE TURNING RADIUS OF A FIRE DEPARTMENT

ACCESS ROAD SHALL BE AS APPROVED BY THE AHJ.

FIRE DEPARTMENT CONNECTION FOR FIRE SUPPRESSION SYSTEMS MUST BE

PROVIDED WITH SUITABLE ALL-WEATHER GROUND ACCESS SURFACE FOR ANY

APPARATUS WITHIN 150 FEET OF SUCH FIRE DEPARTMENT CONNECTIONS.

US Army Corps of Engineers ®

SHEET ID

US

A

RM

Y

CO

RP

S O

F

EN

G

IN

EE

RS

D R

A W N

B Y:

D

ES

IG

N

ED

B

Y:

SU

B M

IT

TE

D B

Y:

SI

ZE

C H

E C

KE

D B

Y:

AN

S I

'D

FI

LE

N

AM

E:

IS

SU

E D

AT

E :

FI

LE

N U

M

BE

R

1 2 3 4 5

D

C

B

A

SHEET OF

LS002

LI

FE

S

AF

ET

Y

S I

TE

P L A

N

AV

IA

TI

O

N M

AI

NT

EN

AN

CE

T

RA

IN

IN

G

F

AC

IL

IT

Y F O

RT

E

US

TI

S, V

A .

N O

RF

O

LK

D

I S

TR

IC

T

NO

R F

O

LK

, V A.

RT

A

SU

BM

IT

TA

L

M .F

O R

D

C .R

O D

R

IG

U

EZ

M .F

O R

D

M .F

O R

D

JU

N

E

PR

O

JE

C T

N O

C O

N

TR

AC

T

N O

LS

0 0

2-

648388

SCALE: 1" = 50'-0"

LIFE SAFETY SITE PLAN

FIRE HYDRANT REQUIREMENTS (UFC 3-600-01 PARA. 9-3.5)

1. FIRE HYDRANTS MUST HAVE (2) 2 1/2" (65mm) HOSE OUTLETS AND (1) 4 1/2" OUTLET.

2. DRY BARREL OR TRAFFIC-TYPE HYDRANTS MUST BE USED IN AREAS WHERE THERE IS A DANGER

OF FREEZING. HYDRANTS MUST BE ABOVEGROUND TYPE AND MATCH THE TYPE USED ON THE

INSTALLATION.

3. HYDRANT CAPS/BARRELS MUST BE COLOR CODED TO PREVENT CROSS-CONNECTION. IN THE

ABSENCE OF AN INSTALLATION ESTABLISHED COLOR CODE STANDARD, THE FOLLOWING COLORS

MUST BE USED; RED FOR NON-POTABLE WATER, YELLOW FOR POTABLE WATER, AND PURPLE

FOR RECLAIMED/REUSE WATER. ALL HYDRANTS MUST ALSO BE MARKED BASED ON THE FIRE

FLOW CAPACITY, IN ACCORDANCE WITH NFPA 291 OR BY THE INSTALLATION ESTABLISHED

MARKING STANDARD.

4. CLEARLY MARK EACH NEW HYDRANT WITH AN IDENTIFICATION NUMBER ASSIGNED BY THE

INSTALLATION.

5. CONSTRUCTION REQUIREMENTS:

· INSTALLATION MUST BE IN ACCORDANCE WITH NFPA 24 EXCEPT AS MODIFIED BY THIS UFC.

· HYDRANTS MUST BE INSTALLED ADJACENT TO PAVED AREAS, ACCESSIBLE TO FIRE

DEPARTMENT APPARATUS.

· SERVICE LATERAL SUPPLYING HYDRANTS MUST BE MINIMUM 6" AND VALVED AT THE

CONNECTION TO THE SERVICE MAIN.

· BARRELS MUST BE LONG ENOUGH TO PERMIT AT LEAST 18" CLEARANCE BETWEEN THE CENTER

OF THE 4 1/2" OUTLET AND GRADE.

· THE GROUND MUST BE GRADED SO THAT ANY SURFACE DRAINAGE IS AWAY FROM THE

HYDRANT.

· THE 4 1/2" OUTLET MUST BE PERPENDICULAR TO THE STREET TO ALLOW STRAIGHT

CONNECTION TO THE PUMPER.

· LANDSCAPING, FENCING, BOLLARDS AND SIMILAR MUST BE LOCATED A MINIMUM OF 24" FROM

THE HORIZONTAL CENTERLINE OF THE HYDRANT AND NOT DIRECTLY IN FRONT OF ANY OUTLET.

6. ALL PARTS OF THE FACILITY EXTERIOR MUST BE WITHIN 350' OF A HYDRANT WITH

CONSIDERATION GIVEN TO ACCESSIBILITY AND OBSTRUCTIONS.

7. AT LEAST ONE HYDRANT MUST BE LOCATED WITHIN 150' OF THE FIRE DEPARTMENT

CONNECTION.

8. VEHICLE PARKING MUST BE PROVIDED WITH HYDRANTS SPACED AT 300' MAXIMUM INTERVALS

AROUND THE PERIMETER.

9. HYDRANTS LOCATED ADJACENT TO PARKING AREAS, VEHICLE TRAFFIC AREAS OR OTHER AREAS

SUBJECT TO MECHANICAL DAMAGE, MUST BE PROTECTED BY BOLLARDS. THE BOLLARDS MUST

BE LOCATED SO THEY ARE NOT DIRECTLY IN FRONT OF AN OUTLET.

NOTES THIS SHEET

50' 100' 150'

SCALE: 1" = 50' - 0"

0'

M

AR

K D

ES

C

R

IP

TI

O

N D

TD

TD

TD

HIGH BAY

68488

A3 220XXX

MTG 1

B 3100

MTG 2

B 5100

VEST

B 1100

STORAGE

B 1100

VESTIBULE

B 1100

WOMEN'S

B 1100

KITCHEN

B 1100

MEN'S

B 1100

MECH.

B 1100

MECH

B 3100

MAIN ELEC.

B 3100

FIRE_PUMP

B 2100

VEST

B 2100STAIR 1

219 EXIT

0.2

EXIT

0.2

CLASS RM 1

B 1450

CLASS RM 2

B 1450

CLASS RM 3

B 1450

MEN'S

B 3100

WOMEN'S

B 3100

WOMEN'S

B 2100

MEN'S

B 3100

CLASS RM 4

B 1450

COMP. MAINT.

B 1450

ELEC. IDF

B 1100

CLASS RM 5

B 1450

TOOL STO.

B 10100

BREAK RM.

B 5100

TELCOM IDF

B 2100

JANITOR

B 1100

RECYCLING

B 2100

CLASS RM 6

B 1450

CLASS RM 7

B 1450

MECH

B 2100

WOMEN'S

B 2100

MEN'S

B 3100

MEN'S

B 3100

WOMEN'S

B 2100

EXIT

0.2

EXIT

0.2

CLASS RM 8

B 1450

CLASS RM 9

B 1450

CLASS RM 10

B 1450

STAIR 2

ELEC.

