VA IRM Plum Dwgs 2020-04-13.pdf
PDF 1 MB Posted
- Solicitation number
- 36C25020B0001
About this file
This package includes construction documents for the Increase IRM Physical Security Project 541-19-102 solicited by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 10.
The documents detail plumbing and fire protection plans and notes for renovations to portions of the third floor at the VAMC Wade Park facility. Phase one plans show demolition and new work for sanitary piping replacements, addition of a sheet metal enclosure and leak detection system for overhead piping, installation of domestic water and sprinkler lines. Phase two plans cover further demolition and installation of domestic water, sprinkler and sanitary piping. Specifications include replacement of all overhead sanitary piping with new cast iron, routing of new piping as high as possible, addition of sheet metal gutters and leak alarms.
View the file
Other files
Show all 19
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
2" V
3" SAN
1 1/2" V
FD-B
CO
3" SAN DN TO SAN
FROM SINK. FIELD
VERIFY EXACT
ROUTING.
74490
L.D. HENDRIX, JR
GN
SS
AI ON EL
T
F EGE
P R O R
SI NR E I
E E R
D
E
ATS
ET O
OI
HOF
DESIGN AND CONSTRUCTION DOCUMENTS AS
INSTRUMENTS OF SERVICE ARE GIVEN IN
CONFIDENCE AND REMAIN THE PROPERTY OF
PERSPECTUS ARCHITECTURE. THE USE OF THIS
DESIGN AND THESE CONSTRUCTION
DOCUMENTS
FOR PURPOSES OTHER THAN THE SPECIFIC
PROJECT NAMED HEREIN IS STRICTLY
PROHIBITED W ITHOUT THE EXPRESSED W RITTEN
CONSENT OF PERSPECTUS ARCHITECTURE.
COPYRIGHT C 2018.
13212 Shaker Square Suite 204 Cleveland, Ohio 44120 P. 216.752.1800 F. 216.752.3833
CONSULTANTS: ARCHITECT:
Drawing Title
Approved: Project Director Location
Project Title
Date Checked Drawn
Drawing Number
Building Number
Project Number
Office of
Facilities
Management
Dwg. of o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t
VA FORM 08-6231, OCT 1978
1 2 3 4 5 6 7 8 9 10
A
1 2 3 4 5 6 7 8 9 10
B
C
D
E
F
A
B
C
D
E
F
VAMC - WADE PARK
Revisions: Date
FULLY SPRINKLERED
FREDRICK, FREDRICK & HELLER
ENGINEERS, INC.
672 EAST ROYALTON ROAD
BROADVIEW HTS., OHIO 44147
TEL. (440)546-9696
FAX: (440)546-9699
BID ISSUE 4/13/20
Increase IRM Physical
Security
541-19-102
DMLLDH
PLUMBING LEGEND AND
GENERAL NOTES
P0.1 4/13/20
ABBREVIATIONS:
CALL OUTS:
SYMBOLS:
DEMOLITION SYMBOLS:
PLUMBING PIPING:
DOMESTIC HOT W ATER RETURN
DOMESTIC HOT W ATER SUPPLY
DOMESTIC COLD W ATER SUPPLY
SANITARY W ASTE
PLUMBING VENT
SAN
PIPE DOW N
PIPE RISE UP
PIPE CAP
FLOOR DRAIN
NATURAL GAS
FIRE SUPPRESSION PIPING
VENT THROUGH ROOFVTR
F
G
HW R
HW
CW
V
AD ACCESS DOOR
ELECTRICAL CONTRACTOR
GENERAL TRADES CONTRACTOR
TEMPERATURE CONTROL CONTRACTOR
HVAC CONTRACTOR
FIRE SUPPRESSION CONTRACTOR
PLUMBING CONTRACTOR
EC
GC
FC
PC
TC
HC
REFERENCE TO CODED NOTE
ABOVE FINISHED FLOORAFF
ROOF OPENINGRO
RD
FD
ROOF DRAIN
FLOOR DRAIN
STRAINER
ISOLATION VALVE
REDUCER
UNION
CHECK VALVE
EXISTING TO REMAIN
EXISTING TO BE REMOVED
X
XR
EXISTING TO BE RELOCATEDXRL
EQUIPMENT OR FIXTURE MARK
BRANCH PIPE CONNECTION
NOTE: THIS LEGEND IS INTENDED TO AID IN THE UNDERSTANDING OF SHORTHAND, SYMBOLS AND ABBREVIATIONS SHOW N IN THESE CONSTRUCTION DOCUMENTS. IT IS NOT THE INTENTION TO DESCRIBE THE PROJECT SCOPE OF W ORK, FOR DETAILED SCOPE OF W ORK PLEASE REFER TO THE SUBSEQUENT DRAW INGS.
EQUIPMENT
TYPE
UNIT NUMBER
A. LOCATIONS AND ROUTING OF EXISTING PIPING, DUCTW ORK AND EQUIPMENT IS PRESUMED FROM EXISTING DRAW INGS. MECHANICAL CONTRACTOR SHALL FIELD VERIFY ALL PRIOR TO COMMENCEMENT OF CONSTRUCTION. NOTIFY ENGINEER OF ANY CONDITIONS W HICH W ILL NOT PERMIT THE W ORK TO BE
PERFORMED AS INDICATED ON THESE DRAW INGS.
B. COORDINATE ALL SHUT-DOW NS OF EXISTING MECHANICAL SYSTEMS W ITH VA A MINIMUM OF
SEVEN W ORKING DAYS IN ADVANCE.
