This document includes an invitation for bids for repair and maintenance services at Hangar Building 25 for the Montana Air National Guard. Key details include replacement of the lower roof membrane, asphalt and drainage repair, installation of floor rails and an overhead crane, replacement of door hardware, installation of a high performance floor coating system, modifications to the fire sprinkler system, and mechanical and electrical upgrades. The pre-bid conference was scheduled for June 13, 2023 and questions were due by June 23, 2023. The bid opening is July 7, 2023. The contract duration is 120 calendar days after notice to proceed. This project is set aside 100% for small businesses with a NAICS code of 236220 and size standard of $45,000,000. The estimated value is between $1,000,000 to $5,000,000. Interested contractors must register in the System for Award Management. The solicitation and amendments will be posted to the Contract Opportunities page at SAM.gov.
View the file
Other files
Show all 28
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
QUESTIONS AND ANSWERS RELATED TO :
SOLICITATION W50S7L-23-B-0002
AS of 30 June 2023
Q1. E0.00 – The Electrical Installation Note #6 states “Contractor shall remove and reinstall all ceiling tiles as required for the execution of electrical work. contractor shall replace ceiling tiles with identical material where damaged by this contractor.”
the electrical renovation note #5 states “the general contractor is responsible for removal and replacement of ceilings, ceiling tiles, and ceiling grids associated with areas of work by all contractors. notify the general contractor of affected areas prior to bidding.” Is the GC or the EC responsible for ceiling tile removal/replacement?
A1. The GC will be responsible for the ceiling tile removal/replacement.
Q2. The submittal register included in SPEC VOL 1 Revised 5.30.23 lists Division 28 – Electronic Safety and Security Submittals for Section 28 31 64 Interior Fire Detection and Alarm System. There appears to be no requirements for FA in the project. Please confirm.
A2. There is no fire alarm in the scope of work.
Q3. Note 214/E1.00 states “Refer to Architectural plans and specifications for additional electrical requirements and information prior to start work.” There are no architectural plans for the solicitation. Please advise.
A3. See page A2.00 Door Schedule B-103A for details.
Q4. Is there a warranty on the existing roof? What specific material is the existing roof? This is needed for the adhesive compatibility for the lightning protection system.
A4. Upper and Lower roof are 60mil EPDM. This roofing was installed in 2011.
Q5. Note 212/E1.00 – Will the existing converter be turned over to the owner and if so where? Or will the E.C. be required to dispose of it?
A5. The EC will be required to dispose of it off site.
Q6. In reference to Sheet A1.20 on the KEYNOTES - DEMOLITION PLAN, Item numbered 6, list rooms B109, B118, B119, B107B, and item number 11, list room B122B to clean floor & prep for installation of (N) Flooring/Floor Coating System.
Clean floor per New Flooring/Floor coating MFR. Conc. Slab to remain. On Sheet A2.00, FIRST FLOOR ROOM FINISH SCHEDULE - these rooms are not called out (labeled) or identified to receive a type of New Flooring.
A6. Rooms which require the removal of existing flooring and/or cleaning/prep of exisitng concrete slab to receive new flooring are shown and keynoted on 1/A1.20, and for new flooring, are shown and keynoted on 1/A2.00. See included reissued sheet A1.20 for updated room finish schedule.
Q7. Sheet A2.10 Reflected Ceiling Plan. Are the GWB Ceiling that get patched and/or removed and replaced for the mechanical, are they suspended GWB Ceilings. Please clarify.
A7. They are believed to be suspended.
Q8. On Sheet C401 Concrete Pavement Joint Plan items labeled as E (D) and E (U) what two detail does these two apply to on Sheet C402.
A8. Joints labeled E(D) on Sheet C401 refer to Detail E/C402, the Doweled (D) option.
Joints labeled E(U) on Sheet C401 refer to Detail E/C402, the Undoweled (U) option.
Q9. On Sheet C401 Concrete Pavement Joint Plan item labeled as E (D), what detail does this apply to on Sheet C402.
A9. Joints labeled E(D) on Sheet C401 refer to Detail E/C402, the Doweled (D) option.
Q10. Would it be possible to clarify on the Bid Items 0001 through 0006 what activity items exactly applied to each bid item. For example, what activities would apply to Item 0002 Architectural, Structural.
A10. See the bid Schedule
Q11. Sheet A2.01 is there a spec section on the (N) Steel Lockers. Please clarify.
A11. See Amendment W50S7L-23-B-0002-P0003
Q12. Has brought up at the Prebid, I believe the 120-day completion date is unrealistic. I would recommend 180 Days.
