This solicitation is for the Increase IRM Physical Security Project 541-19-102 to be awarded by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 10. The solicitation seeks electronic drawings and designs to increase physical security at an IRM facility. Offerors should respond by April 13, 2020 with proposals for providing electronic drawings, designs, and related services to enhance security infrastructure for the specified IRM project. The award date was not specified but is presumed to occur shortly after the response deadline. Details on pricing, set asides, incumbent contractors or additional terms were not provided in the solicitation document.
View the file
Other files
Show all 19
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
LIGHTING FIXTURES LEGEND
LED LIGHTING FIXTURE CONNECTED TO NORMAL CIRCUIT AS INDICATED - TYPE AS SPECIFIED IN SCHEDULE, "A" INDICATES TYPE, "3" INDICATES CIRCUIT NUMBER ASSIGNMENT, "a" INDICATES LOCAL SWITCHING CONTROL.
CONNECT FIXTURES SO THAT ALL LAMPS ARE CONTROLLED BY
LED LIGHTING FIXTURE CONNECTED TO EMERGENCY LIFE SAFETY CIRCUIT - TYPE AS SPECIFIED IN SCHEDULE, "A" INDICATES TYPE, "3" INDICATES CIRCUIT NUMBER ASSIGNMENT. CONNECT AHEAD OF LOCAL SWITCHING.
LED LIGHTING FIXTURE - CONNECTED TO EMERGENCY CRITICAL LIGHTING CIRCUIT - TYPE AS SPECIFIED IN SCHEDULE "A" INDICATES TYPE, "3" INDICATES CIRCUIT NUMBER ASSIGNMENT. CONNECT FIXTURES SO THAT ALL
LAMPS ARE CONTROLLED BY
LED LIGHTING FIXTURE CONNECTED TO NORMAL CIRCUIT AS INDICATED - TYPE AS SPECIFIED IN SCHEDULE, "A" INDICATES TYPE, "3" INDICATES CIRCUIT NUMBER ASSIGNMENT, "a" INDICATES LOCAL SWITCHING CONTROL.
CONNECT FIXTURES SO THAT ALL LAMPS ARE CONTROLLED BY
LED LIGHTING FIXTURE - CONNECTED TO EMERGENCY LIFE SAFETY LIGHTING CIRCUIT - TYPE AS SPECIFIED IN
SCHEDULE. "A" INDICATES TYPE. CONNECT AHEAD OF LOCAL SWITCHING.
EXIT SIGN - CEILING OR WALL MOUNTED - TYPE AS SPECIFIED IN SCHEDULE OR AS INDICATED ON PLANS
EMERGENCY BATTERY LIGHTING FIXTURE - CONNECT TO EMERGENCY LIFE SAFETY CIRCUIT AHEAD OF LOCAL
SWITCHING. TYPE AS SPECIFIED IN SCHEDULE.
A
A
3,a aS aS
A
3,a
A
A aS
RC
D
LIGHTING CONTROLS
20A-1P-120/277V WALL SWITCH - MOUNTED AT 48" AFF UNLESS OTHERWISE NOTED
20A-3WAY-120/277V WALL SWITCH MOUNTED AT 48" UNLESS OTHERWISE NOTED
20A-4WAY-120/277V WALL SWITCH MOUNTED AT 48" UNLESS OTHERWISE NOTED
277V, SINGLE POLE, LARGE PADDLE SWITCH WITH SMALL PRESET, DIMMER SLIDER, 0-10VDC DIMMING SYSTEM, MOUNTED AT 48" AFF UNLESS OTHERWISE NOTED. VERIFY ALL SWITCHES ARE COMPATIBLE WITH FIXTURE AND DRIVER TYPE.
LIGHTING ROOM CONTROLLER - SYSTEM INTEGRATES LOW-VOLTAGE DIMMING SWITCH/SWITCHES AND OCCUPANCY SENSOR AND PROVIDES DIMMING AND CONTROL OUTPUT TO LIGHTING FIXTURES. UTILIZES LOW-VOLTAGE CABLING (CAT6A OR SIMILAR AS PER MANUFACTURER'S WIRING DIAGRAMS) TO CONNECT TO SWITCHING AND OCCUPANCY SENSORS. UTILIZES STANDARD LOW-VOLTAGE (0-10V) CABLING TO CONNECT TO FIXTURE'S DIMMING DRIVER. REFER TO OCCUPANCY SENSOR DIAGRAM FOR ADDITIONAL INFORMATION. ROOM CONTROLLER, OCCUPANCY SENSOR, AND OVER-
RIDE SWITCH SHALL BE A COMPLETE SYSTEM FROM A SINGLE MANUFACTURER.
NOTE: REFER TO "DEVICE AND WALL PLATE DETAIL" FOR ADDITIONAL INFORMATION.
S
S
S
S
OS
DLVS
24V SINGLE POLE, LARGE BUTTON SWITCH WITH INTEGRAL DIMMING FUNCTION - MOUNTED AT 48" AFF UNLESS OTHERWISE NOTED. PROVIDE SINGLE GANG BACK BOX AND 1"C FROM BACK BOX TO ABOVE FINISHED CEILING TO ROUTE LOW-VOLTAGE CABLING. CONNECT COMPLETE TO ROOM CONTROLLER VIA LOW-VOLTAGE CABLING (CAT6A OR SIMILAR AS REQUIRED BY MANUFACTURER'S WIRING DIAGRAMS). SWITCH SHALL BE CAPABLE OF 3- WAY OR 4-WAY OPERATION BY INSTALLATION OF ADDITIONAL SWITCHES. ADDITIONAL SWITCHES MAY BE DIRECTLY CONNECTED TO ROOM CONTROLLER OR DAISY-CHAINED FROM OTHER SWITCHES (AS DIRECTED BY
MANUFACTURER).
DUAL TECHNOLOGY OCCUPANCY SENSOR - CONNECTS TO ROOM CONTROLLER VIA LOW-VOLTAGE CABLING (CAT6A OR SIMILAR AS REQUIRED BY MANUFACTURER'S WIRING DIAGRAMS). PROVIDE FORM C RELAY IN RELAY
UNIT IN ALL OCCUPANCY SENSORS FOR HVAC SWITCHING.
RELAY DESIGNATIONS
# - PROVIDE RELAY WITH NORMALLY OPEN (N.O.) CONTACT(S), # DENOTES THE QUANTITY OF N.O. RELAYS. IF
BLANK, PROVIDE (1) N.O. RELAY.
OTHER DESIGNATIONS
L - "LINEAR COVERAGE", TWO SIDED, 90 LINEAR FT. COVERAGE. IF BLANK, PROVIDE 360 DEG. COVERAGE.
POWER DISTRIBUTION EQUIPMENT
208/120V-3PH-4W-SN PANELBOARD UNLESS OTHERWISE NOTED
480/277V-3PH-4W-SN PANELBOARD UNLESS OTHERWISE NOTED
SPECIAL PANEL OR PULLBOX - SIZE AND TYPE AS NOTED
NON-FUSED DISCONNECT SWITCH - SIZE AND TYPE AS NOTED, WITH TYPE RK1 FUSES
FUSED DISCONNECT SWITCH - SIZE AND TYPE AS NOTED, WITH TYPE RK1 FUSES
ELECTRICAL GROUNDING BUS BAR
EGB
GENERAL LEGEND:
CODED NOTE - "1" INDICATES NOTE NUMBER
REVISION REFERENCE NUMBER
MECHANICAL EQUIPMENT IDENTIFIER
DETAIL REFERENCE - "1" INDICATES DETAIL NUMBER, "E0.1" INDICATES DRAWING NUMBER
COLUMN REFERENCE GRID
INDICATES EXISTING CONSTRUCTION WALL TYPE
INDICATES DEMOLITION WALL TYPE
INDICATES NEW CONSTRUCTION WALL TYPE
AC
GB13
E0.1
A
MOTOR AND MOTOR CONTROLLERS (FLOOR PLAN VIEW)
COMBINATION FUSED MAGNETIC MOTOR STARTER COMPLETE WHITE "HAND-OFF-AUTO" SELECTOR SWITCH AND RED "RUN" PILOT LIGHT IN COVER. NEMA SIZE 0 CONTACTS AND NEMA 1 ENCLOSURE MINIMUM UNLESS OTHERWISE NOTED.
VARIABLE SPEED DRIVE MOTOR CONTROLLER - (REFER TO SPECIFICATIONS SECTION 262911).
CONTROLLER FURNISHED WITH EQUIPMENT
VSD
WIRING DEVICES
20A-125V, HOSPITAL GRADE, GROUNDED DUPLEX RECEPTACLE, MOUNTED IN (1) GANG BACKBOX AT 18" UNLESS
OTHERWISE NOTED. CONNECTED TO NORMAL POWER
DOUBLE 20A-125V, HOSPITAL GRADE, GROUNDED DUPLEX RECEPTACLES, MOUNTED IN (2) GANG BACKBOX AT 18" UNLESS
OTHERWISE NOTED. CONNECTED TO NORMAL POWER.
20A-125V, HOSPITAL GRADE, GROUND FAULT (GF) INTERRUPTER TYPE RECEPTACLE, MOUNTED IN A (2) GANG BACKBOX AT
18" UNLESS OTHERWISE NOTED. CONNECTED TO NORMAL POWER
SAME DEVICE TYPES AS INDICATED ABOVE EXCEPT SHADING INDICATES DEVICE IS CONNECTED TO EMERGENCY CIRCUIT
SPECIAL OUTLETS - TYPES AS NOTED ON PLANS
EMERGENCY POWER OFF PUSHBUTTON WITH COVER. REFER TO "EMERGENCY POWER OFF SYSTEM DIAGRAM AND NOTES"
FOR ADDITIONAL INFORMATION AND WORK REQUIREMENTS.
NOTE: REFER TO "DEVICE AND WALL PLATE DETAIL" FOR ADDITIONAL INFORMATION.
WIRE TERMINATIONS
JJ JUNCTION BOX, CEILING OR WALL MOUNTED, 4" SQ. WITH GROUND LUG, UNLESS OTHERWISE NOTED
MOTOR - HORSEPOWER AND VOLTAGE AS NOTED
3/4" MINIMUM SIZE CONCEALED CONDUIT WITH #12 AWG, THWN STRANDED COPPER CONDUCTORS PLUS SEPARATE #12 GROUND ( ), AND CONDUIT WIRE FILLS IN ACCORDANCE WITH N.E.C. - EMT MAY BE USED IN INTERIOR STUD WALLS, AND ABOVE FINISHED CEILINGS. DEDICATED NEUTRAL CONDUCTORS ARE REQUIRED FOR ALL 120V AND 277V BRANCH CIRCUITS. MULTIWIRE BRANCH CIRCUITS WITH SHARED NEUTRAL CONDUCTORS ARE NOT PERMITTED. ROUTE NO MORE THAN (3) BRANCH CIRCUIT HOMERUNS PER EACH CONDUIT RUN.
