Pages from FA Inspection Report - HILO.pdf

PDF 4 MB Posted

Attached to
Solicitation for Fire Alarms Repair Services (Multi-Island)
Solicitation number
W50SLF26QA009
Issued by

About this file

This is a job work order and fire alarm system inspection/testing report for Phoenix Pacific, Inc. (PPI) documenting assessment services performed on February 18-19, 2025, at six buildings (701-705, 771) located at Keaukaha Military Reservation in Hilo, Hawaii for client Hawk-Niking, LLC.

The assessment identified multiple critical deficiencies requiring repairs. All fire alarm control panels (FACPs) operate as standalone systems without third-party monitoring. Secondary power supply batteries installed in 2009 are physically damaged and require replacement across four buildings: Bldg 701/703/704/705 (12v 18ah), Bldg 704 ICAP Training room (12v 33ah), and Bldg 771 (12v 7ah). A CPU RAM battery (CR2032) requires replacement in Bldg 704 ICAP. An end-of-line capacitor (50uF, 50v) needs replacement for Bldg 702 pull stations. Additionally, three notification devices (strobe horns/pull stations) must be replaced due to failure or weather damage in Bldgs 704, 705, and 771. A sprinkler riser flow switch at Bldg 702 requires replacement but falls outside PPI's scope. Recommended service includes installing a 120vac surge suppressor at the 4100U FACP and further assessment of panel interconnection capabilities. Buildings 751, 752, and 753 have no fire alarm devices. PPI will generate a comprehensive repair quote including 12 hours of technician service and all required materials/parts. The work order specifies service completion, though final quote generation and customer notification remain pending.

View the file

Other files

Show all 26

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

DESCRIPTION:

CALL TYPE:

WORK PERFORMED: DATE of SERVICE:

2/18/2025 , 2/19/2025

TECHNICNIAN:

M.Kanealii

SERVICE:

Assess conditions and operations of the Fire alarm systems for the buildings as follows:

701 ,702 ,703 ,704 ,705 ,771 Buildings below have no devices affiliated or connected to the Fire alarm systems:

751, 752, 753

ACTIONS:

Assessment and findings to include testing below:

*ALL FACPs are operating as STANDALONE systems and do not monitor, report or activate each other. System is not monitored by any third-party entity (exp: Alert Alarm) *****************Bldg. 701,703,704,705 ***************** Monaco Vulcan FACP [Bldg 704 elct rm]

PANEL CONDITION ON ARRIVAL AND COMPLETION:

1 Trouble active [Secondary power supplies]

Power supplies:

PRIMARY: 120vac , 20ah SECONDARY: 12v 18ah [installation date 2009]

Initiating devices:

Pull stations:

[4] 270-SPO (EDWARDS)

Notification devices:

Strobe Horns:

[3] 757-7A-T (EDWARDS)

2045 Lauwiliwili St., Unit 101, Kapolei, HI 96707 Main: (808) 682-1000 info@phoenixpacificinc.com www.phoenixpacificinc.com

JOB WORK ORDER

ORDER #:

240230-3

DATE: 03/06/2025

CLIENT LOCATION: HAWK-NIKING, LLC

235 KELLOG STREET

WAHIAWA , HI 96786

BILLED TO:

HAWK-NIKING, LLC

235 KELLOG STREET

WAHIAWA , HI 96786

HIANG: Hilo B701, B702, B703, B704, & B705 - Assess/Troubleshoot FAS Assess

10 - SERVICE

Deficiencies:

-System is in trouble due to failed batteries -Secondary power supplies installation dated 2009 , Batteries are physically damaged .

Replacements needed -Strobe horn in hallway of bldg. 704,705 did not sound , this device should be replaced.

*****************Bldg.702**************** Pyrotronics System3 CP-30 FACP [Bldg.702 elct rm]

PANEL CONDITION ON ARRIVAL AND COMPLETION:

1 trouble active [ZN2]

Power supplies:

PRIMARY: 120vac,20ah

SECONDARY: N/A

Initiating devices:

Pull stations:

[4] MS57 (PYROTRONICS)

Notification devices:

[2] Bells PID not available

UNMONITORED by FACP:

[1] SPRINKLER RISER FLOW SWICTH (Device drives bell powered by 120vac)

Deficiencies:

- System is in trouble due to a bad EOL/capacitor

- ZN2 pull stations is in trouble assumed from a bad EOL/capacitor, A new capacitor is needed.

- Flow switch for sprinkler riser at Spray booth Bay is damaged, did not activate properly needs to be replaced and should be monitored by the FACP.

*****************Bldg.704 ICAP Training rm**************** SIMPLEX 4100U [Bldg 704 ICAP Training rm]

PANEL CONDITION ON ARRIVAL:

Panel was deenergized on arrival, reasoning is uncertain but, assumed to be due to systems condition being in trouble and not being able to silence. Systems history log was accessed and reviewed. PPI noticed several events occurred related to power outages or over currents. These are likely generated from actual events and the system may had "LATCHED" in reboot when in attempted to restart. This results in the system being in a constant cycle which would keep the trouble PSEUDO sounders activated.

PANEL CONDITION ON STARTUP:

01. Card 2 IDnet Card (250 points) , IdNet CHANNEL FAILURE, "ABNORMAL"

02. CPU FAIL

*PPI tech conducted several different methods to reboot the system and was successful. PPI was able to Test the system and complete the services needed. See below for systems condition on completion.

Power supplies:

PRIMARY: 120vac , 20ah SECONDARY: 12v 18ah [installation date 2009]

Initiating devices:

Pull stations:

[3] 4099-9020 (SIMPLEX)

Smoke Detectors:

[16] 4098-9714 Det w/4098-9792 base (SIMPLEX)

Notification devices:

[3] 49MTV-WRF (SIMPLEX)

PANEL CONDITION ON COMPLETION:

2 Troubles active:

1. Card 1 power supply/charger, Battery missing/low , "ABNORMAL"

2. Ram battery missing/failed, trouble point , "ABNORMAL"

Deficiencies:

-System is in trouble due to failed batteries reflected above -Secondary power supplies installation dated 2009 , batteries are out of date and failed a load test. Replacements needed.

-CPU RAM battery is failed , replacement needed -Uncompleted tie in for alarm relays between 4100U FACP and Monaco FACP at 704 hallway. An Assessment is needed

- Pull station device outside of exit door towards bldg. 771 was untested. This device is severely weathered and is unserviceable and will need to be replaced.

