Vol 1-Specs v2.pdf
PDF 4 MB Posted
- Solicitation number
- 36C25621R0112
About this file
This is a presolicitation notice for a project to replace the roof and HVAC system for Building 3 at the Alexandria VA Health Care System in Pineville, Louisiana. The project cost range is between $5 million and $10 million.
The notice establishes this as a 100% set-aside for Service-Disabled Veteran Owned Small Businesses. Interested offerors must be registered and verified as an SDVOSB in the Vendor Information Pages database and System for Award Management by the time of proposal submission. The prime contractor must perform at least 15% of on-site work costs using its own employees or those of other eligible SDVOSBs for general construction, or 25% for special trade work.
A request for proposal will be issued on or shortly after June 15, 2021 on beta.SAM.gov. Questions are due by the cutoff specified in the RFP. A site visit is tentatively scheduled for June 22, 2021. The contracting officer is Gina Roach and point of contact is Jennings Herbst.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C25621R0112 0001.docx | DOCX document | |
| BLDG 3 Site Visit Information.pdf | ||
| WDLA202110051 04302021.txt | TXT text file | |
| 36C25621R0112.docx | DOCX document | |
| EXHIBIT F REQUEST FOR INFORMATION FORM.docx | DOCX document | |
| Vol 2-Specs.pdf | ||
| ACM and LeadReports.pdf | ||
| Drawings volume 2.pdf | ||
| Drawings Volume 1.pdf | ||
| EXHIBIT D CONTRACTOR EVALUATION FORM CONSTRUCTION SAFETY.docx | DOCX document | |
| EXHIBIT B PAST AND PRESENT PERFORMANCE QUESTIONNAIRE.docx | DOCX document | |
| EXHIBIT E SURETY FORM.docx | DOCX document | |
| J_A 502-19-102 (BC Signed) v1_Redacted.pdf | ||
| EXHIBIT A PERFORMANCE RELEVANCY SURVEY.docx | DOCX document | |
| EXHIBIT G RETURNABLES.docx | DOCX document | |
| Vendor Request Form.xlsx | XLSX spreadsheet | |
| Project Risk Assessment Replace Roof and HVAC building 3.pdf | ||
| EXHIBIT C SUBCONTRACTOR INFORMATION AND CONSENT.docx | DOCX document | |
| VA10091 FMS Vendor Request Form EFT.pdf | ||
| SOW-04052021.docx | DOCX document |
Show all 20
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Building 3 – Replace Roof and HVAC at the
Alexandria VA Medical Center Alexandria, Louisiana
Final Design Submittal Specifications - Vol. 1
12 February 2021 Project Number: 502-19-102
Building 3 – Replace Roof & HVAC, Project No. 502-19-102 12-01-20 Alexandria VAMC, Alexandria, LA
00 01 10-1
DEPARTMENT OF VETERANS AFFAIRS
VHA MASTER SPECIFICATIONS
TABLE OF CONTENTS
Section 00 01 10
SECTION NO. DIVISION AND SECTION TITLES DATE
DIVISION 00 - SPECIAL SECTIONS
00 01 15 List of Drawing Sheets 07-15
DIVISION 01 - GENERAL REQUIREMENTS
01 00 00 General Requirements 03-20 01 32 16.15 Project Schedules (Small Projects – Design/Bid/Build 03-20 01 33 23 Shop Drawings, Product Data, and Samples 05-17 01 35 26 Safety Requirements 02-17 01 42 19 Reference Standards 09-19 01 45 00 Quality Control 03-19 01 45 29 Testing Laboratory Services 11-18 01 45 35 Special Inspections 09-20 01 57 19 Temporary Environmental Controls 01-11 01 58 16 Temporary Interior Signage 07-15 01 74 19 Construction Waste Management 09-13 01 81 13 Sustainable Construction Requirements 10-17 01 91 00 General Commissioning Requirements 10-15
DIVISION 02 – EXISTING CONDITIONS
02 41 00 Demolition 08-17 02 82 11 Traditional Asbestos Abatement 04-19
DIVISION 03 – CONCRETE
03 30 00 Cast-in-Place Concrete 07-19
DIVISION 04 – MASONRY
DIVISION 05 – METALS
05 12 00 Structural Steel Framing 11-18 05 50 00 Metal Fabrications 08-18
DIVISION 06 – WOOD, PLASTICS AND COMPOSITES
06 10 00 Rough Carpentry 10-17 06 20 00 Finish Carpentry 08-16
DIVISION 07 - THERMAL AND MOISTURE PROTECTION
00 01 10-2
07 01 50.19 Preparation for Re-Roofing 02-16 07 22 00 Roof and Deck Insulation 02-16 07 32 13 Clay Roof Tiles & Shingles 02-16 07 54 23 Thermoplastic Polyolefin (TPO) Roofing 08-16 07 60 00 Flashing and Sheet Metal 07-14 07 84 00 Firestopping 02-16 07 92 00 Joint Sealants 10-17
DIVISION 08 - OPENINGS
08 11 13 Hollow Metal Doors and Frames 08-16 08 14 00 Interior Wood Doors 02-16 08 31 13 Access Doors and Frames 02-16 08 51 13 Aluminum Windows 02-16 08 71 00 Door Hardware 10-19 08 90 00 Louvers and Vents 05-15
DIVISION 09 – FINISHES
09 06 00 Schedule for Finishes 04-15 09 22 16 Non-Structural Metal Framing 06-18 09 23 00 Gypsum Plastering 10-15 09 24 00 Portland Cement Plastering 10-15 09 29 00 Gypsum Board 06-18 09 51 00 Acoustical Ceilings 12-18 09 65 13 Resilient Base and Accessories 02-16 09 65 19 Resilient Tile Flooring 05-18 09 68 00 Carpeting 10-15 09 91 00 Painting 01-16
DIVISION 10 – SPECIALTIES
DIVISION 11 – EQUIPMENT
DIVISION 12 – FURNISHINGS
DIVISION 13 - SPECIAL CONSTRUCTION
13 05 41 Seismic Restraint Requirements for Non-Structural
Components 01-14
DIVISION 14– CONVEYING EQUIPEMENT
DIVISION 21- FIRE SUPPRESSION
21 13 13 Wet-Pipe Sprinkler Systems 06-15
DIVISION 22 – PLUMBING
22 05 11 Common Work Results for Plumbing 07-16
00 01 10-3