FIRE ALARM SYSTEM
F
F
F
RS
CM
MM
FIRE ALARM SYSTEM NOTES:
ALL FIRE ALARM SYSTEM DEVICES SHALL BE CONNECTED COMPLETE TO THE MAIN FIRE ALARM SYSTEM CONTROL PANEL IN ACCORDANCE WITH ENGINEER APPROVED MANUFACTURER'S SHOP DRAWING WIRING DIAGRAMS AND DETAILS. CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING A FULLY CODE COMPLIANT FIRE ALARM SYSTEM. DEVICES SHOWN ON PLAN ARE FOR
REFERENCE ONLY.
PROVIDE A 2-GANG MINIMUM SIZE BACKBOX FOR ALL OF THE ABOVE FIRE ALARM DEVICES.
ALL FIRE ALARM SYSTEM CONDUCTORS SHALL BE INSTALL IN 3/4" MINIMUM SIZE COMPLETE CONDUIT SYSTEM WITH COLOR CODED
WIRING AS INDICATED ON SHOP DRAWINGS - MAINTAIN FACILITY COLOR CODING.
ALL NETWORK AND NETWORK CABLES SHALL BE "COMMUNICATION GRADE" TYPE CABLE.
FURNISH, INSTALL AND CONNECT ALL FIRE ALARM DEVICES IN ACCORDANCE WITH WIRING DIAGRAMS PREPARED BY SYSTEM
VENDOR.
EXISTING FIRE ALARM SYSTEM BY NOTIFIER. REFER TO SPECIFICATIONS SECTION 283100 FOR ELECTRICAL REQUIREMENTS.
FIRE ALARM PANELS - MOUNTING INDICATED FOR EACH TYPE.
FACP - EXISTING FIRE ALARM CONTROL PANEL (TYPE AS INDICATED ON PLANS).
MANUAL FIRE ALARM PULL STATION - MOUNT AT 48" AFF TO CENTERLINE OF DEVICE.
FIRE ALARM VISUAL SIGNAL DEVICE (ADA TYPE) MOUNTED 80" AFF UNLESS NOTED. RED HOUSING WITH WHITE "FIRE"
LETTERING.
FIRE ALARM AUDIBLE VISUAL (SPEAKER/STROBE) SIGNAL DEVICE (ADA TYPE) MOUNTED 80"AFF UNLESS NOTED. RED HOUSING
WITH WHITE "FIRE" LETTERING.
SMOKE DETECTOR - ADDRESSABLE INTELLIGENT PHOTOELECTRIC TYPE - CEILING MOUNTED.
EL - ELEVATOR RECALL
DUCT DETECTOR - ADDRESSABLE INTELLIGENT PHOTOELECTRIC DETECTOR, SAMPLING TUBES AND PROGRAMMABLE RELAY BASE. PROVIDE DUCT DETECTOR TEST/RESET SWITCH WITH REMOTE INDICATOR LAMP FOR EACH DUCT DETECTOR.
(TEST SWITCH MAY NOT BE SHOWN ON PLANS)
HEAT DETECTOR
24V COMBINATION SMOKE/FIRE DAMPER - FURNISHED AND INSTALLED BY THE MC. EC SHALL PROVIDE 120V CIRCUIT FOR CONNECTION TO ASSOCIATED LOW-VOLTAGE TRANSFORMER, (1) FIRE ALARM CONTROL MODULE FOR DAMPER CONTROL, (1) FIRE ALARM MONITOR MODULE TO MONITOR DAMPER POWER, AND (1) FIRE ALARM MONITOR MODULE TO MONITOR DAMPER POSITION. PROVIDE ALL NECESSARY CONDUIT AND ASSOCIATED WIRING, PROGRAMMING, ETC. AS REQUIRED TO CONNECT
DAMPER AND FIRE ALARM DEVICES COMPLETE.
CONTROL MODULE - ADDRESSABLE RELAY FOR CONTROL OF SMOKE DAMPERS, ELEVATOR RECALL, MAGNETIC DOOR
HOLDERS, AUTOMATIC DOORS, ETC.
MONITOR MODULE - ADDRESSABLE SUPERVISED FOR MONITORING TAMPER SWITCH , FLOW SWITCH, DAMPER POSITION,ETC.
D
F1.
F2.
F3.
F4.
F5.
F6.
HD
SECURITY SYSTEM LEGEND
SECURITY CONTROL PANEL - SURFACE MOUNTED
LENEL = LENEL SECURITY PANEL
SECURITY CAMERA - STANDARD INDOOR - 2 MEGAPIXEL, 1/2.8" COLOR CMOS SENSOR (1,920 x 1,080 MAX RESOLUTION), PROGRESSIVE SCAN, INTEGRAL 3-10.5MM VARIFOCAL LENS WITH F1.4 MAXIMUM APERTURE RATIO. 92° TO 34° HORIZONTAL FIELD OF VIEW, 50° TO 20° VERTICAL FIELD OF VIEW, WIDE DYNAMIC RANGE, INTEGRAL IR ILLUMINATION WITH 25FT RANGE, OPERATING TEMPERATURE RANGE OF -22°F TO 122°F, POWER OVER ETHERNET (MAX 11W). PROVIDE ALL MOUNTS AND WIRING FOR POWER, DATA, AND CONTROL NECESSARY FOR A COMPLETE INSTALLATION. CAMERA HOUSING SHALL BE
SUITABLE FOR INDOOR USE AND VANDAL RESISTANT (IK10 RATED).
PROXIMITY CARD READER WITH INTEGRAL KEY PAD FOR DUAL-AUTHENTICATION - PROVIDE READER AT ACCESS CONTROLLED DOORS AS INDICATED. REFER TO DETAILS FOR TYPICAL INSTALLATION REQUIREMENTS. INSTALL READER AT
LOCATION INDICATED IN LIEU OF TYPICAL DETAILS WHEN SHOWN ON PLANS.
PROXIMITY CARD READER - PROVIDE READER AT ALL ACCESS CONTROLLED DOORS. REFER TO DETAILS FOR TYPICAL INSTALLATION REQUIREMENTS. INSTALL CARDER AT LOCATION IN LIEU OF TYPICAL DETAILS WHEN SHOWN ON PLANS.
ACCESS CONTROLLED DOOR TYPE 1 - SINGLE DOOR WITH ELECTRIC STRIKE AND HARD WIRED READER (TYPE AS INDICATED).
REFER TO "ACCESS CONTROLLED DOOR TYPE 1 DETAIL".
ACCESS CONTROLLED DOOR TYPE 2 - DOUBLE DOOR WITH ELECTRIC STRIKE AND HARD WIRED READER (TYPE AS
INDICATED). REFER TO "ACCESS CONTROLLED DOOR TYPE 2 DETAIL"
ACCESS CONTROLLED KEY SAFE - KEY SYSTEMS - MODEL SWATBOX OR EQUAL. RECESSED, WALL-MOUNTED KEY STORAGE SAFE WITH DIRECT CONTROL VIA ADJACENT WALL-MOUNTED DUAL-AUTHENTICATION CARD READER.
D1
D2
PROVIDE MINIMUM SIZE BACK BOX AS REQUIRED FOR ALL OF THE ABOVE SECURITY DEVICES AND INSTALL IN 3/4"C MINIMUM
COMPLETE CONDUIT SYSTEM TO JUNCTION BOX ABOVE FINISHED CEILING.
REFER TO SPECIFICATIONS DIVISION 28 FOR FURTHER DETAILS REGARDING THE SECURITY SYSTEM.
MOUNT DEVICES AT MOUNTING HEIGHTS LISTED ABOVE UNLESS OTHERWISE NOTED ON THE FLOOR PLANS. COORDINATE EXACT
MOUNTING LOCATION WITH ARCHITECTURAL ELEVATIONS.
ALL SECURITY SYSTEM ROUGH-INS, CONDUIT, WIRING AND EQUIPMENT/DEVICES SHALL BE PROVIDED BY CONTRACTOR.
CONTRACTOR SHALL VERIFY ALL BACKBOX SIXES WITH VA COR AND MANUFACTURER'S INSTALLATION INSTRUCTIONS PRIOR TO
ROUGH-IN.
FURNISH, INSTALL AND CONNECT ALL SECURITY DEVICES IN ACCORDANCE WITH LENEL SYSTEM PROVIDE. PROVIDE ALL ADDITIONAL LENEL COMPONENTS AS NECESSARY FOR A COMPLETE SYSTEM. SUBMIT ALL LENEL DEVICES WITH SHOP DRAWINGS SUBMITTAL.
PK
S1.
S2.
S3.
S4.
S5.
S6.
SECURITY SYSTEM NOTES:
PK
C
PR
PR
S
ABBREVIATIONS
GENERAL ELECTRICAL SPECIFICATION NOTES:
DEDICATED NEUTRAL CONDUCTORS
AC ABOVE COUNTER AT 9" UNLESS OTHERWISE NOTED
AF AMP FRAME
AFC ABOVE FINISHED CEILING
AFF ABOVE FINISHED FLOOR
AT AMP TRIP
BC BELOW COUNTER AT 18"AFF UNLESS OTHERWISE NOTED
BFC BELOW FINISHED CEILING
CM CEILING MOUNTED
EC ELECTRICAL CONTRACTOR
EG EQUIPMENT GROUND
GC GENERAL CONTRACTOR
GFCI GROUND FAULT CIRCUIT INTERRUPTER
IG ISOLATED GROUND
OIT OFFICE OF INFORMATION TECHNOLOGY
PROVIDE DEFINITION: FURNISH, INSTALL AND CONNECT COMPLETE.
X EXISTING OUTLET, DEVICE, LIGHTING FIXTURE, CONDUIT, ETC. - TO REMAIN
XB INDICATES EXISTING OUTLET, LIGHTING FIXTURE, CONDUIT, ETC - TO BE REMOVED.
PROVIDE BLANK COVER FOR OUTLET AND MAINTAIN CIRCUIT CONTINUITY.
XL NEW LOCATION OF EXISTING OUTLET, DEVICE, LIGHTING FIXTURE, ETC.
