This document package includes construction drawings and specifications for a technology infrastructure upgrade project at a Department of Veterans Affairs medical center. The project involves demolishing existing telecommunications cabling and equipment in preparation for installing new cabling, fiber optic lines, data outlets, wireless access points, and a smart building system. New technology rooms will house fiber distribution and terminal equipment, data switches, wireless controllers, and racks for facility management systems. The contractor must coordinate protection of existing equipment and transition of systems with the VA. The solicitation number is 36C25020B0001 for the Increase IRM Physical Security Project 541-19-102 through the VA Veterans Health Administration VISN 10. The bid due date is April 13, 2020.

View the file

Other files

Show all 19

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

W

TELECOMMUNICATIONS SYSTEM LEGEND

TELECOMMUNICATIONS OUTLET "TCO" - MOUNTED AT 18" AFF UNLESS OTHERWISE NOTED. REFER TO TELECOMMUNICATIONS OUTLET DETAILS ON SUBSEQUENT DRAWING FOR REQUIREMENTS. # REFERS TO THE NUMBER OF CABLE/JACKS TERMINATED

IN EACH FACEPLATE. ADDITIONAL JACK LOCATIONS SHALL BE BLANKED FOR FUTURE USE.

TELECOMMUNICATIONS OUTLET "TCO" - MOUNTED ABOVE COUNTER UNLESS OTHERWISE NOTED. REFER TO

TELECOMMUNICATIONS OUTLET DETAILS ON SUBSEQUENT DRAWING FOR REQUIREMENTS.

TELEPHONE OUTLET - MOUNTED AT 48" AFF UNLESS OTHERWISE NOTED.

WIRELESS ACCESS OUTLET - MOUNTED ABOVE FINISHED CEILING. WIRELESS ACCESS DEVICES PROVIDED BY OWNER.

COORDINATE WITH VA OIT.

"C" DENOTES WIRELESS CELLULAR NETWORK ANTENNA. COORDINATE REMOVAL AND REPLACEMENT OF CELLULAR

ANTENNAS WITH VA OIT.

EQUIPMENT - RACK, CABINET, UPS, ETC. AS NOTED ON PLAN

CABLE TRAY - 12"W X 4"H UNLESS OTHERWISE NOTED - WIRE MESH TYPE IN CORRIDORS, LADDER TYPE IN TELECOM. ROOMS

JUNCTION BOX - SEE ELECTRICAL LEGEND FOR ADDITIONAL INFORMATION.JJ

BUILDING SYSTEM NETWORK LEGEND

SMART BUILDING SYSTEM DATA OUTLIET - PROVIDE 2-GANG WALL MOUNTED BOX WITH SINGLE GANG BLANK COVER PLATE MOUNTED AT 48" AFF UNLESS OTHERWISE NOTED, 1-1/4" WITH PULLWIRE FROM BOX TO MIN. 96" ABOVE FINISHED FLOOR AT

AN ACCESSIBLE LOCATION AND PLASTIC BUSHING ON THE END OF THE CONDUIT.

## - DESIGNATES THE FOTP AT WHICH THE CABLES SHALL BE TERMINATED.

# - DESIGNATES THE NUMBER OF DATA JACKS TO PROVIDE. PROVIDE (1) CAT6A ETHERNET CABLE FROM EACH JACK TO

THE FOTP PATCH PANEL.

S - DESIGNATES THE OUTLET IS PART OF THE SMART BUILDING SYSTEM NETWORK

SX.XX

GENERAL NOTES:

ALL CONDUITS SHALL BE INSTALLED COMPLETE WITH PULLWIRE.

THE NUMBER OF CABLES IN ANY PATHWAY SHALL NOT EXCEED 40% FILL.

REFER TO FACEPLATE DETAILS FOR ADDITIONAL INFORMATION.

T1.

T2.

T3.

ABBREVIATIONS

AC ABOVE COUNTER AT 9" UNLESS OTHERWISE NOTED

AF AMP FRAME

AFC ABOVE FINISHED CEILING

AFF ABOVE FINISHED FLOOR

AT AMP TRIP

BC BELOW COUNTER AT 18"AFF UNLESS OTHERWISE NOTED

BFC BELOW FINISHED CEILING

CM CEILING MOUNTED

EC ELECTRICAL CONTRACTOR

EG EQUIPMENT GROUND

GC GENERAL CONTRACTOR

GFCI GROUND FAULT CIRCUIT INTERRUPTER

IG ISOLATED GROUND

OIT INFORMATION TECHNOLOGY DEPARTMENT

PROVIDE DEFINITION: FURNISH, INSTALL AND CONNECT COMPLETE.

X

XB

XL

XN

XR

XRR

EXISTING OUTLET, DEVICE, LIGHTING FIXTURE, CONDUIT, ETC. - TO REMAIN

INDICATES EXISTING OUTLET, LIGHTING FIXTURE, CONDUIT, ETC - TO BE REMOVED. PROVIDE BLANK COVER

FOR OUTLET AND MAINTAIN CIRCUIT CONTINUITY.

NEW LOCATION OF EXISTING OUTLET, DEVICE, LIGHTING FIXTURE, ETC.

EXISTING OUTLET, DEVICE, LIGHTING FIXTURE, ETC. - TO BE REPLACED WITH NEW OF SPECIFIED TYPE

EXISTING OUTLET, DEVICE, LIGHTING FIXTURE, CONDUIT, ETC. - TO BE REMOVED COMPLETE - MAINTAIN

CIRCUIT CONTINUITY TO ADJACENT OUTLETS, EXTEND CONDUIT AND WIRING AS REQUIRED.

EXISTING OUTLET, DEVICE, LIGHTING FIXTURE, ETC. - TO BE REMOVED AND REINSTALLED AT NEW

LOCATION - EXTEND CONDUIT AND WIRING AS REQUIRED

MC MECHANICAL CONTRACTOR

MLO MAIN LUGS ONLY

NEC NATIONAL ELECTRICAL CODE

NF NOT FUSED

OFE OWNER FURNISHED EQUIPMENT

TC TELECOMMUNICATIONS CONTRACTOR

TCC TEMPERATURE CONTROLS CONTRACTOR

TV TELEVISION

VDC VOICE/DATA CONTRACTOR

VFD VARIABLE FREQUENCY DRIVE

WM WIREMOLD

WP WEATHERPROOF ENCLOSURE - NEMA 4

GENERAL LEGEND:

CODED NOTE - "1" INDICATES NOTE NUMBER

REVISION REFERENCE NUMBER

MECHANICAL EQUIPMENT IDENTIFIER

DETAIL REFERENCE - "1" INDICATES DETAIL NUMBER, "E0.1" INDICATES DRAWING NUMBER

COLUMN REFERENCE GRID

INDICATES EXISTING CONSTRUCTION WALL TYPE

INDICATES DEMOLITION WALL TYPE

INDICATES NEW CONSTRUCTION WALL TYPE

AC

GB13

E0.1

A

POSITION

JACK

TYPE

JACK

COLOR

CABLE

TYPE

CABLE

COLOR

3 BLANK N/A N/A N/A

CAT 6A

RJ 45

BLUE CAT 6A BLUE

CAT 6A

RJ 45

BLUE CAT 6A

2 BLANK N/A N/A

BLUE

N/A

PORT IDENTIFICATION LABELS

XX-XX-XXX

TR IDENTIFIER

PATCH PANEL

PORT NUMBER

XX-XX-XXX

XX-XX-XXX

POSITION

JACK

TYPE

JACK

COLOR

CABLE

TYPE

CABLE

COLOR

3 BLUE BLUE

CAT 6A

RJ 45

BLUE CAT 6A

BLUE

BLUE BLUE

BLUE BLUE

XX-XX-XXX XX-XX-XXX

XX-XX-XXX XX-XX-XXX

PORT IDENTIFICATION LABELS

XX-XX-XXX

TR IDENTIFIER

PATCH PANEL

PORT NUMBER

CAT 6A

RJ 45

CAT 6A

CAT 6A

RJ 45

CAT 6A

CAT 6A

RJ 45

CAT 6A

18" AFF FOR STANDARD LOCATIONS,

54" AFF FOR WALL PHONES, UNLESS

OTHERWISE NOTED

ACCESSIBLE CEILING

FINISHED FLOOR

1-1/4" EMT CONDUIT

INSULATED BUSHING

5" SQ. x 2-7/8"D BACK BOX WITH SINGLE

GANG PLASTER RING.

COVERPLATE AND COMMUNICATION JACK

TO BE PROVIDED BY CONTRACTOR.