C. PRIOR TO INSTALLATION, VERIFY PRECISE LOCATION OF NEW W ALL MOUNTED DEVICES W ITH VA
AND ARCHITECT.
D. PROVIDE ADEQUATE SERVICE CLEARANCE FOR ALL MECHANICAL EQUIPMENT. REFER TO
INSTRUCTIONS FROM THE EQUIPMENT MANUFACTURER.
E. NEW PIPING SHALL NOT BE ROUTED ABOVE ELECTRICAL PANELS. REFER TO ELECTRICAL DRAW INGS
FOR LOCATION OF PANELS.
F. PROVIDE ISOLATION VALVES ON ALL BRANCH PIPING AND ON ALL SUPPLIES TO INDIVIDUAL FIXTURES AND EQUIPMENT. PROVIDE ISOLATION VALVES ON ALL W ATER MAIN BRANCHES IN CORRIDORS AND
W HERE INDICATED ON DRAW INGS.
G. DEMOLITION OF PLUMBING FIXTURES SHALL INCLUDE ASSOCIATED VALVES, PIPING, INSULATION, CARRIERS, ETC. BACK TO ACTIVE MAINS AND CAPPED. INCLUDE REMOVAL AND REPLACEMENT OF CEILINGS AND CUTTING AND PATCHING OF W ALLS AND FLOORS. FILL AND PATCH ALL OPENINGS
CREATED BY THE REMOVAL OF FIXTURES AND PIPING TO MATCH SURROUNDING SURFACES.
H. W HERE W ORK IS SHOW N ABOVE EXISTING CEILINGS THE CONTRACTOR SHALL REMOVE AND REPLACE
EXISTING CEILINGS AS REQUIRED TO PERFORM ALL W ORK DESCRIBED.
I. W HERE CEILING SPACE IS TO BE USED AS A RETURN AIR PLENUM, PIPE SHALL NOT BE PVC PLASTIC AND
ALL W IRING SHALL BE INSTALLED IN CONDUIT OR SHALL BE PLENUM RATED.
PLUMBING AND FIRE PROTECTION LEGEND
PLUMBING GENERAL NOTES
X
XX-XX
LIGHT HAZARD OCCUPANCY
ORDINARY HAZARD GROUP 1 OCCUPANCY
ORDINARY HAZARD GROUP 2 OCCUPANCY
L
OH1
OH2
DEMOLISH TO POINT
CONNECT TO EXISTING
COORDINATE ALL SHUT-DOW NS OF EXISTING SYSTEMS W ITH VA A MINIMUM OF SEVEN W ORKING
DAYS IN ADVANCE.
PRIOR TO INSTALLATION, VERIFY PRECISE LOCATION OF NEW W ALL MOUNTED DEVICES W ITH
OW NER AND ARCHITECT. REFER TO ARCHITECTURAL REFLECTED CEILING PLAN FOR PRECISE
LOCATION OF CEILING MOUNTED DEVICES.
PROVIDE SERVICE CLEARANCE FOR ALL EQUIPMENT. REFER TO INSTRUCTIONS FROM THE
EQUIPMENT MANUFACTURER.
NEW PIPING SHALL NOT BE ROUTED ABOVE ELECTRICAL PANELS. REFER TO ELECTRICAL DRAW INGS
FOR LOCATION OF PANELS.
THE CONTRACTOR SHALL PROVIDE DETAILED DESIGN OF THE SPRINKLER SYSTEM. REFER TO
SPECIFICATIONS.
UNLESS OTHERW ISE NOTED NEW SPRINKLERS SHALL BE AS FOLLOW S:
F.1. AREAS W ITH CEILING: SEMI-RECESSED TYPE W ITH CHROME PLATED ESCUTCHEONS.
F.2. EXPOSDE STRUCTURE: UPRIGHT OR PENDENT TYPE.
THE FIRE PROTECTION SYSTEM IS PERFORMANCE SPECIFIED. ALL SPRINKLER PIPE SIZES SHALL BE
DETERMINED BY FIRE PROTECTION CONTRACTOR, BASED ON HYDRAULIC CALCULATIONS.
PROVIDE SUPPLEMENTAL DRAINS AS NECESSARY TO PROVIDE 100% SYSTEM DRAINAGE TO
PROJECT AREAS. LOCATE DRAINS ABOVE ACCESSIBLE CEILINGS.
REFER TO ARCHITECTURAL PLANS FOR EXACT PHASING REQUIREMENTS.
REFER TO SPECIFICATIONS FOR FIRE SUPPRESSION HAZARD OCCUPANCY CLASSIFICATIONS.
SPRINKLER PIPING SHALL BE A MINIMUM OF ONE INCH.
UNLESS OTHERW ISE STATED ON DRAW INGS OR IN SPECIFICATIONS, ALL SPRINKLER HEADS SHALL
BE QUICK RESPONSE.
ALL HEADS SHALL BE UL LISTED AND FM APPROVED.
ALL SPRINKLER HEADS LOCATED IN CEILING TILES SHALL BE CENTERED.
CONTRACTOR SHALL REMOVE AND REPLACE CEILING TILES AND GRID AS REQUIRED TO COMPLETE DEMOLITION AND NEW W ORK IN AREAS OUTSIDE RENOVATION PROJECT. CONTRACTOR SHALL BE
RESPONSIBLE FOR REPLACING ANY TILES OR GRID DAMAGED DUE TO THIS W ORK.
PROVIDE PROTECTIVE CAGE FOR SPRINKLER HEADS MOUNTED BELOW 7'-6" AFF.
FIRE PROTECTION GENERAL NOTES
A.
