FA Inspection Report - Kalaeloa.pdf
PDF 17 MB Posted
- Solicitation number
- W50SLF26QA009
- Issued by
-
Department of the Army National Guard
About this file
These are fire alarm system service work orders and inspection/testing documentation for Hawk-Niking LLC facilities located at Kalaeloa, Hawaii (Buildings 1922 and 1923 at Saratoga Ave., Pearl Harbor). The documents comprise two service work orders dated November 6 and November 14, 2024, performed by Phoenix Pacific Inc., and an NFPA 72 Fire Alarm and Emergency Communication System Inspection and Testing Form dated November 14, 2024.
The first work order (240230-1, November 6, 2024, 4 hours) documents troubleshooting of a Siemens CP-35 control panel serving both buildings. Key findings include: a permanently stuck alarm on Zone 1 (repair bays, office, and sprinkler) requiring panel replacement; batteries failing load voltage tests (12V 7Ah) and requiring replacement; trouble on Zone 3 (training facility) due to open circuits and wiring issues; King Fisher radio transmission boxes missing electronics with uncertainty about box numbers (77xxx or 99xxx); and a disconnected tamper switch. The second work order (240230-2, November 14, 2024, 4 hours) continued troubleshooting in the training facility, removing four malfunctioning detectors and addressing voltage issues. Follow-up actions specified replacement of the main panel with a conventional system supporting relay output for King Fisher transmission; installation of King Fisher KF1 pushbutton and interface board; replacement of all 16 smoke detectors, 4 stick heat detectors, and 1 heat detector due to age-related line voltage degradation; and continued field wiring troubleshooting. The NFPA 72 inspection form documents system specifications (Siemens CP-35, 4 zones, 1 NAC, 120V primary power, 12V 7Ah batteries rated 24 hours standby/5 minutes alarm), test results showing battery failure, and supervisory station monitoring requirements for the Regional Dispatch Center at JBPH. All work was performed by Alston Chamizo with NICET Level II Fire Alarm Systems certification, with $0.00 billing for both service orders.
View the file
Other files
Show all 26
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DESCRIPTION:
CALL TYPE:
WORK PERFORMED: 11/06/2024
Alston C.
4 Hours
ACTIONS TAKEN:
-Panel services both buildings.
Model Siemens CP-35 4 Zones
1 NAC
Alarm active on zone 1 (repair bays, office, and sprinkler) Trouble active on zone 3 (training facility) Battery trouble active Alarm silence and trouble silence were active on arrival
-Started checking active alarm with waterflow and verified wiring and microswitch are good. Found tamper disconnected and will need to reconnect in series with the waterflow to be monitored.
-Checked the other two pull stations on the zone and both were normal. No short found on the zone 1 to activate the alarm. Wiring was verified to be normal and replaced wiring with jumpers to rule out the field wiring. End of line capacitor was changed with zone 2s to verify the capacitor was not the problem. Alarm will not clear despite this and does not clear despite a cold restart.
*Alarm is being generated by the panel and permanently stuck and needs to be replaced.
-Need to replace 12V 7Ah batteries tested at a low voltage and does not keep power on when 120V is removed. This battery Ah may change on replacement of the panel.
-Troubleshot trouble in training facility.
-Found an open between the outgoing and return.
-Verified wire voltage on exiting the building and made a wiring correction on entering the training facility.
-Traced wiring throughout the facility checking all devices and junction boxes.
-Found a smoke detector above the ceiling in an office that will need to be brought down below the ceiling.
-Was able to verify voltage up to the area around the kitchen where one issue is suspected due to a bad voltage. Another known issue is no voltage being recieved on the return side from the panel
2045 Lauwiliwili St., Unit 101, Kapolei, HI 96707 Main: (808) 682-1000 info@phoenixpacificinc.com www.phoenixpacificinc.com
JOB WORK ORDER
ORDER #:
240230-1
CLIENT LOCATION: HAWK-NIKING, LLC
235 KELLOG STREET
WAHIAWA , HI 96786
BILLED TO:
HAWK-NIKING, LLC
235 KELLOG STREET
WAHIAWA , HI 96786
JBPHH HIANG: KALAELOA - ASSESS/TROUBLESHOOT ADVISEMENT
FROM CODY TQ24-525
10 - SERVICE
to this area.
