BRKR009063 Addendum No. 1 SIGNED.pdf
PDF 9 MB Posted
- Attached to
- New Security Building Federal contract opportunity
- Solicitation number
- W50S6M24B0002
About this file
This document is an addendum to a solicitation for the construction of a new Security Building for the 117th Air Refueling Wing in Birmingham, Alabama. The project, numbered BRKR009063, includes sitework, subgrade excavation, building foundations, architectural, plumbing, mechanical, and electrical work, as well as the relocation of existing utilities for an approximately 9,941 square foot building. The project magnitude is between $5,000,000 and $10,000,000. The solicitation is a 100% small business set-aside with a North American Industry Classification System (NAICS) code of 236220 and a small business size standard of $45,000,000. The addendum revises several drawings and specifications, including the life safety plan, site grading and drainage, landscape details, and insulation requirements. It also provides clarification on the demolition of existing buildings and site access.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| OF 1419 Pg3.pdf | ||
| OF 1419 Pg1.pdf | ||
| SF-30 Amendment 001.pdf | ||
| BRKR 009063 RFI Responses 001 SIGNED.pdf | ||
| PreBid Security.pptx | PPTX presentation | |
| Security Building Pre Bid Meeting 18 July 24 Sign in Roster_0001.pdf | ||
| BRKR 009063 - Type B3 Drawings SIGNED.pdf | ||
| J and A for Brand Name-Sole Source - Security- KMC Controls_Redacted.pdf | ||
| J and A for Brand Name-Sole Source - Security- Monaco_Redacted.pdf | ||
| BRKR009063 Type B3 Specifications Volume 2 SIGNED.pdf | ||
| BRKR009063 Type B3 Specifications Volume 3 SIGNED.pdf | ||
| W50S6M-24-B-0002.pdf | ||
| BRKR009063 Type B3 Specifications Volume 1 SIGNED (1).pdf | ||
| J and A for Brand Name-Sole Source - Security- Stanley Best Locks_Redacted.pdf | ||
| 117th Guest List.xlsx | XLSX spreadsheet | |
| J and A for Brand Name-Sole Source - Security - Advantor_Redacted.pdf |
Show all 16
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SEAY, SEAY & LITCHFIELD, P.C.
1115 S. COURT ST. MONTGOMERY, AL 36104
(334) 263-5162
MAIL@SSLARCH.COM
WWW.SSLARCH.COM
MONTGOMERY DOTHAN AUBURN HUNTSVILLE
The drawings and specifications for the New Security Building, dated June 2024 are amended as follows.
Where there are conflicts between the plans and specifications, previously issued addendum, and this addendum, this addendum shall govern.
Where drawing revisions are included, drawing revisions are indicated within revision clouds.
Where specification sections are modified:
- Added specification text is included as follows: bold italicized text
- Deleted text is indicated as follows: in bold text with a strikethrough.
ITEM NO. 1: The following sheets are being reissued:
• Delete drawing sheet LS1.0 “Life Safety Plan, Criteria, and Calculations” and replace it with the attached drawing sheet LS1.0 with a revised date of 16 July 2024.
• Delete drawing sheet C4.1 “Site Grading and Drainage Plan” and replace it with the attached drawing sheet C4.1 with a revised date of 11 July 2024.
• Delete drawing sheet C7.1 “Pavement Joint Layout” and replace it with the attached drawing sheet C7.1 with a revised date of 11 July 2024.
• Delete drawing sheet L1.0 “Landscape Site Plan” and replace it with the attached drawing sheet
L1.0 with a revised date of 6 August 2024.
• Delete drawing sheet L1.1 “Landscape Details” and replace it with the attached drawing sheet
L1.1 with a revised date of 6 August 2024.
• Delete drawing sheet A3.1 “Finish Schedule” and replace it with the attached drawing sheet A3.1 with a revised date of 16 July 2024.
• Delete drawing sheet A5.2 “Wall Sections” and replace it with the attached drawing sheet A5.2 with a revised date of 16 July 2024.
• Delete drawing sheet A9.1 “Floor Pattern Plan” and replace it with the attached drawing sheet
A9.1 with a revised date of 16 July 2024.
ADDENDUM #: 001
DATE: 7 August 2024
TO: CMSgt. Kevin Hall
FROM: Daniel Burton
PROJECT NAME: New Security Building
PROJECT NUMBER: ANG#: BRKR 009063 / SS&L#: 12072
MONTGOMERY DOTHAN AUBURN HUNTSVILLE
• Delete drawing sheet S0.1 “General Notes / Schedule / Typical Details” and replace it with the attached drawing sheet S0.1 with a revised date of 26 July 2024.
ITEM NO. 2: The following specification section is being reissued:
• Delete specification section 07 2100 “Thermal Insulation” and replace it with the attached specification section 07 2100 with a revised date of 16 July 2024.
• Delete specification section 02 4100 “Demolition” and replace it with the attached specification section 02 4100 with a revised date of 7 August 2024.
ITEM NO. 3: Refer to drawings. Delete structural detail 2/S2.3. This detail is not applicable to the current project scope. No HSS purlins are required by the current project scope.
ITEM NO. 4: Refer to drawing sheet C10.1. Change 8” wall thickness dimension to 6” for all pre-cast concrete storm drainage structures.
ITEM NO. 5: Refer to specification section 23 0593. Delete paragraphs A, B, and C of part 1.5 “Quality
Assurance.” The Government will employ the test and balance company through the Architect’s
Contract for Construction Administration services.
ITEM NO. 6: Refer to specification section 01 5000 “Temporary Facilities and Controls.” Delete part
1.07.
ITEM NO. 7: Refer to specification section 10 8500 “Specialties.” Delete paragraph 2.01(A) and replace it with the following:
“Provide 5 – 23-gallon containers compatible with specified lids and trolley assemblies.”
END OF ADDENDUM
F .E
.C
F.E.C.
F .E
.C
F.E.C.
F .E
.C
F .E
.C
F.E.C.
F.E.C.
102 SF
Electrical /Electrical /Electrical /Electrical /
MechanicalMechanicalMechanicalMechanical
70 SF
JanitorJanitorJanitorJanitor
1060 SF
GuardmountGuardmountGuardmountGuardmount
628 SF
Weapons Issue &Weapons Issue &Weapons Issue &Weapons Issue &
StorageStorageStorageStorage 148a
1230 SF
SupplySupplySupplySupply
26 SF
WaterWaterWaterWater
574 SF
Classroom /Classroom /Classroom /Classroom /
CATS TrainingCATS TrainingCATS TrainingCATS Training
396 SF
Squad LeaderSquad LeaderSquad LeaderSquad Leader
Work AreaWork AreaWork AreaWork Area
124 SF
COMMCOMMCOMMCOMM
105 SF
SIPR / NCICSIPR / NCICSIPR / NCICSIPR / NCIC
130a
276 SF
BDOCBDOCBDOCBDOC
99 SF
BDOCBDOCBDOCBDOC
ConferenceConferenceConferenceConference 130b
33 SF
AlarmAlarmAlarmAlarm
323 SF
ConferenceConferenceConferenceConference
RoomRoomRoomRoom
186 SF
HallHallHallHall
506 SF
HallHallHallHall
163 SF
VestibuleVestibuleVestibuleVestibule
110 SF
NCOICNCOICNCOICNCOIC
156 SF
Quality ControlQuality ControlQuality ControlQuality Control
125 SF
Men's LatrineMen's LatrineMen's LatrineMen's Latrine
124 SF
Women's LatrineWomen's LatrineWomen's LatrineWomen's Latrine
115 SF
Intel /Intel /Intel /Intel /
InvestigationsInvestigationsInvestigationsInvestigations
OfficerOfficerOfficerOfficer
101 SF
ResourceResourceResourceResource
ProtectionProtectionProtectionProtection
101 SF
OperationsOperationsOperationsOperations
OfficerOfficerOfficerOfficer
101 SF
FirstFirstFirstFirst
SeargentSeargentSeargentSeargent
144 SF
CommanderCommanderCommanderCommander 133c
244 SF
Waiting &Waiting &Waiting &Waiting &
OrderlyOrderlyOrderlyOrderly 133a
144 SF
ManagerManagerManagerManager
OfficeOfficeOfficeOffice 133b
101 SF
Supt. OfficeSupt. OfficeSupt. OfficeSupt. Office
323 SF
Break RoomBreak RoomBreak RoomBreak Room
366 SF
HallHallHallHall
374 SF
HallHallHallHall
22 OCCUPANTS
6 OCCUPANTS
7 OCCUPANTS
1 OCCUPANT
1 OCCUPANT
6 OCCUPANTS
22 OCCUPANTS
2 OCCUPANTS
8 OCCUPANTS39 OCCUPANTS
3 OCCUPANTS
1 OCCUPANT BUSINESS AREAS CALCULATED AT 150 GROSS SF PER OCCUPANT = 32 OCCUPANTS.
THIS AREA ASIGNED 12 OCCUPANTS
OCCUPANCY OF ALL OTHER ITEMIZED AREAS (SEE PLAN) = 120 OCCUPANTS
TOTAL OCCUPANCY OF THIS AREA = 152 OCCUPANTS
1 OCCUPANT
21.8
21.8
COMMON PATH OF EGRESS
TRAVEL = 86'-7"
COMMON PATH OF EGRESS
TRAVEL = 50'-4"
1 OCCUPANT
.43
.4
76 OCCUPANTS
EWS
1 OCCUPANT
EWC
EWC
13 OCCUPANTS
.43
0.6
0.6
12 OCCUPANTS
4.8
BUSINESS AREAS CALCULATED AT 150 GROSS SF PER OCCUPANT = 32 OCCUPANTS.
THIS AREA ASIGNED 13 OCCUPANTS
OCCUPANCY OF ALL OTHER ITEMIZED AREAS (SEE PLAN) = 120 OCCUPANTS
TOTAL OCCUPANCY OF THIS AREA = 152 OCCUPANTS
BUSINESS AREAS CALCULATED AT 150 GROSS SF PER OCCUPANT = 32 OCCUPANTS.
THIS AREA ASIGNED 1 OCCUPANT
OCCUPANCY OF ALL OTHER ITEMIZED AREAS (SEE PLAN) = 120 OCCUPANTS
TOTAL OCCUPANCY OF THIS AREA = 152 OCCUPANTS
BUSINESS AREAS CALCULATED AT 150 GROSS SF PER OCCUPANT = 32 OCCUPANTS.
