Pages from FA Inspection Report - MAUI.pdf
PDF 4 MB Posted
- Solicitation number
- W50SLF26QA009
- Issued by
-
Department of the Army National Guard
About this file
This document contains a Job Work Order and associated Fire Alarm and Emergency Communication System Inspection and Testing Forms (NFPA 72, Fig. 14.6.2.4) for three buildings (501, 502, and 503) at the Hawaii Air National Guard facility in Wahiawa and Kahului, Hawaii.
The work order (Order #240230-4, dated 03/14/2025) documents service call testing and assessment of fire alarm systems for HAWK-NIKING, LLC across three buildings performed on 3/3/25 and 3/4/25 for 8 hours total. Building 501 contained a non-operational Quick Start Panel CPU and failed BPS power supply, with multiple failed audio/visual devices including SIGA-278 modules, 270-SPO devices, and G1RF-HDVM devices. Building 502 had both a non-operational Quick Start Panel CPU and a Monaco Panel lacking power, with extensive device failures including 10 pull stations, 14 heat detectors, 1 horn/strobe, and 4 bells; the new extension warehouse had no fire alarm devices. Building 503 contained a non-operational Monaco Panel with defective power supply and zone board, plus failed pull stations, heat detectors, and bells. The three formal NFPA 72 inspection and testing forms document comprehensive system failures across all control units, power supplies, notification appliances, and initiating devices with all components marked as FAIL in visual and functional testing. The follow-up action required is to provide a proposal to replace all defective and non-operational materials, with all three buildings determined to require full fire alarm system upgrades. Phoenix Pacific, Inc. (contact 808-682-1000) performed the inspections under NICET Level II certification.
View the file
Other files
Show all 26
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DESCRIPTION:
CALL TYPE:
WORK PERFORMED: DATE OF SERVCE: 3/3/25 8HRS
PANEL CONDITION UPON ARRIVAL:
1) BLDG 501 PANEL CPU FAULT
2) BLDG 502 PANEL CPU FAULT
3) BLDG 503 PANEL NO POWER
PROBLEM FOUND:
Bldg. 501:
QUICK START PANEL - CPU IS NON-OPERATIONAL
Bldg. 502:
1) QUICK START PANEL - CPU IS NON-OPERATIONAL
2) MONACO PANEL - No Power - NON-OPERATIONAL
Bldg. 503:
MONACO PANEL - NON-OPERATIONAL POWER SUPPLY AND ZONE BOARD.
ACTIONS TAKEN:
BLDG 501:
1) TEST AUDIO/VISUAL AND VERIFY CONVENTIONAL DEVICES AND WIRING.
2) Tested 2each SIGA-278 - FAILED
3) Tested 4 each 270-SPO - FAILED
4) Tested 8 each G1RF-HDVM - FAILED
5) BPS POWER SUPPLY IS NON-OPERATIONAL
BLDG 502:
1) TEST AUDIO/VISUAL FOR QUICK START PANEL.
2) TESTED PULL STATION AND BELLS FOR MONACO PANEL. VERIFY WIRING FOR BOTH.
3) TESTED 10EA - PULL STATION - FAILED
4) TESTED 14EA HEAT DETECTOR - FAILED
5) TESTED 1EA HORN/STROBE - FAILED
6) TESTED 4EA BELLS - FAILED
7) FIRE PANEL, NEW EXTENSION WAREHOUSE DONT HAVE ANY FIRE ALARM DEVICE.
BLDG 503:
2045 Lauwiliwili St., Unit 101, Kapolei, HI 96707 Main: (808) 682-1000 info@phoenixpacificinc.com www.phoenixpacificinc.com
JOB WORK ORDER
ORDER #:
240230-4
DATE: 03/14/2025
CLIENT LOCATION: HAWK-NIKING, LLC
235 KELLOG STREET
WAHIAWA , HI 96786
BILLED TO:
HAWK-NIKING, LLC
235 KELLOG STREET
WAHIAWA , HI 96786
HIANG Maui 501, 502, 503 - Assess/troubelshoot and testing, Test & Inspect
10 - SERVICE
JohnS Callout 3/3 and 3/4/25 2d @ 8h (Reflected in test reports).
TEST ZONE AND VERIFY FIRE ALARM WIRING.
1) TESTED 1EA - PULL STATION - FAILED
2) TESTED 2EA - HEAT DETECTORS - FAILED
3) TESTED - 1EA BELL - FAILED
NOTE: ALL THREE BLDG. FIRE ALARM PANELS WILL NEED TO BE UPGRADED.