22 05 19 Meters and Gages for Plumbing Piping 09-15 22 05 23 General-Duty Valves for Plumbing Piping 09-15 22 07 11 Plumbing Insulation 09-19 22 11 00 Facility Water Distribution 11-19 22 13 00 Facility Sanitary and Vent Piping 09-15 22 33 00 Electric Domestic Water Heaters 09-15
DIVISION 23 – HEATING, VENTILATING, AND AIR
CONDITIONING (HVAC)
23 05 11 Common Work Results for HVAC 08-17 23 05 12 General Motor Requirements for HVAC and Steam
Generation Equipment 08-17
23 05 41 Noise and Vibration Control for HVAC Piping and Equipment
02-15
23 05 93 Testing, Adjusting, and Balancing for HVAC 02-15 23 07 11 HVAC and Boiler Plant Insulation 02-15 23 08 00 Commissioning of HVAC Systems 11-16 23 09 23 Direct-Digital Control System for HVAC 09-11 23 21 13 Hydronic Piping 08-17 23 21 23 Hydronic Pumps 08-17 23 22 13 Steam and Condensate Heating Piping 08-17 23 22 23 Steam Condensate Pumps 08-17 23 25 00 HVAC Water Treatment 02-15 23 31 00 HVAC Ducts and Casings 03-13 23 34 00 HVAC Fans 02-15 23 36 00 Air Terminal Units 02-15 23 37 00 Air Outlets and Inlets 02-15 23 40 00 HVAC Air Cleaning Devices 02-12 23 73 00 Indoor Central-Station Air-Handling Units 04-11 23 82 16 Air Coils 04-11
DIVISION 25 – INTEGRATED AUTOMATION
25 10 10 Advanced Utility Metering System 02-10
DIVISION 26 – ELECTRICAL
26 05 11 Requirements for Electrical Installations 01-16 26 05 19 Low-Voltage Electrical Power Conductors and Cables 01-17 26 05 26 Grounding and Bonding for Electrical Systems 01-17 26 05 33 Raceway and Boxes for Electrical Systems 01-18 26 05 73 Overcurrent Protective Device Coordination Study 01-18 26 24 16 Panelboards 01-18 26 29 11 Motor Controllers 26 29 21 Enclosed Switches and Circuit Breakers 01-17
DIVISION 27 – COMMUNICATIONS
DIVISION 28 – ELECTRONIC SAFETY AND SECURITY
00 01 10-4
28 31 00 Fire Detection and Alarm 10-11
DIVISION 31 – EARTHWORK
DIVISION 32 – EXTERIOR IMPROVEMENTS
DIVISION 33 – UTILITIES
DIVISION 34 – TRANSPORTATION
DIVISION 48 – Electrical Power Generation
*** END ***
Building 3 – Replace Roof & HVAC, Project No. 502-19-102 05-01-20
00 01 15 - 1
SECTION 00 01 15
LIST OF DRAWINGS
The drawings listed below accompanying this specification form a part of the contract.
DRAWING NO. TITLE
GENERAL
G001 COVER SHEET
G002 LEGENDS, ABBREVIATIONS AND NOTES
G003 LIFE SAFETY
ARCHITECTURAL
AS101 SITE STAGING PLAN
AD100 BASEMENT PLAN – EXIST-DEMO
AD 101 FIRST FLOOR RCP – EXIST-DEMO
AD102 SECOND FLOOR RCP – EXIST-DEMO
AD103 THIRD FLOOR RCP – EXIST-DEMO
AD104 ATTIC FLOOR RCP – EXIST-DEMO
AD105 ROOF PLAN – EXIST-DEMO
AD106 CONNECTOR TO BUILDING 2 – EXIST-DEMO
AD107 CONNECTOR TO BUILDING 4 – EXIST-DEMO
A100 BASEMENT FLOOR PLAN
A101 FIRST FLOOR PLAN
A102 SECOND FLOOR PLAN
A103 THIRD FLOOR PLAN
A104 ATTIC PLAN
A110 BASEMENT RCP
A111 FIRST FLOOR RCP
A112 SECOND FLOOR RCP
A113 THIRD FLOOR RCP
A114 ATTIC RCP
A121 ROOF PLAN – BUILDING 3
A122 BUILDING 3 CONNECTOR TO BUILDING 2 PLANS
A123 BUILDING 3 CONNECTOR TO BUILDING 4 PLANS
A201 EXTERIOR ELEVATIONS – BUILDING 3
00 01 15 - 2
A202 EXTERIOR ELEVATIONS – BUILDING 3
A301 BUILDING SECTION
A501 DETAILS
A502 DORMER DETAILS
A601 ROOM FINISH SCHEDULE
ABATEMENT
AB001 FIRST AND SECOND FLOOR ABATEMENT PLAN
AB002 THIRD FLOOR ABATEMENT PLAN
STRUCTURAL
S001 STRUCTURAL NOTES
S002 STRUCTURAL NOTES
S101 FOUNDATION PLAN
S102 TYPICAL FLOOR FRAMING PLAN
S103 ATTIC FLOOR FRAMING PLAN
S301 CONCRETE DETAILS
S501 STEEL DETAILS
FIRE PROTECTION
F001 LEGENDS, GENERAL NOTES, AND DETAILS
FD101 FIRST FLOOR DEMOLITION PLAN
FD102 SECOND FLOOR DEMOLITION PLAN
FD103 THIRD FLOOR DEMOLITION PLAN
FD104 ATTIC DEMOLITION PLAN
FP101 FIRST FLOOR NEW WORK PLAN
FP102 SECOND FLOOR NEW WORK PLAN
FP103 THIRD FLOOR NEW WORK PLAN
FP104 ATTIC NEW WORK PLAN
PLUMBING
P-001 GENERAL NOTES, LEGENDS, ABBREVIATIONS
PL101 BASEMENT DEMOLITION WATER PIPING PLAN
PL102 BASEMENT NEW WORK WATER PIPING PLAN
00 01 15 - 3
MECHANICAL
M001 LEGEND & GENERAL NOTES
M002 SCHEDULES
M003 SCHEDULES
MD101 FIRST FLOOR DEMOLITION DUCT PLAN
MD102 SECOND FLOOR DEMOLITION DUCT PLAN
MD103 THIRD FLOOR DEMOLITION DUCT PLAN
MD104 ATTIC DEMOLITION DUCT PLAN
MD105 BASEMENT DEMOLITION PIPE PLAN
MD106 FIRST FLOOR DEMOLITION PIPE PLAN
MD107 SECOND FLOOR DEMOLITION PIPE PLAN
MD108 THIRD FLOOR DEMOLITION PIPE PLAN
MD109 DEMOLITION CONNECTOR FLOOR PLANS
MH101 FIRST FLOOR NEW WORK DUCTWORK PLANS
MH102 SECOND FLOOR NEW WORK DUCTWORK PLANS
MH103 THIRD FLOOR NEW WORK DUCTWORK PLANS
MH104 ATTIC NEW WORK PLANS
MH105 SECTIONS
MP101 BASEMENT NEW WORK PIPING PLAN
MP102 FIRST FLOOR NEW WORK PIPING PLANS
MP103 SECOND FLOOR NEW WORK PIPING PLANS
MP104 THIRD FLOOR NEW WORK PIPING PLANS
MP105 NEW WORK CONNECTOR FLOOR PLANS
M501 DETAILS
M502 DETAILS
M503 DETAILS
M601 CONTROLS SCHEMATICS
M602 SEQUENCE OF OPERATION
ELECTRICAL
E001 LEGENDS & NOTES
ED101 BASEMENT & 1ST FLOOR DEMOLITION PLANS
ED102 2ND, 3RD, & ATTIC DEMOLITION PLANS
EL101 LIGHTING PLANS
00 01 15 - 4
EL102 LIGHTING PLANS
EP101 BASEMENT EQUIPMENT POWER PLAN
EP 102 EQUIPMENT POWER PLANS
EP601 POWER RISER DIAGRAM AND SCHEDULES
- - - END - - -
00 01 15 - 5
This Page is Blank.