XN EXISTING OUTLET, DEVICE, LIGHTING FIXTURE, ETC. - TO BE REPLACED WITH NEW OF
SPECIFIED TYPE
XR EXISTING OUTLET, DEVICE, LIGHTING FIXTURE, CONDUIT, ETC. - TO BE REMOVED COMPLETE-
MAINTAIN CIRCUIT CONTINUITY TO ADJACENT OUTLETS, EXTEND CONDUIT AND WIRING AS
REQUIRED.
XRR EXISTING OUTLET, DEVICE, LIGHTING FIXTURE, ETC. - TO BE REMOVED AND REINSTALLED
AT NEW LOCATION - EXTEND CONDUIT AND WIRING AS REQUIRED
MC MECHANICAL CONTRACTOR
MLO MAIN LUGS ONLY
NEC NATIONAL ELECTRICAL CODE
NF NOT FUSED
OFE OWNER FURNISHED EQUIPMENT
TC TELECOMMUNICATIONS CONTRACTOR
TCC TEMPERATURE CONTROLS CONTRACTOR
TV TELEVISION
VAF/VAI VA FURNISHED/VA INSTALLED
VFD VARIABLE FREQUENCY DRIVE
WM WIREMOLD
WP WEATHERPROOF ENCLOSURE - NEMA 4
DEDICATED NEUTRAL CONDUCTORS ARE REQUIRED FOR ALL 120V AND 277V BRANCH CIRCUITS. MULTIWIRE BRANCH
CIRCUITS WITH SHARED NEUTRAL CONDUCTORS ARE NOT PERMITTED.
ROUTE NO MORE THAN (3) BRANCH CIRCUIT HOMERUNS PER EACH CONDUIT RUN.
THE FOLLOWING ITEMS SUPERCEDE ITEMS WITHIN THE SPECIFICATIONS:
ALL FIRESTOPPING MATERIAL SHALL BE MANUFACTURED BY STI. ALL INSTALLERS SHALL BE CERTIFIED INSTALLERS OF STI
FIRESTOPPING PRODUCTS AND HAVE PROOF OF CERTIFICATION.
THE USE OF HOSPITAL GRADE HCF CABLE ISNOTPERMITTED ON THIS PROJECT.
THE FOLLOWING SYSTEM CABLING IS PERMITTED TO BE INSTALLED IN THE CABLE TRAY SYSTEM:
A. TEL/DATA CABLING
B. HOSPITAL PAGING SYSTEM
ALL OTHER SPECIAL SYSTEMS CABLING (FIRE ALARM, NURSE CALL, CATV) SHALL BE INSTALLED IN A COMPLETE CONDUIT
SYSTEM. E.C SHALL GROUND CABLE TRAY IN ACCORDANCE WITH N.E.C. ARTICLE 250.96.
GENERAL ELECTRICAL INSTALLATION NOTES:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
ALL MOUNTING HEIGHTS ARE TO CENTER OF DEVICE UNLESS OTHERWISE NOTED.
ALL NEW WALL MOUNTED ELECTRICAL DEVICES ARE TO BE INSTALLED FLUSH IN WALL UNLESS OTHERWISE NOTED.
ALL ELECTRICAL CONDUIT SHALL BE CONCEALED BEHIND FINISHED WALLS AND ABOVE FINISHED CEILING UNLESS OTHERWISE NOTED. THE COST TO CUT AND PATCH WALLS SHALL BE THE RESPONSIBILITY OF THE TRADE REQUIRING
THE CUTTING.
CONTRACTOR IS RESPONSIBLE FOR REMOVAL AND REPLACEMENT OF CEILINGS REQUIRED FOR ELECTRICAL WORK.
CONTRACTOR SHALL REPLACE ANY DAMAGED CEILING TILES.
PRIOR TO INSTALLATION, VERIFY PRECISE LOCATION OF NEW OR RELOCATED WALL OR CEILING MOUNTED DEVICES
WITH ARCHITECTURAL ELEVATIONS AND REFLECTED CEILING PLANS.
COORDINATE ALL SHUT-DOWNS OF EXISTING ELECTRICAL SYSTEMS WITH OWNER A MINIMUM OF FOURTEEN (14) WORKING DAYS IN ADVANCE. ALL SHUT-DOWNS SHALL OCCUR DURING WEEKENDS OR BETWEEN 8:00PM AND 7:00AM
ON WEEKDAYS ("OFF-HOURS"). INCLUDE ALL PREMIUM TIME CHARGES IN BID.
ALL NOISE GENERATING OPERATIONS, INCLUDING CUTTING OF CEILINGS, WALLS AND FLOORS, CORING, DRILLING, ETC.
SHALL BE SCHEDULED DURING WEEKENDS OR BETWEEN 8:00PM AND 7:00AM ON WEEKDAYS ("OFF-HOURS").
INCLUDING ALL PREMIUM TIME CHARGES IN BID.
CONTRACTOR SHALL CONNECT ALL MECHANICAL EQUIPMENT COMPLETE PER MANUFACTURER'S WIRING DIAGRAMS AND INSTRUCTIONS. COORDINATE WITH MECHANICAL CONTRACTOR AND VERIFY LOCATION, VOLTAGE, AMPS, NO. OF WIRES, AND PROTECTION REQUIREMENTS PRIOR TO ROUGH-IN. CONTACT ENGINEER WITH ANY DISCREPANCIES FROM
DESIGN DRAWINGS.
PROVIDE LIQUID-TIGHT FLEXIBLE METAL CONDUIT FOR FINAL CONNECTION TO MECHANICAL EQUIPMENT OR OTHER
EQUIPMENT WHICH MAY PROPAGATE VIBRATION.
ALL FLUORESCENT LAMPS THAT WILL NOT BE REUSED SHALL BE DISPOSED OF IN ACCORDANCE WITH EPA STANDARDS, AND WRITTEN EVIDENCE OF PROPER DISPOSAL SHALL BE FURNISHED TO THE OWNER.
ALL WORK SHALL BE PERFORMED IN STRICT CONFORMANCE WITH THE PHASING REQUIREMENTS OF THE PROJECT.
ALL COSTS ASSOCIATED WITH THESE REQUIREMENTS SHALL BE INCLUDED IN THE BID SUBMITTAL.
CONTRACTOR IS RESPONSIBLE FOR PROVIDING TEMPORARY LIGHTING TO ADEQUATELY LIGHT ALL CONSTRUCTION AREAS, TEMPORARILY PARTITIONED AREAS, AND EXIT CORRIDORS MAINTAINED DURING CONSTRUCTION.
DEFINITION: "PROVIDE" - FURNISH, INSTALL AND CONNECT COMPLETE.
PROJECT AND PHASING SCOPE LINES INDICATE WHERE GENERAL CONSTRUCTION BOUNDARIES OCCUR. ELECTRICAL
WORK AND UTILITY TIE-INS MAY OCCUR OUTSIDE OF SCOPE LINES.
C. SECURITY
VDC VOICE/DATA CONTRACTOR
WM WIREMOLD
S
59459
M.P. LONG
R
ES
O F
I R
GE
NOI
S
P
E
N E
DERT
L EA
E I N
G
R
TS
TEA HF OO
IO
DESIGN AND CONSTRUCTION DOCUMENTS AS
INSTRUMENTS OF SERVICE ARE GIVEN IN
CONFIDENCE AND REMAIN THE PROPERTY OF
PERSPECTUS ARCHITECTURE. THE USE OF THIS
DESIGN AND THESE CONSTRUCTION
DOCUMENTS
FOR PURPOSES OTHER THAN THE SPECIFIC
PROJECT NAMED HEREIN IS STRICTLY
PROHIBITED WITHOUT THE EXPRESSED WRITTEN
CONSENT OF PERSPECTUS ARCHITECTURE.
COPYRIGHT C 2018.
13212 Shaker Square Suite 204 Cleveland, Ohio 44120 P. 216.752.1800 F. 216.752.3833
CONSULTANTS: ARCHITECT:
Drawing Title
Approved: Project Director Location
Project Title
Date Checked Drawn
Drawing Number
Building Number
Project Number
Office of
Facilities
Management
Dwg. of o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t
VA FORM 08-6231, OCT 1978
1 2 3 4 5 6 7 8 9 10
A
1 2 3 4 5 6 7 8 9 10
B
C
D
E
F
A
B
C
D
E
F
VAMC - WADE PARK
Revisions: Date
FULLY SPRINKLERED
18077
FREDRICK, FREDRICK & HELLER
ENGINEERS, INC.
672 EAST ROYALTON ROAD
BROADVIEW HTS., OHIO 44147
TEL. (440)546-9696
FAX: (440)546-9699
BID ISSUE 4/13/20
Increase IRM Physical
Security
541-19-102
CPCMPL
ELECTRICAL LEGEND AND
GENERAL NOTES
E0.1 4/13/20
TYPE A TYPE B TYPE C TYPE D
LIGHT FIXTURE APPEARANCE GUIDE
TYPE E
OCCUPANCY SENSOR PROGRAM SCHEDULE:
OS
RC
DLV
277VAC:24VDC
WHT
BLK
RED - SWITCHED HOT
ROOM
CONTROLLER
NEUTRAL
HOT
LED LIGHTING
FIXTURE DRIVER
24V OCCUPANCY SENSOR
CEILING MOUNTED
SENSOR TYPE ON CONTROL OFF CONTROL
DUAL
TECHNOLOGY
MANUAL
OFF TIME DELAY
MANUAL/SENSOR
AUTO OFF AFTER
15 MINUTES
PURPLE AND GRAY -
0-10V DIMMING
MOUNT ABOVE
FINISHED CEILING
LOW-VOLTAGE CABLE
(CAT6A OR SIMILAR)
TYPICAL
24V DIMMING SWITCH
WALL MOUNTED
BRANCH LIGHTING CIRCUIT
120V OR 277V - SEE PLANS
S
RED - UNSWITCHED HOT TO
NEXT ROOM CONTROLLER
S
59459
M.P. LONG
R
ES
O F
I R
GE
NOI
S
P
E
N E
DERT
L EA
E I N
G
R
TS
TEA HF OO
IO
DESIGN AND CONSTRUCTION DOCUMENTS AS
INSTRUMENTS OF SERVICE ARE GIVEN IN
CONFIDENCE AND REMAIN THE PROPERTY OF
PERSPECTUS ARCHITECTURE. THE USE OF THIS
DESIGN AND THESE CONSTRUCTION
DOCUMENTS
FOR PURPOSES OTHER THAN THE SPECIFIC
PROJECT NAMED HEREIN IS STRICTLY
PROHIBITED WITHOUT THE EXPRESSED WRITTEN
CONSENT OF PERSPECTUS ARCHITECTURE.