INSTALL BLANK COVERS ON ALL UNUSED

COMMUNICATIONS JUNCTION BOXES

CAT 6A CABLES

CABLE TRAY

POSITION

JACK

TYPE

JACK

COLOR

CABLE

TYPE

CABLE

COLOR

3 BLANK N/A N/A N/A

CAT 6A

RJ 45

BLUE CAT 6A BLUE

CAT 6A

RJ 45

BLUE CAT 6A

2 BLANK N/A N/A

BLUE

N/A

FOTP IDENTIFIER

XX-XXX-FOTP-XX

FOTP NUMBER

FOTP ROOM NUMBER

FOTP BUILDING/FLOOR IDENTIFIER

XX-XX-XXX

XX-XX-FOTP-XXX

FACEPLATE ID

XX-XXX-XX

FACEPLATE NUMBER IN ROOM

NUMBER

BUILDING/FLOOR IDENTIFIER

S

59459

M.P. LONG

R

ES

O F

I R

GE

NOI

S

P

E

N E

DERT

L EA

E I N

G

R

TS

TEA HF OO

IO

DESIGN AND CONSTRUCTION DOCUMENTS AS

INSTRUMENTS OF SERVICE ARE GIVEN IN

CONFIDENCE AND REMAIN THE PROPERTY OF

PERSPECTUS ARCHITECTURE. THE USE OF THIS

DESIGN AND THESE CONSTRUCTION

DOCUMENTS

FOR PURPOSES OTHER THAN THE SPECIFIC

PROJECT NAMED HEREIN IS STRICTLY

PROHIBITED WITHOUT THE EXPRESSED WRITTEN

CONSENT OF PERSPECTUS ARCHITECTURE.

COPYRIGHT C 2018.

13212 Shaker Square Suite 204 Cleveland, Ohio 44120 P. 216.752.1800 F. 216.752.3833

CONSULTANTS: ARCHITECT:

Drawing Title

Approved: Project Director Location

Project Title

Date Checked Drawn

Drawing Number

Building Number

Project Number

Office of

Facilities

Management

Dwg. of o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t

VA FORM 08-6231, OCT 1978

1 2 3 4 5 6 7 8 9 10

A

1 2 3 4 5 6 7 8 9 10

B

C

D

E

F

A

B

C

D

E

F

VAMC - WADE PARK

Revisions: Date

FULLY SPRINKLERED

18077

FREDRICK, FREDRICK & HELLER

ENGINEERS, INC.

672 EAST ROYALTON ROAD

BROADVIEW HTS., OHIO 44147

TEL. (440)546-9696

FAX: (440)546-9699

BID ISSUE 4/13/20

Increase IRM Physical

Security

541-19-102

CPCMPL

TECHNOLOGY LEGEND AND

GENERAL NOTES

T0.1 4/13/20

NOT TO SCALE

TYPICAL 2-JACK FACEPLATE DETAIL 4 NOT TO SCALE

TYPICAL 4-JACK FACEPLATE DETAIL 5

NOT TO SCALE

TYPICAL TELECOM ROUGH-IN 6 NOT TO SCALE

TYPICAL SBS SYSTEM FACEPLATE DETAIL 7

UP

36 37

H

L

L1

L2

L3

39 4241403836a

Z3

X

XX

E1 E2

D1 D2

F1 F2 G1 G2 G3 G4 G5 H1 H2 H3

DEMARC

EXISTING 4"C FROM BELOW

RAISED FLOOR TO ABOVE

FINISHED CEILING TO REMAIN

EXISTING 4"C FROM BELOW

RAISED FLOOR TO ABOVE

FINISHED CEILING TO REMAIN

SM

SM

WIREMOLD

XR

TYP.

TYP.

X

X X X X X X

EXISTING FIBER

CABINETS

EXISTING CORE

SWITCH CABINETS

CAB.

A1

CAB.

A2

CAB.

A3

CAB.

A4

CAB.

A5

CAB.

A6

X

EXISTING

ALT DATA

CABINET

X X X X XX X X X

PAGING

SYSTEM

CABINETS

EXISTING ANALOG

PHONE EQUIPMENT

EXISTING (2)

2 POST RACKS

EXISTING PHONE

CABINETS

EXISTING 2

POST RACK

XX

ANALOG PHONE SYSTEM RACKS

FACILITY MANAGEMENT

RACKS

X X X

T2.1

WIREMOLD

XR

X

EXISTING

TELECOM GROUND BAR

(TGB)

2 Bedroom

3A131

Corridor

3A100E

EMS

3A128

L.C.

3A130

L.C.

3A132

EMS

3A134

Toilet/ Shower

3A137A

Tele Health

3A137

FMS-1

3A135-1

MCOR-1

3A135B-1

BATTERY

3A-135A

MCR-1

3A133-1

Passage

3AC312

BB475

HAC

3AC311

EXISTING CABLING FROM DEMARC

LOCATION TO MAIN COMPUTER ROOM

EXISTING 4"C SLEEVES BETWEEN

EXISTING BATTERY ROOM AND

MAIN COMPUTER ROOM

S

59459

M.P. LONG

R

ES

O F

I R

GE

NOI

S

P

E

N E

DERT

L EA

E I N

G

R

TS

TEA HF OO

IO

DESIGN AND CONSTRUCTION DOCUMENTS AS

INSTRUMENTS OF SERVICE ARE GIVEN IN

CONFIDENCE AND REMAIN THE PROPERTY OF

PERSPECTUS ARCHITECTURE. THE USE OF THIS

DESIGN AND THESE CONSTRUCTION

DOCUMENTS

FOR PURPOSES OTHER THAN THE SPECIFIC

PROJECT NAMED HEREIN IS STRICTLY

PROHIBITED WITHOUT THE EXPRESSED WRITTEN

CONSENT OF PERSPECTUS ARCHITECTURE.

COPYRIGHT C 2018.

13212 Shaker Square Suite 204 Cleveland, Ohio 44120 P. 216.752.1800 F. 216.752.3833

CONSULTANTS: ARCHITECT:

Drawing Title

Approved: Project Director Location

Project Title

Date Checked Drawn

Drawing Number

Building Number

Project Number

Office of

Facilities

Management

Dwg. of o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t

VA FORM 08-6231, OCT 1978

1 2 3 4 5 6 7 8 9 10

A

1 2 3 4 5 6 7 8 9 10

B

C

D

E

F

A

B

C

D

E

F

VAMC - WADE PARK

Revisions: Date

FULLY SPRINKLERED

18077

FREDRICK, FREDRICK & HELLER

ENGINEERS, INC.

672 EAST ROYALTON ROAD

BROADVIEW HTS., OHIO 44147

TEL. (440)546-9696

FAX: (440)546-9699

BID ISSUE 4/13/20

Increase IRM Physical

Security

541-19-102

CPCMPL

PARTIAL THIRD FLOOR

TECHNOLOGY DEMOLITION PLAN

- PHASE 1

T2.1 4/13/20

0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'

1/4" = 1'-0"

PARTIAL THIRD FLOOR

TECHNOLOGY DEMOLITION PLAN - PHASE 1 1

TECHNOLOGY DEMOLITION NOTES

D1 ALL EXISTING TELECOMMUNICATIONS OUTLETS, NURSE CALL DEVICES, CONDUIT, WIRING ETC. THAT WILL NOT BE

REUSED IN THE REMODELED INSTALLATION SHALL BE REMOVED UNLESS OTHERWISE NOTED. THIS DEMOLITION SHALL INCLUDE ALL ELECTRICAL ITEMS SHOWN ON THIS PLAN THAT ARE NOT DESIGNATED BY "X", "XN" OR "XRR" AND ALL OTHER ADDITIONAL ITEMS THAT ARE NOT SHOWN BUT THAT MUST BE REMOVED IN ORDER TO PRODUCE A NEAT, FINISHED, PROPERLY FUNCTIONING ELECTRICAL INSTALLATION. MAINTAIN CIRCUIT CONTINUITY TO ALL EXISTING REUSED ELECTRICAL SYSTEMS COMPONENTS - PROVIDE ALL CONDUIT AND WIRING NECESSARY TO ACHIEVE THE SAME. THE CONTRACTOR SHALL FIELD VERIFY THE NATURE AND EXTENT OF ALL DEMOLITION

WORK AND SHALL INCLUDE COST FOR THE SAME IN THE BID SUBMITTAL.

D2 ALL EXISTING REMOVED TECHNOLOGY EQUIPMENT, DEVICES, ETC. THAT ARE NOT RETAINED BY THE OWNER

SHALL BE DISPOSED OF BY THE ELECTRICAL CONTRACTOR.

D3 DASHED WALLS ON PLAN INDICATE EXISTING CONSTRUCTION TO BE REMOVED.

