This document contains a Job Work Order and associated Fire Alarm and Emergency Communication System Inspection and Testing Forms (NFPA 72, Fig. 14.6.2.4) for three buildings (501, 502, and 503) at the Hawaii Air National Guard facility in Wahiawa and Kahului, Hawaii.

The work order (Order #240230-4, dated 03/14/2025) documents service call testing and assessment of fire alarm systems for HAWK-NIKING, LLC across three buildings performed on 3/3/25 and 3/4/25 for 8 hours total. Building 501 contained a non-operational Quick Start Panel CPU and failed BPS power supply, with multiple failed audio/visual devices including SIGA-278 modules, 270-SPO devices, and G1RF-HDVM devices. Building 502 had both a non-operational Quick Start Panel CPU and a Monaco Panel lacking power, with extensive device failures including 10 pull stations, 14 heat detectors, 1 horn/strobe, and 4 bells; the new extension warehouse had no fire alarm devices. Building 503 contained a non-operational Monaco Panel with defective power supply and zone board, plus failed pull stations, heat detectors, and bells. The three formal NFPA 72 inspection and testing forms document comprehensive system failures across all control units, power supplies, notification appliances, and initiating devices with all components marked as FAIL in visual and functional testing. The follow-up action required is to provide a proposal to replace all defective and non-operational materials, with all three buildings determined to require full fire alarm system upgrades. Phoenix Pacific, Inc. (contact 808-682-1000) performed the inspections under NICET Level II certification.

View the file

Other files

Show all 26

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

DESCRIPTION:

CALL TYPE:

WORK PERFORMED: DATE OF SERVCE: 3/3/25 8HRS

PANEL CONDITION UPON ARRIVAL:

1) BLDG 501 PANEL CPU FAULT

2) BLDG 502 PANEL CPU FAULT

3) BLDG 503 PANEL NO POWER

PROBLEM FOUND:

Bldg. 501:

QUICK START PANEL - CPU IS NON-OPERATIONAL

Bldg. 502:

1) QUICK START PANEL - CPU IS NON-OPERATIONAL

2) MONACO PANEL - No Power - NON-OPERATIONAL

Bldg. 503:

MONACO PANEL - NON-OPERATIONAL POWER SUPPLY AND ZONE BOARD.

ACTIONS TAKEN:

BLDG 501:

1) TEST AUDIO/VISUAL AND VERIFY CONVENTIONAL DEVICES AND WIRING.

2) Tested 2each SIGA-278 - FAILED

3) Tested 4 each 270-SPO - FAILED

4) Tested 8 each G1RF-HDVM - FAILED

5) BPS POWER SUPPLY IS NON-OPERATIONAL

BLDG 502:

1) TEST AUDIO/VISUAL FOR QUICK START PANEL.

2) TESTED PULL STATION AND BELLS FOR MONACO PANEL. VERIFY WIRING FOR BOTH.

3) TESTED 10EA - PULL STATION - FAILED

4) TESTED 14EA HEAT DETECTOR - FAILED

5) TESTED 1EA HORN/STROBE - FAILED

6) TESTED 4EA BELLS - FAILED

7) FIRE PANEL, NEW EXTENSION WAREHOUSE DONT HAVE ANY FIRE ALARM DEVICE.

BLDG 503:

2045 Lauwiliwili St., Unit 101, Kapolei, HI 96707 Main: (808) 682-1000 info@phoenixpacificinc.com www.phoenixpacificinc.com

JOB WORK ORDER

ORDER #:

240230-4

DATE: 03/14/2025

CLIENT LOCATION: HAWK-NIKING, LLC

235 KELLOG STREET

WAHIAWA , HI 96786

BILLED TO:

HAWK-NIKING, LLC

235 KELLOG STREET

WAHIAWA , HI 96786

HIANG Maui 501, 502, 503 - Assess/troubelshoot and testing, Test & Inspect

10 - SERVICE

JohnS Callout 3/3 and 3/4/25 2d @ 8h (Reflected in test reports).

TEST ZONE AND VERIFY FIRE ALARM WIRING.

1) TESTED 1EA - PULL STATION - FAILED

2) TESTED 2EA - HEAT DETECTORS - FAILED

3) TESTED - 1EA BELL - FAILED

NOTE: ALL THREE BLDG. FIRE ALARM PANELS WILL NEED TO BE UPGRADED.

