Repair HVAC Basewide Charlotte Drawings 99M001 99M002 99M003.pdf

PDF 1009 KB Posted

Attached to
Replace HVAC Equipment/Systems - Charlotte
Solicitation number
W50S87-20-B-5002
Issued by

About this file

This document package includes mechanical equipment schedules and specifications for replacing HVAC systems at Charlotte Douglas International Airport. The schedules list air handling units, chillers, boilers, pumps, air conditioning equipment, and terminal boxes to be provided. Key details include specifications for new split system heat pumps, DX cooling with gas furnaces, packaged rooftop units, computer room split systems, and a vertical air conditioner. Sizes, capacities, manufacturers, and technical requirements are provided for each piece of mechanical equipment. The related federal contract opportunity is solicitation number W50S87-20-B-5002 for replacing HVAC equipment and systems at Charlotte, issued by the Department of the Army North Carolina Army National Guard. Interested bidders are encouraged to attend a pre-bid conference on May 13, 2020. The document package provides specifications for the mechanical scope of work.

View the file

Other files

Show all 18

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

NONE

PROJECT MANAGER

0 1" 2"

SCALE

FILENAME

DESIGNED BY:

DRAWN BY:

CHECKED BY:

ISSUE DATE DESCRIPTION

1 2 3 4 5 6 7 8

D

C

B

A

SHEET

D. WORLEY

D. WORLEY

M. DIMOFF

CONTRACT #: W9133L-15-D-0004

ANG PROJECT #: FJRP142610

HDR PROJECT #: 10137178

CHARLOTTE DOUGLAS INT'L AIRPORTREPLACE HVAC SYSTEMS

BASE WIDE - CHARLOTTE

NC AIR NATIONAL GUARD

145TH AIRLIFT WING

CHARLOTTE, NC

99M001

N. OVERBY

10137178-02-MP_Master.rvt

MECHANICAL SCHEDULES

7. HINGED DOOR ACCESS

6. DOUBLE WALL SEALED PANEL (R-13) AND LEVEL II THERMAL BREAK

5. PROVIDE UNIT WITH CONFIGURATION AND COMPONENTS AS SHOWN ON PLANS. UNIT SHALL FIT WITHIN SCHEDULED FOOTPRINT.

4. CONTRACTOR TO SET OUTSIDE AIR DAMPER AND SUPPLY AIR RATES EQUAL TO THE ORIGINAL EQUIPMENT OPERATION.

3. VFD ON SUPPLY FAN

2. INTERLOCK CONTROLLER WITH EXISTING BMS

1. SINGLE POINT POWER CONNECTION AND CONTROLLER FOR COMPLETE OPERATION AS NOTED ON PLANS AND SPECIFICATIONS.

NOTES:

02AHU-3 MECH. ROOM 8,000 NOTE 4 80 67 10 2.0 1,800 2 8 14 473 1.1 2 MERV 8 208 / 3 31 50 25 84 x 90 x 96 3080 02HP-3 CARRIER 39MN 17W 1 - 7

02AHU-2 MECH. ROOM 15,000 NOTE 4 80 67 20 2.0 1,800 2 8 14 490 0.49 2 MERV 8 208 / 3 60 100 48 96 x 104 x 120 5001 02HP-2A & 02HP-2B CARRIER 39MN 30W 1 - 7

DB

(°F)

WB

(°F)

HP

E.S.P.

(I.W.C.)

RPM

MAX

# OF

CIRCUITS

# OF

ROWS

FINS PER

INCH

VELOCITY

(FPM)

AIR PRESSURE

DROP (in W.G.)

FILTER THK

(IN)

FINAL

FILTER

VOLTAGE /

PHASE

MCA MOCP FAN FLA

SIZE

(L" x W" x H")

WEIGHT

(LBS)

MANUFACTURER MODEL

MARK LOCATION

NOMINAL

AIRFLOW

(CFM)

MINIMUM

OA (CFM)

ENT. COND FANS COILS FILTERS ELECTRICAL PHYSICAL

MATCHING COND.

UNIT

BASIS OF DESIGN

NOTES

SPLIT SYSTEM AIR HANDLER UNIT SCHEDULE

6. DIGITAL COMPRESSOR

5. LOW AMBIENT HEAD PRESSURE CONTROL

4. BACNET COMMUNICATIONS AND TIE IN TO EXISTING BMS

3. HAIL GUARDS

2. COMPRESSOR SUCTION SERVICE VALVE

1. DISCONNECT

NOTES:

45CH-1 OUTDOORS - EAST BLDG 45 70 95 / 78 R410A 54.0 44.0 164.8 12.0 0.0001 5 SCROLL 27 179 5 2.9 156 175 460 / 3 151 x 88 x 78 3400 CARRIER 30RAP070 1 - 6

EWT

(°F)

LWT

(°F)

GPM

PRESS.