COPYRIGHT C 2018.
13212 Shaker Square Suite 204 Cleveland, Ohio 44120 P. 216.752.1800 F. 216.752.3833
CONSULTANTS: ARCHITECT:
Drawing Title
Approved: Project Director Location
Project Title
Date Checked Drawn
Drawing Number
Building Number
Project Number
Office of
Facilities
Management
Dwg. of o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t
VA FORM 08-6231, OCT 1978
1 2 3 4 5 6 7 8 9 10
A
1 2 3 4 5 6 7 8 9 10
B
C
D
E
F
A
B
C
D
E
F
VAMC - WADE PARK
Revisions: Date
FULLY SPRINKLERED
18077
FREDRICK, FREDRICK & HELLER
ENGINEERS, INC.
672 EAST ROYALTON ROAD
BROADVIEW HTS., OHIO 44147
TEL. (440)546-9696
FAX: (440)546-9699
BID ISSUE 4/13/20
Increase IRM Physical
Security
541-19-102
CPCMPL
LIGHTING FIXTURE SCHEDULE
AND APPEARANCE GUIDE
E0.2 4/13/20
LIGHTING FIXTURE SCHEDULE
TYPE FIXTURE DESCRIPTION MOUNTING MAX HEIGHT
FIXTURE DRIVER
TYPE LUMEN WATTAGE VOLTAGE COLOR TEMP LUMEN MAINTANCE RATING EFFICANCY TYPE QUANTITY
A
4'L X 2.3"H X 12"D SUSPENDED LED DIRECT/INDIRECT FIXTURE, 73% DOWN /
27% UP DISTRIBUTION, EXTRUDED ALUMINIUM AND DIE-FORMED 20 GAUGE
STEEL HOUSING, ACRYLIC MICRO-OPTICS LENS WITH EDGE LIGHT DESIGN,
HIGH REFLECTANCE WHITE POLYESTER POWDERCOAT FINISH.
SUSPENDED AT
LOWEST
DUCTWORK
ELEVATION
0' - 3" LED 3000 22 W 277 V 4000 K L85@60,000 hrs 134 LPW 0-10V Dimming 1
B
4'L X 3"H X 10"D WALL MOUNTED LED DIRECT/INDIRECT FIXTURE, 55%
DOWN / 45% UP DISTRIBUTION, EXTRUDED ALUMINIUM AND DIE-FORMED 20
GAUGE STEEL HOUSING, ACRYLIC MICRO-OPTICS LENS WITH EDGE LIGHT
DESIGN, HIGH REFLECTANCE WHITE POLYESTER POWDERCOAT FINISH.
WALL MOUNTED 0' - 3" LED 2276 27 W 277 V 4000 K L85@60,000 hrs 107 LPW 0-10V Dimming 1
C
4'L X 4"H X 3"W WALL MOUNTED LED STRIP FIXTURE, FROSTED ACRYLIC
DIFFUSER, BAKED WHITE HIGH REFLECTANCE PAINT FINISH, DIE FORMED
STEEL HOUSING, FUSING. MOUNT FIXTURE ABOVE DOOR
WALL MOUNTED 0' - 4" LED 2410 18 W 277 V 4000 K L87@60,000 hrs 130.7 LPW 0-10V Dimming 1
D
2' X 2' RECESSED DIRECT/INDIRECT TROFFER, ACRYLIC FROSTED LENS,
STEEL HOUSING, BAKED WHITE ENAMEL FINISH, STEEL DOOR ASSEMBLY
FOR ACCESS FROM BELOW
LAY-IN GRID 0' - 3 1/4" LED 2410 18 W 277 V 4000 K L89@60,000 hrs 106.9 LPW 0-10V Dimming 1
E
6-3/4'H X 5-3/4"W X 3-5/8"D WALL MOUNTED LED SERVICE LIGHT, SEALED
LED CHAMBER WITH IMPACT-RESISTANT GLASS LENS, ONE-PIECE
DIE-CAST ALUMINUM HINGED GASKETED DOOR, WET LOCATION LISTED,
CARBON BRONZE POLYESTER POWDERCOAT FINISH, WALL MOUNTED AT 8'
ABOVE ROOF.
WALL MOUNTED 0' - 7" LED 2103 18 W 120 V 4000 K L89@72,000 hrs 116.8 LPW 0-10V Dimming 1
EXIT
13"W X 7.5"H X 1-1/8"D LED TYPE, AC ONLY, WALL OR CEILING MOUNT AS
INDICATED ON DRAWINGS, ALUMINUM CANOPY WITH WHITE FINSIH, HIGH
IMPACT CLEAR POLYCABONATE HOUSING, RED LETTERS WITH WHITE
FACE. REFER TO LIGHTING PLANS FOR CUSTOM CONFIGURATION OF
CHEVRON DIRECTIONAL ARROWS. UL 924 LISTED. CONNECT TO
UNSWITCHED EMERGENCY LIFE SAFETY CIRCUIT.
LED 4 W N/A 1CEILING/WALL 1-1/8" N/A UNIV N/A N/A N/A
NOT TO SCALE
TYPICAL LIGHTING ROOM CONTROLLER
WITH LOW-VOLTAGE OCCUPANCY
SENSOR AND SWITCHING WIRING DIAGRAM 1
GENERAL LIGHTING INSTALLATION NOTES
L1 CONTRACTOR SHALL COORDINATE LIGHTING FIXTURE TYPE (GRID OR FLANGE) WITH ACTUAL CEILING TYPE PRIOR TO ORDERING FIXTURES. CONTACT
ENGINEER IF QUESTIONS SHOULD ARISE CONCERNING CEILING TYPES.
L2 CONTRACTOR SHALL VERIFY ALL DRIVER QUANTITIES WITH SWITCHING SHOWN ON PLANS PRIOR TO ORDERING FIXTURES. ADJUST DRIVER QUANTITIES
AS REQUIRED TO MATCH SWITCHING.
L3 VERIFY LIGHTING CIRCUIT VOLTAGE (277V-1Ø OR 120V-1Ø) PRIOR TO ORDERING LIGHTING FIXTURES OR STARTING ROUGH-IN OF BRANCH CIRCUITS.
IMMEDIATELY CONTACT ENGINEER WITH ANY DISCREPANCIES. CONTRACTOR IS RESPONSIBLE FOR ORDERING THE PROPER VOLTAGE FOR LIGHTING
FIXTURES, REGARDLESS OF VOLTAGE SHOWN ON LIGHTING FIXTURE SCHEDULE.
L4 CONTRACTOR SHALL VERIFY ALL FIXTURES TO BE CONTROLLED BY DIMMER SWITCHES AS SHOWN ON PLANS PRIOR TO ORDERING FIXTURES. PROVIDE ARCHITECTURAL DIMMING DRIVER (LED) WITH DIMMING RANGE FROM 100% DOWN TO 1% ON ALL DIMMED FIXTURES AND COMPATIBLE DIMMER CONTROLS
WHERE DIMMING IS INDICATED ON PLANS.
L5 REFER TO ELECTRICAL SPECIFICATIONS FOR LED COLOR TEMPERATURE AND DRIVER TYPE.
1 2 6 7 8 12 19 24 25 26 27 30 33 35 36
E
H
K
N P
Q
R
T
V
W
Y
Z
AA
BB
CC
D
B
A
G
S
U
39 4211 144 15 16 17 20 21 28 31 4038
X
Telecom/IRM
AFLVC1
Elec.
Closet
AFLVC2
E4.1
S
59459
M.P. LONG
R
ES
O F
I R
GE
NOI
S
P
E
N E
DERT
L EA
E I N
G
R
TS
TEA HF OO
IO
DESIGN AND CONSTRUCTION DOCUMENTS AS
INSTRUMENTS OF SERVICE ARE GIVEN IN
CONFIDENCE AND REMAIN THE PROPERTY OF
PERSPECTUS ARCHITECTURE. THE USE OF THIS
DESIGN AND THESE CONSTRUCTION
DOCUMENTS
FOR PURPOSES OTHER THAN THE SPECIFIC
PROJECT NAMED HEREIN IS STRICTLY
PROHIBITED WITHOUT THE EXPRESSED WRITTEN
CONSENT OF PERSPECTUS ARCHITECTURE.
COPYRIGHT C 2018.
13212 Shaker Square Suite 204 Cleveland, Ohio 44120 P. 216.752.1800 F. 216.752.3833
CONSULTANTS: ARCHITECT:
Drawing Title
Approved: Project Director Location
Project Title
Date Checked Drawn
Drawing Number
Building Number
Project Number
Office of
Facilities
Management
Dwg. of o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t
VA FORM 08-6231, OCT 1978
1 2 3 4 5 6 7 8 9 10
A
1 2 3 4 5 6 7 8 9 10
B
C
D
E
F
A
B
C
D
E
F
VAMC - WADE PARK
Revisions: Date
FULLY SPRINKLERED
18077
FREDRICK, FREDRICK & HELLER
ENGINEERS, INC.
672 EAST ROYALTON ROAD
BROADVIEW HTS., OHIO 44147
TEL. (440)546-9696
FAX: (440)546-9699
BID ISSUE 4/13/20
Increase IRM Physical
Security
541-19-102
JRDMPL
SUB BASEMENT ELECTRICAL
KEY PLAN
E1.1 4/13/20
0' 16' 32' 64' 128'0' 16' 32' 64' 128'0' 16' 32' 64' 128'0' 16' 32' 64' 128'0' 16' 32' 64' 128'
1/32" = 1'-0"
SUB BASEMENT ELECTRICAL KEY PLAN 1N
DEDUCT ALTERNATES:
DEDUCT ALTERNATE NO.1:
1. IF DEDUCT ALTERNATE 1 IS ACCEPTED, DELETE ALL WORK ASSOCIATED WITH ROOM AFLVC1.
2. REFER TO ARCHITECTURAL PLANS AND SPECIFICATIONS FOR ADDITIONAL INFORMATION.
DN
DN
DN
DN
1 2 6 7 8 9 12 13 19 24 25 26 27 30 33 34 35 36
H
K
L
Q
T
V
W
Y
Z
F
D
B
A
G
U
39 423 114 15 16 17 18 20 21 28 31 414038
M
X
Comm
BA149
Storage
BA151A
Comm
BAC308
IRM
BB471
IRM
BB379
Telecomm
BC505
IRM
BD421
IRM
Telecomm
Room
BF515
Engineering Closet
BF516
IRM
BF312
IRM
Satellite
Computer/ Equipment
Room
BF101
Telecom
IRM
BFLVC1
Elec.