THIS AREA ASIGNED 6 OCCUPANTS
OCCUPANCY OF ALL OTHER ITEMIZED AREAS (SEE PLAN) = 120 OCCUPANTS
TOTAL OCCUPANCY OF THIS AREA = 152 OCCUPANTS
9 4
ROOM NAMEROOM NAMEROOM NAMEROOM NAME
Exterior Walls - See Wall Type Plan
Interior Walls - See Wall Type Plan
Door/Frame - See Door Schedule
Room Marker
EXIT TRAVEL PATH
ELECTRIC WATER COOLER - SEE PLUMBINGEWC
1 HOUR FIRE RATING (UL U906 / UL U419)
EMERGENCY EXIT SIGNAGE
FIRE EXTINGUISHER BRACKET
(UL RATED 4A:80B:C - SEE SPECIFICATION SECTION 10 4400)FEB
EWS EMERGENCY EYE WASH STATION
3.2
8 OCCUPANT LOAD
REQUIRED EGRESS COMPONENT WIDTH
SYMBOLS LEGEND:
OCCUPANCY TYPE LEGEND:
IBC GROUP (B) BUSINESS
15 NET SF PER OCCUPANT PER UFC 3-600-01
LOW HAZARD PER NFPA 101
IBC GROUP (B) BUSINESS
150 GROSS SF PER OCCUPANT PER NPFA 101
LOW HAZARD PER NFPA 101
IBC GROUP (B) BUSINESS
300 GROSS SF PER OCCUPANT UFC 3-600-01
LOW HAZARD PER NFPA 101
IBC GROUP (B) BUSINESS
500 GROSS SF PER OCCUPANT PER NPFA 101 (STORAGE) / UFC
3-600-01 (MECHANICAL/ELECTRICAL)
LOW HAZARD PER NFPA 101
IBC GROUP (B) BUSINESS
50 NET SF PER OCCUPANT PER NFPA 101
LOW HAZARD PER NFPA 101
Sheet Number
Sheet Title
Project Title
Job Number
Date
Drawn By
Checked By
S o u th C o u rt S tr ee t M o n tg o m er y, A
L
T el . 3
. 2
3.
W W W .S S L A R C H .C O M
A R C H
IT
E C T U R E
I N T E R
IO
R D
E S
IG
N
LS1.0
Life Safety Plan, Criteria, and Calculations
N ew
S ec u ri ty B u ild in g
7t h A ir R ef u el in g W in g
B ir m in gh am , A
L
12072
JUNE 2024
JJ, NB, DCD, JBW, DOB
DCD
APPLICABLE CODES:APPLICABLE CODES:APPLICABLE CODES:APPLICABLE CODES:
BUILDING CODE..........................UFC 1UFC 1UFC 1UFC 1----200200200200----01 / 2021 INTERNATIONAL BUILDING CODE01 / 2021 INTERNATIONAL BUILDING CODE01 / 2021 INTERNATIONAL BUILDING CODE01 / 2021 INTERNATIONAL BUILDING CODE STRUCTURAL CODE............UFC 3UFC 3UFC 3UFC 3----301301301301----01 / IBC 01 / IBC 01 / IBC 01 / IBC 2021202120212021 PLUMBING CODE............UFC 3UFC 3UFC 3UFC 3----420420420420----01 / IBC 01 / IBC 01 / IBC 01 / IBC 2021202120212021 MECHANICAL CODE....................UFC 3UFC 3UFC 3UFC 3----401401401401----01 / IBC 01 / IBC 01 / IBC 01 / IBC 2021202120212021 ELECTRICAL CODE..........UFC 3UFC 3UFC 3UFC 3----501501501501----01 / IBC 01 / IBC 01 / IBC 01 / IBC 2021202120212021 / NFPA 70/ NFPA 70/ NFPA 70/ NFPA 70
ENERGY CODE...............UFC 1UFC 1UFC 1UFC 1----200200200200----02020202
ACCESSIBILITY CODE......ARCHITECTURAL BARRIERS ACT STANDARDSARCHITECTURAL BARRIERS ACT STANDARDSARCHITECTURAL BARRIERS ACT STANDARDSARCHITECTURAL BARRIERS ACT STANDARDS LIFE SAFETY CODE.........UFC 3UFC 3UFC 3UFC 3----600600600600----01 / NFPA 10101 / NFPA 10101 / NFPA 10101 / NFPA 101 ANTI-TERRORIST FORCE PROTECTION.....UFC 4UFC 4UFC 4UFC 4----010010010010----01(DECEMBER 2018)01(DECEMBER 2018)01(DECEMBER 2018)01(DECEMBER 2018)
IBC CHAPTER 3 AND UFC 3IBC CHAPTER 3 AND UFC 3IBC CHAPTER 3 AND UFC 3IBC CHAPTER 3 AND UFC 3----600600600600----01 OCCUPANCY & USE:01 OCCUPANCY & USE:01 OCCUPANCY & USE:01 OCCUPANCY & USE:
NFPA 101 CHAPTER 6:NFPA 101 CHAPTER 6:NFPA 101 CHAPTER 6:NFPA 101 CHAPTER 6:
• SEE LEGEND ON LIFE SAFETY PLAN
IBC CHAPTER 4 IBC CHAPTER 4 IBC CHAPTER 4 IBC CHAPTER 4 ---- SPECIAL DETAILED REQUIREMENTS: SPECIAL DETAILED REQUIREMENTS: SPECIAL DETAILED REQUIREMENTS: SPECIAL DETAILED REQUIREMENTS:
• NOT APPLICABLENOT APPLICABLENOT APPLICABLENOT APPLICABLE
IBC CHAPTER 5 IBC CHAPTER 5 IBC CHAPTER 5 IBC CHAPTER 5 ---- GENERAL BUILDING HEIGHTS & AREAS:GENERAL BUILDING HEIGHTS & AREAS:GENERAL BUILDING HEIGHTS & AREAS:GENERAL BUILDING HEIGHTS & AREAS:
• 9,937 SF (BASE BID AND BID OPTION) GROSS BUILDING AREA
• CONSTRUCTION TYPE = IIIIIIII----B, SPRINKLEDB, SPRINKLEDB, SPRINKLEDB, SPRINKLED
• ALLOWABLE BUILDING HEIGHT (PER TABLE 504.3) (PER TABLE 504.3) (PER TABLE 504.3) (PER TABLE 504.3) TYPE B TYPE B TYPE B TYPE B ---- 75 FEET ABOVE GRADE PLANE75 FEET ABOVE GRADE PLANE75 FEET ABOVE GRADE PLANE75 FEET ABOVE GRADE PLANE
• ALLOWABLE NUMBER OF STORIES ABOVE GRADE PLANE (PER TABLE 504.4) (PER TABLE 504.4) (PER TABLE 504.4) (PER TABLE 504.4) TYPE B TYPE B TYPE B TYPE B ---- 4 STORIES ABOVE GRADE PLANE 4 STORIES ABOVE GRADE PLANE 4 STORIES ABOVE GRADE PLANE 4 STORIES ABOVE GRADE PLANE
• TABULAR BUILDING AREA (PER TABLE 506.2) (PER TABLE 506.2) (PER TABLE 506.2) (PER TABLE 506.2) OCCUPANICESOCCUPANICESOCCUPANICESOCCUPANICES ALLOWABLE AREA ALLOWABLE AREA ALLOWABLE AREA ALLOWABLE AREA
B 92,000 SF
• ALLOWABLE BUILDING AREA (PER SECTION 506.2)(PER SECTION 506.2)(PER SECTION 506.2)(PER SECTION 506.2)
92,000 + (23,000*.75)= 109,250 SF (B)
• FIRE SEPARATION REQUIREMENTS PER TABLE 508.4PER TABLE 508.4PER TABLE 508.4PER TABLE 508.4 OCCUPANCIESOCCUPANCIESOCCUPANCIESOCCUPANCIES RATING (HR)RATING (HR)RATING (HR)RATING (HR) B 0
• INCIDENTAL USE AREAS (PER TABLE 509)(PER TABLE 509)(PER TABLE 509)(PER TABLE 509)
NOT APPLICABLENOT APPLICABLENOT APPLICABLENOT APPLICABLE
IBC CHAPTER 6 TYPES OF CONSTRUCTION:IBC CHAPTER 6 TYPES OF CONSTRUCTION:IBC CHAPTER 6 TYPES OF CONSTRUCTION:IBC CHAPTER 6 TYPES OF CONSTRUCTION:
• CONSTRUCTION TYPE: IIIIIIII----BBBB
• FIRE RATINGS (PER TABLE 601)(PER TABLE 601)(PER TABLE 601)(PER TABLE 601) AS FOLLOWS (EXCEPT WHERE NOTED OTHERWISE)
PRIMARY STRUCTURAL FRAME.............................. 0 HOUR0 HOUR0 HOUR0 HOUR
BEARING WALLS (INTERIOR & EXTERIOR)...................0 HOUR0 HOUR0 HOUR0 HOUR
NON-BEARING WALLS AND PARITIONS (INTERIOR)........0 HOUR0 HOUR0 HOUR0 HOUR
FLOOR CONSTRUCTION AND SECONDARY MEMBERS...0 HOUR0 HOUR0 HOUR0 HOUR
ROOF CONSTRUCTION AND SECONDARY MEMBERS....0 HOUR0 HOUR0 HOUR0 HOUR
UFC 3UFC 3UFC 3UFC 3----600600600600----01(REPLACES IBC CHAPTER 9) 01(REPLACES IBC CHAPTER 9) 01(REPLACES IBC CHAPTER 9) 01(REPLACES IBC CHAPTER 9) ---- FIRE PROTECTION SYSTEMS:FIRE PROTECTION SYSTEMS:FIRE PROTECTION SYSTEMS:FIRE PROTECTION SYSTEMS:
• SECTION 9SECTION 9SECTION 9SECTION 9----1 1 1 1 ---- EMERGENCY VEHICLE ACCESSEMERGENCY VEHICLE ACCESSEMERGENCY VEHICLE ACCESSEMERGENCY VEHICLE ACCESS
1. FACILITY REQUIRESREQUIRESREQUIRESREQUIRES ONE MEANS OF ALL-WEATHER EMERGENCY
VEHICLE GROUND ACCESS IN ACCORDANCE WITH 9999----1.11.11.11.1
2. FACILITY IS NOTIS NOTIS NOTIS NOT REQUIRED AERIAL APPARATUS ACCESS IN
ACCORDANCE WITH 9999----1.21.21.21.2
• SECTION 9SECTION 9SECTION 9SECTION 9----2 2 2 2 ---- FIRE FLOW FOR FACILITIESFIRE FLOW FOR FACILITIESFIRE FLOW FOR FACILITIESFIRE FLOW FOR FACILITIES
1. FIRE FLOW FOR SPRINKLER SYSTEM IS PROVIDED IN ACCORDANCE
WITH 9999----2.12.12.12.1
• SECTION 9SECTION 9SECTION 9SECTION 9----3 3 3 3 ---- SERVICE MAINS AND LATERALSSERVICE MAINS AND LATERALSSERVICE MAINS AND LATERALSSERVICE MAINS AND LATERALS