00 01 15 - 6
This Page is Blank.
Building 3 – Replace Roof & HVAC, Project No. 502-19-102 03-01-20 i
SECTION 01 00 00
GENERAL REQUIREMENTS
TABLE OF CONTENTS
1.1 SAFETY REQUIREMENTS
1.2 GENERAL INTENTION
1.3 STATEMENT OF BID ITEM(S)
1.4 SPECIFICATIONS AND DRAWINGS FOR CONTRACTOR
1.5 CONSTRUCTION SECURITY REQUIREMENTS
1.6 OPERATIONS AND STORAGE AREAS
1.7 ALTERATIONS
1.8 DISPOSAL AND RETENTION
1.9 PROTECTION OF EXISTING VEGETATION, STRUCTURES, EQUIPMENT,
UTILITIES, AND IMPROVEMENTS
1.10 RESTORATION
1.11 PHYSICAL DATA
1.14 AS-BUILT DRAWINGS
1.15 WARRANTY MANAGEMENT
1.16 USE OF ROADWAYS
1.18 TEMPORARY USE OF MECHANICAL AND ELECTRICAL EQUIPMENT
1.19 TEMPORARY USE OF EXISTING ELEVATORS
1.21 TEMPORARY TOILETS
1.22 AVAILABILITY AND USE OF UTILITY SERVICES
1.23 NEW TELEPHONE EQUIPMENT
1.24 TESTS
1.25 INSTRUCTIONS
1.27 RELOCATED EQUIPMENT & ITEMS
1.29 CONSTRUCTION SIGN
1.30 SAFETY SIGN
1.31 PHOTOGRAPHIC DOCUMENTATION
1.32 FINAL ELEVATION Digital Images
1.33 HISTORIC PRESERVATION
ii
01 00 00 -1
SECTION 01 00 00
GENERAL REQUIREMENTS
1.1 SAFETY REQUIREMENTS
Refer to section 01 35 26, SAFETY REQUIREMENTS for safety and infection control requirements.
1.2 GENERAL INTENTION
A. Contractor shall completely prepare site for building operations, including demolition and removal of existing structures, and furnish labor and materials and perform work for the replacement of the roof and HVAC for Building 3 as required by drawings and specifications.
B. Offices of Toland Mizell Molnar, Clark-Nexsen, Innovative Engineering
Inc., Durbin Environmental Consultants, as Architect-Engineers, will render certain technical services during construction. Such services shall be considered as advisory to the Government and shall not be construed as expressing or implying a contractual act of the Government without affirmations by Contracting Officer or his duly authorized representative.
C. Before placement and installation of work subject to tests by testing laboratory retained by Department of Veterans Affairs, the Contractor shall notify the COR in sufficient time to enable testing laboratory personnel to be present at the site in time for proper taking and testing of specimens and field inspection. Such prior notice shall be not less than three work days unless otherwise designated by the COR.
D. All employees of general contractor and subcontractors shall comply with VA security management program and obtain permission of the VA police, be identified by project and employer, and restricted from unauthorized access.
1.3 STATEMENT OF BID ITEM(S)
A. ITEM I, GENERAL CONSTRUCTION: Work includes general construction, alterations, grading, drainage, necessary removal of existing structures and construction and certain other items, in phases as indicated in the construction documents.
01 00 00 -2
ITEM II, Electrical Work: Work includes all labor, material, equipment and supervision to perform the required electrical construction work on this project.
ITEM III, Mechanical Work: Work includes all labor, material, equipment and supervision to perform the required Mechanical construction work on this project.
B. ALTERNATE NO.1: Delete replacing the ACT in Connector 2 on the 2nd and
3rd floors.
C. ALTERNATE NO. 2: Delete replacing the radiators in the Building 4 connector on the 1st floor.
D. ALTERNATE NO. 3: Delete replacing the radiators in the Building 2 connector on the 1st, 2nd and 3rd floor.
E. ALTERNATE NO. 4: Delete painting all interior walls and plaster ceilings of Building 3, Building 2 connector and Building 4 connector/connector vestibule.
F. ALTERNATE NO. 5: Delete the new water heater.
G. BID Line Items
1. 10 squares of clay tile roof shingles ______________________
2. 10 squares of vertical clay tile dormer shingles __________________
3. Replace 1 salvaged half-round windows with 1 new half-round windows in dormers________________________
4. Concrete – 1 cubic yard – delivered and placed ___________________
1.4 SPECIFICATIONS AND DRAWINGS FOR CONTRACTOR
A. Drawings and contract documents may be obtained from the website where the solicitation is posted. Additional copies will be at Contractor's expense.