A12. PoP has been changed to 180 days after NTP
Q13. There was some discussion at the Prebid and site visit walk thru concerning on Sheet A1.20, item 6 – states Remove all equipment and furnishings as REQ. Clean floor per new flooring/floor coatings MFR. Coord/ W/FM/Government. Is it your intent that the General Contractor is responsible for removing all the equipment and furnishings in rooms B119, B118, B109, B107A, and B107B. If so, where are they to be stored and is the General Contractors responsible for replacing the equipment and furnishings back it their original room location after the New Flooring installation has been completed. Please clarify. Item 11 – on Sheet A1.20, states cleaning & prep for installation of (N) floor coating system per MFR but mentions nothing about removing any equipment and furnishes that are located in this room (B122B). Please clarify.
A13. The Government will remove and reinstall the equipement form the areas where the floor coating work will occur.
Q14. On 0006 - Additive Bid For JKSE 172220. Would you please clarify the scope of work for this bid item. Does it include all demo on Sheet C100 and all work shown on Sheet C101 to include new Concrete Pavement, Asphalt Pavement, Landscaping, Concrete Sidewalk, and Storm Water Improvements.
A14. Yes, CLIN 0006- Additive bid includes demolition, time, materials, incidentals, bond, all work to complete the work on the C100 and C101.
Q15 We have some experience with this hangar from 2016 and at the time, some of the MANG members had some unrealistic expectations on how air tight rolling steel door can be. The doors all had baffles, bottom seals and guide brush seals as specified but rolling steels doors are by their nature, leaky when compared to sectional doors. Once we started Door Systems, we addressed the job that Wally’s Overdoor installed and added some extra rubber guide seals and caulked the guides to the walls on the tire shop (B101C) as an experiment in air infiltration. They were better but still leaky as coiling doors are. B-103A is also a special case as it is a door that needs to drop automatically in case the foam fire retardant system is triggered to contain the foam from going outside the building. Because it needs to drop automatically, that door cannot have seals with too much friction against it or it will not drop. That door has a special operator tied into the foam system and the fire alarm. If we could do a site visit to get all the serial numbers from the existing doors and have a meeting about realistic air infiltration expectations, we could then provide a bid to add extra seals to those existing doors.
A15. This is an acceptable approach. During the B80 project in 2020 this door, seal, and baffle work was completed on the exterior roll up doors with great success.
Q16. Per sheet E1.03, Flag note 28 states to re-certify building 25 and 80 however during our site inspection we were not asked to inspect building 80 and there is no direction in the bid documents. Assuming both building have current certification, we recommend the certification by the Underwriters Laboratory be a limited scope inspection for the roof top only, since the work being done is a re-roof and only rooftop lightning protection will be worked on. Is this acceptable?
A16. Yes, that is acceptable. Building 25 and Building 80 each have separate certifications. Only the B25 new lighting protection system will need to be recertified.
Q17. Keynote #6 on A1.20 states; “Remove all equipment and furnishings as required.” This note pertains to numerous rooms. Where will the contractor be required to move the equipment and furnishings to? Is the contractor required to move and reconnect equipment and furnishings afterward?
A17. The Government will remove and reinstall the equipment form the areas where the floor coating work will occur.
Q18. Can you please provide Men’s / Women’s locker specifications and approximate dimensions?
A18. See Amendment W50S7L-23-B-0002-P0003c
Q19. Detail 4/S5.0 shows an equipment pad. Can you tell us where this is located and the size of pad?
A19. See 1/M2.00, ARU-1, located in hangar. Coordinate size with unit manufacturer's requirements.
Q20. Breakroom: A1.20 shows demo a portion of the wall for new doorway, A2.00 shows the new doorway, detail 2/2.00 shows the relocated refrigerator in that new doorway. Please advise.
A20. Coordinate location of relocated refrigerator with Government.
Q21. Can you provide the site visit sign-in sheet?
A21. Sign in sheet has been uploaded to SAM.gov Contracting Opportunities
Q22. Line 11 on the solicitation states 120 days to complete the project. Can this be extended?
A22. PoP has been changed to 180 days after NTP
Q23. Section 010000 paragraph 3.4a state we are to provide metering for our utilities. Is this a requirement for this project?
A23. Yes
Q24. What FOD requirements apply for this project?