*****************Bldg. 771 [Warehouse]***************** Monaco Vulcan FACP [Bldg 704 Hallway outside elct rm]

PANEL CONDITION ON ARRIVAL AND COMPLETION:

1 Trouble active [Secondary power supplies]

Power supplies:

PRIMARY: 120vac , 20ah SECONDARY: 12v 7ah [installation date 2009]

Initiating devices:

Pull stations:

[3]MS57 (PYROTRONICS)

Heat Detectors:

[5] 501 (CHEMETRON)

*TESTING WAS SIMULATED BY SHORTING THE CONTACTS AT THE DEVICE AS THE DEVICES ARE OLD

AND UNRESETABLE. DEVICES ARE ASSUMED OPERABLE FROM READINGS OBTAINED THROUGH

MULTIMETER AND CONDUCTING CONTNIUITY CHECKS TO IMMULATE AN ALARM TO RECIEVE SIGNALS AT

FACP.

Notification devices:

[3] Bells PID not available

Deficiencies:

-Secondary power supplies installation dated 2009 , Batteries are physically damaged , Replacement is needed -Uncompleted tie in for alarm relays from Monaco FACP to SIMPLEX 4100U FACP, An assessment is needed.

FOLLOW UP:

1.PPI to bill accordingly for services for 1 technician 2.PPI to advise customers of findings above,repairs needed and recommendations below.

3.PPI to generate a quote for all repairs to include recommended service for 1 technician at 12 hours of service and parts/materials needed.

REPAIRS NEEDED:

*Replace secondary power supplies and wiring to FACPs below:

-SIMPLEX 4100U [Bldg 704 ICAP Training rm] [2]12v 33ah -Monaco Vulcan FACP [Bldg 704 elct rm] [2]12v 18ah -Monaco Vulcan FACP [Bldg 704 Hallway outside elct rm] [2]12v 7ah

*Replace RAM battery at CPU for below FACP:

-SIMPLEX 4100U [Bldg 704 ICAP Training rm]

*Replace End of line Capacitor for below device:

Bldg.702 warehouse north bay pull station (100-115588) 50uF,50v capacitor)

*Replace devices at locations below:

-[1] 757-7A-T at 704/705 hallway outside operations -[1] 4099-9020 at 704 outside of exit door towards bldg. 771 [1] Sprinkler riser Flow Switch at 702 spray paint booth (Out of PPIs obligation/capabilities)

RECOMMENDED SERVICE:

-Install 120vac inline surge suppressor at the 4100U FACP -Further assess Monaco and 4100U FACP for capabilities to interconnect panels for monitoring.

PARTS/MATERIALS:

-Needed for repairs:

[1] CR2032 battery (RAM) [2] 12v 33ah batteries [2] 12v 18ah batteries

[2] 12v 7ah batteries [1] 100-115588, 50uF,50v capacitor [SIEMENS] [1] 757-7A-T ,Strobe horn [EDWARDS] [1] 4099-9020 addressable pull station [SIMPLEX]

-Needed for recommended service:

[1] DTK-120HW (Surge suppressor)

IS JOB COMPLETE? -- DISC/CREDIT: $0.00

SALES TAX: $0.00

TAXABLE: $0.00

NON-TAXABLE: $0.00

DISCOUNT: $0.00

BALANCE $0.00

NET DUE: $0.00

Customer:

Date: 03/06/2025 03:11 PM

Employee: Mahi Kanealii Date: 03/06/2025 03:11 PM

TERMS AND CONDITIONS

I / We hereby authorize the above work to be done along with the necessary materials and grant Phoenix Pacific, Inc., or its employees permission to test and/or operate the unit to be worked on. An express mechanic's lien is hereby acknowledged to secure payment for the work performed. Payment is due upon completion of work if no prior arrangement has been cleared by Phoenix Pacific, Inc., for credit. I / We agree to pay later fees at the rate of 1-1/2% per month on all accounts remainig unpaid after the due date, plus attorney's fees if collection proceedings are instituted.

PHOTO REPORT

ORDER #:

240230-3

DATE: 02/19/2025

CLIENT: HAWK-NIKING, LLC

STREET: 235 KELLOG STREET

CITY: WAHIAWA, HI 96786

Service_21

Service_20

Service_19 Service_18

Service_17

Service_16

Service_15

Service_14

Service_13

Service_12

Service_11

Service_10

Service_9

Service_8

Service_7

Service_6

Service_5 Service_4

Service_3

Service_2

Service

NFPA 72, Fig. 14.6.2.4 (p. 1 of 11)

Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution.

FIRE ALARM AND EMERGENCY COMMUNICATION SYSTEM INSPECTION AND TESTING FORM

To be completed by the system inspector or tester at the time of the inspection or test.

It shall be permitted to modify this form as needed to provide a more complete and/or clear record.

Insert N/A in all unused lines.

Attach additional sheets, data, or calculations as necessary to provide a complete record.

Date of this inspection or test: 2/19/2025 Time of inspection or test: 0800am

1. PROPERTY INFORMATION

Name of property: Keaukaha Military Reservation , HIANG Bldg.702

Address: Keaukaha Military Reservation

Description of property: MAINTENANCE/SUPPORT

Occupancy type:

Name of property representative: Hawaii Air National Guard

Address:

Phone: Fax: E-mail:

Authority having jurisdiction over this property: Hawaii Air National Guard

Phone: Fax: E-mail:

2. INSTALLATION, SERVICE, AND TESTING CONTRACTOR INFORMATION

Service and/or testing organization for this equipment: Phoenix Pacific INC.

Address: 2045 LAUWILIWILI STREET UNIT 101 KAPOLEI HI96707

Phone: 808-682-1000 Fax: 808-682-1047 E-mail: info@phoenixhawaii.com

Service technician or tester: M.Kanealii

Qualifications of technician or tester: NICET Level II, Fire Alarms Systems

A contract for test and inspection in accordance with NFPA standards is in effect as of: n/a

The contract expires: n/a Contract number: n/a Frequency of tests and inspections: n/a

Monitoring organization for this equipment: n/a

A contract for test and inspection in accordance with NFPA standards is in effect as of: n/a

Address: BLDG 702

Phone: n/a Fax: n/a E-mail: n/a

Entity to which alarms are retransmitted: Phone:

3. TYPE OF SYSTEM OR SERVICE

Fire alarm system (nonvoice)

Fire alarm with in-building fire emergency voice alarm communication system (EVACS)

Mass notification system (MNS)

Combination system, with the following components:

Fire alarm EVACS MNS Two-way, in-building, emergency communication system

Other (specify):

NFPA 72, Fig. 14.6.2.4 (p. 2 of 11)

Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution.

