Attachment_D__Fire_Pump_test_form.docx

DOCX document 34 KB Posted

Attached to
Fire Suppression, Fire Alarm, Fire Sprinkler Systems Inspection, Testing & Maintenance, JBLM, WA
Solicitation number
W911S8-16-R-0006
Issued by

About this file

Attachment D Fire Pump Inspection Form

View the file

Other files

File Type Posted
W911S8-16-R-0006_0004_Fire_Suppression.pdf PDF
W911S8-16-R-0006-0004.pdf PDF
Attachment_E_PWS_W911S8-16-R-0006__Fire_Supp_6_March_2017.docx DOCX document
Amendment_3_-_W911S8-16-R-0006_Fire_Kitchen_Suppression_ITM_3-7-17.pdf PDF
TE_3_-_Revised_3-6-17.xlsx XLSX spreadsheet
Amended_QA_W911S8-16-R-0002_JBLM_Fire_Suppression_6_Mar_2017.docx DOCX document
QA_W911S8-16-R-0002_JBLM_Fire_Suppression_3_March_2017.pdf PDF
W911S8-16-R-0006-0002.pdf PDF
Pre-proposal_Conf_Slides_W911S8-16-R-0006_JBLM_Fire_Suppr_(7Feb2017).pptx PPTX presentation
Site_Visit_Attendee_List_2-7-17.pdf PDF
16-R-0006-0001.pdf PDF
TE_3_-_Revised_1-31-17.xlsx XLSX spreadsheet
Attachment_A_Fire_Alarm_Inspection_&_Testing_form.docx DOCX document
Attachment_E_PWS_W911S8-16-R-0006__Fire_Supp.docx DOCX document
Attachment_C_Sprinkler_System_test_form.docx DOCX document
Attachment_B_Kitchen_hood_suppression_form.doc DOC document
Technical_Exhibit_3_Contractor_Proposal_Data_Matrix.xlsx XLSX spreadsheet
Technical_Exhibit_1_Facilities_List.xlsx XLSX spreadsheet
Attachment_F_WD_15-5539_Rev_2_-_Pierce_County_1-23-17.docx DOCX document
Attachment_A2_Fire_Alarm_continuation_form.docx DOCX document
Exhibit_1_Daily_Inspection_Report.docx DOCX document
W911S8-16-R-0006_JBLM_Fire_Suppression_ITM.pdf PDF
Attachment_G_WD_15-2569_Yakima_County_-_1-23-17.docx DOCX document
Technical_Exhibit_2_Fire_Systems_Building_Devices.xlsx XLSX spreadsheet
Show all 24

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Company Name Lakewood, WA 98000 253-000-0000

SYSTEM #

FIRE PUMP SYSTEM

INSPECTION AND TESTING REPORT

Date
Building Name
Time
Address
Inspector
City, State, Zip
Contact
Phone

Monitoring Entity

Company

Phone

Account

Authority Having Jurisdiction

Name
Phone

Service: |_| Quarterly |_| Semi-Annually |_| Annually

Fire Pump type; electric |_| diesel |_| controller voltage without load with 100% load

Yes
No
N/A
2 YEAR, Control Valves, operate and lubricate valve to endure operability.
|_|
|_|
|_|
2 YEAR, Controllers, calibrate pressure switches.
|_|
|_|
|_|
2 YEAR, Controllers, exercise circuit breakers and switches to verify operability.
|_|
|_|
|_|
2 YEAR, Controllers, inspect fuses.
|_|
|_|
|_|
2 YEAR, Pumps, check coupling alignment to ensure that the shaft is aligned.
|_|
|_|
|_|
2 YEAR, Pumps, check pump shaft end play.
|_|
|_|
|_|
2 YEAR, Pump, lubricate bearings.
|_|
|_|
|_|
2 YEAR, Pump, lubricate couplings.
|_|
|_|
|_|
2 YEAR, Pump, lubricate right angle drives.
|_|
|_|
|_|
2 YEAR, Fuel, sample fuel to verify quality.
|_|
|_|
|_|
2 YEAR, Relief Valves, calibrate valves.
|_|
|_|
|_|
2 YEAR, Emergency Power Supply, test to verify availability and capability for pump motor.
|_|
|_|
|_|
5 YEAR, Pump, conduct flow test to verify pump output
|_|
|_|
|_|
System riser location
Size
Make
Model
Quick opening device |_|N/A
Make
Model
Date of last full trip
Trip Test
Water PSI
Air PSI
Trip Air PSI
Trip Time
sec
Water delivery
min sec
Waterflow test results
Main Drain Size
Static
Residual
Restore

Problems Found:

Corrections Made:

Comments:

This Testing Was Performed In Accordance With Applicable Standards

Inspector

Certificate

Date
Time

Inspector Signature

Site Representative
Date
Time

Signature

Fire Pump Information on page 2.

Fire Pump Information

Fire Pump #1 Information

Manufacturer
Type
Serial #
Comments:
RPM
Max Press
Impeller diameter
GPM

Fire Pump #2 Information: Hanger 0000

Manufacturer
Type
Serial #
Comments:
RPM
Max Press
Impeller diameter
GPM