A24. FOD and Garbage control is paramount it doesn't leave the work area and become FOD. The exterior building work will occur within a Freezone where Aircraft will not be operating. it doesn't leave the work area and become FOD. The Military expectation for FOD and Garbage is, " If you see it pick it up and dispose of it properly is a container."
Any loose garbage not only affects the MT ANG but also the Great Fall International Airport and FedEX.
Q25. Fire sprinkler modifications: There is a conflict between A2.10 and F1.00 regarding how many rooms are incorporated into the work area. Please advise.
A25. F1.00 takes precedence.
Q26. Is there access for the fire sprinkler modifications to be done without removing the ACT and GWB ceilings in all the rooms?
A26. It is approximately 17 feet between the ACT and fire sprinkler lines in the shop and office areas. How the Contractor accesses the lines is up to the Contractor and Ways and Means discussion.
Q27. Will the government remove the scaffolding in the hangar prior to the flooring work?
A27. Yes.
Q28. On page E1.00 flag note 217, is it the intent of the engineer for a new feed for the disconnect or just provide the disconnect and feed to the ARU-1 unit? Flag note 226 page E1.00, are the electrical contractors expected to ground all the floor tiles or just the one? Flag note 215 on page E1.01 calls for 5 receptacles and data outlets, there are 9 of each on the drawing in room B242. Are the 5 of each in the flag note additional? Can I get a business name and contact number or email who installed the current lightning protection system?
A28. 1. ARU-1 is a new unit, provide disconnect and full connections as shown. 2.
Just one connection. 3. Nine (9) is correct. 4. This is something that MTANG would need to provide.
Q29. Would it be possible to get an additional walk through for the project in building 25?
A29. No additional site visits will be held.
Q30. Who is providing the Builders Risk Policy on the project. Please clarify.
A30. Builders Risk Policy is not provided by the Government.
Q31. The solicitation states you have 90 days to award. Is it your intent to make an award before this date. If you take 90 days to award that puts the concrete pavement into the winter. Please Clarify.
A31. Yes, and the Government is aware of the supply, mix design, and weather limitations of the roofing and concrete work and that they may need to happen in the Spring/ Summer of 2024.
Q32. Do we have to temporary fence the areas around the concrete pavement and asphalt paving that is removed and replaced.
A32. The determination to place Temporary Fencing around the Contractor staging is up to the Contractor.
Q33. On sheet S5.0, Detail 2/S5.0, Note reference to “ Expansion Joint Per 1.S1.1.” Detail 1.S1.1 identifies three different details for jointing. Which one does this refer to use for Detail 2.S5.0. Joint.
A33. Detail calls out 'expansion joint per 1/S1.3'. Expansion joint clearly labeled on 1/1.3, of the three shown.
Q34. Can you provide a list of the equipment that has to be moved?
Approximate weight? Is the equipment hard wired to a disconnect? Where do we store this equipment? Does any of the equipment require to be re‐calibrated or re-certified?
A34. The Government will remove and reinstall the equipment form the areas where the floor coating work will occur.
Q35. Confirming we are only to paint the areas shown on the finish schedules or on plan notes?
A35. Yes, only paint areas indicated with shading and/or keynotes to that effect on the drawings. See the room finish schedule on the updated A2.00 sheet.
Q36. Sheet F1.00 note 3: How high is the “main ceiling” from the floor and also from suspended ceiling?
A36. Susponcreteended ceiling is 10' from finish floor. Floor to Floor height is 13'-4".
The upper suspended ceiling by the Fire Sprinklers is 26' -6".
Q37. A2.00 Door Schedule: Can you provide the list of items required, brand and model for each hardware set?
A37. See Specifications Vol. 1.0, Section 08 71 00 - Door Hardware.
Q38. Section 087100 2.8.1: states that the OHD power operator is for the 12x10 door (B107B‐B). The door schedule comments state the operator is for the 14x10 door (B103‐A). Which one gets the operator or do both get operators and controls?
A38. Door B103-A is the only door to receive the operator and exterior keyed switch.
The specifications section lists the incorrect door number.
Q39. Would it be possible for you to arrange and escort to come take a look at the apron?
A39. No additional site visits will be held.
Q40. The flooring companies would like to know on Sheet A2.00 if there is an 4” rubber Base.
A40. Base present and to remain in rooms around perimeter of main hangar. Not present in main hangar space.
Q41. Does Sherwin Williams Resuprime, Resuflor, and Resutile high performance product line meet the High Performance flooring specification?
A41. Yes, Sherwin Williams recently changed the name of their industrial grade high performance flooring product to General Polymers Resuprime, Resuflor, and Resutile.