3. TYPE OF SYSTEM OR SERVICE (continued)

NFPA 72 edition: 2019 Additional description of system(s):

3.1 Control Unit

Manufacturer: SIEMENS PYROTRONICS Model number: SYSTEM 3 (CP- 30)

3.2 Mass Notification System This system does not incorporate an MNS

3.2.1 System Type:

In-building MNS—combination

In-building MNS—stand-alone Wide-area MNS Distributed recipient MNS

Other (specify):

3.2.2 System Features:

Combination fire alarm/MNS MNS ACU only Wide-area MNS to regional national alerting interface

Local operating console (LOC) Direct recipient MNS (DRMNS) Wide-area MNS to DRMNS interface

Wide-area MNS to high-power speaker array (HPSA) interface In-building MNS to wide-area MNS interface

Other (specify):

3.3 System Documentation

An owner’s manual, a copy of the manufacturer’s instructions, a written sequence of operation, and a copy of the record record drawings are stored on site. Location: n/a

3.4 System Software This system does not have alterable site-specific software.

Software revision number: n/a Software last updated on: n/a

A copy of the site-specific software is stored on site. Location: n/a

4. SYSTEM POWER

4.1 Control Unit

4.1.1 Primary Power

Input voltage of control panel: 120 Control panel amps: 20

4.1.2 Engine-Driven Generator This system does not have a generator.

Location of generator:

Location of fuel storage: Type of fuel:

4.1.3 Uninterruptible Power System This system does not have UPS.

Equipment powered by a UPS system:

Location of UPS system:

Calculated capacity of UPS batteries to drive the system components connected to it:

In standby mode (hours): In alarm mode (minutes):

NFPA 72, Fig. 14.6.2.4 (p. 3 of 11)

Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution.

4. SYSTEM POWER (continued)

4.1.4 Batteries

Location: n/a Type: n/a Nominal voltage: n/a Amp/hour rating: n/a

Calculated capacity of batteries to drive the system:

In standby mode (hours): n/a In alarm mode (minutes): n/a

Batteries are marked with date of manufacture.

4.2 In-Building Fire Emergency Voice Alarm Communication System or Mass Notification System

This system does not have an EVACS or MNS.

4.2.1 Primary Power

Input voltage of EVACS or MNS panel: EVACS or MNS panel amps:

4.2.2 Engine-Driven Generator This system does not have a generator.

Location of generator:

Location of fuel storage: Type of fuel:

4.2.3 Uninterruptible Power System This system does not have a UPS.

Equipment powered by a UPS system:

Location of UPS system:

Calculated capacity of UPS batteries to drive the system components connected to it:

In standby mode (hours): In alarm mode (minutes):

4.2.4 Batteries

Location: Type: Nominal voltage: Amp/hour rating:

Calculated capacity of batteries to drive the system:

In standby mode (hours): In alarm mode (minutes):

Batteries are marked with date of manufacture.

4.3 Notification Appliance Power Extender Panels This system does not have power extender panels.

4.3.1 Primary Power

Input voltage of power extender panel(s): Power extender panel amps:

4.3.2 Engine-Driven Generator This system does not have a generator.

Location of generator:

Location of fuel storage: Type of fuel:

4.3.3 Uninterruptible Power System This system does not have a UPS.

Equipment powered by a UPS system:

Location of UPS system:

NFPA 72, Fig. 14.6.2.4 (p. 4 of 11)

Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution.

4.3.4 Batteries

Location: Type: Nominal voltage: Amp/hour rating:

Calculated capacity of batteries to drive the system:

In standby mode (hours): In alarm mode (minutes):

Batteries are marked with date of manufacture.

5. ANNUNCIATORS This system does not have annunciators.

5.1 Location and Description of Annunciators

Annunciator 1:

Annunciator 2:

Annunciator 3:

6. NOTIFICATIONS MADE PRIOR TO TESTING

Monitoring organization Contact: n/a Time:

Building management Contact: n/a Time:

Building occupants Contact: n/a Time:

Authority having jurisdiction Contact: n/a Time:

Other, if required Contact: n/a Time:

7. TESTING RESULTS

7.1 Control Unit and Related Equipment

Description

Visual

Inspection

Functional

Test Comments

Control unit PASS

Lamps/LEDs/LCDs PASS

Fuses PASS

Trouble signals PASS

Disconnect switches PASS

Ground-fault monitoring PASS

Supervision N/A

Local annunciator N/A

Remote annunciators N/A

Power extender panels N/A

Isolation modules N/A

Other (specify) N/A

NFPA 72, Fig. 14.6.2.4 (p. 5 of 11)

Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution.

7. TESTING RESULTS (continued)

7.2 Control Unit Power Supplies

Description

Visual

Inspection

Functional

Test Comments

120-volt power PASS

Generator or UPS N/A

Battery condition N/A

Load voltage N/A

Discharge test N/A

Charger test N/A

Other (specify) N/A

7.3 In-Building Fire Emergency Voice Alarm Communications Equipment

Description

Visual

Inspection

Functional

Test Comments

Control unit N/A

Lamps/LEDs/LCDs N/A

Fuses N/A

Primary power supply N/A

Secondary power supply N/A

Trouble signals N/A

Disconnect switches N/A

Ground-fault monitoring N/A

Panel supervision N/A

System performance N/A

Sound pressure levels

Occupied Yes No

N/A

Ambient dBA

Alarm dBA

(attach report with locations, values, and weather conditions)

System intelligibility

CSI STI

(attach report with locations, values, and weather conditions)

N/A

NFPA 72, Fig. 14.6.2.4 (p. 6 of 11)

Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution.

7.4 Notification Appliance Power Extender Panels

Description

Visual

Inspection

Functional

Test Comments

Lamps/LEDs/LCDs N/A

Fuses N/A

Primary power supply N/A

Secondary power supply N/A

Trouble signals N/A

Ground-fault monitoring N/A

Panel supervision N/A

Other (specify) N/A

7.5 Mass Notification Equipment

Description

Visual

Inspection

Functional

Test Comments

Functional test N/A

Reset/power down test N/A

Fuses N/A

Primary power supply N/A

UPS power test N/A

Trouble signals N/A

Disconnect switches N/A

Ground-fault monitoring N/A

CCU security mechanism N/A

Prerecorded message content N/A

Prerecorded message activation N/A

Software backup performed N/A

Test backup software N/A

Fire alarm to MNS interface N/A

MNS to fire alarm interface N/A

In-building MNS to wide-area

MNS

NFPA 72, Fig. 14.6.2.4 (p. 7 of 11)

Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution.