1. FIRE HYDRANTS ARE PROVIDED IN ACCORDANCE WITH 9999----3.5.83.5.83.5.83.5.8
A. HYDRANTS ARE SPACED AT 300 FT300 FT300 FT300 FT MAXIMUM
• SECTION 9SECTION 9SECTION 9SECTION 9----5 5 5 5 ---- FIRE PUMPSFIRE PUMPSFIRE PUMPSFIRE PUMPS
1. A FIRE PUMP IS NOTIS NOTIS NOTIS NOT REQUIRED TO MEET FIRE PROTECTION DEMAND.
• SECTION 9SECTION 9SECTION 9SECTION 9----7 7 7 7 ---- AUTOMATIC SPRINKLER SYSTEMSAUTOMATIC SPRINKLER SYSTEMSAUTOMATIC SPRINKLER SYSTEMSAUTOMATIC SPRINKLER SYSTEMS
1. PER 9999----7.2.17.2.17.2.17.2.1, AN AUTOMATIC SPRINKLER SYSTEM ISISISIS PROVIDED
• SECTION 9SECTION 9SECTION 9SECTION 9----10 10 10 10 ---- STANDPIPE SYSTEMSSTANDPIPE SYSTEMSSTANDPIPE SYSTEMSSTANDPIPE SYSTEMS
1. PER 9999----10101010, A STANDPIPE SYSTEM IS NOTIS NOTIS NOTIS NOT REQUIRED
• SECTION 9SECTION 9SECTION 9SECTION 9----17 17 17 17 ---- PORTABLE FIRE EXTINGUISHERSPORTABLE FIRE EXTINGUISHERSPORTABLE FIRE EXTINGUISHERSPORTABLE FIRE EXTINGUISHERS
1. PER 9999----17.117.117.117.1, PORTABLE FIRE EXTINGUISHERS ARE NOTARE NOTARE NOTARE NOT REQUIRED
2. 2. 2. 2. FIRE EXTINGUISHERS ARE PROVIDED, SEE PLANS FOR LOCATIONS
IBC CHAPTER 7 IBC CHAPTER 7 IBC CHAPTER 7 IBC CHAPTER 7 ---- FIRE AND SMOKE PROTECTION FEATURES:FIRE AND SMOKE PROTECTION FEATURES:FIRE AND SMOKE PROTECTION FEATURES:FIRE AND SMOKE PROTECTION FEATURES:
• MAXIMUM EXTERIOR WALL OPENINGS (PER TABLE 705.8)(PER TABLE 705.8)(PER TABLE 705.8)(PER TABLE 705.8)
FIRE SEPARATION: DEGREE OF OPENING PROTECTION: ALLOWABLE AREA:
GREATER THAN 30 FTGREATER THAN 30 FTGREATER THAN 30 FTGREATER THAN 30 FT UNPROTECTED, SPRINKLERED , (UP, S)UNPROTECTED, SPRINKLERED , (UP, S)UNPROTECTED, SPRINKLERED , (UP, S)UNPROTECTED, SPRINKLERED , (UP, S) NO LIMITNO LIMITNO LIMITNO LIMIT
IBC CHAPTER 8, UFC 3IBC CHAPTER 8, UFC 3IBC CHAPTER 8, UFC 3IBC CHAPTER 8, UFC 3----600600600600----01, NFPA 101 01, NFPA 101 01, NFPA 101 01, NFPA 101 ---- INTERIOR FINISHES:INTERIOR FINISHES:INTERIOR FINISHES:INTERIOR FINISHES:
• FINISH MATERIAL RATING REQUIREMENTS (PER NFPA 101)(PER NFPA 101)(PER NFPA 101)(PER NFPA 101)
BUSINESS BUSINESS BUSINESS BUSINESS (CHAPTER 38)(CHAPTER 38)(CHAPTER 38)(CHAPTER 38)
EXITS AND EXIT ACCESS CORRIDORS
INTERIOR WALL AND CEILING FINISH - CLASS A OR B (38.3.3.2.1)CLASS A OR B (38.3.3.2.1)CLASS A OR B (38.3.3.2.1)CLASS A OR B (38.3.3.2.1) INTERIOR FLOOR FINISH - CLASS I OR CLASS II (38.3.3.2)CLASS I OR CLASS II (38.3.3.2)CLASS I OR CLASS II (38.3.3.2)CLASS I OR CLASS II (38.3.3.2)
AREAS OTHER THAN EXITS AND EXIT ACCESS CORRIDORS
INTERIOR WALL AND CEILING FINISH - CLASS A, B, OR C (38.3.3.2.2)CLASS A, B, OR C (38.3.3.2.2)CLASS A, B, OR C (38.3.3.2.2)CLASS A, B, OR C (38.3.3.2.2) INTERIOR FLOOR FINISH - COMPLY WITH SECTION 10.2.7COMPLY WITH SECTION 10.2.7COMPLY WITH SECTION 10.2.7COMPLY WITH SECTION 10.2.7
NFPA 101 CHAPTER 7 (REPLACES IBC CHAPTER 10) NFPA 101 CHAPTER 7 (REPLACES IBC CHAPTER 10) NFPA 101 CHAPTER 7 (REPLACES IBC CHAPTER 10) NFPA 101 CHAPTER 7 (REPLACES IBC CHAPTER 10) ---- MEANS OF EGRESS:MEANS OF EGRESS:MEANS OF EGRESS:MEANS OF EGRESS:
• OCCUPANCY LOAD (PER TABLE 7.3.1.2, AS MODIFIED BY UFC 3(PER TABLE 7.3.1.2, AS MODIFIED BY UFC 3(PER TABLE 7.3.1.2, AS MODIFIED BY UFC 3(PER TABLE 7.3.1.2, AS MODIFIED BY UFC 3----600600600600----01)01)01)01):
SEE OCCUPANCY LEGEND
• EGRESS CAPACITY SIZING (PER TABLE 7.3.3.1)(PER TABLE 7.3.3.1)(PER TABLE 7.3.3.1)(PER TABLE 7.3.3.1)
0.2 INCHES PER OCCUPANT (PER TABLE 7.3.3.1)(PER TABLE 7.3.3.1)(PER TABLE 7.3.3.1)(PER TABLE 7.3.3.1) 36 INCHES MIN EGRESS WIDTH (PER SECTION 7.3.4.1)(PER SECTION 7.3.4.1)(PER SECTION 7.3.4.1)(PER SECTION 7.3.4.1)
SEE LIFE SAFETY PLAN FOR INDIVIDUAL ROOM EGRESS ANALYSIS
• NUMBER OF MEANS OF EGRESS (PER SECTION 7.4.1)(PER SECTION 7.4.1)(PER SECTION 7.4.1)(PER SECTION 7.4.1)
TOTAL NUMBER OF EXITS REQUIRED
BUSINESS OCCUPANCY (CHAPTER 38)(CHAPTER 38)(CHAPTER 38)(CHAPTER 38)
GROUND FLOOR GROUND FLOOR GROUND FLOOR GROUND FLOOR ---- 2 EXITS REQUIRED2 EXITS REQUIRED2 EXITS REQUIRED2 EXITS REQUIRED
• COMMON PATH OF EGRESS TRAVEL DISTANCE
BUSINESS OCCUPANCY BUSINESS OCCUPANCY BUSINESS OCCUPANCY BUSINESS OCCUPANCY (CHAPTER 38)(CHAPTER 38)(CHAPTER 38)(CHAPTER 38)
100 FT100 FT100 FT100 FT PER 38.2.5.3.138.2.5.3.138.2.5.3.138.2.5.3.1
• EXIT ACCESS TRAVEL DISTANCE EXIT ACCESS TRAVEL DISTANCE EXIT ACCESS TRAVEL DISTANCE EXIT ACCESS TRAVEL DISTANCE BUSINESS OCCUPANCY BUSINESS OCCUPANCY BUSINESS OCCUPANCY BUSINESS OCCUPANCY (CHAPTER 38)(CHAPTER 38)(CHAPTER 38)(CHAPTER 38)
300 FT300 FT300 FT300 FT PER 38.2.6.338.2.6.338.2.6.338.2.6.3
SEE LIFE SAFTEY PLAN FOR EXIT ACCESS TRAVEL DISTANCE
• CORRIDORS
OCCUPANCY TYPE (B) (B) (B) (B) REQUIRES:
NO FIRE RATING REQUIRED FOR CORRIDOR WALLSNO FIRE RATING REQUIRED FOR CORRIDOR WALLSNO FIRE RATING REQUIRED FOR CORRIDOR WALLSNO FIRE RATING REQUIRED FOR CORRIDOR WALLS
SEE LIFE SAFTEY PLAN FOR LOCATIONS OF RATED CORRIDORS
MINIMUM CORRIDOR WIDTH
BUSINESS OCCUPANCY (CHAPTER 38)(CHAPTER 38)(CHAPTER 38)(CHAPTER 38)
44 INCHES44 INCHES44 INCHES44 INCHES PER 38.2.3.238.2.3.238.2.3.238.2.3.2
DEAD END CORRIDORS
BUSINESS OCCUPANCY (CHAPTER 38)(CHAPTER 38)(CHAPTER 38)(CHAPTER 38)
MAXIMUM OF 50505050 FEET PER 38.2.5.2.138.2.5.2.138.2.5.2.138.2.5.2.1
LIFE SAFETY REQUIREMENTS OUTLINE
PLUMBING FIXTURE SCHEDULE - OFFICE AREA
Occupancy Type
Male Occupancy
Female Occupancy
Plumbing Fixtures Calculations
Water Closets Lavatories Drinking FountainsMen Women Men's Women's
Business 72 18 3.60 0.90 3.60 0.90 1.20
Grand total: 11
PLUMBING FIXTURE CALCULATIONS ARE BASED UPON UTA OCCUPANCY OF 89.