-Checked on King Fisher boxes and found the electronics were removed with boxes and wiring remaining. Will need to replace the interface, KF1, and antenna with cable.
*Need to ensure frequencies will match the recieved box number through RDC. Current box number is 77xxx or 99xxx, unsure due to both numbers being written in multiple areas.
-Because panel is permanently in alarm, removed the notification devices to prevent constant reminder noise from panel. This has no increased risk of safety since panel was already in alarm and silenced and any new alarm would make no notifications to the buildings or to RDC due to the missing radio hardware. The buildings have had no fire alarm support since this zone 1 trouble appeared and will not have any until panel is replaced. RDC will not respond to any alarms until King Fisher is replaced due to missing hardware.
FOLLOW UP ACTIONS:
-Replace panel to clear zone 1 alarm. Will need a conventional panel with relay support to send signals to King Fisher radio.
-Retrieve box number from RDC to order correct frequencies for replacements of panel hardware and antenna with cable. (Interface and push button) -Continue troubleshooting field wiring in the training facility and find wiring issues and bad devices needing to be replaced.
-Terminate tamper to zone 1 wiring. May be transferred to a another zone when panel is replaced.
New wiring to the panel will be needed.
-Replace existing batteries with a possible change in Ah value after panel replacement.
IS JOB COMPLETE? No DISC/CREDIT: $0.00
SALES TAX: $0.00
TAXABLE: $0.00
NON-TAXABLE: $0.00
DISCOUNT: $0.00
BALANCE $0.00
NET DUE: $0.00
Customer:
Date: 11/08/2024 02:50 PM
Employee: Alston Chamizo Date: 11/08/2024 02:50 PM
TERMS AND CONDITIONS
I / We hereby authorize the above work to be done along with the necessary materials and grant Phoenix Pacific, Inc., or its employees permission to test and/or operate the unit to be worked on. An express mechanic's lien is hereby acknowledged to secure payment for the work performed. Payment is due upon completion of work if no prior arrangement has been cleared by Phoenix Pacific, Inc., for credit. I / We agree to pay later fees at the rate of 1-1/2% per month on all accounts remainig unpaid after the due date, plus attorney's fees if collection proceedings are instituted.
DESCRIPTION:
CALL TYPE:
WORK PERFORMED: 11/14/2024
Alston C.
4 Hours
ACTIONS TAKEN:
-Continued troubleshooting smoke detector line.
-Found multiple smoke detectors dropping the voltage on the line.
-These devices were removed and bypassed on the base. Detectors were left on top of the panel.
Three smokes and one heat were removed.
-Also addressed wiring issues while troubleshooting.
-Tested all pull stations, notification devices, and waterflow including the disconnected tamper.
Zone 1 that was stuck in alarm was moved to zone 2 temporarily to test the line.
FOLLOW UP ACTIONS:
-Replace main panel with a conventional system with onboard relays for King Fisher transmission.
-Install King Fisher KF1 (pushbutton) and interface board with batteries for both.
-Recommend replacing all detectors including bases in the training area due to their old age and causing issues on the line. Counted 16 smoke detectors, 4 stick heat detectors, and 1 heat detector. All are 2-wire conventional.