7.5 Mass Notification Equipment (continued)

Description

Visual

Inspection

Functional

Test Comments

MNS to direct recipient MNS N/A

Sound pressure levels

Occupied Yes No

N/A

Ambient dBA

Alarm dBA

(attach report with locations, values, and weather conditions)

System intelligibility

CSI STI

(attach report with locations, values, and weather conditions)

N/A

Other (specify) N/A

7.6 Two-Way Communications Equipment

Description

Visual

Inspection

Functional

Test Comments

Phone handsets N/A

Phone jacks N/A

Off-hook indicator N/A

Call-in signal N/A

System performance N/A

System audibility N/A

System intelligibility N/A

Radio communications enhancement system

N/A

Area of refuge communication system

N/A

Elevator emergency communications system

NFPA 72, Fig. 14.6.2.4 (p. 8 of 11)

Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution.

7.7 Combination Systems

Description

Visual

Inspection

Functional

Test Comments

Fire extinguishing monitoring devices/system

N/A

Carbon monoxide detector/system N/A

Combination fire/security system N/A

Other (specify) N/A

7.8 Special Hazard Systems

Description (specify)

Visual

Inspection

Functional

Test Comments

N/A

N/A

N/A

7.9 Emergency Communications System

Visual

Functional

Simulated operation

Ensure predischarge notification appliances of special hazard systems are not overridden by the MNS.

See NFPA 72, 24.4.1.7.1.

7.10 Monitored Systems

Description (specify)

Visual

Inspection

Functional

Test Comments

Engine-driven generator N/A

Fire pump N/A

Special suppression systems N/A

NFPA 72, Fig. 14.6.2.4 (p. 9 of 11)

Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution.

7.11 Auxiliary Functions

Description

Visual

Inspection

Functional

Test Comments

Door-releasing devices N/A

Fan shutdown N/A

Smoke management/smoke control N/A

Smoke damper operation N/A

Smoke shutter release N/A

Door unlocking N/A

Elevator recall N/A

Elevator shunt trip N/A

MNS override of FA signals N/A

Other (specify) N/A

7.12 Alarm Initiating Device

Device test results sheet attached listing all devices tested and the results of the testing

7.13 Supervisory Alarm Initiating Device

Device test results sheet attached listing all devices tested and the results of the testing

7.14 Alarm Notification Appliances

Appliance test results sheet attached listing all appliances tested and the results of the testing

7.15 Supervisory Station Monitoring

Description

Visual

Inspection

Functional

Test Time Comments

Alarm signal N/A

Alarm restoration N/A

Trouble signal N/A

Trouble restoration N/A

Supervisory signal N/A

Supervisory restoration N/A

NFPA 72, Fig. 14.6.2.4 (p. 10 of 11)

Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution.

8. NOTIFICATIONS THAT TESTING IS COMPLETE

Monitoring organization Contact: N/A Time:

Building management Contact: N/A Time:

Building occupants Contact: N/A Time:

Authority having jurisdiction Contact: N/A Time:

Other, if required Contact: N/A Time:

9. SYSTEM RESTORED TO NORMAL OPERATION

Date: Time:

10. CERTIFICATION

10.1 Inspector Certification:

This system, as specified herein, has been inspected and tested according to all NFPA standards cited herein.

Signed: Printed name: Mahiolii Kanealii Date: 2/19/2025

Organization: Phoenix Pacific Title: NICET II , Fire alarm systems

Phone: 808-682-1000

10.2 Acceptance by Owner or Owner’s Representative:

The undersigned has a service contract for this system in effect as of the date shown below.

Signed: Printed name: Date:

Organization: Title: Phone:

NFPA 72, Fig. 14.6.2.4 (p. 11 of 11)

Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution.

DEVICE TEST RESULTS

(Attach additional sheets if required)

Device Type Address Location Test Results

PullStation (MS series) N/A Bldg.702 Motor.Veh bay 1 PASS

PullStation (MS series) N/A Bldg.702 Motor.Veh bay 2 PASS

PullStation (MS series) N/A Bldg.702 Power pro bay 1 PASS

PullStation (MS series) N/A Bldg.702 Power pro bay 2 PASS

Bell N/A Bldg.702 Power pro bay PASS

Bell N/A Bldg.702 Motor.Veh bay PASS

Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution.

To be completed by the system inspector or tester at the time of the inspection or test.

It shall be permitted to modify this form as needed to provide a more complete and/or clear record.

Name of property: Keaukaha Military Reservation , HIANG Bldg.704

Address: Keaukaha Military Reservation

Description of property: MAINTENANCE/SUPPORT

Occupancy type:

Name of property representative: Hawaii Air National Guard

Address:

Phone: Fax: E-mail:

Authority having jurisdiction over this property: Hawaii Air National Guard

Phone: Fax: E-mail:

2. INSTALLATION, SERVICE, AND TESTING CONTRACTOR INFORMATION

Service and/or testing organization for this equipment: Phoenix Pacific INC.

Address: 2045 LAUWILIWILI STREET UNIT 101 KAPOLEI HI96707

Phone: 808-682-1000 Fax: 808-682-1047 E-mail: info@phoenixhawaii.com

Service technician or tester: M.Kanealii

Qualifications of technician or tester: NICET Level II, Fire Alarms Systems

A contract for test and inspection in accordance with NFPA standards is in effect as of: n/a

The contract expires: n/a Contract number: n/a Frequency of tests and inspections: n/a

Monitoring organization for this equipment: n/a

A contract for test and inspection in accordance with NFPA standards is in effect as of: n/a

Address: BLDG 704

Phone: n/a Fax: n/a E-mail: n/a

Entity to which alarms are retransmitted: Phone:

3. TYPE OF SYSTEM OR SERVICE

Fire alarm system (nonvoice)

Fire alarm with in-building fire emergency voice alarm communication system (EVACS)

Mass notification system (MNS)

Combination system, with the following components:

Fire alarm EVACS MNS Two-way, in-building, emergency communication system

Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution.

