This is a Questions and Answers document providing clarification on the B330 Mold Remediation solicitation (W50S9B26Q0022) issued by the Department of the Army National Guard for work at Joint Base Langley-Eustis, Langley AFB, Hampton, Virginia. The document does not address specific products or services requirements but rather responds to bidder inquiries regarding the solicitation details. The Q&A file serves to clarify ambiguities and provide additional guidance to prospective small business contractors preparing quotations for the mold remediation project, which includes professional remediation services in a 485 SF break room (B330) with negative pressure containment, decontamination, and cleaning, as well as monitoring for an adjacent 580 SF office space.

View the file

Other files

Show all 11

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Questions and Answers 3 21 September 2026

Q1: Do we need to build a containment in the adjacent room next to the contaminated room or just put air machines in the adjacent room.

A1: Put scrubbers in adjacent room. No containment in adjacent room.

Q2: To get the negative pressure we will need to be able to put the poly from floor to deck. The ceiling grid will prevent us from doing that on the four walls. The ceiling grid will need to be demoed because we will have to clean up in the ceiling. We will have to wipe down and Hepa vac all items about the ceiling. Is removing and reinstalling the ceiling grid acceptable?

A2: Ceiling grid treatment addressed in previous question. Ceiling grid shall not be demoed. See SOW for instructions on ceiling. SOW p.5, Sec 2.1.1: Remove ALL ceiling tiles for disposal. (NOTE: Existing Clg Grid to remain in service.)

Q3: Is the GWB where ceiling grid is attached to remain? The GWB could possibly have mold in it and don’t recommend leaving it. This was mentioned in the visit.

A3: All drywall shall be demolished and disposed of. Ceiling grid treatment addressed in previous) question.