Closet
BFLVC2
Security
BF468A
E4.1
E4.1
E4.1
E4.1
E4.1
E4.2
E4.2
E4.1
E4.1
E4.1
E4.2
ELEC
BC315
EQSBAC-1
UP THROUGH FIRST AND
SECOND FLOORS TO THIRD
FLOOR
CR-PPA
LEB4CR
X
X
X
X
LMB2-CR
UP TO FIRST
FLOOR
S
59459
M.P. LONG
R
ES
O F
I R
GE
NOI
S
P
E
N E
DERT
L EA
E I N
G
R
TS
TEA HF OO
IO
DESIGN AND CONSTRUCTION DOCUMENTS AS
INSTRUMENTS OF SERVICE ARE GIVEN IN
CONFIDENCE AND REMAIN THE PROPERTY OF
PERSPECTUS ARCHITECTURE. THE USE OF THIS
DESIGN AND THESE CONSTRUCTION
DOCUMENTS
FOR PURPOSES OTHER THAN THE SPECIFIC
PROJECT NAMED HEREIN IS STRICTLY
PROHIBITED WITHOUT THE EXPRESSED WRITTEN
CONSENT OF PERSPECTUS ARCHITECTURE.
COPYRIGHT C 2018.
13212 Shaker Square Suite 204 Cleveland, Ohio 44120 P. 216.752.1800 F. 216.752.3833
CONSULTANTS: ARCHITECT:
Drawing Title
Approved: Project Director Location
Project Title
Date Checked Drawn
Drawing Number
Building Number
Project Number
Office of
Facilities
Management
Dwg. of o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t
VA FORM 08-6231, OCT 1978
1 2 3 4 5 6 7 8 9 10
A
1 2 3 4 5 6 7 8 9 10
B
C
D
E
F
A
B
C
D
E
F
VAMC - WADE PARK
Revisions: Date
FULLY SPRINKLERED
18077
FREDRICK, FREDRICK & HELLER
ENGINEERS, INC.
672 EAST ROYALTON ROAD
BROADVIEW HTS., OHIO 44147
TEL. (440)546-9696
FAX: (440)546-9699
BID ISSUE 4/13/20
Increase IRM Physical
Security
541-19-102
JRDMPL
BASEMENT ELECTRICAL KEY
PLAN
E1.2 4/13/20
0' 16' 32' 64' 128'0' 16' 32' 64' 128'0' 16' 32' 64' 128'0' 16' 32' 64' 128'0' 16' 32' 64' 128'
1/32" = 1'-0"
BASEMENT ELECTRICAL KEY PLAN 1N
DEDUCT ALTERNATES:
DEDUCT ALTERNATE NO.1:
1. IF DEDUCT ALTERNATE 1 IS ACCEPTED, DELETE ALL WORK ASSOCIATED WITH ROOM BFLVC1 AND BF101.
2. REFER TO ARCHITECTURAL PLANS AND SPECIFICATIONS FOR ADDITIONAL INFORMATION.
DEDUCT ALTERNATE NO.3:
1. IF DEDUCT ALTERNATE 3 IS ACCEPTED, DELETE ALL WORK ASSOCIATED WITH ROOM BF312, BF515, BD421, BC505, BB471, BAC308, BA149, BA151A, AND BB379.
DN
DN
DN
DN
DN
FEC
1 2 6 7 8 9 12 13 19 24 25 26 27 29 30 32 33 34 35 36 37
E
H
K
L
Q
T
V
W
Y
Z
F
D
B
A
G
U
39 423 114 15 16 17 18 20 21 28 31 4023
M
X
Comm
Clos
1A181
Comm
1AC262
Comm
1A114
Telecomm
1C519
IRM
Telecomm
Room
1F515
Electric
Closet
1F516
Tele.
Closet
K122A
Data
1E257
Telecom/
IRM
1FLVC1
Elec.
Closet
1FLVC2
E4.2
E4.2
E4.2
E4.2
E4.2
E4.2
E4.3
E4.3
E4.3
E4.2
E4.3
E4.3
LE12CR
E4.3
IRM
1E334
IRM
1E491
IRM
1C300D
IRM
1B496
IRM
1B100
DOWN TO BASEMENT
FROM THIRD FLOOR
LM12B-CR
LM11-CR
DOWN TO
BASEMENT TO
PANEL LEB4CR
E4.2
OI&T
1B468
E4.3
Elect.
1D211
S
59459
M.P. LONG
R
ES
O F
I R
GE
NOI
S
P
E
N E
DERT
L EA
E I N
G
R
TS
TEA HF OO
IO
DESIGN AND CONSTRUCTION DOCUMENTS AS
INSTRUMENTS OF SERVICE ARE GIVEN IN
CONFIDENCE AND REMAIN THE PROPERTY OF
PERSPECTUS ARCHITECTURE. THE USE OF THIS
DESIGN AND THESE CONSTRUCTION
DOCUMENTS
FOR PURPOSES OTHER THAN THE SPECIFIC
PROJECT NAMED HEREIN IS STRICTLY
PROHIBITED WITHOUT THE EXPRESSED WRITTEN
CONSENT OF PERSPECTUS ARCHITECTURE.
COPYRIGHT C 2018.
13212 Shaker Square Suite 204 Cleveland, Ohio 44120 P. 216.752.1800 F. 216.752.3833
CONSULTANTS: ARCHITECT:
Drawing Title
Approved: Project Director Location
Project Title
Date Checked Drawn
Drawing Number
Building Number
Project Number
Office of
Facilities
Management
Dwg. of o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t
VA FORM 08-6231, OCT 1978
1 2 3 4 5 6 7 8 9 10
A
1 2 3 4 5 6 7 8 9 10
B
C
D
E
F
A
B
C
D
E
F
VAMC - WADE PARK
Revisions: Date
FULLY SPRINKLERED
18077
FREDRICK, FREDRICK & HELLER
ENGINEERS, INC.
672 EAST ROYALTON ROAD
BROADVIEW HTS., OHIO 44147
TEL. (440)546-9696
FAX: (440)546-9699
BID ISSUE 4/13/20
Increase IRM Physical
Security
541-19-102
JRDMPL
FIRST FLOOR ELECTRICAL KEY
PLAN
E1.3 4/13/20
0' 16' 32' 64' 128'0' 16' 32' 64' 128'0' 16' 32' 64' 128'0' 16' 32' 64' 128'0' 16' 32' 64' 128'
1/32" = 1'-0"
FIRST FLOOR ELECTRICAL KEY PLAN 1
N
DEDUCT ALTERNATES:
DEDUCT ALTERNATE NO.1:
1. IF DEDUCT ALTERNATE 1 IS ACCEPTED, DELETE ALL WORK ASSOCIATED WITH ROOM 1FLVC1.
2. REFER TO ARCHITECTURAL PLANS AND SPECIFICATIONS FOR ADDITIONAL INFORMATION.
DEDUCT ALTERNATE NO.4:
1. IF DEDUCT ALTERNATE 4 IS ACCEPTED, DELETE ALL WORK ASSOCIATED WITH ROOM K122A, 1E491, 1F515, 1C519, 1B496, 1A114, 1A181, 1AC262, 1B100, 1C300D, 1E257, AND 1E334.
1 2 5 6 7 8 9 12 13 19 24 25 26 27 29 30 32 33 34 35 36 37
E
H
K
L
Q
T
V
W
Y
Z
F
D
B
A
G
U
39 423 114 15 16 17 18 20 21 28 31 4123
M
X
Comm
Clos
2A186
Closet, Electrical
2A158
Comm
2A103
Comm.
K223
Telecom/
IRM
2FLVC1
Elec.
Closet
2FLVC2
E4.4
E4.3
E4.3
E4.3
E4.4
E4.4
E4.4
E4.4
E4.4
IRM
2E331
IRM
2C134
IRM
2B149
Plaster &
Splint
Closet
DOWN TO BASEMENT
FROM THIRD FLOOR
S
59459
M.P. LONG
R
ES
O F
I R
GE
NOI
S
P
E
N E
DERT
L EA
E I N
G
R
TS
TEA HF OO
IO
DESIGN AND CONSTRUCTION DOCUMENTS AS
INSTRUMENTS OF SERVICE ARE GIVEN IN
CONFIDENCE AND REMAIN THE PROPERTY OF
PERSPECTUS ARCHITECTURE. THE USE OF THIS
DESIGN AND THESE CONSTRUCTION
DOCUMENTS
FOR PURPOSES OTHER THAN THE SPECIFIC
PROJECT NAMED HEREIN IS STRICTLY
PROHIBITED WITHOUT THE EXPRESSED WRITTEN
CONSENT OF PERSPECTUS ARCHITECTURE.
COPYRIGHT C 2018.
13212 Shaker Square Suite 204 Cleveland, Ohio 44120 P. 216.752.1800 F. 216.752.3833
CONSULTANTS: ARCHITECT:
Drawing Title
Approved: Project Director Location
Project Title
Date Checked Drawn
Drawing Number
Building Number
Project Number
Office of
Facilities
Management
Dwg. of o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t
VA FORM 08-6231, OCT 1978
1 2 3 4 5 6 7 8 9 10
A
1 2 3 4 5 6 7 8 9 10
B
C
D
E
F
A
B
C
D
E
F
VAMC - WADE PARK
Revisions: Date
FULLY SPRINKLERED
18077
FREDRICK, FREDRICK & HELLER
ENGINEERS, INC.
672 EAST ROYALTON ROAD
BROADVIEW HTS., OHIO 44147
TEL. (440)546-9696
FAX: (440)546-9699
BID ISSUE 4/13/20
Increase IRM Physical
Security
541-19-102
JRDMPL
SECOND FLOOR ELECTRICAL
KEY PLAN
E1.4 4/13/20
0' 16' 32' 64' 128'0' 16' 32' 64' 128'0' 16' 32' 64' 128'0' 16' 32' 64' 128'0' 16' 32' 64' 128'
1/32" = 1'-0"
SECOND FLOOR ELECTRICAL KEY PLAN 1N
DEDUCT ALTERNATES:
DEDUCT ALTERNATE NO.1:
1. IF DEDUCT ALTERNATE 1 IS ACCEPTED, DELETE ALL WORK ASSOCIATED WITH ROOM 2FLVC1.
2. REFER TO ARCHITECTURAL PLANS AND SPECIFICATIONS FOR ADDITIONAL INFORMATION.
DEDUCT ALTERNATE NO.4:
1. IF DEDUCT ALTERNATE 4 IS ACCEPTED, DELETE ALL WORK ASSOCIATED WITH ROOM K223, 2E331, 2B149, 2A103, 2A158, 2A186, 2C363, AND 2C134
UP
1 2 5 6 7 8 9 12 13 19 24 25 26 27 29 30 32 33 34 35 36 37
E
H
K
L
Q
T
V
W
Y
Z
F
D
B
A
G
U
39 423 114 15 16 17 18 20 21 28 31 414038
M
X
E4.4
E4.4
E4.5
E4.4
E4.4
E4.5
ETD-MDPB
DOWN TO BASEMENT VIA
SECOND AND FIRST
FLOORS
ETD-2
ETD-4
ETD-3
X
X
ERE31-CR
X
Telecom/ IRM
3FLVC1
IRM
3B129
Telecom Rm
3B162C-2
IRM
3A101
ELEC.