FOLLOW UP ACTIONS: PROVIDE PROPOSAL TO REPLACE DEFECTIVE/NON-OPERATIONAL MATERIALS
IMAGE ATTACHMENTS
Title: BLDG 503 BELL Date: Mar 5, 2025 12:00 AM Description: --
Title: BLDG 503 FACP Date: Mar 5, 2025 12:00 AM Description: --
Title: BLDG 502 FACP WATER DAMAGE Date: Mar 5, 2025 12:00 AM Description: --
Title: BLDG 502 FACP Date: Mar 5, 2025 12:00 AM Description: --
IS JOB COMPLETE? Yes DISC/CREDIT: $0.00
SALES TAX: $0.00
TAXABLE: $0.00
NON-TAXABLE: $0.00
DISCOUNT: $0.00
BALANCE $0.00
NET DUE: $0.00
Customer:
Date: 03/14/2025 01:50 PM
Employee: Dante Arriola Date: 03/14/2025 01:50 PM
TERMS AND CONDITIONS
I / We hereby authorize the above work to be done along with the necessary materials and grant Phoenix Pacific, Inc., or its employees permission to test and/or operate the unit to be worked on. An express mechanic's lien is hereby acknowledged to secure payment for the work performed. Payment is due upon completion of work if no prior arrangement has been cleared by Phoenix Pacific, Inc., for credit. I / We agree to pay later fees at the rate of 1-1/2% per month on all accounts remainig unpaid after the due date, plus attorney's fees if collection proceedings are instituted.
NFPA 72, Fig. 14.6.2.4 (p. 1 of 11)
Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution.
FIRE ALARM AND EMERGENCY COMMUNICATION SYSTEM INSPECTION AND TESTING FORM
To be completed by the system inspector or tester at the time of the inspection or test.
It shall be permitted to modify this form as needed to provide a more complete and/or clear record.
Insert N/A in all unused lines.
Attach additional sheets, data, or calculations as necessary to provide a complete record.
Date of this inspection or test: 3 MARCH 2025 Time of inspection or test: 0730AM
1. PROPERTY INFORMATION
Name of property: HIANG MAUI B501
Address: 75 KULEANA ST. KAHULUI
Description of property: OFFICE/ WEARHOUSE
Occupancy type:
Name of property representative: HAWAII AIR NATIONAL GUARD
Address:
Phone: Fax: E-mail:
Authority having jurisdiction over this property: HAWAII AIR NATIONAL GUARD
Phone: Fax: E-mail:
2. INSTALLATION, SERVICE, AND TESTING CONTRACTOR INFORMATION
Service and/or testing organization for this equipment: Phoenix Pacific INC.
Address: 2045 LAUWILIWILI STREET UNIT 101 KAPOLEI HI96707
Phone: 808-682-1000 Fax: 808-682-1047 E-mail: info@phoenixhawaii.com
Service technician or tester: J. Luce
Qualifications of technician or tester: NICET Level II, FireAlarm Systems, A contract for test and inspection in accordance with NFPA standards is in effect as of:
The contract expires: Contract number: Frequency of tests and inspections:
Monitoring organization for this equipment: Regional Dispatch Center, JBPH
A contract for test and inspection in accordance with NFPA standards is in effect as of:
Address: Bldg 167 JBPH
Phone: 808-4747-2222 Fax: E-mail:
Entity to which alarms are retransmitted: Phone:
3. TYPE OF SYSTEM OR SERVICE
Fire alarm system (nonvoice)
Fire alarm with in-building fire emergency voice alarm communication system (EVACS)
Mass notification system (MNS)
Combination system, with the following components:
Fire alarm EVACS MNS Two-way, in-building, emergency communication system
Other (specify):
NFPA 72, Fig. 14.6.2.4 (p. 2 of 11)
Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution.
3. TYPE OF SYSTEM OR SERVICE (continued)
NFPA 72 edition: 2019 Additional description of system(s):
3.1 Control Unit
Manufacturer: EDWARDS SYSTEM TECHNOLOGY Model number: QUICK START
3.2 Mass Notification System This system does not incorporate an MNS
3.2.1 System Type:
In-building MNS—combination
In-building MNS—stand-alone Wide-area MNS Distributed recipient MNS
Other (specify):
3.2.2 System Features:
Combination fire alarm/MNS MNS ACU only Wide-area MNS to regional national alerting interface
Local operating console (LOC) Direct recipient MNS (DRMNS) Wide-area MNS to DRMNS interface
Wide-area MNS to high-power speaker array (HPSA) interface In-building MNS to wide-area MNS interface
Other (specify):
3.3 System Documentation
An owner’s manual, a copy of the manufacturer’s instructions, a written sequence of operation, and a copy of the record record drawings are stored on site. Location: HAWAII AIR NATIONAL GUARD
3.4 System Software This system does not have alterable site-specific software.
Software revision number: 2.5 Software last updated on:
A copy of the site-specific software is stored on site. Location:
4. SYSTEM POWER
4.1 Control Unit
4.1.1 Primary Power
Input voltage of control panel: 120 Control panel amps: 20
4.1.2 Engine-Driven Generator This system does not have a generator.
Location of generator:
Location of fuel storage: Type of fuel:
4.1.3 Uninterruptible Power System This system does not have UPS.
Equipment powered by a UPS system:
Location of UPS system:
Calculated capacity of UPS batteries to drive the system components connected to it:
In standby mode (hours): In alarm mode (minutes):
NFPA 72, Fig. 14.6.2.4 (p. 3 of 11)
Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution.