B.
C.
D.
E.
F
G.
H.
I.
J.
K.
L.
M.
N.
O.
P.
THIS PROJECT CONSISTS OF MULTIPLE TRADES OF W ORK PERFORMED W ITHIN AN EXISTING
BUILDING, ALL OF W HICH ALLOW S VERY LITTLE PERMISSABLE RANGE OF VARIATION. THE
CONTRACTOR SHALL TAKE CAREFUL CONSIDERATION W ITH THE COORDINATION AND
INSTALLATION OF THE MULTITUDE OF NEW SYSTEMS W HILE ALSO ACCOMMODATING ANY
EXISTING SYSTEMS TO REMAIN.
THE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING ALL TRADES ASSOCIATED W ITH
THIS PROJECT AND ISSUING COORDINATION PLANS PRIOR TO COMMENCEMENT OF EACH PHASE
OF CONSTRUCTION.
THE COORDINATION DRAW INGS SHALL ILLUSTRATE ALL SYSTEMS IN PLACE. NO EXCEPTIONS!
THIS CONTRACTOR SHALL SHOW ALL NECESSARY OFFSETS, TRANSITIONS, ETC. AS REQUIRED IN
ORDER TO ACCOMMODATE CONDITIONS IDENTIFIED IN THE FIELD.
IF CONFLICTS ARE IDENTIFIED DURING DEVELOPMENT OF COORDINATION PLANS, THE
CONTRACTOR SHALL NOTIFY THE VA COR. ARCHITECT, AND/OR ENGINEER OF ANY CONDITIONS
W HICH W ILL NOT PERMIT THE W ORK TO BE PERFORMED AS INDICATED ON THE PROJECT PLANS.
A COMPLETED SET OF COORDINATION PLANS ISSUED FOR REVIEW SHALL CONFIRM THAT THE
CONTRACTOR FULLY UNDERSTANDS THE PROJECT CONSTRAINTS AND ALL KNOW N CONFLICTS
HAVE BEEN ADDRESSED.
PROJECT COORDINATION NOTES
A.
B.
C.
D.
E.
PLUMBING FIXTURE CONNECTION SCHEDULE
MARK FIXTURE
CW
BRANCH PIPE SIZE
HW W ASTE VENT
FD-B - - 3" 1-1/2"FLOOR DRAIN
NOTES:
1. ALL PIPE SIZES ARE AS SCHEDULED, UNLESS INDICATED OTHERW ISE
ON PLANS.
PENETRATION OF FIRE/SMOKE BARRIERS
PIPE/DUCT
TYPICAL METHOD OF SECURING
HANGER RODS IN CONCRETE
SLABS AND BEAMS.
NOTE:
1. APPLICABLE TO PENETRATIONS
OF ALL FIRE RATED MEMBRANES,
IN ACCORDANCE W ITH NFPA 101.
REFER TO SPECIFICATIONS
SECTION FOR FIRE STOPPING
SYSTEMS.
INSULATED
PIPE OR
DUCT
FLOOR
FIRESTOP MATERIAL
3/4" [19mm]
APPROVED FIRESTOP
INSULATION W ITH
VAPOR BARRIER
PIPE SLEEVE
W HERE SPECIFIED
1/4" [6mm]Ø
ANCHOR ROD FOR
NEW CONSTRUCTION
W ELD
FLOOR OR DECK PENETRATION
PARTITION OR CHASE PENETRATION
6"
[152mm]
6"
[152mm]
MASONRY
PARTITIO
N
PARTITION SUPPORT
FIRESTOP
MATERIAL
6"
[152mm]
6" [152mm]
3/4" [19mm] APPROVED
FIRESTOP INSULATION
W ITH VAPOR BARRIER
DRYW ALL PARTITION
INSULATED
PIPE OR
DUCT
STEEL EXPANSION SHIELD FOR
EXISTING CONSTRUCTION AND
INSERTS FOR NEW CONTRUCTION.
THIS TYPE SHALL BE USED ONLY IN
SLABS OR BEAMS OF 4" (100MM) MIN
DEPTH
3/8" (10 MM) MIN DIA EXPANSION
BOLTS FOR EXISTING
CONTRUCTION AND INSERTS FOR
NEW CONTRUCTION
CONCRETE
FLOOR SLAB
CLIP
ANGL
E
NUTS & W ASHERS
3/8" (10 MM) MIN DIA
HANGER RODS
TURNBUCKLE
3/8" (10 MM) MIN
DIA HANGER RODS
3/8" (10 MM) MIN DIA INSERTS
NEW CONTRUCTION ONLY
TYPICAL PIPE HANGERSVENT THROUGH ROOF DETAIL
NOTE: FOR TRAPEZE HANGER TAKE SPACING OF SMALLEST SIZE ON TRAPEZE.
MAXIMUM PIPE/TUBING SUPPORT SPACING
TUBING 5 FT
NOM. SIZE
PIPE
THRU (20)
6 8 10
(32)(25) (40)
(65)
(50)
(75)
ADJUSTABLE CLEVIS HANGER
TYPE 43 - SEE SPECIFICATIONS
SADDLE
W ELD
1312 14 16
(125)(100)
(150)
(200)
TO 1000 LB. (453 KG) UNIFORM LOAD
TRAPEZE HANGER FOR UP
PROVIDE INSULATION SHIELD
SIDE VIEW
1 5/8" (43 MM) 12 GAGE1" (25 MM) MAX.