B 1100

TR

B 2100

EXIT

0.2

EXIT

0.2

EXIT

0.2

EXIT

0.2

EXIT

0.2

EXIT

0.2

BREAK AREA

B 5100

TD

TD

TD

TD

TD

TD TDTD

TD

TD

TOTAL DISTANCE: 226'-2"

TOTAL DISTANCE: 260'-3 3/4"

C P

CP

COMMON PATH

DISTANCE: 49'

CP

COMMON PATH

DISTANCE: 34'-8"

TD

MECHANICAL

YARD

500 KVA

TRANSFORMER

500 KVA

TRANSFORMER

300 KVA

TRANSFORMER

EXIT

0.2

GSE

S 2500

C P

C P

COMMON PATH

DISTANCE: 56'

/2

2 2

BUILDING DESCRIPTION:

THIS BUILDING IS DEDICATED TO THE INSTRUCTION ON AIRCRAFT MAINTENANCE. THE GIB CONTAINS 10 CLASSROOMS WITH A NORMAL OCCUPANCY OF 14 EACH (12 STUDENTS, 1 INSTRUCTOR, 1 OBSERVER). THE STUDENTS WILL ATTEND CLASSROOM INSTRUCTION, AND WILL THEN MOVE TO THE HIGH BAY TRAINING AREA FOR FURTHER TECHNICAL INSTRUCTION IN THEIR SMALL GROUPS. THE HIGH BAY TRAINING AREA IS AN UNDIVIDED SPACE OF 72,388GSF USED FOR DEMONSTRATION TRAINING OF REPAIR TECHNIQUES ON ACTUAL UN- FUELED ROTARY AIRCRAFT, WITH SEVERAL SUCH AIRCRAFT STAGED THROUGHOUT THE BAYS FOR SMALL GROUP INSTRUCTION. DUE TO THE SPECIFICITY AND HANDS-ON NATURE OF THIS TRAINING, THE USING ACTIVITY ANTICIPATES THE TOTAL OCCUPANCY OF THE HIGH BAY TRAINING AREA TO NOT EXCEED 220 PERSONS AT ANY GIVEN TIME, THEREFORE THE IBC TABLE 1004.1.2 CALCULATION OF PERSONS FOR A-3 ASSEMBLY IS NOT REPRESENTATIVE OF THE ACTUAL PROPOSED USE OF THIS SPACE. FURTHERMORE, ALTHOUGH IT IS POSSIBLE FOR THE 10 CLASSROOM GROUPS OF 14 (PLUS ANY SUPPORT PERSONNEL) TO OCCUPY THE HIGH BAY TRAINING SPACE AT ONE TIME, THEY WILL NOT BE CONCENTRATED BUT WILL INSTEAD BE DISPERSED BY CLASS TO TRAIN ON INDIVIDUAL AIRCRAFT, WITH EACH TRAINING GROUP BEING LESS THAN 50 PERSONS. MULTIPLE EXITS FROM THE SPACE ARE PROVIDED.

List Of Fluids/Materials Utilized Within Facility Product Name NSN SDS # Grease, Syntex (12 oz tube) 9150-00-506-8497 ns-3913-G1 Grease, WTR (5 lb can) 9150-00-145-0268 GN22-4 Oil, Air Compressor 9150-LLN009382 4F9784ZF21 Oil, DOD-L-85734 (QT can) 9150-01-209-2684 40 1740 Oil, Aircraft, MIL-PRF-7808 (QT can) 9150-00-782-2627 40 1742 Hydraulic Fluid, MIL-PRF-83282 (QT can) 9150-00-149-7431 40 1791 Oil, Aircraft, MIL-PRF-23699 (QT can) 9150-00-985-7099 40 1477 NAV II Exterior Aircraft Cleaner 6850-00-181-7594 4141

STORAGE

S 11500

EXIT

0.2

TD

TD

TD

TOTAL DISTANCE : 108'

1 PER NFPA 101, PARAGRAPH 7.2.1.4.2 THE DOOR MAY SWING

INTO THE ROOM SINCE THE OCCUPANCY IS LESS THAN 50

(TYPICAL OF ALL CLASSROOMS ON THIS HALLWAY).

STRUCTURAL MATERIALS UTILIZED TO PROVIDE SUPPORTING

CONSTRUCTION FOR (AS DEFINED ON STRUCTURAL FRAMING

SHEETS S-141 TO S-143) STAIRS, OCCUPANCY SEPARATIONS,

AND ELEVATOR CONSTRUCTION ARE REQUIRED TO BE 1-HR

FIRE RATED PER IBC PARAGRAPH 707.5.1. REFER TO SHEET

A-412 AND A-413 FOR REPRESENTATION OF 1-HR

HORIZONTAL SHAFTWALL AT TOP OF STAIR SHAFT.

US Army Corps of Engineers ®

SHEET ID

US

A

RM

Y

CO

RP

S O

F

EN

G

IN

EE

RS

D R

A W N

B Y:

D

ES

IG

N

ED

B

Y:

SU

B M

IT

TE

D B

Y:

SI

ZE

C H

E C

KE

D B

Y:

AN

S I

'D

FI

LE

N

AM

E:

IS

SU

E D

AT

E :

FI

LE

N U

M

BE

R

1 2 3 4 5

D

C

B

A

SHEET OF

LS111

O

VE

R

AL

L

FI

R

ST

F L O

O R

L

IF

E S A

FE

T Y

P

LA

N

AV

IA

TI

O

N M

AI

NT

EN

AN

CE

T

RA

IN

IN

G

F

AC

IL

IT

Y F O

RT

E

US

TI

S, V

A .

N O

RF

O

LK

D

I S

TR

IC

T

NO

R F

O

LK

, V A.

RT

A

SU

BM

IT

TA

L

M .F

O R

D

C .R

O D

R

IG

U

EZ

M .F

O R

D

M .F

O R

D

JU

N

E

PR

O

JE

C T

N O

C O

N

TR

AC

T

N O

LS

1 1

1-

648389

SCALE: 1" = 20'-0"

OVERALL FIRST FLOOR LIFE SAFETY PLAN

1" = 20'-0" 20' 10' 0' 40'20' 80'

GRAPHIC SCALE

LEGEND

XXX

XXX

XXXX X

ROOM LABEL

SQUARE FOOTAGE

PERSONS PER SPACE

OCCUPANCY LOAD FACTOR

OCCUPANCY

TD TRAVEL DISTANCE TO AN EXIT

CP COMMON PATH TO POINT WHERE TWO

PATHS OF EGRESS ARE AVAILABLE

BUILDING EXIT

1-HR FIRE RATED BARRIER WALL

OPTIONAL BID ITEM AREA

EXIT SIGN

XXXX

XXXX

XXXX

XXXX

XXXX

EGRESS ELEMENT

EGRESS WIDTH (CLEAR - DOOR)

EXIT WIDTH PER PERSON (IN)

CAPACITY (PEOPLE)

ACTUAL PEOPLE

(NOMINAL - STAIRS)

SCALE: 1" = 20'-0"

BID OPTION #4 - GSE STORAGE

NOTES THIS SHEET

N

SCALE: NTS

KEY PLAN

'C' 'B' 'A'

'F' 'E' 'D''G'

M

AR

K D

ES

C

R

IP

TI

O

N D

S3.1

S3.1S3.1 S3.1

S3.1

S3.1

NIC - TV

NIC - TV

ELEC.

100B 1

STORAGE

500B 1

TR

100B 1

MECH.

100B 1

OPEN OFF.

100B 27

STAIR 1

JANITOR

100B 1

WOMEN'S

100B 2

MEN'S

100B 3

STORAGE

500S 1

RECYCLING

100B 1

OPEN OFF.

100B 14

USER SERV.

100B 4

ELEC.