4. SYSTEM POWER (continued)
4.1.4 Batteries
Location: By Fire Alarm Control Panel
Type: Interstate Nominal voltage: 12V Amp/hour rating: 18Ah
Calculated capacity of batteries to drive the system:
In standby mode (hours): In alarm mode (minutes):
Batteries are marked with date of manufacture.
4.2 In-Building Fire Emergency Voice Alarm Communication System or Mass Notification System
This system does not have an EVACS or MNS.
4.2.1 Primary Power
Input voltage of EVACS or MNS panel: 120 V EVACS or MNS panel amps:
4.2.2 Engine-Driven Generator This system does not have a generator.
Location of generator:
Location of fuel storage: Type of fuel:
4.2.3 Uninterruptible Power System This system does not have a UPS.
Equipment powered by a UPS system:
Location of UPS system:
Calculated capacity of UPS batteries to drive the system components connected to it:
In standby mode (hours): In alarm mode (minutes):
4.2.4 Batteries
Location: Type: Nominal voltage: Amp/hour rating:
Calculated capacity of batteries to drive the system:
In standby mode (hours): In alarm mode (minutes):
Batteries are marked with date of manufacture.
4.3 Notification Appliance Power Extender Panels This system does not have power extender panels.
4.3.1 Primary Power
Input voltage of power extender panel(s): Power extender panel amps:
4.3.2 Engine-Driven Generator This system does not have a generator.
Location of generator:
Location of fuel storage: Type of fuel:
4.3.3 Uninterruptible Power System This system does not have a UPS.
Equipment powered by a UPS system:
Location of UPS system:
NFPA 72, Fig. 14.6.2.4 (p. 4 of 11)
Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution.
4.3.4 Batteries
Location: Type: Nominal voltage: Amp/hour rating:
Calculated capacity of batteries to drive the system:
In standby mode (hours): In alarm mode (minutes):
Batteries are marked with date of manufacture.
5. ANNUNCIATORS This system does not have annunciators.
5.1 Location and Description of Annunciators
Annunciator 1:
Annunciator 2:
Annunciator 3:
6. NOTIFICATIONS MADE PRIOR TO TESTING
Monitoring organization Contact: Time:
Building management Contact: Time:
Building occupants Contact: Time:
Authority having jurisdiction Contact: Time:
Other, if required Contact: Time:
7. TESTING RESULTS
7.1 Control Unit and Related Equipment
Description Visual
Inspection Functional
Test Comments
Control unit FAIL
Lamps/LEDs/LCDs FAIL
Fuses
Trouble signals FAIL
Disconnect switches
Ground-fault monitoring
Supervision FAIL
Local annunciator FAIL
Remote annunciators
Power extender panels FAIL
Isolation modules
Other (specify)
NFPA 72, Fig. 14.6.2.4 (p. 5 of 11)
Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution.
7. TESTING RESULTS (continued)
7.2 Control Unit Power Supplies
Description Visual
Inspection Functional
Test Comments
120-volt power
Generator or UPS
Battery condition FAIL
Load voltage FAIL
Discharge test FAIL
Charger test FAIL
Other (specify)
7.3 In-Building Fire Emergency Voice Alarm Communications Equipment
Description Visual
Inspection Functional
Test Comments
Control unit
Lamps/LEDs/LCDs
Fuses
Primary power supply
Secondary power supply
Trouble signals
Disconnect switches
Ground-fault monitoring
Panel supervision
System performance
Sound pressure levels
Occupied Yes No
Ambient dBA
Alarm dBA
(attach report with locations, values, and weather conditions)
System intelligibility
CSI STI
(attach report with locations, values, and weather conditions)
NFPA 72, Fig. 14.6.2.4 (p. 6 of 11)
Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution.