D4 REFER TO TECHNOLOGY LEGEND FOR ALL SYMBOL DESIGNATIONS. NOTE SPECIAL ATTENTION TO SELECTED EXISTING DEVICES, WIREWAYS, ETC. MARKED XB, XRR OR XN, AND REMOVE/BLANK OFF, RELOCATE OR REPLACE

THESE COMPONENTS AS REQUIRED.

D6 THE TELECOMMUNICATIONS CONTRACTOR SHALL CLOSELY COORDINATE ALL TECHNOLOGY DEMOLITION WORK WITH THE GENERAL AND MECHANICAL CONTRACTORS, AND SHALL DISCONNECT ALL REQUIRED CIRCUITS IN A

TIMELY MANNER.

N

# TECHNOLOGY CODED NOTES

EXISTING CABLING IS ROUTED FROM ABOVE FINISHED CEILING TO BELOW RAISED FLOOR LEVEL IN THIS LOCATION AND TRANSITIONS FROM BATTERY ROOM TO MCR VIA EXISTING CONDUIT SLEEVES THROUGH WALL. EXISTING CABLING INCLUDES (6) 50-PAIR CAT3 COPPER BUNDLE CABLES, (8) BLUE CAT5E CABLES, (5) WHITE CAT5E CABLES, (1) 12-STRAND SINGLE-MODE FIBER OPTIC BUNDLE CABLE AND (1) 12-STRAND, 50/125 MULTI-MODE FIBER OPTIC BUNDLE CABLE. EXISTING CABLING SHALL BE REPLACED WITH NEW AND DEMOLISHED COMPLETE BACK TO SOURCE AFTER EXISTING LOADS ARE CUTOVER TO NEW CABLING. REFER

TO NEW TECHNOLOGY PLAN - PHASE 1 FOR ADDITIONAL INFORMATION.

REMOVE EXISTING TELECOMMUNICATIONS OUTLETS AND CABLING COMPLETE BACK TO SOURCE.2

TECHNOLOGY PROTECTION GENERAL NOTE

DATA CENTER EXISTING EQUIPMENT MUST REMAIN OPERATIONAL AT ALL TIMES UNLESS A SHUTDOWN REQUEST IS APPROVED BY VA COR FOR INDIVIDUAL SYSTEMS AS REQUIRED UNDER THE SCOPE OF THIS PROJECT. EXISTING EQUIPMENT MUST REMAIN FREE OF CONSTRUCTION DEBRIS AND MUST REMAIN OPEN TO COOLING AND VENTILATION TO MEET MANUFACTURER'S OPERATING TEMPERATURE REQUIREMENTS. CONTRACTOR SHALL RETAIN VALUE FACILITY SERVICES (CONTACT KURT YANTZ, PH. #800-583-8374) TO PROTECT EXISTING TELECOMMUNICATIONS EQUIPMENT DURING DEMOLITION. COORDINATE PROTECTION REQUIREMENTS WITH VA COR

AND VA OIT.

NOT TO SCALE

EXISTING CABLING FIELD CONDITIONS 2

H

L

L1

L2

L3

39 4241403836a

Z3

X

D1 D2

F1 F2 G1 G2 G3 G4 G5 H1 H2 H3

DEMARC X

X X X X X X

X

EXISTING

ALT DATA

CABINET

PHONE SYSTEM COPPER BACKBONE AND TERMINATIONS

X X X X X X X X

PAGING

SYSTEM

CABINETS

EXISTING ANALOG

PHONE EQUIPMENT

EXISTING (2)

2 POST RACKS

EXISTING PHONE

CABINETS

EXISTING 2

POST RACK

E1 E2

BATTERY

CABINET

X X

ANALOG PHONE

SYSTEM

RECTIFIER

EXISTING FIBER TIP

AND EQUIPMENT CABINETS

X

X X

X

X

EXISTING

TELECOM GROUND BAR

(TGB)

XR

FIRE RATED

PATHWAYS

X

FIRE RATED

PATHWAYS

X

X

X

X

X

X

X

FD

B1

B2

B3

E1

E2

A1 A2 A3 A4 A5 A6

XX X X

X X

X

XX

S

59459

M.P. LONG

R

ES

O F

I R

GE

NOI

S

P

E

N E

DERT

L EA

E I N

G

R

TS

TEA HF OO

IO

DESIGN AND CONSTRUCTION DOCUMENTS AS

INSTRUMENTS OF SERVICE ARE GIVEN IN

CONFIDENCE AND REMAIN THE PROPERTY OF

PERSPECTUS ARCHITECTURE. THE USE OF THIS

DESIGN AND THESE CONSTRUCTION

DOCUMENTS

FOR PURPOSES OTHER THAN THE SPECIFIC

PROJECT NAMED HEREIN IS STRICTLY

PROHIBITED WITHOUT THE EXPRESSED WRITTEN

CONSENT OF PERSPECTUS ARCHITECTURE.

COPYRIGHT C 2018.

13212 Shaker Square Suite 204 Cleveland, Ohio 44120 P. 216.752.1800 F. 216.752.3833

CONSULTANTS: ARCHITECT:

Drawing Title

Approved: Project Director Location

Project Title

Date Checked Drawn

Drawing Number

Building Number

Project Number

Office of

Facilities

Management

Dwg. of o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t

VA FORM 08-6231, OCT 1978

1 2 3 4 5 6 7 8 9 10

A

1 2 3 4 5 6 7 8 9 10

B

C

D

E

F

A

B

C

D

E

F

VAMC - WADE PARK

Revisions: Date

FULLY SPRINKLERED

18077

FREDRICK, FREDRICK & HELLER

ENGINEERS, INC.

672 EAST ROYALTON ROAD

BROADVIEW HTS., OHIO 44147

TEL. (440)546-9696

FAX: (440)546-9699

BID ISSUE 4/13/20

Increase IRM Physical

Security

541-19-102

CPCMPL

PARTIAL THIRD FLOOR

TECHNOLOGY DEMOLITION PLAN

- PHASE 2

T2.2 4/13/20

0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'

1/4" = 1'-0"

PARTIAL THIRD FLOOR

TECHNOLOGY DEMOLITION PLAN - PHASE 2 1N

TECHNOLOGY DEMOLITION NOTES

D1 ALL EXISTING TELECOMMUNICATIONS OUTLETS, NURSE CALL DEVICES, CONDUIT, WIRING ETC. THAT WILL NOT BE

REUSED IN THE REMODELED INSTALLATION SHALL BE REMOVED UNLESS OTHERWISE NOTED. THIS DEMOLITION SHALL INCLUDE ALL ELECTRICAL ITEMS SHOWN ON THIS PLAN THAT ARE NOT DESIGNATED BY "X", "XN" OR "XRR" AND ALL OTHER ADDITIONAL ITEMS THAT ARE NOT SHOWN BUT THAT MUST BE REMOVED IN ORDER TO PRODUCE A NEAT, FINISHED, PROPERLY FUNCTIONING ELECTRICAL INSTALLATION. MAINTAIN CIRCUIT CONTINUITY TO ALL EXISTING REUSED ELECTRICAL SYSTEMS COMPONENTS - PROVIDE ALL CONDUIT AND WIRING NECESSARY TO ACHIEVE THE SAME. THE CONTRACTOR SHALL FIELD VERIFY THE NATURE AND EXTENT OF ALL DEMOLITION

WORK AND SHALL INCLUDE COST FOR THE SAME IN THE BID SUBMITTAL.

D2 ALL EXISTING REMOVED TECHNOLOGY EQUIPMENT, DEVICES, ETC. THAT ARE NOT RETAINED BY THE OWNER

SHALL BE DISPOSED OF BY THE ELECTRICAL CONTRACTOR.

D3 DASHED WALLS ON PLAN INDICATE EXISTING CONSTRUCTION TO BE REMOVED.

D4 REFER TO TECHNOLOGY LEGEND FOR ALL SYMBOL DESIGNATIONS. NOTE SPECIAL ATTENTION TO SELECTED EXISTING DEVICES, WIREWAYS, ETC. MARKED XB, XRR OR XN, AND REMOVE/BLANK OFF, RELOCATE OR REPLACE

THESE COMPONENTS AS REQUIRED.

D6 THE TELECOMMUNICATIONS CONTRACTOR SHALL CLOSELY COORDINATE ALL TECHNOLOGY DEMOLITION WORK WITH THE GENERAL AND MECHANICAL CONTRACTORS, AND SHALL DISCONNECT ALL REQUIRED CIRCUITS IN A

TIMELY MANNER.

