Volusia_County_Southwest_Storage_and_Repump_Facility_-_Drawings_(December_2025).pdf
PDF 47 MB Posted
- Attached to
- Southwest Storage and Repump Facility
- Solicitation number
- 26-B-50IF
- Issued by
- Volusia County, Florida
About this file
Summary of Volusia County Southwest Storage and Repump Facility Construction Plans
This file comprises comprehensive construction drawings and specifications for the Volusia County Southwest Storage and Repump Facility project in Debary, Florida. The project, managed by Volusia County Utilities with design by CPH Consulting, LLC, involves the construction of a new 2.0 million-gallon potable water ground storage tank, a high-service pump station with three 750 GPM pumps, a combined operations building housing electrical/IT and chemical storage facilities, and complete site development infrastructure. The facility is designed to enhance system capacity and operational reliability for the County's Southwest Service Area. The drawings indicate a project address of 798 Fort Florida Road, DeBary, Florida 32713, and include detailed civil, structural, architectural, mechanical, electrical, and instrumentation plans prepared under Florida Professional Engineer licenses and stamped for 100% submittal status as of October 2025. The project encompasses approximately 3,066 square feet of building space, including a 1,806 square-foot tank room, 666 square-foot pump room, 325 square-foot electrical room, and 69 square-foot IT/secure room, all constructed to Florida Building Code 2023 standards with Type V non-sprinklered construction.
The design specifications require a 2.0 MG ground storage tank with specialized features including prestressed concrete construction, chlorine and ammonia chemical injection systems, flow monitoring equipment, and complete electrical/instrumentation integration. Construction details specify reinforced concrete foundations with 4,000 PSI compressive strength, 8-inch concrete masonry unit walls, and light-gauge metal roof truss systems with standing seam metal roof covering. The project includes comprehensive stormwater management with treatment volume of 1,644 cubic feet, erosion and sediment control measures, site grading with multiple drainage swales, and a 5,249 cubic foot stormwater retention pond. Mechanical systems include air handling units, multiple split air conditioning units, exhaust fans, and complete ductwork distribution. Electrical infrastructure incorporates a 208V single-phase service with variable frequency drives for pump operation, backup generator capabilities, and comprehensive control systems. All work must comply with Volusia County Utilities standards, Florida Department of Environmental Protection requirements, and local jurisdictional permits, with the contractor responsible for obtaining all necessary state, county, and local permits prior to construction commencement.
View the file
Other files
Show all 12
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Know what's below.
before you dig.Call
R
*NOTICE*
THIS SET OF PLANS IS NOT VALID FOR CONSTRUCTION PURPOSES WITHOUT BEING STAMPED
"APPROVED FOR CONSTRUCTION BY CPH INC." PLANS WITHOUT THIS STAMP ARE GIVEN FOR
INFORMATIONAL PURPOSES ONLY.
VOLUSIA COUNTY
Southwest Storage And Repump Facility
JOB# V03120
DATE: OCTOBER 2025
c 2025
1117 East Robinson Street Orlando, FL 32801 Ph: 407.425.0452
C 2025 www.cphcorp.com eA Full Servic
A & E Firm
Index of Sheets
SEE SHEET G-01
County Officials
COUNTY CHAIR
Jeff Brower
COUNTY COUNCIL
At-Large: Jake Johansson
District 2: Matt Reinhart District 3: Danny Robins
District 4: Troy Kent
COUNTY MANAGER
George Recktenwald
DIRECTOR OF UTILITIES
Michael Ulrich
SR. UTILITY ENGINEER
Dr. Erin Reed, P.E.
District 5: David Santiago
District 1: Don Dempsey
CPH Consulting, LLC A Full Service A & E Firm
Plans Prepared By:
State of Florida Licenses:
Engineer No. 3215
Surveyor No. LB7143 Architect. No. AA26000926 Landscape No. LC000298
ROBERTO MARCOS GONZALEZ, P.E.
P.E. LIC. # 56875
Drawing name: J:\V03120\Civil\DWG\_DWG Fort Florida GST\V03120 Cover.dwg Sep 15, 2025 - 8:46am dg.Holland
100% SUBMITTAL
ADDRESS: 798 FORT FLORIDA RD. DEBARY 32713
M-07
M-08
M-09
M-10
M-11
M-13
A001
A002
A010
M-12
GROUND STORAGE TANK DETAILS
HIGH SERVICE PUMPS PIPING PLAN
HIGH SERVICE PUMPS SECTIONS
CHEMICAL TANKS PLAN
CHEMICAL TANKS SECTIONS
CHEMICAL INJECTION ASSEMBLY AND
CHEMICAL ACCESS BOX DETAILS
SOLENOID CONTROLLED SUSTAINING
VALVE AND CHECK VALVE ASSEMBLIES
FLOW METER AND
CHEMICAL INJECTION ASSEMBLIES
SHEET INDEX AND DRAWING CONVENTIONS
GENERAL INFORMATION AND ABBREVIATIONS
CODE SUMMARY, CALCULATIONS &
LIFE SAFETY PLAN
STANDARD DETAILSD-01
D-02
D-03
STANDARD DETAILS
STANDARD DETAILS
A031
A101
A201
PARTITION TYPES & NOTES
ARCHITECTURAL FLOOR PLAN
EXTERIOR ELEVATIONS
A521 DETAILS
M-14
STANDARD DETAILSD-04
1G-0
A203 EXTERIOR ELEVATIONS
SHEET NO.
G-01
G-02
G-03
G-04
G-05
C-01
C-02
C-03
C-04
C-05
C-06
M-01
M-02
M-03
M-04
DRAWING INDEX
COVER
GENERAL NOTES AND VICINITY MAP
SYMBOLS & ABBREVIATIONS
PROCESS FLOW DIAGRAM
HYDRAULIC GRADE LINE
BOUNDARY AND TOPOGRAPHIC SURVEY
TREE REMOVAL PLAN
OVERALL GRADING PLAN
CONNECTION TO FORT FLORIDA ROAD
SITE FINAL GRADING PLAN
YARD PIPING PLAN
GROUND STORAGE TANK FLOOR AND ROOF PLAN
GROUND STORAGE TANK DETAILS
GROUND STORAGE TANK DETAILS
GROUND STORAGE TANK DETAILS
SWPPP EROSION CONTROL NOTES AND DETAILSC-07
C-08
STORMWATER DETAILSC-09
STORMWATER DETAILSC-10
SWPPP EROSION CONTROL DETAILS
SIGNATURE SHEET
G-06
C-06A PIPE CONFLICT CROSS SECTIONS
OUTFALL STRUCTURE AND CROSS SECTIONSC-11
TITLE SHEET NO.
DRAWING INDEX
TITLE SHEET NO.
DRAWING INDEX
TITLE
M-05 GROUND STORAGE TANK DETAILS
MP0
E-01
E-02
E-05
E-06
MECHANICAL TITLE SHEET
ELECTRICAL NOTES, SYMBOLS &
ABBREVIATIONS
OVERALL ELECTRICAL SITE PLAN
SINGLE LINE DIAGRAM
CONTROL RISER DIAGRAM
E-08 VFD ELEMENTARY DIAGRAM
E-09 PCP BACK UP CONTROL DIAGRAM
E-11 HIGH SERVICE PUMP ROOM ELECTRICAL PLAN
E-12
CHEMICAL STORAGE FACILITY
ELECTRICAL PLAN
E-13 OVERALL BUILDING LIGHT PLAN
E-14 OVERALL BUILDING GROUNDING &
LIGHTING PROTECTION PLAN
E-15
SOLENOID VALVE / FLOW METER ASSEMBLY
& CHECK VALVE ASSEMBLY ELECTRICAL PLANS
E-16 FLOW METER ASSEMBLY ELECTRICAL PLAN
E-17 GROUND STORAGE TANK ELECTRICAL PLAN
E-18 GENERATOR ELECTRICAL PLAN
E-19 LIGHT FIXTURE SCHEDULE & DETAILS
E-20 PANEL SCHEDULE
E-21 ELECTRICAL DETAILS - 1
E-22 ELECTRICAL DETAILS - 2
E-23 ELECTRICAL DETAILS - 3
E-24 ELECTRICAL DETAILS - 4
I-01 NOTES, SYMBOLS, AND ABBREVIATIONS
I-02 P&ID PROCESS
I-03 DUPLEX SKID SYSTEM
I-04 POWER MANAGEMENT
I-05 PICS NETWORK SYSTEM BLOCK DIAGRAM
FOUNDATION PLANS100
FOOTING SECTION DETAILSS101
CONCRETE PAD & FOOTING DETAILSS102
CONCRETE PAD DETAILSS103
CONCRETE PAD DETAILSS104
S105
S106
TYPICAL CONCRETE DETAILSS107
FRAMING PLANS200
ABBREVIATIONS AND WIND PRESSURE TABLESS002
STRUCTURAL GENERAL NOTESS001
CONCRETE PAD DETAILS
CONCRETE SLAB DETAILS
MP1 MECHANICAL AND PLUMBING PLAN
SS-01 SECURITY SITE PLANS
SS-02 SECURITY SYSTEM ACCESS DETAILS
SS-03 OVERALL OPERATIONS BUILDING SECURITY
SYSTEM PLAN
SS-04 SECURITY SYSTEM BLOCK DIAGRAM
E-03 ELECTRICAL SITE PLAN
E-04 CONDUIT & DUCTBANK SECTIONS
E-07 MISC DIAGRAMS
TYPICAL CONCRETE DETAILSS108
M-06 GROUND STORAGE TANK DETAILS
A301
A500
BUILDING SECTIONS
DOOR SCHEDULE
SHEET NO.
DRAWING INDEX
TITLE
E-10 ELECTRICAL ROOM & IT ROOM POWER PLAN
I-06 UPS POWER ELEMENTARY DIAGRAM
PROJECT ENGINEER / CIVIL
ROBERTO MARCOS
GONZALEZ, P.E. REG. #56875
CPH CONSULTING, LLC
500 WEST FULTON STREET
SANFORD, FL 32771
ENGINEER C.O.A. #3215
DATE
CONSTRUCTION PLANS:
SHEET NO. SHEET DESCRIPTION
G-01-G-06 GENERAL SHEETS
C-02-C-10 CIVIL PLANS
M-01-M-014 MECHANICAL PLANS
D-01-D-04 STANDARD DETAILS
Roberto Marcos Gonzalez, State of Florida, Professional Engineer, License No. 56875. This item has been digitally signed and sealed by Roberto Marcos Gonzalez, PE on the date indicated here.
Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies.
STRUCTURAL
EDUARDO AVILES NIEVES, P.E.
FLORIDA REG. #85877
CPH CONSULTING, LLC
500 WEST FULTON STREET
SANFORD, FL 32771
ENGINEER C.O.A. #3215
DATE
CONSTRUCTION PLANS:
SHEET NO. SHEET DESCRIPTION
G-02 SIGNATURE SHEET
S001,S200, STRUCTURAL PLANS
Eduardo Aviles Nieves, State of Florida, Professional Engineer, License No. 85877. This item has been digitally signed and sealed by Eduardo Aviles Nieves, PE on the date indicated here. Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies.