NFPA 72 edition: 2019 Additional description of system(s):

3.1 Control Unit

Manufacturer: Monaco Enterprises Model number: VULCAN 1

3.2 Mass Notification System This system does not incorporate an MNS

3.2.1 System Type:

In-building MNS—combination

In-building MNS—stand-alone Wide-area MNS Distributed recipient MNS

Other (specify):

3.2.2 System Features:

Combination fire alarm/MNS MNS ACU only Wide-area MNS to regional national alerting interface

Local operating console (LOC) Direct recipient MNS (DRMNS) Wide-area MNS to DRMNS interface

Wide-area MNS to high-power speaker array (HPSA) interface In-building MNS to wide-area MNS interface

Other (specify):

3.3 System Documentation

An owner’s manual, a copy of the manufacturer’s instructions, a written sequence of operation, and a copy of the record record drawings are stored on site. Location: n/a

3.4 System Software This system does not have alterable site-specific software.

Software revision number: n/a Software last updated on: n/a

A copy of the site-specific software is stored on site. Location: n/a

4. SYSTEM POWER

4.1 Control Unit

4.1.1 Primary Power

Input voltage of control panel: 120 Control panel amps: 20

4.1.2 Engine-Driven Generator This system does not have a generator.

Location of generator:

Location of fuel storage: Type of fuel:

4.1.3 Uninterruptible Power System This system does not have UPS.

Equipment powered by a UPS system:

Location of UPS system:

Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution.

4.1.4 Batteries

Location: FACP Type: SLA Nominal voltage: 12vdc Amp/hour rating: 18ah

Calculated capacity of batteries to drive the system:

In standby mode (hours): n/a In alarm mode (minutes): n/a

Batteries are marked with date of manufacture.

4.2 In-Building Fire Emergency Voice Alarm Communication System or Mass Notification System

This system does not have an EVACS or MNS.

4.2.1 Primary Power

Input voltage of EVACS or MNS panel: EVACS or MNS panel amps:

4.2.2 Engine-Driven Generator This system does not have a generator.

Location of generator:

Location of fuel storage: Type of fuel:

4.2.3 Uninterruptible Power System This system does not have a UPS.

Equipment powered by a UPS system:

Location of UPS system:

Calculated capacity of UPS batteries to drive the system components connected to it:

In standby mode (hours): In alarm mode (minutes):

4.2.4 Batteries

Location: Type: Nominal voltage: Amp/hour rating:

Calculated capacity of batteries to drive the system:

In standby mode (hours): In alarm mode (minutes):

Batteries are marked with date of manufacture.

4.3 Notification Appliance Power Extender Panels This system does not have power extender panels.

4.3.1 Primary Power

Input voltage of power extender panel(s): Power extender panel amps:

4.3.2 Engine-Driven Generator This system does not have a generator.

Location of generator:

Location of fuel storage: Type of fuel:

4.3.3 Uninterruptible Power System This system does not have a UPS.

Equipment powered by a UPS system:

Location of UPS system:

Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution.

Location: Type: Nominal voltage: Amp/hour rating:

Calculated capacity of batteries to drive the system:

In standby mode (hours): In alarm mode (minutes):

Batteries are marked with date of manufacture.

5. ANNUNCIATORS This system does not have annunciators.

5.1 Location and Description of Annunciators

Annunciator 1:

Annunciator 2:

Annunciator 3:

6. NOTIFICATIONS MADE PRIOR TO TESTING

Monitoring organization Contact: n/a Time:

Building management Contact: n/a Time:

Building occupants Contact: n/a Time:

Authority having jurisdiction Contact: n/a Time:

Other, if required Contact: n/a Time:

7. TESTING RESULTS

7.1 Control Unit and Related Equipment

Description

Visual

Inspection

Functional

Test Comments

Control unit PASS

Lamps/LEDs/LCDs PASS

Fuses PASS

Trouble signals PASS

Disconnect switches PASS

Ground-fault monitoring PASS

Supervision N/A

Local annunciator N/A

Remote annunciators N/A

Power extender panels N/A

Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution.

7.2 Control Unit Power Supplies

Description

Visual

Inspection

Functional

Test Comments

120-volt power PASS

Generator or UPS N/A

Battery condition FAILED

Load voltage FAILED

Discharge test N/A

Charger test N/A

Other (specify) N/A

7.3 In-Building Fire Emergency Voice Alarm Communications Equipment

Description

Visual

Inspection

Functional

Test Comments

Control unit N/A

Lamps/LEDs/LCDs N/A

Fuses N/A

Primary power supply N/A

Secondary power supply N/A

Trouble signals N/A

Disconnect switches N/A

Ground-fault monitoring N/A

Panel supervision N/A

System performance N/A

Sound pressure levels

Occupied Yes No

N/A

Ambient dBA

Alarm dBA

(attach report with locations, values, and weather conditions)

System intelligibility

CSI STI

(attach report with locations, values, and weather conditions)

Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution.

7.4 Notification Appliance Power Extender Panels

Description

Visual

Inspection

Functional

Test Comments

Lamps/LEDs/LCDs N/A

Fuses N/A

Primary power supply N/A

Secondary power supply N/A

Trouble signals N/A

Ground-fault monitoring N/A

Panel supervision N/A

Other (specify) N/A

7.5 Mass Notification Equipment

Description

Visual

Inspection

Functional

Test Comments

Functional test N/A

Reset/power down test N/A

Fuses N/A

Primary power supply N/A

UPS power test N/A

Trouble signals N/A

Disconnect switches N/A

Ground-fault monitoring N/A

CCU security mechanism N/A

Prerecorded message content N/A

Prerecorded message activation N/A

Software backup performed N/A

Test backup software N/A

Fire alarm to MNS interface N/A

MNS to fire alarm interface N/A

In-building MNS to wide-area

Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution.

7.5 Mass Notification Equipment (continued)

Description

Visual

Inspection

Functional

Test Comments

MNS to direct recipient MNS N/A

Sound pressure levels

Occupied Yes No

N/A

Ambient dBA

Alarm dBA

(attach report with locations, values, and weather conditions)

System intelligibility

CSI STI

(attach report with locations, values, and weather conditions)

N/A

Other (specify) N/A

7.6 Two-Way Communications Equipment

Description

Visual

Inspection

Functional

Test Comments

Phone handsets N/A

Phone jacks N/A

Off-hook indicator N/A

Call-in signal N/A

System performance N/A

System audibility N/A

System intelligibility N/A

Radio communications enhancement system

N/A

Area of refuge communication system

N/A

Elevator emergency communications system

Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution.