7.4 Notification Appliance Power Extender Panels
Description Visual
Inspection Functional
Test Comments
Lamps/LEDs/LCDs FAIL
Fuses
Primary power supply
Secondary power supply FAIL
Trouble signals
Ground-fault monitoring
Panel supervision FAIL
Other (specify)
7.5 Mass Notification Equipment
Description Visual
Inspection Functional
Test Comments
Functional test
Reset/power down test
Fuses
Primary power supply
UPS power test
Trouble signals
Disconnect switches
Ground-fault monitoring
CCU security mechanism
Prerecorded message content
Prerecorded message activation
Software backup performed
Test backup software
Fire alarm to MNS interface
MNS to fire alarm interface
In-building MNS to wide-area
MNS
NFPA 72, Fig. 14.6.2.4 (p. 7 of 11)
Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution.
7.5 Mass Notification Equipment (continued)
Description Visual
Inspection Functional
Test Comments
MNS to direct recipient MNS
(attach report with locations, values, and weather conditions)
System intelligibility
CSI STI
7.6 Two-Way Communications Equipment
Description Visual
Inspection Functional
Test Comments
Phone handsets
Phone jacks
Off-hook indicator
Call-in signal
System performance
System audibility
System intelligibility
Radio communications enhancement system
Area of refuge communication system
Elevator emergency communications system
NFPA 72, Fig. 14.6.2.4 (p. 8 of 11)
Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution.
7.7 Combination Systems
Description Visual
Inspection Functional
Test Comments
Fire extinguishing monitoring devices/system
Carbon monoxide detector/system
Combination fire/security system
Other (specify)
7.8 Special Hazard Systems
Description (specify) Visual
Inspection Functional
Test Comments
7.9 Emergency Communications System
Visual
Functional
Simulated operation
Ensure predischarge notification appliances of special hazard systems are not overridden by the MNS.
See NFPA 72, 24.4.1.7.1.
7.10 Monitored Systems
Description (specify) Visual
Inspection Functional
Test Comments
Engine-driven generator
Fire pump
Special suppression systems
NFPA 72, Fig. 14.6.2.4 (p. 9 of 11)
Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution.
7.11 Auxiliary Functions
Description Visual
Inspection Functional
Test Comments
Door-releasing devices
Fan shutdown
Smoke management/smoke control
Smoke damper operation
Smoke shutter release
Door unlocking
Elevator recall
Elevator shunt trip
MNS override of FA signals
Other (specify)
7.12 Alarm Initiating Device
Device test results sheet attached listing all devices tested and the results of the testing
7.13 Supervisory Alarm Initiating Device
Device test results sheet attached listing all devices tested and the results of the testing
7.14 Alarm Notification Appliances
Appliance test results sheet attached listing all appliances tested and the results of the testing
7.15 Supervisory Station Monitoring
Description Visual
Inspection Functional
Test Time Comments
Alarm signal FAIL
Alarm restoration FAIL
Trouble signal FAIL
Trouble restoration FAIL
Supervisory signal FAIL
Supervisory restoration FAIL
NFPA 72, Fig. 14.6.2.4 (p. 10 of 11)
Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution.
8. NOTIFICATIONS THAT TESTING IS COMPLETE
Monitoring organization Contact: Time:
Building management Contact: Time:
Building occupants Contact: Time:
Authority having jurisdiction Contact: Time:
Other, if required Contact: Time:
9. SYSTEM RESTORED TO NORMAL OPERATION
Date: Time:
10. CERTIFICATION
10.1 Inspector Certification:
This system, as specified herein, has been inspected and tested according to all NFPA standards cited herein.
Signed: Printed name: Dante arriola Date: 03 MARCH 25
Organization: Phoenix Pacific Title: TECH Phone: 808-682-1000
10.2 Acceptance by Owner or Owner’s Representative:
The undersigned has a service contract for this system in effect as of the date shown below.
Signed: Printed name: Date:
Organization: Title: Phone:
NFPA 72, Fig. 14.6.2.4 (p. 11 of 11)
Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution.
DEVICE TEST RESULTS
(Attach additional sheets if required)
Device Type Address Location Test Results
PULL STATION ALL EXIT DOOR ALL FAIL
HORN/STROBE IN BLDG ALL FAIL
Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution.
To be completed by the system inspector or tester at the time of the inspection or test.
It shall be permitted to modify this form as needed to provide a more complete and/or clear record.
Date of this inspection or test: 3 MARCH 2025 Time of inspection or test: 12:00PM
Name of property: HIANG MAUI B502
Address: 75 KULEANA ST. KAHULUI
Description of property: OFFICE/ WEARHOUSE
Occupancy type:
Name of property representative: HAWAII AIR NATIONAL GUARD
Address:
Phone: Fax: E-mail:
Authority having jurisdiction over this property: HAWAII AIR NATIONAL GUARD
Phone: Fax: E-mail:
2. INSTALLATION, SERVICE, AND TESTING CONTRACTOR INFORMATION
Service and/or testing organization for this equipment: Phoenix Pacific INC.