# TECHNOLOGY CODED NOTES

REMOVE EXISTING TELECOMMUNICATIONS CABINETS COMPLETE AFTER VA OIT TRANSITIONS EXISTING FACILITY SYSTEMS EQUIPMENT (LENEL, PATIENT WIRELESS, AND HILLROM) TO NEW EQUIPMENT RACKS IN

NEW FMS ROOM. COORDINATE REMOVAL WITH VA COR AND VA OIT.

EXISTING (5) 4" CONDUITS WITH CAT3 AND OPTICAL FIBER BUNDLE CABLING ROUTED FROM ABOVE FINISHED CEILING TO BELOW RAISED FLOOR. CONTRACTOR SHALL PROVIDE NEW STEEL CHANNEL SUPPORT STRUCTURE TO RE-SUPPORT EXISTING CONDUITS PRIOR TO DEMOLITION OF EXISTING WALL. CONDUITS ARE

EXISTING TO REMAIN.

TECHNOLOGY PROTECTION GENERAL NOTE

DATA CENTER EXISTING EQUIPMENT MUST REMAIN OPERATIONAL AT ALL TIMES UNLESS A SHUTDOWN REQUEST IS APPROVED BY VA COR FOR INDIVIDUAL SYSTEMS AS REQUIRED UNDER THE SCOPE OF THIS PROJECT. EXISTING EQUIPMENT MUST REMAIN FREE OF CONSTRUCTION DEBRIS AND MUST REMAIN OPEN TO COOLING AND VENTILATION TO MEET MANUFACTURER'S OPERATING TEMPERATURE REQUIREMENTS. CONTRACTOR SHALL RETAIN VALUE FACILITY SERVICES (CONTACT KURT YANTZ, PH. #800-583-8374) TO PROTECT EXISTING TELECOMMUNICATIONS EQUIPMENT DURING DEMOLITION. COORDINATE PROTECTION REQUIREMENTS WITH VA COR AND VA OIT.

H

L

L1

L2

L3

39 4241403836a

Z3

D1 D2

XX

NEW

NEW

NEW

F R

O N

T

F R

O N

T

DEMARC

AREA

X

NEW NEW

NEW

NEW

6 6

X X X X X X

CAB.

A1

CAB.

A2

CAB.

A3

CAB.

A4

CAB.

A5

CAB.

A6

FACILITY MANAGEMENT

RACKS

X X X

FINAL

BATTERY

CABINET

NEW

(VAF/VAI)

NEW

(VAF/VAI)

PHONE SYSTEM

RECTIFIER

SM SM

PHONE SYSTEM COPPER BACKBONE AND TERMINATIONS

PHONE EQUIPMENT

(2)

2-POST

RACKS

PHONE

CABINETS

EXISTING

2-POST RACK

H1 H2 H3G1 G2 G3 G4 G5F1 F2 F3 F4

X X X X X X X X

X

X X X

X

PAGING

SYSTEM

CABINETS

CAB.

FD

CAB.

B1

CAB.

B2

CAB.

B3

NEW

NEW

NEW

CAB.

E2

CAB.

E1

T3.1

T3.1

7 7

MCR-1

3A133-1

BATTERY

3A-135A

FMS-1

3A135-1

MCOR-1

3A135B-1

Tele Health

3A137

Toilet/ Shower

3A137A

Corridor

3A100E

2 Bedroom

3A131

EMS

3A128

L.C.

3A130

L.C.

3A132

EMS

3A134

BB475

Passage

3AC312

HAC

3AC311

X

TGB8

TEMPORARY

BATTERY

CABINET

NEW

(VAF/VAI)

2 2

NEW

NEW

NEW 40KW

480V-480V

UPS-B

A/C

PREACTION

PANEL

BATTERIES

B A

T T

E R

IE

S

X

X

X

X

X

EXISTING ALT

DATA RACK

RECTIFIER

RACKS

A/CX

X

A/CX

EXISTING UPS

SBS

FOTP

FUTURE

(N.I.C.)

S2.01

S2.01

S2.01 10

CRAC-4

CRAC-3

S2.01 10

PROVIDE (2) NEW 50-PAIR

66-BLOCK TERMINATION

STRIP AND TERMINATE

NEW CAT3 CABLING.

PROVIDE (2) NEW 100-PAIR

66-BLOCK TERMINATION

STRIP AND TERMINATE

NEW CAT3 CABLING.

RELOCATE EXISTING

SURFACE MOUNTED

TCOs AS REQUIRED TO

ACCOMMODATE NEW

TERMINATION BLOCK

INSTALLATION.

PROVIDE NEW GROUND CONDUCTORS

FROM EXISTING EQUIPMENT TO NEW

GROUND BAR LOCATION. REFER TO CODED

NOTE #8 FOR ADDITIONAL INFORMATION

(TYPICAL FOR ALL EXISTING CONNECTIONS)

S

59459

M.P. LONG

R

ES

O F

I R

GE

NOI

S

P

E

N E

DERT

L EA

E I N

G

R

TS

TEA HF OO

IO

DESIGN AND CONSTRUCTION DOCUMENTS AS

INSTRUMENTS OF SERVICE ARE GIVEN IN

CONFIDENCE AND REMAIN THE PROPERTY OF

PERSPECTUS ARCHITECTURE. THE USE OF THIS

DESIGN AND THESE CONSTRUCTION

DOCUMENTS

FOR PURPOSES OTHER THAN THE SPECIFIC

PROJECT NAMED HEREIN IS STRICTLY

PROHIBITED WITHOUT THE EXPRESSED WRITTEN

CONSENT OF PERSPECTUS ARCHITECTURE.

COPYRIGHT C 2018.

13212 Shaker Square Suite 204 Cleveland, Ohio 44120 P. 216.752.1800 F. 216.752.3833

CONSULTANTS: ARCHITECT:

Drawing Title

Approved: Project Director Location

Project Title

Date Checked Drawn

Drawing Number

Building Number

Project Number

Office of

Facilities

Management

Dwg. of o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t

VA FORM 08-6231, OCT 1978

1 2 3 4 5 6 7 8 9 10

A

1 2 3 4 5 6 7 8 9 10

B

C

D

E

F

A

B

C

D

E

F

VAMC - WADE PARK

Revisions: Date

FULLY SPRINKLERED

18077

FREDRICK, FREDRICK & HELLER

ENGINEERS, INC.

672 EAST ROYALTON ROAD

BROADVIEW HTS., OHIO 44147

TEL. (440)546-9696

FAX: (440)546-9699

BID ISSUE 4/13/20

Increase IRM Physical

Security

541-19-102

CPCMPL

PARTIAL THIRD FLOOR

TECHNOLOGY PLAN - PHASE 1

T3.1 4/13/20

0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'

1/4" = 1'-0"

PARTIAL THIRD FLOOR

TECHNOLOGY PLAN - PHASE 1 1

TECHNOLOGY GENERAL NOTES

T1 REFER TO THE ARCHITECTURAL PLANS FOR EQUIPMENT LAYOUT. CLOSELY COORDINATE THE EXACT LOCATION OF

ALL OUTLETS AND DEVICES WITH ARCHITECTURAL ELEVATIONS. ADJUST LOCATIONS AND MOUNTING HEIGHTS WHERE NECESSARY TO PREVENT INTERFERENCE WITH FURNITURE, FIXED CASEWORK, EQUIPMENT, ETC. VERIFY

ALL CHANGES PRIOR TO ROUGH-IN.

T2 CONTRACTOR SHALL VERIFY ALL EQUIPMENT LOCATIONS, MOUNTING HEIGHTS, AND CONNECTION REQUIREMENTS

(DATA OUTLETS, ETC) WITH EQUIPMENT VENDOR PRIOR TO ROUGH-IN.

T3 ALL NEW TECHNOLOGY UNTILITIES IN CORRIDORS SHALL BE ROUTED AS HIGH AS POSSIBLE.

T4 REFER TO ARCHITECTURAL PLANS FOR EXACT PHASING REQUIREMENTS.

N

# TECHNOLOGY CODED NOTES

PROVIDE (6) NEW 50-PAIR CAT3 COPPER BUNDLE CABLES (INDOOR, PLENUM RATED) FROM DEMARC AREA TO PHONE SYSTEM RACKS IN MAIN COMPUTER ROOM (MCR). ROUTE CABLING IN NEW CABLE TRAY TO MCR AND TRANSITION TO NEW J-HOOKS ON 5'-0" CENTERS OVER TO PHONE RACKS. ROUTE CABLING AS HIGH AS POSSIBLE IN J-HOOKS. PROVIDE (6) NEW 50-PAIR PUNCHDOWN BLOCKS IN DEMARC AREA AND IN EXISTING

PHONE RACKS AND TERMINATE NEW CABLING. COORDINATE EXACT PUNCHDOWN BLOCK MOUNTING

LOCATION WITH VA OIT. ASSUME 100FT LENGTH PER CABLE FOR BIDDING PURPOSES. VA SHALL RE-PATCH EXISTING LOADS AT BOTH ENDS TO ABANDON EXISTING CABLING ROUTED THROUGH BATTERY ROOM TO FACILITATE DEMOLITION OF EXISTING CABLES. REFER TO DETAIL #2 ON THIS SHEET FOR ADDITIONAL

INFORMATION.