100B 1

OFFICE

100B 1

BREAK RM.

100B 3

TR

100B 2

OFFICE

100B 2

CONF. RM.

100B 5

MEN'S

100B 3

OPEN OFF.

100B 14OPEN OFF.

100B 24

JANITOR

100B 1

WOMEN'S

100B 2

STORAGE

500S 1

ELEC.

100B 1

TR

100B 2

EXIT

0.2

XO

100B 1

CO

100B 1 1SG

100B 1

OPS

100B 1

EXIT

0.2

TD

TOTAL DISTANCE: 200'-5"

CP

COMMON PATH

DISTANCE: 29'

T

9.5

TDTD

TD

45 KVA TRANSFORMER

.3

45 KVA

TRANSFORMER

STAIR 2

.3

45 KVA

TRANSFORMER

List of Fluids/Materials Used Within Facility Product Name NSN SDS # Grease, Syntex (12 oz tube) 9150-00-506-8497 ns-3913-G1 Grease, WTR (5 lb can) 9150-00-145-0268 GN22-4 Oil, Air Compressor 9150-LLN009382 4F9784ZF21 Oil, DOD-L-85734 (QT can) 9150-01-209-2684 40 1740 Oil, Aircraft, MIL-PRF-7808 (QT can) 9150-00-782-2627 40 1742 Hydraulic Fluid, MIL-PRF-83282 (QT can) 9150-00-149-7431 40 1791 Oil, Aircraft, MIL-PRF-23699 (QT can) 9150-00-985-7099 40 1477 NAV II Exterior Aircraft Cleaner 6850-00-181-7594 4141

US Army Corps of Engineers ®

SHEET ID

US

A

RM

Y

CO

RP

S O

F

EN

G

IN

EE

RS

D R

A W N

B Y:

D

ES

IG

N

ED

B

Y:

SU

B M

IT

TE

D B

Y:

SI

ZE

C H

E C

KE

D B

Y:

AN

S I

'D

FI

LE

N

AM

E:

IS

SU

E D

AT

E :

FI

LE

N U

M

BE

R

1 2 3 4 5

D

C

B

A

SHEET OF

LS112

O

VE

R

AL

L

SE

C O

N D

F

LO

O R

L

IF

E

SA

FE

TY

P L A

N

AV

IA

TI

O

N M

AI

NT

EN

AN

CE

T

RA

IN

IN

G

F

AC

IL

IT

Y F O

RT

E

US

TI

S, V

A .

N O

RF

O

LK

D

I S

TR

IC

T

NO

R F

O

LK

, V A.

RT

A

SU

BM

IT

TA

L

M .F

O R

D

C .R

O D

R

IG

U

EZ

M .F

O R

D

M .F

O R

D

JU

N

E

PR

O

JE

C T

N O

C O

N

TR

AC

T

N O

LS

1 1

2-

648390

SCALE: 1" = 20'-0"

OVERALL SECOND FLOOR PLAN

1" = 20'-0" 20' 10' 0' 40'20' 80'

GRAPHIC SCALE

LEGEND

XXX

XXX

XXXX X

ROOM LABEL

SQUARE FOOTAGE

PERSONS PER SPACE

OCCUPANCY LOAD FACTOR

OCCUPANCY

XXXX

XXXX

XXXX

XXXX

XXXX

EGRESS ELEMENT

EGRESS WIDTH (CLEAR - DOOR)

EXIT WIDTH PER PERSON (IN)

CAPACITY (PEOPLE)

ACTUAL PEOPLE

TD TRAVEL DISTANCE TO AN EXIT

CP COMMON PATH TO POINT WHERE TWO

PATHS OF EGRESS ARE AVAILABLE

BUILDING EXIT

1-HR FIRE RATED BARRIER WALL

EXIT SIGN

(NOMINAL - STAIRS)

M

AR

K D

ES

C

R

IP

TI

O

N D

DETAIL NOTES:

NO SCALE

ELEVATOR ZONE CONTROL DETAILSPRINKLER WET PIPE RISER DIAGRAM - TYPICAL FOR 3

A1

C1 C3

INSPECTOR'S TEST CONNECTION

NOT TO SCALE

FIRE SPRINKLER HEAD SCHEDULE

NO SCALE

TO SPRINKLER SYSTEMFROM SPRINKLER BULK MAIN RISER CHECK VALVE

FLOW SWITCH

WATER PRESSURE GAUGE

MAIN DRAIN VALVE

MAIN DRAIN

O S & Y GATE VALVE W / SUPERVISORY

SWITCH / BUTTERFLY VALVE

BACKFLOW PREVENTER TEST HEADER

SMOOTH BORE CORROSION-RESISTANT

OUTLET GIVING FLOW EQUIVALENT TO ONE

SPRINKLER HEAD

UNION

TEST VALVE IN

READILY ACCESSIBLE

LOCATION

PLUG, FOR TESTING

REMOVE & INSTALL

TEMPORARY

CONNECTION

SEE NOTE

BRANCH LINE

PITCH

NOTE: TO MINIMIZE CONDENSATION OF WATER IN THE DROP TO THE TEST

CONNECTION, PROVIDE A NIPPLE-UP OFF THE BRANCH LINE.

ZONE CONTROL VALVE WITH TAMPER SWITCH

WATER FLOW SWITCH LESS RETARD

SIGHT GLASS

TEST VALVE

SECTIONAL DRAIN VALVE

SPRINKLER MAIN TO SERVE ELEVATOR RELATED SPACES

UNION WITH CORROSION RESISTANT ORIFICE GIVING FLOW

EQUIVALENT TO SMALLEST SPRINKLER ORIFICE IN SYSTEM

TO DRAIN

TEMP.TYPESYM. MAKE KMODELRESPONSE ORFICE FINISHLINK LENGTH

155°VICTAULIC CONCEALED -QUICK 5.6 1/2" BULB WHITE -

155°VICTAULIC UPRIGHT -QUICK 5.6 1/2" BULB BRASS -

1 2

8 12

5 7

SP111

SP111 SP112

PIPE TURN UP

PIPE TURN DOWN (DN)

CHECK VALVE (CV)

BUTTERFLY VALVE

PIPE CAPPED

GATE VALVE (GV)

NEW WORK NOTE DESIGNATION

REDUCED PRESSURE

FIRE PROTECTION PIPING

BACKFLOW PREVENTER (RPBP)

SOLENOID VALVE

AFF

AC ABOVE CEILING

ABOVE FINISHED FLOOR

1 HOUR FIRE RATED WALL

1 HOUR FIRE & SMOKE RATED WALL

2 HOUR FIRE & SMOKE RATED WALL

2 HOUR FIRE RATED WALL

SMOKE PARTITION

FIRE SPRINKLER RISER

HYDRAULIC REFERENCE POINT

REMOTE AREA BOUNDARY

AFG ABOVE FINISHED GRADE

FDC FIRE DEPARTMENT CONNECTION

GAL GALLON

GPH GALLON PER HOUR

GPM GALLONS PER MINUTE

HD HEAD

HP HORSE POWER

NFPA NATIONAL FIRE

PROTECTION ASSOCIATION

W/ WITH

SIDEWALL SPRINKLER HEAD

UPRIGHT PENDANT HEAD

CONCEALED PENDANT HEAD

SHEET WHERE SHOWN/CUT

DETAIL/RISER/ENLARGED PLAN

X

Level 1 0' - 0"

Level 2 16' - 0"

Level 3 28' - 0"

HIGH BAY

SYSTEM MAIN

HIGH BAY

BRANCH PIPING

11.2 K FACTOR UPRIGHT

SPRINKLER (TYP.)