STRENGTH INSULATION
PROVIDE HIGH COMPRESSIVE
TYPE 1 - SEE SPECIFICATIONS
ADJUSTABLE CLEVIS HANGER
HANGER ROD
UNDER INSULATION SHIELD
AT HANGER
INSULATION SHIELD
TEMPERATURE PIPE)
REQUIRED FOR LOW
BARRIER TYPE IS
INSULATION (VAPOR
SPACING ON
36" (900 MM) MAX.
BAND
(9 PCF MIN. DENSITY)
HANGER RODS W ITH
(8" (200 MM) MIN.)
CHANNEL OR 2"x2"x1/4"
(50x50x8 MM) ANGLE
864 532 2 1/21 1/21 1 1/4IN.
(MM)
(M)
FT.
FT.
(M)
(5.8)(5.2)(4.1) (4.9)(3.7)(3.0) (3.4)(2.7)(2.1)
(4.9)(4.1)(3.7) (4.0)(3.0)(2.4)(1.8)5 FT
THRU 3/4
(2.1) (2.1)
(2.1)
(2.7)
(2.4)
1/2" (15 MM) DIA.
EACH CHANNEL
AND INSERT FOR ALL PIPING
INSULATION
ROOFING
VENT (SEE PLANS
FOR SIZES,
MINIMUM 3-INCHES)
FLASH VENT W ITH 6 LB.
LEAD CAP AND BASE.
ROLL CAP 1" INTO TOP
OF VENT. BASE TO BE
2'-0" SQUARE
TRAP PRIMER DETAIL
NOTES:
1. ALL FLOOR DRAINS SHALL BE
PROVIDED W ITH A TRAP PRIMER.
FLOOR DRAIN
TRAP PRIMER VALVE
ISOLATION VALVE
COLD W ATER MAIN
FLOOR
1/2" CONTINUOUS
SOFT
COPPER TUBING,
(TYPICAL) NO JOINTS
DOMESTIC W ATER BACKFLOW PREVENTER DETAIL
THREADED DRAIN VALVE W ITH CAP
1"
CW
REDUCED PRESSURE BACKFLOW ASSEMBLY
W ITH
STRAINER AND DRAIN CUP. TO EQUIPMENT
ROUTE INDIRECT
W ASTE THROUGH
FLOOR TO 5TH
FLOOR
NOT TO SCALE
SANITARY ISOMETRIC 1
NOT TO SCALE NOT TO SCALE
NOT TO SCALENOT TO SCALE
NOT TO SCALE NOT TO SCALE
UP
36 37
H
L
L1
L2
L3
39 42414038
M
36a
Z3
3 TYP.
3 TYP.
2TYP.
2"Ø
4"Ø
3"Ø 2"Ø
4"Ø
2"Ø
3"Ø
4"Ø
CO
CO
XR - 2"
XR - 4"
XR - 4"
XR - 4"
XR - 3"
XR - 4"
X - 4"
X - 4"
X - 4" F
XR - 3/4"
XR - 3/4"
X-CU
X-CU
X-CU
BATTERY
3A-135A
MCOR-1
3A135B-1
FMS-1
3A135-1
Tele Health
3A137
L.C.
3A132
Corridor
3A100E
MCR-1
3A133-1
Passage
3AC312
HAC
3AC311
2 Bedroom
3A131
74490
L.D. HENDRIX, JR
GN
SS
AI ON EL
T
F EGE
P R O R
SI NR E I
E E R
D
E
ATS
ET O
OI
HOF
DESIGN AND CONSTRUCTION DOCUMENTS AS
INSTRUMENTS OF SERVICE ARE GIVEN IN
CONFIDENCE AND REMAIN THE PROPERTY OF
PERSPECTUS ARCHITECTURE. THE USE OF THIS
DESIGN AND THESE CONSTRUCTION
DOCUMENTS
FOR PURPOSES OTHER THAN THE SPECIFIC
PROJECT NAMED HEREIN IS STRICTLY
PROHIBITED W ITHOUT THE EXPRESSED W RITTEN
CONSENT OF PERSPECTUS ARCHITECTURE.
COPYRIGHT C 2018.
13212 Shaker Square Suite 204 Cleveland, Ohio 44120 P. 216.752.1800 F. 216.752.3833
CONSULTANTS: ARCHITECT:
Drawing Title
Approved: Project Director Location
Project Title
Date Checked Drawn
Drawing Number
Building Number
Project Number
Office of
Facilities
Management
Dwg. of o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t
VA FORM 08-6231, OCT 1978
1 2 3 4 5 6 7 8 9 10
A
1 2 3 4 5 6 7 8 9 10
B
C
D
E
F
A
B
C
D
E
F
VAMC - WADE PARK
Revisions: Date
FULLY SPRINKLERED
FREDRICK, FREDRICK & HELLER
ENGINEERS, INC.
672 EAST ROYALTON ROAD
BROADVIEW HTS., OHIO 44147
TEL. (440)546-9696
FAX: (440)546-9699
BID ISSUE 4/13/20
Increase IRM Physical
Security
541-19-102
DMLLDH
PARTIAL THIRD FLOOR
PLUMBING AND FIRE
PROTECTION DEMOLITION PLAN
- PHASE 1
P1.1 4/13/20
0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'
1/4" = 1'-0"
PARTIAL THIRD FLOOR PLUMBING AND FIRE
PROTECTION DEMOLITION PLAN - PHASE 1 1
# CODED NOTES:
1 REMOVE EXISTING EYEW ASH STATION AND ASSOCIATED MIXING VALVE COMPLETELY. REMOVE
W ATER, DRAIN, AND VENT PIPING BACK TO MAINS AND CAP.