LIFE SAFETY CALCULATIONS:
1/8" = 1'-0"LS1.0
1 LIFE SAFETY PLAN (Base Bid)
Rev. Description Date
1 ADD 01 7/16/24
N
L1.0
"B" Street
Bach us
Driv e
L1.1
Sim
BID OPTION
NEW STRIPING-
SEE CIVIL
EXISTING FENCE
TO REMAIN
NEW FENCE
BU
ILD
IN
G
BU
ILD
IN
G
L1.0
L1.1
Sim ___________ L1.1
Sim
(4 .9
M
/8
EXISTING GRASS
NEW CONCRETE CURB &
GUTTER - SEE CIVIL
NEW CONCRETE
WALKWAYS - SEE CIVIL
EXISITNG ASPHALT PAVING -
SEE CIVIL
NEW EMERALD ZOYSIA SEED
NEW ASPHALT PAVING -
SEE CIVIL
Pourous Fill
Foundation Drain - See Civil
Guardrail
S e e C iv il
V a ri e s
Reinforcing Steel (See Structural)
M
IN
L1.1
Sim
N Bach us Driv e
MATERIAL STORAGE
AREA
DELIVERY ACCESS
POINT
DELIVERY ACCESS
POINT
B2
TEMPORARY
CONSTRUCTION
FENCING
CONTRACTOR
PERSONNEL
VEHICLES ONLY
INDICATES EXISTING ASPHALT
PAVING INTENDED TO REMAIN.
CONTRACTOR TO REPAIR
ASPHALT TO PRE-WORK
CONDITIONS PRIOR TO
BENEFICIAL OCCUPANCY IF
DAMAGED.
CONTRACTOR
PERSONNEL
PARKING ONLY
GOVERNMENT
PARKING
MATERIAL STORAGE AREA
EXISTING FENCING
TO REMAIN
SIDEWALK- SEE
CIVIL
SIDEWALK- SEE
CIVIL
2 TREAD @ 12" EACH
NOSING
(0.31M)
1' - 0"
(0.30M)
1' - 0"
(0 .5
M
(0 .5
M
1-1/2" O.D. STEEL HANDRAIL, FULLY WELDED TO
VERTICAL SUPPORTS, RETURN TO POST
1-1/2" O.D. STEEL HANDRAIL, FULLY WELDED TO
TOP OF ALL VERTICAL SUPPORTS
(0 .3
M
(0 .9
M
HANDRAIL RETURNS TO POST
FULLY WELD ALL CONNECTIONS
1-1/2" SQUARE STEEL VERTICAL
SUPPORTS SPACED-MAX 4' 0" O.C.
1 1/2" SQUARE STEEL VERTICAL
SUPPORTS SPACED-MAX 4' 0" O.C.
1-1/2" O.D. STEEL HANDRAIL, FULLY WELDED TO
TOP OF ALL VERTICAL SUPPORTS
R
IS
E R
S
E A
C H
Sheet Number
Sheet Title
Project Title
Job Number
Date
Drawn By
Checked By
S o u th C o u rt S tr ee t M o n tg o m er y, A
L
T el . 3
. 2
3.
W W W .S S L A R C H .C O M
A R C H
IT
E C T U R E
I N T E R
IO
R D
E S
IG
N
L1.0
Landscape Site Plan
N ew
S ec u ri ty B u ild in g
7t h A ir R ef u el in g W in g
B ir m in gh am , A
L
12072
JUNE 2024
JJ, NB, DCD, JBW, DOB
DCD
1" = 30'-0"L1.0 1 Landscape Site Plan (Base Bid)
1/8" = 1'-0" Site Plan Legend
Landscaping Notes:
1. Plants shall be adjusted on the site to avoid conflicts with underground utilities, surface drainage ways, and exterior lighting standards. Adjustment shall be approved prior to planting.
2. Plant mix for all plantings shall be as detailed in specifications.
3. Plant materials shall be nursery-grown, root-pruned, stock conformed to ANSI Z.60.1 standards of nursery stock.
4. Inspections at place of growth shall not impair the right of rejection at site.
5. Remove all soil and vegetation to a depth of 9" in areas to receive shrubs or ground covers and replace with soil mix.
6. Do not injure root systems of existing trees.
7. Verify exact number and locations of all plantings with architect.
8. If any existing plantings or trees are disturbed, distressed, or die - contractor to replace by matching existing plants.
9. Landscaper note existing soild conditions in geotechnical report in specifications and make site visit to become familiar with existing soil conditions.
10. Landscaper to verify existing grades. Consult with architect before installation of any trees, shrubs, or ground covers.
11. Contractor to sod all areas disturbed by construction activities in addition to that shown in drawings.
12. Provide river rock mulch at all planting areas unless specifically noted otherwise.
Tree Protection Notes:
1. Protect trees and shrubs designated to remain with 6' ht. chain link fence.
2. Erect fencing before starting any other construction activities on site.
3. Protected areas may not be used for storage of materials or equipment, parking or wash-off areas.
4. Do not trench or fill within fenced ares without architect's on-site review and approval.
5. Fences shall remain in place until completion of the project, unless approved by the architect
6. Mow areas within tree protection fencing every other week during the growing season (March - November).
3/4" = 1'-0"L1.0 4 Retaining Wall Detail
Rev. Description Date
1 ADD 01 8/6/24
1" = 80'-0"L1.0 3 Site Access Plan
3/4" = 1'-0"L1.0 2 Typical Handrail Detail
1. REFER TO SPECIFICATION SECTION 01 2300 FOR DESCRIPTION OF BID OPTION.
GENERAL NOTES:
STAINLESS STEEL PINS
GROUT-FILLED 8" CMU
12" GROUT-FILLED
CMU
PEJ
CONCRETE PAVING - SEE CIVIL
BRICK
EPOXY PAINT
EQUAL TO ROCKCAST CO100
STAINLESS STEEL THROUGH WALL FLASHING WITH
3/4" HEMMED DRIP EDGE (BOTH SIDES) , SET IN FULL
BED OF SEALANT
CHAIN LINK FENCE POST(S) AS REQUIRED TO SUPPORT
HORIZONTAL CHAIN LINK ENCLOSURE OF
MECHANICAL YARD
WEEP
S E
E C
IV
IL
V
A R
IE
S
FOOTING (SEE STRUCTURAL)
POROUS FILL
FOUNDATION DRAIN
(SEE CIVIL)
MATCH BUILDING
ELEVATION
+/- 50'-0"
CHILLER (SEE MECHANICAL)
TRANSFORMER
(SEE ELECTRICAL)
MANUEL
TRANSFORMER
SWITCH (SEE
ELECTRICAL)
8' - 0"
CONDENSOR (SEE
MECHANICAL)
PROVIDE HORIZONTAL CHAIN LINK
FABRIC AND FENCE POSTS AS REQUIRED
TO COVER MECHANICAL COURTYARD.
COORDINATE HEIGHT AND POST SPACING
WITH CHILLER MANUFACTURER. (BID OPTION)
L1.1
Sim
L1.1
Sim
BASE BIDBID OPTION
GATE (BID OPTION)
SEE DETAIL 3/L1.1
1" DIA. TUBE WEEPS THROUGH
WALL AT ELEVATION 650.75
10' 0" MINIMUM
V e ri fy a nd
C o o rd in at e w it h C hi lle r M an uf ac tu re r
"A G
0' - 1" 0' - 1"
EQ EQ
WRAP BRICK AROUND JAMBS (TYPICAL)
GATES - PROVIDE DIAGONAL BRACING AS REQUIRED
HEAVY DUTY HINGES BY GATE MANUFACTURER
SLIDE BOLT BY GATE MANUFACTURER
CANE BOLT BY GATE MANUFACTURER
RECESSED STRIKE EMBEDDED IN CONCRETE (TYPICAL)
0' - 5" 0' - 5"
SEE PLAN
L1.1
Sim
16" DIA.
5 X 5 X 3/8" STEEL TUBE COLUMNS
5 X 5 X 3/8" STEEL TUBE COLUMNS
FIXED LOUVERED GATES - SEE
SECTION 05 5000
5"x5"x3/8" STEEL TUBE, FILL
WITH CONCRETE
1/2" PEJ, ALL SIDES
PAVING - SEE CIVIL
SLOPE TOP OF CONCRETE AWAY
FROM STEEL TUBE
STONE CAP INSTALL SEALANT AT ALL WALL
CAP JOINTS
WRAP BRICK AROUND JAMBS
0' - 4" 0' - 4"
SEE STRUCTURAL WHERE FOOTINGS OCCUR AT
FULL HEIGHT COLUMNS
4" FENCE SLAT
4"X4"X1/4" GATE FRAMING
(2 .1
M
M in im u m
GROUT-FILLED CMU
12" GROUT-FILLED
CMU
PEJ
CONCRETE PAVING - SEE CIVIL
EPOXY PAINT
WEEP
FOOTING (SEE STRUCTURAL)
POROUS FILL
FOUNDATION DRAIN
(SEE CIVIL)
BRICK
EQUAL TO ROCKCAST CO100
PAINTED STEEL GUARDRAIL
STAINLESS STEEL THROUGH WALL FLASHING WITH 3/4"
HEMMED DRIP EDGE (BOTH SIDES) , SET IN FULL BED OF
SEALANT
STAINLESS STEEL PINS
T/W = 654.50
L1.1
Sim
(1 .8
M
(3.66M)
12' - 0"
(0.91M)
3' - 0"
(0.91M)
3' - 0"
4" Concrete Pad
Bicycle Rack - See Specifications
(0.61M)
2' - 0"
(0 .6
M
(0.30M)
1' - 0"
(0.30M)
1' - 0"
Bicycle Rack - See Specifications
Plastisol Finish to Extend min. 1" below grade
4" Concrete Pad
3/4" PEJ - Typical Concrete Footing
(0 .1
M
M
IN
(0 .1
M
E Q
E Q
DESIGN LOADS IN SPEC SECTION 05 5213
VERTICALS SPACED AS REQ. TO ACHIEVE
1-1/2" STEEL TUBES - PAINTED
PROVIDE ANCHORING AS
REQUIRED TO ACHIEVE DESIGN
LOADS IN SPEC SECTION 05 5213
Sheet Number
Sheet Title
Project Title
Job Number
Date
Drawn By
Checked By
S o u th C o u rt S tr ee t M o n tg o m er y, A
L
T el . 3
. 2
3.
W W W .S S L A R C H .C O M
A R C H
IT
E C T U R E
I N T E R
IO
R D
E S
IG
N
L1.1
Landscape Details
N ew
S ec u ri ty B u ild in g
7t h A ir R ef u el in g W in g
B ir m in gh am , A
L
12072
JUNE 2024
JJ, NB, DCD, JBW, DOB
DCD
1" = 1'-0"L1.1 1 Mechanical Screen Wall (Bid Option)
1" = 10'-0"L1.1
2 MECH/ELECTRICAL COURT LAYOUT
1/2" = 1'-0"L1.1
3 FENCE GATE (BID OPTION)
1" = 1'-0"L1.1
4 GATE SECTION (BID OPTION)
1" = 1'-0"L1.1 5 Mechanical Screen Wall (Base Bid)
Rev. Description Date
1 ADD 01 8/6/24
1. REFER TO SPECIFICATION SECTION 01 2300 FOR
DESCRIPTION OF BID OPTIONS.