HIGH BAY SYSTEM

BACK MAIN

HIGH BAY

SYSTEM

FRONT MAIN

WET PIPE

SPRINKLER

RISER

BULK MAIN

US Army Corps of Engineers ®

SHEET ID

US

A

RM

Y

CO

RP

S O

F

EN

G

IN

EE

RS

D R

A W N

B Y:

D

ES

IG

N

ED

B

Y:

SU

B M

IT

TE

D B

Y:

SI

ZE

C H

E C

KE

D B

Y:

AN

S I

'D

FI

LE

N

AM

E:

IS

SU

E D

AT

E :

FI

LE

N U

M

BE

R

1 2 3 4 5

D

C

B

A

SHEET OF

SP001

LE

G

EN

D

, N O

TE

S

AN

D

A

BB

R

EV

IA

T I

O N

S

AV

IA

TI

O

N M

AI

NT

EN

AN

CE

T

RA

IN

IN

G

F

AC

IL

IT

Y F O

RT

E

US

TI

S, V

A .

N O

RF

O

LK

D

I S

TR

IC

T

NO

R F

O

LK

, V A.

RT

A

SU

BM

IT

TA

L

D .B

O G

G S

B.

W

AL

L

M .F

O R

D

M .F

O R

D

JU

N

E

PR

O

JE

C T

N O

C O

N

TR

AC

T

N O

SP

1-

648391

LEGENDS & ABBREVIATIONS

SCALE: 3/32" = 1'-0" SP114

A2 HIGH BAY SYSTEM SECTION

M

AR

K D

ES

C

R

IP

TI

O

N D

FLOW TEST RESULTS:

RESIDUAL:

FLOW:

DATE:

TIME:

STATIC:

LOCATION:

CONDUCTED BY:

60 PSI

56 PSI

1074 GPM

OLD DOMINION UTILITY SERVICES

02-17-2017 02:05 P.M.

FORT EUSTIS, VIRGINIA

NO SCALE

SITE PLAN

US Army Corps of Engineers ®

SHEET ID

US

A

RM

Y

CO

RP

S O

F

EN

G

IN

EE

RS

D R

A W N

B Y:

D

ES

IG

N

ED

B

Y:

SU

B M

IT

TE

D B

Y:

SI

ZE

C H

E C

KE

D B

Y:

AN

S I

'D

FI

LE

N

AM

E:

IS

SU

E D

AT

E :

FI

LE

N U

M

BE

R

1 2 3 4 5

D

C

B

A

SHEET OF

SP002

SI

TE

P

LA

N

AV

IA

TI

O

N M

AI

NT

EN

AN

CE

T

RA

IN

IN

G

F

AC

IL

IT

Y F O

RT

E

US

TI

S, V

A .

N O

RF

O

LK

D

I S

TR

IC

T

NO

R F

O

LK

, V A.

RT

A

SU

BM

IT

TA

L

D .B

O G

G S

B.

W

AL

L

M .F

O R

D

M .F

O R

D

JU

N

E

PR

O

JE

C T

N O

C O

N

TR

AC

T

N O

SP

2-

648392

2 INLET FDC,

MOUNTED ON WALL

M

AR

K D

ES

C

R

IP

TI

O

N D

8"8"8"

110 109 108 107 106

SA1

SP

SP

SP

SP

SP111

SP114

SP

SP

SP401

C1

4" WET PIPE

SPRINKLER RISER

SEE FIRST FLOOR

BID OPTION, SP901,

FOR

CONTINUATION.

8" SPRINKLER

SERVICE, REFER TO

SITE UTILITIES FOR

CONTINUATION

FIRE PUMP

TEST HEADER

2 INLET FDC

MOUNTED ON

WALL

INSPECTOR'S TEST

CONNECTION, SEE

DETAIL SHEET

SP001

4" WET PIPE

SPRINKLER RISER

4" MAIN UP TO 2ND

FLOOR

EXTERIOR EQUIPMENT YARD

C2

SP001

A1

SP001

1 THIS SPACE SHALL BE DESIGNATED AS ORDINARY

HAZARD.

LIGHT HAZARD NOTE:

ALL SPACES SHALL BE DESIGNATED AS LIGHT HAZARD

OCCUPANCY UNLESS OTHERWISE NOTED.

US Army Corps of Engineers ®

SHEET ID

US

A

RM

Y

CO

RP

S O

F

EN

G

IN

EE

RS

D R

A W N

B Y:

D

ES

IG

N

ED

B

Y:

SU

B M

IT

TE

D B

Y:

SI

ZE

C H

E C

KE

D B

Y:

AN

S I

'D

FI

LE

N

AM

E:

IS

SU

E D

AT

E :

FI

LE

N U

M

BE

R

1 2 3 4 5

D

C

B

A

SHEET OF

SP111

FI

R

ST

F

LO

O

R P

LA

N

AR

EA

A

AV

IA

TI

O

N M

AI

NT

EN

AN

CE

T

RA

IN

IN

G

F

AC

IL

IT

Y F O

RT

E

US

TI

S, V

A .

N O

RF

O

LK

D

I S

TR

IC

T

NO

R F

O

LK

, V A.

RT

A

SU

BM

IT

TA

L

D .B

O G

G S

B.

W

AL

L

M .F

O R

D

M .F

O R

D

JU

N

E

PR

O

JE

C T

N O

C O

N

TR

AC

T

N O

SP

1-

648393

SCALE: 1/8" = 1'-0"

FIRST FLOOR PLAN - AREA A

1ST FLOOR AREA A

ROOM SCHEDULE

ROOM # ROOM NAME

101 CIRCULATION

102 TEF

103 MAIN

ELECTRICAL

105 MECHANICAL

106 CLASSROOM #01

107 CLASSROOM #02

108 CLASSROOM #03

109 WOMEN'S

110 MEN'S

134 MEN'S

135 HIGH BAY TRAINING

137 FIRE PUMP

SA1 STAIR A

N

8' 16' 24'

SCALE: 1/8" = 1' - 0"

0'

SCALE: NTS

KEY PLAN

'C' 'B' 'A'

'F' 'E' 'D''G'

NOTES THIS SHEET

M

AR

K D

ES

C

R

IP

TI

O

N D

8"8"8"8"

111120

115 114

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

F

ELEVATOR ZONE CONTROL

VALVE ASSEMBLY, SEE

DETAIL SHEET SP001

SIDEWALL SPRINKLER IN

ELEVATOR PIT

116 100 SB1

104101A

C3

SP001

1 THIS SPACE SHALL BE DESIGNATED AS ORDINARY

HAZARD.

LIGHT HAZARD NOTE:

ALL SPACES SHALL BE DESIGNATED AS LIGHT HAZARD

OCCUPANCY UNLESS OTHERWISE NOTED.

US Army Corps of Engineers ®

SHEET ID

US

A

RM

Y

CO

RP

S O

F

EN

G

IN

EE

RS

D R

A W N

B Y:

D

ES

IG

N

ED

B

Y:

SU

B M

IT

TE

D B

Y:

SI

ZE

C H

E C

KE

D B

Y:

AN

S I

'D

FI

LE

N

AM

E:

IS

SU

E D

AT

E :

FI

LE

N U

M

BE

R

1 2 3 4 5

D

C

B

A

SHEET OF

SP112

FI

R

ST

F

LO

O

R P

LA

N

AR

EA

B

AV

IA

TI

O

N M

AI

NT

EN

AN

CE

T

RA

IN

IN

G

F

AC

IL

IT

Y F O

RT

E

US

TI

S, V

A .