ARCHITECTURAL
KET WEST, A.I.A.
FLORIDA REG. #AR102902
CPH CONSULTING, LLC
500 WEST FULTON STREET
SANFORD, FL 32771
ENGINEER C.O.A. #3215
DATE
CONSTRUCTION PLANS:
SHEET NO. SHEET DESCRIPTION
G-02 SIGNATURE SHEET
A001-A521 ARCHITECTURAL PLANS
ELECTRICAL / INSTRUMENTATION
STEPHEN E. BAILEY, P.E.
FLORIDA REG. #42461
BAILEY ENGINEERING CONSULTANTS, INC.
10620 GRIFFIN ROAD, SUITE 202
COOPER CITY, FL 33328
ENGINEER C.O.A. #6783
DATE
CONSTRUCTION PLANS:
SHEET NO. SHEET DESCRIPTION
G-02 SIGNATURE SHEET
E-01-E-21 ELECTRICAL PLANS
I-01-I-05 INSTRUMENTATION PLANS
Stephen E. Bailey, State of Florida, Professional Engineer, License No. 42461. This item has been digitally signed and sealed by Stephen E. Bailey, PE on the date indicated here. Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies.
HVAC / PLUMBING
JEFFREY A. DEAL, P.E.
FLORIDA REG. #87451
CPH CONSULTING, LLC
500 WEST FULTON STREET
SANFORD, FL 32771
ENGINEER C.O.A. #3215
DATE
CONSTRUCTION PLANS:
SHEET NO. SHEET DESCRIPTION
G-02 SIGNATURE SHEET
M0-00-MP-1 HVAC PLANS
Jeffrey A. Deal, State of Florida, Professional Engineer, License No. 87451. This item has been digitally signed and sealed by Jeffrey A. Deal, PE on the date indicated here. Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies.
SURVEY
PAUL J. KATREK, P.S.M.
FLORIDA REG. #6233
CPH CONSULTING, LLC
500 WEST FULTON STREET
SANFORD, FL 32771
ENGINEER C.O.A. #LB7143
DATE
CONSTRUCTION PLANS:
SHEET NO. SHEET DESCRIPTION
G-02 SIGNATURE SHEET
C-01 (V-01) SURVEY SHEET
The electronic signature hereon is in compliance with the Florida Administrative Code (FAC) 5J-17.062(3) and the seal appearing on this document was authorized by Paul J. Katrek, PSM, 6233 per 5J-17.062(2).
THE ABOVE PROFESSIONAL ENGINEER SHALL BE RESPONSIBLE FOR THE
FOLLOWING SHEETS IN ACCORDANCE WITH RULE 61G15-23.004, F.A.C.
THE ABOVE PROFESSIONAL ENGINEER SHALL BE RESPONSIBLE FOR THE
FOLLOWING SHEETS IN ACCORDANCE WITH RULE 61G15-23.004, F.A.C.
THE ABOVE PROFESSIONAL ARCHITECT SHALL BE RESPONSIBLE FOR THE
FOLLOWING SHEETS IN ACCORDANCE WITH RULE 61G15-23.004, F.A.C.
THE ABOVE PROFESSIONAL ENGINEER SHALL BE RESPONSIBLE FOR THE
FOLLOWING SHEETS IN ACCORDANCE WITH RULE 61G15-23.004, F.A.C.
THE ABOVE PROFESSIONAL ENGINEER SHALL BE RESPONSIBLE FOR THE
FOLLOWING SHEETS IN ACCORDANCE WITH RULE 61G15-23.004, F.A.C.
THE ABOVE PROFESSIONAL ENGINEER SHALL BE RESPONSIBLE FOR THE
FOLLOWING SHEETS IN ACCORDANCE WITH RULE 61G15-23.004, F.A.C.
Job No.
Date:
Checked by:
Designed by:
Drawn by:
Sheet No.No. DateNo. Date Revision Revision www.cphcorp.com1
8 SOUTHWEST STORAGE AND
REPUMP FACILITY
Debary, Florida V03120 4/22/2025
RG
VM/RG
GCM
C 2025
1117 East Robinson Street Orlando, FL 32801 Ph: 407.425.0452
CPH CONSULTING, LLC
A Full Service A & E Firm
Plans Prepared By:
State of Florida Licenses:
Engineer No. 3215
Surveyor No. LB7143 Architect. No. AA26000926 Landscape No. LC000298
Building Better Communities Together
100% SUBMITTAL
Drawing name: J:\V03120\Civil\DWG\_DWG Fort Florida GST\V03120 Signature Sheet.dwg Sep 02, 2025 - 11:06am dg.Holland
G-02SIGNATURE SHEET
FO
R
T
FL
O R
ID
A
R O
A D
FORT FLORIDA ROAD
LAKE
KONOMAC
G-03GENERAL NOTES
AND VICINITY MAP
GENERAL NOTES
1. CITY OF DEBARY AND VOLUSIA COUNTY UTILITIES SHALL BE NOTIFIED AT LEAST SEVEN (7) DAYS PRIOR TO ANY CONSTRUCTION
ACTIVITY, OR PRIOR TO ANY ACTIVITY REQUIRING THE PRESENCE OF OR AN ACTION BY UTILITIES STAFF SUCH AS SCHEDULING VALVE OPERATION, PRESSURE TESTING, PIPE CONNECTION, PUMP STATION OPERATIONS OR SHUTDOWNS, ETC.
2. THE CONTRACTOR SHALL NOTIFY VOLUSIA COUNTY AT LEAST 48 HOURS PRIOR TO ANY UTILITIES CONSTRUCTION.
3. PRIOR TO CONSTRUCTION, THE CONTRACTOR SHALL MAKE A PRE-CONSTRUCTION VIDEO (DVD/ FLASH DRIVE FORMAT) IN ACCORDANCE WITH THE SPECIFICATIONS. IN PARTICULAR, THE VIDEO SHALL DOCUMENT THE CONDITION OF EXISTING DRIVEWAYS, BUILDINGS, STRUCTURES, MAILBOXES, SIGNS, FENCES, AND LANDSCAPING WITHIN PROPOSED CONSTRUCTION LIMITS.
4. THE CONTRACTOR SHALL RECOGNIZE AND ABIDE BY ALL OSHA EXCAVATION SAFETY STANDARDS, INCLUDING THE FLORIDA TRENCH SAFETY ACT (FS 553.60-553.64). ANY MATERIAL, CONSTRUCTION METHODS, OR MATERIAL COST TO COMPLY WITH THESE LAWS SHALL BE
INCIDENTAL TO THE CONTRACTOR.
5. THE CONTRACTOR SHALL OBTAIN FROM THE OWNER COPIES OF ALL AVAILABLE REGULATORY AGENCY PERMITS AND LOCAL AGENCY
PERMITS.
6. SHOULD A PIPE EMERGENCY OCCUR, THE CONTRACTOR SHALL IMMEDIATELY NOTIFY VOLUSIA COUNTY UTILITIES AND ENGINEER.
7. WATER, WASTEWATER AND RECLAIMED WATER VALVES, PUMP STATIONS OR OTHER UTILITY INFRASTRUCTURE ARE TO BE OPERATED ONLY BY VOLUSIA COUNTY UTILITIES PERSONNEL. ALL VALVES BEING INSTALLED ARE TO REMAIN CLOSED DURING CONSTRUCTION.
8. ALL EXISTING WATER MAINS, FORCE MAINS, GRAVITY PIPES AND OTHER UTILITY FACILITIES WITHIN THE LIMITS OF THE PROJECT WILL BE
SUPPORTED AND PROTECTED AGAINST DAMAGE DURING CONSTRUCTION.
9. THE CONTRACTOR SHALL EXERCISE EXTREME CAUTION WHEN EXCAVATING IN PROXIMITY OF WATER MAINS, WASTEWATER FORCE MAINS, AND GRAVITY MAINS AND RECLAIMED WATER MAINS. WATER MAIN, FORCE MAIN, GRAVITY MAIN AND RECLAIMED WATER MAIN LOCATIONS SHOWN ON THE PLANS ARE NOT EXACT OR GUARANTEED. THE CONTRACTOR IS RESPONSIBLE FOR FIELD VERIFYING
EXISTING UTILITY LOCATIONS.
10. LOCATIONS OF EXISTING UTILITIES AS SHOWN IS APPROXIMATE. THE CONTRACTOR SHALL FIELD VERIFY THE EXISTENCE AND LOCATION OF ALL UNDERGROUND UTILITIES AND DETERMINE THE STATUS OF SAID UTILITY, PRIOR TO ANY DEMOLITION OR CONNECTION OF PROPOSED UTILITIES. CONTRACTOR SHALL CONTACT UTILITY OWNERS, INCLUDING FIBER OPTICS COMPANIES, AT LEAST SEVEN (7) DAYS PRIOR TO CONSTRUCTION AND A MINIMUM OF 48 HOURS PRIOR TO ANY EXCAVATION. EXTREME CAUTION SHALL BE EXERCISED IN
AREAS OF FIBER OPTICS AND GAS MAINS.
11. IMMEDIATELY AT ONSET OF CONSTRUCTION, CONTRACTOR SHALL FIELD VERIFY HORIZONTAL AND VERTICAL LOCATIONS OF ALL EXISTING UTILITIES CRITICAL TO COMPLETING THE PROJECT (INCLUDING WATER, SEWER, RECLAIMED WATER, POWER, TELEPHONE, GAS AND CABLE TV) AND SHALL EVALUATE POTENTIAL CONFLICTS IN A WRITTEN REPORT. ANY CONFLICTS SHALL BE REPORTED TO
ENGINEER/OWNER IMMEDIATELY UPON DISCOVERY AND DETAILED IN THE REPORT.
12. ALL UTILITIES CONSTRUCTION CONNECTING TO THE VOLUSIA COUNTY UTILITIES SYSTEM SHALL CONFORM TO THE CURRENT VOLUSIA COUNTY'S SPECIFICATIONS FOR WASTEWATER AND WATER MAIN CONSTRUCTION UNLESS OTHERWISE NOTED.
13. SUPPORT AND PROTECT ALL EXISTING UTILITIES. CONTRACTOR SHALL CONTACT UTILITY OWNERS FOR LOCATION OF ALL EXISTING FACILITIES. CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING WITH UTILITY OWNERS AND BE RESPONSIBLE FOR PROVIDING TEMPORARY SUPPORT FOR UTILITY POLES, LIGHT POLES, AND ALL OTHER UTILITIES DURING CONSTRUCTION.
14. ALL PIPE, PIPE FITTINGS AND APPURTENANCES INSTALLED UNDER THIS PROJECT WILL BE COLOR CODED OR MARKED IN ACCORDANCE
WITH VOLUSIA COUNTY UTILITIES STANDARDS.
