Attachment_B_Kitchen_hood_suppression_form.doc

DOC document 814 KB Posted

Attached to
Fire Suppression, Fire Alarm, Fire Sprinkler Systems Inspection, Testing & Maintenance, JBLM, WA
Solicitation number
W911S8-16-R-0006
Issued by

About this file

Attachment B Kitchen Hood Inspection Form

View the file

Other files

File Type Posted
W911S8-16-R-0006_0004_Fire_Suppression.pdf PDF
W911S8-16-R-0006-0004.pdf PDF
Attachment_E_PWS_W911S8-16-R-0006__Fire_Supp_6_March_2017.docx DOCX document
Amendment_3_-_W911S8-16-R-0006_Fire_Kitchen_Suppression_ITM_3-7-17.pdf PDF
TE_3_-_Revised_3-6-17.xlsx XLSX spreadsheet
Amended_QA_W911S8-16-R-0002_JBLM_Fire_Suppression_6_Mar_2017.docx DOCX document
QA_W911S8-16-R-0002_JBLM_Fire_Suppression_3_March_2017.pdf PDF
W911S8-16-R-0006-0002.pdf PDF
Pre-proposal_Conf_Slides_W911S8-16-R-0006_JBLM_Fire_Suppr_(7Feb2017).pptx PPTX presentation
Site_Visit_Attendee_List_2-7-17.pdf PDF
16-R-0006-0001.pdf PDF
TE_3_-_Revised_1-31-17.xlsx XLSX spreadsheet
Attachment_A_Fire_Alarm_Inspection_&_Testing_form.docx DOCX document
Attachment_E_PWS_W911S8-16-R-0006__Fire_Supp.docx DOCX document
Attachment_C_Sprinkler_System_test_form.docx DOCX document
Attachment_D__Fire_Pump_test_form.docx DOCX document
Technical_Exhibit_3_Contractor_Proposal_Data_Matrix.xlsx XLSX spreadsheet
Technical_Exhibit_1_Facilities_List.xlsx XLSX spreadsheet
Attachment_F_WD_15-5539_Rev_2_-_Pierce_County_1-23-17.docx DOCX document
Attachment_A2_Fire_Alarm_continuation_form.docx DOCX document
Exhibit_1_Daily_Inspection_Report.docx DOCX document
W911S8-16-R-0006_JBLM_Fire_Suppression_ITM.pdf PDF
Attachment_G_WD_15-2569_Yakima_County_-_1-23-17.docx DOCX document
Technical_Exhibit_2_Fire_Systems_Building_Devices.xlsx XLSX spreadsheet
Show all 24

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Fire and Emergency Services

Joint Base Lewis-McChord

RANGE HOOD SYSTEM

Acceptance and Semi-Annual Certification

Facility Name:
DATE:
Building Number:
Address:

Procedure

Upon completion of the work, inspection and tests shall be made by the contractor’s representative and witnessed by an owner’s representative. All defects shall be corrected and system left in service before contractor’s personnel finally leave the job.

A certificate shall be filled out and signed by both representatives. Copies shall be prepared for approving authorities, owners and contractor. It is understood the owner’s representative’s signature in no way prejudices any claim against contractor for faulty material, poor workmanship, or failure to comply with approving authority’s requirements or local ordinances.

General Information
System Number of

System Manufacture;

FORMTEXT

FORMTEXT

FORMTEXT

FORMTEXT

FORMTEXT

Type of System: Wet Chemical FORMCHECKBOX Dry Chemical FORMCHECKBOX

CO2….. FORMCHECKBOX

H20 FORMCHECKBOX

System is free of any prior discharge, damage or tampering
FORMCHECKBOX

Yes FORMCHECKBOX No

Problems Found;

FORMTEXT

FORMTEXT

FORMTEXT

FORMTEXT

FORMTEXT

FORMTEXT

FORMTEXT

FORMTEXT

FORMTEXT

Cylinder
Pressure gauge or weight is at acceptable level.
FORMCHECKBOX
Date of last hydrostatic test of cylinder.
Date;
Last date pressurized dry chemical system had chemical examined.
Date;

Expellant gas cartridge; C02 FORMCHECKBOX psi Nitrogen FORMCHECKBOX pounds

Nozzles
Nozzles are in proper positions
FORMCHECKBOX
Nozzles are covered by blow-off caps
FORMCHECKBOX

Yes FORMCHECKBOX No

Pipe and Fittings
All piping and conduit is immobilized with proper hangers and brackets

Date fusible links last changed (Required Annually)

FORMCHECKBOX

Yes FORMCHECKBOX No

FORMTEXT

FORMTEXT

Operation
System operated properly from most remote fusible link
FORMCHECKBOX
System operated properly from all manual actuators
FORMCHECKBOX
Automatic shut down of fuel / power operated properly
FORMCHECKBOX

Yes FORMCHECKBOX No

EXHAUST SYSTEM
Exhaust system ON/ Return OFF at time of activation
FORMCHECKBOX

Yes FORMCHECKBOX No

Final Inspection
Is system alarmed
FORMCHECKBOX
All cooking surfaces are protected
FORMCHECKBOX
Inspection and service tag on system cylinder
FORMCHECKBOX
Is the hood and duct free from grease and sludge accumulation
FORMCHECKBOX
System is now fully operational and free from obstructions
FORMCHECKBOX

Yes FORMCHECKBOX No

Corrections Made

This range hood system has been evaluated in accordance with manufacturer’s recommendations and NFPA standards: 96, 17 & 17A

Performance Evaluation .
Name
Date
Agency:
Certification Number:
Address:
Phone #
Signature
Signature

IAW NFPA 96,17 &17A