Address: 2045 LAUWILIWILI STREET UNIT 101 KAPOLEI HI96707
Phone: 808-682-1000 Fax: 808-682-1047 E-mail: info@phoenixhawaii.com
Service technician or tester: J. Luce
Qualifications of technician or tester: NICET Level II, FireAlarm Systems, A contract for test and inspection in accordance with NFPA standards is in effect as of:
The contract expires: Contract number: Frequency of tests and inspections:
Monitoring organization for this equipment: Regional Dispatch Center, JBPH
A contract for test and inspection in accordance with NFPA standards is in effect as of:
Address: Bldg 167 JBPH
Phone: 808-4747-2222 Fax: E-mail:
Entity to which alarms are retransmitted: Phone:
3. TYPE OF SYSTEM OR SERVICE
Fire alarm system (nonvoice)
Fire alarm with in-building fire emergency voice alarm communication system (EVACS)
Mass notification system (MNS)
Combination system, with the following components:
Fire alarm EVACS MNS Two-way, in-building, emergency communication system
Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution.
NFPA 72 edition: 2019 Additional description of system(s):
3.1 Control Unit
Manufacturer: EDWARDS SYSTEM TECHNOLOGY Model number: QUICK START
3.2 Mass Notification System This system does not incorporate an MNS
3.2.1 System Type:
In-building MNS—combination
In-building MNS—stand-alone Wide-area MNS Distributed recipient MNS
Other (specify):
3.2.2 System Features:
Combination fire alarm/MNS MNS ACU only Wide-area MNS to regional national alerting interface
Local operating console (LOC) Direct recipient MNS (DRMNS) Wide-area MNS to DRMNS interface
Wide-area MNS to high-power speaker array (HPSA) interface In-building MNS to wide-area MNS interface
Other (specify):
3.3 System Documentation
An owner’s manual, a copy of the manufacturer’s instructions, a written sequence of operation, and a copy of the record record drawings are stored on site. Location: HAWAII AIR NATIONAL GUARD
3.4 System Software This system does not have alterable site-specific software.
Software revision number: 2.5 Software last updated on:
A copy of the site-specific software is stored on site. Location:
4. SYSTEM POWER
4.1 Control Unit
4.1.1 Primary Power
Input voltage of control panel: 120 Control panel amps: 20
4.1.2 Engine-Driven Generator This system does not have a generator.
Location of generator:
Location of fuel storage: Type of fuel:
4.1.3 Uninterruptible Power System This system does not have UPS.
Equipment powered by a UPS system:
Location of UPS system:
Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution.
4.1.4 Batteries
Location: Fire Alarm Control Panel
Type: Nominal voltage: 12V Amp/hour rating: 18Ah
Calculated capacity of batteries to drive the system:
In standby mode (hours): In alarm mode (minutes):
Batteries are marked with date of manufacture.
4.2 In-Building Fire Emergency Voice Alarm Communication System or Mass Notification System
This system does not have an EVACS or MNS.
4.2.1 Primary Power
Input voltage of EVACS or MNS panel: 120 V EVACS or MNS panel amps:
4.2.2 Engine-Driven Generator This system does not have a generator.
Location of generator:
Location of fuel storage: Type of fuel:
4.2.3 Uninterruptible Power System This system does not have a UPS.
Equipment powered by a UPS system:
Location of UPS system:
Calculated capacity of UPS batteries to drive the system components connected to it:
In standby mode (hours): In alarm mode (minutes):
4.2.4 Batteries
Location: Type: Nominal voltage: Amp/hour rating:
Calculated capacity of batteries to drive the system:
In standby mode (hours): In alarm mode (minutes):
Batteries are marked with date of manufacture.
4.3 Notification Appliance Power Extender Panels This system does not have power extender panels.
4.3.1 Primary Power
Input voltage of power extender panel(s): Power extender panel amps:
4.3.2 Engine-Driven Generator This system does not have a generator.
Location of generator:
Location of fuel storage: Type of fuel:
4.3.3 Uninterruptible Power System This system does not have a UPS.
Equipment powered by a UPS system:
Location of UPS system:
Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution.
Location: Type: Nominal voltage: Amp/hour rating:
Calculated capacity of batteries to drive the system:
In standby mode (hours): In alarm mode (minutes):
Batteries are marked with date of manufacture.