REMOVE EXISTING SANITARY PIPING AND RE-INSTALL NEW CAST IRON BELL & SPIGOT PIPING, SAME
SIZE. COORDINATE SHUTDOW N OF PLUMBING FIXTURES ABOVE W ITH VA COR.
REPLACE EXISTING SHEETMETAL GUTTER SYSTEM IN ITS ENTIRETY W ITH A NEW SHEETMETAL GUTTER SYSTEM. GUTTER SYSTEM SHALL ENCLOSE ALL SANITARY PIPING ABOVE PROJECT SCOPE AREA. SEAL UP TO DECK W ATERTIGHT. SLOPE IN DIRECTION OF FLOW . PROVIDE LEAK DETECTION W ITH AUDIBLE
ALARM. ALARM TO BAS. PROVIDE ACCESS PANEL AT EACH CLEANOUT.
EXISTING PRE-ACTION SPRINKLER CABINET TO REMAIN.
EXISTING PRE-ACTION SPRINKLER PIPING SERVICE TO OIT ROOM SHALL REMAIN UNDER PHASE 1.
DEMOLISH UNIT COLD W ATER HUMIDIFIER LINE AND CONDENSATE DRAIN PIPE BACK TO MAINS AND
CAP.
EXACT CONDITIONS MAY NOT BE ILLUSTRATED ON THIS DRAW ING. FIELD VERIFY ALL EXISTING ABOVE-
CEILING PIPING.
ALL ABOVE-CEILING SANITARY PIPING IN THE PROJECT SCOPE AREA SHALL BE REPLACED W ITH NEW CAST IRON BELL & SPIGOT PIPING. REPLACEMENT PIPING SHALL BE SAME AS CURRENT SIZE.
INSTALL NEW SANITARY PIPING AS HIGH AS POSSIBLE.
NEW SANITARY PIPING CAN BE RE-ROUTED DIFFERENTLY, IF IT ALLOW S FOR A REDUCTION IN OVERALL
PIPE LENGTH AND ALLOW S FOR INSTALLATION AT A HIGHER ELEVATION.
ALL OVERHEAD PIPING SHALL BE PROVIDED A NEW SHEET METAL GUTTER SYSTEM. GUTTER SHALL PROTECT FROM LEAKAGE DOW N INTO ROOM. GUTTERS SHALL EXTEND UP TO DECK AND BE SEALED AT
ALL SEAMS W ATERTIGHT.
PROVIDE ACCESS PANEL AT EACH CLEANOUT.
GUTTERS SHALL BE PROVIDED LEAK DETECTION W ITH AUDIBLE ALARM. ALARM TO BAS.
GENERAL NOTES:
A.
B.
C.
D.
E.
F.
G.
N
H
L
L1
L2
L3
39 42414038
M
36a
Z3
X-CU
X-CU
X-CU
2 TYP.
3 TYP.
3TYP.
XR - 3"
X - 3/4" CW
XR - 2"
XR - 4"
XR - 2"
XR - 3"
XR - 4"
XR - 3"
XR-F
CAP
FMS-2
3A135-2
MCOR-2
3A135B-2
74490
L.D. HENDRIX, JR
GN
SS
AI ON EL
T
F EGE
P R O R
SI NR E I
E E R
D
E
ATS
ET O
OI
HOF
DESIGN AND CONSTRUCTION DOCUMENTS AS
INSTRUMENTS OF SERVICE ARE GIVEN IN
CONFIDENCE AND REMAIN THE PROPERTY OF
PERSPECTUS ARCHITECTURE. THE USE OF THIS
DESIGN AND THESE CONSTRUCTION
DOCUMENTS
FOR PURPOSES OTHER THAN THE SPECIFIC
PROJECT NAMED HEREIN IS STRICTLY
PROHIBITED W ITHOUT THE EXPRESSED W RITTEN
CONSENT OF PERSPECTUS ARCHITECTURE.
COPYRIGHT C 2018.
13212 Shaker Square Suite 204 Cleveland, Ohio 44120 P. 216.752.1800 F. 216.752.3833
CONSULTANTS: ARCHITECT:
Drawing Title
Approved: Project Director Location
Project Title
Date Checked Drawn
Drawing Number
Building Number
Project Number
Office of
Facilities
Management
Dwg. of o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t
VA FORM 08-6231, OCT 1978
1 2 3 4 5 6 7 8 9 10
A
1 2 3 4 5 6 7 8 9 10
B
C
D
E
F
A
B
C
D
E
F
VAMC - WADE PARK
Revisions: Date
FULLY SPRINKLERED
FREDRICK, FREDRICK & HELLER
ENGINEERS, INC.
672 EAST ROYALTON ROAD
BROADVIEW HTS., OHIO 44147
TEL. (440)546-9696
FAX: (440)546-9699
BID ISSUE 4/13/20
Increase IRM Physical
Security
541-19-102
DMLLDH
PARTIAL THIRD FLOOR
PLUMBING AND FIRE
PROTECTION DEMOLITION PLAN
- PHASE 2
P1.3 4/13/20
0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'
1/4" = 1'-0"
PARTIAL THIRD FLOOR PLUMBING AND FIRE
PROTECTION DEMOLITION PLAN - PHASE 2 1
# CODED NOTES:
1 REMOVE ABANDONED 2-INCH VENT LINE TO POINT INDICATED AND CAP.
REMOVE EXISTING SANITARY PIPING AND RE-INSTALL NEW CAST IRON BELL & SPIGOT PIPING, SAME
SIZE. COORDINATE SHUTDOW N OF PLUMBING FIXTURES ABOVE W ITH VA COR.