DROP (FT)

FOUL

FACTOR

QTY TYPE

RLA

(EA.)

LRA

(EA.)

FAN NO.

FAN FLA

(EA.)

MCA MOCP

VOLTAGE /

PHASE

SIZE

(L"xW"xH")

WEIGHT

(LBS)

MANUFACTURER MODEL

MARK LOCATION SERVES

TOTAL

CAPACITY

(TONS)

AMB TEMP

DB/WB °F

REFRIG.

EVAPORATOR DATA COMPRESSOR DATA CONDENSER DATA ELEC DATA PHYSICAL DATA BASIS OF DESIGN

NOTES

AIR COOLED CHILLER SCHEDULE

4. COOLING CAPACITY BASED ON 95°F OUTDOOR AIR TEMPERATURE.

3. DISCONNECT SWITCH

2. HAIL GUARD

1. 2-STAGE SCROLL COMPRESSOR WITH LOW AMBIENT CONTROL.

NOTES:

02HP-3 OUTDOORS - WEST AHU-3 232 181 11.0 214 130 4 1/4 2 80 / 67 R-410A 30.1 225 73.7 100 208 / 3 86.4 x 67.1 x 50.4 800 CARRIER 38AUQB25A0M5 1 - 4

02HP-2B OUTDOORS - NORTH AHU-2 232 181 11.0 214 130 4 1/4 2 80 / 67 R-410A 30.1 225 73.7 100 208 / 3 86.4 x 67.1 x 50.4 800 CARRIER 38AUQB25A0M5 1 - 4

02HP-2A OUTDOORS - NORTH AHU-2 232 181 11.0 214 130 4 1/4 2 80 / 67 R-410A 30.1 225 73.7 100 208 / 3 86.4 x 67.1 x 50.4 800 CARRIER 38AUQB25A0M5 1 - 4

TOTAL SENSIBLE EER @47F @17F RLA LRA

COOLING HEATING FAN

NO.

FAN

HP

COMP

NO.

ENT. AIR

DB / WB °F

REFRIG.

COMPRESSOR

MCA MOCP

VOLTAGE /

PHASE

SIZE (L"xW"xH")

WEIGHT

(LBS.)

MANUFACTURER MODEL

MARK LOCATION SERVES

CAPACITY (MBH) CONDENSER DATA ELECTRICAL DATA PHYSICAL BASIS OF DESIGN

NOTES

SPLIT SYSTEM HEAT PUMP SCHEDULE

8. HOT GAS REHEAT HUMIDITY CONTROL

7. EXTERNAL STATIC PRESSURE TO BE SET EQUAL TO THE MEASURED EXTERNAL STATIC PRESSURE RECORDED IN THE T&B REPORT PERFORMED PRIOR TO START OF CONSTRUCTION

6. HINGED DOORS

5. OUTSIDE AIR DAMPER SHALL BE SET TO PROVIDE FRESH AIR EQUAL TO THE MEASURED OUTSIDE AIRFLOW RECORDED IN T&B REPORT PERFORMED PROIR TO START OF CONSTRUCTION.

4. DISCHARGE AIR AND OUTSIDE AIR TEMPERATURE SENSORS

3. LOW AMBIENT CONTROL

2. MANUFACTURER'S ROOF CURB ADAPTER

1. 2-STAGE SCROLL COMPRESSOR

NOTES:

61RTU-7 2 800 NOTE 6 NOTE 8 DIRECT - 1/2 23.0 18.0 R410A 60 49 -- 208 / 1 19.4 30 32.6 x 48.8 x 44.1 344 12 15 CARRIER 48VG-A240603 1 - 7

61RTU-6 5 2000 NOTE 6 NOTE 8 DIRECT 1.06 -- 63.0 48.3 R410A 110 88 16 x 16 x 2 208 / 3 29 40 74 x 47 x 41 650 12 16 CARRIER 48GCEN06B1A5 1 - 8

61RTU-5 4 1600 NOTE 6 NOTE 8 DIRECT 0.72 -- 50 37 R410A 67 53 16 x 25 x 2 208 / 3 24 30 73 x 47 x 41 600 12 16 CARRIER 48GCDN05B1A5 1 - 8