5. ANNUNCIATORS This system does not have annunciators.
5.1 Location and Description of Annunciators
Annunciator 1:
Annunciator 2:
Annunciator 3:
6. NOTIFICATIONS MADE PRIOR TO TESTING
Monitoring organization Contact: Time:
Building management Contact: Time:
Building occupants Contact: Time:
Authority having jurisdiction Contact: Time:
Other, if required Contact: Time:
7. TESTING RESULTS
7.1 Control Unit and Related Equipment
Description Visual
Inspection Functional
Test Comments
Control unit FAIL
Lamps/LEDs/LCDs FAIL
Fuses
Trouble signals FAIL
Disconnect switches
Ground-fault monitoring
Supervision FAIL
Local annunciator FAIL
Remote annunciators
Power extender panels FAIL
Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution.
7.2 Control Unit Power Supplies
Description Visual
Inspection Functional
Test Comments
120-volt power
Generator or UPS
Battery condition FAIL
Load voltage FAIL
Discharge test FAIL
Charger test FAIL
Other (specify)
7.3 In-Building Fire Emergency Voice Alarm Communications Equipment
Description Visual
Inspection Functional
Test Comments
Control unit
Lamps/LEDs/LCDs
Fuses
Primary power supply
Secondary power supply
Trouble signals
Disconnect switches
Ground-fault monitoring
Panel supervision
System performance
(attach report with locations, values, and weather conditions)
System intelligibility
CSI STI
Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution.
7.4 Notification Appliance Power Extender Panels
Description Visual
Inspection Functional
Test Comments
Lamps/LEDs/LCDs FAIL
Fuses
Primary power supply
Secondary power supply FAIL
Trouble signals
Ground-fault monitoring
Panel supervision FAIL
Other (specify)
7.5 Mass Notification Equipment
Description Visual
Inspection Functional
Test Comments
Functional test
Reset/power down test
Fuses
Primary power supply
UPS power test
Trouble signals
Disconnect switches
Ground-fault monitoring
CCU security mechanism
Prerecorded message content
Prerecorded message activation
Software backup performed
Test backup software
Fire alarm to MNS interface
MNS to fire alarm interface
Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution.
7.5 Mass Notification Equipment (continued)
Description Visual
Inspection Functional
Test Comments
MNS to direct recipient MNS
(attach report with locations, values, and weather conditions)
System intelligibility
CSI STI
Description Visual
Inspection Functional
Test Comments
Phone handsets
Phone jacks
Off-hook indicator
Call-in signal
System performance
System audibility
System intelligibility
Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution.
7.7 Combination Systems
Description Visual
Inspection Functional
Test Comments
Other (specify)
7.8 Special Hazard Systems
Description (specify) Visual
Inspection
Functional
Simulated operation
Ensure predischarge notification appliances of special hazard systems are not overridden by the MNS.
See NFPA 72, 24.4.1.7.1.
7.10 Monitored Systems
Description (specify) Visual
Inspection Functional
Test Comments
Engine-driven generator
Fire pump
Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution.
7.11 Auxiliary Functions
Description Visual
Inspection Functional
Test Comments
Door-releasing devices
Fan shutdown
Smoke management/smoke control
Smoke damper operation
Smoke shutter release
Door unlocking
Elevator recall
Elevator shunt trip
MNS override of FA signals
Other (specify)
7.12 Alarm Initiating Device
Device test results sheet attached listing all devices tested and the results of the testing
7.13 Supervisory Alarm Initiating Device
Device test results sheet attached listing all devices tested and the results of the testing
7.14 Alarm Notification Appliances
Appliance test results sheet attached listing all appliances tested and the results of the testing
7.15 Supervisory Station Monitoring
Description Visual
Inspection Functional
Test Time Comments
Alarm signal FAIL
Alarm restoration FAIL
Trouble signal FAIL
Trouble restoration FAIL
Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution.
Monitoring organization Contact: Time:
Building management Contact: Time:
Building occupants Contact: Time:
Authority having jurisdiction Contact: Time:
Other, if required Contact: Time:
9. SYSTEM RESTORED TO NORMAL OPERATION
Date: Time:
10. CERTIFICATION
10.1 Inspector Certification:
This system, as specified herein, has been inspected and tested according to all NFPA standards cited herein.
Signed: Printed name: Dante arriola Date: 03 MARCH 25
Organization: Phoenix Pacific Title: TECH Phone: 808-682-1000
10.2 Acceptance by Owner or Owner’s Representative:
The undersigned has a service contract for this system in effect as of the date shown below.
Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution.
PULL STATION ALL EXIT DOOR ALL FAIL
HEAT DETECTOR IN BLDG ALL FAIL
HORN/STROBE IN BLDG FAIL
BELL IN BLDG ALL FAIL
Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution.
To be completed by the system inspector or tester at the time of the inspection or test.
It shall be permitted to modify this form as needed to provide a more complete and/or clear record.