REPLACE EXISTING SHEETMETAL GUTTER SYSTEM IN ITS ENTIRETY W ITH A NEW SHEETMETAL GUTTER SYSTEM. GUTTER SYSTEM SHALL ENCLOSE ALL PIPING ABOVE PROJECT SCOPE AREA. SEAL UP TO DECK W ATERTIGHT. SLOPE IN DIRECTION OF FLOW . PROVIDE LEAK DETECTION W ITH AUDIBLE ALARM.
ALARM TO BAS. PROVIDE ACCESS PANEL AT EACH CLEANOUT.
EXISTING PRE-ACTION SPRINKLER CABINET TO REMAIN.
REMOVE ALL EXISTING PRE-ACTION SPRINKLER PIPING AND HEADS SERVING EXISTING OIT ROOM.
REMOVE BACK TO POINT INDICATED. REFER TO NEW PLAN FOR RECONNECTION.
EXACT CONDITIONS MAY NOT BE ILLUSTRATED ON THIS DRAW ING. FIELD VERIFY ALL EXISTING ABOVE-
CEILING PIPING.
ALL ABOVE-CEILING SANITARY PIPING IN THE PROJECT SCOPE AREA SHALL BE REPLACED W ITH NEW CAST IRON BELL & SPIGOT PIPING. REPLACEMENT PIPING SHALL BE SAME AS CURRENT SIZE.
INSTALL NEW SANITARY PIPING AS HIGH AS POSSIBLE.
NEW SANITARY PIPING CAN BE RE-ROUTED DIFFERENTLY, IF IT ALLOW S FOR A REDUCTION IN OVERALL
PIPE LENGTH AND ALLOW S FOR INSTALLATION AT A HIGHER ELEVATION.
ALL OVERHEAD SANITARY PIPING SHALL BE PROVIDED A NEW SHEET METAL GUTTER SYSTEM. GUTTER SHALL PROTECT FROM LEAKAGE DOW N INTO ROOM. GUTTERS SHALL EXTEND UP TO DECK AND BE
SEALED AT ALL SEAMS W ATERTIGHT.
PROVIDE ACCESS PANEL AT EACH CLEANOUT.
GUTTERS SHALL BE PROVIDED LEAK DETECTION W ITH AUDIBLE ALARM. ALARM TO BAS.
GENERAL NOTES:
A.
B.
C.
D.
E.
F.
G.
N
H
L
L1
L2
L3
39 42414038
M
36a
Z3
CRAC-3
CRAC-4
2 TYP.
2 TYP.
1TYP.
2"Ø
4"Ø
3"Ø 2"Ø
4"Ø
2"Ø
3"Ø
4"Ø
CO
CO
4" SAN
2" SAN
4" SAN
4" SAN
4" SAN
L
L
L
1" CW
1" CW
1" CW
3/4" CW
1/2" CW
1/2" CW
F
2" VTR
FD-B
F
HAC
3AC311
Passage
3AC312
2 Bedroom
3A131
BATTERY
3A-135A
MCOR-1
3A135B-1
FMS-1
3A135-1
MCR-1
3A133-1
X-CU
X-CU
X-CU
Corridor
3A100E
Tele Health
3A137
REW ORK EXISTING SPRINKLER SYSTEM IN
OUTLINED AREA IN ORDER TO MAINTAIN
SPRINKLER COVERAGE UNTIL PHASE 2. PROVIDE
ADDITIONAL HEADS, W HERE NECESSARY.
PROOVIDE NEW W ET-PIPE SPRINKLER LINE FROM
INDICATED POINT TO OUTLINED AREA. PROVIDE
ALL NEW MAIN AND BRANCH PIPING AND ALL NEW
HEADS.
OUTLINED AREA SHALL BE SPRINKLERED BY PRE-
ACTION SYSTEM. CONNECT TO PRE-ACTION MAIN
AT CABINET. PROVIDE ALL NEW MAIN AND
BRANCH PIPING AND ALL NEW HEADS. LABEL
PIPING FOR PRE-ACTION.
EE
J
3" SAN
CO
1-1/2" V UP
FD-B ABOVE
3" SAN DN TO SAN
FROM MOP BASIN.
FIELD VERIFY EXACT
ROUTING.
CO
X-MB
74490
L.D. HENDRIX, JR
GN
SS
AI ON EL
T
F EGE
P R O R
SI NR E I
E E R
D
E
ATS
ET O
OI
HOF
DESIGN AND CONSTRUCTION DOCUMENTS AS
INSTRUMENTS OF SERVICE ARE GIVEN IN
CONFIDENCE AND REMAIN THE PROPERTY OF
PERSPECTUS ARCHITECTURE. THE USE OF THIS
DESIGN AND THESE CONSTRUCTION
DOCUMENTS
FOR PURPOSES OTHER THAN THE SPECIFIC
PROJECT NAMED HEREIN IS STRICTLY
PROHIBITED W ITHOUT THE EXPRESSED W RITTEN
CONSENT OF PERSPECTUS ARCHITECTURE.
COPYRIGHT C 2018.
13212 Shaker Square Suite 204 Cleveland, Ohio 44120 P. 216.752.1800 F. 216.752.3833
CONSULTANTS: ARCHITECT:
Drawing Title
Approved: Project Director Location
Project Title
Date Checked Drawn
Drawing Number
Building Number
Project Number
Office of
Facilities
Management
Dwg. of o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t
VA FORM 08-6231, OCT 1978
1 2 3 4 5 6 7 8 9 10
A
1 2 3 4 5 6 7 8 9 10
B
C
D
E
F
A
B
C
D
E
F
VAMC - WADE PARK
Revisions: Date
FULLY SPRINKLERED
FREDRICK, FREDRICK & HELLER
ENGINEERS, INC.