GENERAL NOTES:1/2" = 1'-0"L1.1
6 Bicylce Plan Details
1" = 1'-0"L1.1 7 Bicycle Rack Section
1" = 1'-0"L1.1 8 Typical Guardrail Section & Elevation
PL1: Manufacturer: Formica
Color: Noir Cedar 1547-PG
CPT1: Manufacturer: Shaw Contract
Style: Memory Tile
Color: Nestle
Size: 24" x 24"
Install Method: Monolithic RB1: Manufacturer: Roppe
Color: P178 Pewter
VCT1: Manufacturer: Armstrong
Style: Premium Excelon Raffia Stream
Color: Rain 55901
Size: 12" x 24"
Install Pattern: Ashlar
HT1: Manufacturer: Daltile
Style: Exquisite
Color: Ivory EQ10
Size: 12 x 24
Install Pattern: 1/3 Ashlar
HT2: Manufacturer: Daltile
Style: Chord
Color: Canon Gray
Size: 12 x 24
Install Pattern: 1/3 Ashlar
GROUT: Manufacturer: Laticrete
Color: Dusty Grey 60
HT3: Manufacturer: Daltile
Style: Exquisite
Color: Ivory EQ10
Size: 2 x 4
Install Pattern: Brick Pattern Mosaic
CARPET
RUBBER BASE
VINYL COMPOSITION TILE FLOORING
TILE
FINISH SCHEDULE LEGEND
ACT1: Manufacturer: Armstrong
Style: Cirrus
Size: 24" x 24" x 7/8"
Suspension System: Type I1
Edge: Square
See specification section 09 5100
ACT2: Manufacturer: Armstrong
Style: Clean Room VL
Size: 24" x 24" x 7/8"
Suspension System: Type I1
Edge: Square
See specification section 09 5100
ACOUSTIC CEILING
PLASTIC LAMINATE
PNT1: Manufacturer: Sherwin Williams
Color: Agreeable Gray SW7029
PNT2: Manufacturer: Sherwin Williams
Color: Urbane Bronze SW7048
PNT3: Manufacturer: Sherwin Williams
Color: Dovetail SW7018
PNT4: Manufacturer: Sherwin Williams
Color: Requisite Gray SW7023
PNT5: Manufacturer: Sherwin Williams
Color: Agreeable Gray SW7029
PAINT
ST1: Manufacturer: Oshkosh
Type: SWB
Color: Chestnut 1550
DOOR STAIN/ WOOD STAIN TO MATCH
SS1: Manufacturer: Corian
Color: Carbon Concrete
SOLID SURFACE
WS1: Manufacturer: Mecho
Type: ThernoVeil
Color: 1516 Eggshell
Openess: 3%
WINDOW SHADES
SC: Sealed Concrete
See Spec Section: 09 9123
CONCRETE
FRP: Refer to Specification Section 06 8316
FIBERGLASS REINFORCED PANELING
SS2: HANDRYERS
Manufacturer: Corian Solid Surface
Color: Cameo White
Edge Finish: Square
WM1: Manufacturer: Pawling Corp.
Style: EM-650
Rigid Back Nylon Capet Inserts: 519 Near Black
WALK OFF MAT - SEE SPECIFICATION 12 4813
Sheet Number
Sheet Title
Project Title
Job Number
Date
Drawn By
Checked By
S o u th C o u rt S tr ee t M o n tg o m er y, A
L
T el . 3
. 2
3.
W W W .S S L A R C H .C O M
A R C H
IT
E C T U R E
I N T E R
IO
R D
E S
IG
N
A3.1
Finish Schedule
N ew
S ec u ri ty B u ild in g
7t h A ir R ef u el in g W in g
B ir m in gh am , A
L
12072
JUNE 2024
JJ, NB, DCD, JBW, DOB
DCD
FINISH SCHEDULE - BASE BID & BID OPTION #4
NO. ROOM NAME
FLOOR FINISH BASE FINISH WALL FINISH
CEILING FINISH
DOORS WINDOW MILLWORK
TOILET
PARTITIONS NOTES
BASE BID FLOOR
FINISH
BID OPTION
FLOOR FINISH BASE BID
BID
OPTION
BASE BID BID OPTION
FINISH
CASING &
TRIM SHADE SILL
CASEWORK COUNTER
TOPNORTH EAST SOUTH WEST NORTH EAST SOUTH WEST UPPER LOWER
Level 1
121 Vestibule VCT 1, WM 1 VCT 1, WM 1 RUBBER RUBBER PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 ACT 1 ST 1 PNT 2
122 Intel / Investigations Officer VCT 1 CPT 1 RUBBER RUBBER PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 ACT 1 ST 1 PNT 2 WS 1
123 Electrical / Mechanical SC SC RUBBER RUBBER PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 Exposed / PNT 4 ST 1 PNT 2
124 Janitor SC SC RUBBER RUBBER FRP / PNT 1 FRP / PNT 1 FRP / PNT 1 FRP / PNT 1 FRP / PNT 1 FRP / PNT 1 FRP / PNT 1 FRP / PNT 1 ACT 2 ST 1 PNT 2 PROVIDE FRP PANELS TO 8'-0" AFF AND PNT-1 ABOVE ON WALLS
125 Resource Protection VCT 1 CPT 1 RUBBER RUBBER PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 ACT 1 ST 1 PNT 2 WS 1
126 Women's Latrine HT-2 HT-2 HT-2 HT-2 HT-1, HT-2, PNT 3 HT-1, HT-2, PNT 3 HT-1, HT-2, PNT 3 HT-1, HT-2, PNT 3 HT 1 HT 1 HT 1 HT 1 ACT 2 ST 1 PNT 2 PL1 SS1 STAINLESS REFER TO ELEVATIONS FOR EXTENT OF TILE INCLUDED IN BASE BID
127 Operations Officer VCT 1 CPT 1 RUBBER RUBBER PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 ACT 1 ST 1 PNT 2 WS 1
128 Hall VCT 1 VCT 1 RUBBER RUBBER PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 ACT 1 ST 1 PNT 2
129 Conference Room VCT 1 CPT 1 RUBBER RUBBER PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 ACT 1 ST 1 PNT 2 WS 1
130 BDOC VCT 1 CPT 1 RUBBER RUBBER PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 ACT 1 ST 1 PNT 2
130a SIPR / NCIC VCT 1 VCT 1 RUBBER RUBBER PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 ACT 1 ST 1 PNT 2
130b BDOC Conference VCT 1 CPT 1 RUBBER RUBBER PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 ACT 1 ST 1 PNT 2
131 First Seargent VCT 1 CPT 1 RUBBER RUBBER PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 ACT 1 ST 1 PNT 2 WS 1
132 Latrine HT-2 HT-2 HT-2 HT-2 HT-1, HT-2, PNT 3 HT-1, HT-2, PNT 3 HT-1, HT-2, PNT 3 HT-1, HT-2, PNT 3 HT 1 HT 1 HT 1 HT 1 ACT 2 ST 1 PNT 2 REFER TO ELEVATIONS FOR EXTENT OF TILE INCLUDED IN BASE BID
133a Waiting & Orderly VCT 1 CPT 1 RUBBER RUBBER PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 ACT 1 ST 1 PNT 2 WS 1
133b Manager Office VCT 1 CPT 1 RUBBER RUBBER PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 ACT 1 ST 1 PNT 2 WS 1
133c Commander VCT 1 CPT 1 RUBBER RUBBER PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 ACT 1 ST 1 PNT 2 WS 1
134 Alarm VCT 1 VCT 1 RUBBER RUBBER PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 ACT 1 ST 1 PNT 2
135 Supt. Office VCT 1 CPT 1 RUBBER RUBBER PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 ACT 1 ST 1 PNT 2 WS 1
136 Hall VCT 1 VCT 1 RUBBER RUBBER PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 ACT 1 ST 1 PNT 2
137 Break Room VCT 1 VCT 1 RUBBER RUBBER PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 ACT 1 ST 1 PNT 2 WS 1 PL1 PL1 SS1
138 COMM VCT 1 VCT 1 RUBBER RUBBER PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 ACT 1 ST 1 PNT 2
139 Quality Control VCT 1 CPT 1 RUBBER RUBBER PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 ACT 1 ST 1 PNT 2 WS 1
140 Men's Latrine HT-2 HT-2 HT-2 HT-2 HT-1, HT-2, PNT 3 HT-1, HT-2, PNT 3 HT-1, HT-2, PNT 3 HT-1, HT-2, PNT 3 HT-1 HT-1 HT-1 HT-1 ACT 2 ST 1 PNT 2 PL1 SS1 STAINLESS REFER TO ELEVATIONS FOR EXTENT OF TILE INCLUDED IN BASE BID
141 NCOIC VCT 1 CPT 1 RUBBER RUBBER PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 ACT 1 ST 1 PNT 2 WS 1
142 Hall VCT 1 VCT 1 RUBBER RUBBER PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 ACT 1 ST 1 PNT 2
143 Vestibule VCT 1, WM 1 VCT 1, WM 1 RUBBER RUBBER PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 ACT 1 ST 1 PNT 2
144 Guardmount SC SC RUBBER RUBBER PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 ACT 1 ST 1 PNT 2 PL1 PL1 SS1
145 Squad Leader Work Area VCT 1 CPT 1 RUBBER RUBBER PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 ACT 1 ST 1 PNT 2 WS 1
146 Hall VCT 1 VCT 1 RUBBER RUBBER PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 ACT 1 ST 1 PNT 2
147 Classroom / CATS Training VCT 1 CPT 1 RUBBER RUBBER PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 ACT 1 ST 1 PNT 2 WS 1
148a Weapons Issue & Storage SC SC RUBBER RUBBER PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 ACT 1 PNT 2 PNT 2
148b Latrine SC HT-2 RUBBER HT-2 PNT 3 PNT 3 PNT 3 PNT 3 HT-1 HT-1 HT-1 HT-1 ACT 2 PNT 2 PNT 2 REFER TO ELEVATIONS FOR EXTENT OF TILE INCLUDED IN BASE BID
150 Supply SC SC RUBBER RUBBER PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 Exposed / PNT 4 PNT 2 PNT 2 PAINT ALL EXPOSED STRUCTURAL AND MEP ITEMS IN CEILING OF THIS SPACE.