PROVIDE (1) 12-STRAND, 50/125 MULTI-MODE FIBER OPTIC CABLE AND (1) 12-STRAND, SINGLE-MODE FIBER OPTIC CABLE ROUTED FROM FIBER TELECOMMUNICATION INFORMATION PLANT (TIP) RACKS (RACKS A1, A2, AND A3) IN MCR AND TERMINATE IN EXISTING FIBER TERMINATION BOX IN DEMARC AREA. CABLES SHALL BE ARMORED CLAD, PLENUM RATED. ROUTE CABLING VIA NEW CABLE TRAY. EXISTING FIBER TERMINATION BOXES HAVE A 24-STRAND CAPACITY WITH AVAILABILITY TO TERMINATE 12-STRANDS. EXISTING 12-STRAND MM FIBER IS TERMINATED IN THIS LOCATION. CONTRACTOR SHALL PROVIDE NEW 12-STRAND MM FIBER IN SPARE 12-STRAND TERMINATION AREA. VA SHALL RE-PATCH FIBER AT BOTH ENDS TO ABANDON THE EXISTING 12- STRANDS OF MM FIBER ROUTED THROUGH BATTERY ROOM TO FACILITATE DEMOLITION OF EXISTING CABLE.

CONTRACTOR SHALL DISCONNECT ABANDONED MM FIBER AND PROVIDE NEW SINGLE-MODE FIBER

TERMINATED IN NEWLY CREATED SPARE CAPACITY. VA SHALL RE-PATCH FIBER AT BOTH ENDS TO ABANDON THE EXISTING 12-STRANDS OF SM FIBER. BOTH ABANDONED FIBER OPTIC CABLES SHALL BE REMOVED COMPLETE ONCE EXISTING SYSTEMS ARE RE-PATCHED. ASSUME 100FT LENGTH PER CABLE FOR BIDDING

PURPOSES.

PROVIDE NEW CAT6A CABLING TO ABANDON EXISTING (8) BLUE AND (5) WHITE CAT5E CABLING ROUTED THROUGH BATTERY ROOM. ASSUME ALL (13) CABLES ARE TO BE REPLACE AND ROUTED FROM SOURCE TO DESTINATION AND RECONNECTED TO FACILITATE DEMOLITION OF EXISTING CABLING. ASSUME 300FT LENGTH

PER CABLE FOR BIDDING PURPOSES.

CONTRACTOR SHALL PROVIDE NEW 45U CABINET FOR FACILITY MANAGEMENT SERVICES (FMS). COORDINATE INSTALLATION WITH VA COR AND OIT. REFER TO CABINET SPECIFICATIONS ON THIS SHEET AND POWER PLANS

FOR ADDITIONAL INFORMATION AND WORK REQUIREMENTS.

NEW FIBER OPTIC DISTRIBUTION RACK. PROVIDE 72-STRAND, 50/125 MULTI-MODE FIBER OPTIC CABLE AND 72- STRAND, SINGLE-MODE FIBER OPTIC CABLE FROM NEW DISTRIBUTION RACK TO EXISTING FIBER TIP IN MCR.

FIBER OPTIC BUNDLE CABLES SHALL BE ARMORED CLAD, PLENUM RATED, FIBER OPTIC CABLE AND SHALL EACH BE TERMINATED IN A NEW FIBER TERMINATION BOX AT EACH LOCATION. REFER TO TECHNOLOGY RACK

DETAILS FOR ADDITIONAL INFORMATION.

PROVIDE NEW 18"W x 4"H CABLE TRAY APPROXIMATELY AT LOCATION SHOWN. PROVIDE CABLE TRAY AT APPROXIMATELY 7'-0" ABOVE RAISED FLOOR. COORDINATE CABLE TRAY HEIGHT WITH NEW DUCTWORK. IF POSSIBLE, MATCH MOUNTING HEIGHT OF EXISTING CABLE TRAY IN MCR ABOVE FIBER RACK. IF NOT POSSIBLE, MOUNT CABLE TRAY LOW ENOUGH TO AVOID INTERFERENCE WITH DUCTWORK AND RAMP CABLE TRAY TO

MATCH EXISTING MOUNTING HEIGHT AT RACKS.

PROVIDE (2) SETS OF (4) 4"SQ. FIRE-RATED PATHWAYS EACH CONSISTING OF ENCLOSED HEAVY GAUGE GALVANIZED STEEL PATHWAY CONTAINING BUILT-IN FIRE SEALING SYSTEM SUFFICIENT TO MAINTAIN THE HOURLY FIRE RATING OF THE BARRIER BEING PENETRATED. THE SELF CONTAINED SEALING SYSTEM SHALL AUTOMATICALLY ADJUST TO THE INSTALLED CABLE LOADING AND SHALL PERMIT THE CABLES TO BE INSTALLED, REMOVED, OR RETROFIT WITHOUT THE NEED TO REMOVE OR REINSTALL THE FIRE-STOPPING MATERIAL. THE PATHWAY SHALL BE UL LISTED AND TESTED TO THE REQUIREMENTS OF ASTM E814.

EXISTING TELECOMMUNICATIONS GROUND BAR (TGB) SHALL BE DEMOLISHED IN PHASE 2. RELOCATE EXISTING BONDING CONDUCTORS COMPLETE TO NEW TGB LOCATION AND RECONNECT COMPLETE. ASSUME

(3) #1/0AWG, (3) #1AWG, AND (4) #6AWG CONDUCTORS WITH 150FT OF LENGTH EACH FOR BIDDING PURPOSES.

REFER TO DETAIL #3 ON THIS SHEET FOR ADDITIONAL INFORMATION.

PROVIDE NEW COPPER GROUNDING BUSBARS WALL MOUNTED ON INSULATORS AT 18" AFF PER

SPECIFICATIONS IN AVAILABLE SPACE IN MCR AND FMS ROOMS. BOND BUSBARS TOGETHER VIA #3/0 AWG GROUND CONDUCTOR. BOND ALL TELECOM EQUIPMENT RACKS, CABINETS, UPS EQUIPMENT, LADDER TRAYS, AND EQUIPMENT ENCLOSURES TO BUSBAR WITH #6AWG GREEN INSULATED STRANDED COPPER BONDING

CABLE VIA 2-BOLT HOLE COMPRESSION LUG CONNECTOR.

PROVIDE SBC SYSTEM TCO FOR EQUIPMENT INDICATED. PROVIDE CAT6A CABLES AND TERMINATE TO PATCH PANEL AT FOTP INDICATED. PROVIDE PATCH CABLE AND ACTIVATE PORT VIA SMART BUILDING SYSTEM SWITCH. PROVIDE SMART BUILDING SYSTEM PROGRAMMING TO DISPLAY EQUIPMENT DATA ON SMART BUILDING SYSTEM SCREEN. COORDINATE DATA TO BE DISPLAY WITH VA COR PRIOR TO PROGRAMMING.

NOT TO SCALE

CAT3 TERMINATION LOCATIONS 2

NOT TO SCALE

EXISTING TGB CONDITIONS 3

CABINET SPECIFICATIONS

CABINET:

• APC NETSHELTER SX

• MANUFACTURER PART #: 42UAR3140

RACK LOCK KIT:

• NETBOTZ RACK ACCESS POD 170

• MANUFACTURER PART #: NBPD0171

POWER DISTRIBUTION:

• APC RACK PDU STRIP

• 30A-280V-1PH

• (16) 5-20R, (1) C19 AND (7) C13 OUTLETS

• MANUFACTURER PART #: AP8970

TECHNOLOGY PROTECTION GENERAL NOTE

DATA CENTER EXISTING EQUIPMENT MUST REMAIN OPERATIONAL AT ALL TIMES UNLESS A SHUTDOWN REQUEST IS APPROVED BY VA COR FOR INDIVIDUAL SYSTEMS AS REQUIRED UNDER THE SCOPE OF THIS PROJECT. EXISTING EQUIPMENT MUST REMAIN FREE OF CONSTRUCTION DEBRIS AND MUST REMAIN OPEN TO COOLING AND VENTILATION TO MEET MANUFACTURER'S OPERATING TEMPERATURE REQUIREMENTS. CONTRACTOR SHALL RETAIN VALUE FACILITY SERVICES (CONTACT KURT YANTZ, PH. #800-583-8374) TO PROTECT EXISTING TELECOMMUNICATIONS EQUIPMENT DURING DEMOLITION. COORDINATE PROTECTION REQUIREMENTS WITH VA COR AND VA OIT.