1.5 CONSTRUCTION SECURITY REQUIREMENTS
A. Security Plan:
1. The security plan defines both physical and administrative security procedures that will remain effective for the entire duration of the project.
2. The General Contractor is responsible for assuring that all sub-contractors working on the project and their employees also comply with these regulations.
B. Security Procedures:
1. General Contractor’s employees shall not enter the project site without appropriate badge. They may also be subject to inspection of their personal effects when entering or leaving the project site.
01 00 00 -3
2. Before starting work the General Contractor shall give one week’s notice to the Contracting Officer so that security arrangements can be provided for the employees. This notice is separate from any notices required for utility shutdown described later in this section.
3. No photography of VA premises is allowed without written permission of the Contracting Officer.
4. VA reserves the right to close down or shut down the project site and order General Contractor’s employees off the premises in the event of a national emergency. The General Contractor may return to the site only with the written approval of the Contracting Officer.
C. Key Control:
1. The General Contractor shall provide duplicate keys and lock combinations to the Contracting officers representative (COR) for the purpose of security inspections of every area of project including tool boxes and parked machines and take any emergency action.
2. The General Contractor shall turn over all permanent lock cylinders to the VA locksmith for permanent installation. See Section 08 71
00, DOOR HARDWARE and coordinate.
E. Document Control:
1. Before starting any work, the General Contractor/Sub Contractors shall submit an electronic security memorandum describing the approach to following goals and maintaining confidentiality of
“sensitive information”.
2. The General Contractor is responsible for safekeeping of all drawings, project manual and other project information. This information shall be shared only with those with a specific need to accomplish the project.
3. Certain documents, sketches, videos or photographs and drawings may be marked “Law Enforcement Sensitive” or “Sensitive Unclassified”.
Secure such information in separate containers and limit the access to only those who will need it for the project. Return the information to the Contracting Officer upon request.
4. These security documents shall not be removed or transmitted from the project site without the written approval of Contracting
Officer.
5. All paper waste or electronic media such as CD’s and diskettes shall be shredded and destroyed in a manner acceptable to the VA.
01 00 00 -4
6. Notify Contracting Officer and Site Security Officer immediately when there is a loss or compromise of “sensitive information”.
7. All electronic information shall be stored in specified location following VA standards and procedures using an Engineering Document
Management Software (EDMS).
a. Security, access and maintenance of all project drawings, both scanned and electronic shall be performed and tracked through the
EDMS system.
b. “Sensitive information” including drawings and other documents may be attached to e-mail provided all VA encryption procedures are followed.
F. Motor Vehicle Restrictions
1. Vehicle authorization request shall be required for any vehicle entering the site and such request shall be submitted 24 hours before the date and time of access. Access shall be restricted to picking up and dropping off materials and supplies.
2. A limited number of permits shall be issued for General Contractor and its employees for parking in designated areas only.
1.6 OPERATIONS AND STORAGE AREAS
A. The Contractor shall confine all operations (including storage of materials) on Government premises to areas authorized or approved by the Contracting Officer. The Contractor shall hold and save the
Government, its officers and agents, free and harmless from liability of any nature occasioned by the Contractor's performance.
B. Temporary buildings (e.g., storage sheds, shops, offices) and utilities may be erected by the Contractor only with the approval of the
Contracting Officer and shall be built with labor and materials furnished by the Contractor without expense to the Government. The temporary buildings and utilities shall remain the property of the
Contractor and shall be removed by the Contractor at its expense upon completion of the work. With the written consent of the Contracting
Officer, the buildings and utilities may be abandoned and need not be removed.
C. The Contractor shall, under regulations prescribed by the Contracting
Officer, use only established roadways, or use temporary roadways constructed by the Contractor when and as authorized by the Contracting
Officer. When materials are transported in prosecuting the work, vehicles shall not be loaded beyond the loading capacity recommended by the manufacturer of the vehicle or prescribed by any Federal, State, or
01 00 00 -5 local law or regulation. When it is necessary to cross curbs or sidewalks, the Contractor shall protect them from damage. The
Contractor shall repair or pay for the repair of any damaged curbs, sidewalks, or roads.
(FAR 52.236-10)
D. Working space and space available for storing materials shall be determined by the COR.
E. Workmen are subject to rules of Medical Center. Execute work in such a manner as to interfere as little as possible with work being done by others. Keep roads clear of construction materials, debris, standing construction equipment and vehicles at all times.
F. Execute work so as to interfere as little as possible with normal functioning of Medical Center as a whole, including operations of utility services, fire protection systems and any existing equipment, and with work being done by others. Use of equipment and tools that transmit vibrations and noises through the building structure, are not permitted in buildings that are occupied, during construction, jointly by patients or medical personnel, and Contractor's personnel, except as permitted by COR where required by limited working space.
1. Do not store materials and equipment in other than assigned areas.
Be aware and knowledgeable of exterior utilities before transporting and placing materials in their final destination.
2. Schedule delivery of materials and equipment to immediate construction working areas within buildings in use by Department of
Veterans Affairs in quantities sufficient for not more than two workdays. Provide unobstructed access to Medical Center areas required to remain in operation.
3. Where access by Medical Center personnel to vacated portions of buildings is not required, storage of Contractor's materials and equipment will be permitted subject to F. Utilities Services:
Where necessary to cut existing pipes, electrical wires, conduits, cables, etc., of utility services, or of fire protection systems or communications systems (except telephone), they shall be cut and capped at suitable places where shown; or, in absence of such indication, where directed by COR. All such actions shall be coordinated with the COR or Utility Company involved:
4. Whenever it is required that a connection fee be paid to a public utility provider for new permanent service to the construction
01 00 00 -6 project, for such items as water, sewer, electricity, gas or steam, payment of such fee shall be the responsibility of the Government and not the Contractor.
G. Phasing:
The Medical Center must maintain its operation 24 hours a day 7 days a week. Therefore, any interruption in service must be scheduled and coordinated with the COR to ensure that no lapses in operation occur.