15. ALL BACKFILL SHALL BE COMPACTED TO NOT LESS THAN 95% OF MINIMUM DRY DENSITY AS MEASURED BY AASHTO T-180 METHOD 'D' TEST (MODIFIED PROCTOR) IN OPEN AREAS AND NOT LESS THAN 98% OF MAXIMUM DRY DENSITY AS MEASURED BY AASHTO T-180 METHOD 'D' TEST (MODIFIED PROCTOR) UNDER ASPHALT OR CONCRETE PAVEMENT AND WITHIN 3-FT OF PAVEMENT. ALL SOIL TESTING TO BE CONDUCTED BY THE CONTRACTOR. THE CONTRACTOR SHALL PROVIDE ALL REASONABLE ASSISTANCE DURING THE SOIL TESTING. RESULTS, PASSING OR FAILING, SHALL BE PROVIDED TO VOLUSIA COUNTY FOR REVIEW.
16. MAINTAIN EMERGENCY VEHICLE ACCESS TO ALL BUSINESSES AND RESIDENCES AT ALL TIMES.
17. ALL MAINS SHALL BE CONSTRUCTED AS SHOWN ON PLANS. A MINIMUM COVER OF 36 INCHES SHALL BE MAINTAINED ON ALL MAINS, WHERE IT IS NOT OTHERWISE SPECIFIED ON PLANS OR DIRECTED BY ENGINEER.
18. PIPE LENGTHS SHOWN ON PLANS ARE APPROXIMATE. ACTUAL LENGTHS ARE TO BE DETERMINED DURING CONSTRUCTION.
19. NO VALVE BOXES, METERS, PORTIONS OF MANHOLES OR OTHER APPURTENCES OF ANY KIND SHALL BE LOCATED IN ANY PORTION OF A CURB-AND-GUTTER SECTION. CONTRACTOR SHALL ADVISE ENGINEER IMMEDIATELY UPON DISCOVERY OF A POTENTIAL CONFLICT.
20. CONTRACTOR SHALL PROVIDE DETAILED AS-BUILT DRAWINGS OF ALL EXISTING UTILITIES UNCOVERED IN TRENCHES. THE AS-BUILT SHALL RECORD LOCATION, SIZE, TYPE, ELEVATION AND OWNER OF ALL UTILITY FACILITIES UNCOVERED.
21. WHEN USING SCALED DATA CONSIDER THAT THESE PLANS MAY HAVE ALTERED IN SIZE DURING REPRODUCTION.
22. LOCATIONS AND DIMENSIONS OF EXISTING RIGHT-OF-WAYS AND EASEMENTS ARE BASED ON BEST AVAILABLE INFORMATION. VERIFY AND STAKE THE LIMITS OF THE RIGHT-OF-WAYS AND EASEMENTS IN ORDER TO AVOID ENCROACHMENTS BEFORE AND DURING
CONSTRUCTION.
23. WHEN OBTAINING DATA AND INFORMATION FROM THE PLANS, FIGURES SHALL BE USED IN REFERENCE TO SCALED DIMENSIONS.
24. COMPLETE ALL CONSTRUCTION WITHIN RIGHT OF WAY LIMITS AND EASEMENT LIMITS, UNLESS OTHERWISE NOTED.
25. RESTORE ALL EXISTING IMPROVEMENTS AND DISTURBED AREAS TO ORIGINAL OR BETTER CONDITION.
26. ASPHALTIC CONCRETE DRIVES SHALL BE COMPLETED TO THE ORIGINAL EDGE OF PAVEMENT. THE CONTRACTOR IS RESPONSIBLE FOR MAINTAINING THE EXISTING PAVEMENT OUTSIDE OF NEW PAVING LIMITS. THE CONTRACTOR SHALL BE RESPONSIBLE FOR REPAIRING
ALL DAMAGE TO THE EXISTING ROADWAY OUTSIDE THE NEW PAVING LIMITS.
27. THE CONTRACTOR SHALL BE RESPONSIBLE FOR SATISFYING ALL REQUIREMENTS OF REGULATORY AGENCY PERMITS FOR
CONSTRUCTION ACTIVITIES AND RELATED ACTIVITIES.
28. BENCHMARK LOCATIONS AND ELEVATIONS ARE SHOWN IN THE PLANS AS REPRESENTED BY THE SURVEYOR AT THE TIME OF SURVEY.
CONTRACTOR SHALL VERIFY ITS CORRECTNESS AT THE TIME OF CONSTRUCTION AND INSTALL HIS OWN TEMPORARY BENCHMARKS AS NECESSARY. ANY DISCREPANCIES SHALL BE IMMEDIATELY BROUGHT TO THE ATTENTION OF THE ENGINEER.
29. WHERE REQUIRED, AT NO ADDITIONAL COST TO VOLUSIA COUNTY UTILITIES, THE CONTRACTOR SHALL USE TEMPORARY SHEETING OR TRENCH BOXES TO MINIMIZE THE SIZE OF EXCAVATIONS AND PROTECT EXISTING ROADWAYS, UTILITIES AND OTHER FACILITIES.
CONTRACTOR TO COMPLY WITH OSHA TRENCH SAFETY REQUIREMENTS AT ALL TIMES.
30. NEW OR RELOCATED UNDERGROUND WATER MAINS SHALL BE LAID TO PROVIDE A HORIZONTAL DISTANCE OF AT LEAST SIX FEET, AND PREFERABLY TEN FEET, BETWEEN THE OUTSIDE OF THE WATER MAIN AND THE OUTSIDE OF ANY EXISTING OR PROPOSED GRAVITY-OR PRESSURE-TYPE SANITARY SEWER, WASTEWATER FORCEMAIN, OR PIPELINE CONVEYING RECLAIMED WATER NOT REGULATED UNDER PART III OF CHAPTER 62-610, F.A.C. THE MINIMUM HORIZONTAL SEPARATION DISTANCE BETWEEN WATER MAINS AND GRAVITY-TYPE SANITARY SEWERS SHALL BE REDUCED TO THREE FEET WHERE THE BOTTOM OF THE WATER MAIN IS LAID AT LEAST SIX INCHES ABOVE THE TOP OF THE SEWER. NEW OR RELOCATED UNDERGROUND WATER MAINS CROSSING ANY EXISTING OR PROPOSED GRAVITY-OR VACUUM-TYPE SANITARY SEWER SHALL BE LAID SO THE OUTSIDE OF THE WATER MAIN IS AT LEAST SIX INCHES, AND PREFERABLY 12 INCHES, ABOVE 3 OR AT LEAST 12 INCHES BELOW THE OUTSIDE OF THE OTHER PIPELINE. HOWEVER, IT IS PREFERABLE TO LAY THE WATER MAIN ABOVE THE OTHER PIPELINE. NEW OR RELOCATED UNDERGROUND WATER MAINS CROSSING ANY EXISTING OR PROPOSED PRESSURE TYPE SANITARY SEWER, WASTEWATER OR STORMWATER FORCEMAIN, OR PIPELINE CONVEYING RECLAIMED WATER SHALL BE LAID SO THE OUTSIDE OF THE WATER MAIN IS AT LEAST 12 INCHES ABOVE OR BELOW THE OUTSIDE OF THE OTHER PIPELINE.
HOWEVER, IT IS PREFERABLE TO LAY THE WATER MAIN ABOVE THE OTHER PIPELINE.
31. AT THE UTILITY CROSSINGS DESCRIBED ABOVE, ONE FULL LENGTH OF WATER MAIN SHALL BE CENTERED ABOVE OR BELOW THE OTHER PIPELINE SO THE WATER MAIN JOINTS WILL BE AS FAR AS POSSIBLE FROM THE OTHER PIPELINE. ALTERNATIVELY, AT SUCH CROSSINGS, THE PIPES SHALL BE ARRANGED SO THAT ALL WATER MAIN JOINTS ARE AT LEAST THREE FEET FROM ALL JOINTS IN VACUUM-TYPE SANITARY SEWERS, OR PIPELINES CONVEYING RECLAIMED WATER REGULATED UNDER PART III OF CHAPTER 62-610, F.A.C., AND AT LEAST SIX FEET FROM ALL JOINTS IN GRAVITY-OR PRESSURE-TYPE SANITARY SEWERS, WASTEWATER FORCEMAINS, OR PIPELINES
CONVEYING RECLAIMED WATER NOT REGULATED UNDER PART III OF CHAPTER 62-610, F.A.C.
32. THE CONTRACTOR SHALL CALL SUNSHINE STATE ONE CALL NO LESS THAN TWO WORKING DAYS PRIOR TO THE START OF
CONSTRUCTION - PHONE - 800-432-4777.
33. THE DISPOSAL OF ANY EXCESS EARTHWORK MATERIAL SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR.
34. SALVAGE AND/OR DISPOSAL OF ALL EXISTING EQUIPMENT SHALL BE AT THE DIRECTION OF THE ENGINEER AND VOLUSIA COUNTY
UTILITIES.
35. THE CONTRACTOR SHALL BE RESPONSIBLE FOR PROPER DISPOSAL OF ALL STRUCTURES, PIPE, CONDUIT, WIRE, FITTINGS, ETC. THAT
DEMOLISHED, DISASSEMBLED, OR REMOVED.
36. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ANY DE-WATERING REQUIRED DURING CONSTRUCTION AND TO OBTAIN AND PAY FOR
PERMITS REQUIRED FOR TEMPORARY DEWATERING.
37. THE CONTRACTOR SHALL FURNISH AND INSTALL ALL TEMPORARY PLUGS, BLOCKING, TAPS, AND TESTING EQUIPMENT REQUIRED TO
COMPLETE PRESSURE TESTING, AS SPECIFIED.
38. CONTRACTOR TO RESTORE ALL DAMAGED AND DISTURBED AREAS TO EQUAL OR BETTER CONDITION. CONTRACTOR SHALL INCLUDE IN HIS BID ALL COSTS FOR RESTORATION OF ALL LANDSCAPED AND SODDED AREAS DISTURBED AS PART OF HIS WORK.
39. CONTRACTOR TO COMPLETE HIS WORK AT THE END OF EACH DAY AND REOPEN SIDEWALKS FOR PUBLIC USE. SIDEWALKS SHALL CONSIST OF A STABILIZED ASPHALTIC SURFACE, OR EQUAL, SUITABLE FOR PUBLIC FOOT TRAFFIC.
40. THE CONTRACTOR IS RESPONSIBLE FOR IMPLEMENTING AND MAINTAINING EROSION AND SEDIMENT CONTROL MEASURES PRIOR TO
AND DURING CONSTRUCTION IN ACCORDANCE WITH THE DRAWINGS AND SPECIFICATIONS.