61RTU-4 4 1600 NOTE 6 NOTE 8 DIRECT 0.72 -- 50 37 R410A 67 53 16 x 25 x 2 208 / 3 24 30 72 x 47 x 41 600 12 16 CARRIER 48GCDN05B1A5 1 - 8

61RTU-3 8.5 3400 NOTE 6 NOTE 8 BELT 1.7 -- 103.6 81.0 R410A 125 103 20 x 20 x 2 208 / 3 39 50 88 x 59 x 49 1000 12 -- CARRIER 48HCDE09B1A5 1 - 8

61RTU-2 5 2000 NOTE 6 NOTE 8 DIRECT 1.06 -- 63.0 48.3 R410A 67 53 16 x 16 x 2 208 / 3 29 40 74 x 47 x 41 650 12 16 CARRIER 48GCDN06B1A5 1 - 8

61RTU-1 2 800 NOTE 6 NOTE 8 DIRECT - 1/2 23.0 18.0 R410A 60 49 -- 208 / 1 19.4 30 32.6 x 48.8 x 44.1 344 12 15 CARRIER 48VG-A240603 1 - 7

49RTU-1 2 800 NOTE 6 NOTE 8 DIRECT - 1/2 23.0 18.0 R410A 60 49 -- 208 / 1 19.4 30 32.6 x 48.8 x 44.1 344 12 15 CARRIER 48VG-A240603 1 - 7

(MBH) (MBH) (MBH)

TOTAL

(MBH)

SENSIBLE REFRIG.

TYPE

INPUT OUTPUT VOLTAGE

/ PHASE

MCA MOCP

AIRFLOW

(CFM)

OUTDOOR

AIRFLOW

(CFM)

E.S.P

(IN. WG.)

DRIVE BHP HP MANUFACTURER MODEL NO.

MARK

NO.

NOMINAL

TONS

SUPPLY COOLING CAPACITY

(AT 95F AMBIENT)

HEATING

CAPACITY FILTER

SIZE

(L"xW"xH")

ELECTRICAL

UNIT SIZE

(L"xW"xH")

WEIGHT

(LBS)

EER SEER

BASIS OF DESIGN

NOTES

GAS PACKAGED ROOFTOP UNIT SCHEDULE

MAR 2020 B-3 DESIGN SUBMITTAL

NOTE: "EQUAL TO" MANUFACTURERS CAN BE SUBMITTED FOR ALL UNITS DESCRIBED IN THE

SCHEDULE AS LONG AS THEY MEET OR EXCEED THE PERFORMANCE AND SPECIFICATIONS

OF THE BASIS OF DESIGN. A SUBSTITUTION REQUEST MUST BE SUBMITTED TO THE

CONTRACTING OFFICER DURING CONSTRUCTION FOR APPROVAL. SEE SPEC SECTION 01 33 00.

0 1" 2"

SCALE

FILENAME

DESIGNED BY:

DRAWN BY:

CHECKED BY:

ISSUE DATE DESCRIPTION

1 2 3 4 5 6 7 8

D

C

B

A

SHEET

D. WORLEY

D. WORLEY

M. DIMOFF

CONTRACT #: W9133L-15-D-0004

ANG PROJECT #: FJRP142610

HDR PROJECT #: 10137178

CHARLOTTE DOUGLAS INT'L AIRPORTREPLACE HVAC SYSTEMS

BASE WIDE - CHARLOTTE

NC AIR NATIONAL GUARD

145TH AIRLIFT WING

CHARLOTTE, NC

99M002

N. OVERBY

10137178-02-MP_Master.rvt

MECHANICAL SCHEDULES

9. EXISTING CONDENSING UNIT TO REMAIN. INTERLOCK NEW FURNACE UNIT WITH EXISTING THERMOSTAT/CONTROLS.

8. VARIABLE SPEED SUPPLY FAN

7. CRANKCASE HEATER

6. LOW AMBIENT CONTROL

5. OUTSIDE AIR DAMPER SHALL BE SET TO PROVIDE FRESH AIR EQUAL TO THE MEASURED OUTSIDE AIRFLOW RECORDED IN T&B REPORT PERFORMED PROIR TO START OF CONSTRUCTION.