N O

RF

O

LK

D

I S

TR

IC

T

NO

R F

O

LK

, V A.

RT

A

SU

BM

IT

TA

L

D .B

O G

G S

B.

W

AL

L

M .F

O R

D

M .F

O R

D

JU

N

E

PR

O

JE

C T

N O

C O

N

TR

AC

T

N O

SP

2-

648394

SCALE: 1/8" = 1'-0"

FIRST FLOOR PLAN - AREA B

1ST FLOOR AREA B

ROOM SCHEDULE

ROOM # ROOM NAME

100 VEST

101 CIRCULATION

101A LOBBY

104 ELEV MECH

111 CLASSROOM #04

112 CLASSROOM #05

113 ELEC IDF

114 COMPUTER MAINTENANCE

115 BREAK ROOM

116 BREAK AREA

117 RECYCLING

118 JAN

119 TELCOM IDF

120 CLASSROOM #06

132 TOOL STORAGE/ISSUE

133 WOMEN'S

135 HIGH BAY TRAINING

EA1 ELEV

SB1 STAIR B

N

8' 16' 24'

SCALE: 1/8" = 1' - 0"

0'

SCALE: NTS

KEY PLAN

'C' 'B' 'A'

'F' 'E' 'D''G'

NOTES THIS SHEET

M

AR

K D

ES

C

R

IP

TI

O

N D

8"8"8"8"

6"

6"

6"

126 125 124

123 121

SP

SP

SP

SP

SP

SP

SP113

SP116

4" WET PIPE

SPRINKLER RISER

INSPECTOR'S TEST STATION,

SEE DETAIL SHEET SP001

130 131A1

SP001

C1

SP001

1 THIS SPACE SHALL BE DESIGNATED AS ORDINARY

HAZARD.

LIGHT HAZARD NOTE:

ALL SPACES SHALL BE DESIGNATED AS LIGHT HAZARD

OCCUPANCY UNLESS OTHERWISE NOTED.

US Army Corps of Engineers ®

SHEET ID

US

A

RM

Y

CO

RP

S O

F

EN

G

IN

EE

RS

D R

A W N

B Y:

D

ES

IG

N

ED

B

Y:

SU

B M

IT

TE

D B

Y:

SI

ZE

C H

E C

KE

D B

Y:

AN

S I

'D

FI

LE

N

AM

E:

IS

SU

E D

AT

E :

FI

LE

N U

M

BE

R

1 2 3 4 5

D

C

B

A

SHEET OF

SP113

FI

R

ST

F

LO

O

R P

LA

N

AR

EA

C

AV

IA

TI

O

N M

AI

NT

EN

AN

CE

T

RA

IN

IN

G

F

AC

IL

IT

Y F O

RT

E

US

TI

S, V

A .

N O

RF

O

LK

D

I S

TR

IC

T

NO

R F

O

LK

, V A.

RT

A

SU

BM

IT

TA

L

D .B

O G

G S

B.

W

AL

L

M .F

O R

D

M .F

O R

D

JU

N

E

PR

O

JE

C T

N O

C O

N

TR

AC

T

N O

SP

3-

648395

SCALE: 1/8" = 1'-0"

FIRST FLOOR PLAN - AREA C

1ST FLOOR AREA C

ROOM SCHEDULE

ROOM # ROOM NAME

101 CIRCULATION

103 STAIR #2

120 CLASSROOM #06

121 CLASSROOM #07

122 MECH

123 WOMEN'S

124 MEN'S

125 CLASSROOM #08

126 CLASSROOM #09

127 CLASSROOM #10

128 ELEC

129 TR

130 MEN'S

131 WOMEN'S

135 HIGH BAY TRAINING

N

8' 16' 24'

SCALE: 1/8" = 1' - 0"

0'

SCALE: NTS

KEY PLAN

'C' 'B' 'A'

'F' 'E' 'D''G'

NOTES THIS SHEET

M

AR

K D

ES

C

R

IP

TI

O

N D

SP111

SP114

REFER TO SHEET SP124 FOR

SPRINKLER WORK, THIS AREA

SP001

A2

US Army Corps of Engineers ®

SHEET ID

US

A

RM

Y

CO

RP

S O

F

EN

G

IN

EE

RS

D R

A W N

B Y:

D

ES

IG

N

ED

B

Y:

SU

B M

IT

TE

D B

Y:

SI

ZE

C H

E C

KE

D B

Y:

AN

S I

'D

FI

LE

N

AM

E:

IS

SU

E D

AT

E :

FI

LE

N U

M

BE

R

1 2 3 4 5

D

C

B

A

SHEET OF

SP114

FI

R

ST

F

LO

O

R P

LA

N

AR

EA

D

AV

IA

TI

O

N M

AI

NT

EN

AN

CE

T

RA

IN

IN

G

F

AC

IL

IT

Y F O

RT

E

US

TI

S, V

A .

N O

RF

O

LK

D

I S

TR

IC

T

NO

R F

O

LK

, V A.

RT

A

SU

BM

IT

TA

L

D .B

O G

G S

B.

W

AL

L

M .F

O R

D

M .F

O R

D

JU

N

E

PR

O

JE

C T

N O

C O

N

TR

AC

T

N O

SP

4-

648396

SCALE: 1/8" = 1'-0"

FIRST FLOOR PLAN - AREA D

1ST FLOOR AREA D

ROOM SCHEDULE

ROOM # ROOM NAME

135 HIGH BAY TRAINING

N

8' 16' 24'

SCALE: 1/8" = 1' - 0"

0'

SCALE: NTS

KEY PLAN

'C' 'B' 'A'

'F' 'E' 'D''G'

M

AR

K D

ES

C

R

IP

TI

O

N D

SP

SP

SP

SP

SP

SP

SP

SP

REFER TO SHEET SP125 FOR

SPRINKLER WORK, THIS AREA

US Army Corps of Engineers ®

SHEET ID

US

A

RM

Y

CO

RP

S O

F

EN

G

IN

EE

RS

D R

A W N

B Y:

D

ES

IG

N

ED

B

Y:

SU

B M

IT

TE

D B

Y:

SI

ZE

C H

E C

KE

D B

Y:

AN

S I

'D

FI

LE

N

AM

E:

IS

SU

E D

AT

E :

FI

LE

N U

M

BE

R

1 2 3 4 5

D

C

B

A

SHEET OF

SP115

FI

R

ST

F

LO

O

R P

LA

N

AR

EA

E

AV

IA

TI

O

N M

AI

NT

EN

AN

CE

T

RA

IN

IN

G

F

AC

IL

IT

Y F O

RT

E

US

TI

S, V

A .

N O

RF

O

LK

D

I S

TR

IC

T

NO

R F

O

LK

, V A.

RT

A

SU

BM

IT

TA

L

D .B

O G

G S

B.