Date of this inspection or test: 4 MARCH 2025 Time of inspection or test: 7:30AM
Name of property: HIANG MAUI B503
Address: 75 KULEANA ST. KAHULUI
Description of property: OFFICE/ WEARHOUSE
Occupancy type:
Name of property representative: HAWAII AIR NATIONAL GUARD
Address:
Phone: Fax: E-mail:
Authority having jurisdiction over this property: HAWAII AIR NATIONAL GUARD
Phone: Fax: E-mail:
2. INSTALLATION, SERVICE, AND TESTING CONTRACTOR INFORMATION
Service and/or testing organization for this equipment: Phoenix Pacific INC.
Address: 2045 LAUWILIWILI STREET UNIT 101 KAPOLEI HI96707
Phone: 808-682-1000 Fax: 808-682-1047 E-mail: info@phoenixhawaii.com
Service technician or tester: J. Luce
Qualifications of technician or tester: NICET Level II, FireAlarm Systems, A contract for test and inspection in accordance with NFPA standards is in effect as of:
The contract expires: Contract number: Frequency of tests and inspections:
Monitoring organization for this equipment: Regional Dispatch Center, JBPH
A contract for test and inspection in accordance with NFPA standards is in effect as of:
Address: Bldg 167 JBPH
Phone: 808-4747-2222 Fax: E-mail:
Entity to which alarms are retransmitted: Phone:
3. TYPE OF SYSTEM OR SERVICE
Fire alarm system (nonvoice)
Fire alarm with in-building fire emergency voice alarm communication system (EVACS)
Mass notification system (MNS)
Combination system, with the following components:
Fire alarm EVACS MNS Two-way, in-building, emergency communication system
Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution.
NFPA 72 edition: 2019 Additional description of system(s):
3.1 Control Unit
Manufacturer: MONACO ENTERPRISES Model number: 220-004
3.2 Mass Notification System This system does not incorporate an MNS
3.2.1 System Type:
In-building MNS—combination
In-building MNS—stand-alone Wide-area MNS Distributed recipient MNS
Other (specify):
3.2.2 System Features:
Combination fire alarm/MNS MNS ACU only Wide-area MNS to regional national alerting interface
Local operating console (LOC) Direct recipient MNS (DRMNS) Wide-area MNS to DRMNS interface
Wide-area MNS to high-power speaker array (HPSA) interface In-building MNS to wide-area MNS interface
Other (specify):
3.3 System Documentation
An owner’s manual, a copy of the manufacturer’s instructions, a written sequence of operation, and a copy of the record record drawings are stored on site. Location: HAWAII AIR NATIONAL GUARD
3.4 System Software This system does not have alterable site-specific software.
Software revision number: Software last updated on:
A copy of the site-specific software is stored on site. Location:
4. SYSTEM POWER
4.1 Control Unit
4.1.1 Primary Power
Input voltage of control panel: 120 Control panel amps: 20
4.1.2 Engine-Driven Generator This system does not have a generator.
Location of generator:
Location of fuel storage: Type of fuel:
4.1.3 Uninterruptible Power System This system does not have UPS.
Equipment powered by a UPS system:
Location of UPS system:
Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution.
4.1.4 Batteries
Location: Fire Alarm Control Panel
Type: Nominal voltage: 12V Amp/hour rating: 7Ah
Calculated capacity of batteries to drive the system:
In standby mode (hours): In alarm mode (minutes):
Batteries are marked with date of manufacture.
4.2 In-Building Fire Emergency Voice Alarm Communication System or Mass Notification System
This system does not have an EVACS or MNS.
4.2.1 Primary Power
Input voltage of EVACS or MNS panel: EVACS or MNS panel amps:
4.2.2 Engine-Driven Generator This system does not have a generator.
Location of generator:
Location of fuel storage: Type of fuel:
4.2.3 Uninterruptible Power System This system does not have a UPS.
Equipment powered by a UPS system:
Location of UPS system:
Calculated capacity of UPS batteries to drive the system components connected to it:
In standby mode (hours): In alarm mode (minutes):
4.2.4 Batteries
Location: Type: Nominal voltage: Amp/hour rating:
Calculated capacity of batteries to drive the system:
In standby mode (hours): In alarm mode (minutes):
Batteries are marked with date of manufacture.
4.3 Notification Appliance Power Extender Panels This system does not have power extender panels.
4.3.1 Primary Power
Input voltage of power extender panel(s): Power extender panel amps:
4.3.2 Engine-Driven Generator This system does not have a generator.
Location of generator:
Location of fuel storage: Type of fuel:
4.3.3 Uninterruptible Power System This system does not have a UPS.
Equipment powered by a UPS system:
Location of UPS system:
Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution.
Location: Type: Nominal voltage: Amp/hour rating:
Calculated capacity of batteries to drive the system:
In standby mode (hours): In alarm mode (minutes):
Batteries are marked with date of manufacture.