4. DISCONNECT SWITCH

3. WALL MOUNTED PROGRAMMABLE THERMOSTAT/CONTROLLER WITH BACNET CAPABILITY TO TIE IN TO EXISTING BMS

2. R-410A REFRIGERANT

1. COOLING CAPACITY BASED ON 95º F OUTDOOR AIR TEMPERATURE

NOTES:

69CU-1 / 69GF-1 3 R410A 14.5 1200 NOTE 5 0.5 0.5 115 / 1 70 60 59 17" 80 / 67 32.7 25.9 17.8 30 208 / 1 186 CARRIER 24ACA436C003 CAPMP3617ALA 59MN7A060V17-14 1 - 8

67CU-3 / 67GF-3 4 R410A 14.5 1600 NOTE 5 0.5 1.0 115 / 1 70 80 78 21" 80 / 67 44.3 33.7 8.4 15 460 / 3 243 CARRIER 24AHA448A006 CAPMP4821ALA 59MN7A080V21--20 1 - 8

67CU-2 / 67GF-2 4 R410A 14.5 1600 NOTE 5 0.5 1.0 115 / 1 70 80 78 21" 80 / 67 44.3 33.7 8.4 15 460 / 3 243 CARRIER 24AHA448A006 CAPMP4821ALA 59MN7A080V21--20 1 - 8

67CU-1 / 67GF-1 5 R410A 14.5 1800 NOTE 5 0.5 1.0 115 / 1 70 98 95 21" 80 / 67 57.8 43.4 9.7 15 460 / 3 245 CARRIER 24AHA460A006 CAPMP6021ALA 59MN7A10021-20 1 - 8

63CU-7 / 63GF-7 3 R410A 14.5 1000 NOTE 5 0.5 0.5 115 / 1 70 60 59 17" 80 / 67 33.1 24.6 -- -- 208 / 1 214 CARRIER 24AHA436A006 CAPMP3617ALA 59MN7A060V17-14 1 - 8

63CU-6 / 63GF-6 4 R410A 14.5 1700 NOTE 5 0.5 1.0 115 / 1 70 80 78 21" 80 / 67 44.3 33.7 8.4 15 460 / 3 243 CARRIER 24AHA448A006 CAPMP4821ALA 59MN7A080V21--20 1 - 8

63CU-5 / 63GF-5 3 R410A 14.5 1200 NOTE 5 0.5 0.5 115 / 1 70 60 59 17" 80 / 67 33.6 26.39 7.6 15 460 / 3 214 CARRIER 24AHA436A006 CAPMP3617ALA 59MN7A060V17-14 1 - 8

63GF-4 4 R410A 14.5 1400 NOTE 5 0.5 1.0 115 / 1 70 80 78 21" 80 / 67 44.3 33.7 EXISTING CARRIER EXISTING CAPMP4821ALA 59MN7A080V21--20 1 - 5 , 8 , 9

63GF-3 5 R410A 14.5 1800 NOTE 5 0.5 1.0 115 / 1 70 98 95 21" 80 / 67 57.8 43.4 EXISTING CARRIER EXISTING CAPMP6021ALA 59MN7A10021-20 1 - 5 , 8 , 9

63CU-2 / 63GF-2 4 R410A 14.5 1500 NOTE 5 0.5 1.0 115 / 1 70 80 78 21" 80 / 67 44.3 33.7 8.4 15 460 / 3 243 CARRIER 24AHA448A006 CAPMP4821ALA 59MN7A080V21--20 1 - 8

63GF-1 5 R410A 14.5 1800 NOTE 5 0.5 1.0 115 / 1 70 98 95 21" 80 / 67 57.8 43.4 EXISTING CARRIER EXISTING CAPMP6021ALA 59MN7A10021-20 1 - 5 , 8 , 9

TOTAL SENSIBLE

HP

VOLTAGE /

PHASE

EAT (°F)

INPUT

(MBH)

OUTPUT

(MBH)

CABINET

WIDTH

EAT db/wb °F

CAPACITY (MBH)

MCA MOCP

VOLTAGE /

PHASE

DX COIL FURNACE / AHU

DESIGN

CFM

OA CFM

E.S.P.

(IN WG)

FAN DATA GAS HEATING DATA DX COOLING COIL DATA ELECTRICAL

WEIGHT

(LBS)

MANUFACTURER OUTDOOR UNIT

MARK

NO.