41. THE EROSION AND SEDIMENT CONTROL MEASURES SHOWN ON THE PLANS REPRESENT A MINIMUM REQUIREMENT. THE CONTRACTOR IS RESPONSIBLE FOR DETERMINING ADDITIONAL EROSION AND SEDIMENT CONTROL MEASURES NEEDED IN ORDER TO PREVENT THE TRANSFER OF SEDIMENT FROM THE PROJECT AREA AND PREVENT THE EROSION OF SURFACES DURING CONSTRUCTION, AS NEEDED TO
PROTECT ADJACENT PROPERTIES AND WATER BODIES.
42. IN THE EVENT THAT WATER IS ENCOUNTERED DURING CONSTRUCTION, DEWATERING SHALL BE CONDUCTED. THE CONTRACTOR IS SOLELY RESPONSIBLE FOR THE DESIGN, INSTALLATION, OPERATION, AND SUBSEQUENT REMOVAL OF DEWATERING SYSTEMS AND THEIR SAFETY AND CONFORMITY WITH LOCAL, COUNTY, STATE AND FEDERAIL CODES, AND REGULATIONS. IF DEWATERING EQUIPMENT
NEEDED EXCEEDS ANY OF THE FOLLOWING:
43. 6" PUMP VOLUTE; 2) 100,000 GPD TOTAL 24 HOUR (1 DAY) DEWATERING, AND; 3) 1,000,000 GPD PUMP CAPACOUNTY, THE CONTRACTOR SHALL BE REQUIRED TO PERMIT THE DEWATERING SYSTEM WITH THE ST. JOHNS RIVER WATER MANAGEMENT DISTRICT (SJRWMD). THE ENGINEER AND/OR OWNER SHALL BE NOTIFIED IMMEDIATELY IF ANY OF THE ABOVE THRESHOLDS ARE EXCEEDED.
44. DEWATERING DISCHARGE FROM THE SITE SHALL COMPLY WITH ALL NPDES GENERAL PERMIT REQUIREMENTS AND STATE WATER QUALITY STANDARDS. PROVIDE ALL TESTING AND PERMITTING REQUIRED AND COMPLY WITH ALL TREATMENT OR DISPOSAL METHODS
REQUIRED TO MEET ALL LOCAL, STATE AND FEDERAL REQUIREMENTS.
45. UNLESS OTHERWISE DIRECTED BY THE OWNER OR ENGINEER, THE CONTRACTOR IS EXPECTED TO CONTAIN ALL CONSTRUCTION ACTIVITIES WITHIN THE PROPERTY BOUNDARY, RIGHT-OF-WAY AND EASEMENTS, AND OTHER AREAS SPECIFICALLY DESIGNATED FOR CONSTRUCTION. AT NO TIME SHALL THE CONTRACTOR DISTURB SURROUNDING PROPERTIES OR TRAVEL ON SURROUNDING PROPERTIES WITHOUT WRITTEN CONSENT FROM THE PROPERTY OWNER. ANY REPAIR OR RECONSTRUCTION OF DAMAGED AREAS IN SURROUNDING PROPERTIES SHALL BE REPAIRED BY THE CONTRACTOR ON AN IMMEDIATE BASIS. ALL COSTS FOR REPAIRS SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR AND NO EXTRA COMPENSATION SHALL BE PROVIDED.
46. UNLESS OTHERWISE NOTED ON THE PLANS, THE CONTRACTOR SHALL USE THE GEOMETRY PROVIDED ON THE CONSTRUCTION PLANS.
BENCHMARK INFORMATION SHALL BE PROVIDED TO THE CONTRACTOR BY THE OWNER OR OWNER'S SURVEYOR. ANY DISCREPANCIES BETWEEN FIELD MEASUREMENTS AND CONSTRUCTION PLAN INFORMATION SHALL BE BROUGHT TO THE ATTENTION OF THE ENGINEER
IMMEDIATELY.
47. THE ENTIRE PROJECT SITE SHALL BE THOROUGHLY CLEANED AT THE COMPLETION OF THE WORK. CLEAN ALL INSTALLED PIPELINES, STRUCTURES, SIDEWALKS, PAVED AREAS, ACCUMULATED SILT IN PONDS, PLUS ALL ADJACENT AREAS AFFECTED BY CONSTRUCTION, AS DIRECTED BY THE OWNER OR JURISDICTIONAL AGENCY. EQUIPMENT TO CLEAN THESE SURFACES SHALL BE SUBJECT TO APPROVAL BY
THE OWNER.
PRESSURIZED PIPING SYSTEMS
1. CONTRACTOR TO SUBMIT CERTIFICATION DOCUMENTING THAT ALL PIPE AND FITTINGS USED TO CONVEY POTABLE WATER SHALL CONFORM TO NSF INTERNATIONAL STANDARD 61
(DRINKING WATER SYSTEM COMPONENTS).
2. BURIED PIPE SHALL CONFORM WITH ANSI/AWWA C150/A21.50 AND C151/ A21.51, AND SHALL HAVE A MINIMUM WORKING PRESSURE OF 150 PSI.
3. EXPOSED PIPE 4 INCHES AND LARGER SHALL BE FLANGED AND SHALL CONFORM WITH AWWA/ANSI C115/A21.15, AND SHALL HAVE A MINIMUM WORKING PRESSURE OF 150 PSI.
4. ALL FLANGES SHALL BE CLASS 125, AND SHALL BE FULLY MACHINE FACED AFTER BEING SCREWED TIGHTLY ON THE PIPE. BOLTS AND NUT SHALL CONFORM TO ASTM A307, GRADE B.
5. FITTINGS SHALL BE MANUFACTURED OF DUCTILE IRON, CONFORMING TO ANSI/AWWA C110/A21.10 OR ANSI/AWWA C153/A21.53.
6. ALL FULL BODY (C110/A21.10) FITTINGS SHALL BE PRESSURE RATED TO 250 PSI, MINIMUM. ALL COMPACT FITTINGS (C153/A21.53) SHALL BE PRESSURE RATED TO 350 PSI, MINIMUM.
7. INTERIOR LINING SHALL BE STANDARD THICKNESS CEMENT MORTAR LINING AND BITUMINOUS SEAL COAT, CONFORMING TO ANSI/AWWA C104/A21.4.
8. MECHANICAL AND PUSH-ON JOINTS SHALL BE RUBBER GASKETED, CONFORMING TO ANSI/AWWA C111/A21.11. MECHANICAL JOINT BOLTS AND NUTS SHALL CONFORM TO ASTM A307, GRADE B. DUCTILE IRON GLANDS SHALL BE PROVIDED WITH DUCTILE IRON PIPE.
9. PIPE JOINTS SHALL BE RESTRAINED UPSTREAM AND DOWNSTREAM OF FITTINGS IN ACCORDANCE WITH THE MANUFACTURER'S REQUIREMENTS OR THE TABLE SHOWN IN THE
DRAWINGS, WHICHEVER IS GREATER.
HYDROSTATIC TESTS
1. ALL PIPE SECTIONS TO BE PRESSURE TESTED SHALL BE SUBJECTED TO A HYDROSTATIC PRESSURE OF 150 PSI. THE DURATION OF EACH PRESSURE TEST SHALL BE FOR A PERIOD OF 2 HOURS. IF DURING THE TEST, THE INTEGRITY OF THE TESTED LINE IS IN QUESTION, THE COUNTY MAY REQUIRE A 6 HOUR PRESSURE TEST. THE BASIC PROVISIONS OF AWWA C-600 SHALL BE APPLICABLE.
2. AFTER COMPLETION OF THE PRESSURE TEST, A LEAKAGE TEST SHALL BE CONDUCTED TO DETERMINE THE QUANTITY OF WATER LOST BY LEAKAGE UNDER THE SPECIFIED TEST
PRESSURE. APPLICABLE PROVISIONS OF AWWA C600 SHALL APPLY.
ALLOWABLE LEAKAGE IN GALLONS PER HOUR FOR PIPELINE SHALL NOT BE GREATER THAN THAT DETERMINED BY THE FORMULA:
L = SD (P)2
133,200
NOTE:
L = ALLOWABLE LEAKAGE IN GALLONS PER HOUR
S = LENGTH OF PIPE TESTED, IN FEET.
D = NOMINAL DIAMETER OF THE PIPE IN INCHES.
P = AVERAGE TEST PRESSURE DURING LEAKAGE TEST IN POUNDS PER SQUARE INCH GAUGE.
LEAKAGE IS DEFINED AS THE QUANTITY OF WATER TO BE SUPPLIED IN THE NEWLY LAID PIPE OR ANY VALVED SECTION UNDER TEST, WHICH IS NECESSARY TO MAINTAIN THE SPECIFIED LEAKAGE TEST PRESSURE AFTER THE PIPE HAS BEEN FILLED WITH WATER AND THE AIR EXPELLED. SHOULD ANY TEST OF PIPE LAID DISCLOSE LEAKAGE GREATER THAN THAT ALLOWED, CONTRACTOR SHALL LOCATE AND REPLACE OR REPAIR THE DEFECTIVE JOINTS, PIPE OR VALVE UNTIL THE LEAKAGE FROM SUBSEQUENT TESTING IS WITHIN THE SPECIFIED ALLOWANCE.
DISINFECTION OF WATER MAINS
1. ALL DISINFECTION WORK SHALL BE ACCEPTABLE TO FDEP AND THE STATE DEPARTMENT OF HEALTH. IF ANY REQUIREMENTS OF THIS SECTION ARE IN CONFLICT WITH REQUIREMENTS OF THE AUTHORITY FOR DISINFECTION, THOSE OF THE AUTHORITY SHALL GOVERN. THE WATER MAIN DISINFECTION AND BACTERIOLOGICAL SAMPLING AND METHODS OF DISINFECTION FOR ALL WATER CONTAINMENT DEVICES AND PIPING SYSTEMS SHALL CONFORM TO AWWA C651.
2. SECTIONS OF PIPE TO BE DISINFECTED SHALL FIRST BE FLUSHED (FULL DIAMETER) TO REMOVE ANY SOLIDS OR CONTAMINATED MATERIAL THAT MAY HAVE BECOME LODGED IN THE PIPE. IF NO HYDRANT IS INSTALLED AT THE END OF THE MAIN, THEN A BLOW-OFF VALVE SHALL BE PROVIDED LARGE ENOUGH TO DEVELOP A VELOCITY OF AT LEAST 2.5 FEET PER SECOND IN THE MAIN.
ALL TAPS REQUIRED FOR CHLORINATION OR FLUSHING PURPOSE, OR FOR TEMPORARY OR PERMANENT RELEASE OF AIR SHALL BE PROVIDED FOR BY THE CONTRACTOR AS A PART OF THE CONSTRUCTION OF WATER MAINS. AFTER THE DISINFECTION, ALL SUCH TAPS SHALL BE SEALED TO THE SATISFACTION OF THE COUNTY.