FOLLOW UP ACTIONS: PROVIDE PROPOSAL TO REPLACE DEFECTIVE/NON-OPERATIONAL MATERIALS

IMAGE ATTACHMENTS

Title: BLDG 503 BELL Date: Mar 5, 2025 12:00 AM Description: --

Title: BLDG 503 FACP Date: Mar 5, 2025 12:00 AM Description: --

Title: BLDG 502 FACP WATER DAMAGE Date: Mar 5, 2025 12:00 AM Description: --

Title: BLDG 502 FACP Date: Mar 5, 2025 12:00 AM Description: --

IS JOB COMPLETE? Yes DISC/CREDIT: $0.00

SALES TAX: $0.00

TAXABLE: $0.00

NON-TAXABLE: $0.00

DISCOUNT: $0.00

BALANCE $0.00

NET DUE: $0.00

Customer:

Date: 03/14/2025 01:50 PM

Employee: Dante Arriola Date: 03/14/2025 01:50 PM

TERMS AND CONDITIONS

I / We hereby authorize the above work to be done along with the necessary materials and grant Phoenix Pacific, Inc., or its employees permission to test and/or operate the unit to be worked on. An express mechanic's lien is hereby acknowledged to secure payment for the work performed. Payment is due upon completion of work if no prior arrangement has been cleared by Phoenix Pacific, Inc., for credit. I / We agree to pay later fees at the rate of 1-1/2% per month on all accounts remainig unpaid after the due date, plus attorney's fees if collection proceedings are instituted.

NFPA 72, Fig. 14.6.2.4 (p. 1 of 11)

Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution.

FIRE ALARM AND EMERGENCY COMMUNICATION SYSTEM INSPECTION AND TESTING FORM

To be completed by the system inspector or tester at the time of the inspection or test.

It shall be permitted to modify this form as needed to provide a more complete and/or clear record.

Insert N/A in all unused lines.

Attach additional sheets, data, or calculations as necessary to provide a complete record.

Date of this inspection or test: 3 MARCH 2025 Time of inspection or test: 0730AM

1. PROPERTY INFORMATION

Name of property: HIANG MAUI B501

Address: 75 KULEANA ST. KAHULUI

Description of property: OFFICE/ WEARHOUSE

Occupancy type:

Name of property representative: HAWAII AIR NATIONAL GUARD

Address:

Phone: Fax: E-mail:

Authority having jurisdiction over this property: HAWAII AIR NATIONAL GUARD

Phone: Fax: E-mail:

2. INSTALLATION, SERVICE, AND TESTING CONTRACTOR INFORMATION

Service and/or testing organization for this equipment: Phoenix Pacific INC.

Address: 2045 LAUWILIWILI STREET UNIT 101 KAPOLEI HI96707

Phone: 808-682-1000 Fax: 808-682-1047 E-mail: info@phoenixhawaii.com

Service technician or tester: J. Luce

Qualifications of technician or tester: NICET Level II, FireAlarm Systems, A contract for test and inspection in accordance with NFPA standards is in effect as of:

The contract expires: Contract number: Frequency of tests and inspections:

Monitoring organization for this equipment: Regional Dispatch Center, JBPH

A contract for test and inspection in accordance with NFPA standards is in effect as of:

Address: Bldg 167 JBPH

Phone: 808-4747-2222 Fax: E-mail:

Entity to which alarms are retransmitted: Phone:

3. TYPE OF SYSTEM OR SERVICE

Fire alarm system (nonvoice)

Fire alarm with in-building fire emergency voice alarm communication system (EVACS)

Mass notification system (MNS)

Combination system, with the following components:

Fire alarm EVACS MNS Two-way, in-building, emergency communication system

Other (specify):

NFPA 72, Fig. 14.6.2.4 (p. 2 of 11)

Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution.

3. TYPE OF SYSTEM OR SERVICE (continued)

NFPA 72 edition: 2019 Additional description of system(s):

3.1 Control Unit

Manufacturer: EDWARDS SYSTEM TECHNOLOGY Model number: QUICK START

3.2 Mass Notification System This system does not incorporate an MNS

3.2.1 System Type:

In-building MNS—combination

In-building MNS—stand-alone Wide-area MNS Distributed recipient MNS

Other (specify):

3.2.2 System Features:

Combination fire alarm/MNS MNS ACU only Wide-area MNS to regional national alerting interface

Local operating console (LOC) Direct recipient MNS (DRMNS) Wide-area MNS to DRMNS interface

Wide-area MNS to high-power speaker array (HPSA) interface In-building MNS to wide-area MNS interface

Other (specify):

3.3 System Documentation

An owner’s manual, a copy of the manufacturer’s instructions, a written sequence of operation, and a copy of the record record drawings are stored on site. Location: HAWAII AIR NATIONAL GUARD

3.4 System Software This system does not have alterable site-specific software.

Software revision number: 2.5 Software last updated on:

A copy of the site-specific software is stored on site. Location:

4. SYSTEM POWER

4.1 Control Unit

4.1.1 Primary Power

Input voltage of control panel: 120 Control panel amps: 20

4.1.2 Engine-Driven Generator This system does not have a generator.

Location of generator:

Location of fuel storage: Type of fuel:

4.1.3 Uninterruptible Power System This system does not have UPS.

Equipment powered by a UPS system:

Location of UPS system:

Calculated capacity of UPS batteries to drive the system components connected to it:

In standby mode (hours): In alarm mode (minutes):

NFPA 72, Fig. 14.6.2.4 (p. 3 of 11)

Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution.