H

L

L1

L2

L3

39 4241403836a

Z3

DEMARC

X

X X

X

X

X

EXISTING 2

POST RACK

ALT

DATA

CABINET

BATTERY

CABINET

X

PHONE

SYSTEM

RECTIFIER

X

X X

X

SM SM

EXISTING FIBER TIP

AND EQUIPMENT CABINETS

A1 A2 A3 A4 A5 A6

FD

B1

B2

B3

X

X

X

X

E1 X

E2 X

FUTURE TELECOMMUNICATIONS CABINETS

PHONE SYSTEM COPPER BACKBONE AND TERMINATIONS

ANALOG

PHONE EQUIPMENT(2) 2-POST RACKS

PHONE

CABINETS

EXISTING 2

POST RACK

H1 H2 H3G1 G2 G3 G4 G5F1 F2 F3 F4

X X X X X X X X

X

X X X

X

X X X X X X

EX.

FIRE RATED

PATHWAYS

EX.

FIRE RATED

PATHWAYS

C1 C2 C3 C4 C5 C6

MCR-2

3A133-2

FMS-2

3A135-2

MCOR-2

3A135B-2

TGB

X

TGB

X

X

X X

X

UPS

UPS

PREACTION

PANEL

X

SBS

FOTP

FUTURE

(N.I.C.)

X

X

S2.01

S2.011

S2.011

S2.01

S

59459

M.P. LONG

R

ES

O F

I R

GE

NOI

S

P

E

N E

DERT

L EA

E I N

G

R

TS

TEA HF OO

IO

DESIGN AND CONSTRUCTION DOCUMENTS AS

INSTRUMENTS OF SERVICE ARE GIVEN IN

CONFIDENCE AND REMAIN THE PROPERTY OF

PERSPECTUS ARCHITECTURE. THE USE OF THIS

DESIGN AND THESE CONSTRUCTION

DOCUMENTS

FOR PURPOSES OTHER THAN THE SPECIFIC

PROJECT NAMED HEREIN IS STRICTLY

PROHIBITED WITHOUT THE EXPRESSED WRITTEN

CONSENT OF PERSPECTUS ARCHITECTURE.

COPYRIGHT C 2018.

13212 Shaker Square Suite 204 Cleveland, Ohio 44120 P. 216.752.1800 F. 216.752.3833

CONSULTANTS: ARCHITECT:

Drawing Title

Approved: Project Director Location

Project Title

Date Checked Drawn

Drawing Number

Building Number

Project Number

Office of

Facilities

Management

Dwg. of o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t

VA FORM 08-6231, OCT 1978

1 2 3 4 5 6 7 8 9 10

A

1 2 3 4 5 6 7 8 9 10

B

C

D

E

F

A

B

C

D

E

F

VAMC - WADE PARK

Revisions: Date

FULLY SPRINKLERED

18077

FREDRICK, FREDRICK & HELLER

ENGINEERS, INC.

672 EAST ROYALTON ROAD

BROADVIEW HTS., OHIO 44147

TEL. (440)546-9696

FAX: (440)546-9699

BID ISSUE 4/13/20

Increase IRM Physical

Security

541-19-102

CPCMPL

PARTIAL THIRD FLOOR

TECHNOLOGY PLAN - PHASE 2

T3.2 4/13/20

TECHNOLOGY GENERAL NOTES

T1 REFER TO THE ARCHITECTURAL PLANS FOR EQUIPMENT LAYOUT. CLOSELY COORDINATE THE EXACT LOCATION OF

ALL OUTLETS AND DEVICES WITH ARCHITECTURAL ELEVATIONS. ADJUST LOCATIONS AND MOUNTING HEIGHTS WHERE NECESSARY TO PREVENT INTERFERENCE WITH FURNITURE, FIXED CASEWORK, EQUIPMENT, ETC. VERIFY

ALL CHANGES PRIOR TO ROUGH-IN.

T2 CONTRACTOR SHALL VERIFY ALL EQUIPMENT LOCATIONS, MOUNTING HEIGHTS, AND CONNECTION REQUIREMENTS

(DATA OUTLETS, ETC) WITH EQUIPMENT VENDOR PRIOR TO ROUGH-IN.

T3 ALL NEW TECHNOLOGY UNTILITIES IN CORRIDORS SHALL BE ROUTED AS HIGH AS POSSIBLE.

T4 REFER TO ARCHITECTURAL PLANS FOR EXACT PHASING REQUIREMENTS.

0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'

1/4" = 1'-0"

PARTIAL THIRD FLOOR

TECHNOLOGY PLAN - PHASE 2 1N

TECHNOLOGY PROTECTION GENERAL NOTE

DATA CENTER EXISTING EQUIPMENT MUST REMAIN OPERATIONAL AT ALL TIMES UNLESS A SHUTDOWN REQUEST IS APPROVED BY VA COR FOR INDIVIDUAL SYSTEMS AS REQUIRED UNDER THE SCOPE OF THIS PROJECT. EXISTING EQUIPMENT MUST REMAIN FREE OF CONSTRUCTION DEBRIS AND MUST REMAIN OPEN TO COOLING AND VENTILATION TO MEET MANUFACTURER'S OPERATING TEMPERATURE REQUIREMENTS. CONTRACTOR SHALL RETAIN VALUE FACILITY SERVICES (CONTACT KURT YANTZ, PH. #800-583-8374) TO PROTECT EXISTING TELECOMMUNICATIONS EQUIPMENT DURING DEMOLITION. COORDINATE PROTECTION REQUIREMENTS WITH VA COR AND VA OIT.

# TECHNOLOGY CODED NOTES

PROVIDE SBC SYSTEM TCO FOR EQUIPMENT INDICATED. PROVIDE CAT6A CABLES AND TERMINATE TO PATCH PANEL AT FOTP INDICATED. PROVIDE PATCH CABLE AND ACTIVATE PORT VIA SMART BUILDING SYSTEM SWITCH. PROVIDE SMART BUILDING SYSTEM PROGRAMMING TO DISPLAY EQUIPMENT DATA ON SMART BUILDING SYSTEM SCREEN. COORDINATE DATA TO BE DISPLAY WITH VA COR PRIOR TO PROGRAMMING.

PLAN VIEW

TELECOM GROUNDING BUSBAR (TGB)

4" H

5/16" DIA. TYP.

7/16" DIA. MOUNTING HOLES - TYPICAL

#6AWG TO NEAREST METAL (STEEL) BUILDING FRAME

#6AWG TO UPS EQUIPMENT GROUND BAR

#6AWG TO LADDER RUNWAYS AND CABLE TRAY SYSTEMS

IF THIS CONNECTOR OR CABLE IS LOOSE OR MUST BE REMOVED,

PLEASE CALL THE BUILDING TELECOMMUNICATION MANAGER

WARNING - TELECOM BONDING BUSBAR

FOR TECHNOLOGY EQUIPMENT ONLY -

NOT TO BE USED AS AN ELECTRICAL SYSTEM GROUND

RED POLY INSULATORS,

GRADE 1 - 2" DIA.

4"H x 20"W x 1/4"D COPPER

BONDING BUS BAR

NON-METALLIC WASHER

CONCRETE BLOCK OR

STUD WALL PARTITION

FINISHED SURFACE

5/16" HEX HEAD

BOLTS - LENGTH

AS REQUIRED

H-TYPE IRREVERSIBLE

COMPRESSION TYPE

CONNECTOR - TYPICAL

RACK BONDING

CONDUCTOR (RBC) -

TYP.

TELECOMMUNICATIONS

EQUIPMENT BONDING

CONDUCTOR (TEBC) - TYP.

#6AWG BONDING

CONDUCTOR -

TYP.

TYPICAL DATA RACK OR CABINET

IN MCR #3A-133

NETWORK SWITCH

FURNISHED BY OWNER

FIBER

TERMINATION

HOUSING

PATCH PANEL

TELECOM GROUNDING BUSBAR (TGB)

(RECONNECTION OF EXISTING BONDING CONDUCTORS IS NOT

SHOWN, REFER TO TECHNOLOGY FLOOR PLANS FOR ADDITIONAL

INFORMATION AND WORK REQUIREMENTS)

4" H

5/16" DIA. TYP.