3. BEFORE BEING PLACED INTO SERVICE, ALL NEW MAINS AND REPAIRED PORTIONS OF, OR EXTENSIONS TO EXISTING MAINS SHALL BE CHLORINATED SO THAT THE INITIAL CHLORINE RESIDUAL IS NOT LESS THAN 50/L MG AND THAT A CHLORINE RESIDUAL OF NOT LESS THAN 25 MG/L REMAINS IN THE WATER AFTER STANDING 24 HOURS IN THE PIPE.
4. CHLORINE MAY BE APPLIED AS A LIQUID CHLORINE (GAS-WATER MIXTURE), OR A MIXTURE OF WATER AND HIGH-TEST CALCIUM HYPOCHLORITE. CONTRACTOR SHALL ASSUME RESPONSIBILITY FOR SAFE HANDLING OF CHLORINE AND SHALL MEET REQUIREMENTS OF OSHA AND OTHER REGULATORY AGENCIES FOR SAFE HANDLING OF CHLORINE.
5. THE PREFERRED POINT OF APPLICATION OF THE CHLORINATING AGENT IS AT THE BEGINNING OF THE PIPE LINE EXTENSION OR ANY VALVED SECTION OF IT, AND THROUGH A CORPORATION STOP INSERTED IN THE PIPE. THE WATER INJECTOR FOR DELIVERING THE CHLORINE-BEARING WATER INTO THE PIPE SHOULD BE SUPPLIED FROM A TAP MADE ON THE PRESSURE SIDE OF THE GATE VALVE CONTROLLING THE FLOW INTO THE PIPE LINE EXTENSION. ALTERNATE POINTS OF APPLICATIONS MAY BE USED WHEN APPROVED OR
DIRECTED BY THE COUNTY.
6. TREATED WATER SHALL BE RETAINED IN THE PIPE AT LEAST 24 HOURS. AFTER THIS PERIOD, THE CHLORINE RESIDUAL AT PIPE EXTREMITIES AND AT OTHER REPRESENTATIVE
POINTS SHALL BE AT LEAST 25 MG/L.
7. IN THE PROCESS OF CHLORINATING NEWLY LAID PIPE, ALL VALVES OR OTHER APPURTENANCE SHALL BE OPERATED WHILE THE PIPELINE IS FILLED WITH THE CHLORINATING AGENT
AND UNDER NORMAL OPERATING PRESSURE.
8. FOLLOWING CHLORINATION, ALL TREATED WATER SHALL BE THOROUGHLY FLUSHED FROM THE NEWLY LAID PIPE WATER SAMPLES COLLECTED ON 2 SUCCESSIVE DAYS FROM THE TREATED PIPING SYSTEM, AS DIRECTED BY THE COUNTY, SHALL SHOW ACCEPTABLE BACTERIOLOGICAL RESULTS. ALL BACTERIOLOGICAL TESTING SHALL BE PERFORMED BY THE
COUNTY.
9. PROPER CHAIN OF CUSTODY PROCEDURES MUST BE FOLLOWED AND SAMPLES SHALL ONLY BEVCOLLECTED BY CERTIFIED LABORATORY PERSONNEL IN THE PRESENCE OF COUNTY PERSONNEL. COPIES OF TESTING RESULTS AND ALL RELATED CORRESPONDENCE WITH THE FLORIDA DEPARTMENT OF ENVIRONMENTAL REGULATIONS (F.D.E.P.) SHALL BE
SUBMITTED TO THE COUNTY.
Job No.
Date:
Checked by:
Designed by:
Drawn by:
Sheet No.No. DateNo. Date Revision Revision www.cphcorp.com1
8 SOUTHWEST STORAGE AND
REPUMP FACILITY
Debary, Florida V03120 4/22/2025
RG
VM/RG
GCM
C 2025
1117 East Robinson Street Orlando, FL 32801 Ph: 407.425.0452
CPH CONSULTING, LLC
A Full Service A & E Firm
Plans Prepared By:
State of Florida Licenses:
Engineer No. 3215
Surveyor No. LB7143 Architect. No. AA26000926 Landscape No. LC000298
Building Better Communities Together
100% SUBMITTAL
ROBERTO MARCOS GONZALEZ, P.E.
P.E. LIC. # 56875
Drawing name: J:\V03120\Civil\DWG\_DWG Fort Florida GST\V03120 General Notes.dwg Sep 11, 2025 - 7:56am dg.Holland
PRIOR TO THE START OF ANY CONSTRUCTION ACTIVITY, IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO NOTIFY THE VARIOUS UTILITIES AND TO MAKE THE NECESSARY ARRANGEMENTS FOR ANY RELOCATION TO THESE UTILITIES WITH THE OWNER OF THE UTILITY.
THE CONTRACTOR SHALL EXERCISE CAUTION WHEN CROSSING AN UNDERGROUND UTILITY, WHETHER SHOWN ON THE PLANS OR LOCATED BY THE UTILITY COMPANY. ANY DELAY OR INCONVENIENCE CAUSED TO THE CONTRACTOR BY THE RELOCATION OF VARIOUS UTILITIES
SHALL BE INCIDENTAL, WITH NO COMPENSATION FROM THE UTILITY OR THE COUNTY.
QUALITY CONTROL TESTING REQUIREMENTS
ALL TESTING RESULTS FOR NEW CONSTRUCTION SHALL BE PROVIDED TO THE OWNER. TESTING REQUIREMENTS ARE TO BE IN ACCORDANCE WITH THE UTILITIES' SPECIFICATIONS AND REQUIREMENTS. ALL TEST RESULTS SHALL BE PROVIDED (PASSING AND FAILING)
ON A REGULAR AND IMMEDIATE BASIS.
SHOP DRAWINGS
HOP DRAWINGS AND CERTIFICATIONS FOR ALL SYSTEM MATERIAL AND ALL STRUCTURES, ARE REQUIRED. THE CONTRACTOR SHALL SUBMIT SHOP DRAWINGS TO THE OWNER FOR APPROVAL PRIOR TO ORDERING THE MATERIALS REQUIRED FOR CONSTRUCTION.
NOTICE OF APPLICABILITY
WHEREVER STATE, COUNTY OR LOCAL STANDARD SPECIFICATIONS DIFFER FROM THOSE CONTAINED HEREIN: THE CONTRACTOR SHALL NOTIFY THE ENGINEER AND OWNER FOR CLARIFICATION. TYPICALLY THE MORE STRINGENT SHALL GOVERN.
PRE-CONSTRUCTION CONFERENCE
A PRE-CONSTRUCTION CONFERENCE SHALL BE REQUIRED WITH THE UTILITIES, ENGINEER, AND CONTRACTOR IN ATTENDANCE.
PRE-CONSTRUCTION CONFERENCE SHALL BE SCHEDULE PRIOR TO ANY CONSTRUCTION COMMENCEMENT. ALL JURISDICTIONAL PERMITS, AND CONNECTION FEES SHALL BE IN PLACE PRIOR TO PRE-CONSTRUCTION CONFERENCE SCHEDULING. THE UTILITY REQUIRES AT LEAST
72 HOURS NOTICE FOR SCHEDULING OF PRE-CONSTRUCTION CONFERENCE.
GENERAL PROJECT DATA
PERMITS AND PERMIT REQUIREMENTS
THE OWNER SHALL PROVIDE THE FDEP PERMIT FOR CONSTRUCTION OF PWS COMPONENTS, WATER MAIN, SANITARY SEWER GRINDER
PUMPS STATION AND FORCE MAIN.
THE CONTRACTOR SHALL BE RESPONSIBLE FOR PAYING FOR AND OBTAINING ALL OTHER REQUIRED STATE, COUNTY, COUNTY AND OTHER REGULATORY AGENCY PERMITS FOR THIS PROJECT. THE CONTRACTOR SHALL BE RESPONSIBLE FOR PICKING UP ALL REQUIRED PERMITS FROM THE CITY OF DEBARY BUILDING DIVISION USING THEIR CONTRACTOR'S LICENSE PRIOR TO THE START OF ANY CONSTRUCTION
ACTIVITIES.
EXISTING UTILITY LOCATIONS
SURVEY PROVIDED BY CPH SURVEYING.
INFORMATION PROVIDED IS BASED ON THE AVAILABLE DATA. THE CONTRACTOR SHALL FIELD VERIFY THE EXISTENCE AND LOCATION OF EXISTING UTILITIES PRIOR TO CONSTRUCTION AND NOTIFY THE COUNTY AND THE ENGINEER IF ANY CONFLICTS EXIST.
A SINGLE POINT UTILITY LOCATION SERVICE HAS BEEN SET UP FOR PARTICIPATING UTILITIES. CONTRACTOR IS TO CONTACT THE SUNSHINE STATE ONE CALL CENTER AT LEAST TWO (2) AND NO MORE THAN FIVE (5) WORKING DAYS PRIOR TO THE SPECIFIC CONSTRUCTION ACTIVITY FOR FIELD LOCATION. NOTE THAT NOT ALL UTILITIES PARTICIPATE IN THIS PROGRAM. CONTRACTOR SHOULD CONTACT NON-PARTICIPATING UTILITIES SEPARATELY FOR THEIR FIELD LOCATING OF FACILITIES. PER FLORIDA STATUTE 553.851, THE CONTRACTOR OR EXCAVATOR IS REQUIRED TO NOTIFY THE GAS COMPANY TWO (2) WORKING DAYS PRIOR TO STARTING EXCAVATION.
AS-BUILTS
SHALL BE PROVIDED BY THE CONTRACTOR TO THE ENGINEER TWO WEEKS PRIOR TO FINAL INSPECTION. ALL AS-BUILT DATA SHALL BE PROVIDED BY A FLORIDA LICENSED SURVEYOR, SIGNED, SEALED, AND DATED BY THE RESPONSIBLE PARTY. SEE INDIVIDUAL SECTIONS IN THE SPECIFICATIONS FOR ADDITIONAL AS-BUILT REQUIREMENTS. CONTRACTOR SHALL SUPPLY MEASURED RED-LINED DRAWINGS TO BE USED FOR FDEP CLEARANCE AND SEPARATE SURVEYED FINAL AS-BUILTS PRIOR TO FINAL INSPECTION.
GENERAL CONSTRUCTION REQUIREMENTS
OWNER/OPERATOR
VOLUSIA COUNTY WILL OWN, OPERATE AND MAINTAIN THE FACILITY AND ASSOCIATED COMPONENTS. THE CONTRACTOR SHALL BE EXPECTED TO MEET ALL THE REQUIREMENTS OF THE UTILITIES AND JURISDICTIONAL AGENCIES.
DRAINAGE
IT SHALL BE THE CONTRACTORS RESPONSIBILITY TO ENSURE ADEQUATE DRAINAGE IS PROVIDED TO THE EXISTING SITE DURING CONSTRUCTION. AT NO TIME SHALL THERE BE FLOODING IN THE CONTRACTORS WORK AREA AS A RESULT OF THE DEMOLITION OR
CONSTRUCTION
LIMITS OF DISTURBANCE
AT NO TIME SHALL THE CONTRACTOR DISTURB SURROUNDING PROPERTIES OR TRAVEL ON SURROUNDING PROPERTIES WITHOUT WRITTEN CONSENT FROM THE PROPERTY OWNER. REPAIR OR RECONSTRUCTION OF DAMAGED AREAS ON SURROUNDING PROPERTIES SHALL BE PERFORMED BY THE CONTRACTOR ON AN IMMEDIATE BASIS. ALL COSTS FOR REPAIRS SHALL BE THE
RESPONSIBILITY OF THE CONTRACTOR WITH NO COMPENSATION FROM THE OWNER.