4. SYSTEM POWER (continued)

4.1.4 Batteries

Location: By Fire Alarm Control Panel

Type: Interstate Nominal voltage: 12V Amp/hour rating: 18Ah

Calculated capacity of batteries to drive the system:

In standby mode (hours): In alarm mode (minutes):

Batteries are marked with date of manufacture.

4.2 In-Building Fire Emergency Voice Alarm Communication System or Mass Notification System

This system does not have an EVACS or MNS.

4.2.1 Primary Power

Input voltage of EVACS or MNS panel: 120 V EVACS or MNS panel amps:

4.2.2 Engine-Driven Generator This system does not have a generator.

Location of generator:

Location of fuel storage: Type of fuel:

4.2.3 Uninterruptible Power System This system does not have a UPS.

Equipment powered by a UPS system:

Location of UPS system:

Calculated capacity of UPS batteries to drive the system components connected to it:

In standby mode (hours): In alarm mode (minutes):

4.2.4 Batteries

Location: Type: Nominal voltage: Amp/hour rating:

Calculated capacity of batteries to drive the system:

In standby mode (hours): In alarm mode (minutes):

Batteries are marked with date of manufacture.

4.3 Notification Appliance Power Extender Panels This system does not have power extender panels.

4.3.1 Primary Power

Input voltage of power extender panel(s): Power extender panel amps:

4.3.2 Engine-Driven Generator This system does not have a generator.

Location of generator:

Location of fuel storage: Type of fuel:

4.3.3 Uninterruptible Power System This system does not have a UPS.

Equipment powered by a UPS system:

Location of UPS system:

NFPA 72, Fig. 14.6.2.4 (p. 4 of 11)

Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution.

4.3.4 Batteries

Location: Type: Nominal voltage: Amp/hour rating:

Calculated capacity of batteries to drive the system:

In standby mode (hours): In alarm mode (minutes):

Batteries are marked with date of manufacture.

5. ANNUNCIATORS This system does not have annunciators.

5.1 Location and Description of Annunciators

Annunciator 1:

Annunciator 2:

Annunciator 3:

6. NOTIFICATIONS MADE PRIOR TO TESTING

Monitoring organization Contact: Time:

Building management Contact: Time:

Building occupants Contact: Time:

Authority having jurisdiction Contact: Time:

Other, if required Contact: Time:

7. TESTING RESULTS

7.1 Control Unit and Related Equipment

Description Visual

Inspection Functional

Test Comments

Control unit FAIL

Lamps/LEDs/LCDs FAIL

Fuses

Trouble signals FAIL

Disconnect switches

Ground-fault monitoring

Supervision FAIL

Local annunciator FAIL

Remote annunciators

Power extender panels FAIL

Isolation modules

Other (specify)

NFPA 72, Fig. 14.6.2.4 (p. 5 of 11)

Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution.

7. TESTING RESULTS (continued)

7.2 Control Unit Power Supplies

Description Visual

Inspection Functional

Test Comments

120-volt power

Generator or UPS

Battery condition FAIL

Load voltage FAIL

Discharge test FAIL

Charger test FAIL

Other (specify)

7.3 In-Building Fire Emergency Voice Alarm Communications Equipment

Description Visual

Inspection Functional

Test Comments

Control unit

Lamps/LEDs/LCDs

Fuses

Primary power supply

Secondary power supply

Trouble signals

Disconnect switches

Ground-fault monitoring

Panel supervision

System performance

Sound pressure levels

Occupied Yes No

Ambient dBA

Alarm dBA

(attach report with locations, values, and weather conditions)

System intelligibility

CSI STI

(attach report with locations, values, and weather conditions)

NFPA 72, Fig. 14.6.2.4 (p. 6 of 11)

Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution.

7.4 Notification Appliance Power Extender Panels

Description Visual

Inspection Functional

Test Comments

Lamps/LEDs/LCDs FAIL

Fuses

Primary power supply

Secondary power supply FAIL

Trouble signals

Ground-fault monitoring

Panel supervision FAIL

Other (specify)

7.5 Mass Notification Equipment

Description Visual

Inspection Functional

Test Comments

Functional test

Reset/power down test

Fuses

Primary power supply

UPS power test

Trouble signals

Disconnect switches

Ground-fault monitoring

CCU security mechanism

Prerecorded message content

Prerecorded message activation

Software backup performed

Test backup software

Fire alarm to MNS interface

MNS to fire alarm interface

In-building MNS to wide-area

MNS

NFPA 72, Fig. 14.6.2.4 (p. 7 of 11)

Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution.