It is the CONTRACTOR'S responsibility to develop a work plan and schedule detailing, at a minimum, the procedures to be employed, the equipment and materials to be used, the interim life safety measure to be used during the work, and a schedule defining the duration of the work with milestone subtasks. The work to be outlined shall include, but not be limited to:
To ensure such executions, Contractor shall furnish the COR with a schedule of approximate phasing with dates on which the Contractor intends to accomplish work in each specific area of site, building or portion thereof. In addition, Contractor shall notify the COR two weeks in advance of the proposed date of starting work in each specific area of site, building or portion thereof. Arrange such phasing dates to ensure accomplishment of this work in successive phases mutually agreeable to Medical Center Director, COR and Contractor, as follows:
Phase 1000:
Attic and Roof
• This will be demolition and prework on the attic and roof and preparing for the HVAC work. Weekend or after-hours work cannot be supported by the facility throughout the job.
• Contractor to measure existing main SA, RA and EA air flows and corresponding static pressures diff at the fans prior to demolition.
The measured values will be used to balance the new AHU-3-2 (which will serve as the temporary AHU).
• Due to the amount of material to be demolished on the roof and wood substrate/structure to be replaced, it is expected that there will be a large amount of noise carried through the windows and ceilings for everyone in the building. There will also be some structural work prior to Phase 1001 starting that will provide supports for the future AHUs in the attic. Some loud noise can be expected with this.
• ACM and Lead Paint Removal Work will take place during this phase in the Attic and Basement and on the Exterior.
• Coordinate completion of roof, dormer, downspout, c.i. boot connections to existing rainwater collection system with mechanical work.
01 00 00 -7
Phase 1001:
Attic
• Install EF-3-1 above existing AHU including as much of the new EA ductwork as will fit. New EA ducts need to be ready to connect to the existing main EA ducts but not yet.
• Install AHU-3-2, corresponding OA and relief ducts.
• Provide temporary SA duct from AHU-3-2 to the existing 16" dia. SA duct riser at col grid D11 but do not connect yet.
• Provide temporary RA ductwork from AHU-3-2 to existing 24x12 ra riser but do not connect yet.
• Connect temporary CHW hose from the existing riser near col grid D11 to
AHU-3-2.
• Connect temporary HW hoses from AHU-3-2 routed outside down to the basement to the new HW heating system but do not connect yet.
Basement
• Demo steam piping to the east side. provide electric portable heating on the East side rooms.
• Complete work on foundation vents and foundation ventilation fans.
• Install new pipe risers but do not penetrate slab yet.
• Instead connect temporary CHW hoses from the new riser stub-outs to the existing CHW riser near col grid D11.
• Then disconnect that existing CHW riser from its existing connection to the CHW main.
• As for heating HW use the temporary HW hoses to bring Heating HW to the attic.
Phase 1002:
The electrical work of getting the power to the attic must be completed by phase 1002. This will also necessitate some floor penetrations on each floor with accompanying noise to get to the attic from the basement.
Attic
• Connect new EA ducts to the existing main EA ducts.
• Connect temporary SA duct from AHU-3-2 to the existing 16" dia SA duct riser at col grid D11.
• Connect temporary RA ductwork from AHU-3-2 to existing 24x12 RA riser.
• Connect temporary HW heating hoses to AHU-3-2. Then disconnect the existing AHU from duct & piping.
• Run the AHU-3-2 at a speed to satisfy the previously measured CFM, OA and SP’s. AHU-3-2 is now serving the building.
Phase 1003:
Attic
• Complete the Demo of attic except for the existing CHW risers near col grid D11.
3rd Floor
• Ceiling slab penetration is required near column D3 to pick up existing
EA duct riser serving 3rd, 2nd and 1st floor.
Phase 1004:
• Complete installation of AHU-3-1 and EF-3-1, ductwork & piping, including duct and piping risers, except don’t penetrate the slabs yet.
01 00 00 -8
• Connect temporary CHW hose from the existing riser to AHU-3-1. Connect temporary HW hoses from hose serving AHU 3-2 to the new HW piping that will serve AHU-3-1 and the HW piping riser down to the floors.
Phase 1005:
3rd Floor
• Move people and equipment out of the workspace.
• ACM and Lead Paint Removal Work, ceiling demolition and rework, wall demolition and rework, plumbing demolition and rework, and Fire Protection demolition and rework will take place during this phase on the 3rd Floor.
• Demolish and install per drawings. Install duct and pipe risers and penetrate the ceiling slab to the attic. Don’t penetrate the floor slab to the 2nd floor yet.
• Connect duct risers to the attic.
• Connect VAV HW piping to the new HW riser at the attic.
• Balance AHU-3-1 and EF-3-1 to serve only the floor areas already renovated.
• Balance AHU-3-2 to serve the areas renovated and the existing floors below. Remove temporary portable heaters on the East side rooms.
• Punchout space and move people and equipment back into the workspace.
2nd Floor
• Ceiling slab penetration is required near column D3 to pick up existing
EA duct riser serving 2nd and 1st floor.
Phase 1006:
2nd Floor
• Move people and equipment out of the workspace.
• ACM and Lead Paint Removal Work, ceiling demolition and rework, wall demolition and rework, and Fire Protection demolition and rework will take place during this phase on the 2nd Floor.
• Demolish and install per drawings. Install duct and pipe risers and penetrate the ceiling slab to the 3rd Floor. Don’t penetrate the floor slab to the 1st floor yet.
• Connect duct risers to the 3rd floor.
• Connect VAV HW piping to the new HW riser at the 3rd floor.
• Balance AHU-3-1 and EF-3-1 to serve only the floor areas already renovated.
• Balance AHU-3-2 to serve the areas renovated and the existing floors below. Remove temporary portable heaters on the East side rooms.
• Punchout space and move people and equipment back into the workspace 1st Floor
• Ceiling slab penetration is required near column D3 to pick up existing
EA duct riser serving 1st floor.
Phase 1007:
1st Floor
• Move people and equipment out of the work space.
• ACM and Lead Paint Removal Work, ceiling demolition and rework, wall demolition and rework, and Fire Protection demolition and rework will take place during this phase on the 1st Floor.
01 00 00 -9
1007A 1st Floor
• First demolish the area near and around the col grids E3 and F3 (where the main pipes are). Demolish the piping and install the risers.
Penetrate the ceiling and floor slabs to the 2nd floor and basement.
Connect all HW and chilled risers from the basement to the 2nd floor.
1007B
• Connect new CHW piping from the new risers to AHU-3-1 and AHU-3-2.
• Connect new HW piping from the new risers AHU-3-1 and AHU-3-2.
• Disconnect all temporary hoses.