CONTINUOUS ACCESS SHALL BE MAINTAINED FOR THE SURROUNDING PROPERTIES AT ALL TIMES DURING THE PROJECT.
FILL MATERIAL
FILL MATERIALS SHALL NOT CONTAIN ANY MUCK, STUMPS, ROOTS, BRUSH, VEGETATIVE MATTER, RUBBISH OR OTHER MATERIAL THAT WILL NOT COMPACT INTO A SUITABLE AND ENDURING BACKFILL. FILL SHALL BE CLEAN, NON-ORGANIC, GRANULAR MATERIAL
WITH NOT MORE THAN 10% PASSING THE NO. 200 SIEVE.
COMPACTION
FILL MATERIALS PLACED UNDER ROADWAYS AND DRIVEWAYS SHALL BE COMPACTED TO AT LEAST 98% OF THE MAXIMUM DENSITY AS SPECIFIED IN ASTM D1557. ALL OTHER FILL AREAS ARE TO BE COMPACTED TO AT LEAST 95% MAXIMUM DENSITY AS SPECIFIED IN ASTM D1557. FILL MATERIALS SHALL BE PLACED AND COMPACTED IN A MAXIMUM OF 12" LIFTS. THE CONTRACTOR SHALL PROVIDE THE ENGINEER AND OWNER WITH ALL (PASSING AND FAILING) TESTING RESULTS. RESULTS SHALL BE PROVIDED ON A TIMELY AND
REGULAR BASIS PRIOR TO CONTRACTOR'S PAY REQUEST SUBMITTAL.
CLEARING AND GRUBBING
THE CONTRACTOR SHALL BE RESPONSIBLE FOR CLEARING AND GRUBBING FOR THE CONSTRUCTION. SEE PLANS FOR LIMITS OF CLEARING AND GRUBBING. ALL AREAS TO BE CLEARED SHALL BE FIELD STAKED AND REVIEWED BY THE OWNER PRIOR TO ANY
CONSTRUCTION.
N
VICINITY MAP
1" = 400'
SOUTHWEST STORAGE
AND REPUMP FACILITY
PROJECT LOCATION
SECTION IS TAKEN.
DRAWING NUMBER ON WHICH
SECTION LETTER.
FOR THE PROJECT.
INDICATES DETAIL IS STANDARD
DETAIL IS TAKEN. DASH HERE
DRAWING NUMBER ON WHICH
DETAIL IS DRAWN.
DRAWING NUMBER ON WHICH
DETAIL NUMBER
DETAIL & SECTION
IDENTIFICATION
EXISTING PIPE (EXPOSED)
EXISTING PIPE (HIDDEN)
PROPOSED PIPE (EXPOSED)
PROPOSED PIPE (HIDDEN)
MECHANICAL JOINT
FLANGED JOINT
FLEXIBLE COUPLING WITH
FLANGED COUPLING ADAPTER
COUPLING
ELBOW UP
ELBOW DOWN
CONCENTRIC REDUCER
ECCENTRIC REDUCER
TEE DOWN
TEE UP
UNION
BLIND FLANGE
TYPICAL VALVE SYMBOLS (1)
GATE VALVE
BALL OR GLOBE VALVE
PLUG VALVE
CHECK VALVE
BUTTERFLY VALVE
SOLENOID VALVE
PRESSURE REGULATING VALVE
THRUST TIES
PIPE AND FITTING SYMBOL NOTES
SIMPLIFIED JOINT SYMBOL IS USED FOR ALL SINGLE LINE PIPING
SHOWN ON THE INTERIOR AND EXTERIOR PIPING DRAWINGS.
BOTH SIMPLIFIED AND COMPLEX JOINT REPRESENTATIONS MAY BE
SHOWN ON THE CONTRACT DRAWINGS.
UNLESS MODIFIED BY THE GENERAL PROJECT NOTES OR DETAILED
ON THE THE LAYOUT AND SCHEMATIC DRAWINGS, PIPE AND FITTING
JOINT REQUIREMENTS FOR THE VARIOUS PIPE MATERIALS ARE
DEFINED IN THE CONTRACT SPECIFICATIONS.
1.
2.
3.
THE CONTRACTOR IS RESPONSIBLE FOR PROVIDING THE REQUIRED
FITTINGS TO CONSTRUCT THE PROJECT AS DETAILED. THE
MATERIALS, COATINGS, AND LININGS SHALL BE AS REQUIRED BY
THE SPECIFICATIONS. FITTING MATERIALS SHALL MATCH THE PIPE
4.
AND PROCESS WHERE FITTING IS TO BE INSTALLED EXCEPT WHEN
SPECIFICALLY NOTED ON THE PLANS OR IN THE SPECIFICATIONS.
GENERAL PIPING SYMBOLS
CAP OR PLUG
PRESSURE GAUGE LOCATIONS
EXISTING PIPE (ABANDONED)
Abbreviation Legend:
MECHANICAL JOINT
90° BEND TEE
45° BEND 22-1/2° BEND
REDUCER WYE
TYPICAL PIPING SYMBOLS
OR C-900, C-905
DUCTILE IRON
OR STAINLESS STEEL
90° BEND TEE
45° BEND 22-1/2° BEND
CONCENTRIC REDUCER
(SIDE VIEW)
WYE
DUCTILE IRON
ECCENTRIC REDUCER
(SIDE VIEW)
FLANGED
2" PVC GLUE JOINT
90° BEND TEE
45° BEND 22-1/2° BEND
REDUCER
WYE
COUPLING ADAPTER
FLANGED FITTINGS
TYPICAL PIPING SYMBOLS
TYPICAL PIPING SYMBOLS
NOTES:
1. VALVES MAY BE DRAWN WITH DIFFERENT
JOINT CONNECTIONS (FLANGED SHOWN).
2. FITTINGS SHALL HAVE SAME PRESSURE
RATING AS PIPING USED.
Job No.
Date:
Checked by:
Designed by:
Drawn by:
Sheet No.No. DateNo. Date Revision Revision www.cphcorp.com1
8 SOUTHWEST STORAGE AND
REPUMP FACILITY
Debary, Florida V03120 4/22/2025
RG
VM/RG
GCM
C 2025
1117 East Robinson Street Orlando, FL 32801 Ph: 407.425.0452
CPH CONSULTING, LLC
A Full Service A & E Firm
Plans Prepared By:
State of Florida Licenses:
Engineer No. 3215
Surveyor No. LB7143 Architect. No. AA26000926 Landscape No. LC000298
Building Better Communities Together
100% SUBMITTAL
ROBERTO MARCOS GONZALEZ, P.E.
P.E. LIC. # 56875
Drawing name: J:\V03120\Civil\DWG\_DWG Fort Florida GST\V03120 Symbols.dwg Sep 02, 2025 - 11:06am dg.Holland
G-04SYMBOLS & ABBREVIATIONS
2.0 MG GROUND
STORAGE TANK
CL2
NO NO NO
NO
NO
NO
NC
NO
FM
NH3
PRE CHLORAMINE
GST DISCHARGE
RESIDUAL
SAMPLE TAP
NO
POST CHLORAMINE
DISCHARGE
RESIDUAL
SAMPLE TAP
NO NO
750 GPM
HSP No. 3
8" FIRE
STATION
SUPPLY
NC
NO NO
HAND GRAP
SAMPLE TAP
HAND GRAB
SAMPLE TAP
SWSRF
PROJECT LIMITS
SWSRF
PROJECT LIMITS
2" BLOW-OFF
ASSEMBLY
2" BLOW OFF
ASSEMBLY
PD-3C-6"
PS-3A-6"
PD-2C-6"
PS-2A-6"
PD-1C-6"
PS-1A-6"
DR-1-8"
N-1-16"
N-2-16"
F-3-16"
GS-1-24"
F-1-16"
BS-1-16"
N-3-16" (CV)
750 GPM
HSP No. 2
750 GPM
HSP No. 1
PIT
NO
D-1-16"
FUTURE
PUMP
PIT
ARV
FM
PD-3B-6" (CV)
ARVARV
INFLUENT
RESIDUAL
SAMPLE TAP
FM
F-2-16"
NONO
NC
H-1-6"
LEGEND
CHECK VALVE
GATE VALVE
ABOVE GROUND PIPE
FLOW METERFM
NORMALLY OPENNO
AMMONIANH3
CHLORINECL2
NORMALLY CLOSEDNC
BELOW GROUND PIPE
GALLONS PER MINUTE
HIGH SERVICE PUMP
SOUTH WEST STORAGE AND
REPUMP FACILITY
SWSRF
GPM
HSP
STATIC MIXER
FUTURE ABOVE GROUND PIPE
BACK PRESSURE SUSTAINING
SOLENOID VALVE
FIRE HYDRANT
PIT
VALVE ABBREVIATION
GST FILL LINEF
BYPASS STORAGE LINEBS
GST SUCTION LINEGS
PUMP SUCTION LINEPS
PUMP DISCHARGE LINEPD
NORMAL OPEN LINEN
DISCHARGE LINED
HYDRANT LINEH
REDUCE PRESSURE ZONERPZ
NAME - # - DIAMETER VALVE TAG
DRAIN LINEDR
REDUCE PRESSURE ZONE
BACK FLOW PREVENTER
RPZ BFP
PRESSURE
GAUGE TRANSMITTER
RPZ-1-2"
PD-2B-6" (CV) PD-1B-6" (CV)
DRAINAGE INLET
Job No.
Date:
Checked by:
Designed by:
Drawn by:
Sheet No.No. DateNo. Date Revision Revision www.cphcorp.com1
8 SOUTHWEST STORAGE AND
REPUMP FACILITY
Debary, Florida V03120 4/22/2025
RG
VM/RG
GCM
C 2025
1117 East Robinson Street Orlando, FL 32801 Ph: 407.425.0452
CPH CONSULTING, LLC
A Full Service A & E Firm
Plans Prepared By:
State of Florida Licenses:
Engineer No. 3215
Surveyor No. LB7143 Architect. No. AA26000926 Landscape No. LC000298
Building Better Communities Together
100% SUBMITTAL
ROBERTO MARCOS GONZALEZ, P.E.