7.7 Combination Systems

Description

Visual

Inspection

Functional

Test Comments

Fire extinguishing monitoring devices/system

N/A

Carbon monoxide detector/system N/A

Combination fire/security system N/A

Other (specify) N/A

7.8 Special Hazard Systems

Description (specify)

Visual

Inspection

Functional

Test Comments

N/A

N/A

N/A

7.9 Emergency Communications System

Visual

Functional

Simulated operation

Ensure predischarge notification appliances of special hazard systems are not overridden by the MNS.

See NFPA 72, 24.4.1.7.1.

7.10 Monitored Systems

Description (specify)

Visual

Inspection

Functional

Test Comments

Engine-driven generator N/A

Fire pump N/A

Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution.

7.11 Auxiliary Functions

Description

Visual

Inspection

Functional

Test Comments

Door-releasing devices N/A

Fan shutdown N/A

Smoke management/smoke control N/A

Smoke damper operation N/A

Smoke shutter release N/A

Door unlocking N/A

Elevator recall N/A

Elevator shunt trip N/A

MNS override of FA signals N/A

Other (specify) N/A

7.12 Alarm Initiating Device

Device test results sheet attached listing all devices tested and the results of the testing

7.13 Supervisory Alarm Initiating Device

Device test results sheet attached listing all devices tested and the results of the testing

7.14 Alarm Notification Appliances

Appliance test results sheet attached listing all appliances tested and the results of the testing

7.15 Supervisory Station Monitoring

Description

Visual

Inspection

Functional

Test Time Comments

Alarm signal N/A

Alarm restoration N/A

Trouble signal N/A

Trouble restoration N/A

Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution.

Monitoring organization Contact: N/A Time:

Building management Contact: N/A Time:

Building occupants Contact: N/A Time:

Authority having jurisdiction Contact: N/A Time:

Other, if required Contact: N/A Time:

9. SYSTEM RESTORED TO NORMAL OPERATION

Date: Time:

10. CERTIFICATION

10.1 Inspector Certification:

This system, as specified herein, has been inspected and tested according to all NFPA standards cited herein.

Signed: Printed name: Mahiolii Kanealii Date: 2/19/2025

Organization: Phoenix Pacific Title: NICET II , Fire alarm systems

Phone: 808-682-1000

10.2 Acceptance by Owner or Owner’s Representative:

The undersigned has a service contract for this system in effect as of the date shown below.

Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution.

PullStation (270-SPO) N/A Bldg.705 Entrance Gate PASS

PullStation (270-SPO) N/A Bldg.705 Hallway PASS

PullStation (270-SPO) N/A Bldg.704 near Restrooms PASS

PullStation (270-SPO) N/A Bldg.703 PASS

Strobe Horn (757-7A-T) N/A Bldg.705 Hallway FAILED

Strobe Horn (757-7A-T) N/A Bldg.701 entrance PASS

Strobe Horn (757-7A-T) N/A Bldg.703 PASS

Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution.

To be completed by the system inspector or tester at the time of the inspection or test.

It shall be permitted to modify this form as needed to provide a more complete and/or clear record.

Name of property: Keaukaha Military Reservation , HIANG Bldg.704 ICAP Training room

Address: Keaukaha Military Reservation

Description of property: MAINTENANCE/SUPPORT

Occupancy type:

Name of property representative: Hawaii Air National Guard

Address:

Phone: Fax: E-mail:

Authority having jurisdiction over this property: Hawaii Air National Guard

Phone: Fax: E-mail:

2. INSTALLATION, SERVICE, AND TESTING CONTRACTOR INFORMATION

Service and/or testing organization for this equipment: Phoenix Pacific INC.

Address:

2045 LAUWILIWILI STREET UNIT 101 KAPOLEI HI96707

Phone:

808-682-1000

Fax: 808-682-1047 E-mail: info@phoenixhawaii.com

Service technician or tester: M.Kanealii

Qualifications of technician or tester: NICET Level II, Fire Alarms Systems

A contract for test and inspection in accordance with NFPA standards is in effect as of: n/a

The contract expires: n/a Contract number: n/a Frequency of tests and inspections: n/a

Monitoring organization for this equipment:

n/a

A contract for test and inspection in accordance with NFPA standards is in effect as of: n/a

Address:

BLDG.704 ICAP TRAINING RM

Phone:

n/a

Fax: n/a E-mail: n/a

Entity to which alarms are retransmitted: n/a

Phone: n/a

3. TYPE OF SYSTEM OR SERVICE

Fire alarm system (nonvoice)

Fire alarm with in-building fire emergency voice alarm communication system (EVACS)

Mass notification system (MNS)

Combination system, with the following components:

Fire alarm EVACS MNS Two-way, in-building, emergency communication system

Other (specify):

mailto:info@phoenixhawaii.com

Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution.

NFPA 72 edition: 2019 Additional description of system(s):

3.1 Control Unit

Manufacturer: SIMPLEX Model number: 4100U

3.2 Mass Notification System This system does not incorporate an MNS

3.2.1 System Type:

In-building MNS—combination

In-building MNS—stand-alone Wide-area MNS Distributed recipient MNS

Other (specify):

3.2.2 System Features:

Combination fire alarm/MNS MNS ACU only Wide-area MNS to regional national alerting interface

Local operating console (LOC) Direct recipient MNS (DRMNS) Wide-area MNS to DRMNS interface

Wide-area MNS to high-power speaker array (HPSA) interface In-building MNS to wide-area MNS interface

Other (specify):

3.3 System Documentation

An owner’s manual, a copy of the manufacturer’s instructions, a written sequence of operation, and a copy of the record record drawings are stored on site. Location: n/a

3.4 System Software This system does not have alterable site-specific software.

Software revision number: 11.09.01 rev3 Software last updated on: 8/5/24

A copy of the site-specific software is stored on site. Location: n/a

4. SYSTEM POWER

4.1 Control Unit

4.1.1 Primary Power

Input voltage of control panel: 120 Control panel amps: 20

4.1.2 Engine-Driven Generator This system does not have a generator.

4.1.3 Uninterruptible Power System This system does not have UPS.

Equipment powered by a UPS system:

Location of UPS system:

Location of generator:

Location of fuel storage: Type of fuel:

Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution.