7.5 Mass Notification Equipment (continued)

Description Visual

Inspection Functional

Test Comments

MNS to direct recipient MNS

(attach report with locations, values, and weather conditions)

System intelligibility

CSI STI

7.6 Two-Way Communications Equipment

Description Visual

Inspection Functional

Test Comments

Phone handsets

Phone jacks

Off-hook indicator

Call-in signal

System performance

System audibility

System intelligibility

Radio communications enhancement system

Area of refuge communication system

Elevator emergency communications system

NFPA 72, Fig. 14.6.2.4 (p. 8 of 11)

Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution.

7.7 Combination Systems

Description Visual

Inspection Functional

Test Comments

Fire extinguishing monitoring devices/system

Carbon monoxide detector/system

Combination fire/security system

Other (specify)

7.8 Special Hazard Systems

Description (specify) Visual

Inspection Functional

Test Comments

7.9 Emergency Communications System

Visual

Functional

Simulated operation

Ensure predischarge notification appliances of special hazard systems are not overridden by the MNS.

See NFPA 72, 24.4.1.7.1.

7.10 Monitored Systems

Description (specify) Visual

Inspection Functional

Test Comments

Engine-driven generator

Fire pump

Special suppression systems

NFPA 72, Fig. 14.6.2.4 (p. 9 of 11)

Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution.

7.11 Auxiliary Functions

Description Visual

Inspection Functional

Test Comments

Door-releasing devices

Fan shutdown

Smoke management/smoke control

Smoke damper operation

Smoke shutter release

Door unlocking

Elevator recall

Elevator shunt trip

MNS override of FA signals

Other (specify)

7.12 Alarm Initiating Device

Device test results sheet attached listing all devices tested and the results of the testing

7.13 Supervisory Alarm Initiating Device

Device test results sheet attached listing all devices tested and the results of the testing

7.14 Alarm Notification Appliances

Appliance test results sheet attached listing all appliances tested and the results of the testing

7.15 Supervisory Station Monitoring

Description Visual

Inspection Functional

Test Time Comments

Alarm signal FAIL

Alarm restoration FAIL

Trouble signal FAIL

Trouble restoration FAIL

Supervisory signal FAIL

Supervisory restoration FAIL

NFPA 72, Fig. 14.6.2.4 (p. 10 of 11)

Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution.

8. NOTIFICATIONS THAT TESTING IS COMPLETE

Monitoring organization Contact: Time:

Building management Contact: Time:

Building occupants Contact: Time:

Authority having jurisdiction Contact: Time:

Other, if required Contact: Time:

9. SYSTEM RESTORED TO NORMAL OPERATION

Date: Time:

10. CERTIFICATION

10.1 Inspector Certification:

This system, as specified herein, has been inspected and tested according to all NFPA standards cited herein.

Signed: Printed name: Dante arriola Date: 03 MARCH 25

Organization: Phoenix Pacific Title: TECH Phone: 808-682-1000

10.2 Acceptance by Owner or Owner’s Representative:

The undersigned has a service contract for this system in effect as of the date shown below.

Signed: Printed name: Date:

Organization: Title: Phone:

NFPA 72, Fig. 14.6.2.4 (p. 11 of 11)

Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution.

DEVICE TEST RESULTS

(Attach additional sheets if required)

Device Type Address Location Test Results

PULL STATION ALL EXIT DOOR ALL FAIL

HORN/STROBE IN BLDG ALL FAIL

Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution.

To be completed by the system inspector or tester at the time of the inspection or test.

It shall be permitted to modify this form as needed to provide a more complete and/or clear record.

Date of this inspection or test: 3 MARCH 2025 Time of inspection or test: 12:00PM

Name of property: HIANG MAUI B502

Address: 75 KULEANA ST. KAHULUI

Description of property: OFFICE/ WEARHOUSE

Occupancy type:

Name of property representative: HAWAII AIR NATIONAL GUARD

Address:

Phone: Fax: E-mail:

Authority having jurisdiction over this property: HAWAII AIR NATIONAL GUARD

Phone: Fax: E-mail:

2. INSTALLATION, SERVICE, AND TESTING CONTRACTOR INFORMATION

Service and/or testing organization for this equipment: Phoenix Pacific INC.