672 EAST ROYALTON ROAD
BROADVIEW HTS., OHIO 44147
TEL. (440)546-9696
FAX: (440)546-9699
BID ISSUE 4/13/20
Increase IRM Physical
Security
541-19-102
DMLLDH
PARTIAL THIRD FLOOR
PLUMBING AND FIRE
PROTECTION PLAN - PHASE 1
P2.1 4/13/20
0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'
1/4" = 1'-0"
PARTIAL THIRD FLOOR PLUMBING AND FIRE
PROTECTION PLAN - PHASE 1 2
# CODED NOTES:
1 REMOVE EXISTING SANITARY PIPING AND RE-INSTALL NEW CAST IRON BELL & SPIGOT PIPING, SAME SIZE.
COORDINATE SHUTDOW N OF PLUMBING FIXTURES ABOVE W ITH VA COR.
PROVIDE NEW SHEET METAL GUTTER SYSTEM. GUTTER SYSTEM SHALL ENCLOSE ALL PIPING ABOVE PROJECT SCOPE AREA. SEAL UP TO DECK W ATERTIGHT. SLOPE IN DIRECTION OF FLOW . PROVIDE LEAK DETECTION W ITH AUDIBLE ALARM. ALARM TO BAS. PROVIDE ACCESS PANEL AT EACH CLEANOUT.
ROUTE 1" APPROXIMATELY 20 LF AND CONNECT TO LOCAL CW MAIN. FIELD VERIFY ROUTE.
PROVIDE NEW BACKFLOW PREVENTER. MOUNT UP HIGH IN HOUSEKEEPING CLOSET. PIPE DRAIN DOW N
TO MOP SINK.
1" CW CAPPED FOR PHASE 2.
PIPE 1/2'" CW TO CRAC UNIT HUMIDIFIER.
1/2" CW DN TO FD TRAP PRIMER.
1-1/2"V TO FD.
SPRINKLER BRANCH FROM W ET-PIPE MAIN TO SERVE OUTLINED AREA. SIZE PER NFPA.
PRE-ACTION SPRINKLER BRANCHED FROM CABINET. SIZE PER NFPA.
EXACT CONDITIONS MAY NOT BE ILLUSTRATED ON THIS DRAW ING. FIELD VERIFY ALL EXISTING ABOVE-
CEILING PIPING.
ALL ABOVE-CEILING SANITARY PIPING IN THE PROJECT SCOPE AREA SHALL BE REPLACED W ITH NEW CAST IRON BELL & SPIGOT PIPING. REPLACEMENT PIPING SHALL BE SAME AS CURRENT SIZE.
INSTALL NEW SANITARY PIPING AS HIGH AS POSSIBLE.
NEW SANITARY PIPING CAN BE RE-ROUTED DIFFERENTLY, IF IT ALLOW S FOR A REDUCTION IN OVERALL
PIPE LENGTH AND ALLOW S FOR INSTALLATION AT A HIGHER ELEVATION.
ALL OVERHEAD PIPING SHALL BE PROVIDED A NEW SHEET METAL GUTTER SYSTEM. GUTTER SHALL PROTECT FROM LEAKAGE DOW N INTO ROOM. GUTTERS SHALL EXTEND UP TO DECK AND BE SEALED AT
ALL SEAMS W ATERTIGHT.
PROVIDE ACCESS PANEL AT EACH CLEANOUT.
GUTTERS SHALL BE PROVIDED LEAK DETECTION W ITH AUDIBLE ALARM. ALARM TO BAS.
GENERAL NOTES:
A.
B.
C.
D.
E.
F.
G.
SPRINKLER LEGEND
0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'
1/4" = 1'-0"
PARTIAL SECOND FLOOR PLUMBING AND FIRE
PROTECTION PLAN - PHASE 1 3NN
H
L
L1
L2
L3
39 42414038
M
36a
Z3
CRAC-3
CRAC-4
CRAC-2
CRAC-1
CO
CO
2" SAN
X - 3/4" CW
2" SAN
4" SAN 4" SAN
3" SAN
4" SAN
4" SAN
4" SAN
2" SAN
2" SAN
1 TYP.
2 TYP.2TYP.
1" CW
MCR-2
3A133-2
MCOR-2
3A135B-2
FMS-2
3A135-2
OUTLINED AREA SHALL BE SPRINKLERED BY PRE-ACTION SYSTEM. CONNECT
TO PRE-ACTION MAIN AT CABINET. PROVIDE ALL NEW MAIN AND BRANCH
PIPING AND ALL NEW HEADS. LABEL PIPING FOR PRE-ACTION.
74490
L.D. HENDRIX, JR
GN
SS
AI ON EL
T
F EGE
P R O R
SI NR E I
E E R
D
E
ATS
ET O
OI
HOF
DESIGN AND CONSTRUCTION DOCUMENTS AS
INSTRUMENTS OF SERVICE ARE GIVEN IN
CONFIDENCE AND REMAIN THE PROPERTY OF
PERSPECTUS ARCHITECTURE. THE USE OF THIS
DESIGN AND THESE CONSTRUCTION
DOCUMENTS
FOR PURPOSES OTHER THAN THE SPECIFIC
PROJECT NAMED HEREIN IS STRICTLY
PROHIBITED W ITHOUT THE EXPRESSED W RITTEN
CONSENT OF PERSPECTUS ARCHITECTURE.