3C-105
Tel/Com Clos
3AC267
Tel/Com
3AC322
S
59459
M.P. LONG
R
ES
O F
I R
GE
NOI
S
P
E
N E
DERT
L EA
E I N
G
R
TS
TEA HF OO
IO
DESIGN AND CONSTRUCTION DOCUMENTS AS
INSTRUMENTS OF SERVICE ARE GIVEN IN
CONFIDENCE AND REMAIN THE PROPERTY OF
PERSPECTUS ARCHITECTURE. THE USE OF THIS
DESIGN AND THESE CONSTRUCTION
DOCUMENTS
FOR PURPOSES OTHER THAN THE SPECIFIC
PROJECT NAMED HEREIN IS STRICTLY
PROHIBITED WITHOUT THE EXPRESSED WRITTEN
CONSENT OF PERSPECTUS ARCHITECTURE.
COPYRIGHT C 2018.
13212 Shaker Square Suite 204 Cleveland, Ohio 44120 P. 216.752.1800 F. 216.752.3833
CONSULTANTS: ARCHITECT:
Drawing Title
Approved: Project Director Location
Project Title
Date Checked Drawn
Drawing Number
Building Number
Project Number
Office of
Facilities
Management
Dwg. of o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t
VA FORM 08-6231, OCT 1978
1 2 3 4 5 6 7 8 9 10
A
1 2 3 4 5 6 7 8 9 10
B
C
D
E
F
A
B
C
D
E
F
VAMC - WADE PARK
Revisions: Date
FULLY SPRINKLERED
18077
FREDRICK, FREDRICK & HELLER
ENGINEERS, INC.
672 EAST ROYALTON ROAD
BROADVIEW HTS., OHIO 44147
TEL. (440)546-9696
FAX: (440)546-9699
BID ISSUE 4/13/20
Increase IRM Physical
Security
541-19-102
JRDMPL
THIRD FLOOR ELECTRICAL KEY
PLAN
E1.5 4/13/20
N
0' 16' 32' 64' 128'0' 16' 32' 64' 128'0' 16' 32' 64' 128'0' 16' 32' 64' 128'0' 16' 32' 64' 128'
1/32" = 1'-0"
THIRD FLOOR ELECTRICAL KEY PLAN 1
# KEY PLAN CODED NOTES
PROVIDE NEW FEEDERS FOR EXISTING PANELBOARDS FROM EXISTING PANELBOARD ERE31-CR AND PREPARE FOR TERMINATION PRIOR TO CUTOVER TO MINIMIZE SERVICE DISRUPTION. COORDINATE PANELBOARD SHUTDOWN WITH VA COR AT LEAST (14) DAYS PRIOR. REFER TO ONE-LINE DIAGRAM FOR
FEEDER INFORMATION AND PANELBOARD SCHEDULES FOR EXISTING PANELBOARD INFORMATION.
PROVIDE NEC COMPLIANT PULLBOXES ALONG NEW FEEDER RUNS ON 100' CENTERS, AFTER (4) 90-DEGREE BENDS, OR WHERE REQUIRED TO MEET MANUFACTURER'S PULLING SPECIFICATIONS OF CONDUCTORS BEING INSTALLED. FIELD VERIFY EXACT LOCATIONS OF ALL PULLBOXES AND COORDINATE WITH EXISTING AND NEW SYSTEMS ABOVE CEILING TO MAINTAIN PULLBOX ACCESSIBILITY AFTER PROJECT IS COMPLETED.
NEW TELECOMMUNICATIONS OUTLETS (TCOs) SHALL BE CABLED BACK TO THIS ROOM. TERMINATE NEW
CAT6A CABLING COMPLETE TO NEW PATCH PANEL IN AN EXISTING RACK.
PATHWAY SHOP DRAWING REQUIREMENT
APPROXIMATE ROUTING SHOWN ON THIS DRAWING FOR POWER FEEDERS ARE ONLY INTENDED TO INDICATE GENERAL SCOPE OF WORK. CONTRACTOR MUST FIELD VERIFY ACTUAL ROUTING AND SUBMIT "PATHWAY SHOP DRAWING" TO VA COR FOR APPROVAL AND COORDINATION. DRAWING SHALL BE MINIMUM 1/16" = 1'-0" SCALE AND SHALL INDICATE, BUT IS NOT LIMITED TO, PROPOSED ROUTE, PULLBOXES, PENETRATIONS THROUGH FLOORS AND LIFE SAFETY BARRIERS (SMOKE AND FIRE), ETC. WHERE ROUTING IS ABOVE FINISHED CEILING IN OCCUPIED AREAS, INDICATE APPROXIMATE LENGTH OF TIME AND EXTENT OF WORK REQUIRED TO COMPLETE ROUTING.
DEDUCT ALTERNATES:
DEDUCT ALTERNATE NO.1:
1. IF DEDUCT ALTERNATE 1 IS ACCEPTED, DELETE ALL WORK ASSOCIATED WITH ROOM 1FLVC1.
2. REFER TO ARCHITECTURAL PLANS AND SPECIFICATIONS FOR ADDITIONAL INFORMATION.
DEDUCT ALTERNATE NO.2:
1. IF DEDUCT ALTERNATE 2 IS ACCEPTED, DELETE ALL WORK ASSOCIATED WITH ROOM 3B129, 3A101, 3AC322, 3AC267, AND 3B162C.
1 2 5 6 7 8 9 12 13 19 24 25 26 30 32 33 34 35 36 37
H
K
L
Q
T
V
W
Y
Z
F
D
B
A
G
U
39 423 11 144 15 16 17 18 20 21 31 4123
M
X
Com
Room
4AC231
Tel/Com
Room
4AC352
E4.5
E4.5
E4.5
E4.5
E4.5
IRM
4A101
IRM
4B145RA42
ERA44-CR
ERA42-CR
IRM
4FLVC1
ELEC
4FLVC2
S
59459
M.P. LONG
R
ES
O F
I R
GE
NOI
S
P
E
N E
DERT
L EA
E I N
G
R
TS
TEA HF OO
IO
DESIGN AND CONSTRUCTION DOCUMENTS AS
INSTRUMENTS OF SERVICE ARE GIVEN IN
CONFIDENCE AND REMAIN THE PROPERTY OF
PERSPECTUS ARCHITECTURE. THE USE OF THIS
DESIGN AND THESE CONSTRUCTION
DOCUMENTS
FOR PURPOSES OTHER THAN THE SPECIFIC
PROJECT NAMED HEREIN IS STRICTLY
PROHIBITED WITHOUT THE EXPRESSED WRITTEN
CONSENT OF PERSPECTUS ARCHITECTURE.
COPYRIGHT C 2018.
13212 Shaker Square Suite 204 Cleveland, Ohio 44120 P. 216.752.1800 F. 216.752.3833
CONSULTANTS: ARCHITECT:
Drawing Title
Approved: Project Director Location
Project Title
Date Checked Drawn
Drawing Number
Building Number
Project Number
Office of
Facilities
Management
Dwg. of o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t
VA FORM 08-6231, OCT 1978
1 2 3 4 5 6 7 8 9 10
A
1 2 3 4 5 6 7 8 9 10
B
C
D
E
F
A
B
C
D
E
F
VAMC - WADE PARK
Revisions: Date
FULLY SPRINKLERED
18077
FREDRICK, FREDRICK & HELLER
ENGINEERS, INC.
672 EAST ROYALTON ROAD
BROADVIEW HTS., OHIO 44147
TEL. (440)546-9696
FAX: (440)546-9699
BID ISSUE 4/13/20
Increase IRM Physical
Security
541-19-102
JRDMPL
FOURTH FLOOR ELECTRICAL KEY
PLAN
E1.6 4/13/20
N
0' 16' 32' 64' 128'0' 16' 32' 64' 128'0' 16' 32' 64' 128'0' 16' 32' 64' 128'0' 16' 32' 64' 128'
1/32" = 1'-0"
FOURTH FLOOR ELECTRICAL KEY PLAN 1
DEDUCT ALTERNATES:
DEDUCT ALTERNATE NO.1:
1. IF DEDUCT ALTERNATE 1 IS ACCEPTED, DELETE ALL WORK ASSOCIATED WITH ROOM 4FLVC1.
2. REFER TO ARCHITECTURAL PLANS AND SPECIFICATIONS FOR ADDITIONAL INFORMATION.
DEDUCT ALTERNATE NO.2:
1. IF DEDUCT ALTERNATE 2 IS ACCEPTED, DELETE ALL WORK ASSOCIATED WITH ROOM 4B145, 4A101, 4AC352, AND
4AC231.
H
K
L
Q
T
V
W
Y
F
D
B
A
G
U
39 423 11 144 15 16 17 18 20 21 31 4123
M
X
ELEC
5FLVC2
IRM
5FLVC1
E4.5
E4.5
E4.5
IRM
5B156
IRM
5A100
RB51
ELE51-CR
S
59459
M.P. LONG
R
ES
O F
I R
GE
NOI
S
P
E
N E
DERT
L EA
E I N
G
R
TS
TEA HF OO
IO
DESIGN AND CONSTRUCTION DOCUMENTS AS
INSTRUMENTS OF SERVICE ARE GIVEN IN
CONFIDENCE AND REMAIN THE PROPERTY OF
PERSPECTUS ARCHITECTURE. THE USE OF THIS
DESIGN AND THESE CONSTRUCTION
DOCUMENTS
FOR PURPOSES OTHER THAN THE SPECIFIC
PROJECT NAMED HEREIN IS STRICTLY
PROHIBITED WITHOUT THE EXPRESSED WRITTEN
CONSENT OF PERSPECTUS ARCHITECTURE.
COPYRIGHT C 2018.