7/16" DIA. MOUNTING HOLES - TYPICAL

#6AWG TO NEAREST METAL (STEEL) BUILDING FRAME

#6AWG TO PREACTION SYSTEM CONTROL PANEL

#6AWG TO ACCESS CONTROL PANEL ENCLOSURE

#6AWG TO LADDER RUNWAYS AND CABLE TRAY SYSTEMS

#6AWG TO EACH CRAC UNIT IN MCR

#6 AWG COMMON

TELECOMMUNICATIONS BACKBONE

BONDING CONDUCTOR (CTBB)

PATCH PANEL

#6AWG BONDING

CONDUCTOR -

TYP.

NETWORK SWITCH

FURNISHED BY OWNER

FIBER

TERMINATION

HOUSING

TELECOMMUNICATIONS

EQUIPMENT BONDING

CONDUCTOR (TEBC) - TYP.

TELECOMMUNICATIONS

EQUIPMENT BONDING

CONDUCTOR (TEBC) - TYP.

TELECOMMUNICATIONS

EQUIPMENT BONDING

CONDUCTOR (TEBC) - TYP.

TELECOMMUNICATIONS

EQUIPMENT BONDING

CONDUCTOR (TEBC) - TYP.

TELECOMMUNICATIONS

EQUIPMENT BONDING

CONDUCTOR (TEBC) - TYP.

TELECOMMUNICATIONS

EQUIPMENT BONDING

CONDUCTOR (TEBC) - TYP.

TELECOMMUNICATIONS

EQUIPMENT BONDING

CONDUCTOR (TEBC) - TYP.

TELECOMMUNICATIONS

EQUIPMENT BONDING

CONDUCTOR (TEBC) - TYP.

TELECOMMUNICATIONS

EQUIPMENT BONDING

CONDUCTOR (TEBC) - TYP.

#6AWG TO UPS EQUIPMENT GROUND BAR

TELECOMMUNICATIONS

EQUIPMENT BONDING

CONDUCTOR (TEBC) - TYP.

#6AWG BONDING

CONDUCTOR -

TYP.

NETWORK SWITCH

FURNISHED BY OWNER

FIBER

TERMINATION

HOUSING

PATCH PANEL PATCH PANEL

#6AWG BONDING

CONDUCTOR -

TYP.

NETWORK SWITCH

FURNISHED BY OWNER

FIBER

TERMINATION

HOUSING

TYPICAL DATA RACK OR CABINET

IN FMS #3A-135

#6AWG TO EACH CRAC UNIT IN FMS ROOM

#6AWG TO EACH EPO SYSTEM CONTROL PANEL

TELECOMMUNICATIONS

EQUIPMENT BONDING

CONDUCTOR (TEBC) - TYP.

VERTICALLY

MOUNTED RACK

BONDING BUSBAR

(RBB) - TYPICAL

VERTICALLY

MOUNTED RACK

BONDING BUSBAR

(RBB) - TYPICAL

PROVIDE GREEN

PHENOLIC LABEL

WITH WHITE LETTERS

S

59459

M.P. LONG

R

ES

O F

I R

GE

NOI

S

P

E

N E

DERT

L EA

E I N

G

R

TS

TEA HF OO

IO

DESIGN AND CONSTRUCTION DOCUMENTS AS

INSTRUMENTS OF SERVICE ARE GIVEN IN

CONFIDENCE AND REMAIN THE PROPERTY OF

PERSPECTUS ARCHITECTURE. THE USE OF THIS

DESIGN AND THESE CONSTRUCTION

DOCUMENTS

FOR PURPOSES OTHER THAN THE SPECIFIC

PROJECT NAMED HEREIN IS STRICTLY

PROHIBITED WITHOUT THE EXPRESSED WRITTEN

CONSENT OF PERSPECTUS ARCHITECTURE.

COPYRIGHT C 2018.

13212 Shaker Square Suite 204 Cleveland, Ohio 44120 P. 216.752.1800 F. 216.752.3833

CONSULTANTS: ARCHITECT:

Drawing Title

Approved: Project Director Location

Project Title

Date Checked Drawn

Drawing Number

Building Number

Project Number

Office of

Facilities

Management

Dwg. of o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t

VA FORM 08-6231, OCT 1978

1 2 3 4 5 6 7 8 9 10

A

1 2 3 4 5 6 7 8 9 10

B

C

D

E

F

A

B

C

D

E

F

VAMC - WADE PARK

Revisions: Date

FULLY SPRINKLERED

18077

FREDRICK, FREDRICK & HELLER

ENGINEERS, INC.

672 EAST ROYALTON ROAD

BROADVIEW HTS., OHIO 44147

TEL. (440)546-9696

FAX: (440)546-9699

BID ISSUE 4/13/20

Increase IRM Physical

Security

541-19-102

CPCMPL

TECHNOLOGY GROUNDING

DETAILS

T4.1 4/13/20

NOT TO SCALE

TELECOMMUNICATIONS GROUNDING DETAIL 4

EXISTING 40RU CABINET

CABINET A1

NEW FIBER OPTIC BACKBONE CABLING

TO NEW FMS ROOM FIBER TERMINATION

BOXES

(72 STRANDS 60/125 MULTI-MODE

AND 72 STRANDS SINGLE-MODE)

EX. 144-STRAND

MULTI-MODE (MM)

FIBER TERMINATION BOX

EX. 24-STRAND SM FIBER BOX

EX. 48-PORT SWITCH

EX. CISCO CATALYST 6500E

CORE SWITCH

(1) 48-PORT COPPER CARD

(3) 48-PORT FIBER CARDS

(2) 10Gb ETHERNET CARDS

(1) SUPERVISOR CARD

(4) BLANK SLOTS

EX. 72-STRAND

FIBER TERMINATION BOX

EX. 72-STRAND

FIBER TERMINATION BOX

EXISTING 40RU CABINET

CABINET A2

EX. 72-STRAND

MULTI-MODE (MM)

FIBER TERMINATION BOX

EX. 72-STRAND

MULTI-MODE (MM)

FIBER TERMINATION BOX

EX. 72-STRAND

MULTI-MODE (MM)

FIBER TERMINATION BOX

EX. 72-STRAND

MULTI-MODE (MM)

FIBER TERMINATION BOX

EX. 72-STRAND

MULTI-MODE (MM)

FIBER TERMINATION BOX

EX. 72-STRAND

MULTI-MODE (MM)

FIBER TERMINATION BOX

EX. CABLE MANAGEMENT

EX. 24-STRAND MM FIBER BOX

EX. 24-STRAND MM FIBER BOX

EX. 24-STRAND MM FIBER BOX

EXISTING 40RU CABINET

EX. CISCO CATALYST 6500

CORE SWITCH

(1) 48-PORT COPPER CARD

(2) 48-PORT FIBER CARDS

(2) 10Gb ETHERNET CARDS

(1) SUPERVISOR CARD

(4) BLANK SLOTS

EX. 48-STRAND MM

FIBER TERMINATION BOX

EX. 48-PORT SWITCH

EX. CABLE MANAGEMENT

CABINET A3

EXISTING 40RU CABINET

CABINET A4

EX. 48-STRAND MM

FIBER TERMINATION BOX

EX. CABLE MANAGEMENT

EX. 48-STRAND SM

FIBER TERMINATION BOX

EX. 72-STRAND SM & MM

FIBER TERMINATION BOX

EX. 144-STRAND SM

FIBER TERMINATION BOX

EX. 48-STRAND SM FIBER BOX

EX. 72-STRAND FIBER BOX

EX. 72-STRAND

FIBER TERMINATION BOX

EX. 72-STRAND

FIBER TERMINATION BOX

EX. 24-STRAND MM FIBER BOX

EX. 24-STRAND MM FIBER BOX

EXISTING 40RU CABINET

CABINET A5

EX. 12-STRAND FIBER BOX

EX. CISCO

4300 SERIES ROUTER

EX. TIME WARNER SWITCH

EX. CISCO 3300 MOBILITY ENG.

EX. CISCO 8500 WIRELESS CT.

EX. CISCO 8500 ID SERV. ENG.

EX. CISCO 8500 WIRELESS CT.

EX. GIGAMON NODE

(2) RU FOR FIBER GBICS

(1) RU FOR FIBER TERM.