151 Water SC SC RUBBER RUBBER PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 PNT 1 Exposed PNT 2 PNT 2
Rev. Description Date
1 ADD 01 7/16/24
1. REFER TO SPECIFICATION SECTION 01 2300 FOR DESCRIPTION OF BID OPTIONS.
GENERAL NOTES:
A5.2
A5.2
Standard Brick
Airspace
Rigid Insulation
Bond Beam - See Structural
Concrete Footing - See Structural
CMU
See Curtain Wall Schedule
CMU
(0.05M) 0' - 2"
Paint Structure and Ductwork Where Exposed in Room 150
Cast Stone (Where Occurs) See Elevations for Locations
Acoustical Ceiling Tile (Where Occurs) Refer to Finish Schedule
Brick Rowlock
(1.05M)
3' - 5 1/4"
Weep
Air Barrier
S E
E S
T R
U C
T U
R A
L
(3 .6
M
(0 .6
M
A3.4
A3.4
Level 1 0' - 0"
A5.2
Standard Brick
Airspace
Rigid Insulation
CMU
Concrete Footing - See Structural
(0 .6
M
Acoustical Ceiling Tile (See Reflected Ceiling Plan)
CMU
(0.05M) 0' - 2"
A5.2
(1.05M)
3' - 5 1/4"
Air Barrier
Bond Beam- See Structural A5.3
Standard Brick
Airspace
Rigid Insulation
CMU
Air Barrier
Bond Beam - See Structural
Metal Stud Framing As Required
Weep
Backer Rod w/ Sealant
A2.3
Sim
Metal Soffit Panel
Metal Closure Trim
3' - 5 1/4"
Air Barrier Sheathing
A5.3
Level 1 0' - 0"
Concrete Footing - See Structural
Air Barrier
Termination Bar & Sealant - See Flashing Detail
Mortar Net
Through Wall Flashing
Metal Drip Edge
CMU
A5.4
S e e S tr u c tu ra l
Wall Base - See Finish Schedule
Brick
(0.19M)
0' - 7 3/8" SEE STRUCTURAL
Weep
Rigid Insulation
CMU
Air Barrier
Backer Rod w/ Sealant
A2.3
Sim
Air Barrier Sheathing
Metal Wall Panel
(1.05M)
3' - 5 1/4"
A5.3
Bond Beam- See Structural
Continuous Insulation Channel
Metal Soffit Panel
Metal Closure Trim
Level 1 0' - 0"
A5.3
Sim
A5.2
Metal Wall Panel
Rigid Insulation
CMU - See Structural
Standard Brick
Concrete Footing - See Structural
A5.2
Acoustical Ceiling Tile (See Reflected Ceiling Plan)
(3 .6
M
CMU - See Structural
S E
E S
T R
U C
T U
R A
L
(0 .6
M
Air Barrier
(1.05M)
3' - 5 1/4"
Bond Beam- See Structural
Sheet Number
Sheet Title
Project Title
Job Number
Date
Drawn By
Checked By
S o u th C o u rt S tr ee t M o n tg o m er y, A
L
T el . 3
. 2
3.
W W W .S S L A R C H .C O M
A R C H
IT
E C T U R E
I N T E R
IO
R D
E S
IG
N
A5.2
Wall Sections
N ew
S ec u ri ty B u ild in g
7t h A ir R ef u el in g W in g
B ir m in gh am , A
L
12072
JUNE 2024
JJ, NB, DCD, JBW, DOB
DCD
3/4" = 1'-0"A5.2 2 Typical Wall Section at Window
3/4" = 1'-0"A5.2
Typical Wall Section at High Roof (Bid Option)
1 1/2" = 1'-0"A5.2 4 Roof Eave Detail
1 1/2" = 1'-0"A5.2 5 Wall Base Detail
1 1/2" = 1'-0"A5.2 3 Roof Eave Detail at Metal Stud
3/4" = 1'-0"A5.2
Typical Wall Section at Metal Wall Panel
Rev. Description Date
1 ADD 01 7/16/24
VCT-1
HT-2
WM-1
SC
FLOOR PATTERN LEGEND
CPT-1
Carpet
Vinyl Transition Strip Equal to Johnsonite Systems 1/4" Max Vertical Change, 1/2" Max Vertical change if sloped at 1:2 (accessible compliant)
Vinyl Tile Flooring - Vinyl Flooring - Refer to Finish Floor Drawings and Specs to
/2
/4
1. REFER TO SPECIFICATION SECTION 01 2300 FOR DESCRIPTION OF BID OPTION.
GENERAL NOTES:
Vinyl Tile Flooring - Vinyl Flooring - Refer to Finish Floor Drawings and Specs
WALK OFF MAT
CONCRETE SLAB -
REFER TO
MANUFACTURER'S
REQUIREMENTS FOR
SLAB DEPRESSION
EQUAL TO SCHLUTER - VINPRO-S (SIZE AS
REQUIRED FOR EACH MATERIAL TRANSITION)
SEALANT
CONCRETE SLAB FLOOR
EQUAL TO SCHLUTER - VINPRO-U (SIZE
AS REQUIRED FOR EACH MATERIAL
TRANSITION)
Vinyl Tile Flooring - Vinyl Flooring - Refer to Finish Floor Drawings and Specs
NOTE: DIFFERENT HEIGHT TRANSITIONS FROM LVT TO CONCRETE
V E R
IF
Y
/4
M
A X
CARPET
CONCRETE SLAB
EQUAL TO SCHLUTER - RENO-TK (SIZE AS
REQUIRED FOR EACH MATERIAL
TRANSITION)
TILE
NOTE: DIFFERENT HEIGHT TRANSITION FROM TILE TO CARPET
V E R
IF
Y
/4
M
A X
Vinyl Tile Flooring - Vinyl Flooring - Refer to Finish Floor Drawings and Specs
CONCRETE SLAB
EQUAL TO SCHLUTER - RENO-TK (SIZE AS
REQUIRED FOR EACH MATERIAL
TRANSITION)
TILE
NOTE: DIFFERENT HEIGHT
TRANSITIONS FROM LVT TO TILE
V E R
IF
Y
V E R
IF
Y
/4
M
A X
FINISH CONCRETE FLOOR
EQUAL TO SCHLUTER - RENO U
(SIZE AS REQUIRED FOR EACH
MATERIAL TRANSITION)
TILE
CONCRETE SLAB
Sheet Number
Sheet Title
Project Title
Job Number
Date
Drawn By
Checked By
S o u th C o u rt S tr ee t M o n tg o m er y, A
L
T el . 3
. 2
3.
W W W .S S L A R C H .C O M
A R C H
IT
E C T U R E
I N T E R
IO
R D
E S
IG
N
A9.1
Floor Pattern Plan
N ew
S ec u ri ty B u ild in g
7t h A ir R ef u el in g W in g
B ir m in gh am , A
L
12072
JUNE 2024
JJ, NB, DCD, JBW, DOB
DCD
12" = 1'-0"A9.1
2 CARPET TO LVT/VCT TRANSITION
1/8" = 1'-0"A9.1 1 Floor Pattern Plan (Base Bid)
12" = 1'-0"A9.1
WALK OFF MAT TO LVT/VCT
TRANSITION
1/8" = 1'-0"A9.1 7 Floor Pattern Plan (Bid Option)
Rev. Description Date
1 ADD 01 7/16/24
1" = 1'-0"A9.1
8 CONCRETE TO LVT/VCT TRANSITION
1" = 1'-0"A9.1
9 TILE TO CARPET TRANSITION
1" = 1'-0"A9.1
10 TILE TO LVT/VCT TRANSITION
12" = 1'-0"A9.1
12 CONCRETE TO TILE TRANSITION
1 1
TYPICAL SLAB CONSTRUCTION
W.W.F.
JOINT DETAIL-(C.J.)
ALTERNATE SLAB CONSTRUCTION
JOINT DETAIL (SAWED JOINT)
W.W.F.
SAW CUT 1/8"x1" DEEP
SAWED JOINT. FILL
JOINT W/ SEALANT.
NOTE:
IF SAWED JOINTS ARE USED,
JOINTS MUST BE SAWED
SAME DAY AS SLAB POUR.
WOOD FORMED
KEYED JOINT
/2
6" 6"
6x6-W1.4x W1.4 W.W.F.
TYPICAL THICKENED SLAB DETAIL
(2)#4 CONT. W/
#3 @ 3'-0"O.C.
#4 @ EA. JAMB & @
48"O.C., CENTERED.
FILL CELLS W/
CONC. FULL HT. OF
WALL ONLY @ #4.
1' - 4"
SEE ARCH. DWGS.
NOTE:
PROVIDE A TYPICAL
THICKENED SLAB UNDER
ALL C.M.U. PARTITIONS
NOT BEARING ON A FTG.
OR GRADE BEAM.
M A
X
T Y
P
IC
A L S
C R
E W
S P
A C
IN
G
I N
T E
R
IO
R S
U P
P O
R T
S
6" MAX. TYPICAL SCREW SPACING
@ CONT. STEEL SUPPORT
M A
X
T Y
P
IC
A L S
C R
E W
S P
A C
IN
G
E
N D
S U
P P
O R
T S
TYPICAL ROOF DECK FASTENING REQUIREMENTS
SIDE LAP
DECK
SUPPORT
SIDE LAP ATTACHMENT
W/ #10 SCREWS @
8"O.C.
NO SCALE
2" LAP
DECK SHALL BE MIN. (3)SPAN CONTINUOUS
NOTE:
ALL SCREWS @ CONT. SUPPORTS SHALL BE #12 SELF-DRILLING
SELF-TAPPING SCREWS. PROVIDE (2)#10 SCREWS @ EA. SUPPORT
WHERE 2x TONGUE & GROOVE DECKING OCCURS.
1±
1±
TYPICAL 'X'-BRACING DETAIL
TOP CHORD OF TRUSSES
WEB MEMBER
OF TRUSSESSTEEL DECK
3 5/8"x1 5/8"x16GA. "C"
SECTION X-BRACING
BOTTOM CHORD
OF TRUSSES
NOTE:
WHERE "PIGGY BACK"
TRUSSES OCCUR, PROVIDE
ADDITIONAL, SEPERATE,
VERT. X-BRACING FOR
PIGGY-BACKS.
3 5/8"x1 5/8"x16GA. "C"
SECTION CONTINUOUS.
TYPICAL NON-BEARING C.M.U. WALL
ANCHORAGE DETAIL AT COLD-FORMED STEEL
TRUSSES
WALL PARALLEL TO TRUSSES
WALL PERPENDICULAR TO TRUSSES
8"
8"
/4
TOP OF MASONRY
(2)#12 SCREWS @ EA.
HORIZ. "C", TYPICAL.
PRE-ENG. PREFAB.
COLD-FORMED
STEEL TRUSSES
6"x1 5/8"x16GA.
UNPUNCHED "C"
STUDS @ 48"O.C.
1/4"x7"x7" WELD PLATE W/ (2)1/2"Øx4" HEADED
STUDS @ 48"O.C.
TRUSS BOTTOM
CHORD, TYPICAL.