W

AL

L

M .F

O R

D

M .F

O R

D

JU

N

E

PR

O

JE

C T

N O

C O

N

TR

AC

T

N O

SP

5-

648397

SCALE: 1/8" = 1'-0"

FIRST FLOOR PLAN - AREA E

N

8' 16' 24'

SCALE: 1/8" = 1' - 0"

0'

SCALE: NTS

KEY PLAN

'C' 'B' 'A'

'F' 'E' 'D''G'

1ST FLOOR AREA E

ROOM SCHEDULE

ROOM # ROOM NAME

135 HIGH BAY TRAINING

M

AR

K D

ES

C

R

IP

TI

O

N D

6"

SP

SP

SP

SP

SP113

SP116

SP116

SP117

REFER TO SHEET SP126 FOR

SPRINKLER WORK, THIS AREA

SEE SHEET SP117, FIRST

FLOOR PLAN AREA G FOR

CONTINUATION.4"

US Army Corps of Engineers ®

SHEET ID

US

A

RM

Y

CO

RP

S O

F

EN

G

IN

EE

RS

D R

A W N

B Y:

D

ES

IG

N

ED

B

Y:

SU

B M

IT

TE

D B

Y:

SI

ZE

C H

E C

KE

D B

Y:

AN

S I

'D

FI

LE

N

AM

E:

IS

SU

E D

AT

E :

FI

LE

N U

M

BE

R

1 2 3 4 5

D

C

B

A

SHEET OF

SP116

FI

R

ST

F

LO

O

R P

LA

N

AR

EA

F

AV

IA

TI

O

N M

AI

NT

EN

AN

CE

T

RA

IN

IN

G

F

AC

IL

IT

Y F O

RT

E

US

TI

S, V

A .

N O

RF

O

LK

D

I S

TR

IC

T

NO

R F

O

LK

, V A.

RT

A

SU

BM

IT

TA

L

D .B

O G

G S

B.

W

AL

L

M .F

O R

D

M .F

O R

D

JU

N

E

PR

O

JE

C T

N O

C O

N

TR

AC

T

N O

SP

6-

648398

SCALE: 1/8" = 1'-0"

FIRST FLOOR PLAN - AREA F

N

8' 16' 24'

SCALE: 1/8" = 1' - 0"

0'

SCALE: NTS

KEY PLAN

'C' 'B' 'A'

'F' 'E' 'D''G'

1ST FLOOR AREA F

ROOM SCHEDULE

ROOM # ROOM NAME

135 HIGH BAY TRAINING

M

AR

K D

ES

C

R

IP

TI

O

N D

B

I

G

E

A

7 87.5

FROM WET PIPE SPRINKLER RISER

SUPPLYING UPPER BAY SYSTEM.

SEE SHEET SP113 FOR FURTHER

INFORMATION.

2" 2"

2" 2"

2" 2"

2" 2"

2" 2"

4"

4"

4"

4"

4"

4"

1 THIS SPACE SHALL BE DESIGNATED AS ORDINARY

HAZARD.

US Army Corps of Engineers ®

SHEET ID

US

A

RM

Y

CO

RP

S O

F

EN

G

IN

EE

RS

D R

A W N

B Y:

D

ES

IG

N

ED

B

Y:

SU

B M

IT

TE

D B

Y:

SI

ZE

C H

E C

KE

D B

Y:

AN

S I

'D

FI

LE

N

AM

E:

IS

SU

E D

AT

E :

FI

LE

N U

M

BE

R

1 2 3 4 5

D

C

B

A

SHEET OF

SP117

FI

R

ST

F

LO

O

R P

LA

N

AR

EA

G

AV

IA

TI

O

N M

AI

NT

EN

AN

CE

T

RA

IN

IN

G

F

AC

IL

IT

Y F O

RT

E

US

TI

S, V

A .

N O

RF

O

LK

D

I S

TR

IC

T

NO

R F

O

LK

, V A.

RT

A

SU

BM

IT

TA

L

D .B

O G

G S

B.

W

AL

L

M .F

O R

D

M .F

O R

D

JU

N

E

PR

O

JE

C T

N O

C O

N

TR

AC

T

N O

SP

7-

648399

1ST FLOOR AREA G

ROOM SCHEDULE

ROOM # ROOM NAME

160 GSE

SCALE: 1/8" = 1'-0"

FIRST FLOOR PLAN - AREA G N

8' 16' 24'

SCALE: 1/8" = 1' - 0"

0'

SCALE: NTS

KEY PLAN

'C' 'B' 'A'

'F' 'E' 'D''G'

NOTES THIS SHEET

M

AR

K D

ES

C

R

IP

TI

O

N D

4"4"4"4"4"4"4"4"4"

2" 2"

2" 2"

2" 2"

2" 2"

2" 2"

2" 2"

2" 2"

2" 2"

2" 2"

2" 2"

2" 2"

2" 2"

2" 2"

2" 2"

2" 2"

2" 2"

2" 2"

2" 2"

DN TO SPRINKLER RISER

210 209

SA2

205 203

DN TO SPRINKLER

RISER

1 1

SP

SP

SP

SP

SP121

SP124

206A

1 THIS SPACE SHALL BE DESIGNATED AS ORDINARY

HAZARD.

LIGHT HAZARD NOTE:

ALL SPACES SHALL BE DESIGNATED AS LIGHT HAZARD

OCCUPANCY UNLESS OTHERWISE NOTED.

US Army Corps of Engineers ®

SHEET ID

US

A

RM

Y

CO

RP

S O

F

EN

G

IN

EE

RS

D R

A W N

B Y:

D

ES

IG

N

ED

B

Y:

SU

B M

IT

TE

D B

Y:

SI

ZE

C H

E C

KE

D B

Y:

AN

S I

'D

FI

LE

N

AM

E:

IS

SU

E D

AT

E :

FI

LE

N U

M

BE

R

1 2 3 4 5

D

C

B

A

SHEET OF

SP121

SE

C

O N

D F

LO

O

R P

L A N

A R

EA

A

AV

IA

TI

O

N M

AI

NT

EN

AN

CE

T

RA

IN

IN

G

F

AC

IL

IT

Y F O

RT

E

US

TI

S, V

A .

N O

RF

O

LK

D

I S

TR

IC

T

NO

R F

O

LK

, V A.

RT

A

SU

BM

IT

TA

L

D .B

O G

G S

B.

W

AL

L

M .F

O R

D

M .F

O R

D

JU

N

E

PR

O

JE

C T

N O

C O

N

TR

AC

T

N O

SP

1-

648400

SCALE: 1/8" = 1'-0"

SECOND FLOOR PLAN - AREA A

2ND FLOOR AREA A

ROOM SCHEDULE

ROOM # ROOM NAME

202 TR

203 ELEC

204 STORAGE

205 MECH

206 OPEN OFFICE

207 JAN

208 CIRCULATION

209 WOMEN'S

210 MEN'S

N

8' 16' 24'

SCALE: 1/8" = 1' - 0"

0'

SCALE: NTS

KEY PLAN

'C' 'B' 'A'

'F' 'E' 'D''G'

NOTES THIS SHEET

M

AR

K D

ES

C

R

IP

TI

O

N D

128 130 132

1056 1035 1014

1057 1036 1015

1058 1037 1016

1059 1038 1017

1060 1039 1018

1061 1040 1019

1062 1041 1020

1063 1042 1021 4"4"4"4"4"4"4"4"4"4"4"

2" 2"

2"

2" 2"

2"

2" 2"

2"

2" 2"

2"

2" 2"

2"

2" 2"

2"

2" 2"

2"

2" 2"

2"

2" 2"

2"

2" 2"

2"

2" 2"

2"

EA2

218220

SB2

SP

SP

SP

SP

SP

SP

SP

SP

1 THIS SPACE SHALL BE DESIGNATED AS ORDINARY

HAZARD.