NOMINAL

TONS

REFRIG. SEER

INDOOR UNIT OUTDOOR UNIT BASIS OF DESIGN

NOTES

SPLIT SYSTEM DX COOILING W/GAS FURNACE SCHEDULE

8. VARIABLE SPEED SUPPLY FAN

7. CRANKCASE HEATER

6. LOW AMBIENT CONTROL

5. CONTRACTOR TO SET OUTSIDE AIR DAMPER AND SUPPLY AIR RATES EQUAL TO THE ORIGINAL EQUIPMENT OPERATION

4. DISCONNECT SWITCH

3. WALL MOUNTED PROGRAMMABLE THERMOSTAT/CONTROLLER WITH BACNET CAPABILITY TO TIE IN TO EXISTING BMS

2. R-410A REFRIGERANT

1. COOLING CAPACITY BASED ON 95º F OUTDOOR AIR TEMPERATURE

NOTES:

67CU-4 / 67AH-4 1.5 R410A -- / 14.0 600 NOTE 5 0.4 0.33 208 / 1 26.1 30 5 THROWAWAY 2 18.0 9.6 17.8 13.6 208 / 1 11.8 20 170 CARRIER 25HCC518A003 FB4CNP018L05 1 - 8

DESIGN

CFM

OA CFM

E.S.P.

(IN WG)

HP

VOLTAGE /

PHASE

MCA MOCP

AUX. HEAT

(kW)

TYPE

THICKNESS

(in.)

@47°F

(MBH)

@17°F

(MBH)

TOTAL

(MBH)

SENSIBLE

(MBH)

VOLTAGE /

PHASE

MCA MOCP

FAN DATA ELECTRICAL DATA FILTER DATA HEATING CAPACITY COOLING CAPACITY ELECTRICAL DATA

WEIGHT

(LBS)

MANUFACTURER

HEAT PUMP UNIT

(OUTDOOR)

AIR HANDLING UNIT

(INDOOR)

MARK

NO.

NOMINAL

TONS

REFRIG.

SEER /

EER

INDOOR UNIT OUTDOOR UNIT BASIS OF DESIGN

NOTES

SPLIT SYSTEM HEAT PUMP SCHEDULE

8. VARIABLE SPEED, EC PLUG FANS (QTY 2)

7. DIGITAL SCROLL COMPRESSORS / DUAL CIRCUIT

6. DISCONNECT

5. STEAM CANISTER HUMIDIFIER

4. NETWORK INTERFACE CARD TO CONNECT TO EXISTING BMS

3. DUCT KIT, HIGH TEMPERATURE STAT, AND FILTER CLOG INDICATOR

2. MODULATING HOT GAS REHEAT AND LOW AMBIENT CONTROL

1. WALL MOUNTED CONTROLLER FOR COMPLETE OPERATION AS NOTED ON PLANS AND SPECIFICATIONS

NOTES:

45AC-4 2ND FLOOR 885 - 75 50 1/2 0.3 - - 21.8 16.7 - 4.7 4.3 2 MERV 8 208 / 1 16.4 25 13.4 208/1 42.8 45 34.2 45CU-4 LEIBERT PFH027A-PLN MMD24ENPHE 1 - 6

45AC-3 2ND FLOOR 8,000 - 75 50 -- 0.3 - - 203 162 - 25 22 4 MERV 8 460 / 3 6.3 15 5.6 460 / 3 69.4 70 57.1 45CU-3 LEIBERT MCL110E8 DS053ADA1E1 1 - 8

45AC-2 2ND FLOOR 750 -- 75 50 0.2 0.3 - - 18.4 15.3 - 2.5 2 MERV 8 208 / 1 14.8 25 12.1 208 / 1 7.8 15 6.2 45CU-2 LEIBERT PFH020A-PLN MMD18ENPH0 1 - 6

45AC-1 2ND FLOOR 750 -- 75 50 0.2 0.3 - - 18.4 15.3 - 2.5 2 MERV 8 208 / 1 14.8 25 12.1 208 / 1 7.8 15 6.2 45CU-1 LEIBERT PFH020A-PLN MMD18ENPH0 1 - 6

DB

(°F)

RH

(%) HP

E.S.P.

(I.W.C.)