2045 Lauwiliwili St., Unit 101, Kapolei, HI 96707 Main: (808) 682-1000 info@phoenixpacificinc.com www.phoenixpacificinc.com
JOB WORK ORDER
ORDER #:
240230-2
DATE: 11/14/2024
CLIENT LOCATION: HAWK-NIKING, LLC
Hawk-Niking LLC Wasp Blvd Pearl Harbor , HI 96860
BILLED TO:
HAWK-NIKING, LLC
235 KELLOG STREET
WAHIAWA , HI 96786
HIANG KALAELOA - CONTINUE TROUBLESHOOTING AT TRAINING
FACILITY
10 - SERVICE
IS JOB COMPLETE? No DISC/CREDIT: $0.00
SALES TAX: $0.00
TAXABLE: $0.00
NON-TAXABLE: $0.00
DISCOUNT: $0.00
BALANCE $0.00
NET DUE: $0.00
Customer:
Date: 11/14/2024 02:07 PM
Employee: Alston Chamizo Date: 11/14/2024 02:07 PM
TERMS AND CONDITIONS
I / We hereby authorize the above work to be done along with the necessary materials and grant Phoenix Pacific, Inc., or its employees permission to test and/or operate the unit to be worked on. An express mechanic's lien is hereby acknowledged to secure payment for the work performed. Payment is due upon completion of work if no prior arrangement has been cleared by Phoenix Pacific, Inc., for credit. I / We agree to pay later fees at the rate of 1-1/2% per month on all accounts remainig unpaid after the due date, plus attorney's fees if collection proceedings are instituted.
Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution.
FIRE ALARM AND EMERGENCY COMMUNICATION SYSTEM INSPECTION AND TESTING FORM
To be completed by the system inspector or tester at the time of the inspection or test.
It shall be permitted to modify this form as needed to provide a more complete and/or clear record.
Insert N/A in all unused lines.
Attach additional sheets, data, or calculations as necessary to provide a complete record.
Date of this inspection or test: 11/14/2024 Time of inspection or test: 11/14/2024 1200
1. PROPERTY INFORMATION
Name of property: HIANG KALAELOA Bldg. 1922 & 1923
Address: Bldg. 1922 & 1923 Saratoga Ave.
Description of property:
Bldg. 1922 Comm. Elec.
Facility Bldg. 1923 Tacan Bay Supply Warehouse
Occupancy type:
Bldg. 1922 Business Bldg. 1923 Storage
Name of property representative:
Paul.Apostol R JR SSGT
USAF ANG 297
CAOS/DOMP
Address: N/A
Phone: N/A
Fax: N/A E-mail: paul.apostol@us.af.mil
Authority having jurisdiction over this property:
Phone: Fax: E-mail:
2. INSTALLATION, SERVICE, AND TESTING CONTRACTOR INFORMATION
Service and/or testing organization for this equipment: Phoenix Pacific INC.
Address:
2045 LAUWILIWILI STREET UNIT 101 KAPOLEI HI96707
Phone:
808-682-1000 Fax: 808-682-1047 E-mail: info@phoenixhawaii.com
Service technician or tester:
Qualifications of technician or tester: NICET Level II, Fire Alarm Systems, A contract for test and inspection in accordance with NFPA standards is in effect as of:
The contract expires: Contract number: Frequency of tests and inspections:
Monitoring organization for this equipment: Regional Dispatch Center, JBPH
A contract for test and inspection in accordance with NFPA standards is in effect as of:
Address: Bldg 167 JBPH
Phone:
808-4747-2222 Fax:
E-mail:
Entity to which alarms are retransmitted: Regional DIspatch Center
Phone: (808) 474-2222
3. TYPE OF SYSTEM OR SERVICE
Fire alarm system (nonvoice)
Fire alarm with in-building fire emergency voice alarm communication system (EVACS)
Mass notification system (MNS)
Combination system, with the following components:
Fire alarm EVACS MNS Two-way, in-building, emergency communication system
Other (specify):
NFPA 72, Fig. 14.6.2.4 (p. 1 of 11) mailto:info@phoenixhawaii.com
Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution.
Software revision number: N/A Software last updated on:
A copy of the site-specific software is stored on site. Location:
3. TYPE OF SYSTEM OR SERVICE (continued)
NFPA 72 edition: 2009 Additional description of system(s):
3.1 Control Unit
Manufacturer: Siemens Bldg. 1922 Model number: Siemens CP-35
3.2 Mass Notification System This system does not incorporate an MNS
3.2.1 System Type:
In-building MNS—combination
In-building MNS—stand-alone Wide-area MNS Distributed recipient MNS
Other (specify):
3.2.2 System Features:
Combination fire alarm/MNS MNS ACU only Wide-area MNS to regional national alerting interface
Local operating console (LOC) Direct recipient MNS (DRMNS) Wide-area MNS to DRMNS interface
Wide-area MNS to high-power speaker array (HPSA) interface In-building MNS to wide-area MNS interface
Other (specify):
3.3 System Documentation
An owner’s manual, a copy of the manufacturer’s instructions, a written sequence of operation, and a copy of the record