LIGHT HAZARD NOTE:

ALL SPACES SHALL BE DESIGNATED AS LIGHT HAZARD

OCCUPANCY UNLESS OTHERWISE NOTED.

US Army Corps of Engineers ®

SHEET ID

US

A

RM

Y

CO

RP

S O

F

EN

G

IN

EE

RS

D R

A W N

B Y:

D

ES

IG

N

ED

B

Y:

SU

B M

IT

TE

D B

Y:

SI

ZE

C H

E C

KE

D B

Y:

AN

S I

'D

FI

LE

N

AM

E:

IS

SU

E D

AT

E :

FI

LE

N U

M

BE

R

1 2 3 4 5

D

C

B

A

SHEET OF

SP122

SE

C

O N

D F

LO

O

R P

L A N

A R

EA

B

AV

IA

TI

O

N M

AI

NT

EN

AN

CE

T

RA

IN

IN

G

F

AC

IL

IT

Y F O

RT

E

US

TI

S, V

A .

N O

RF

O

LK

D

I S

TR

IC

T

NO

R F

O

LK

, V A.

RT

A

SU

BM

IT

TA

L

D .B

O G

G S

B.

W

AL

L

M .F

O R

D

M .F

O R

D

JU

N

E

PR

O

JE

C T

N O

C O

N

TR

AC

T

N O

SP

2-

648401

SCALE: 1/8" = 1'-0"

SECOND FLOOR PLAN - AREA B

2ND FLOOR AREA B

ROOM SCHEDULE

ROOM # ROOM NAME

200 LOBBY

200A LOBBY

208 CIRCULATION

211 RECYCLING

212 STORAGE

213 CIRCULATION

214 OPEN OFFICE

215 ELEC

216 OFF

217 CO

218 USER SERVER

219 XO

220 BREAK

ROOM

221 OPS

222 OFF

223 1SG

224 TR

225 OPEN OFFICE

EA2 ELEV

SB2 STAIR B

N

8' 16' 24'

SCALE: 1/8" = 1' - 0"

0'

SCALE: NTS

KEY PLAN

'C' 'B' 'A'

'F' 'E' 'D''G'

NOTES THIS SHEET

M

AR

K D

ES

C

R

IP

TI

O

N D

REMOTE AREA #

SPRINKLERS FLOWING:

FILE:

HAZARD CLASSIFICATION:

SYSTEM TYPE:

DENSITY (GPM/SQ.FT.):

REQUIRED AREA (SQ.FT.):

ACTUAL AREA (SQ.FT.):

SPRINKLER DEMAND (GPM):

RESIDUAL PRESSURE AT BOR (PSI):

HOSE ALLOWANCE (GPM):

EXCESS AVAILABLE PRESSURE (PSI):

17174 - RA3

LIGHT

WET

.10 1,500 1,547.7 321.71 82.07 14.35

100 102 104 106 108 110 112 114 116 118 120 122 1244"4"4"4"4"4"4"4"4"4"4"

DN TO RISER

SC2

2" 2"

2"

2" 2"

2"

2" 2"

2"

2" 2"

2"

2" 2"

2"

2" 2"

2"

2" 2"

2"

2" 2"

2"

2" 2"

2"

2" 2"

2"

2" 2"

2"

2" 2"

2"

REMOTE AREA #3

304305

3003 3001

3004 3002

A2

SP501

SP

SP

SP

SP

SP123

SP126

1 THIS SPACE SHALL BE DESIGNATED AS ORDINARY

HAZARD.

LIGHT HAZARD NOTE:

ALL SPACES SHALL BE DESIGNATED AS LIGHT HAZARD

OCCUPANCY UNLESS OTHERWISE NOTED.

US Army Corps of Engineers ®

SHEET ID

US

A

RM

Y

CO

RP

S O

F

EN

G

IN

EE

RS

D R

A W N

B Y:

D

ES

IG

N

ED

B

Y:

SU

B M

IT

TE

D B

Y:

SI

ZE

C H

E C

KE

D B

Y:

AN

S I

'D

FI

LE

N

AM

E:

IS

SU

E D

AT

E :

FI

LE

N U

M

BE

R

1 2 3 4 5

D

C

B

A

SHEET OF

SP123

SE

C

O N

D F

LO

O

R P

L A N

A R

EA

C

AV

IA

TI

O

N M

AI

NT

EN

AN

CE

T

RA

IN

IN

G

F

AC

IL

IT

Y F O

RT

E

US

TI

S, V

A .

N O

RF

O

LK

D

I S

TR

IC

T

NO

R F

O

LK

, V A.

RT

A

SU

BM

IT

TA

L

D .B

O G

G S

B.

W

AL

L

M .F

O R

D

M .F

O R

D

JU

N

E

PR

O

JE

C T

N O

C O

N

TR

AC

T

N O

SP

3-

648402

SCALE: 1/8" = 1'-0"

SECOND FLOOR PLAN - AREA C

2ND FLOOR AREA C

ROOM SCHEDULE

ROOM # ROOM NAME

225 OPEN OFFICE

226 CIRCULATION

227 CONFERENCE ROOM

228 MEN'S

229 JAN

230 WOMEN'S

231 OPEN OFFICE

232 TR

233 ELEC

234 STORAGE

SC2 STAIR C

N

8' 16' 24'

SCALE: 1/8" = 1' - 0"

0'

SCALE: NTS

KEY PLAN

'C' 'B' 'A'

'F' 'E' 'D''G'

NOTES THIS SHEET

M

AR

K D

ES

C

R

IP

TI

O

N D

4"4"4"4"4"4"4"4"4"

2"2"2"2"2"2"2"2"2"

2"2"2"2"2"2"2"2"2"

SP121

SP124

1 THIS SPACE SHALL BE DESIGNATED AS ORDINARY

HAZARD.

US Army Corps of Engineers ®

SHEET ID

US

A

RM

Y

CO

RP

S O

F

EN

G

IN

EE

RS

D R

A W N

B Y:

D

ES

IG

N

ED

B

Y:

SU

B M

IT

TE

D B

Y:

SI

ZE

C H

E C

KE

D B

Y:

AN

S I

'D

FI

LE

N

AM

E:

IS

SU

E D

AT

E :

FI

LE

N U

M

BE

R

1 2 3 4 5

D

C

B

A

SHEET OF

SP124

SE

C

O N

D F

LO

O

R P

L A N

A R

EA

D

AV

IA

TI

O

N M

AI

NT

EN

AN

CE

T

RA

IN

IN

G

F

AC

IL

IT

Y F O

RT

E

US

TI

S, V

A .

N O

RF

O

LK

D

I S

TR

IC

T

NO

R F

O

LK

, V A.

RT

A

SU

BM

IT

TA

L

D .B

O G

G S

B.