P.E. LIC. # 56875
Drawing name: J:\V03120\Civil\DWG\_DWG Fort Florida GST\V03120 Flow Diagram.dwg Sep 02, 2025 - 11:07am dg.Holland
G-05PROCESS FLOW DIAGRAM
16" DIP SRF SUPPLY LINE
24" DIP GST
SUCTION LINE
16" HDPE16" HDPE
24" DIP HSP MANIFOLD
24" DIP HSP HEADER 24" DIP WATER SUPPLY
LINE TO HSP
16" DIP GST BYPASS LINE
16" DIP GST FILL LINE
16" DIP DISCHARGE LINE
24" DIP SW SRF
DISCHARGE LINE
16" DIP SW SRF BYPASS LINE
2" WATER SUPPLY
SERVICE METER TO SWSRF
16" PVC WM
16" x 3/4" TAPPING
SADDLE WITH
CORP STOP
FF EL 24.00
LWL EL 26.50
PAD EL. 23.00
MIN. OPERATING LEVEL
EL. 28.00
HIGH
SERVICE
PUMP No. 1
HIGH
SERVICE
PUMP No. 3
HIGH
SERVICE
PUMP No. 2
INLET RISER
EL 30.00
NH3CL2
EL 26.50
OUT LET
EL 24.50
FG EL 24.00
HWL EL 58.08
HYDRAULIC GRADE LINE
TOW EL 58.08
TOW
EL 146.00
TO DISTRIBUTION SYSTEM
AT SET PRESSURE - 65 PSI
ELEVATION
TOP OF WALL
LEGEND
EL =
TOW =
LOW WATER LEVEL LWL =
HIGH WATER LEVELHWL =
FINISHED FLOORFF =
FINISHED GRADEFG =
GROUND
STORAGE TANK
PRESSURE SUSTAINING VALVEPSV =
PRESSURE STEP DOWN
AFTER PSV EL 158.00 FT (60 PSI)
HSP VFD SET PRESSURE - 65 PSI (176.15 FT)
HEADLOSS = APPROXIMATE 12 FT
(FRICTION AND MINOR LOSSES)
FILL LINE
OVER
FLOW EL 58.33
FUTURE HIGH
SERVICE
PUMP
EL 26.50
FF EL 23.50
Job No.
Date:
Checked by:
Designed by:
Drawn by:
Sheet No.No. DateNo. Date Revision Revision www.cphcorp.com1
8 SOUTHWEST STORAGE AND
REPUMP FACILITY
Debary, Florida V03120 4/22/2025
RG
VM/RG
GCM
C 2025
1117 East Robinson Street Orlando, FL 32801 Ph: 407.425.0452
CPH CONSULTING, LLC
A Full Service A & E Firm
Plans Prepared By:
State of Florida Licenses:
Engineer No. 3215
Surveyor No. LB7143 Architect. No. AA26000926 Landscape No. LC000298
Building Better Communities Together
100% SUBMITTAL
ROBERTO MARCOS GONZALEZ, P.E.
P.E. LIC. # 56875
Drawing name: J:\V03120\Civil\DWG\_DWG Fort Florida GST\V03120 Hydrau Grade.dwg Sep 02, 2025 - 11:07am dg.Holland
G-06HYDRAULIC GRADE LINE
FORT FLORIDA ROAD
S 89°53'21" E (SP) 657.96'(C)
S
°2 2'
E (S
P)
1.
C
N
0°
'2 7"
W (S
P)
2.
C
N 89°55'29" W (SP) 658.33'(C)
THIS SURVEY IS NOT VALID WITHOUT SURVEY SHEETS 1 THROUGH 5 OF 5.
BOUNDARY AND
TOPOGRAPHIC SURVEYSECTIONS 8-TOWNSHIP 19 SOUTH-RANGE 30 EAST
CITY OF DEBARY, VOLUSIA COUNTY, FLORIDA
FORT FLORIDA ROAD
VOLUSIA COUNTY STORAGE & REPUMP FACILITY
N
050 50 100
Scale: 1" = 50'
Job No.
Approved By:
Checked By:
Field Crew:
Drawn By:
V03120
J. Watson J. Fleming L. Stoffel
P. Katrek C 2025Date: 9/8/2023
500 West Fulton Street Sanford, FL 32771 Ph: 407.322.6841
CPH, LLC
A Full Service A & E Firm
Plans Prepared By:
State of Florida License:
Surveyor No. LB7143www.cphcorp.com
Building Better Communities Together
Sheet No.
V1.1 Survey Sheet 2No. DateNo. Date Revision Revision
Drawing name: J:\V03120\Civil\DWG\_DWG Fort Florida GST\V03120 Survey.dwg Sep 02, 2025 - 11:07am dg.Holland
C-01
FORT FLORIDA ROAD
SSSS
TREE REMOVAL LIST
TREE TYPE DBH QTY
Maple Tree 5" 6 Maple Tree 6" 9 Maple Tree 7" 8 Maple Tree 8" 7 Maple Tree 9" 1 Maple Tree 10" 8 Maple Tree 11" 1 Maple Tree 12" 9 Maple Tree 13" 5 Maple Tree 14" 10 Maple Tree 15" 1 Maple Tree 16" 3 Maple Tree 18" 5 Maple Tree 20" 4 Maple Tree 30" 1 Oak Tree 7" 1 Oak Tree 10" 1 Palm Tree 6" 3 Palm Tree 7" 2 Palm Tree 8" 5 Palm Tree 9" 3 Palm Tree 10" 6 Palm Tree 12" 1 Palm Tree 13" 5 Palm Tree 14" 2 Palm Tree 15" 2 Palm Tree 16" 1 Palm Tree 20" 2 Palm Tree 22" 1 Pine Tree 38" 2
Unknown Tree 5" 1
C-02TREE REMOVAL PLAN
Graphic Scale in Feet
20 20 40
INSTALL FDOT SILT FENCE TYPE III
N
PROPERTY BOUNDARY
INSTALL FDOT SILT
FENCE TYPE III
TREE TO REMAIN
TREE TO BE REMOVE
TREE LEGEND:
PROPERTY BOUNDARY
TREE TO BE REMOVED AS A
PART OF FIRE STATION PROJECT
Job No.
Date:
Checked by:
Designed by:
Drawn by:
Sheet No.No. DateNo. Date Revision Revision www.cphcorp.com1
8 SOUTHWEST STORAGE AND
REPUMP FACILITY
Debary, Florida V03120 4/22/2025
RG
VM/RG
GCM
C 2025
1117 East Robinson Street Orlando, FL 32801 Ph: 407.425.0452
CPH CONSULTING, LLC
A Full Service A & E Firm
Plans Prepared By:
State of Florida Licenses:
Engineer No. 3215
Surveyor No. LB7143 Architect. No. AA26000926 Landscape No. LC000298
Building Better Communities Together
100% SUBMITTAL
ROBERTO MARCOS GONZALEZ, P.E.
P.E. LIC. # 56875
Drawing name: J:\V03120\Civil\DWG\_DWG Fort Florida GST\V03120 Tree Removal.dwg Sep 11, 2025 - 7:55am dg.Holland
W W
W
18 18 18
SSSS
W
W
1717.5
17.5
15.5
15.5
SS
SSSSSSSSSS
SI
TE
B
EN
C H
M A
R K
22 21
PROPOSED
STORM WATER POND
N
Graphic Scale in Feet
30 30 60
TIE INTO
FIRE STATION SWALE
FIRE STATION SITE
INSTALL SILT FENCE
23.00
PROPERTY BOUNDARY 4' WIDE SWALE
(3' OFF PROPERTY
BOUNDARY)
6' WIDE CONVAYANCE SWALE
PROPERTY BOUNDARY
3:1 SLOPE
4:1 SLOPE
2:1 SLOPE
4:1 SLOPE
4:1 SLOPE
4:1 SLOPE
4:1 SLOPE
PROPERTY BOUNDARY
6'
4:1 SLOPE
NOTE:
1. CONTRACTOR TO FOLLOW
RECOMMENDATIONS CONTAINED
WITHIN THE PROJECT GEOTECHNICAL
REPORT WHEN PERFORMING WORK
ON THE SW STORAGE AND REPUMP
FACILITY SITE.
INSTALL FDOT TYPE III
SILT FENCE
C-03 Sheet No.
6' WIDE
CONVAYANCE
SWALE
SOUTHWEST STORAGE SITE
Job No.
Date:
Checked by:
Designed by:
Drawn by:
Sheet No.No. DateNo. Date Revision Revision www.cphcorp.com1
8 SOUTHWEST STORAGE AND
REPUMP FACILITY
Debary, Florida V03120 4/22/2025
RG
VM/RG
GCM
C 2025
1117 East Robinson Street Orlando, FL 32801 Ph: 407.425.0452
CPH CONSULTING, LLC
A Full Service A & E Firm
Plans Prepared By:
State of Florida Licenses:
Engineer No. 3215
Surveyor No. LB7143 Architect. No. AA26000926 Landscape No. LC000298
Building Better Communities Together
100% SUBMITTAL
Drawing name: J:\V03120\Civil\DWG\_DWG Fort Florida GST\V03120 Grading Plans.dwg Sep 11, 2025 - 7:57am dg.Holland
ALLEN CLAYTON LANE, JR., P.E.
P.E. LIC. # 60144
D-4C-05
B
D-4
A
C-05
FO
R
T
FL
O R
ID
A
R O
AD
4:1 SLOPE
OVERALL GRADING PLAN
SEE DEBARY FIRE STATION
PLANS FOR TREE REMOVAL
W W
W
SSSS
W
W
SS
SSSSSSSSSS
CONNECTION TO
FORT FLORIDA ROAD C-04
GENERATOR PAD
TRANSFORMER PAD
ELECTRICAL ROOM
CHLORINE TANK
AMMONIA TANK
PROPOSED LEGEND:
BURIED PIPE
ABOVE GROUND PIPE
SECURE IT ROOM4
HSP ROOM7
Graphic Scale in Feet
30 30 60
N
FO
R
T
FL
O R
ID
A
R O
AD
STORM
WATER POND
BOLLARD (TYP.)
PROPERTY BOUNDARY
FLOW
METER
ASSEMBLY
FIRE HYDRANT
(TYP.)
24" DIP DISCHARGE
NH3
CL2
NO
NC
NO
NC
NO
24'
LIGHT
POLE (TYP.)
WETLAND
WATER MAIN TO BE CONSTRUCTED
PRIOR TO SOUTHWEST SRF
SEE SITE SPECIFIC NOTE 1
PROPERTY BOUNDARY
16" DIP DISCHARGE
NC
NO
NO
NO
16" DIP GST FILL LINE
REDUCER
FUTURE CITY OF DEBARY
FIRE STATION
CHEMICAL
INJECTION
ASSEMBLY
24' WIDE
ASPHALT
DRIVEWAY
24" DIP GST
SUCTION LINE
GATE VALVE
16" x 24" REDUCER
2.0 MG GST
24' WIDE
CONC
DRIVEWAY
NO
CHECK
VALVE
ASSEMBLY
BOLLARD (TYP.)
BACKFLOW
PREVENTER
AND SERVICE
METER
ASSEMBLY
Job No.