EX. FORESCOUT

COUNTERACT NAC

EX. FORESCOUT

COUNTERACT NAC

EX. NGENIUS INFINISTREAM

EXISTING 42RU CABINET

CABINET A6

EX. 24-PORT PATCH PANEL

EX. STEELHEAD RIVERBED

WAN OPTIMIZATION

EX. NGENIUS INFINISTREAM

EX. CISCO ASR 1006 ROUTER

(1) ASR 1000-SIP-BLANK

(2) ASR 1000-SIP10

(1) ASR 1000-ESP BLANK

(1) ASR 1000-ESP20

(1) ASR 1000-RP BLANK

(1) ASR 1000-RP1

EX. CISCO ASR 1006 ROUTER

(1) ASR 1000-SIP-BLANK

(2) ASR 1000-SIP10

(1) ASR 1000-ESP BLANK

(1) ASR 1000-ESP20

(2) ASR 1000-RP1

EX. CABLE MANAGEMENT

NEW 144-STRAND CAPACITY

MM FIBER TERMINATION BOX

NEW 144-STRAND CAPACITY

SM FIBER TERMINATION BOX

NEW 42RU CABINET

CABINET FD

42NEW 144-STRAND CAPACITY

MM FIBER TERMINATION BOX

NEW 144-STRAND CAPACITY

SM FIBER TERMINATION BOX

CABINET B1

CABINET B2

CABINET B3

NEW PAIR 62.5 MULTIMODE

FIBER OPTIC CABLE

NEW LENEL PANELS

WITH 2020 AND 1320

DEVICES INCLUDED.

REFER TO ENLARGED

OIT PLANS

NEW GREEN

CAT6A CABLE

CAMERAS

(TYPICAL)

NEW GREEN

CAT6A CABLE

EXISTING

COMMUNICATION ROOMS

EQUIPMENT WITH NEW

LENEL SWITCH

EXISTING TELECOM ROOM

FIBER PATCH PANEL

KEY SAFE

EXISTING PAIR 62.5

MULTIMODE

FIBER OPTIC CABLE

EXISTING LENEL

PANELS

WITH 2020 AND 1320

DEVICES. REFER TO

ENLARGED OIT PLANS

EXISTING GREEN

CAT6 CABLE

CAMERAS

(TYPICAL)

NEW GREEN

CAT6A CABLE

EXISTING

COMMUNICATION ROOMS

EQUIPMENT WITH EXISTING

LENEL SWITCH

EXISTING TELECOM ROOM

FIBER PATCH PANEL

X

X

X

EXISTING LENEL

SWITCH

EXISTING MULTI-MODE

FIBER BUNDLE BETWEEN TR

ROOM AND MCR WITH (1)

PAIR PATCHED TO EXISTING

LENEL SYSTEM

EXISTING MULTI-MODE

FIBER BUNDLE BETWEEN TR

ROOM AND MCR WITH (1)

PAIR PATCHED TO EXISTING

LENEL SYSTEM

PROVIDE FIBER PATCH TO

CONNECT NEW FIBER

COMPLETE TO NEW

MULTIMODE FIBER

TERMINATION BOX.

RELOCATED 4507

LENEL CORE SWITCH

BY OTHERS

(COORDINATE EXACT

MOUNTING LOCATION

WITH VA OIT)

PROVIDE FIBER PATCH CABLES TO CONNECT

EXISTING FIBER COMPLETE TO LENEL CORE

SWITCH FOR NEW LENEL SYSTEM SWITCHES.

X

X

REFER TO FLOOR PLANS FOR CABINET

SPECIFICATION INFORMATION. TYPICAL FOR ALL

NEW CABINETS PROVIDED UNDER THE SCOPE

OF THIS PROJECT.

NEW 42RU CABINET NEW 42RU CABINET NEW 42RU CABINET

RACK DESIGNATED FOR

FACILITY MANAGEMENT

SYSTEM(S) EQUIPMENT

(PAGING, FIRE ALARM,

BUILDING MANAGEMENT

SYSTEM, ETC).

RACKS SHALL BE

POPULATED WITH

EQUIPMENT BY VA OIT.

RACK DESIGNATED FOR

FACILITY MANAGEMENT

SYSTEM(S) EQUIPMENT

(PAGING, FIRE ALARM,

BUILDING MANAGEMENT

SYSTEM, ETC).

RACKS SHALL BE

POPULATED WITH

EQUIPMENT BY VA OIT.

# CODED NOTES

PROVIDE NEW 48-PORT SWITCH FOR LEVEL SYSTEM IN EXISTING RACK. PROVIDE FIBER PATCH BETWEEN EXISTING FIBER PATCH PANEL AND NEW SWITCH MATCH EXISTING VA SWITCHES (10/100/100, PoE+, STACKABLE WITH FIBER SFPS SWITCH).

CONTRACTOR SHALL PROVIDE A GROUP OF (64) CARD READER LICENSES AND 55 CAMERA LICENSES FOR

THIS PROJECT PLUS 5 SPARE CAMERA LICENSE..

S

59459

M.P. LONG

R

ES

O F

I R

GE

NOI

S

P

E

N E

DERT

L EA

E I N

G

R

TS

TEA HF OO

IO

DESIGN AND CONSTRUCTION DOCUMENTS AS

INSTRUMENTS OF SERVICE ARE GIVEN IN

CONFIDENCE AND REMAIN THE PROPERTY OF

PERSPECTUS ARCHITECTURE. THE USE OF THIS

DESIGN AND THESE CONSTRUCTION

DOCUMENTS

FOR PURPOSES OTHER THAN THE SPECIFIC

PROJECT NAMED HEREIN IS STRICTLY

PROHIBITED WITHOUT THE EXPRESSED WRITTEN

CONSENT OF PERSPECTUS ARCHITECTURE.

COPYRIGHT C 2018.

13212 Shaker Square Suite 204 Cleveland, Ohio 44120 P. 216.752.1800 F. 216.752.3833

CONSULTANTS: ARCHITECT:

Drawing Title

Approved: Project Director Location

Project Title

Date Checked Drawn

Drawing Number

Building Number

Project Number

Office of

Facilities

Management

Dwg. of o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t

VA FORM 08-6231, OCT 1978

1 2 3 4 5 6 7 8 9 10

A

1 2 3 4 5 6 7 8 9 10

B

C

D

E

F

A

B

C

D

E

F

VAMC - WADE PARK

Revisions: Date

FULLY SPRINKLERED

18077

FREDRICK, FREDRICK & HELLER

ENGINEERS, INC.

672 EAST ROYALTON ROAD

BROADVIEW HTS., OHIO 44147

TEL. (440)546-9696

FAX: (440)546-9699

BID ISSUE 4/13/20

Increase IRM Physical

Security

541-19-102

CPCMPL

TECHNOLOGY RACK DETAILS

T4.2 4/13/20

NOT TO SCALE

MAIN COMPUTER ROOM FIBER MDF

AND FMS ROOM FIBER MDF - RACK DETAIL 1

GENERAL NOTES:

1. CONTRACTOR SHALL PROGRAM DEVICES PER VA NAMING STANDARD:

CAMERA: C(1B-100): C = CAMERA, 1 = FLOOR, B = BUILDING SECTION, 100 = ROOM NUMBER

DOOR: D(BB-100): D = DOOR, B = FLOOR, B = BUILDING SECTION, 100 = ROOM NUMBER

PANIC BUTTON: P(1C-100): P = PANIC BUTTON, 1 = FLOOR, C = BUILDING SECTION, 100 = ROOM NUMBER

T0.1 - TECHNOLOGY LEGEND AND GENERAL NOTES
18077 FFH CF R18_jduale
T0.1 - TECHNOLOGY LEGEND AND GENERAL NOTES
T2.1 - PARTIAL THIRD FLOOR TECHNOLOGY DEMOLITION PLAN - PHASE 1
18077 FFH CF R18_jduale
T2.1 - PARTIAL THIRD FLOOR TECHNOLOGY DEMOLITION PLAN - PHASE 1
T2.2 - PARTIAL THIRD FLOOR TECHNOLOGY DEMOLITION PLAN - PHASE 2
18077 FFH CF R18_jduale
T2.2 - PARTIAL THIRD FLOOR TECHNOLOGY DEMOLITION PLAN - PHASE 2
T3.1 - PARTIAL THIRD FLOOR TECHNOLOGY PLAN - PHASE 1
18077 FFH CF R18_jduale
T3.1 - PARTIAL THIRD FLOOR TECHNOLOGY PLAN - PHASE 1
T3.2 - PARTIAL THIRD FLOOR TECHNOLOGY PLAN - PHASE 2
18077 FFH CF R18_jduale
T3.2 - PARTIAL THIRD FLOOR TECHNOLOGY PLAN - PHASE 2
T4.1 - TECHNOLOGY GROUNDING DETAILS
18077 FFH CF R18_jduale
T4.1 - TECHNOLOGY GROUNDING DETAILS
T4.2 - TECHNOLOGY RACK DETAILS
18077 FFH CF R18_jduale
T4.2 - TECHNOLOGY RACK DETAILS

File details come from the government source that posted it. Updated .