3.4 System Software This system does not have alterable site-specific software.
4. SYSTEM POWER
4.1 Control Unit
4.1.1 Primary Power
Input voltage of control panel: 120V Control panel amps: 20A
4.1.2 Engine-Driven Generator This system does not have a generator.
4.1.3 Uninterruptible Power System This system does not have UPS.
Equipment powered by a UPS system:
Location of UPS system:
Calculated capacity of UPS batteries to drive the system components connected to it:
NFPA 72, Fig. 14.6.2.4 (p. 2 of 11) record drawings are stored on site. Location:
Location of generator:
Location of fuel storage: Type of fuel:
In standby mode (hours): In alarm mode (minutes):
Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution.
4. SYSTEM POWER (continued)
4.1.4 Batteries
Location: In FACP Type: Batteries 1 Nominal voltage: 12V Amp/hour rating: 7Ah
Calculated capacity of batteries to drive the system:
In standby mode (hours): 24 In alarm mode (minutes): 5
Batteries are marked with date of manufacture.
4.2 In-Building Fire Emergency Voice Alarm Communication System or Mass Notification System
This system does not have an EVACS or MNS.
4.2.1 Primary Power
Input voltage of EVACS or MNS panel: 120 V EVACS or MNS panel amps:
4.2.2 Engine-Driven Generator This system does not have a generator.
4.2.3 Uninterruptible Power System This system does not have a UPS.
4.2.4 Batteries
Location: Type: Nominal voltage: Amp/hour rating:
4.3 Notification Appliance Power Extender Panels This system does not have power extender panels.
4.3.1 Primary Power
4.3.2 Engine-Driven Generator This system does not have a generator.
4.3.3 Uninterruptible Power System This system does not have a UPS.
NFPA 72, Fig. 14.6.2.4 (p. 3 of 11)
Input voltage of power extender panel(s): Power extender panel amps:
Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution.
4. SYSTEM POWER (continued)
4.3.4 Batteries
Location: Type: Nominal voltage: Amp/hour rating:
5. ANNUNCIATORS This system does not have annunciators.
5.1 Location and Description of Annunciators
6. NOTIFICATIONS MADE PRIOR TO TESTING
7. TESTING RESULTS
7.1 Control Unit and Related Equipment
Description
Visual Inspection
Functional Test
Comments
Control unit
Lamps/LEDs/LCDs
Fuses
Trouble signals
Battery Trouble Active. Alarm Silence and Trouble Silence were acrtive on arrival.
Disconnect switches
Ground-fault monitoring
Supervision
Local annunciator
Remote annunciators
Power extender panels
Isolation modules
Other (specify)
NFPA 72, Fig. 14.6.2.4 (p. 4 of 11)
Annunciator 1:
Annunciator 2:
Annunciator 3:
Monitoring organization Contact: Time:
Building management Contact: Time:
Building occupants Contact: Time:
Authority having jurisdiction Contact: Time:
Other, if required Contact: Time:
7. TESTING RESULTS (continued)
Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution.
7.2 Control Unit Power Supplies
Inspection
120-volt power
Pass
Generator or UPS
Battery condition
Fail, batteries tested at a low voltage and doesn't keep power on when 120V is removed.
Load voltage
Discharge test
Charger test
7.3 In-Building Fire Emergency Voice Alarm Communications Equipment
Inspection
Control unit
Primary power supply
Secondary power supply
Panel supervision
System performance
Sound pressure levels
Occupied Yes No
Ambient dBA
Alarm dBA
(attach report with locations, values, and weather conditions)
System intelligibility
CSI STI
(attach report with locations, values, and weather conditions)
NFPA 72, Fig. 14.6.2.4 (p. 5 of 11)
Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution.