Address: 2045 LAUWILIWILI STREET UNIT 101 KAPOLEI HI96707

Phone: 808-682-1000 Fax: 808-682-1047 E-mail: info@phoenixhawaii.com

Service technician or tester: J. Luce

Qualifications of technician or tester: NICET Level II, FireAlarm Systems, A contract for test and inspection in accordance with NFPA standards is in effect as of:

The contract expires: Contract number: Frequency of tests and inspections:

Monitoring organization for this equipment: Regional Dispatch Center, JBPH

A contract for test and inspection in accordance with NFPA standards is in effect as of:

Address: Bldg 167 JBPH

Phone: 808-4747-2222 Fax: E-mail:

Entity to which alarms are retransmitted: Phone:

3. TYPE OF SYSTEM OR SERVICE

Fire alarm system (nonvoice)

Fire alarm with in-building fire emergency voice alarm communication system (EVACS)

Mass notification system (MNS)

Combination system, with the following components:

Fire alarm EVACS MNS Two-way, in-building, emergency communication system

Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution.

NFPA 72 edition: 2019 Additional description of system(s):

3.1 Control Unit

Manufacturer: EDWARDS SYSTEM TECHNOLOGY Model number: QUICK START

3.2 Mass Notification System This system does not incorporate an MNS

3.2.1 System Type:

In-building MNS—combination

In-building MNS—stand-alone Wide-area MNS Distributed recipient MNS

Other (specify):

3.2.2 System Features:

Combination fire alarm/MNS MNS ACU only Wide-area MNS to regional national alerting interface

Local operating console (LOC) Direct recipient MNS (DRMNS) Wide-area MNS to DRMNS interface

Wide-area MNS to high-power speaker array (HPSA) interface In-building MNS to wide-area MNS interface

Other (specify):

3.3 System Documentation

An owner’s manual, a copy of the manufacturer’s instructions, a written sequence of operation, and a copy of the record record drawings are stored on site. Location: HAWAII AIR NATIONAL GUARD

3.4 System Software This system does not have alterable site-specific software.

Software revision number: 2.5 Software last updated on:

A copy of the site-specific software is stored on site. Location:

4. SYSTEM POWER

4.1 Control Unit

4.1.1 Primary Power

Input voltage of control panel: 120 Control panel amps: 20

4.1.2 Engine-Driven Generator This system does not have a generator.

Location of generator:

Location of fuel storage: Type of fuel:

4.1.3 Uninterruptible Power System This system does not have UPS.

Equipment powered by a UPS system:

Location of UPS system:

Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution.

4.1.4 Batteries

Location: Fire Alarm Control Panel

Type: Nominal voltage: 12V Amp/hour rating: 18Ah

Calculated capacity of batteries to drive the system:

In standby mode (hours): In alarm mode (minutes):

Batteries are marked with date of manufacture.

4.2 In-Building Fire Emergency Voice Alarm Communication System or Mass Notification System

This system does not have an EVACS or MNS.

4.2.1 Primary Power

Input voltage of EVACS or MNS panel: 120 V EVACS or MNS panel amps:

4.2.2 Engine-Driven Generator This system does not have a generator.

Location of generator:

Location of fuel storage: Type of fuel:

4.2.3 Uninterruptible Power System This system does not have a UPS.

Equipment powered by a UPS system:

Location of UPS system:

Calculated capacity of UPS batteries to drive the system components connected to it:

In standby mode (hours): In alarm mode (minutes):

4.2.4 Batteries

Location: Type: Nominal voltage: Amp/hour rating:

Calculated capacity of batteries to drive the system:

In standby mode (hours): In alarm mode (minutes):

Batteries are marked with date of manufacture.

4.3 Notification Appliance Power Extender Panels This system does not have power extender panels.

4.3.1 Primary Power

Input voltage of power extender panel(s): Power extender panel amps:

4.3.2 Engine-Driven Generator This system does not have a generator.

Location of generator:

Location of fuel storage: Type of fuel:

4.3.3 Uninterruptible Power System This system does not have a UPS.

Equipment powered by a UPS system:

Location of UPS system:

Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution.

Location: Type: Nominal voltage: Amp/hour rating:

Calculated capacity of batteries to drive the system:

In standby mode (hours): In alarm mode (minutes):

Batteries are marked with date of manufacture.

5. ANNUNCIATORS This system does not have annunciators.

5.1 Location and Description of Annunciators

Annunciator 1:

Annunciator 2:

Annunciator 3:

6. NOTIFICATIONS MADE PRIOR TO TESTING

Monitoring organization Contact: Time:

Building management Contact: Time:

Building occupants Contact: Time:

Authority having jurisdiction Contact: Time:

Other, if required Contact: Time:

7. TESTING RESULTS

7.1 Control Unit and Related Equipment

Description Visual

Inspection Functional

Test Comments

Control unit FAIL

Lamps/LEDs/LCDs FAIL

Fuses

Trouble signals FAIL

Disconnect switches

Ground-fault monitoring

Supervision FAIL

Local annunciator FAIL

Remote annunciators

Power extender panels FAIL

Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution.

