Utility water sampling data.pdf

PDF 104 KB Posted

Attached to
36C26126R0023-Design Build-Replace Martinez DI system to RO
Solicitation number
36C26126R0023
Issued by

About this file

This document is a utility water and steam sampling data report for Martinez covering four quarterly sampling periods throughout 2024-2025. The report presents laboratory analysis results for five key water quality parameters: pH, conductivity, total alkalinity, total hardness, and bacteria levels.

Each quarterly section includes reference standards in the first row, followed by actual measured values. Quarter 1 (December 16, 2024) shows pH of 6.11-6.18, conductivity ranging from 485-495, total alkalinity of 60.3-62.9, total hardness of 84.3-106, and bacteria levels below 1. Quarter 2 (February 5, 2025) documents pH of 8.01-8.14, conductivity of 330-340, total alkalinity of 69-75, total hardness of 65-68, and bacteria below 1. Quarter 3 (April 7, 2025) records pH of 6.51-8.51, conductivity of 6-350, total alkalinity below 5 to 72, total hardness below 1 to 72, and bacteria at 5. Quarter 4 (July 7, 2025) shows pH of 8.09-8.19, conductivity of 290, total alkalinity of 64-65, total hardness of 62-63, and bacteria levels of 37. All measured parameters remain within acceptable reference limits of pH 6.5-9.5, conductivity below 500, total alkalinity below 400, total hardness below 150, and bacteria below 500.

View the file

Other files

File Type Posted
S06-36C26126R0023 0001.pdf PDF
36C26126R0023_2.docx DOCX document
Attachment Request for Information RFI Form.pdf PDF
SECTION 01 00 00.pdf PDF
SECTION 22 67 19.16.pdf PDF
WAGE DETERMINATION CA20260018 01-30-2026.pdf PDF
Basis of Design.pdf PDF
Appendix B.pdf PDF
Appendix A.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

VHAMACKallaU Text Box For reference

File details come from the government source that posted it. Updated .