1007C 1st Floor
• Demolish and install per drawings. Install duct and pipe risers and penetrate the ceiling slab to the 2nd floor. Penetrate the floor slab to the basement.
• Connect duct risers to the 2nd floor.
• Connect VAV HW piping to the new HW riser at the 2nd floor.
• Connect pipe risers to the basement risers.
• Balance AHU-3-1, AHU-3-2 and EF-3-1. Remove temporary portable heaters on the East side rooms.
• Punchout space and move people and equipment back into the workspace.
Phase 1008:
• Demolish and install the rest of the work per drawings to include the connectors between buildings.
• Punchout the building and turn it over to the VA.
H. Building No. 3 will be occupied during performance of work; but immediate areas of alterations will be vacated.
1. Certain areas of Building No. 3 will be occupied by Medical Center personnel for various phases as listed above:
Contractor shall take all measures and provide all material necessary for protecting existing equipment, personnel and property in affected areas of construction against dust and debris, so that equipment and affected areas to be used in the Medical Centers operations will not be hindered. These routes adjacent, above or below, whether access or egress shall be isolated from the construction area. Coordinate alteration work in areas occupied by
Department of Veterans Affairs so that Medical Center operations will continue during the construction period in occupied areas.
2. Immediate areas of alterations not mentioned in preceding
Subparagraph 1 will be temporarily vacated while alterations are performed.
01 00 00 -10
I. Construction Fence: Before construction operations begin, Contractor shall provide a chain link construction fence, 2.1m (seven feet) minimum height, around the construction area indicated on the drawings.
Provide gates as required for access with necessary hardware, including hasps and padlocks. Fasten fence fabric to terminal posts with tension bands and to line posts and top and bottom rails with tie wires spaced at maximum 375mm (15 inches). Bottom of fences shall extend to 25mm
(one inch) above grade. Remove the fence when directed by COR.
J. When a building and/or construction site is turned over to Contractor, Contractor shall accept entire responsibility including upkeep and maintenance therefore:
1. Contractor shall maintain a minimum temperature of 4 degrees C (40 degrees F) at all times, except as otherwise specified.
2. Contractor shall maintain in operating condition existing fire protection and alarm equipment. In connection with fire alarm equipment, Contractor shall make arrangements for pre-inspection of site with Fire Department or Company (Department of Veterans Affairs or municipal) whichever will be required to respond to an alarm from
Contractor's employee or watchman.
K. Utilities Services: Maintain existing utility services for Medical
Center at all times. Provide temporary facilities, labor, materials, equipment, connections, and utilities to assure uninterrupted services.
Where necessary to cut existing water, steam, gases, sewer or air pipes, or conduits, wires, cables, etc. of utility services or of fire protection systems and communications systems (including telephone), they shall be cut and capped at suitable places where shown; or, in absence of such indication, where directed by COR //.
1. No utility service such as water, gas, steam, sewers or electricity, or fire protection systems and communications systems may be interrupted without prior approval of COR. Electrical work shall be accomplished with all affected circuits or equipment de-energized.
When an electrical outage cannot be accomplished, work on any energized circuits or equipment shall not commence without a detailed work plan, the Medical Center Director’s prior knowledge and written approval. Refer to specification Sections 26 05 11, REQUIREMENTS FOR ELECTRICAL INSTALLATIONS, 27 05 11 REQUIREMENTS FOR
COMMUNICATIONS INSTALLATIONS and 28 05 00, COMMON WORK RESULTS FOR
ELECTRONIC SAFETY AND SECURITY for additional requirements.
01 00 00 -11
2. Contractor shall submit a request to interrupt any such services to
COR, in writing, 7 days in advance of proposed interruption. Request shall state reason, date, exact time of, and approximate duration of such interruption.
3. Contractor will be advised (in writing) of approval of request, or of which other date and/or time such interruption will cause least inconvenience to operations of Medical Center. Interruption time approved by Medical Center may occur at other than Contractor's normal working hours.
4. Major interruptions of any system must be requested, in writing, at least 15 calendar days prior to the desired time and shall be performed as directed by the COR.
5. In case of a contract construction emergency, service will be interrupted on approval of COR. Such approval will be confirmed in writing as soon as practical.
6. Whenever it is required that a connection fee be paid to a public utility provider for new permanent service to the construction project, for such items as water, sewer, electricity, gas or steam, payment of such fee shall be the responsibility of the Government and not the Contractor.
L. Abandoned Lines: All service lines such as wires, cables, conduits, ducts, pipes and the like, and their hangers or supports, which are to be abandoned but are not required to be entirely removed, shall be sealed, capped or plugged at the main, branch or panel they originate from. The lines shall not be capped in finished areas, but shall be removed and sealed, capped or plugged in ceilings, within furred spaces, in unfinished areas, or within walls or partitions; so that they are completely behind the finished surfaces.
M. To minimize interference of construction activities with flow of
Medical Center traffic, comply with the following:
1. Keep roads, walks and entrances to grounds, to parking and to occupied areas of buildings clear of construction materials, debris and standing construction equipment and vehicles. Wherever excavation for new utility lines cross existing roads, at least one lane must be open to traffic at all times with approval.
2. Method and scheduling of required cutting, altering and removal of existing roads, walks and entrances must be approved by the COR.
01 00 00 -12
N. Coordinate the work for this contract with other construction operations as directed by COR. This includes the scheduling of traffic and the use of roadways, as specified in Article, USE OF ROADWAYS.
1.7 ALTERATIONS
A. Survey: Before any work is started, the Contractor shall make a thorough survey with the COR areas of buildings in which alterations occur and areas which are anticipated routes of access, and furnish a report, signed by both, to the Contracting Officer. This report shall list by rooms and spaces:
1. Existing condition and types of resilient flooring, doors, windows, walls and other surfaces not required to be altered throughout affected areas of building.
2. Existence and conditions of items such as plumbing fixtures and accessories, electrical fixtures, equipment, venetian blinds, shades, etc., required by drawings to be either reused or relocated, or both.
3. Shall note any discrepancies between drawings and existing conditions at site.
4. Shall designate areas for working space, materials storage and routes of access to areas within buildings where alterations occur, and which have been agreed upon by Contractor and COR.
B. Any items required by drawings to be either reused or relocated or both, found during this survey to be nonexistent, or in opinion of COR, to be in such condition that their use is impossible or impractical, shall be furnished and/or replaced by Contractor with new items in accordance with specifications which will be furnished by Government.