W

AL

L

M .F

O R

D

M .F

O R

D

JU

N

E

PR

O

JE

C T

N O

C O

N

TR

AC

T

N O

SP

4-

648403

SCALE: 1/8" = 1'-0"

SECOND FLOOR PLAN - AREA D

N

8' 16' 24'

SCALE: 1/8" = 1' - 0"

0'

SCALE: NTS

KEY PLAN

'C' 'B' 'A'

'F' 'E' 'D''G'

2ND FLOOR AREA D

ROOM SCHEDULE

ROOM # ROOM NAME

135 HIGH BAY TRAINING

NOTES THIS SHEET

M

AR

K D

ES

C

R

IP

TI

O

N D

FILE:

HAZARD CLASSIFICATION:

SYSTEM TYPE:

DENSITY (GPM/SQ.FT.):

REQUIRED AREA (SQ.FT.):

ACTUAL AREA (SQ.FT.):

SPRINKLER DEMAND (GPM):

RESIDUAL PRESSURE AT BOR (PSI):

HOSE ALLOWANCE (GPM):

EXCESS AVAILABLE PRESSURE (PSI):

17174 - RA1

ORDINARY

WET

0.20 2,628 1301.65 46.92 13.26

1127 129 131 133

1043 1022 1001

1044 1023 1002

1045 1024 1003

1046 1025 1004

1047 1026 1005

1048 1027 1006

1049 1028 1007

1050 1029 1008

1051 1030 1009

1052 1031 1010

1053 1032 1011

1054 1033 1012

1055 1034 1013

1056 1035 1014

4"4"4"4"4"4"4"4"4"4"4"

REMOTE AREA 1

2"2"2"2"2"2"2"2"2"2"2"

2"2"2"2"2"2"2"2"2"2"2"

2"2"2"2"2"2"2"2"2"2"2"

B3

SP501

SP

SP

SP

SP

SP

SP

SP

SP

1 THIS SPACE SHALL BE DESIGNATED AS ORDINARY

HAZARD.

US Army Corps of Engineers ®

SHEET ID

US

A

RM

Y

CO

RP

S O

F

EN

G

IN

EE

RS

D R

A W N

B Y:

D

ES

IG

N

ED

B

Y:

SU

B M

IT

TE

D B

Y:

SI

ZE

C H

E C

KE

D B

Y:

AN

S I

'D

FI

LE

N

AM

E:

IS

SU

E D

AT

E :

FI

LE

N U

M

BE

R

1 2 3 4 5

D

C

B

A

SHEET OF

SP125

SE

C

O N

D F

LO

O

R P

L A N

A R

EA

E

AV

IA

TI

O

N M

AI

NT

EN

AN

CE

T

RA

IN

IN

G

F

AC

IL

IT

Y F O

RT

E

US

TI

S, V

A .

N O

RF

O

LK

D

I S

TR

IC

T

NO

R F

O

LK

, V A.

RT

A

SU

BM

IT

TA

L

D .B

O G

G S

B.

W

AL

L

M .F

O R

D

M .F

O R

D

JU

N

E

PR

O

JE

C T

N O

C O

N

TR

AC

T

N O

SP

5-

648404

SCALE: 1/8" = 1'-0"

SECOND FLOOR PLAN - AREA E N

8' 16' 24'

SCALE: 1/8" = 1' - 0"

0'

SCALE: NTS

KEY PLAN

'C' 'B' 'A'

'F' 'E' 'D''G'

2ND FLOOR AREA E

ROOM SCHEDULE

ROOM # ROOM NAME

135 HIGH BAY TRAINING

NOTES THIS SHEET

M

AR

K D

ES

C

R

IP

TI

O

N D

103 105 107 109 111 113 115 117 119 121 123 125

4"4"4"4"4"4"4"4"4"4"4"4"

2" 2"

2"

2" 2"

2"

2" 2"

2"

2" 2"

2"

2" 2"

2"

2" 2"

2"

2" 2"

2"

2" 2"

2"

2" 2"

2"

2" 2"

2"

2" 2"

2"

2" 2"

2"

SP

SP

SP

SP

SP123

SP126

SP126

SP127

US Army Corps of Engineers ®

SHEET ID

US

A

RM

Y

CO

RP

S O

F

EN

G

IN

EE

RS

D R

A W N

B Y:

D

ES

IG

N

ED

B

Y:

SU

B M

IT

TE

D B

Y:

SI

ZE

C H

E C

KE

D B

Y:

AN

S I

'D

FI

LE

N

AM

E:

IS

SU

E D

AT

E :

FI

LE

N U

M

BE

R

1 2 3 4 5

D

C

B

A

SHEET OF

SP126

SE

C

O N

D F

LO

O

R P

L A N

A R

EA

F

AV

IA

TI

O

N M

AI

NT

EN

AN

CE

T

RA

IN

IN

G

F

AC

IL

IT

Y F O

RT

E

US

TI

S, V

A .

N O

RF

O

LK

D

I S

TR

IC

T

NO

R F

O

LK

, V A.

RT

A

SU

BM

IT

TA

L

D .B

O G

G S

B.

W

AL

L

M .F

O R

D

M .F

O R

D

JU

N

E

PR

O

JE

C T

N O

C O

N

TR

AC

T

N O

SP

6-

648405

SCALE: 1/8" = 1'-0"

SECOND FLOOR PLAN - AREA F

N

8' 16' 24'

SCALE: 1/8" = 1' - 0"

0'

SCALE: NTS

KEY PLAN

'C' 'B' 'A'

'F' 'E' 'D''G'

2ND FLOOR AREA F

ROOM SCHEDULE

ROOM # ROOM NAME

135 HIGH BAY TRAINING

M

AR

K D

ES

C

R

IP

TI

O

N D

1/4" = 1'-0"

5' 10'0' 5'FIRE PUMP DETAIL (FP-1 AND JP-1)

FIRE PUMP SCHEDULE

BACKFLOW PREVENTER DISCHARGE PIPING DETAIL

18" MINIMUM OR *

X AND Y BY 1 SIZE.

X" x Y" SCHEDULE 40 PVC ELBOW

* = INCREASE BOTH PIPE SIZESCONCRETE FLOOR SLAB

AT MINIMUM 1/4" PER FOOT SLOPE

DISCHARGE PIPE Y" SCH 40 PVC

10'-0" MAXIMUM OR *

AIR GAP: 4" MINIMUM

X" SCHEDULE 40 PVC RISER PIPE

(SECURE TO WALL OR FLOOR)

RISER

PIPE "X"

SIZE,

INCHES

FITTING TO ADAPT AIR TO PIPE DIAMETER REQUIRED

AIR GAP FITTING ON RPBP

BL

DG

. E

XT

ER

IO

R

PREVENTER

INCHES

BACKFLOW

3/4" 1"

SIZE,

3" 2" 1 1/2"

4" 6"

8" 10"

8"

RATE,

GPM

DESIGN

DISCHARGE

SIZE,

RISER

2" 3"

INCHES

PIPE "Y"

4" 6"

4"

BLDG. INTERIOR

PROVIDE DOWNSPOUT NOZZLE

(LAMBS TONGUE) ON EXTERIOR

WALL FOR DISCHARGE PIPING

SUPPORT AS REQUIRED

NO SCALE

FIRE PUMP CONTROL PANEL (OPPOSITE WALL)

JOCKEY PUMP CONTROL PANEL (OPPOSITE WALL)

JOCKEY PUMP ( JP-1)

PRESSURE GUAGE

VALVE

WAFER CHECK VALVE

FIRE PUMP PACKAGE SKIDS

BUTTERFLY VALVE

8" FIRE MAIN

DOUBLE CHECK TYPE BACKFLOW PREVENTER

CHECK VALVE

PUMP BYPASS

TO COMBINED…