CONT. U-BLOCK W/
#5 TOP & BOTTOM
#4 @ EA. JAMB & 48"O.C.,
CENTERED. FILL CELLS
W/ CONC. FULL HT. OF
WALL ONLY @ #4.
NOTE:
COPE FLANGES AS
SHOWN @ TRUSS
BOTTOM CHORDS.
TYP.
TOP OF MASONRY
/4
1/4"x4"x4" WELD PLATE W/ 1/2"Øx4" HEADED
STUD @ EA. TRUSS
CONT. U-BLOCK W/
#5 TOP & BOTTOM
#4 @ EA. JAMB & 48"O.C.,
CENTERED. FILL CELLS
W/ CONC. FULL HT. OF
WALL ONLY @ #4.
TRUSS BOT. CHORD
SIMPSON DTC TRUSS
CLIP @ EA. TRUSS
LENGTH
SCH. PL. 1' - 4"
TYPICAL BEAM BEARING ON C.M.U. WALL DETAIL (PARALLEL)
END OF DOWELS
PROVIDE 2" LONG HORIZ.
SLOTTED HOLES IN BEAM &
PLATE. FINGER TIGHTEN
NUTS & UPSET THREADS.
CONT. U-BLOCK
W/ #5 TOP & BOT.
SEE PLAN FOR
BEAM SIZE
5/8"Ø SMOOTH DOWELS
WELDED TO BEAM
SCHEDULED BEARING PLATE &
ANCHOR BOLTS ON 1"± GROUT
FILL (2)CELLS (16") W/ CONC.
FULL HT. BELOW BEARING &
REINF. W/ 1-BAR SAME SIZE
AS WALL REINF. EA. CELL.
TYPICAL BEAM BEARING ON C.M.U.
WALL DETAIL (PERPENDICULAR)
CONT. U-BLOCK W/ #5
TOP & BOT. EACH SIDE
PROVIDE 1"Ø HOLES IN
BEAM WEB FOR PASSAGE
OF U-BLOCK REINF. DO NOT
WELD REBAR TO BEAM.
FILL (2)CELLS (16") W/
CONC. FULL HT. BELOW
BEARING & REINF. W/ 1-
BAR SAME SIZE AS
WALL REINF. EA. CELL.
SEE PLAN FOR
BEAM SIZE
PROVIDE 2" LONG HORIZ.
SLOTTED HOLES IN BEAM &
PLATE. FINGER TIGHTEN
NUTS & UPSET THREADS.
SCHEDULED BEARING
PLATE & ANCHOR
BOLTS ON 1"± GROUT
SEE PLAN
NOTE:
FILL ADD'L. CELL(S) FULL HT. AS
REQ'D. TO ACHIEVE SOLID
BEARING BELOW ENTIRE LENGTH
OF BEARING PLATE, TYP.
TYPICAL U-BLOCK STEP DETAIL
CONT. U-BLOCK REINF.
ADD'L. 'Z' BAR REINF. SAME
SIZE & NO. AS CONT. U-
BLOCK REINF. IN BOTTOM.
1' - 4" 1' - 4"
M A
X
TYPICAL JOIST WHERE LOAD IS ADDED
OTHER THAN AT PANEL POINT
L2x2x1/4 WELDED TO TOP &
BOTTOM CHORD @ POINT OF
LOAD & NEAREST OPPOSITE
CHORD PANEL POINT.
TYP.
LOAD
LOAD
1/4" PEJ. W/
SEALANT
6x6-W1.4x W1.4 W.W.F.
FINISH GRADE.
SEE CIVIL DWGS.
M
IN
M A
X
6' - 0"
3' - 6" 1' - 0" 1' - 6"
(7)#5 CONT.
TOP & BOTTOM
UNDER DRAIN.
SEE CIVIL DWGS.
#5 @ 12"O.C., EA. FACE
#5 @ 12"O.C., 1 1/2" CLEAR
#7 @ 12"O.C., 2" CLEAR
TYPICAL RETAINING WALL SECTION
(SEE CIVIL DWGS. FOR LOCATION)
S P
L
IC
E
C L A
S S
B
TYPICAL EQUIPMENT PAD DETAIL
W.W.F.
S E
E P
L A
N
#4 @ 12"O.C., EA.
WAY, CENTERED.
MIN.
6"
O.S.F. OF
EQUIPMENT
TOOL EDGE
1. BEAR 8" HIGH U-BLOCKS 8" EACH END &
16" & 24" HIGH U-BLOCKS 16" EACH END.
2. FILL CELLS W/ CONCRETE FULL HEIGHT @
U-BLOCK BEARING FOR ENTIRE LENGTH
OF BEARING & REINFORCE EACH CELL W/
BAR SAME SIZE AS WALL REINFORCING.
VERTICAL REINFORCING SHALL BE
CONTINUOUS THRU LINTEL @ BEARING.
3. FILL CELLS OF U-BLOCK LINTEL TO FULL
HEIGHT IN ONE POUR.
4. BEAR CONC. BEAMS 16" EA. END. USE
REINF. BAR EA. FACE (8"O.C. = 4 BARS
TOTAL EA. JAMB). SEE TYP. JAMB
CONDITION @ CONC. BEAM LINTELS THIS
SHEET.
NOTES:
/2
M A
X
WIDTH
SCH.
SCH. REINF.
BLOCK W/
KNOCK-OUT WEBS
SCH. WALL REINF.
16" HIGH U-BLOCK
/2
M A
X
WIDTH
SCH.
SCH. REINF.
FILL CELLS FULL
HT. AT SAME TIME
SCH. WALL REINF.
24" HIGH U-BLOCK
BLOCK W/
KNOCK-OUT WEBS
L6x6x3/8 CONT. W/ 5/8"Øx4" EMBEDMENT
EXP. BOLT @ 24"O.C.
/2
7 5/8"
(2)#5 CONT. TOP &
BOT. W/ #3 @ 6"O.C.
16" DEEP CONC. LINTEL
BEARING & BASE PLATE SCHEDULE
MARK PLATE SIZE ANCHOR BOLT
NO. & SIZE
BP-1 3/4"x10"x10" (4)3/4"Øx16" HEADED
BP-3 3/4"x7"x16" (2)3/4"Øx14" HEADED
BP-2 3/4"x11"x16" (2)3/4"Øx14" HEADED
PLATE
TYPE
A
BASE PLATE TYPES
TYPE A TYPE B
B & C
B & C
CENTERLINE
OF WALL
/2
T Y
P
1/4
BP-4 1 1/4"x7"x16" (2)3/4"Øx14" HEADEDB & C
TYPE C
CENTERLINE
OF TRUSS
CENTERLINE
OF WALL
S E
E S
E C
T
IO
N
S FILL 1-CELL (8") FULL
HEIGHT OF WALL W/
CONC. @ REINF. W/ 1-BAR
SAME SIZE AS WALL
REINF. FULL HEIGHT
JAMB AT LINTELS
BEARING 8"
S E
E S
E C
T
IO
N
S FILL 2-CELL (16") FULL
HEIGHT OF WALL W/
CONC. @ REINF. W/ 1-BAR
SAME SIZE AS WALL
REINF. FULL HEIGHT
JAMB AT LINTELS
BEARING 16"
TYPICAL JAMB REINFORCING DETAILS
(UNLESS NOTED OTHERWISE ON DRAWINGS)
(2)#5 EA. CELL, (3)CELLS
TOTAL. (EA. FACE AS SHOWN)
/2
/2
CL. C.M.U.
1' - 4"
NOTE:
ALL JAMB REINF. SHALL BE CONT. THRU LINTEL.
MAINTAIN 3" VERT. BAR SPACING WHERE LINTEL HORIZ.
REINF. PASSES BETWEEN VERT. BARS. MAINTAIN 1"
CLEARANCE BETWEEN BEAM HORIZ. BARS.
FILL CELLS SOLID
W/ CONC. FULL HT.
TYPICAL JAMB CONDITION @
CONC. BEAM LINTELS
Sheet Number
Sheet Title
Project Title
Job Number
Date
Drawn By
Checked By
S o u th C o u rt
S tr ee t
M o n tg o m er y, A
L
T el
. 3 4.
. 5
W W W .S S L A R C H .C O M
A R
C H
IT
E
C T
U R
E
I N
T E
R
IO
R D
E S
IG
N
06-17-24
S0.1
General Notes / Schedules / Typical Details
N ew
S ec u ri ty B u ild in g
7t h A ir R ef u el in g
W in g B ir m in gh am , A la b am a
12072
JUNE 2024
GENERAL NOTES
FOUNDATION:
1. THE BEARING STRATA OF ALL FOOTINGS AND GRADE BEAMS SHALL BE
INSPECTED AND APPROVED BY THE SOILS TESTING LABORATORY PRIOR
TO PLACING THE REINFORCING STEEL AND CONCRETE.
2. ALL FOOTINGS SHALL BEAR ON AN UNDISTURBED SOIL STRATA OR
COMPACTED FILL CAPABLE OF SUSTAINING THE LOADS.
3. FOOTINGS WERE DESIGNED FOR AN ALLOWABLE SOIL BEARING OF
P = 2500 PSF.THE TESTING AGENCY SHALL VERIFY THAT THE SOILS ARE
CAPABLE OF SUSTAINING 2500 PSF PRIOR TO CONCRETE PLACEMENT.
4. ELEVATIONS SHOWN ON PLAN ARE TOP OF FOOTINGS AND ARE MINIMUM
DEPTH. DIFFERENT OR UNUSUAL CONDITIONS SHALL BE REPORTED TO
THE ARCHITECT AND/OR ENGINEER.
5. ALL FOOTING REINFORCEMENT SHALL BE HELD SECURELY FROM THE
GROUND. CONCRETE BLOCK AND BROKEN TILE SHALL NOT BE USED.
CONCRETE OR CLAY BRICK MAY BE USED.
6. DOWEL ALL FOOTINGS AND WALLS WHERE THEY ABUT WITH SAME STEEL
AS VERTICAL.
7. PROVIDE PREFORMED EXPANSION JOINT WHERE SHOWN.
8. IN FOOTINGS PROVIDE CORNER BARS AT ALL EXTERIOR BUILDING CORNERS.
9. DO NOT BACK FILL BEHIND FOUNDATION WALLS UNTIL TOP AND BOTTOM
SLABS HAVE BEEN POURED AND ATTAINED THEIR DESIGN STRENGTHS.
10. BACK FILL BOTH SIDES OF FOUNDATION WALLS AT SAME TIME TO
PREVENT OVERTURNING.
11. BACK FILL BEHIND ALL RETAINING WALLS AND BASEMENT WALLS SHALL
BE AN APPROVED GRANULAR MATERIAL.