Provided the contract work is changed by reason of this subparagraph B, the contract will be modified accordingly, under provisions of clause entitled "DIFFERING SITE CONDITIONS" (FAR 52.236-2) and "CHANGES" (FAR
52.243-4 and VAAR 852.236-88).
C. Re-Survey: Thirty days before expected partial or final inspection date, the Contractor and COR together shall make a thorough re-survey of the areas of buildings involved. They shall furnish a report on conditions then existing, of resilient flooring, doors, windows, walls and other surfaces as compared with conditions of same as noted in first condition survey report:
1. Re-survey report shall also list any damage caused by Contractor to such flooring and other surfaces, despite protection measures; and, will form basis for determining extent of repair work required of
01 00 00 -13
Contractor to restore damage caused by Contractor's workmen in executing work of this contract.
D. Protection: Provide the following protective measures:
1. Wherever existing roof surfaces are disturbed they shall be protected against water infiltration. In case of leaks, they shall be repaired immediately upon discovery.
2. Temporary protection against damage for portions of existing structures and grounds where work is to be done, materials handled, and equipment moved and/or relocated.
3. Protection of interior of existing structures at all times, from damage, dust and weather inclemency. Wherever work is performed, wall and floor surfaces that are to remain in place shall be adequately protected prior to starting work, and this protection shall be maintained intact until all work in the area is completed.
1.8 DISPOSAL AND RETENTION
A. Materials and equipment accruing from work removed and from demolition of buildings or structures, or parts thereof, shall be disposed of as follows:
1. Reserved items which are to remain property of the Government are noted on drawings or in specifications as items to be stored. Items that remain property of the Government shall be removed or dislodged from present locations in such a manner as to prevent damage which would be detrimental to re-installation and reuse. Store such items where directed by COR.
2. Items not reserved shall become property of the Contractor and be removed by Contractor from Medical Center.
3. Items of portable equipment and furnishings located in rooms and spaces in which work is to be done under this contract shall remain the property of the Government. When rooms and spaces are vacated by the Department of Veterans Affairs during the alteration period, such items which are NOT required by drawings and specifications to be either relocated or reused will be removed by the Government in advance of work to avoid interfering with Contractor's operation.
4. PCB Transformers and Capacitors, if found: The Contractor shall be responsible for disposal of the Polychlorinated Biphenyl (PCB) transformers and capacitors. The transformers and capacitors shall be taken out of service and handled in accordance with the procedures of the Environmental Protection Agency (EPA) and the
Department of Transportation (DOT) as outlined in Code of Federal
01 00 00 -14
Regulation (CFR), Titled 40 and 49 respectively. The EPA's Toxic
Substance Control Act (TSCA) Compliance Program Policy Nos. 6-PCB-6 and 6-PCB-7 also apply. Upon removal of PCB transformers and capacitors for disposal, the "originator" copy of the Uniform
Hazardous Waste Manifest (EPA Form 8700-22), along with the Uniform
Hazardous Waste Manifest Continuation Sheet (EPA Form 8700-22A) shall be returned to the Contracting Officer who will annotate the contract file and transmit the Manifest to the Medical Center's
Chief.
a. Copies of the following listed CFR titles may be obtained from the Government Printing Office:
40 CFR 261........Identification and Listing of Hazardous Waste
40 CFR 262........Standards Applicable to Generators of Hazardous
Waste
40 CFR 263........Standards Applicable to Transporters of
Hazardous Waste
40 CFR 761........PCB Manufacturing, Processing, Distribution in
Commerce, and use Prohibitions
49 CFR 172........Hazardous Material tables and Hazardous
Material Communications Regulations
49 CFR 173........Shippers - General Requirements for Shipments and Packaging
49 CRR 173........Subpart A General
49 CFR 173........Subpart B Preparation of Hazardous Material for
Transportation
49 CFR 173........Subpart J Other Regulated Material; Definitions and Preparation
TSCA..............Compliance Program Policy Nos. 6-PCB-6 and 6-
PCB-7
1.9 PROTECTION OF EXISTING VEGETATION, STRUCTURES, EQUIPMENT, UTILITIES, AND
IMPROVEMENTS
A. The Contractor shall preserve and protect all structures, equipment, and vegetation (such as trees, shrubs, and grass) on or adjacent to the work site, which are not to be removed and which do not unreasonably interfere with the work required under this contract. The Contractor shall only remove trees when specifically authorized to do so and shall avoid damaging vegetation that will remain in place. If any limbs or branches of trees are broken during contract performance, or by the careless operation of equipment, or by workmen, the Contractor shall
01 00 00 -15 trim those limbs or branches with a clean cut and paint the cut with a tree-pruning compound as directed by the Contracting Officer.
B. The Contractor shall protect from damage all existing improvements and utilities at or near the work site and on adjacent property of a third party, the locations of which are made known to or should be known by the Contractor. The Contractor shall repair any damage to those facilities, including those that are the property of a third party, resulting from failure to comply with the requirements of this contract or failure to exercise reasonable care in performing the work. If the
Contractor fails or refuses to repair the damage promptly, the
Contracting Officer may have the necessary work performed and charge the cost to the Contractor.
(FAR 52.236-9)
C. Refer to Section 01 57 19, TEMPORARY ENVIRONMENTAL CONTROLS, for additional requirements on protecting vegetation, soils and the environment. Refer to Articles, "Alterations", "Restoration", and
"Operations and Storage Areas" for additional instructions concerning repair of damage to structures and site improvements.
1.10 RESTORATION
A. Remove, cut, alter, replace, patch and repair existing work as necessary to install new work. Except as otherwise shown or specified, do not cut, alter or remove any structural work, and do not disturb any ducts, plumbing, steam, gas, or electric work without approval of the
COR. Existing work to be altered or extended and that is found to be defective in any way, shall be reported to the COR before it is disturbed. Materials and workmanship used in restoring work, shall conform in type and quality to that of original existing construction, except as otherwise shown or specified.
B. Upon completion of contract, deliver work complete and undamaged.
Existing work (walls, ceilings, partitions, floors, mechanical and electrical work, lawns, paving, roads, walks, etc.) disturbed or removed as a result of performing required new work, shall be patched, repaired, reinstalled, or replaced with new work, and refinished and left in as good condition as existed before commencing work.