4.1.4 Batteries

Location: FACP Type: SLA Nominal voltage: 12vdc Amp/hour rating: 33Ah

Calculated capacity of batteries to drive the system:

In standby mode (hours): n/a In alarm mode (minutes): n/a

Batteries are marked with date of manufacture.

4.2 In-Building Fire Emergency Voice Alarm Communication System or Mass Notification System

This system does not have an EVACS or MNS.

4.2.1 Primary Power

4.2.2 Engine-Driven Generator This system does not have a generator.

4.2.3 Uninterruptible Power System This system does not have a UPS.

4.2.4 Batteries

Location: Type: Nominal voltage: Amp/hour rating:

4.3 Notification Appliance Power Extender Panels This system does not have power extender panels.

4.3.1 Primary Power

4.3.2 Engine-Driven Generator This system does not have a generator.

4.3.3 Uninterruptible Power System This system does not have a UPS.

Input voltage of EVACS or MNS panel: EVACS or MNS panel amps:

Input voltage of power extender panel(s): Power extender panel amps:

Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution.

Location: Type: Nominal voltage: Amp/hour rating:

5. ANNUNCIATORS This system does not have annunciators.

5.1 Location and Description of Annunciators

6. NOTIFICATIONS MADE PRIOR TO TESTING

Monitoring organization Contact: n/a Time:

Building management Contact: n/a Time:

Building occupants Contact: n/a Time:

Authority having jurisdiction Contact: n/a Time:

Other, if required Contact: n/a Time:

7. TESTING RESULTS

7.1 Control Unit and Related Equipment

Description

Visual Inspection

Functional Test

Comments

Control unit

PASS

Lamps/LEDs/LCDs

Fuses

Trouble signals

Disconnect switches

Ground-fault monitoring

Supervision

Local annunciator

Remote annunciators

Power extender panels

Isolation modules

Other (specify)

Annunciator 1:

Annunciator 2:

Annunciator 3:

Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution.

7.2 Control Unit Power Supplies

Inspection

120-volt power

Generator or UPS

Battery condition

FAILED

Load voltage

FAILED

Discharge test

Charger test

7.3 In-Building Fire Emergency Voice Alarm Communications Equipment

Inspection

Control unit

Primary power supply

Secondary power supply

Panel supervision

System performance

Sound pressure levels

Occupied Yes No

Ambient dBA

Alarm dBA

(attach report with locations, values, and weather conditions)

System intelligibility

CSI STI

(attach report with locations, values, and weather conditions)

Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution.

7.4 Notification Appliance Power Extender Panels

Inspection

Secondary power supply

Panel supervision

7.5 Mass Notification Equipment

Inspection

Functional test

Reset/power down test

UPS power test

CCU security mechanism

Prerecorded message content

Prerecorded message activation

Software backup performed

Test backup software

Fire alarm to MNS interface

MNS to fire alarm interface

In-building MNS to wide-area

Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution.

7.5 Mass Notification Equipment (continued)

Inspection

MNS to direct recipient MNS

Sound pressure levels

Occupied Yes No

Ambient dBA

Alarm dBA

(attach report with locations, values, and weather conditions)

System intelligibility

CSI STI

(attach report with locations, values, and weather conditions)

7.6 Two-Way Communications Equipment

Inspection

Phone handsets

Phone jacks

Off-hook indicator

Call-in signal

System performance

System audibility

System intelligibility

Radio communications enhancement system

Area of refuge communication system

Elevator emergency communications system

Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution.

7.7 Combination Systems

Inspection

Fire extinguishing monitoring devices/system

Carbon monoxide detector/system

Combination fire/security system

7.8 Special Hazard Systems

Description (specify)

Inspection

7.9 Emergency Communications System

Functional

Simulated operation

Ensure predischarge notification appliances of special hazard systems are not overridden by the MNS.

See NFPA 72, 24.4.1.7.1.

7.10 Monitored Systems

Description (specify)

Inspection

Engine-driven generator

Fire pump

Special suppression systems

Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution.

7.11 Auxiliary Functions

Inspection

Door-releasing devices

Fan shutdown

Smoke management/smoke control

Smoke damper operation

Smoke shutter release

Door unlocking

Elevator recall

Elevator shunt trip

MNS override of FA signals

7.12 Alarm Initiating Device

Device test results sheet attached listing all devices tested and the results of the testing

7.13 Supervisory Alarm Initiating Device

Device test results sheet attached listing all devices tested and the results of the testing

7.14 Alarm Notification Appliances

Appliance test results sheet attached listing all appliances tested and the results of the testing

7.15 Supervisory Station Monitoring

Inspection

Time

Alarm signal

Alarm restoration

Trouble signal

Trouble restoration

Supervisory signal

Supervisory restoration

Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution.

Monitoring organization Contact: N/A Time:

Building management Contact: N/A Time:

Building occupants Contact: N/A Time:

Authority having jurisdiction Contact: N/A Time:

Other, if required Contact: N/A Time:

9. SYSTEM RESTORED TO NORMAL OPERATION

10. CERTIFICATION

10.1 Inspector Certification:

This system, as specified herein, has been inspected and tested according to all NFPA standards cited herein.

Signed: Printed name: Mahiolii Kanealii Date: 2/19/2025

Organization: Phoenix Pacific Title: NICET II , Fire alarm systems

Phone: 808-682-1000

10.2 Acceptance by Owner or Owner’s Representative:

The undersigned has a service contract for this system in effect as of the date shown below.

Date: Time:

Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution.