7.2 Control Unit Power Supplies

Description Visual

Inspection Functional

Test Comments

120-volt power

Generator or UPS

Battery condition FAIL

Load voltage FAIL

Discharge test FAIL

Charger test FAIL

Other (specify)

7.3 In-Building Fire Emergency Voice Alarm Communications Equipment

Description Visual

Inspection Functional

Test Comments

Control unit

Lamps/LEDs/LCDs

Fuses

Primary power supply

Secondary power supply

Trouble signals

Disconnect switches

Ground-fault monitoring

Panel supervision

System performance

(attach report with locations, values, and weather conditions)

System intelligibility

CSI STI

Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution.

7.4 Notification Appliance Power Extender Panels

Description Visual

Inspection Functional

Test Comments

Lamps/LEDs/LCDs FAIL

Fuses

Primary power supply

Secondary power supply FAIL

Trouble signals

Ground-fault monitoring

Panel supervision FAIL

Other (specify)

7.5 Mass Notification Equipment

Description Visual

Inspection Functional

Test Comments

Functional test

Reset/power down test

Fuses

Primary power supply

UPS power test

Trouble signals

Disconnect switches

Ground-fault monitoring

CCU security mechanism

Prerecorded message content

Prerecorded message activation

Software backup performed

Test backup software

Fire alarm to MNS interface

MNS to fire alarm interface

Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution.

7.5 Mass Notification Equipment (continued)

Description Visual

Inspection Functional

Test Comments

MNS to direct recipient MNS

(attach report with locations, values, and weather conditions)

System intelligibility

CSI STI

Description Visual

Inspection Functional

Test Comments

Phone handsets

Phone jacks

Off-hook indicator

Call-in signal

System performance

System audibility

System intelligibility

Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution.

7.7 Combination Systems

Description Visual

Inspection Functional

Test Comments

Other (specify)

7.8 Special Hazard Systems

Description (specify) Visual

Inspection

Functional

Simulated operation

Ensure predischarge notification appliances of special hazard systems are not overridden by the MNS.

See NFPA 72, 24.4.1.7.1.

7.10 Monitored Systems

Description (specify) Visual

Inspection Functional

Test Comments

Engine-driven generator

Fire pump

Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution.

7.11 Auxiliary Functions

Description Visual

Inspection Functional

Test Comments

Door-releasing devices

Fan shutdown

Smoke management/smoke control

Smoke damper operation

Smoke shutter release

Door unlocking

Elevator recall

Elevator shunt trip

MNS override of FA signals

Other (specify)

7.12 Alarm Initiating Device

Device test results sheet attached listing all devices tested and the results of the testing

7.13 Supervisory Alarm Initiating Device

Device test results sheet attached listing all devices tested and the results of the testing

7.14 Alarm Notification Appliances

Appliance test results sheet attached listing all appliances tested and the results of the testing

7.15 Supervisory Station Monitoring

Description Visual

Inspection Functional

Test Time Comments

Alarm signal FAIL

Alarm restoration FAIL

Trouble signal FAIL

Trouble restoration FAIL

Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution.

Monitoring organization Contact: Time:

Building management Contact: Time:

Building occupants Contact: Time:

Authority having jurisdiction Contact: Time:

Other, if required Contact: Time:

9. SYSTEM RESTORED TO NORMAL OPERATION

Date: Time:

10. CERTIFICATION

10.1 Inspector Certification:

This system, as specified herein, has been inspected and tested according to all NFPA standards cited herein.

Signed: Printed name: Dante arriola Date: 03 MARCH 25

Organization: Phoenix Pacific Title: TECH Phone: 808-682-1000

10.2 Acceptance by Owner or Owner’s Representative:

The undersigned has a service contract for this system in effect as of the date shown below.

Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution.

PULL STATION ALL EXIT DOOR ALL FAIL

HEAT DETECTOR IN BLDG ALL FAIL

HORN/STROBE IN BLDG FAIL

BELL IN BLDG ALL FAIL

Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution.

To be completed by the system inspector or tester at the time of the inspection or test.

It shall be permitted to modify this form as needed to provide a more complete and/or clear record.