Date:
Checked by:
Designed by:
Drawn by:
Sheet No.No. DateNo. Date Revision Revision www.cphcorp.com1
8 SOUTHWEST STORAGE AND
REPUMP FACILITY
Debary, Florida V03120 4/22/2025
RG
VM/RG
GCM
C 2025
1117 East Robinson Street Orlando, FL 32801 Ph: 407.425.0452
CPH CONSULTING, LLC
A Full Service A & E Firm
Plans Prepared By:
State of Florida Licenses:
Engineer No. 3215
Surveyor No. LB7143 Architect. No. AA26000926 Landscape No. LC000298
Building Better Communities Together
100% SUBMITTAL
ROBERTO MARCOS GONZALEZ, P.E.
P.E. LIC. # 56875
Drawing name: J:\V03120\Civil\DWG\_DWG Fort Florida GST\V03120 Conn To FL Rd.dwg Sep 02, 2025 - 11:09am dg.Holland
NO
NO
SOLENOID CONTROLLED BACK
PRESSURE SUSTAINING VALVE
AND FLOW METER ASSEMBLY
CONNECT TO
16" GATE VALVE
10' UTILITY
EASEMENT
10' DRAINAGE
EASEMENT
16" HDPE WATER MAIN
TO BE CONSTRUCTED
PRIOR TO SOUTHWEST SRF
SEE SITE SPECIFIC NOTE 1 8" X 16" TEE
8" GATE VALVE
5' POWER
EASEMENT RESTRAINED JOINT
CAP WITH 2" TAP AND
2" ASSEMBLY BLOW-OFF
SEE SITE SPECIFIC NOTE 2
5' POWER
EASEMENT PROPOSED
POWER POLE
16" HDPE WATER MAIN
TO BE CONSTRUCTED
PRIOR TO SOUTHWEST SRF
SEE SITE SPECIFIC NOTE 1
TANK 15'
CONSTRUCTION
BUFFER
RESTRAINED JOINT
CAP WITH 2" TAP AND
2" ASSEMBLY BLOW-OFF
SEE SITE SPECIFIC NOTE 2
OPERATIONS
BUILDING
HOSE BIBB
(TYP.)
5 ' UTILITY
EASEMENT
CONNECT TO
16" GATE VALVE
CONNECT TO
2" FM GATE VALVE
16" DIP GST
BY-PASS
2" PVC
WATER
LINE
PROPOSED 6' HIGH
CHAIN LINK FENCE
SILT FENCE
6' CHAIN LINK FENCEX
O
SITE SPECIFIC NOTES:
1. OFF-SITE 16-INCH WM (BY OTHERS).
2. CONTRACTOR TO REMOVE 2-INCH BLOW OFF ASSEMBLY AND CONNECT NEW 16-INCH LINE TO EXISTING.
3. CONTRACTOR TO CUT EDGE OF EXISTING ASPHALT AND TIE NEW ASPHALT TO EXISTING.
4. CONTRACTOR TO COORDINATE WITH CITY OF DEBARY WHEN PERFORMING WORK ON THE FIRE STATION PROPERTY.
5. REINFORCED CONCRETE DRIVEWAY WITH FIBER MESH.
SEE SITE SPECIFIC
NOTES 3 & 4
ROADWAY LEGEND:
CONCRETE
ASPHALT
24' WIDE BLACK
CANTILEVER
ROLL GATE
16" x 2" TAPPING
SADDLE WITH
CORP STOP
2" POLY
FORCE MAIN
16" DIP SWSRF SUPPLY LINE
16" x 24"
REDUCER
SEE
NOTE 5
SEE DEBARY FIRE STATION
PLANS FOR TREE REMOVAL
16" x 3/4" TAPPING
SADDLE WITH
CORP STOP
SSSS
22 21
SITE FINAL GRADING PLAN
Graphic Scale in Feet
20 20 40
PROPERTY BOUNDARY
PROPERTY BOUNDARY
GENERATOR
CONCRETE SLAB
EL. 23.00
TRANSFORMER
CONCRETE SLAB
EL. 23.00
2.0 MG GST
FF EL. 24.00
22.95
23.0 22.80
22.80
22.80
22.80
22.70
23.00
23.10 HP
23.10 HP
22.85
22.80
22.80
22.80
22.80 22.80
23.00
22.80
22.80
22.80
22.95
22.85
22.85
22.85
22.80
22.80 23.00 HP
23.00
23.00
23.00
23.00
22.80
23.00
23.00
MES INV. 14.00
OPERATION
BUILDING
FF EL. 23.50
CONTROL STRUCTURE
(SEE DETAIL OS-1,
SHEET D-4)
STORM WATER POND
(CONSTRUCTED
AS PART OF MASS
GRADING PLAN)
TYPE C INLET
RETICULINE GRATE
RIM 21.00
W. INV. 15.25
22.75
24' WIDE
CONCRETE
DRIVWAY
N
TANK 15'
CONSTRUCTION
BUFFER
NOTES:
1. CONTRACTOR TO FOLLOW RECOMMENDATIONS
CONTAINED WITHIN THE PROJECT
GEOTECHNICAL REPORT WHEN PERFORMING
WORK ON THE SW STORAGE AND REPUMP
FACILITY SITE.
2. CONTRACTOR TO CONFIRM THE ELEVATION AT
EXTERIOR EQUIPMENT PADS AND SIDEWALKS
WITH COUNTY AND CIVIL ENGINEER AFTER
BUILDING IS CONSTRUCTED.
SOLENOID CONTROLLED
BACK PRESSURE
SUSTAINING VALVE AND
FLOW METER ASSEMBLY
CONCRETE SLAB EL. 23.10
FLOW METER,
BACKFLOW
PREVENTER AND
SERVICE METER
ASSEMBLY
CONCRETE SLAB
EL. 23.50
21.5522.29
21.60
22.00
22.29 22.00
S-1
S-4
S-2
S-3
S-1
STORM STRUCTURE SCHEDULE
TYPE D INLET
CAST IRON GRATE
RIM 22.60
N. INV. 18.30
E. INV. 14.95
W. INV.14.95
S-2
S-3 S-4
TYPE C INLET
RETICULINE GRATE
RIM 21.00
E. INV. 16.75
TYPE D INLET
CAST IRON GRATE
RIM 22.55
E. INV. 14.50
W. INV.16.60
S. INV. 14.50
PIPE RUN LENGTH
(L.F.)
PIPE DIA.
(IN.)
SLOPE
STORM PIPE SCHEDULE
S-1 TO S-2 117 15" RCP
S-2 TO S-4 134 18" RCP
S-3 TO S-4 30 15" RCP
0.26
0.50 0.34
PROPOSED STORM SEWER WITH INLET
EXISTING CONTOUR LINE
PROPOSED CONTOUR LINE
56.52 x
PROPOSED STORM INLET NUMBER
PROPOSED SPOT ELEVATION
EXISTING ELEVATION
EASEMENT LINE
PROPOSED FINISH FLOOR ELEVATION
60.00
F.F. EL. 23.50
S-1
LEGEND
PERIMETER SWALE, THE STORM WATER POND,
OUTFALL STRUCTURE AND PIPE HAVE BEEN
COMPLETED AS A PART OF THE MASS GRADING
FOR THE SITE. CONTRACTOR TO VERIFY THE
EXISTING PERIMETER SWALES, STORM WATER
POND, OUTFALL STRUCTURE AND PIPE ARE
PROPERLY MAINTAINED DURING CONSTRUCTION.
SITE SPECIFIC NOTES:
23.0
22.70
22.75
22.70 23.00 HP
23.00 HP
23.10 HP
23.00
C-05
S-4 TO MES 160 24" RCP 0.31
INSTALL SILT FENCE
Job No.
Date:
Checked by:
Designed by:
Drawn by:
Sheet No.No. DateNo. Date Revision Revision www.cphcorp.com1
8 SOUTHWEST STORAGE AND
REPUMP FACILITY
Debary, Florida V03120 4/22/2025
RG
VM/RG
GCM
C 2025
1117 East Robinson Street Orlando, FL 32801 Ph: 407.425.0452
CPH CONSULTING, LLC
A Full Service A & E Firm
Plans Prepared By:
State of Florida Licenses:
Engineer No. 3215
Surveyor No. LB7143 Architect. No. AA26000926 Landscape No. LC000298
Building Better Communities Together
100% SUBMITTAL
Drawing name: J:\V03120\Civil\DWG\_DWG Fort Florida GST\V03120 Grading Plans.dwg Sep 02, 2025 - 11:09am dg.Holland
ALLEN CLAYTON LANE, JR., P.E.
P.E. LIC. # 60144
INSTALL SILT FENCE
CHECK VALVE ASSEMBLY
CONCRETE SLAB EL. 23.00
CHEMICAL INJECTION
ASSEMBLY CONCRETE
SLAB EL. 23.00
S-5
S-5
TYPE C INLET
CAST IRON GRATE
RIM 22.70
S. INV. 18.45
CONCRETE
WALKWAY SLAB
23.00
23.00
22.70
22.85
22.70
22.95
23.00
22.90
22.90
TO
C
23.35
EO
P 23.00
23.00 H
P
S-5 TO S-2 17 15" RCP 0.88
23.10 23.10
23.00
22.95
TOTAL SITE AREA: 3.02 AC
TOTAL IMPERVIOUS AREA: 0.692 AC
PROVIDED TREATMENT VOLUME: 1,644FT ^3 (0.38 AF)
TOTAL POND AVAILABLE STORAGE VOLUME: 5,2497 FT ^3 (1.21AF)
TOTAL POND VOLUME: 1.75 AF
DESIGN STORM EVENT: 100 YR/24HR (11.5")
STORMWATER TREATMENT
TO
C
23.35
EO
P 22.90
23.45
23.45
TO
C
23.35
EO
P 22.80
CONCRETE SLAB
EL. 23.00
23.50 23.50
23.1023.10
23.50
23.50 23.50
23.00
0S-1
MES WITH RIP RAP
S. INV. 17.50
OS-1 TO MES 30 15" RCP 1.67
SS
C-06YARD PIPING PLAN
Graphic Scale in Feet
20 20 40
TANK 15'
CONSTRUCTION
BUFFER
FIRE HYDRANT
(TYP.)
INSTALL FDOT SILT FENCE TYPE III
N
BOLLARD
8' O.C. (TYP.)
GENERATOR
CONCRETE SLAB
SEE SITE
SPECIFIC NOTES 4
TRANSFORMER CONCRETE SLAB
TO BE INSTALL PER FPL REQUIREMENT
AS
PH
AL
T
D R
IV
EW
AY
CHECK VALVE
ASSEMBLY
(SEE DETAIL
ON M-13)
BACKFLOW
PREVENTER
AND SERVICE
METER ASSEMBLY
16" DIP DISCHARGE
LIGHT
POLE (TYP.)
5' UTILITY
EASEMENT
PROPERTY BOUNDARY
INSTALL SILT…
This is the start of the file's text. The full file is on GovTribe.