Pull Station (4099-9020) N/A Bldg.704 ICAP rm Entry PASS

Pull Station (4099-9020) N/A Bldg.704 ICAP rm exit PASS

Pull Station (4099-9020) N/A Bldg.704 outside exit towards 771

UNTESTED/ NOT ABLE TO TEST

SEVERELY WEATHERED TO BE

REPLACED

Smoke Detector (4098-9714) N/A Bldg.704 ICAP rm ceiling 1 PASS

Smoke Detector (4098- 9714)

N/A Bldg.704 ICAP rm ceiling 2 PASS

Smoke Detector (4098- 9714)

N/A Bldg.704 ICAP rm ceiling

PASS

Smoke Detector (4098-9714) N/A Bldg.704 ICAP rm ceiling

PASS

Smoke Detector (4098-9714) N/A Bldg.704 ICAP rm ceiling

PASS

Smoke Detector (4098-9714) N/A Bldg.704 ICAP rm ceiling 6 PASS

Smoke Detector (4098-9714) N/A Bldg.704 ICAP rm ceiling 7 PASS

Smoke Detector (4098-9714) N/A Bldg.704 ICAP rm ceiling 8 PASS

Smoke Detector (4098-9714) N/A Bldg.704 ICAP rm ceiling 9 PASS

Smoke Detector (4098-9714) N/A Bldg.704 ICAP rm ceiling

PASS

Smoke Detector (4098-9714) N/A Bldg.704 ICAP rm ceiling

PASS

Smoke Detector (4098-9714) N/A Bldg.704 ICAP rm ceiling

PASS

Smoke Detector (4098-9714) N/A Bldg.704 ICAP rm ceiling

PASS

Smoke Detector (4098-9714) N/A Bldg.704 ICAP rm ceiling

PASS

Smoke Detector (4098-9714) N/A Bldg.704 ICAP rm ceiling

PASS

Smoke Detector (4098-9714) N/A Bldg.704 ICAP rm ceiling

PASS

Strobe Horn (49MTV-WRF ) N/A Blfg.704 ICAP rm entry PASS

Strobe Horn (49MTV-WRF ) N/A Bldg.704 ICAP rm exit PASS

Strobe Horn (49MTV-WRF ) N/A Bldg.704 outside ICAP facing 771

Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution.

To be completed by the system inspector or tester at the time of the inspection or test.

It shall be permitted to modify this form as needed to provide a more complete and/or clear record.

Name of property: Keaukaha Military Reservation , HIANG Bldg.771

Address: Keaukaha Military Reservation

Description of property: MAINTENANCE/SUPPORT

Occupancy type:

Name of property representative: Hawaii Air National Guard

Address:

Phone: Fax: E-mail:

Authority having jurisdiction over this property: Hawaii Air National Guard

Phone: Fax: E-mail:

2. INSTALLATION, SERVICE, AND TESTING CONTRACTOR INFORMATION

Service and/or testing organization for this equipment: Phoenix Pacific INC.

Address: 2045 LAUWILIWILI STREET UNIT 101 KAPOLEI HI96707

Phone: 808-682-1000 Fax: 808-682-1047 E-mail: info@phoenixhawaii.com

Service technician or tester: M.Kanealii

Qualifications of technician or tester: NICET Level II, Fire Alarms Systems

A contract for test and inspection in accordance with NFPA standards is in effect as of: n/a

The contract expires: n/a Contract number: n/a Frequency of tests and inspections: n/a

Monitoring organization for this equipment: n/a

A contract for test and inspection in accordance with NFPA standards is in effect as of: n/a

Address: BLDG 771

Phone: n/a Fax: n/a E-mail: n/a

Entity to which alarms are retransmitted: n/a Phone: n/a

3. TYPE OF SYSTEM OR SERVICE

Fire alarm system (nonvoice)

Fire alarm with in-building fire emergency voice alarm communication system (EVACS)

Mass notification system (MNS)

Combination system, with the following components:

Fire alarm EVACS MNS Two-way, in-building, emergency communication system

Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution.

NFPA 72 edition: 2019 Additional description of system(s):

3.1 Control Unit

Manufacturer: Monaco Enterprises Model number: VULCAN 1

3.2 Mass Notification System This system does not incorporate an MNS

3.2.1 System Type:

In-building MNS—combination

In-building MNS—stand-alone Wide-area MNS Distributed recipient MNS

Other (specify):

3.2.2 System Features:

Combination fire alarm/MNS MNS ACU only Wide-area MNS to regional national alerting interface

Local operating console (LOC) Direct recipient MNS (DRMNS) Wide-area MNS to DRMNS interface

Wide-area MNS to high-power speaker array (HPSA) interface In-building MNS to wide-area MNS interface

Other (specify):

3.3 System Documentation

An owner’s manual, a copy of the manufacturer’s instructions, a written sequence of operation, and a copy of the record record drawings are stored on site. Location: n/a

3.4 System Software This system does not have alterable site-specific software.

Software revision number: n/a Software last updated on: n/a

A copy of the site-specific software is stored on site. Location: n/a

4. SYSTEM POWER

4.1 Control Unit

4.1.1 Primary Power

Input voltage of control panel: 120 Control panel amps: 20

4.1.2 Engine-Driven Generator This system does not have a generator.

Location of generator:

Location of fuel storage: Type of fuel:

4.1.3 Uninterruptible Power System This system does not have UPS.

Equipment powered by a UPS system:

Location of UPS system:

Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution.

4.1.4 Batteries

Location: FACP Type: SLA Nominal voltage: 12vdc Amp/hour rating: 7ah

Calculated capacity of batteries to drive the system:

In standby mode (hours): n/a In alarm mode (minutes): n/a

Batteries are marked with date of manufacture.

4.2 In-Building Fire Emergency Voice Alarm Communication System or Mass Notification System

This system does not have an EVACS or MNS.

4.2.1 Primary Power

Input voltage of EVACS or MNS panel: EVACS or MNS panel amps:

4.2.2 Engine-Driven Generator This system does not have a generator.

Location of generator:

Location of fuel storage: Type of fuel:

4.2.3 Uninterruptible Power System This system does not have a UPS.

Equipment powered by a UPS system:

Location of UPS system:

Calculated capacity of UPS batteries to drive the system components connected to it:

In standby mode (hours): In alarm mode (minutes):

4.2.4 Batteries

Location: Type: Nominal voltage: Amp/hour rating:

Calculated capacity of batteries to drive the system:

In standby mode (hours): In alarm mode (minutes):

Batteries are marked with date of manufacture.

4.3 Notification Appliance Power Extender Panels This system does not have power extender panels.

4.3.1 Primary Power

Input voltage of power extender panel(s): Power extender panel amps:

4.3.2 Engine-Driven Generator This system does not have a generator.

Location of generator:

Location of fuel storage: Type of fuel:

4.3.3 Uninterruptible Power System This system does not have a UPS.

Equipment powered by a UPS system:

Location of UPS system:

Copyright © 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution.

Location: Type: Nominal voltage: Amp/hour rating:

Calculated capacity of batteries to drive the system:

In standby mode (hours): In alarm mode (minutes):

Batteries are marked with date of manufacture.

5. ANNUNCIATORS This system does not have annunciators.

5.1 Location and Description of Annunciators

Annunciator 1:

Annu…

This is the start of the file's text. The full file is on GovTribe.