CONCRETE:
1. ALL CONCRETE SHALL HAVE A COMPRESSIVE STRENGTH AT 28 DAYS OF
F'c = 3000 PSI AND A MAXIMUM WATER-CEMENT RATIO OF 0.53.
ALL CONCRETE FOR EXTERIOR APPLICATIONS SHALL CONTAIN
ENTRAINED AIR. SEE SPECS FOR ADDITIONAL INFORMATION.
2. REINFORCING STEEL SHALL CONFORM TO ASTM A615 GRADE 60.
3. WELDED WIRE FABRIC SHALL CONFORM TO ASTM A185 OR ASTM A1064.
4. UNLESS NOTED OTHERWISE PROTECTIVE COVERING OF REINFORCEMENT
SHALL BE AS FOLLOWS ( SEE DETAILS ) : FOOTINGS AND GRADE BEAMS
3" CLEAR BOTTOM AND SIDES, 1 1/2" CLEAR TOP. CONCRETE SLABS
3/4" CLEAR. WALLS 1 1/2" CLEAR SIDES. BEAMS 1 1/2" CLEAR TO
STIRRUPS. FORMED CONCRETE COLUMNS 1 1/2" CLEAR TO TIES.
5. LAP ALL CONCRETE WALL VERTICAL REINFORCING AND CONCRETE BEAM
HORIZONTAL REINFORCING WITH CLASS B LAP SPLICES. LAP ALL OTHER
CONTINUOUS BARS WITH CLASS A SPLICES UNLESS NOTED OTHERWISE.
6. PLACING PLANS AND DETAILS SHALL BE IN ACCORDANCE WITH THE
LATEST "A.C.I. DETAILING MANUAL".
7. STEEL FABRICATOR SHALL SUBMIT SHOP DRAWINGS FOR THE ARCHITECT
AND/OR ENGINEER'S REVIEW.
8. DO NOT RUN CONDUITS, RACEWAYS, OR PIPES IN CONCRETE SLABS, BEAMS,
OR COLUMNS WITHOUT SPECIFIC APPROVAL FROM BLACKBURN DANIELS O'BARR.
MASONRY:
1. PROVIDE MASONRY HORIZONTAL JOINT REINFORCEMENT 16" O.C.
VERTICAL IN ALL CONCRETE BLOCK WALLS. REINFORCEMENT SHALL BE
FOR TOTAL WIDTH OF CAVITY WALLS.
2. WHERE CONCRETE OR STEEL BEAMS BEAR ON CONCRETE BLOCK WALLS, BLOCK
CELLS SHALL BE FILLED WITH CONCRETE 1'-4" WIDE TO FOUNDATION AND
REINFORCED WITH A #5 EACH CELL UNLESS NOTED OR DETAILED OTHERWISE.
3. CONCRETE OR GROUT FOR BLOCK FILL SHALL HAVE 3/8 INCH MAXIMUM
SIZE COARSE AGGREGATE AND SUFFICIENT WATER SO THE CONCRETE
WILL FLOW INTO THE BLOCK CELLS WITHOUT LEAVING VOIDS. HEIGHT
OF LIFT WHEN FILLING CELLS SHALL NOT EXCEED 4'-0".
4. CONCRETE OR GROUT FILL FOR C.M.U. SHALL HAVE A 28 DAY COMPRESSIVE
STRENGTH OF F'c = 3000 PSI. ON 16" AND DEEPER U-BLOCKS, FILL
CELLS FULL HEIGHT OF LINTEL AT SAME TIME.
5. ANCHOR ALL MASONRY WALLS TO STEEL COLUMNS WITH STRAP ANCHORS
AT 16" O.C. VERTICALLY UNLESS SHOWN OTHERWISE.
6. UNLESS INDICATED OTHERWISE PROVIDE KEYED RUBBER MASONRY
CONTROL JOINTS AT A MAXIMUM SPACING OF 25'-4". JOINT SHALL
BE DISCONTINUOUS AT BOND BEAM. COORDINATE EXACT LOCATIONS
WITH ARCHITECT.
7. PROVIDE REINFORCING BAR SUPPORTS TO CENTER VERTICAL
REINFORCING IN MASONRY WALLS.
8. PROVIDE 48 DIAMETER LAP SPLICE IN VERTICAL MASONRY REINFORCING.
9. PROVIDE CORNER BARS IN U-BLOCK BOND BEAMS AT CORNERS, TYPICAL.
10. ALL CMU SHALL BE PLACED IN A RUNNING BOND PATTERN UNLESS NOTED
OTHERWISE ON ARCHITECTURAL DRAWINGS.
11. VERTICAL REINFORCING SHALL BE CONTINUOUS THROUGH BOND BEAMS AND
LINTELS (CUT OUT OR NOTCH BOTTOM OF U-BLOCKS AS REQUIRED -- DO NOT
SUBSTITUTE BLOCK WITH KNOCK-OUT WEBS WHERE STANDARD U-BLOCK IS
INDICATED). FOR BOND BEAMS AT TOP OF WALL, EXTEND VERTICAL
REINFORCING TO 1" CLEAR TOP OF BOND BEAM.
STRUCTURAL STEEL:
1. ALL STRUCTURAL STEEL W AND WT SHAPES SHALL CONFORM TO ASTM
A992 (GRADE 50). OTHER SHAPES SHALL CONFORM TO ASTM, A36,
LATEST EDITION (EXCEPT STEEL JOISTS AND TUBE SECTIONS).
2. STRUCTURAL STEEL TUBE SECTIONS SHALL CONFORM TO ASTM A500,
GRADE B, Fy = 46.0 KSI.
3. HEADED STUDS SHALL BE TYPE B SHEAR CONNECTORS (Fu = 65 KSI).
4. STEEL FABRICATOR SHALL SUBMIT SHOP DRAWINGS FOR THE ARCHITECT
AND/OR ENGINEER'S REVIEW.
5. THE CONTRACTOR SHALL VERIFY ALL SH0P DRAWINGS DIMENSIONS WITH
STRUCTURAL AND ARCHITECTURAL PLANS AND DETAILS.
6. BOLTED CONNECTIONS SHALL BE MADE WITH HIGH STRENGTH BOLTS
CONFORMING TO ASTM A325. USE 3/4 INCH DIAMETER MINIMUM.
UNLESS NOTED OTHERWISE, ALL BOLTS SHALL BE TIGHTENED AS FULLY
PRETENSIONED BEARING CONNECTIONS.
7. CONNECTIONS NOT SHOWN ON DRAWINGS SHALL BE DESIGNED
BY THE FABRICATOR. WHERE POSSIBLE USE DOUBLE ANGLE
CONNECTIONS. USE MAXIMUM NUMBER OF BOLTS FOR DEPTH
OF BEAM WITH SINGLE ROW OF BOLTS. WHERE DOUBLE ANGLE
CONNECTIONS ARE NOT POSSIBLE, FABRICATOR SHALL DESIGN
CONNECTION FOR CAPACITY EQUIVALENT TO DBL-ANGLE CONNECTION
WITH MAX NO. BOLTS UNLESS DETAILED OTHERWISE.
8. FOR DBL-ANGLE CONNECTIONS, MIN ANGLE THICKNESS SHALL BE 5/16"
FOR 3/4 INCH DIAMETER BOLTS AND 3/8" FOR 7/8 INCH DIAMETER BOLTS
AND LARGER.
9. UNLESS SHOWN OTHERWISE PROVIDE 1/2 X 7 1/2 X 7 1/2 BEARING
PLATES ON 1 INCH GROUT WITH 2-3/4" DIAMETER ANCHOR BOLTS
UNDER ALL STEEL BEAMS THAT BEAR ON MASONRY WALLS.
10. OPEN WEB STEEL JOIST SHALL CONFORM TO THE SPECIFICATIONS OF
THE AISC AND SJI AND TO THE LATEST OSHA STEEL ERECTION STANDARD.
11. UNLESS SHOWN OTHERWISE PROVIDE BRIDGING, BEARING SEATS, AND
STABILIZER PLATES IN ACCORDANCE WITH ABOVE SPECIFICATIONS AND
STANDARD.
12. ALL BRIDGING SHALL BE SECURELY ANCHORED AT END OF EACH RUN.
WELD TO STEEL BEAM OR ANCHOR TO MASONRY WALL WITH 3/8 "
ANCHOR BOLTS.
13. WHERE JOISTS CAN NOT BEAR 2 1/2 INCHES ON STEEL BEAMS,
STAGGER LOCATION OF JOISTS TO PROVIDE 2 1/2 INCHES MINIMUM
BEARING.
14. ROOF JOISTS AND BRIDGING SHALL BE DESIGNED FOR A NET UPLIFT
OF 15 PSF (ASD).
15. ANY MEMBER CALLED OUT TO BE BENT TO RADIUS SHALL BE FABRICATED OUT
OF PLATE WITH EQUIVALENT SECTION PROPERTIES IF BENDING TO RADIUS
IS IMPRACTICAL.
COLD-FORMED STEEL TRUSSES:
1. PROVIDE PREFABRICATED, PRE-ENGINEERED, COLD-FORMED STEEL TRUSSES
WHERE INDICATED ON PLAN.
2. ALL TRUSSES SHALL BE DESIGNED AND MANUFACTURED TO MEET THE
FOLLOWING WORKING LOADS AND CODES.
MINIMUM LOADS:
ROOF LIVE LOAD...............20 PSF.
ROOF DEAD LOAD............20 PSF. (INCLUDES LOAD FROM FUTURE SOLAR PANEL ARRAY)
CEILING LOAD...................10 PSF.
3. MANUFACTURER SHALL SUBMIT SHOP DRAWINGS AND DESIGN CAL-
CULATIONS FOR EACH TYPE TRUSS. DESIGNS SHALL BE SIGNED BY A
REGISTERED PROFESSIONAL ENGINEER, REGISTERED IN THE STATE OF
ALABAMA.
4. PROVIDE CAMBER IN ALL TRUSSES.
5. ALL TRUSSES SHALL BE SHOP-FABRICATED. FIELD-FABRICATED TRUSSES
ARE NOT ACCEPTABLE. THE TOP AND BOTTOM CHORDS SHALL BE FABRICATED
FROM SECTIONS THAT ARE SYMMETRICAL ABOUT THE Y-Y AXIS. "C" SECTIONS
ARE NOT ACCEPTABLE.
6. ANCHOR ALL TRUSSES TO SUPPORTS WITH GALVANIZED ANCHORS PER
MANUFACTURER'S RECOMMENDATIONS UNLESS SHOWN OTHERWISE ON THE
STRUCTURAL CONTRACT DRAWINGS. TRUSS MANUFACTURER SHALL INDICATE
ON SHOP DRAWINGS THE REQUIRED ANCHORAGE TO RESIST NET…
This is the start of the file's text. The full file is on GovTribe.