7.4 Notification Appliance Power Extender Panels
Inspection
Secondary power supply
Panel supervision
7.5 Mass Notification Equipment
Inspection
Functional test
Reset/power down test
UPS power test
CCU security mechanism
Prerecorded message content
Prerecorded message activation
Software backup performed
Test backup software
Fire alarm to MNS interface
MNS to fire alarm interface
In-building MNS to wide-area
MNS
NFPA 72, Fig. 14.6.2.4 (p. 6 of 11)
Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution.
7.5 Mass Notification Equipment (continued)
Inspection
MNS to direct recipient MNS
Sound pressure levels
Occupied Yes No
Ambient dBA
Alarm dBA
(attach report with locations, values, and weather conditions)
System intelligibility
CSI STI
(attach report with locations, values, and weather conditions)
7.6 Two-Way Communications Equipment
Inspection
Phone handsets
Phone jacks
Off-hook indicator
Call-in signal
System performance
System audibility
System intelligibility
Radio communications enhancement system
Area of refuge communication system
Elevator emergency communications system
NFPA 72, Fig. 14.6.2.4 (p. 7 of 11)
Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution.
7.7 Combination Systems
Inspection
Fire extinguishing monitoring devices/system
Carbon monoxide detector/system
Combination fire/security system
7.8 Special Hazard Systems
Description (specify)
Inspection
7.9 Emergency Communications System
Functional
Simulated operation
Ensure predischarge notification appliances of special hazard systems are not overridden by the MNS.
See NFPA 72, 24.4.1.7.1.
7.10 Monitored Systems
Description (specify)
Inspection
Engine-driven generator
Fire pump
Special suppression systems
NFPA 72, Fig. 14.6.2.4 (p. 8 of 11)
Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution.
7.11 Auxiliary Functions
Inspection
Door-releasing devices
Fan shutdown
Smoke management/smoke control
Smoke damper operation
Smoke shutter release
Door unlocking
Elevator recall
Elevator shunt trip
MNS override of FA signals
7.12 Alarm Initiating Device
Device test results sheet attached listing all devices tested and the results of the testing
7.13 Supervisory Alarm Initiating Device
Device test results sheet attached listing all devices tested and the results of the testing
7.14 Alarm Notification Appliances
Appliance test results sheet attached listing all appliances tested and the results of the testing
7.15 Supervisory Station Monitoring
Inspection
Time
Alarm signal
N/A Replace Pushbutton. Due to electronicsbeing removed,Interface Boards need to replaced.
Alarm restoration
Boards need to replaced
Trouble signal
Trouble restoration
Supervisory signal
Supervisory restoration
NFPA 72, Fig. 14.6.2.4 (p. 9 of 11)
Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution.
8. NOTIFICATIONS THAT TESTING IS COMPLETE
Monitoring organization Contact: Time: 1200
Building management Contact:
Time: 1200
Building occupants Contact: Local Staff Time: 1200
Authority having jurisdiction Contact:
Time: 1200
Other, if required Contact: HAWK-NIKING Time: 1200
9. SYSTEM RESTORED TO NORMAL OPERATION
Date: 11/14/2024 Time: 1200
10. CERTIFICATION
10.1 Inspector Certification:
This system, as specified herein, has been inspected and tested according to all NFPA standards cited herein.
Signed: Printed name: Alston Chamizo Date: 11/14/2024
Organization: Phoenix Pacific Title: Fire Alarm Technician Phone: 808-682-1000
10.2 Acceptance by Owner or Owner’s Representative:
The undersigned has a service contract for this system in effect as of the date shown below.
Signed: Printed name: Date:
Organization: Title: Phone:
NFPA 72, Fig. 14.6.2.4 (p. 10 of 11)
Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution.
DEVICE TEST RESULTS
(Attach additional sheets if required)
Device Type Address Location Test Results
Heat Detector
Stick Heat Detector
Smoke Detector
Office Fail, smoke detector was found above ceiling and needs to be brought down below the ceiling.
NFPA 72, Fig. 14.6.2.4 (p. 11 of 11)