RPM

MAX

HEATING

TOT. (MBH)

COOLING

TOT. (MBH)

COOLING

SENS (MBH)

HOT GAS

REHEAT (MBH)

FILTER THK

(IN)

FINAL

FILTER

VOLTAGE /

PHASE

MCA MOCP FLA

VOLTAGE /

PHASE

MCA MOCP FLA MANUFACTURER

MODEL

(OUTDOOR)

MODEL

(INDOOR)

MARK LOCATION

NOMINAL

AIRFLOW

(CFM)

MINIMUM

OA (CFM)

ENT. COND INDOOR FAN COILS ELECTRIC

REHEAT COIL

(kW)

STEAM

HUMIDIFIER

(LB/HR)

FILTERS ELECTRICAL (OUTDOOR) ELECTRICAL (INDOOR)

MATCHING

HEAT PUMP

BASIS OF DESIGN

NOTES

COMPUTER ROOM SPLIT SYSTEM SCHEDULE

MAR 2020 B-3 DESIGN SUBMITTAL

NOTE: "EQUAL TO" MANUFACTURERS CAN BE SUBMITTED FOR ALL UNITS DESCRIBED IN THE

SCHEDULE AS LONG AS THEY MEET OR EXCEED THE PERFORMANCE AND SPECIFICATIONS

0 1" 2"

SCALE

FILENAME

DESIGNED BY:

DRAWN BY:

CHECKED BY:

ISSUE DATE DESCRIPTION

1 2 3 4 5 6 7 8

D

C

B

A

SHEET

D. WORLEY

D. WORLEY

M. DIMOFF

CONTRACT #: W9133L-15-D-0004

ANG PROJECT #: FJRP142610

HDR PROJECT #: 10137178

CHARLOTTE DOUGLAS INT'L AIRPORTREPLACE HVAC SYSTEMS

BASE WIDE - CHARLOTTE

NC AIR NATIONAL GUARD

145TH AIRLIFT WING

CHARLOTTE, NC

99M003

N. OVERBY

10137178-02-MP_Master.rvt

MECHANICAL SCHEDULES

3. CONDENSATE NUETRALIZATION KIT

2. BOILER OPERATING POINTS AND WATER SETPOINTS TO MATCH EXISTING SYSTEM OPERATION

1. ASME CSD-1 DDC CONTROLS THAT CAN BE INTEGRATED BUILDING DDC CONTROLS SYSTEMS, FM FUEL TRAIN AND SAFETY TRIM

NOTES:

45B-1 MECH RM CONDENSING 1,999 1,920 1942 96% 160 NOTE 2 14.5 16 20 120 / 1 DIV. 26 8 8 LOCHINVAR FB-2001 1 - 3

INPUT

(MBH)

OUTPUT

(MBH)

GAS

(CFH)

MAX.

EFF.

EWT

(°F)

LWT

(°F)

FLOW MIN/MAX

(GPM)

PRESS.

LOSS (FT)

AMPS MOCP VOLT/PH DISC.

DIA.

(IN)

DIA.

(IN)

MANUFACTURER MODEL

MARK LOCATION TYPE

CAPACITY PRESS.

RATING

(PSI)

WATER ELECTRICAL DATA FLUE C.A. BASIS OF DESIGN

NOTES

BOILER SCHEDULE

1. CONTRATOR TO MEASURE AND MATCH EXISTING

NOTES:

45P-4 MECH. RM HOT WATER LOOP CENTRIFUGAL 199 - - - 155 - 20 - 460 / 3 CS DIV. 26 BELL & GOSSETT 2.5AC 1

45P-3 MECH. RM HOT WATER LOOP CENTRIFUGAL 199 - - - 155 - 20 - 460 / 3 CS DIV. 26 BELL & GOSSETT 2.5AC 1

45P-2 MECH. RM CHILLED WATER LOOP CENTRIFUGAL 152 - - - 60 - 5 - 460 / 3 CS DIV. 26 BELL & GOSSETT 2BD 1

45P-1 MECH. RM CHILLED WATER LOOP CENTRIFUGAL 152 - - - 60 - 5 - 460 / 3 CS DIV. 26 BELL & GOSSETT 2BD 1

02P-1 MECH. RM HOT WATER LOOP CENTRIFUGAL 38 140 180 145 45 61.8 1.5 3450 208 / 1 VARIABLE DIV. 26 BELL & GOSSETT 1.25AAB

HP

(WATTS)

RPM VOLT/PH

CONTROL

TYPE

DISC. BY MANUFACTURER MODEL

MARK LOCATION SERVES TYPE

FLOW

GPM

TEMP

OPER

To, ˚F

TEMP

MAX.

˚F

PRESS.

MAX.

PSIG

HEAD

FT WG

'@ To

MIN

EFF

MOTOR DATA BASIS OF DESIGN

NOTES

PUMP SCHEDULE

1. PROVIDE ALL WIRING, TRANSFORMERS AND DEVICES NECESSARY FOR COMPLETE INTEGRATION WITH BUILDING HVAC DDC CONTROL SYSTEM.