13212 Shaker Square Suite 204 Cleveland, Ohio 44120 P. 216.752.1800 F. 216.752.3833
CONSULTANTS: ARCHITECT:
Drawing Title
Approved: Project Director Location
Project Title
Date Checked Drawn
Drawing Number
Building Number
Project Number
Office of
Facilities
Management
Dwg. of o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t
VA FORM 08-6231, OCT 1978
1 2 3 4 5 6 7 8 9 10
A
1 2 3 4 5 6 7 8 9 10
B
C
D
E
F
A
B
C
D
E
F
VAMC - WADE PARK
Revisions: Date
FULLY SPRINKLERED
18077
FREDRICK, FREDRICK & HELLER
ENGINEERS, INC.
672 EAST ROYALTON ROAD
BROADVIEW HTS., OHIO 44147
TEL. (440)546-9696
FAX: (440)546-9699
BID ISSUE 4/13/20
Increase IRM Physical
Security
541-19-102
JRDMPL
FIFTH FLOOR ELECTRICAL KEY
PLAN
E1.7 4/13/20
N 0' 16' 32' 64' 128'0' 16' 32' 64' 128'0' 16' 32' 64' 128'0' 16' 32' 64' 128'0' 16' 32' 64' 128'
1/32" = 1'-0"
FIFTH FLOOR ELECTRICAL KEY PLAN 1
DEDUCT ALTERNATES:
DEDUCT ALTERNATE NO.1:
1. IF DEDUCT ALTERNATE 1 IS ACCEPTED, DELETE ALL WORK ASSOCIATED WITH ROOM 5FLVC1.
2. REFER TO ARCHITECTURAL PLANS AND SPECIFICATIONS FOR ADDITIONAL INFORMATION.
DEDUCT ALTERNATE NO.2:
1. IF DEDUCT ALTERNATE 2 IS ACCEPTED, DELETE ALL WORK ASSOCIATED WITH ROOM 5B156 AND 5A100.
H
K
L
Q
T
V
W
Y
F
D
B
A
G
U
39 423 11 144 15 16 17 18 20 21 31 41403823
M
X
Telecom/
IRM
5FLVC1
Elec.
Closet
5FLVC2
E4.6
E4.6
E4.6
IRM
6B119
IRM
6A100
S
59459
M.P. LONG
R
ES
O F
I R
GE
NOI
S
P
E
N E
DERT
L EA
E I N
G
R
TS
TEA HF OO
IO
DESIGN AND CONSTRUCTION DOCUMENTS AS
INSTRUMENTS OF SERVICE ARE GIVEN IN
CONFIDENCE AND REMAIN THE PROPERTY OF
PERSPECTUS ARCHITECTURE. THE USE OF THIS
DESIGN AND THESE CONSTRUCTION
DOCUMENTS
FOR PURPOSES OTHER THAN THE SPECIFIC
PROJECT NAMED HEREIN IS STRICTLY
PROHIBITED WITHOUT THE EXPRESSED WRITTEN
CONSENT OF PERSPECTUS ARCHITECTURE.
COPYRIGHT C 2018.
13212 Shaker Square Suite 204 Cleveland, Ohio 44120 P. 216.752.1800 F. 216.752.3833
CONSULTANTS: ARCHITECT:
Drawing Title
Approved: Project Director Location
Project Title
Date Checked Drawn
Drawing Number
Building Number
Project Number
Office of
Facilities
Management
Dwg. of o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t
VA FORM 08-6231, OCT 1978
1 2 3 4 5 6 7 8 9 10
A
1 2 3 4 5 6 7 8 9 10
B
C
D
E
F
A
B
C
D
E
F
VAMC - WADE PARK
Revisions: Date
FULLY SPRINKLERED
18077
FREDRICK, FREDRICK & HELLER
ENGINEERS, INC.
672 EAST ROYALTON ROAD
BROADVIEW HTS., OHIO 44147
TEL. (440)546-9696
FAX: (440)546-9699
BID ISSUE 4/13/20
Increase IRM Physical
Security
541-19-102
JRDMPL
SIXTH FLOOR ELECTRICAL KEY
PLAN
E1.8 4/13/20
N
0' 16' 32' 64' 128'0' 16' 32' 64' 128'0' 16' 32' 64' 128'0' 16' 32' 64' 128'0' 16' 32' 64' 128'
1/32" = 1'-0"
SIXTH FLOOR ELECTRICAL KEY PLAN 1
DEDUCT ALTERNATES:
DEDUCT ALTERNATE NO.1:
1. IF DEDUCT ALTERNATE 1 IS ACCEPTED, DELETE ALL WORK ASSOCIATED WITH ROOM 6FLVC1.
2. REFER TO ARCHITECTURAL PLANS AND SPECIFICATIONS FOR ADDITIONAL INFORMATION.
DEDUCT ALTERNATE NO.2:
1. IF DEDUCT ALTERNATE 2 IS ACCEPTED, DELETE ALL WORK ASSOCIATED WITH ROOM 6B119 AND 6A100.
OS
F
F
HD
HD
HD
HD
OS
OS
OS
36 37
H
L
L1
L2
L3
39 4241403836a
Z3
2 Bedroom
3A131
MCR-1
3A133-1
FMS-1
3A135-1
Closet
3A135BA
Passage
3AC312
HAC
3AC311
X X
X
X
XX
XX
X
XX
X X X
XX
X
X X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
MCOR-1
3A135B-1
Tele Health
3A137
Toilet/ Shower
3A137A
Corridor
3A100E
L.C.
3A130
EMS
3A128
EMS
3A134 L.C.
3A132
TYP.
TYP.
S
59459
M.P. LONG
R
ES
O F
I R
GE
NOI
S
P
E
N E
DERT
L EA
E I N
G
R
TS
TEA HF OO
IO
DESIGN AND CONSTRUCTION DOCUMENTS AS
INSTRUMENTS OF SERVICE ARE GIVEN IN
CONFIDENCE AND REMAIN THE PROPERTY OF
PERSPECTUS ARCHITECTURE. THE USE OF THIS
DESIGN AND THESE CONSTRUCTION
DOCUMENTS
FOR PURPOSES OTHER THAN THE SPECIFIC
PROJECT NAMED HEREIN IS STRICTLY
PROHIBITED WITHOUT THE EXPRESSED WRITTEN
CONSENT OF PERSPECTUS ARCHITECTURE.
COPYRIGHT C 2018.
13212 Shaker Square Suite 204 Cleveland, Ohio 44120 P. 216.752.1800 F. 216.752.3833
CONSULTANTS: ARCHITECT:
Drawing Title
Approved: Project Director Location
Project Title
Date Checked Drawn
Drawing Number
Building Number
Project Number
Office of
Facilities
Management
Dwg. of o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t
VA FORM 08-6231, OCT 1978
1 2 3 4 5 6 7 8 9 10
A
1 2 3 4 5 6 7 8 9 10
B
C
D
E
F
A
B
C
D
E
F
VAMC - WADE PARK
Revisions: Date
FULLY SPRINKLERED
18077
FREDRICK, FREDRICK & HELLER
ENGINEERS, INC.
672 EAST ROYALTON ROAD
BROADVIEW HTS., OHIO 44147
TEL. (440)546-9696
FAX: (440)546-9699
BID ISSUE 4/13/20
Increase IRM Physical
Security
541-19-102
CPCMPL
PARTIAL THIRD FLOOR LIGHTING
AND FIRE ALARM DEMOLITION
PLAN - PHASE 1
E2.1 4/13/20
0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'
1/4" = 1'-0"
PARTIAL THIRD FLOOR
LIGHTING AND FIRE ALARM DEMO PLAN - PHASE 1 1N
ELECTRICAL DEMOLITION NOTES
D1 ALL EXISTING LIGHTING FIXTURES, RECEPTACLES, SPECIAL SYSTEMS OUTLETS, CONDUIT, WIRING ETC. THAT WILL
NOT BE REUSED IN THE REMODELED INSTALLATION SHALL BE REMOVED UNLESS OTHERWISE NOTED. THIS DEMOLITION SHALL INCLUDE ALL ELECTRICAL ITEMS SHOWN ON THIS PLAN THAT ARE NOT DESIGNATED BY "X", "XN" OR "XRR" AND ALL OTHER ADDITIONAL ITEMS THAT ARE NOT SHOWN BUT THAT MUST BE REMOVED IN ORDER TO
PRODUCE A NEAT, FINISHED, PROPERLY FUNCTIONING ELECTRICAL INSTALLATION. MAINTAIN CIRCUIT CONTINUITY TO ALL EXISTING REUSED ELECTRICAL SYSTEMS COMPONENTS - PROVIDE ALL CONDUIT AND WIRING NECESSARY TO ACHIEVE THE SAME. THE CONTRACTOR SHALL FIELD VERIFY THE NATURE AND EXTENT OF ALL DEMOLITION
WORK AND SHALL INCLUDE COST FOR THE SAME IN THE BID SUBMITTAL.
D2 ALL EXISTING REMOVED ELECTRICAL EQUIPMENT, DEVICES, ETC. THAT ARE NOT RETAINED BY THE OWNER SHALL
BE DISPOSED OF BY THE ELECTRICAL CONTRACTOR.
D3 DASHED WALLS ON PLAN INDICATE EXISTING CONSTRUCTION TO BE REMOVED.
D4 REFER TO ELECTRICAL LEGEND FOR ALL SYMBOL DESIGNATIONS. NOTE SPECIAL ATTENTION TO SELECTED EXISTING DEVICES, WIREWAYS, ETC. MARKED XB, XRR OR XN, AND REMOVE/BLANK OFF, RELOCATE OR REPLACE
THESE COMPONENTS AS REQUIRED.
D5 MAINTAIN CIRCUIT CONTINUITY TO ALL EXISTING ELECTRICAL SYSTEM COMPONENTS IN AREAS NOT BEING REMODELED UNLESS OTHERWISE NOTED. PROVIDE ALL CONDUIT AND WIRING EXTENSIONS NECESSARY TO
ACHIEVE SAME.
D6 THE ELECTRICAL CONTRACTOR SHALL CLOSELY COORDINATE ALL ELECTRICAL DEMOLITION WORK WITH THE GENERAL AND MECHANICAL CONTRACTORS, AND SHALL DISCONNECT ALL REQUIRED CIRCUITS IN A TIMELY
MANNER.