C. At Contractor's own expense, Contractor shall immediately restore to service and repair any damage caused by Contractor's workmen to existing piping and conduits, wires, cables, etc., of utility services
01 00 00 -16 or of fire protection systems and communications systems (including telephone) which are not scheduled for discontinuance or abandonment.
D. Expense of repairs to such utilities and systems not shown on drawings or locations of which are unknown will be covered by adjustment to contract time and price in accordance with clause entitled "CHANGES"
(FAR 52.243-4 and VAAR 852.236-88) and "DIFFERING SITE CONDITIONS" (FAR
52.236-2).
1.11 PHYSICAL DATA
A. Data and information furnished or referred to below is for the
Contractor's information. The Government shall not be responsible for any interpretation of or conclusion drawn from the data or information by the Contractor.
1.14 AS-BUILT DRAWINGS
A. The contractor shall maintain two full size sets of as-built drawings which will be kept current during construction of the project, to include all contract changes, modifications and clarifications.
B. All variations shall be shown in the same general detail as used in the contract drawings. To ensure compliance, as-built drawings shall be made available for the COR review, as often as requested.
C. Contractor shall deliver two approved completed sets of as-built drawings in the electronic version (scanned PDF) to the COR within 15 calendar days after each completed phase and after the acceptance of the project by the COR.
D. Paragraphs A, B, & C shall also apply to all shop drawings.
1.15 WARRANTY MANAGEMENT
A. Warranty Management Plan: Develop a warranty management plan which contains information relevant to FAR 52.246-21 Warranty of Construction in at least 30 days before the planned pre-warranty conference, submit one set of the warranty management plan. Include within the warranty management plan all required actions and documents to assure that the
Government receives all warranties to which it is entitled. The plan must be in narrative form and contain sufficient detail to render it suitable for use by future maintenance and repair personnel, whether tradesman, or of engineering background, not necessarily familiar with this contract. The term “status” as indicated below must include due date and whether item has been submitted or was approved. Warranty information made available during the construction phase must be submitted to the Contracting Officer for approval prior to each monthly invoice for payment. Assemble approved information in a binder and turn
01 00 00 -17 over to the Government upon acceptance of the work. The construction warranty period will begin on the date of the project acceptance and continue for the product warranty period. A joint 4 month and 9 month warranty inspection will be conducted, measured from time of acceptance, by the Contactor and the Contracting Officer. Include in the warranty management plan, but not limited to, the following:
1. Roles and responsibilities of all personnel associated with the warranty process, including points of contact and telephone numbers within the company of the Contractor, subcontractors, manufacturers or suppliers involved.
2. Furnish with each warranty the name, address and telephone number of each of the guarantor’s representatives nearest project location.
3. Listing and status of delivery of all Certificates of Warranty for extended warranty items, to include roofs, HVAC balancing, pumps, motors, transformers and for all commissioned systems such as fire protection and alarm systems, sprinkler systems and lightning protection systems, etc.
4. A list for each warranted equipment item, feature of construction or system indicating:
a. Name of item.
b. Model and serial numbers.
c. Location where installed.
d. Name and phone numbers of manufacturers and suppliers.
e. Name and phone numbers of manufacturers or suppliers.
f. Names, addresses and phone numbers of sources of spare parts.
g. Warranties and terms of warranty. Include one-year overall warranty of construction, including the starting date of warranty of construction. Items which have extended warranties must be indicated with separate warranty expiration dates.
h. Starting point and duration of warranty period.
i. Summary of maintenance procedures required to continue the warranty in force.
j. Cross-reference to specific pertinent Operation and Maintenance manuals.
k. Organizations, names and phone numbers of persons to call for warranty service.
l. Typical response time and repair time expected for various warranted equipment.
01 00 00 -18
5. The plans for attendance at the 4 and 9-month post construction warranty inspections conducted by the government.
6. Procedure and status of tagging of all equipment covered by extended warranties.
7. Copies of instructions to be posted near selected pieces of equipment where operation is critical for warranty and/or safety reasons.
B. Performance Bond: The Performance Bond must remain effective throughout the construction period.
1. In the event the Contractor fails to commence and diligently pursue any construction warranty work required, the Contracting Officer will have the work performed by others, and after completion of the work, will charge the remaining construction warranty funds of expenses incurred by the Government while performing the work, including, but not limited to administrative expenses.
2. In the event sufficient funds are not available to cover the construction warranty work performed by the Government at the contractor’s expenses, the Contracting Officer will have the right to recoup expenses from the bonding company.
3. Following oral or written notification of required construction warranty repair work, the Contractor shall respond in a timely manner. Written verification will follow oral instructions. Failure to respond will be cause for the Contracting Officer to proceed against the Contractor.
C. Pre-Warranty Conference: Prior to contract completion, and at a time designated by the Contracting Officer, the Contractor shall meet with the Contracting Officer to develop a mutual understanding with respect to the requirements of this section. Communication procedures for
Contractor notification of construction warranty defects, priorities with respect to the type of defect, reasonable time required for
Contractor response, and other details deemed necessary by the
Contracting Officer for the execution of the construction warranty will be established/ reviewed at this meeting. In connection with these requirements and at the time of the Contractor’s quality control completion inspection, furnish the name, telephone number and address of a licensed and bonded company which is authorized to initiate and pursue construction warranty work action on behalf of the Contractor.
This point of contract will be located within the local service area of the warranted construction, be continuously available and be responsive
01 00 00 -19 to Government inquiry on warranty work action and status. This requirement does not relieve the Contractor of any of its responsibilities in conjunction with other portions of this provision.
D. Contractor’s Response to Construction Warranty Service Requirements:
Following oral or written notification by the Contracting Officer, the
Contractor shall respond to construction warranty service requirements in accordance with the “Construction Warranty Service Priority List” and the three categories of priorities listed below. Submit a report on any warranty item that has been repaired during the warranty period.
Include within the report the cause of the problem, date reported, corrective action taken, and when the repair was completed. If the
Contractor does not perform the construction warranty within the timeframe specified, the Government will perform the work and back charge the construction warranty payment item established.
1. First Priority Code 1. Perform onsite inspection to evaluate situation, and determine course of action within 4 hours, initiate work within 6 hours and work continuously to completion or relief.
2. Second Priority Code 2. Perform onsite inspection to evaluate situation, and determine course of action within 8 hours, initiate work within 24 hours and work continuously to completion or relief.
3.