5. ANNUNCIATORS This system does not have annunciators.
5.1 Location and Description of Annunciators
Annunciator 1:
Annunciator 2:
Annunciator 3:
6. NOTIFICATIONS MADE PRIOR TO TESTING
Monitoring organization Contact: Time:
Building management Contact: Time:
Building occupants Contact: Time:
Authority having jurisdiction Contact: Time:
Other, if required Contact: Time:
7. TESTING RESULTS
7.1 Control Unit and Related Equipment
Description Visual
Inspection Functional
Test Comments
Control unit FAIL
Lamps/LEDs/LCDs FAIL
Fuses
Trouble signals FAIL
Disconnect switches
Ground-fault monitoring
Supervision FAIL
Local annunciator FAIL
Remote annunciators
Power extender panels FAIL
Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution.
7.2 Control Unit Power Supplies
Description Visual
Inspection Functional
Test Comments
120-volt power
Generator or UPS
Battery condition FAIL
Load voltage FAIL
Discharge test FAIL
Charger test FAIL
Other (specify)
7.3 In-Building Fire Emergency Voice Alarm Communications Equipment
Description Visual
Inspection Functional
Test Comments
Control unit
Lamps/LEDs/LCDs
Fuses
Primary power supply
Secondary power supply
Trouble signals
Disconnect switches
Ground-fault monitoring
Panel supervision
System performance
(attach report with locations, values, and weather conditions)
System intelligibility
CSI STI
Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution.
7.4 Notification Appliance Power Extender Panels
Description Visual
Inspection Functional
Test Comments
Lamps/LEDs/LCDs FAIL
Fuses
Primary power supply
Secondary power supply FAIL
Trouble signals
Ground-fault monitoring
Panel supervision FAIL
Other (specify)
7.5 Mass Notification Equipment
Description Visual
Inspection Functional
Test Comments
Functional test
Reset/power down test
Fuses
Primary power supply
UPS power test
Trouble signals
Disconnect switches
Ground-fault monitoring
CCU security mechanism
Prerecorded message content
Prerecorded message activation
Software backup performed
Test backup software
Fire alarm to MNS interface
MNS to fire alarm interface
Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution.
7.5 Mass Notification Equipment (continued)
Description Visual
Inspection Functional
Test Comments
MNS to direct recipient MNS
(attach report with locations, values, and weather conditions)
System intelligibility
CSI STI
Description Visual
Inspection Functional
Test Comments
Phone handsets
Phone jacks
Off-hook indicator
Call-in signal
System performance
System audibility
System intelligibility
Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution.
7.7 Combination Systems
Description Visual
Inspection Functional
Test Comments
Other (specify)
7.8 Special Hazard Systems
Description (specify) Visual
Inspection
Functional
Simulated operation
Ensure predischarge notification appliances of special hazard systems are not overridden by the MNS.
See NFPA 72, 24.4.1.7.1.
7.10 Monitored Systems
Description (specify) Visual
Inspection Functional
Test Comments
Engine-driven generator
Fire pump
Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution.
7.11 Auxiliary Functions
Description Visual
Inspection Functional
Test Comments
Door-releasing devices
Fan shutdown
Smoke management/smoke control
Smoke damper operation
Smoke shutter release
Door unlocking
Elevator recall
Elevator shunt trip
MNS override of FA signals
Other (specify)
7.12 Alarm Initiating Device
Device test results sheet attached listing all devices tested and the results of the testing
7.13 Supervisory Alarm Initiating Device
Device test results sheet attached listing all devices tested and the results of the testing
7.14 Alarm Notification Appliances
Appliance test results sheet attached listing all appliances tested and the results of the testing
7.15 Supervisory Station Monitoring
Description Visual
Inspection Functional
Test Time Comments
Alarm signal FAIL
Alarm restoration FAIL
Trouble signal FAIL
Trouble restoration FAIL
Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution.
Monitoring organization Contact: Time:
Building management Contact: Time:
Building occupants Contact: Time:
Authority having jurisdiction Contact: Time:
Other, if required Contact: Time:
9. SYSTEM RESTORED TO NORMAL OPERATION
Date: Time:
10. CERTIFICATION
10.1 Inspector Certification:
This system, as specified herein, has been inspected and tested according to all NFPA standards cited herein.
Signed: Printed name: Dante arriola Date: 03 MARCH 25
Organization: Phoenix Pacific Title: TECH Phone: 808-682-1000
10.2 Acceptance by Owner or Owner’s Representative:
The undersigned has a service contract for this system in effect as of the date shown below.
Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution.
PULL STATION ALL EXIT DOOR FAIL
HEAT DETECTOR IN BLDG ALL FAIL
BELL IN BLDG FAIL