TECHNOLOGY PROTECTION GENERAL NOTE
DATA CENTER EXISTING EQUIPMENT MUST REMAIN OPERATIONAL AT ALL TIMES UNLESS A SHUTDOWN REQUEST IS APPROVED BY VA COR FOR INDIVIDUAL SYSTEMS AS REQUIRED UNDER THE SCOPE OF THIS PROJECT. EXISTING EQUIPMENT MUST REMAIN FREE OF CONSTRUCTION DEBRIS AND MUST REMAIN OPEN TO COOLING AND VENTILATION TO MEET MANUFACTURER'S OPERATING TEMPERATURE REQUIREMENTS. CONTRACTOR SHALL RETAIN VALUE FACILITY SERVICES (CONTACT KURT YANTZ, PH. #800-583-8374) TO PROTECT EXISTING TELECOMMUNICATIONS EQUIPMENT DURING DEMOLITION. COORDINATE PROTECTION REQUIREMENTS WITH VA COR AND VA OIT.
# ELECTRICAL DEMOLITION PLAN CODED NOTES
DEMOLISH EXISTING LIGHTING FIXTURES AND CONTROLS COMPLETE. MAINTAIN CIRCUIT CONTINUITY TO
FIXTURES OUTSIDE THIS AREA.
DEMOLISH EXISTING FIRE ALARM DEVICE COMPLETE. MAINTAIN ADDRESSIBLE OR AUDIBLE/VISUAL CIRCUIT
CONTINUITY TO DEVICES OUTSIDE THIS AREA.
VA OIT EXISTING CONDITIONS GENERAL NOTE
UPON COMPLETED REMOVAL OF EXISTING CEILINGS, CONTRACTOR SHALL VACATE THE PROJECT AREA AND VA OIT SHALL BE GIVEN UP TO (3) WEEKS TO REMOVE, REWORK, RESUPPORT OR OTHERWISE CLEAN-UP EXISTING CONDITIONS ABOVE THE CEILING. CONTRACTOR SHALL NOTIFY VA COR (2) WEEKS PRIOR TO VACATING THE PROJECT SCOPE TO ALLOW FOR PROPER PREPARATION FOR WORK BY VA OIT. CONTRACTOR SHALL RESUME WORK OPERATIONS UPON NOTIFICATION FROM VA COR OF COMPLETION OF ACTIVITIES BY VA OIT.
C R
ML
P E
C R
ML
ML
P E
J
J
J
J
J
C R
ML
36 37
H
L
L1
L2
L3
39 424038
M
36a
2 Bedroom
3A131
MCR-1
3A133-1
BB475
MCOR-1
3A135B-1
FMS-1
3A135-1
Closet
3A135BA
BATTERY
3A-135A
Passage
3AC312
HAC
3AC311
LC3-LS
TR-RC3-TP
RC3-TP
ETD3
ETD-MDP
ETD-1A
ETD1
ETD2A
T-ETD
A/C
A/C
SPD
BATTERIES
B A
T T
E R
IE
S
UPS
X
X
X
X
X
X
XX
X
X
X
EXISTING LENEL
DOOR PANEL
X
A/C A/C
A/C
PREACTION
SYSTEM
PANEL
UPS
X
X
X
X
XR
X
X X X X X X
X
X
X X X X X X X X X
EXISTING FIBER
CABINETS
EXISTING LENEL
DOOR PANEL
X
EXISTING CORE
SWITCH CABINETS
EXISTING PHONE
SYSTEM SWITCHES
EXISTING (2)
2-POST RACKS
EXISTING PHONE
CABINETS
EXISTING 2
POST RACK
EXISTING
ALT DATA
RACK
FACILITY
MANAGEMENT
RACKS
PAGING
SYSTEM
CABINETS
DEMAR
C
X-CU
X-CU
X-CU
X
X
XX
XR
XR
XR
XR
X
X
X
EXISTING 4"C FROM BELOW
RAISED FLOOR TO ABOVE
FINISHED CEILING TO REMAIN
EXISTING 4"C FROM BELOW
RAISED FLOOR TO ABOVE
FINISHED CEILING TO REMAIN
X
EXISTING
BATTERY ALARM
SYSTEM
SM
SM
SM
SM SM SM
WIREMOLD
XR
X
X X
EXISTING PHONE
SYSTEM RECTIFIERS
XXX
X
X
X X X
X
X
X
X X X
PHONE SYSTEM COPPER BACKBONE AND TERMINATIONS
X
F1 F2 F3 F4 G1 G2 G3 G4 G5
A1 A2 A3 A4 A5 A6
H1 H2 H3
J1 J2 J3
Tele Health
3A137
Toilet/ Shower
3A137A
EMS
3A134
L.C.
3A132
L.C.
3A130
EMS
3A128
Corridor
3A100E
X
X
EXISTING
GROUND BUS BAR
X
X
X
X
S
59459
M.P. LONG
R
ES
O F
I R
GE
NOI
S
P
E
N E
DERT
L EA
E I N
G
R
TS
TEA HF OO
IO
DESIGN AND CONSTRUCTION DOCUMENTS AS
INSTRUMENTS OF SERVICE ARE GIVEN IN
CONFIDENCE AND REMAIN THE PROPERTY OF
PERSPECTUS ARCHITECTURE. THE USE OF THIS
DESIGN AND THESE CONSTRUCTION
DOCUMENTS
FOR PURPOSES OTHER THAN THE SPECIFIC
PROJECT NAMED HEREIN IS STRICTLY
PROHIBITED WITHOUT THE EXPRESSED WRITTEN
CONSENT OF PERSPECTUS ARCHITECTURE.
COPYRIGHT C 2018.
13212 Shaker Square Suite 204 Cleveland, Ohio 44120 P. 216.752.1800 F. 216.752.3833
CONSULTANTS: ARCHITECT:
Drawing Title
Approved: Project Director Location
Project Title
Date Checked Drawn
Drawing Number
Building Number
Project Number
Office of
Facilities
Management
Dwg. of o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t
VA FORM 08-6231, OCT 1978
1 2 3 4 5 6 7 8 9 10
A
1 2 3 4 5 6 7 8 9 10
B
C
D
E
F
A
B
C
D
E
F
VAMC - WADE PARK
Revisions: Date
FULLY SPRINKLERED
18077
FREDRICK, FREDRICK & HELLER
ENGINEERS, INC.
672 EAST ROYALTON ROAD
BROADVIEW HTS., OHIO 44147
TEL. (440)546-9696
FAX: (440)546-9699
BID ISSUE 4/13/20
Increase IRM Physical
Security
541-19-102
CPCMPL
PARTIAL THIRD FLOOR POWER
AND SECURITY DEMOLITION
PLAN - PHASE 1
E2.2 4/13/20
N
ELECTRICAL DEMOLITION NOTES
D1 ALL EXISTING LIGHTING FIXTURES, RECEPTACLES, SPECIAL SYSTEMS OUTLETS, CONDUIT, WIRING ETC. THAT WILL
NOT BE REUSED IN THE REMODELED INSTALLATION SHALL BE REMOVED UNLESS OTHERWISE NOTED. THIS DEMOLITION SHALL INCLUDE ALL ELECTRICAL ITEMS SHOWN ON THIS PLAN THAT ARE NOT DESIGNATED BY "X", "XN" OR "XRR" AND ALL OTHER ADDITIONAL ITEMS THAT ARE NOT SHOWN BUT THAT MUST BE REMOVED IN ORDER TO
PRODUCE A NEAT, FINISHED, PROPERLY FUNCTIONING ELECTRICAL INSTALLATION. MAINTAIN CIRCUIT CONTINUITY TO ALL EXISTING REUSED ELECTRICAL SYSTEMS COMPONENTS - PROVIDE ALL CONDUIT AND WIRING NECESSARY TO ACHIEVE THE SAME. THE CONTRACTOR SHALL FIELD VERIFY THE NATURE AND EXTENT OF ALL DEMOLITION
WORK AND SHALL INCLUDE COST FOR THE SAME IN THE BID SUBMITTAL.
D2 ALL EXISTING REMOVED ELECTRICAL EQUIPMENT, DEVICES, ETC. THAT ARE NOT RETAINED BY THE OWNER SHALL
BE DISPOSED OF BY THE ELECTRICAL CONTRACTOR.
D3 DASHED WALLS ON PLAN INDICATE EXISTING CONSTRUCTION TO BE REMOVED.
D4 REFER TO ELECTRICAL LEGEND FOR ALL SYMBOL DESIGNATIONS. NOTE SPECIAL ATTENTION TO SELECTED EXISTING DEVICES, WIREWAYS, ETC. MARKED XB, XRR OR XN, AND REMOVE/BLANK OFF, RELOCATE OR REPLACE
THESE COMPONENTS AS REQUIRED.
D5 MAINTAIN CIRCUIT CONTINUITY TO ALL EXISTING ELECTRICAL SYSTEM COMPONENTS IN AREAS NOT BEING REMODELED UNLESS OTHERWISE NOTED. PROVIDE ALL CONDUIT AND WIRING EXTENSIONS NECESSARY TO
ACHIEVE SAME.
D6 THE ELECTRICAL CONTRACTOR SHALL CLOSELY COORDINATE ALL ELECTRICAL DEMOLITION WORK WITH THE GENERAL AND MECHANICAL CONTRACTORS, AND SHALL DISCONNECT ALL REQUIRED CIRCUITS IN A TIMELY
MANNER.
0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'
1/4" = 1'-0"
PARTIAL THIRD FLOOR
POWER AND SECURITY DEMO PLAN - PHASE 1 1
# ELECTRICAL DEMOLITION PLAN CODED NOTES
DISCONNECT EXISTING COMPUTER ROOM AIR CONDITIONING UNIT TO FACILITATE DEMOLITION. REMOVE BRANCH CIRCUIT CONDUIT AND WIRING COMPLETE BACK TO SOURCE. TURN OFF EXISTING BREAKER AND
RE-LABEL AS "SPARE".
REMOVE EXISTING ACCESS CONTROL DEVICES COMPLETE TO FACILITATE REPLACEMENT OF EXISTING
DOOR AND INSTALLATION OF NEW ACCESS CONTROL DEVICES.
TECHNOLOGY PROTECTION GENERAL NOTE
DATE CENTER EXISTING EQUIPMENT MUST REMAIN OPERATIONAL AT ALL TIMES UNLESS A SHUTDOWN REQUEST IS APPROVED BY VA COR FOR INDIVIDUAL SYSTEMS AS REQUIRED UNDER THE SCOPE OF THIS PROJECT. EXISTING EQUIPMENT MUST REMAIN FREE OF CONSTRUCTION DEBRIS AND MUST REMAIN OPEN TO COOLING AND VENTILATION TO MEET MANUFACTURER'S OPERATING TEMPERATURE REQUIREMENTS. CONTRACTOR SHALL RETAIN VALUE FACILITY SERVICES (CONTACT KURT YANTZ, PH.