NOTES:

VAV-3.8 BUILDING 2 9 225 735 225 735 0.27 2 17.3 1 0.25 65 86.6 140 105.1 30 PRICE SDV 1

VAV-3.7 BUILDING 2 9 210 700 210 700 0.25 2 17 1 0.25 65 87.3 140 105.7 30 PRICE SDV 1

VAV-3.6 BUILDING 2 16 615 2040 615 2040 0.34 2 47.3 2.75 0.87 65 86.4 140 105.1 30 PRICE SDV 1

VAV-3.5 BUILDING 2 12 375 1240 375 1240 0.38 2 28.3 1.75 0.82 65 86 140 107.3 30 PRICE SDV 1

VAV-3.4 BUILDING 2 12 355 1180 355 1180 0.35 2 27.8 1.75 0.82 65 86.7 140 107.8 30 PRICE SDV 1

VAV-3.3 BUILDING 2 14 475 1580 475 1580 0.32 2 35.9 2 0.47 65 85.9 140 103.6 30 PRICE SDV 1

VAV-3.2 BUILDING 2 12 300 1000 300 1000 0.27 2 22.7 1.25 0.45 65 85.8 140 103.3 30 PRICE SDV 1

VAV-3.1 BUILDING 2 12 345 1140 345 1140 0.33 2 27.5 1.75 0.82 65 87.2 140 108.1 30 PRICE SDV 1

VAV-2.21 BUILDING 2 12 320 1060 320 1060 0.3 2 25.2 1.5 0.62 65 86.8 140 106.1 30 PRICE SDV 1

VAV-2.20 BUILDING 2 10 255 850 255 850 0.34 2 20 1.25 0.37 65 86.6 140 107.7 30 PRICE SDV 1

VAV-2.19 BUILDING 2 9 195 650 195 650 0.22 2 16.6 1 0.25 65 88.5 140 106.5 30 PRICE SDV 1

VAV-2.18 BUILDING 2 14 465 1540 465 1540 0.3 2 35.6 2 0.47 65 86.3 140 103.9 30 PRICE SDV 1

VAV-2.17 BUILDING 2 8 175 575 175 575 0.33 2 12.8 0.75 0.12 65 85.4 140 105.5 30 PRICE SDV 1

VAV-2.16 BUILDING 2 4 85 280 85 280 0.14 2 7.9 0.5 0.04 65 90.7 140 108.4 30 PRICE SDV 1

VAV-2.15 BUILDING 2 4 85 275 85 275 0.13 2 7.8 0.5 0.04 65 91 140 108.6 30 PRICE SDV 1

VAV-2.14 BUILDING 2 7 135 440 135 440 0.25 2 11.8 0.75 0.12 65 89.5 140 108.4 30 PRICE SDV 1

VAV-2.13 BUILDING 2 8 160 520 160 520 0.28 2 12.4 0.75 0.12 65 86.9 140 106.6 30 PRICE SDV 1

VAV-2.12 BUILDING 2 8 150 485 150 485 0.25 2 12.2 0.75 0.12 65 88 140 107.4 30 PRICE SDV 1

VAV-2.11 BUILDING 2 6 90 300 90 300 0.22 2 8.1 0.5 0.04 65 89.6 140 107.6 30 PRICE SDV 1

VAV-2.10 BUILDING 2 7 125 415 125 415 0.22 2 11.5 0.75 0.12 65 90.4 140 109.1 30 PRICE SDV 1

VAV-2.9 BUILDING 2 9 225 735 225 735 0.27 2 17.3 1 0.25 65 86.6 140 105.1 30 PRICE SDV 1

VAV-2.8 BUILDING 2 12 315 1035 315 1035 0.29 2 25 1.5 0.62 65 87.2 140 106.3 30 PRICE SDV 1

VAV-2.7 BUILDING 2 12 330 1090 330 1090 0.31 2 25.4 1.5 0.62 65 86.4 140 105.8 30 PRICE SDV 1

VAV-2.6 BUILDING 2 10 235 770 235 770 0.29 2 17.5 1 0.25 65 85.9 140 104.6 30 PRICE SDV 1

VAV-2.5 BUILDING 2 8 180 590 180 590 0.34 2 12.9 0.75 0.12 65 85.1 140 105.3 30 PRICE SDV 1

VAV-2.4 BUILDING 2 10 245 810 245 810 0.32 2 19.7 1.25 0.37 65 87.3 140 108.2 30 PRICE SDV 1