COPYRIGHT C 2018.
13212 Shaker Square Suite 204 Cleveland, Ohio 44120 P. 216.752.1800 F. 216.752.3833
CONSULTANTS: ARCHITECT:
Drawing Title
Approved: Project Director Location
Project Title
Date Checked Drawn
Drawing Number
Building Number
Project Number
Office of
Facilities
Management
Dwg. of o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t
VA FORM 08-6231, OCT 1978
1 2 3 4 5 6 7 8 9 10
A
1 2 3 4 5 6 7 8 9 10
B
C
D
E
F
A
B
C
D
E
F
VAMC - WADE PARK
Revisions: Date
FULLY SPRINKLERED
FREDRICK, FREDRICK & HELLER
ENGINEERS, INC.
672 EAST ROYALTON ROAD
BROADVIEW HTS., OHIO 44147
TEL. (440)546-9696
FAX: (440)546-9699
BID ISSUE 4/13/20
Increase IRM Physical
Security
541-19-102
DMLLDH
PARTIAL THIRD FLOOR
PLUMBING AND FIRE
PROTECTION PLAN - PHASE 2
P2.3 4/13/20
0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'
1/4" = 1'-0"
PARTIAL THIRD FLOOR PLUMBING AND FIRE
PROTECTION PLAN - PHASE 2 1N
# CODED NOTES:
1 REMOVE EXISTING SANITARY PIPING AND RE-INSTALL NEW CAST IRON BELL & SPIGOT PIPING, SAME SIZE.
COORDINATE SHUTDOW N OF PLUMBING FIXTURES ABOVE W ITH VA COR.
PROVIDE NEW SHEET METAL GUTTER SYSTEM. GUTTER SYSTEM SHALL ENCLOSE ALL SANITARY PIPING ABOVE PROJECT SCOPE AREA. SEAL UP TO DECK W ATERTIGHT. SLOPE IN DIRECTION OF FLOW . PROVIDE LEAK DETECTION W ITH AUDIBLE ALARM. ALARM TO DECK. PROVIDE ACCESS PANEL AT EACH CLEANOUT.
PIPE 3/4" CW TO CRAC UNIT HUMIDIFIER.
EXTEND NEW SPRINKLER PIPING FROM PRE-ACTION SYSTEM TO SERVE OUTLINED ARE. SIZE PER NFPA.
1" CW DOW N TO BELOW RAISED FLOOR. ROUTE TO CRAC HUMIDIFIERS.
EXACT CONDITIONS MAY NOT BE ILLUSTRATED ON THIS DRAW ING. FIELD VERIFY ALL EXISTING ABOVE-
CEILING PIPING.
ALL ABOVE-CEILING SANITARY PIPING IN THE PROJECT SCOPE AREA SHALL BE REPLACED W ITH NEW CAST IRON BELL & SPIGOT PIPING. REPLACEMENT PIPING SHALL BE SAME AS CURRENT SIZE.
INSTALL NEW SANITARY PIPING AS HIGH AS POSSIBLE.
NEW SANITARY PIPING CAN BE RE-ROUTED DIFFERENTLY, IF IT ALLOW S FOR A REDUCTION IN OVERALL
PIPE LENGTH AND ALLOW S FOR INSTALLATION AT A HIGHER ELEVATION.
ALL OVERHEAD PIPING SHALL BE PROVIDED A NEW SHEET METAL GUTTER SYSTEM. GUTTER SHALL PROTECT FROM LEAKAGE DOW N INTO ROOM. GUTTERS SHALL EXTEND UP TO DECK AND BE SEALED AT
ALL SEAMS W ATERTIGHT.
PROVIDE ACCESS PANEL AT EACH CLEANOUT.
GUTTERS SHALL BE PROVIDED LEAK DETECTION W ITH AUDIBLE ALARM. ALARM TO BAS.
GENERAL NOTES:
A.
B.
C.
D.
E.
F.
G.
SPRINKLER LEGEND
| P0.1 - PLUMBING LEGEND AND GENERAL NOTES |
| 18077 FFH CF R18_ifowler |
| P0.1 - PLUMBING LEGEND AND GENERAL NOTES |
| P1.1 - PARTIAL THIRD FLOOR PLUMBING AND FIRE PROTECTION DEMOLITION PLAN - PHASE 1 |
| 18077 FFH CF R18_ifowler |
| P1.1 - PARTIAL THIRD FLOOR PLUMBING AND FIRE PROTECTION DEMOLITION PLAN - PHASE 1 |
| P1.3 - PARTIAL THIRD FLOOR PLUMBING AND FIRE PROTECTION DEMOLITION PLAN - PHASE 2 |
| 18077 FFH CF R18_ifowler |
| P1.3 - PARTIAL THIRD FLOOR PLUMBING AND FIRE PROTECTION DEMOLITION PLAN - PHASE 2 |
| P2.1 - PARTIAL THIRD FLOOR PLUMBING AND FIRE PROTECTION PLAN - PHASE 1 |
| 18077 FFH CF R18_ifowler |
| P2.1 - PARTIAL THIRD FLOOR PLUMBING AND FIRE PROTECTION PLAN - PHASE 1 |
| P2.3 - PARTIAL THIRD FLOOR PLUMBING AND FIRE PROTECTION PLAN - PHASE 2 |
| 18077 FFH CF R18_ifowler |
| P2.3 - PARTIAL THIRD FLOOR PLUMBING AND FIRE PROTECTION PLAN - PHASE 2 |
File details come from the government source that posted it. Updated .