Date of this inspection or test: 4 MARCH 2025 Time of inspection or test: 7:30AM

Name of property: HIANG MAUI B503

Address: 75 KULEANA ST. KAHULUI

Description of property: OFFICE/ WEARHOUSE

Occupancy type:

Name of property representative: HAWAII AIR NATIONAL GUARD

Address:

Phone: Fax: E-mail:

Authority having jurisdiction over this property: HAWAII AIR NATIONAL GUARD

Phone: Fax: E-mail:

2. INSTALLATION, SERVICE, AND TESTING CONTRACTOR INFORMATION

Service and/or testing organization for this equipment: Phoenix Pacific INC.

Address: 2045 LAUWILIWILI STREET UNIT 101 KAPOLEI HI96707

Phone: 808-682-1000 Fax: 808-682-1047 E-mail: info@phoenixhawaii.com

Service technician or tester: J. Luce

Qualifications of technician or tester: NICET Level II, FireAlarm Systems, A contract for test and inspection in accordance with NFPA standards is in effect as of:

The contract expires: Contract number: Frequency of tests and inspections:

Monitoring organization for this equipment: Regional Dispatch Center, JBPH

A contract for test and inspection in accordance with NFPA standards is in effect as of:

Address: Bldg 167 JBPH

Phone: 808-4747-2222 Fax: E-mail:

Entity to which alarms are retransmitted: Phone:

3. TYPE OF SYSTEM OR SERVICE

Fire alarm system (nonvoice)

Fire alarm with in-building fire emergency voice alarm communication system (EVACS)

Mass notification system (MNS)

Combination system, with the following components:

Fire alarm EVACS MNS Two-way, in-building, emergency communication system

Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution.

NFPA 72 edition: 2019 Additional description of system(s):

3.1 Control Unit

Manufacturer: MONACO ENTERPRISES Model number: 220-004

3.2 Mass Notification System This system does not incorporate an MNS

3.2.1 System Type:

In-building MNS—combination

In-building MNS—stand-alone Wide-area MNS Distributed recipient MNS

Other (specify):

3.2.2 System Features:

Combination fire alarm/MNS MNS ACU only Wide-area MNS to regional national alerting interface

Local operating console (LOC) Direct recipient MNS (DRMNS) Wide-area MNS to DRMNS interface

Wide-area MNS to high-power speaker array (HPSA) interface In-building MNS to wide-area MNS interface

Other (specify):

3.3 System Documentation

An owner’s manual, a copy of the manufacturer’s instructions, a written sequence of operation, and a copy of the record record drawings are stored on site. Location: HAWAII AIR NATIONAL GUARD

3.4 System Software This system does not have alterable site-specific software.

Software revision number: Software last updated on:

A copy of the site-specific software is stored on site. Location:

4. SYSTEM POWER

4.1 Control Unit

4.1.1 Primary Power

Input voltage of control panel: 120 Control panel amps: 20

4.1.2 Engine-Driven Generator This system does not have a generator.

Location of generator:

Location of fuel storage: Type of fuel:

4.1.3 Uninterruptible Power System This system does not have UPS.

Equipment powered by a UPS system:

Location of UPS system:

Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution.

4.1.4 Batteries

Location: Fire Alarm Control Panel

Type: Nominal voltage: 12V Amp/hour rating: 7Ah

Calculated capacity of batteries to drive the system:

In standby mode (hours): In alarm mode (minutes):

Batteries are marked with date of manufacture.

4.2 In-Building Fire Emergency Voice Alarm Communication System or Mass Notification System

This system does not have an EVACS or MNS.

4.2.1 Primary Power

Input voltage of EVACS or MNS panel: EVACS or MNS panel amps:

4.2.2 Engine-Driven Generator This system does not have a generator.

Location of generator:

Location of fuel storage: Type of fuel:

4.2.3 Uninterruptible Power System This system does not have a UPS.

Equipment powered by a UPS system:

Location of UPS system:

Calculated capacity of UPS batteries to drive the system components connected to it:

In standby mode (hours): In alarm mode (minutes):

4.2.4 Batteries

Location: Type: Nominal voltage: Amp/hour rating:

Calculated capacity of batteries to drive the system:

In standby mode (hours): In alarm mode (minutes):

Batteries are marked with date of manufacture.

4.3 Notification Appliance Power Extender Panels This system does not have power extender panels.

4.3.1 Primary Power

Input voltage of power extender panel(s): Power extender panel amps:

4.3.2 Engine-Driven Generator This system does not have a generator.

Location of generator:

Location of fuel storage: Type of fuel:

4.3.3 Uninterruptible Power System This system does not have a UPS.

Equipment powered by a UPS system:

Location of UPS system:

Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution.

Location: Type: Nominal voltage: Amp/hour rating:

Calculated capacity of batteries to drive the system:

In standby mode (hours): In alarm mode (minutes):

Batteries are marked with date of manufacture.