VAV-2.3 BUILDING 2 12 330 1085 330 1085 0.31 2 25.3 1.5 0.62 65 86.5 140 105.8 30 PRICE SDV 1

VAV-2.2 BUILDING 2 12 305 1015 305 1015 0.28 2 24.8 1.5 0.62 65 87.5 140 106.5 30 PRICE SDV 1

VAV-2.1 BUILDING 2 12 400 1320 400 1320 0.42 2 28.8 1.75 0.82 65 85.1 140 106.6 30 PRICE SDV 1

VAV-1.6 BUILDING 2 16 600 2000 600 2000 0.33 2 47.1 2.75 0.87 65 86.7 140 105.3 30 PRICE SDV 1

VAV-1.5 BUILDING 2 16 605 2010 605 2010 0.33 2 47.1 2.75 0.87 65 86.6 140 105.3 30 PRICE SDV 1

VAV-1.4 BUILDING 2 14 430 1415 430 1415 0.27 2 32.5 1.75 0.37 65 86.2 140 102.3 30 PRICE SDV 1

VAV-1.3 BUILDING 2 8 190 630 190 630 0.38 2 14.9 1 0.19 65 86.7 140 109.9 30 PRICE SDV 1

VAV-1.2 BUILDING 2 12 380 1255 380 1255 0.39 2 28.4 1.75 0.82 65 85.8 140 107.2 30 PRICE SDV 1

VAV-1.1 BUILDING 2 14 550 1830 550 1830 0.4 2 43.5 2.75 0.82 65 86.9 140 108 30 PRICE SDV 1

MIN MAX MIN MAX

MAX AIR PD

(IN WG)

# OF

ROWS

CAPACITY

(MBH)

FLOW

(GPM)

WPD

(FT)

EAT

(°F)

LAT

(°F)

EWT

(°F)

LWT

(°F)

MANUFACTURER MODEL

MARK LOCATION

AIR INLET

SIZE (IN)

COOLING

AIRFLOW (CFM)

HEATING

AIRFLOW (CFM)

REHEAT COIL MAX

DISCHARGE

NC

BASIS OF DESIGN

NOTES

VAV TERMINAL BOXES WITH HOT WATER REHEAT SCHEDULE

MAR 2020 B-3 DESIGN SUBMITTAL

4. 2 INCH MERV 8 FILTER

3. LOW AMBIENT OPERATION KIT

2. WALL MOUNTED THERMOSTAT.

1. DISCONNECT SWITCH

NOTES:

72WMU-2 800 0.3 23.6 18.0 R410A 9.0 46 50 208 / 1 8 310 BARD W24A2-A08 1 - 4

72WMU-1 800 0.3 23.6 18.0 R410A 9.0 46 50 208 / 1 8 310 BARD W24A2-A08 1 - 4

(MBH) (MBH)

TOTAL SENSIBLE

MCA MOCP

VOLTAGE /

PHASE

ELEC. HEAT

(kW)

MANUFACTURER MODEL

MARK

NOMINAL

CFM

ESP

(IN WC)

COOLING CAPACITY

REFRIG.

MIN

EER

ELECTRICAL DATA

WEIGHT

(LBS)

BASIS OF DESIGN

NOTES

SINGLE PACKAGED VERTICAL AIR CONDITIONER SCHEDULE

1. PROVIDE BLADDER RATED FOR 215˚F AND TANK/SYSTEM MAWP = 125 PSIG

NOTES:

02ET-1 MECH. RM HW HEATING 45 140 40 40 10 12 9 3 12 x 22 AMTROL EXTROL AX-15-V 1

MAX MIN MAX MIN

MANUFACTURER MODEL

MARK LOCATION

SYSTEM

SERVED

SYSTEM

VOLUME

GAL

TEMP RANGE

°F

PRESS RANGE

PSI

BLADDER

PRESS

PSI

TANK

VOLUME

GAL

ACCEPTANCE

VOLUME

GAL

TANK SIZE

DIA x L

IN

BASIS OF DESIGN

NOTES

EXPANSION TANK SCHEDULE

NOTE: "EQUAL TO" MANUFACTURERS CAN BE SUBMITTED FOR ALL UNITS DESCRIBED IN THE

SCHEDULE AS LONG AS THEY MEET OR EXCEED THE PERFORMANCE AND SPECIFICATIONS