5. ANNUNCIATORS This system does not have annunciators.

5.1 Location and Description of Annunciators

Annunciator 1:

Annunciator 2:

Annunciator 3:

6. NOTIFICATIONS MADE PRIOR TO TESTING

Monitoring organization Contact: Time:

Building management Contact: Time:

Building occupants Contact: Time:

Authority having jurisdiction Contact: Time:

Other, if required Contact: Time:

7. TESTING RESULTS

7.1 Control Unit and Related Equipment

Description Visual

Inspection Functional

Test Comments

Control unit FAIL

Lamps/LEDs/LCDs FAIL

Fuses

Trouble signals FAIL

Disconnect switches

Ground-fault monitoring

Supervision FAIL

Local annunciator FAIL

Remote annunciators

Power extender panels FAIL

Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution.

7.2 Control Unit Power Supplies

Description Visual

Inspection Functional

Test Comments

120-volt power

Generator or UPS

Battery condition FAIL

Load voltage FAIL

Discharge test FAIL

Charger test FAIL

Other (specify)

7.3 In-Building Fire Emergency Voice Alarm Communications Equipment

Description Visual

Inspection Functional

Test Comments

Control unit

Lamps/LEDs/LCDs

Fuses

Primary power supply

Secondary power supply

Trouble signals

Disconnect switches

Ground-fault monitoring

Panel supervision

System performance

(attach report with locations, values, and weather conditions)

System intelligibility

CSI STI

Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution.

7.4 Notification Appliance Power Extender Panels

Description Visual

Inspection Functional

Test Comments

Lamps/LEDs/LCDs FAIL

Fuses

Primary power supply

Secondary power supply FAIL

Trouble signals

Ground-fault monitoring

Panel supervision FAIL

Other (specify)

7.5 Mass Notification Equipment

Description Visual

Inspection Functional

Test Comments

Functional test

Reset/power down test

Fuses

Primary power supply

UPS power test

Trouble signals

Disconnect switches

Ground-fault monitoring

CCU security mechanism

Prerecorded message content

Prerecorded message activation

Software backup performed

Test backup software

Fire alarm to MNS interface

MNS to fire alarm interface

Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution.

7.5 Mass Notification Equipment (continued)

Description Visual

Inspection Functional

Test Comments

MNS to direct recipient MNS

(attach report with locations, values, and weather conditions)

System intelligibility

CSI STI

Description Visual

Inspection Functional

Test Comments

Phone handsets

Phone jacks

Off-hook indicator

Call-in signal

System performance

System audibility

System intelligibility

Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution.

7.7 Combination Systems

Description Visual

Inspection Functional

Test Comments

Other (specify)

7.8 Special Hazard Systems

Description (specify) Visual

Inspection

Functional

Simulated operation

Ensure predischarge notification appliances of special hazard systems are not overridden by the MNS.

See NFPA 72, 24.4.1.7.1.

7.10 Monitored Systems

Description (specify) Visual

Inspection Functional

Test Comments

Engine-driven generator

Fire pump

Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution.

7.11 Auxiliary Functions

Description Visual

Inspection Functional

Test Comments

Door-releasing devices

Fan shutdown

Smoke management/smoke control

Smoke damper operation

Smoke shutter release

Door unlocking

Elevator recall

Elevator shunt trip

MNS override of FA signals

Other (specify)

7.12 Alarm Initiating Device

Device test results sheet attached listing all devices tested and the results of the testing

7.13 Supervisory Alarm Initiating Device

Device test results sheet attached listing all devices tested and the results of the testing

7.14 Alarm Notification Appliances

Appliance test results sheet attached listing all appliances tested and the results of the testing

7.15 Supervisory Station Monitoring

Description Visual

Inspection Functional

Test Time Comments

Alarm signal FAIL

Alarm restoration FAIL

Trouble signal FAIL

Trouble restoration FAIL

Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution.

Monitoring organization Contact: Time:

Building management Contact: Time:

Building occupants Contact: Time:

Authority having jurisdiction Contact: Time:

Other, if required Contact: Time:

9. SYSTEM RESTORED TO NORMAL OPERATION

Date: Time:

10. CERTIFICATION

10.1 Inspector Certification:

This system, as specified herein, has been inspected and tested according to all NFPA standards cited herein.

Signed: Printed name: Dante arriola Date: 03 MARCH 25

Organization: Phoenix Pacific Title: TECH Phone: 808-682-1000

10.2 Acceptance by Owner or Owner’s Representative:

The undersigned has a service contract for this system in effect as of the date shown below.

Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution.

PULL STATION ALL EXIT DOOR FAIL

HEAT DETECTOR IN BLDG ALL FAIL

BELL IN BLDG FAIL